ESBD_500440_1774456608504_Attachment B - Project Drawings.pdf

PDF 4 MB Posted

Attached to
North & South Plant Chiller Replacement
Solicitation number
734-03202026-KM
Issued by
Johnson County, Beaumont City, Texas

About this file

This is a set of construction document drawings for the Lamar North and South Plant Chiller Replacement project located at Lamar University in Beaumont, Texas. The project involves the replacement of existing chillers CH-1 and CH-2 at both the North Central Plant and South Central Plant facilities. The scope of work includes demolition of four existing 800-ton water-cooled chillers, removal of associated piping and electrical systems, installation of four new 800-ton chillers with R-513A refrigerant, and replacement of selected balance and isolation valves, control devices, and magnetic flow meters. The new chillers will feature marine water boxes on the condenser barrels with side connections and stacked chilled water supply and return flange connections. The project documents are dated March 19, 2026, and include mechanical demolition plans, piping renovation plans, ductwork and refrigerant monitoring plans, electrical power renovation plans, mechanical schedules, and detailed construction specifications. The drawings indicate that existing chiller CH-3 will remain in service and that existing refrigerant relief piping, exhaust fans, and isolation valves will be retained where applicable.

The project requires coordination with existing building systems including the chilled water distribution system serving North and West campus areas, condenser water supply and return headers, and refrigerant exhaust and monitoring systems. New refrigerant monitoring panels compliant with MSA Chillgard 5000 standards will be installed to support the new R-513A refrigerant while maintaining compatibility with the existing R-134A refrigerant used in chiller CH-3. Electrical work includes installation of new medium-voltage reduced-voltage soft-start starters, branch circuits with 5kV cable, and control circuits for each new chiller. The contractor must field-verify existing equipment locations, obtain owner approval for service interruptions, coordinate with the construction manager and owner to minimize operational disruption, and comply with all National Electrical Code requirements and fire-resistance rating standards. The project documents specify that demolition and installation work will be fast-tracked to allow all four chillers to be operational simultaneously, with existing housekeeping pads reused to support the new equipment on neoprene isolation pads.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS - EQUIPMENT

AC - AIR CONDITIONING UNIT /

AIR COMPRESSOR

ACB - ACTIVE CHILLED BEAM

ACC - AIR COOLED CONDENSER

ACCU - AIR COOLED CONDENSING UNIT

ACU - AIR CONDITIONING UNIT

ACDH - AIR CURTAIN DOOR HEATER

ADS - AIR AND DIRT SEPARATOR

AHU - AIR HANDLING UNIT

AMD - AIR MIXING DEVICE

AS - AIR SEPARATOR

AT - AIR TERMINAL DEVICE

B - BOILER

BBS - BOILER BLOWDOWN

SEPARATOR

BCU - BLOWER COIL UNIT

BFS - BOILER FEEDWATER SYSTEM

BH - BOOSTER HUMIDIFIER

BHRS - BOILER BLOWDOWN HEAT

RECOVERY SYSTEM

C - CONVECTOR

CC - COOLING COIL

CD - CEILING DIFFUSER

CH - CHILLER

CP - CONDENSATE PUMP /

CONTROL PANEL

CRAC - COMPUTER ROOM

AIR CONDITIONER

CT - COOLING TOWER

CTS - COOLING TOWER SUMP

CUH - CABINET UNIT HEATER

CV - CONVERTOR

D - DAMPER

DA - DEAERATOR

DC - DUST COLLECTOR /

DRY COOLER

DH - DEHUMIDIFIER

DOAS - DEDICATED OUTSIDE AIR

SYSTEM

DT - DAY TANK

EF - EXHAUST FAN

EG - EXHAUST GRILLE

EH - EXHAUST HOOD /

ELECTRIC HEATER

EJ - EXPANSION JOINT

ERW - ENERGY RECOVERY WHEEL

ET - EXPANSION TANK

EV - EXHAUST VALVE

EXV - ELECTRONIC EXPANSION VALVE

F - FILTER

FAI - FRESH AIR INTAKE

FCU - FAN COIL UNIT

FD - FLOOR DRAIN /

FLOOR DIFFUSER

FFU - FAN FILTER UNIT

FOP - FUEL OIL PUMP

FOT - FUEL OIL TANK

FR - FIN TUBE RADIATION

FT - FLASH TANK

FU - FURNACE

G - GRILLE

H - HUMIDIFIER

HC - HEATING COIL

HP - HEAT PUMP

HRC - HEAT RECOVERY COIL

HR - HOSE REEL

HRD - HEAT RECLAIM DEVICE

HRW - HEAT RECOVERY WHEEL

HRU - HEAT RECOVERY UNIT

HT - HEAT TRACE

HX - HEAT EXCHANGER

IH - INTAKE HOOD

IRH - INFRARED RADIANT HEATER

L - LOUVER

LD - LINEAR DIFFUSER\

LG - LINEAR GRILLE

MAU - MAKE-UP AIR UNIT

MCC - MOTOR CONTROL CENTER

P - PUMP

PCB - PASSIVE CHILLED BEAM

PHC - PREHEAT COIL

PRV - PRESSURE REDUCING VALVE /

PRESSURE REGULATING VALVE

RCP - RADIANT CEILING PANEL

RF - RETURN FAN

RH - RELIEF HOOD

RC - REHEAT COIL

RTU - ROOF TOP AIR HANDLING UNIT

RV - RELIEF VALVE

SAD - SOUND ATTENUATING DEVICE

SC - SOLAR COLLECTOR

SCR - SILICON CONTROLLED RECTIFIER

SD - SUCTION DIFFUSER

SF - SUPPLY FAN

SG - SUPPLY GRILLE

SRV - SAFETY RELIEF VALVE

ST - STEAM TRAP

T - TANK

TF - TRANSFER FAN

TG - TRANSFER GRILLE

TXV - THERMAL EXPANSION VALVE

UH - UNIT HEATER

USG - UNFIRED STEAM GENERATOR

UST - UNDERGROUND STORAGE TANK

UV - UNIT VENTILATOR

V - VALVE

VFD - VARIABLE FREQUENCY DRIVE

VRF - VARIABLE REFRIGERANT FLOW

WCC - WATER COOLED CONDENSER

WCCU - WATER COOLED CONDENSING

UNIT

WF - WATER FILTER

WFM - WATER FLOW METER

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AL - ALUMINUM

ALT - ALTERNATE

AP - ACCESS PANEL

AVG - AVERAGE

BAS - BUILDING AUTOMATION SYSTEM

BE - BATTERY EXHAUST

BHP - BRAKE HORSEPOWER

BOD - BOTTOM OF DUCT

BOP - BOTTOM OF PIPE

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNITS

PER HOUR

BWE - BAKED WHITE ENAMEL

CA - COMBUSTION AIR

CAP - CAPACITY

CAV - CONSTANT AIR VOLUME

CE - CAGEWASH EXHAUST

CFCI - CONTRACTOR FURNISHED,

CONTRACTOR INSTALLED

CFH - CUBIC FEET PER HOUR

CFM - CUBIC FEET PER MINUTE

CL - CENTERLINE

CLG - CEILING

COND - CONDENSATE /

CONDENSER

CONN - CONNECTION

COP - CENTER OF PIPE

CS - CARBON STEEL

CU - COPPER

DAT - DISCHARGE AIR TEMPERATURE

DB - DRY BULB

DDC - DIRECT DIGITAL CONTROL

DE - DISHWASHER EXHAUST

DIA - DIAMETER

DIM - DIMENSION

DP - DEW POINT

DX - DIRECT EXPANSION

EA - EXHAUST AIR / EACH

EAT - ENTERING AIR TEMPERATURE

EC - ELECTRICAL CONTRACTOR

ECM - ELECTRICALLY COMMUTATED

MOTOR

EDR - EQUIVALENT DIRECT RADIATION

EFF - EFFICIENCY

EG - ETHYLENE GLYCOL

EL - ELEVATION

ESP - EXTERNAL STATIC PRESSURE

ETR - EXISTING TO REMAIN

EWT - ENTERING WATER

TEMPERATURE

EXH - EXHAUST

FA - FIELD ADJUSTABLE

FAT - FINAL AIR TEMPERATURE

FC - FAIL CLOSED

FHE - FUME HOOD EXHAUST

FLA - FULL LOAD AMPS

FLP - FAIL LAST POSITION

FLR - FLOOR

FO - FAIL OPEN

FPI - FINS PER INCH

FPM - FEET PER MINUTE

FPS - FEET PER SECOND

FT - FEET

GA - GAUGE

GAL - GALLONS

GC - GENERAL CONTRACTOR

GE - GENERAL EXHAUST

GPM - GALLONS PER MINUTE

GR - GRAINS

GS - GALVANIZED STEEL

H - HEIGHT

HP - HORSE POWER /

HIGH POINT

HR - HUMIDITY RATIO /

HOUR

HZ - HERTZ

IA - INSTRUMENT AIR

IE - INVERT ELEVATION

IN - INCH

KE - KITCHEN EXHAUST

KO - KNOCK-OUT

KW - KILOWATT

KWH - KILOWATT - HOUR

L - LENGTH

LAT - LEAVING AIR TEMPERATURE

LB - POUND

LBS - POUNDS

LEA - LABORATORY EXHAUST AIR

LGE - LABORATORY GENERAL EXHAUST

LP - LOW POINT

LSA - LABORATORY SUPPLY AIR

LWT - LEAVING WATER TEMPERATURE

MAX - MAXIMUM

MBH - THOUSANDS OF BTU PER HOUR

MC - MECHANICAL CONTRACTOR

MEP - MECHANICAL, ELECTRICAL,

AND PIPING

MER - MECHANICAL EQUIPMENT ROOM

MIN - MINIMUM

NA - NOT APPLICABLE

NC - NORMALLY CLOSED

NIC - NOT IN CONTRACT

NO - NORMALLY OPEN

NOM - NOMINAL

NPS - NOMINAL PIPE SIZE

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTSIDE AIR

OC - ON CENTER

OED - OPEN END DUCT

OFCI - OWNER FURNISHED,

CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED,

OWNER INSTALLED

OV - OUTLET VELOCITY

PA - PLANT AIR

PC - PLUMBING CONTRACTOR

PCF - POUNDS PER CUBIC FOOT

PD - PRESSURE DROP

PG - PROPYLENE GLYCOL

PH - PHASE

PP - POLYPROPYLENE

PPH - POUNDS PER HOUR

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSIA - POUNDS PER SQUARE INCH

