Electrical_Drawings_Daytona_Beach_Main_Street_Pier_Railings_Renovation_-_Revised_-_Signed.pdf

PDF 11 MB Posted

Attached to
2620ITB - Main Street Pier Repairs - 2026
Solicitation number
2620ITB
Issued by
Volusia County, Florida

About this file

This is a set of electrical drawings and specifications for the City of Daytona Beach's Main Street Pier Partial Boardwalk and Railing Replacement project (Project Number 2019-4115). The drawings, prepared by Alexander H. Parrish, P.E., and certified by GRAEF USA, detail comprehensive electrical demolition and renovation work for a waterfront pier structure. The project scope includes removal of existing lighting fixtures, conduit, and wiring; reinstallation of salvaged poles and fixtures; installation of new weather-resistant GFCI receptacles mounted in stainless steel enclosures on railing posts; and photometric analysis to verify lighting performance. The electrical work must comply with the Florida Building Code 8th Edition (2023), Florida Energy Conservation Code, Florida Fire Prevention Code, and the National Electrical Code 2020. All wiring shall be in conduit (minimum 3/4" unless otherwise noted) with solid copper #12 AWG minimum, grounding conductors in all circuits, and no shared neutral conductors. Materials specified include copper grounding conductors, copper-clad steel ground rods, Square D panelboards and circuit breakers, self-ventilated dry-type transformers, heavy-duty fused safety switches, and specification-grade receptacles from manufacturers such as Hubbell, Leviton, or Pass & Seymour.

The contractor is responsible for preparing and submitting all required construction permits and securing necessary licenses before starting work, with all fees paid by the contractor. A short circuit, coordination, and arc flash study must be performed by a third-party consultant and submitted for engineer approval prior to releasing electrical distribution equipment for manufacture. All work shall be guaranteed for a minimum of one year after final acceptance. The contractor must provide temporary service in construction areas, coordinate with mechanical and other trades, maintain fire alarm protection throughout construction phases, and document all existing conditions prior to demolition. Lighting photometric calculations for the pier boardwalk specify an average of 1.8 footcandles with a maximum of 3.9 and minimum of 0.1 footcandles, with post-installation photometric measurement and analysis required to verify design compliance. The contractor must include costs for training a minimum of eight hours of owner instruction by a factory-certified lighting control product representative. No pricing information, contract award dates, or response deadlines are detailed in the electrical drawings themselves; these details would be found in the associated solicitation documents for the Main Street Pier Repairs project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AS NOTED

A

B

C

1 2 3 4 5

2019-4115

10/14/2025

AHP

AHP

MSA

A

B

C

1 2 3 4 5

Al ex an de r H . P ar ris h

PE

2AL

EX

ANDER H . PARR ISH

PROFESS I ONA L ENG I N

EE

R

L I CENSE

F L O R I D A

STATE OF

No. 87322

This item has been electronic signed and sealed by Alexander H. Parrish on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

CITY OF DAYTONA BEACH

MAIN STREET PIER

PARTIAL BOARDWALK AND

RAILING REPLACEMENT

SEAL:

DRAWN BY:

APPROVED BY:

SCALE:

CHECKED BY:

DATE:

PROJECT NUMBER:

PROJECT TITLE:

ISSUE:

PROJECT INFORMATION:

SHEET TITLE:

SHEET NUMBER:

www.graef-usa.com

2300 Maitland Center Parkway, Suite 210 Maitland, FL 32751 407 / 659 6500

CERT # 4270

PERMIT SET

1P 2P 3P 4P 1P, 1W 1P, 2W 2P, 2W 2P, 3W 3P, 2W 3P, 3W 3P, 4W 4P, 4W A

AC

AF

AFF

AFG

AIC

ANSI

AL

AS

AT

ARCH

ATS

A / V

AWG

B

BF

BFF

BFG

BLDG

C

CAM

CAT

CATV

CB

CKT

CLG

CO

CT

CU

CL

DC

DR

DISC

DW

DWG

E

EC

EMT

ETR

ER

ERL

ERLD

EWC

EX

FA

FLA

FO

FPC

GC

GFCI

GFPE

GND

GRC

HH

HP

HVAC

HZ

ISP

IT

JB

KVA

KW

LP

LS

LTG

LV

MC

MCA

MCC

MDP

MH

MISC

MLO

MTD

MTG

MTS

MW

MV

N / A

NC

NEC

NIC

NO

NTS

OSP

P

PB

PC

PH

PNL

PP

PR

PRI

PROJ

PVC

REC

RE / CKT

REF

RSC

SC

SEC

SN

SP