ABSOLUTE

PSIG - POUNDS PER SQUARE INCH

GAUGE

QTY - QUANTITY

RA - RETURN AIR

RH - RELATIVE HUMIDITY

RPM - REVOLUTIONS PER MINUTE

SA - SUPPLY AIR

SCCR - SHORT CIRCUIT CURRENT RATING

SCH - SCHEDULE

SOG - SLAB ON GRADE

SP - STATIC PRESSURE

SQ - SQUARE

SS - STAINLESS STEEL

TA - TRANSFER AIR

TBR - TO BE REMOVED

TCC - TEMPERATURE CONTROL

CONTRACTOR

TE - TOILET EXHAUST

TOB - TOP OF BEAM

TOD - TOP OF DUCT /

TOP OF DECK

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB

TSP - TOTAL STATIC PRESSURE

TYP - TYPICAL

V - VOLTS

VAV - VARIABLE AIR VOLUME

VEA - VIVARIUM EXHAUST AIR

VEL - VELOCITY

VP - VELOCITY PRESSURE

VSA - VIVARIUM SUPPLY AIR

VTR - VENT THRU ROOF

W - WATT /

WIDTH

WB - WET BULB

WC - WATER COLUMN

WG - WATER GAUGE

WMG - WIRE MESH GRILLE

WPD - WATER PRESSURE DROP

WWM - WELDED WIRE MESH

X - EXISTING

ABBREVIATIONS - GENERAL

RHG

LPG

FOS

FOR

FOV

FOF

FOG

LOS

LOR

RWS

RWR

LPS

LPC

HPS(XX)

HPC(XX)

CPD

HWS

HWR

CHWS

CHWR

BFW

BBD

GWR

GWS

D

PCWS

PCWR

RL

RS

FUEL RETURN

FUEL SUPPLY

IA(XX)

CA(XX)

FUEL OIL FILL

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

LIQUIFIED PETROLEUM GAS

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

FUEL OIL GAUGE

LUBRICATION OIL RETURN

LUBRICATION OIL SUPPLY

JACKET WATER SUPPLY

JACKET WATER RETURN

COMPRESSED AIR (XX=PSI)

RECLAIM WATER RETURN

RECLAIM WATER SUPPLY

INSTRUMENT AIR (XX=PSI)BOILER FEED WATER

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE

CONDENSATE PUMP DISCHARGE

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

TOWER WATER SUPPLY

TOWER WATER RETURN

BOILER BLOW DOWN

GLYCOL WATER SUPPLY

GLYCOL WATER RETURN

PROCESS COOLING

WATER RETURN

PROCESS COOLING

WATER SUPPLY

VENT

DRAIN

TWR

TWS

FS

FR

JWS

JWR

V

CCC COOLING COIL CONDENSATE

NG(XX) NATURAL GAS (XX=PSI)

NP NON-POTABLE WATER

PHWS

PHWR PREHEAT WATER RETURN

PREHEAT WATER SUPPLY

PIPING SYSTEM LABELS

(FC) = FAIL CLOSED (CONTROL VALVE)

(FO) = FAIL OPEN (CONTROL VALVE)

(NC) = NORMALLY CLOSED (CONTROL VALVE)

(NO) = NORMALLY OPEN (CONTROL VALVE)

(XX) = DEFINES FAIL POSITION OR NORMAL POSITION

BUTTERFLY VALVE DRAIN VALVE W/ HOSE

CONNECTION

VALVES

GATE VALVE

GLOBE VALVE

BALL VALVE

SHUTOFF VALVE (BUTTERFLY

VALVE FOR 2-1/2" AND LARGER.

BALL VALVE FOR 2" AND

SMALLER)

GAUGE VALVE

PLUG VALVE

BALANCING VALVE

THERMAL EXPANSION VALVE

SPRING CHECK VALVE

SWING CHECK VALVE

DIAPHRAGM VALVE

2-WAY SOLENOID CONTROL VALVE

(VALVE BODY AS SPECIFIED)

S

XX

2-WAY MOTOR CONTROL VALVE

(VALVE BODY AS SPECIFIED)

M

XX

2-WAY CONTROL VALVE

(VALVE BODY AS SPECIFIED)XX

3-WAY MIXING VALVE WITH ARROW

INDICATING FAIL POSITION

3-WAY DIVERTING VALVE WITH

ARROW INDICATING FAIL POSITION

TRIPLE DUTY VALVE

GAS SHUTOFF VALVE

ANGLE VALVE

DRAIN VALVE W/ HOSE

CONNECTION AND CAP

LOCKSHIELD VALVE

PRESSURE REDUCING VALVE -

PRV (DOWNSTREAM CONTROL

POINT)

INLET PRESSURE

REGULATING VALVE

(UPSTREAM CONTROL POINT)

AIR-LOADED PRESSURE

REDUCING VALVE - PRV

(DOWNSTREAM CONTROL

POINT)

PRESSURE RELIEF VALVE

(RV) OR SAFETY VALVE (SV)

VACUUM RELIEF/VACUUM

BREAKER

RUPTURE DISK - VACUUM

RELIEF

FLOAT OPERATED VALVE

QUICK OPENING VALVE

RPBP

OR

ECCENTRIC REDUCER

CONCENTRIC REDUCER

PIPING

TOP CONNECTION

(45° OR 90°)

BOTTOM CONNECTION

(45° OR 90°)

45° PIPE RISE(R) / DROP(D)

TEE (REFER TO

SPECIFICATION FOR SIDE,

TOP OR BOTTOM TEE)

EXISTING PIPING

TO BE REMOVED

EXISTING PIPING TO REMAIN

LINE CONTINUATION BREAK

ELBOW UP

ELBOW DOWN

DOUBLE-LINESINGLE-LINE

OR

FLOW DIRECTION

CONNECTION POINT

R

N/A

GENERAL PIPELINE STRAINER

WITHOUT DRAIN BLOWDOWN

VALVE

GENERAL PIPELINE STRAINER

WITH DRAIN BLOWDOWN VALVE

STEAM & CONDENSATE

PIPELINE STRAINER WITH

BLOWDOWN VALVE

WATER SYSTEM PIPELINE

STRAINER WITH BLOWDOWN

VALVE

DUPLEX BASKET STRAINER

BASKET STRAINER

FLANGE

UNION

2" AND SMALLER, CAP OR PLUG

2-1/2" AND LARGER, BLIND FLANGE

INVERTED BUCKET STEAM TRAP

FLOAT AND THERMOSTATIC

STEAM TRAP

THERMOSTATIC STEAM TRAP

EXPANSION JOINT

PIPE FLEXIBLE CONNECTOR

BALL JOINT

FILTER/REGULATOR

THERMOMETER

PRESSURE GAUGE

(WITH GAUGE VALVE)

FLOW ELEMENT

(SENSOR)

FLOW SWITCH

AUTOMATIC AIR VENT

MANUAL AIR VENT

THERMOSTATIC AIR VENT

TEST PLUG

(PRESSURE/TEMP.)

ECCENTRIC REDUCER

DIRECTION OF PITCH (DOWN)

PIPE GUIDE

PIPE SLEEVE

PIPE ANCHOR

CONCENTRIC REDUCER

SUCTION DIFFUSER

PIPING SPECIALTIES

SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT

APPLY TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE

CONTRACT DOCUMENTS.

MECHANICAL SYMBOLS AND ABBREVIATIONS

PILOT POSITIONER

MODULATING WITH

SOLENOID

MODULATING

GENERAL

MANUAL

FUSIBLE LINK

TWO POSITION

SPRING RETURN

DOUBLE ACTING

TWO POSITION

ELECTRIC MOTOR DRIVEN

S

M

ACTUATORS

DOUBLESINGLE

W

R=1.5W

EXHAUST AIR (EA) DUCT (SOLID LINES

TYPICAL FOR EXHAUST AIR UP,

HIDDEN LINE DOWN)

DUCT RISE/DROP W/ 90° ELBOWS

(OVAL DUCTS)

DUCT RISE (R)/DROP(D) W/ 45° ELBOWS

(RECTANGULAR DUCTS)

DUCT RISE/DROP W/ 90° ELBOWS

(ROUND DUCTS)

DUCT RISE(R)/DROP(D) W/ 45°

ELBOWS (ROUND OR OVAL DUCTS)

DUCT RISE/DROP W /90° ELBOWS

(SUPPLY RECTANGULAR DUCT SHOWN)

RETURN AIR (RA), RELIEF AIR, OR

TRANSFER AIR (TA) DUCT (SOLID LINES

TYPICAL FOR RETURN, RELIEF,OR

TRANSFER AIR UP, HIDDEN LINE DOWN)

SUPPLY AIR (SA) OR OUTDOOR AIR (OA)

DUCT (SOLID LINES TYPICAL FOR

SUPPLY AIR AND OUTDOOR AIR UP,

HIDDEN LINE DOWN)

EXISTING DUCT TO BE REMOVED

EXISTING DUCT TO REMAIN

TRANSITION - CONCENTRIC

TRANSITION - ECCENTRIC

SQUARE TEE (FOR LOW

PRESSURE SA DIVERGING ONLY)

ROUND/ROUND BRANCH TAKE-OFF

RECTANGULAR/ROUND BRANCH TAKE-OFF

R=1.5W

BULLHEAD TEE (FOR LOW

PRESSURE SA DUCTWORK ONLY)

15° MAX. FOR DIVERGING,

25° MAX FOR CONVERGING

RADIUS TEE

W

OR

15° MAX. FOR DIVERGING,

25° MAX FOR CONVERGING

45° LATERAL BRANCH

LINE CONTINUATION BREAK

(RECTANGULAR, ROUND)

RADIUS ELBOW

DUCTWORK

R R

R

G - RETURN OR EXHAUST GRILLE

SG - SUPPLY GRILLE

LD - LINEAR DIFFUSER

LG - LINEAR RET/EXH GRILLE

TG - TRANSFER GRILLE

12x6 G-1

12x6 EA

EXHAUST AIR DUCT

RETURN AIR DUCT (RA)

NECK SIZE IN INCHES

AIR QUANTITY (CFM)

DUCT SIZE IN INCHES

(NET INSIDE DIMENSIONS)

FIRST FIGURE: SIDE SHOWN

SECOND FIGURE: SIDE NOT

SHOWN

GRILLE, REGISTER NOTATION

10ø CD-1

10ø SA

SUPPLY AIR DUCT

NECK SIZE IN

INCHES

CEILING DIFFUSER

(CD) IDENTIFICATION

AIR QUANTITY (CFM)

DUCT SIZE IN INCHES

(NET INSIDE DIMENSIONS)

(ROUND SHOWN)

ø INDICATES ROUND.

#/# INDICATES OVAL.

FIRST FIGURE: SIDE SHOWN

SECOND FIGURE: SIDE NOT SHOWN

DIFFUSER AIR PATTERN

1 ARROW: 1 WAY

2 ARROWS: 2 WAY

3 ARROWS: 3 WAY

4 ARROWS: 4 WAY

NO ARROWS: 4 WAY

DIFFUSER NOTATION

(FC) = FAIL CLOSED (DAMPER)

(FO) = FAIL OPEN (DAMPER)

(NC) = NORMALLY CLOSED (DAMPER)

(NO) = NORMALLY OPEN (DAMPER)

(XX) = DEFINES FAIL POSITION OR NORMAL POSITION

1-1/2 HOUR RATED FIRE DAMPER

3 HOUR RATED FIRE DAMPER

BACKDRAFT DAMPER

CONTROL DAMPER

MANUAL BALANCING DAMPER

BD

F

FA

PARALLEL BLADE DAMPER

OPPOSED BLADE DAMPER

COMBINATION FIRE/

SMOKE DAMPER

GENERAL

SMOKE DAMPER

BUBBLE TIGHT DAMPER

BT

OR

FS

S

DAMPERS

SUPPLY DIFFUSER OR GRILLE

(HORIZONTAL MOUNT)

RETURN REGISTER OR

GRILLE (HORIZONTAL MOUNT)

EXHAUST REGISTER OR GRILLE

(HORIZONTAL MOUNT)

EXHAUST OR RETURN

REGISTER OR GRILLE

(VERTICAL MOUNT)

SUPPLY REGISTER OR

GRILLE (VERTICAL

MOUNT)

ROUND

DIFFUSER

SINGLE LINE-HARD

OR FLEXIBLE

CONNECTION

DOUBLE LINE-HARD OR

FLEXIBLE CONNECTION

DUCTWORK AT DIFFUSERS & GRILLES

DUCTWORK SPECIALTIES

FLEXIBLE DUCT

DUCT FLEXIBLE CONNECTION

POINT OF CHANGE IN DUCT

CONSTRUCTION BY

PRESSURE CLASS

DUCT REHEAT COIL

ACCESS DOOR

BUTTERFLY TYPE VALVE

WITH CONTROLLER ANGLED

DOWN, SEE DETAIL

OR

BUTTERFLY TYPE VALVE

WITH CONTROLLER LOCATED

ON SIDE OF VALVE

VAV SUPPLY AIR VALVE

AIR FLOW MEASURING

STATION

AM

VENTURI VALVE WITH

CONTROLLER ANGLED DOWN,

SEE DETAIL

OR

VENTURI VALVE WITH

CONTROLLER LOCATED ON

SIDE OF VALVE

TEMPERATURE INDICATOR

(THERMOMETER) WITH

THERMOWELL

TI

OR

TI

TEMPERATURE

INDICATOR

(THERMOMETER)

WITHOUT THERMOWELL

(DIRECT INSERTION)

TW

THERMOWELL

TE

TEMPERATURE ELEMENT

(DIRECT INSERTION)

TS

STRAP ON PIPE

TEMPERATURE

INSTRUMENT (AQUASTAT)

TE

TEMPERATURE ELEMENT

WITH TRANSMITTER AND

THERMOWELL

TT

PRESSURE INDICATOR

(PRESSURE GAUGE)

WITH GAUGE VALVE

PI

OR

PDT PRESSURE

DIFFERENTIAL

TRANSMITTER

FE

FLOW ELEMENT

(FLOW SENSOR)

OR

FE FLOW ELEMENT WITH

TRANSMITTER (FLOW

METER)

FT

FI

FLOW

INDICATOR/FLOW

METER

FLOW SWITCH

FS

OR

GAUGE CONNECTION

WITH GAUGE VALVE

COMMON INSTRUMENTATION DEVICES

T THERMOSTAT OR TEMPERATURE SENSOR

HUMIDISTAT OR HUMIDITY SENSOR

NIGHT CYCLE CONTROL THERMOSTAT

THERMOSTAT WITH INSULATING BASE

PRESSURE TRANSMITTER

PRESSURE DIFFERENTIAL TRANSMITTER

H

T N

T B

PT

PDT

DUCT SMOKE DETECTOR

PRESSURE SENSOR

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

OXYGEN SENSOR

VOC SENSOR

REFRIGERANT SENSOR

F

SD

P

A

CO2

A

CO

A O2

A

VOC

A R

FIELD MOUNTED CONTROLS

DCW DOMESTIC COLD WATER

ULTRA-LOW PRESSURE

CONDENSATE

ULTRA-LOW PRESSURE STEAMULPS

ULPC

HRS

HRR

HEAT RECOVER WATER SUPPLY

HEAT RECOVER WATER RETURN

CS CLEAN STEAM

CSC CLEAN STEAM CONDENSATE

CSW COLD SOFT WATER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

RHWR REHEAT WATER RETURN

RHWS REHEAT WATER SUPPLY

RO REVERSE OSMOSIS WATER

SCHR SECONDARY CHILLED WATER

RETURN

SCHS SECONDARY CHILLED WATER

SUPPLY

HTHWR HIGH TEMPERATURE HOT

WATER RETURN

HTHWS HIGH TEMPERATURE HOT

WATER SUPPLY

RUPTURE DISK - PRESSURE

RELIEF

GAS PRESSURE REGULATOR

REDUCED PRESSURE

BACKFLOW PREVENTER

(RPBP)

THERMODYNAMIC STEAM TRAP

B BIMETAL STEAM TRAP

SHEET SYMBOLS

A/15B-6

SPECIALTY ITEMS

(I.E. GAUGE FILTER, ETC.)

REFER TO EQUIPMENT LIST

M-1

ROOM NAME & NUMBER

DESIGNATION

SECTION DESIGNATION.

-TOP INDICATES SECTION NUMBER,

-BOTTOM INDICATES ON WHICH

SHEET SECTION APPEARS

MATCHLINE

DESIGNATION

DETAIL REFERENCE.

-TOP INDICATES SECTION NUMBER,

-BOTTOM INDICATES ON WHICH

SHEET SECTION APPEARS

REVISION REFERENCE.

REFER TO SHEET REVISION

BLOCK

SHEET KEYNOTE REFERENCE

PLAN CONTINUATION REFERENCE.

-BOTTOM INDICATES ON WHICH

SHEET CONTINUATION APPEARS

SCHEDULED EQUIPMENT DESIGNATION.

-TOP INDICATES EQUIPMENT

ABBREVIATION

-BOTTOM INDICATES EQUIPMENT

NUMBER

REFER TO EQUIPMENT SCHEDULES

ELEVATION DESIGNATION.

REFERENCE OFFICIAL

PROJECT DATUM

EQ

POINT OF NEW

CONNECTION TO EXISTING

REFER

M-1

M-1

ROOM NAME

HALFTONE LIGHT LINE

INDICATES EXISTING WORK

HEAVY DASHED LINE WITH

HATCH INDICATES

EXISTING WORK TO BE

DEMOLISHED

HEAVY LINE INDICATES

NEW WORKDETAIL REFERENCE, INDICATING

DETAIL NUMBER / SHEET ON WHICH

DETAIL APPEARS.

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

12" = 1'-0"

25174-02

03/19/2026

M001

XZRR

MECHANICAL

SYMBOLS &

ABBREVIATIONS

4400 S M L King Jr Pkwy, Beaumont, TX 77705

Rev Date Description

03/19/2026

0' - 4 1/2"

MD201

18 19

EXISTING CHILLER

CH-2

EXISTING CHILLER

CH-1

EXISTING CHILLER

CH-3

EXIST.

CHWP-3

EXIST.

CHWP-2

EXIST.

CHWP-1

EXISTING HOT WATER BOILERS

EXISTING HOT WATER

PUMPS

M600

LEVEL 01

0' - 0"

LEVEL 01

0' - 0"

LEVEL 1

0' - 0"

ROOF

20' - 0"

ROOF

20' - 0"

ROOF

20' - 0"

CH-1 CH-2

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

1/4" = 1'-0"

25174-02

03/19/2026

MD201

XZRR

MECHANICAL

DEMOLITION

PLAN - LEVEL 01 -

NORTH PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL NOTES

A. WORK SHALL CONFORM TO OWNERS CONSTRUCTION AND INFLECTION CONTROL

PROCEDURES.

B. WHERE DEMOLITION WORK NECESSARILY DIMINISHES OR ADVERSELY AFFECTS

LIFE-SAFETY SYSTEM SUCH AS SPRINKLER SYSTEMS AND/OR FIRE ALARM SYSTEMS

COORDINATE SUCH WORK THROUGH CONSTRUCTION MANAGER, OWNER AND FIRE

MARSHAL.

C. SERVICES SHALL NOT BE INTERRUPTED OR CHANGED WITHOUT WRITTEN

PERMISSION AND SCHEDULE APPROVED BY OWNER. WHERE DEMOLITION WORK

INTERFERES WITH OWNERS USE OF PREMISES, SCHEDULE WORK THROUGH OWNER

TO MINIMIZE INCONVENIENCE TO OWNER.

D. CONSTRUCTION MANAGER AND CONTRACTOR SHALL COORDINATE AND FIELD

VERIFY EXISTING PIPING, DUCTWORK, AND CONTROL DISCONNECTION POINTS.

PROVIDE VALVES, TEMPORARY CAPS AND/OR PLUGS TO ISOLATE PORTIONS OF

SYSTEMS TO FACILITATE PHASING OR WORK OR TO ISOLATE PORTIONS OF

SYSTEMS TO REMAIN FROM PORTIONS TO BE DEMOLISHED.

E. EXISTING DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHOWN ARE BASED ON

AVAILABLE DOCUMENTATION OF EXISTING CONDITIONS AND FIELD OBSERVATIONS.

DRAWINGS DO NOT SHOW IN DETAIL FULL EXTENT OF REQUIRED DEMOLITION WORK.

CONTRACTOR SHALL VISIT SITE AND REVIEW PRIOR TO BID OR NEGOTIATED

CONTRACT TO DETERMINE SCOPE O DEMOLITION WORK. PROVIDE COMPLETE

DEMOLITION WORK REQUIRED TO ACCOMPLISH PROJECT SCOPE. COORDINATE

EXTENT OF DEMOLITION WORK WITH DRAWING INDICATING NEW WORK.

F. WHERE EQUIPMENT, PIPING, DUCTWORK AND OR OTHER ITEMS ARE INDICATED TO

BE REMOVED, REMOVE RELATED SUPPORTS BACK TO ATTACHMENTS TO BUILDING

STRUCTURE. IN PERFORMING DEMOLITION WORK, DO NOT DAMAGE OR MODIFY

BUILDING STRUCTURE, INCLUDING REMOVAL OF CONCRETE OR STEEL STRUCTURAL

MATERIALS OR COMPONENTS TO ACCOMPLISH REMOVAL OF ATTACHMENTS TO

BUILDING STRUCTURE WITHOUT WRITTEN APPROVAL OF STRUCTURAL ENGINEER OF

RECORD.

G. OTHER THAN STRUCTURAL ATTACHMENTS, WHERE EXISTING WORK IS REMOVED,

MATERIALS SHALL BE REMOVED TO A POINT BELOW FINISHED FLOORS OR BEHIND

FINISHED WALLS TO ALLOW FOR THE INSTALLATION OF NEW FINISHED MATERIALS.

SUPPORT REMAINING WORK IN ACCORDANCE WITH REQUIREMENTS FOR NEW

INSTALLATION.

H. WHERE CONTROL DEVICES ARE REMOVED, REMOVE ASSOCIATED WIRING, CONDUIT,

AND PNEUMATIC TUBING AS APPLICABLE.

I. PATCH OPENINGS IN WALLS, CEILINGS, ROOF AND FLOOR SURFACES DAMAGED,

CREATED, OR LEFT BY DEMOLITION WORK. PATCHING SHALL MATCH EXISTING FIRE-

RESISTANCE RATINGS AND WHERE POSSIBLE,SHALL MATCH EXISTING ADJACENT

SURFACES AS TO THICKNESS, TEXTURE, MATERIALS AND COLORS TO SATISFACTION

OF OWNER.

J. EXISTING TO REMAIN INSULATION DAMAGED BY CONTRACTOR SHALL BE REPAIRED

OR REPLACED IN KIND.

K. PROTECT EXISTING DUCTWORK, DIFFUSERS, AND GRILLES TO REMAIN FROM

CONSTRUCTION DUST AND DEBRIS.

SCALE: 1/4" = 1'-0"

MECHANICAL DEMOLITION - LEVEL-1 - NORTH PLANT

SHEET KEYED NOTES#

1. EXISTING HOUSE KEEPING PADS FOR EXISTING CHILLER CH-1 AND CH-2 SHALL REMAIN

IN PLACE TO PROVIDE SUPPORT FOR NEW CHILLERS CH-1 AND CH-2.

2. DISCONNECT POWER TO EXISTING ELECTRICAL DISCONNECT FOR EXISTING CHILLER

CH-1 AND CH-2 TO PREPARE FOR REMOVAL OF THE CHILLERS. REFER TO ELECTRICAL

DRAWINGS.

3. DISCONNECT ELECTRICAL POWER TO EXISTING STARTER CABINETS AND REMOVE

STARTERS FROM EXISTING PAD AND THE BUILDING. REFER TO ELECTRICAL DRAWINGS

FOR ADDITIONAL INFORMATION AND DETAILS .

4. DISCONNECT ELECTRICAL POWER TO EXISTING CHILLER CH-1 AND CH-2 TO PREPARE

FOR CHILLER REMOVAL. REFER TO ELECTRICAL DRAWINGS FOR DISCONNECT

REQUIREMENTS.

5. CLOSE EXISTING ISOLATION VALVES FOR EXISTING CONDENSER WATER SUPPLY LINES

TO PREPARE FOR DISCONNECT AND REMOVAL OF THE EXISTING CONDENSER WATER

SUPPLY CONNECTIONS TO CHILLER CH-1 AND CH-2.

6. CLOSE EXISTING ISOLATION VALVES FOR EXISTING CONDENSER WATER RETURN LINES

TO PREPARE FOR DISCONNECT AND REMOVAL OF THE EXISTING CONDENSER WATER

RETURN CONNECTIONS TO CHILLER CH-1 AND CH-2.

7. CLOSE EXISTING ISOLATION VALVE FOR EXISTING CHILLED WATER RETURN LINES TO

PREPARE FOR DISCONNECT AND REMOVAL OF THE EXISTING CHILLED WATER RETURN

CONNECTIONS TO CHILLER CH-1 AND CH-2.()

8. DISCONNECT EXISTING CONDENSER WATER SUPPLY PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-1 AND THE FLANGE CONNECTION TO

THE EXISTING CONTROL-VALVE MOUNTED OVERHEAD AND REMOVE THE EXISTING

PIPING BETWEEN THE TWO POINTS AND THE CONTROL VALVE TO ALLOW FOR

REMOVAL AND NEW CHILLER TO BE INSTALLED.

9. DISCONNECT EXISTING CONDENSER WATER RETURN PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-1 AND THE FLANGE CONNECTION IN

THE OVERHEAD LINE AND REMOVE THE EXISTING PIPING BETWEEN THE TWO POINTS

TO ALLOW FOR REMOVAL OF THE CHILLER

10. DISCONNECT EXISTING CHILLED WATER RETURN PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-1 AND THE FLANGE CONNECTION

OVERHEAD AND REMOVE THE EXISTING PIPING BETWEEN THE TWO POINTS TO ALLOW

FOR REMOVAL OF THE CHILLER.

11. DISCONNECT EXISTING CHILLED WATER SUPPLY PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-1 AND THE FLANGE CONNECTION FOR

THE EXISTING ISOLATION VALVE AND REMOVE THE EXISTING PIPING AND FAILED

BALANCE VALVE BETWEEN THE TWO POINTS TO ALLOW FOR REMOVAL OF THE

CHILLER.

12. EXISTING REFRIGERANT RELIEF PIPING TO BE REMOVED TO ALLOW EXISTING

CHILLERS TO BE REMOVED AND THE NEW CHILLERS TO BE INSTALLED. COORDINATE

REMOVAL OF THE CHILLERS FROM THE SITE WITH THE OWNER.

SCALE: 1/4" = 1'-0"

CHILLER CH-1 -CH-2 DEMOLITION SECTION

13. DISCONNECT EXISTING CONDENSER WATER SUPPLY PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-2 AND THE FLANGE CONNECTION TO

THE EXISTING CONTROL-VALVE MOUNTED OVERHEAD AND REMOVE THE EXISTING

PIPING BETWEEN THE TWO POINTS TO ALLOW FOR THE REMOVAL OF THE CHILLER.

14. DISCONNECT EXISTING CONDENSER WATER RETURN PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-2 AND THE FLANGE CONNECTION IN

THE OVERHEAD LINE AND REMOVE THE EXISTING PIPING BETWEEN THE TWO POINTS

TO ALLOW FOR REMOVAL OF THE CHILLER.

15. DISCONNECT EXISTING CHILLED WATER RETURN PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-2 AND THE FLANGE CONNECTION

MOUNTED OVERHEAD AND REMOVE THE EXISTING PIPING BETWEEN THE TWO POINTS

TO ALLOW FOR REMOVAL OF THE CHILLER.

16. DISCONNECT EXISTING CHILLED WATER SUPPLY PIPING FROM THE FLANGE

CONNECTION ON THE FACE OF THE CHILLER CH-2 AND THE FLANGE CONNECTION TO

THE EXISTING ISOLATION VALVE MOUNTED OVERHEAD AND REMOVE THE EXISTING

PIPING BETWEEN THE TWO POINTS TO ALLOW FOR REMOVAL OF THE CHILLER.

17. EXISTING EXPANSION TANK AND EXISTING CONNECTIONS SHALL REMAIN IN PLACE

AND IN-SERVICE AS THE EXISTING CHILLER IS REMOVED. PROTECT TANK AND PIPING

FROM DAMAGE AS THE CHILLER IS REMOVED.

18. EXISTING ELECTRICAL DISCONNECTS MOUNTED ON SOUTH WALL ADJACENT TO

EXISTING CHILLER CH-1 SHALL REMAIN IN-PLACE AND IN-SERVICE AS THE EXISTING

CHILLERS ARE REMOVED.

19. REMOVE EXISTING REFRIGERANT MONITORING PANEL AND ASSOCIATED TUBING TO

CH-1 AND CH-2. EXISTING CH-3 TUBING, CONTROL WIRING TO EXISTING REFRIGERANT

EXHAUST FANS, PUSH BUTTONS AND AUDIO/VISUAL ALARMS SHALL BE

DISCONNECTED AND REMAIN IN PLACE FOR NEW REFRIGERANT MONITORING PANEL

CONNECTION. RE: M203 FOR RENOVATION WORK.

NORTH PLANT

MD301

MD301

CH-1 STARTER

CABINET

CH-2

CH-1

CH-3

CHWP-1 CHWP-2

CH-2 STARTER

CABINET

MAIN ELECTRICAL ROOM

BOILER AND HW PUMP ROOM

CH-1

CH-2

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

As indicated

25174-02

03/19/2026

MD301

XZRR

MECHANICAL

DEMOLITION

PLAN - LEVEL 01 -

SOUTH PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL NOTES

SHEET KEYED NOTES#

1. TO PREPARE FOR THE DEMOLITION OF EXISTING CHILLERS CH-1 AND CH-2, EXISTING

CHILLER CH-3 MUST BE TAKEN OFF-LINE AND ALL ISOLATION VALVES ON THE CHILLED

WATER AND CONDENSER WATER CONNECTIONS CLOSED.

2. DISCONNECT CONDENSER WATER RETURN CONNECTION AT THE WATER-BOX OUTLET

AND THE FLANGE CONNECTION AT THE ISOLATION VALVE CONNECTED TO THE

CONDENSER WATER RETURN HEADER OVERHEAD AND REMOVE ALL PIPING BETWEEN

THE TWO POINTS. SET ASIDE ALL PIPING, FITTINGS AND ACCESSORIES FOR RE-

INSTALLATION ONCE NEW CHILLERS HAVE BEEN SET IN PLACE.

3. DISCONNECT CONDENSER WATER SUPPLY CONNECTION AT THE WATER-BOX INLET

AND THE FLANGE CONNECTION AT THE ISOLATION VALVE CONNECTED TO THE

CONDENSER WATER SUPPLY HEADER OVERHEAD AND REMOVE ALL PIPING BETWEEN

THE TWO POINTS. SET ASIDE ALL PIPING, FITTINGS AND ACCESSORIES FOR RE-

INSTALLATION ONCE NEW CHILLERS HAVE BEEN SET IN PLACE.

4. ONCE BOTH SETS OF PIPING CONNECTIONS ARE REMOVED, DISCONNECT WATER-BOX

FROM THE CHILLER CONDENSER BARREL AND SET ASIDE TO CLEAR THE PATH TO

REMOVE EXISTING CHILLERS CH-1 AND CH-2 FROM THE BUILDING.

5. TO PREPARE FOR THE DEMOLITION OF EXISTING CHILLERS CH-1 AND CH-2, ISOLATE

POWER AT THE EXISTING MAIN DISCONNECT SWITCHES LOCATED IN THE MAIN

ELECTRICAL ROOM. ONCE POWER IS ISOLATED, DISCONNECT EXISTING ELECTRICAL

FEEDERS TO EXISTING CHILLERS CH-1 AND CH-2 AT THE STARTER CABINET ENTRANCE

CONNECTIONS AND AT THE CHILLERS. ONCE ELECTRICAL FEEDERS AND CONDUITS

ARE DISCONNECTED, REMOVE EXISTING STARTER CABINETS. REFER TO ELECTRICAL

DRAWINGS FOR ADDITIONAL DETAILS.

6. CLOSE EXISTING ISOLATION AND CONTROL VALVES ON THE EXISTING CONDENSER

WATER SUPPLY, CONDENSER WATER RETURNS, CHILLED WATER SUPPLY AND CHILLED

WATER RETURN PIPING TO EXISTING CHILLERS CH-1 AND CH-2 TO STOP FLOW TO THE

CHILLERS.

7. DISCONNECT EXISTING CONDENSER WATER SUPPLY FLANGE CONNECTION AT THE

FACE OF THE EXISTING CHILLER CH-2 AND THE FLANGE CONNECTION TO THE EXISTING

CONTROL VALVE OVERHEAD AND REMOVE ALL PIPING, FITTINGS AND ACCESSORIES

BETWEEN THE TWO POINTS. SET ASIDE ALL REMOVED COMPONENTS FOR POSSIBLE

FUTURE REUSE.

8. DISCONNECT EXISTING CONDENSER WATER RETURN FLANGE CONNECTION AT THE

FACE OF THE EXISTING CHILLER CH-2 AND THE FLANGE CONNECTION OVERHEAD AND

REMOVE ALL PIPING, FITTINGS AND ACCESSORIES BETWEEN THE TWO POINTS. SET

ASIDE ALL REMOVED COMPONENTS FOR POSSIBLE FUTURE REUSE.

9. DISCONNECT EXISTING CHILLED WATER RETURN FLANGE CONNECTION AT THE FACE

OF THE EXISTING CHILLER CH-2 AND THE FLANGE CONNECTION IN THE RETURN PIPE

ABOVE THE EXISTING CHILLER AND REMOVE ALL PIPING, FITTINGS, VALVES AND

ACCESSORIES BETWEEN THE TWO POINTS. SET ASIDE ALL REMOVED COMPONENTS

FOR POSSIBLE FUTURE REUSE.

10. DISCONNECT EXISTING CHILLED WATER SUPPLY FLANGE CONNECTION AT THE FACE

OF THE CHILLER CH-2 AND THE FLANGE CONNECTION IN THE SUPPLY PIPE ABOVE AND

REMOVE ALL PIPING, FITTINGS AND ACCESSORIES BETWEEN THE TWO POINTS. SET

ASIDE ALL REMOVED COMPONENTS FOR POSSIBLE FUTURE REUSE.

11. EXISTING REFRIGERANT RELIEF PIPING BELOW ROOF TO BE REMOVED TO ALLOW

EXISTING CHILLERS TO BE REMOVED AND NEW CHILLERS TO BE INSTALLED. ONCE

ELECTRICAL POWER AND PIPING CONNECTIONS ARE REMOVED, REMOVE EXISTING

CHILLERS CH-1 AND CH-2 FROM THE BUILDING. EXISTING HOUSEKEEPING PADS WILL

STAY IN PLACE FOR FUTURE USE.

12. DISCONNECT EXISTING CHILLED WATER SUPPLY CONNECTION TO THE FLANGE

CONNECTION AT THE FACE OF THE EXISTING CHILLER CH-1 AND THE FLANGE

CONNECTION TO THE EXISTING ISOLATION VALVE IN THE PIPING ABOVE THE CHILLER

AND REMOVE ALL PIPING, FITTINGS AND ACCESSORIES BETWEEN THE TWO POINTS.

SET ASIDE ALL REMOVED COMPONENTS FOR POSSIBLE FUTURE REUSE.

13. DISCONNECT EXISTING CHILLED WATER RETURN CONNECTION TO THE FLANGE

CONNECTION AT THE FACE OF THE EXISTING CHILLER CH-1 AND THE FLANGE

CONNECTION IN THE VERTICAL PIPE AND REMOVE ALL PIPING, FITTINGS, VALVES AND

ACCESSORIES BETWEEN THE TWO POINTS. SET ASIDE ALL REMOVED COMPONENTS

FOR POSSIBLE FUTURE REUSE.

14. DISCONNECT EXISTING CONDENSER WATER RETURN CONNECTION TO THE FLANGE

CONNECTION AT THE FACE OF THE EXISTING CHILLER CH-1 AND THE FLANGE

CONNECTION AT THE ISOLATION VALVE IN THE RETURN PIPE AND REMOVE ALL PIPING,

FITTINGS, VALVES AND ACCESSORIES BETWEEN THE TWO POINTS. SET ASIDE ALL

REMOVED COMPONENTS FOR POSSIBLE FUTURE REUSE.

15. DISCONNECT EXISTING CONDENSER WATER SUPPLY CONNECTION AT FACE OF

CHILLER CH-1 AND THE FLANGE TO THE EXISTING CONTROL VALVE OVERHEAD AND

REMOVE ALL PIPING, FITTINGS AND ACCESSORIES BETWEEN THE TWO POINTS. SET

ASIDE ALL REMOVED COMPONENTS FOR POSSIBLE FUTURE REUSE.

16. REMOVE EXISTING REFRIGERANT MONITORING PANEL AND ASSOCIATED TUBING AND

SENSORS TO CH-1 AND CH-2. EXISTING CH-3 TUBING, SENSORS, CONTROL WIRING TO

EXISTING REFRIGERANT EXHAUST FANS, PUSH BUTTONS AND AUDIO/VISUAL ALARMS

SHALL REMAIN IN PLACE FOR NEW REFRIGERANT MONITORING PANEL CONNECTION.

RE: M302 FOR RENOVATION WORK.

SCALE: 3/16" = 1'-0"

MECHANICAL DEMOLITION - LEVEL 01 - SOUTH PLANT

SCALE: 1/4" = 1'-0"

CHILLER CH-1 DEMOLITION

SCALE: 1/4" = 1'-0"

CHILLER CH-2 DEMOLITION

A. WORK SHALL CONFORM TO OWNERS CONSTRUCTION AND INFLECTION CONTROL

PROCEDURES.

B. WHERE DEMOLITION WORK NECESSARILY DIMINISHES OR ADVERSELY AFFECTS

LIFE-SAFETY SYSTEM SUCH AS SPRINKLER SYSTEMS AND/OR FIRE ALARM SYSTEMS

COORDINATE SUCH WORK THROUGH CONSTRUCTION MANAGER, OWNER AND FIRE

MARSHAL.

C. SERVICES SHALL NOT BE INTERRUPTED OR CHANGED WITHOUT WRITTEN

PERMISSION AND SCHEDULE APPROVED BY OWNER. WHERE DEMOLITION WORK

INTERFERES WITH OWNERS USE OF PREMISES, SCHEDULE WORK THROUGH OWNER

TO MINIMIZE INCONVENIENCE TO OWNER.

D. CONSTRUCTION MANAGER AND CONTRACTOR SHALL COORDINATE AND FIELD

VERIFY EXISTING PIPING, DUCTWORK, AND CONTROL DISCONNECTION POINTS.

PROVIDE VALVES, TEMPORARY CAPS AND/OR PLUGS TO ISOLATE PORTIONS OF

SYSTEMS TO FACILITATE PHASING OR WORK OR TO ISOLATE PORTIONS OF

SYSTEMS TO REMAIN FROM PORTIONS TO BE DEMOLISHED.

E. EXISTING DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHOWN ARE BASED ON

AVAILABLE DOCUMENTATION OF EXISTING CONDITIONS AND FIELD OBSERVATIONS.

DRAWINGS DO NOT SHOW IN DETAIL FULL EXTENT OF REQUIRED DEMOLITION WORK.

CONTRACTOR SHALL VISIT SITE AND REVIEW PRIOR TO BID OR NEGOTIATED

CONTRACT TO DETERMINE SCOPE O DEMOLITION WORK. PROVIDE COMPLETE

DEMOLITION WORK REQUIRED TO ACCOMPLISH PROJECT SCOPE. COORDINATE

EXTENT OF DEMOLITION WORK WITH DRAWING INDICATING NEW WORK.

F. WHERE EQUIPMENT, PIPING, DUCTWORK AND OR OTHER ITEMS ARE INDICATED TO

BE REMOVED, REMOVE RELATED SUPPORTS BACK TO ATTACHMENTS TO BUILDING

STRUCTURE. IN PERFORMING DEMOLITION WORK, DO NOT DAMAGE OR MODIFY

BUILDING STRUCTURE, INCLUDING REMOVAL OF CONCRETE OR STEEL STRUCTURAL

MATERIALS OR COMPONENTS TO ACCOMPLISH REMOVAL OF ATTACHMENTS TO

BUILDING STRUCTURE WITHOUT WRITTEN APPROVAL OF STRUCTURAL ENGINEER OF

RECORD.

G. OTHER THAN STRUCTURAL ATTACHMENTS, WHERE EXISTING WORK IS REMOVED,

MATERIALS SHALL BE REMOVED TO A POINT BELOW FINISHED FLOORS OR BEHIND

FINISHED WALLS TO ALLOW FOR THE INSTALLATION OF NEW FINISHED MATERIALS.

SUPPORT REMAINING WORK IN ACCORDANCE WITH REQUIREMENTS FOR NEW

INSTALLATION.

H. WHERE CONTROL DEVICES ARE REMOVED, REMOVE ASSOCIATED WIRING, CONDUIT,

AND PNEUMATIC TUBING AS APPLICABLE.

I. PATCH OPENINGS IN WALLS, CEILINGS, ROOF AND FLOOR SURFACES DAMAGED,

CREATED, OR LEFT BY DEMOLITION WORK. PATCHING SHALL MATCH EXISTING FIRE-

RESISTANCE RATINGS AND WHERE POSSIBLE,SHALL MATCH EXISTING ADJACENT

SURFACES AS TO THICKNESS, TEXTURE, MATERIALS AND COLORS TO SATISFACTION

OF OWNER.

J. EXISTING TO REMAIN INSULATION DAMAGED BY CONTRACTOR SHALL BE REPAIRED

OR REPLACED IN KIND.

K. PROTECT EXISTING DUCTWORK, DIFFUSERS, AND GRILLES TO REMAIN FROM

CONSTRUCTION DUST AND DEBRIS.

SOUTH PLANT

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

25174-02

03/19/2026

M101

XZRR

MECHANICAL

SITE PLANS

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL BEAUMONT, TEXAS AREA

LAMAR UNIVERSITY CAMPUS

NORTH CENTRAL PLANT

SOUTH CENTRAL PLANT

GENERAL LAMAR CAMPUS AREA

EXISTING CHWS &CHWR

DISTRIBUTION TO NORTH

CAMPUS

EXISTING CHWS &CHWR

DISTRIBUTION TO WEST

CAMPUS

EXISTING CH-2 MAIN

DISCONNECT CABINET

EXISTING CH-1 MAIN

DISCONNECT CABINET

CH-2N

CH-1N

CHWP-1

CHWP-2

CHWP-3

12"CHR

14"CHS

12"CHR

10"CHR

10"CHS

12"CHR 12"CHS

12"TWS

12"TWR

18"CHR 18"CHR

12"TWR

16"TWR

14"TWS14"TWS12"TWS

12"TWR

10"CHR

14"CHS

12"CHR

12"CHR

8"CHR

8"CHS

10"CHR

10"CHS

10"CHR

14"CHS

8"CHR

8"CHS

6"CHS

6"CHR

M600

CH-3

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

1/4" = 1'-0"

25174-02

03/19/2026

M201

XZRR

MECHANICAL

PIPING

RENOVATION

PLAN - LEVEL 01 -

NORTH PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

SCALE: 1/4" = 1'-0"

MECHANICAL PIPING RENOVATION PLAN - LEVEL 01 - NORTH PLANT

GENERAL NOTES SHEET KEYED NOTES#

A. FLOOR PLANS AND SECTIONS INCLUDE PIPE ROUTING, MAJOR VALVES, AND MAJOR

PIPING SPECIALITIES. REFER TO DETAILS AND SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

B. INSULATE ALL NEW PIPING, VALVES, FITTINGS AND ACCESSORIES REQUIRED TO

CONNECT NEW CHILLERS.

C. REPAIR/REPLACE ANY INSULATION DAMAGED DURING DEMOLITION OR THE

INSTALLATION OF NEW PIPING.

D. EXISTING PIPE SUPPORTS SHALL BE REUSED TO SUPPORT NEW PIPING WHERE

POSSIBLE. PROVIDE NEW PIPE SUPPORTS WHERE REQUIRED TO MATCH EXISTING AND

PROVIDE ADEQUATE SUPPORT TO THE NEW PIPING.

E. PROVIDE FLOOR SUPPORTS FOR NEW ELBOWS CONNECTED TO THE FRONT OF THE

CHILLERS TO PROVIDE ADDITIONAL SUPPORT, SUPPORTS MUST BE REMOVABLE TO

ALLOW FOR FUTURE SERVICE TO THE CHILLERS.

1. EXISTING HOUSEKEEPING PADS SHALL BE UTILIZED TO SUPPORT THE NEW CHILLERS

CH-1N AND CH-2N. CONTRACTOR SHALL FIELD VERIFY THE SIZE OF THE EXISTING

PADS AND MAKE ADJUSTMENTS AS REQUIRED TO PROVIDE ALL REQUIRED SUPPORT

FOR THE NEW CHILLERS.

2. NEW CHILLERS CH-1N AND CH-2N SHALL BE PLACED ON THE EXISTING HOUSEKEEPING

PADS ON NEOPRENE PADS WITH A MINIMUM THICKNESS OF 1 1/2" UNDER THE

SUPPORT POINTS OF THE CHILLERS IN ACCORDANCE WITH MANUFACTURERS

RECOMMENDATIONS.

3. PROVIDE NEW 12" DIA. CWR PIPE FROM THE UPPER CONDENSER WATER BOX

CONNECTION UP TO THE EXISTING CWR FLANGE CONNECTION OVERHEAD. RE: M800

DETAIL 5 FOR CONNECTION REQUIREMENTS.

4. PROVIDE NEW 12" DIA. CWS PIPE FROM THE LOWER CONDENSER WATER BOX

CONNECTION UP TO THE EXISTING CWS CONTROL VALVE OVERHEAD. RE: M800

DETAIL 5 FOR CONNECTION REQUIREMENTS.

5. PROVIDE NEW 12" DIA. CHWR PIPE FROM THE LOWER CHILLED WATER RETURN

FLANGE CONNECTED TO THE FACE OF THE EVAPORATOR BARREL UP TO EXISTING

FLANGE IN THE EXISTING CHWR HEADER OVERHEAD. RE-INSTALL EXISTING

ISOLATION VALVE IN THE VERTICAL RISER AT A SUFFICIENT HEIGHT TO ALLOW FOR

REMOVAL OF LOWER CONNECTION FOR CHILLER MAINTENANCE. RE: M800 DETAIL 5

FOR CONNECTION REQUIREMENTS.

6. PROVIDE NEW 12" DIA. CHWS PIPE FROM THE CHILLED WATER SUPPLY FLANGE AT

THE FACE OF THE NEW CHILLER EVAPORATOR BARREL UP TO EXISTING CHWS PIPE

OVERHEAD WHERE THE EXISTING BALANCE WAS REMOVED DURING DEMOLITION AND

INSTALL NEW 12" DIA. BALANCE VALVE BEFORE THE EXISTING 12" ISOLATION VALVE.

PROVIDE NEW CONNECTION FLANGES IN THE NEW SUPPLY PIPING TO ALLOW

REMOVAL OF THE CONNECTION TO THE CHILLER FACE TO PROVIDE ACCESS FOR

CHILLER MAINTENANCE. RE: M800 DETAIL 5 FOR CONNECTION REQUIREMENTS.

7. THE EXISTING ISOLATION VALVE AT THE CONNECTION POINT OF THE EXISTING 12"

CHWS TO THE CHWS HEADER OVERHEAD SHALL REMAIN IN SERVICE.

8. SET NEW CHILLER CH-1 AND CH-2 STARTER CABINETS ON EXISTING HOUSE KEEPING

PADS AND CONNECT EXISTING ELECTRICAL FEEDERS FOR THE NEW CHILLER CH-1N

AND CH-2N TO THW NEW STARTER CABINETS AND EXISTING DISCONNECT CABINETS

FOR CHILLER THE TWO CHILLERS LOCATED AT THE WEST END OF THE MECHANICAL

ROOM. RE: ELECTRICAL DRAWINGS FOR WIRING DETAILS.

9. PROVIDE NEW REFRIGERANT RELIEF PIPING TO CONNECT NEW REFRIGERANT RELIEF

POINTS ON THE NEW CHILLER TO THE EXISTING REFRIGERANT RELIEF PIPING

OVERHEAD THAT RUNS UP THROUGH THE ROOF. CONTRACTOR SHALL VERIFY LINE

SIZE OF THE EXISTING PIPING UP THROUGH ROOF BASED ON THE REFRIGERANT

SELECTED FOR THE NEW CHILLER AND ADJUST PIPE SIZE AS REQUIRED.

10. PROVIDE NEW 12" DIA. CWR PIPE FROM THE UPPER CONDENSER WATER BOX

CONNECTION UP TO EXISTING CONNECTION FLANGE IN THE EXISTING CWR PIPE

OVERHEAD. RE: M800 DETAIL 5 FOR CONNECTION REQUIREMENTS.

NEW CHILLER CH-1N

NEW CWR CONNECTION-CH-1N

EXISTING CHILLED WATER PUMPS

CAMPUS DISTRIBUTION TUNNEL-

SOUTH

NEW FLOW

METER-

FM-4N -CH-1N

CWR

NEW CWS CONNECTION-CH-1N

NEW CHWR CONNECTION-CH-1N

NEW CHWS CONNECTION-CH-1N

NEW FLOW

METER-FM-1N -

CH-1N CHWR

EXISTING CONTROL

VALVE CH-1N CWS

EXISTING CONTROL

VALVE -CH-2N - CWR

EXISTING CONTROL

VALVE - CH-2N -CHWR

EXISTING CONTROL

VALVE CH-1N - CHWR

NEW FLOW FLOW

METER- FM-5N -

CH-2N CWR

NEW FLOW FLOW METER-

FM-2N - CH-2N CHWR

EXISTING CONTROL

VALVE - CH-2N

CHWS BY-PASS

NEW EMERGENCY

PUSH BUTTON AND

STROBE

NEW REFRIGERANT

RELIEF PIPING.

11. PROVIDE NEW 12" DIA. CWS PIPE FROM THE LOWER CONDENSER WATER BOX

CONNECTION U P TO THE CONNECTION FLANGE FOR THE EXISTING CWS CONTROL

VALVE IN THE CWS PIPE OVERHEAD. EXISTING CONTROL VALVE SHALL REMAIN IN

SERVICE. RE: M800 DETAIL 5 FOR CONNECTION REQUIREMENTS.

12. PROVIDE NEW 12" DIA. CHWR PIPE TO THE LOWER CHILLED WATER FLANGE

CONNECTED TO THE FACE OF THE EVAPORATOR BARREL UP TO EXISTING

CONNECTION FLANGE IN THE EXISTING CHWR PIPE OVERHEAD. RE-INSTALL EXISTING

ISOLATION VALVE IN THE VERTICAL SECTION OF PIPE AT A SUFFICIENT ELEVATION TO

ALLOW FOR REMOVAL OF THE CONNECTION ELBOW FOR FUTURE CHILLER

MAINTENANCE. RE: M800 DETAIL 5 FOR CONNECTION REQUIREMENTS.

13. PROVIDE NEW 12" DIA. CHWS PIPE FROM THE CHILLED WATER SUPPLY FLANGE AT THE

FACE OF THE NEW CHILLER EVAPORATOR BARREL UP TO THE POINT OF DEMOLITION

IN THE EXISTING CHWS PIPE OVERHEAD AND ADD A NEW BALANCE VALVE. EXISTING

ISOLATION VALVE IN THE EXISTING CHWS CONNECTION TO THE EXISTING CHWS

HEADER OVERHEAD SHALL REMAIN IN SERVICE. PROVIDE CONNECTION FLANGES AT

A SUITABLE LOCATION TO ALLOW REMOVAL OF THE CONNECTION ELBOWS FOR

FUTURE CHILLER MAINTENANCE. RE: M800 DETAIL 5 FOR CONNECTION

REQUIREMENTS.

14. REPLACE EXISTING FLOW METER FOR THE CH-1N CHWR WITH NEW MAGNETIC FLOW

METER - FM-1N.

15. REPLACE EXISTING FLOW METER FOR THE CH-1N CWR WITH NEW MAGNETIC FLOW

METER - FM-4N.

16. REPLACE EXISTING FLOW METER FOR THE CH-2N CHWR WITH NEW MAGNETIC FLOW

METER - FM-5N.

17. REPLACE EXISTING FLOW METER FOR THE CH-2N CWR WITH NEW MAGNETIC FLOW

METER - FM-2N.

18. PROVIDE NEW REFRIGERANT MONITORING PANEL TO SUPPORT NEW CHILLERS CH-1N

AND CH-2N AND EXISTING CHILLER CH-3. PROVIDE NEW SENSOR LINES FOR NEW

CHILLERS CH-1N AND CH-2N FROM NEW PANEL AND RECONNECT EXISTING SENSOR

LINES TO EXISTING CHILLER CH-3 TO NEW PANEL. RE: M202 FOR ADDITIONAL DETAIL.

NORTH PLANT

NEW CHILLER CH-2N

30x16

30x16 x

16X24

CHILLER CH-2N

CHILLER CH-1N

12 11

M600

14 14

NORTH CENTRAL PLANT VENTILATION CALCULATIONS

CHILLERS CH-1N AND CH-2N (WEST SECTION)

(CALCULATION IS BASED ON NEW REFRIGERANT R513A

AND ON THE ASSUMPTION THAT ONE CHILLER WILL BE

LEAKING. CONTRACTOR SHALL VERIFY CALCULATION

IF R514A OR OTHER REFRIGERANT IS UTILIZED. )

PURGE SYSTEM EXPANSION

CHILLER REFRIGERANT LBS: - 2,499

Q=100 X 2499√

Q= 100 X 49.00 = 4,999 CFM

USE 5,000 CFM

EXISTING EXHAUST FAN EF-1 - RATED AT 5000 CFM

AND TWO EXISTING DROPS AT 2,500 CFM EACH WILL

CONTINUE TO BE UTILIZED.

(RE-BALANCE FAN FOR 5,000 CFM)

GENERAL EXHAUST:

TOTAL WEST AREA: 3,100 S.F.

0.5 CFM/S.F. = 3,100 S.F. X 0.5

= 1,550 CFM

EXISTING GENERAL EXHAUST - EF-2 = 8,000 CFM

EXISTING GENERAL EXHAUST - EF-3 = 600 CFM

CURRENT GENERAL EXHAUST IS SUFFICIENT

NORTH CENTRAL PLANT VENTILATION CALCULATIONS

CHILLERS CH-3 (EAST SECTION)

(CALCULATION IS BASED ON EXISTING REFRIGERANT

R134A AND ON THE ASSUMPTION THAT ONE CHILLER

WILL BE LEAKING.

PURGE SYSTEM EXPANSION

CHILLER REFRIGERANT LBS: - 1,250

Q=100 X 1,250√

Q= 100 X 35.36 = 3,536 CFM

USE 4,000 CFM

EXISTING REFRIGERANT EXHAUST FAN EF-4 - RATED

AT 8,000 CFM

(CURRENT REFRIGERANT EXHAUST IS SUFFICIENT)

GENERAL EXHAUST:

TOTAL WEST AREA: 1,600 S.F.

0.5 CFM/S.F. = 1, 600 X 0.5 =

= 800 CFM

EXISTING GENERAL EXHAUST - EF-5 = 3,500 CFM

CURRENT GENERAL EXHAUST IS SUFFICIENT

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

As indicated

25174-02

03/19/2026

M202

XZRR

DUCTWORK AND

REFRIGERANT

MONITORING

PLAN - NORTH

PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL NOTES SHEET KEYED NOTES#

A. A 1. EXISTING 16" X 24" EXHAUST DROP DOWN TO 12" ABOVE FINISH FLOOR SHALL REMAIN

IN-PLACE AND IN-SERVICE TO SUPPORT REFRIGERANT EXHAUST REQUIREMENTS FOR

NEW CHILLER CH-1N. DUCT MUST BE PROTECTED WHILE ORIGINAL CHILLER IS BEING

REMOVED AND THE NEW CHILLER INSTALLED.

2. EXISTING 30" X 16" REFRIGERANT EXHAUST DUCT OVERHEAD WILL REMAIN IN-PLACE

AND IN-SERVICE.

3. EXISTING 16" X 24" EXHAUST DROP DOWN TO 12" ABOVE FINISH FLOOR SHALL REMAIN

IN-PLACE AND IN-SERVICE TO SUPPORT REFRIGERANT EXHAUST REQUIREMENTS FOR

EXISTING CHILLER CH-2N THAT WILL REMAIN IN SERVICE.

4. EXISTING 24" X 30" EXHAUST DUCT UP TO EXISTING EXHAUST FAN EF-1 ON ROOF SHALL

REMAIN IN PLACE AND IN-SERVICE TO SUPPORT THE NEW REFRIGERANT EXHAUST

REQUIREMENTS. REFER TO SHEET M204 FOR ADDITIONAL INFORMATION ON EXISTING

FAN ON ROOF.

5. EXISTING EXHAUST FAN DISCONNECT SHALL REMAIN IN-PLACE AND IN-SERVICE TO

SUPPORT EXISTING EXHAUST FAN ON ROOF.

6. NEW REFRIGERANT MONITORING PANEL CAPABLE OF BEING CALIBRATED FOR NEW

REFRIGERANT SELECTED FOR NEW CHILLERS CH-1N AND CH-2N (R513A, R514A) AND

EXISTING REFRIGERANT R134A FOR EXISTING CHILLER CH-3. PANEL SHALL BE MSA

CHILLGARD 5000 OR APPROVED EQUAL. PANEL SHALL HAVE SUFFICIENT NUMBER

PORTS TO CONNECT THREE CHILLERS AND CAPABLE OF BEING CALIBRATED TO R513A,

R514A AND R134A REFRIGERANTS. CONNECT EXISTING EXHAUST FANS ON ROOF, PUSH

BUTTONS, AUDIO/VISUAL ALARMS AND BAS SYSTEM TO NEW PANEL.

7. REUSE EXISTING SENSOR TUBING OR RUN TWO NEW SENSOR LINES IN CONDUIT FROM

THE NEW MONITOR PANEL TO EXISTING CHILLER CH-3.

8. EXISTING REFRIGERANT SENSORS FOR CHILLER CH-3 CALIBRATED FOR R134A

REFRIGERANT SHALL BE REPLACED WITH NEW IR TYPE SENSORS CALIBRATED FOR

R134A.

9. RUN NEW SENSOR LINES FROM NEW WALL MOUNTED PANEL OVERHEAD TO SW AND NE

CORNERS OF NEW CHILLERS CH-1N AND CH-2N IN 1/2" CONDUIT.

10. PROVIDE NEW IR SENSORS CALIBRATED FOR NEW SELECTED REFRIGERANT ON

OPPOSITE CORNERS OF THE NEW CHILLERS AND CONNECT TO NEW SENSOR LINES.

11. PROVIDE NEW EMERGENCY PUSH BUTTON, SIMILAR TO EXISTING PUSH BUTTONS ON

INTERIOR WALL NEXT TO EXISTING EXIT DOOR FROM THE NORTH PLANT AND CONNECT

TO NEW REFRIGERANT MONITORING PANEL AND EXISTING ROOF MOUNTED

REFRIGERANT EXHAUST FAN.

12. NEW WALL MOUNTED EMERGENCY STROBE LIGHT ON THE INTERIOR OF THE

EXTERIOR WALL NEXT TO NORTH PLANT ENTRY DOOR AND CONNECT TO NEW

MONITORING PANEL. NEW STROBE WILL BE ACTIVATED IF A REFRIGERANT LEAK IS

INDICATED BY THE MONITORING PANELS.

13. EXISTING AIR BREATHING DEVICE CABINET AND BREATHING DEVICE SHALL BE

REPLACED WITH NEW CABINET AND BREATHING DEVICE.

14. EXISTING WALL MOUNTED PUSH BUTTONS AND AUDIO/VISUAL DEVICES SHALL REMAIN

IN SERVICE.

SCALE: 1/4" = 1'-0"1

DUCTWORK AND REFRIGERANT MONITORING PLAN -NORTH PLANT

SCALE: 3/16" = 1'-0"2

NORTH PLANT EXHAUST

NORTH PLANT

EF-2 -

GENERAL

EXHAUST

(EXISTING)

EF-1 -

REFRIGERANT

EXHAUST

(EXISTING)

EF-4 -

REFRIGERANT

EXHAUST

(EXISTING)

EF-3 -

GENERAL

EXHAUST

(EXISTING)

EF-5 -

BOILER

EXHAUST

(EXISTING)

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

1/4" = 1'-0"

25174-02

03/19/2026

M203

RR

MECHANICAL

ROOF PLAN -

NORTH PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL NOTES SHEET KEYED NOTES#

A. A 1. EXISTING ROOF MOUNTED GENERAL EXHAUST FAN EF-2 SHALL REMAIN IN SERVICE TO

PROVIDE GENERAL EXHAUST TO THE WEST SECTION OF NORTH CENTRAL PLANT. -

APPROXIMATE CAPACITY - 8,000 CFM. CLEAN EXISTING FAN AND VERIFY CURRENT AIR

FLOW.

2. EXISTING ROOF MOUNTED REFRIGERANT EXHAUST FAN EF-1 SHALL REMAIN IN PLACE

AND IN-SERVICE TO PROVIDE EMERGENCY EXHAUST TO NEW CHILLERS CH-1N AND

CH-2N. EF-1 SHALL BE CLEANED, REPAIRED AS REQUIRED AND RE-BALANCED TO

PROVIDE A TOTAL EMERGENCY EXHAUST FLOW OF 5,000 CFM TO SUPPORT THE

EXHAUST REQUIREMENTS FOR NEW CHILLERS CH-1 AND CH-2. (LOREN COOK - MODEL

225R8B 1.5 HP)

3. EXISTING CONTINUOUS RUN GENERAL EXHAUST FAN EF-3 SHALL STAY IN-SERVICE.

(GREENHECK MODEL GB-240-10-V - S/N-11095042 0712 - 600 CFM @0.25" SP - .75 HP) FAN

PROVIDES ADDITIONAL GENERAL EXHAUST TO THE NORTH PLANT WEST SECTION.

CLEAN EXISTING FAN AND VERIFY CURRENT AIR FLOW.

4. EXISTING ROOF MOUNTED REFRIGERANT EXHAUST FAN EF-4 SHALL REMAIN IN PLACE

AND IN-SERVICE TO PROVIDE EMERGENCY EXHAUST TO EXISTING CHILLER CH-3.

CURRENT ESTIMATED AIR FLOW IS 8,000 CFM. EF-4 SHALL BE CLEANED, REPAIRED AS

REQUIRED AND CURRENT AIRFLOW READINGS TAKEN TO VERIFY AVAILABLE AIR FLOW.

(DAYTON - MODEL 4YYH - S/N-11565624 0311 - .125" SP - 3/4 HP)

5. EXISTING CONTINUOUS RUN GENERAL EXHAUST FAN EF-5 FOR THE BOILER AREA

SHALL STAY IN-SERVICE. (TWIN CITY MODEL -120BE - APPROXIMATE CAPACITY 3,500)

NO VERIFICATION OF AIR FLOW IS REQUIRED.

6. EXISTING ROOF HATCH OPENING WITH LADDER UP FROM LEVEL-1.

7. EXISTING REFRIGERANT RELIEF PIPING SERVING CHILLER CH-1N SHALL REMAIN IN-

PLACE AND IN-SERVICE TO PROVIDE REFRIGERANT RELIEF FOR NEW CHILLER CH-1N.

8. EXISTING REFRIGERANT RELIEF PIPING SERVING CHILLER CH-2N SHALL REMAIN IN-

PLACE AND IN-SERVICE TO CONTINUE TO PROVIDE REFRIGERANT RELIEF FOR

EXISTING CHILLER CH-2N.

9. EXISTING EXHAUST STACKS FOR EXISTING HOT WATER BOILERS SHALL STAY IN-PLACE

AND IN-SERVICE.

10. EXISTING REFRIGERANT RELIEF PIPING SERVING CHILLER CH-3 SHALL REMAIN IN-

PLACE AND IN-SERVICE TO CONTINUE TO PROVIDE REFRIGERANT RELIEF FOR

EXISTING CHILLER CH-3.

SCALE: 1/4" = 1'-0"

MECHANICAL DUCT RENOVATION PLAN - ROOF - NORTH

NORTH PLANT

Rev Date Description

XZ

EXISTING CHILLER

CH-3

EXIST.

CHWP-3

EXIST.

CHWP-2

EXIST.

CHWP-1

EXISTING HOT WATER BOILERS

EXISTING HOT WATER

PUMPS

7'-7"

15'-7" x 8'-2" x 6"

15'-7" x 8'-2" x 6"

5'-0"

5'-6"

EDGE OF EXISTING

HOUSE KEEPING PAD

EDGE OF EXISTING

HOUSE KEEPING PAD

STARTER CABINET

HOUSEKEEPING PADS

FOR NEW CHILLERS

EXISTING CHILLER

MAIN DISCONNECT

CABINETS

CH-1 CH-2

CH-1

CH-2

EXISTING PIPE

TUNNEL

EXISTING PIPE

TUNNEL

CHILLERS WILL ENTER

NORTH PLANT THROUGH

EXISTING ROLL-UP DOOR.

EXIST.

HWP-1

CH-1

CH-2

Project Number

Date Issued

Issuance and Revisions

Sheet Title

Scale

Project Title

Drawn By Checked By

Sheet Number

Affiliated

Affiliated Engineers, Inc.

Twenty Greenway Plaza, Suite 410

Houston, Texas 77046

Tel 713.548.8900 Fax 713.548.9801

Engineers

TEXAS REGISTERED ENGINEERING FIRM F-8301

LAMAR NORTH AND

SOUTH PLANT CHILLER

REPLACEMENT

100% CONSTRUCTION

DOCUMENTS

03/19/2026

1/4" = 1'-0"

25174-02

03/19/2026

M204

XZRR

CHILLER

REPLACEMENT

PLAN- NORTH

PLANT

4400 S M L King Jr Pkwy, Beaumont, TX 77705

GENERAL NOTES

SCALE: 1/4" = 1'-0"

CHILLER PLACEMENT PLAN - NORTH PLANT

SHEET KEYED NOTES#

CHILLER PLACEMENT PLAN - NORTH PLANT (FOR REFERENCE)

THE CHILLER REPLACEMENT PROJECT FOR THE NORTH CENTRAL PLANT WILL INCLUDE THE REPLACEMENT OF EXISTING CHILLERS CH-1 AND CH-2 LOCATED IN THE FRONT SECTION OF THE NORTH

PLANT. EXISTING CHILLER CH-3, LOCATED IN THE REAR EQUIPMENT ROOM OF THE NORTH PLANT WILL REMAIN IN PLACE AND IN SERVICE. THE REPLACEMENT PROJECT WILL INCLUDE THE REPLACEMENT OF EXISTING CHILLERS CH-1 AND CH-2, ALONG WITH THE REPLACEMENT OF SELECTED BALANCE AND ISOLATION VALVES. SELECTED CONTROL DEVICES AS WELL AS MAGNETIC FLOW

METERS WILL ALSO BE INCLUDED IN THE REPLACEMENT

THE NEW CHILLERS WILL INCLUDE A MARINE WATER BOX ON THE CONDENSER BARREL FOR EACH CHILLER. SINCE NEW CHILLER CH-1 WILL HAVE THE CONDENSER ON THE LEFT SIDE OF THE CHILLER AND CH-2 WILL BE OPPOSITE HAND AND WILL HAVE THE CONDENSER WATER BOX ON THE RIGHT, IT WILL BE BENEFICIAL TO BRING CHILLER CH-2 INTO THE PLANT FIRST AND SET IT ON THE EXISTING SUPPORT PAD BEFORE CHILLER CH-1 IS BROUGHT IN. THE DEMOLITION AND INSTALLATION PROCESS WILL BE FAST-TRACKED TO ALLOW ALL FOUR CHILLERS TO BE INSTALLED AT ONE TIME. CHILLER CHILLERS CH-1 AND CH-2 WILL BE TWO PASS EVAPORATOR /CONDENSER MACHINES WITH A CONDENSER WATER-BOX WITH SIDE CONNECTIONS AND STACKED CHILLED WATER SUPPLY AND RETURN FLANGE CONNECTIONS ATTACHED TO THE END OF THE EVAPORATOR BARREL. ALL CONNECTIONS WILL BE ON THE SAME END WITH THE CONDENSER BARREL ON THE LEFT OR RIGHT WHEN FACING

THE MACHINE.

THE EXISTING CHILLERS WILL BE DISMANTLED AS REQUIRED,AND REMOVED THROUGH THE OVERHEAD DOOR IN THE SOUTH EXTERIOR WALL. THE NEW CHILLERS WILL BE BROUGHT INTO THE NORTH PLANT THROUGH THE OVERHEAD DOOR. ONCE INSIDE THE PLANT, THE CHILLER MUST BE ROTATED AND MOVED ONTO THE EXISTING SUPPORT PAD.

A. FOR THE CHILLER CH-1 AND CH-2 REPLACEMENT, ALL PIPING, VALVES, FITTINGS,

CONTROL DEVICES AND OTHER ACCESSORIES WILL BE REMOVED CAREFULLY AND SET

ASIDE AND STORED FOR POSSIBLE REUSE TO INSTALL THE NEW CHILLERS. THE GOAL

WILL BE TO REUSE AS MUCH OF THE EXISTING COMPONENTS AS POSSIBLE.

B. THE EXISTING CONCRETE HOUSE KEEPING PADS WILL BE REUSED TO SUPPORT

THE NEW CHILLERS. ONCE THE CHILLERS ARE REMOVED, THE CONTRACTOR SHALL

REPAIR THE SURFACE OF THE PADS TO PROVIDE A CLEAN MOUNTING SURFACE. DUE

TO THE SIZE OF THE SUPPORT PADS FOR THE NEW CARRIER CHILLERS, THE EXISTING

PADS CAN BE USED AS IS, BUT THE ENDS OF THE NEW CHILLERS MAY EXTEND PAST

THE END EDGES OF THE PADS. IF DESIRED, ADDITIONAL SECTIONS OF PAD CAN BE

ADDED.

C. PLACEMENT OF THE NEW CHILLER ON THE EXISTING PAD WILL BE FIELD

DETERMINED TO MINIMIZE PIPING REMOVAL AND REPLACEMENT WHILE MAINTAINING

MAXIMUM ACCESS SPACE AROUND THE CHILLERS.

NEW CHILLER ENTRY

POINT - SOUTH ROLL-UP

DOOR

NORTH PLANT

1. EXISTING HOUSEKEEPING PAD DIMENSIONS ARE FOR REFERENCE. CONTRACTOR

TO FIELD VERIFY BEFORE RIGGING.

NORTH PLANT

NEW CHILLER

CH-1S

EXISTING

CHILLER CH-3

EXISTING

CHWP-1

EXISTING

CHWP-2

EXISTING STARTER

CABINET-CH-1

EXISTING STARTER

CABINET-CH-2

NEW CHILLER

CH-1 MAIN

DISCONNECT

CABINET

NEW CHILLER

CH-2 MAIN

DISCONNECT

CABINET

EXISTING

CHWP-3

NEW CHILLERS WILL BE

BROUGHT INTO THE SOUTH

PLANT THROUGH THE

SOUTH OVERHEAD DOOR.

THE NEW CHILLERS WILL

NEED TO STAY CLOSE TO

THE WALL SO THAT THEY

WILL SQUEEZE THROUGH

THE SPACE BETWEEN

CHILLER CH-3 AND THE WALL

AS THE NEW CHILLERS MOVE

THROUGH THE SECOND DOOR

OPENING, THE CHILLERS WILL NEED

TO START ROTATING TO MISS THE

WALLS ON THE RIGHT SIDE.

AS THE NEW CHILLERS CONTINUE

TO MOVE NORTH IN THE PLANT, THE

CHILLERS WILL NEED TO CONTINUE

ROTATING TO MISS THE WALLS ON

THE RIGHT SIDE THAT ARE FARTHER

WEST THAT ARE FARTHER WEST

THAN THE SECOND WALL OPENING.

THE FIRST CHILLER TO BE SET WILL BE

CH-1 THAT WILL BE FARTHEST BACK. THE

EXISTING PADS WILL BE UTILIZED AND

SHOULD BE LARGE ENOUGH TO

SUPPORT THE NEW CHILLER FRAME.

THE SECOND CHILLER TO BE SET WILL

BE CH-2 THAT WILL BE CLOSER TO THE

FRONT. ONCE IT IS…

This is the start of the file's text. The full file is on GovTribe.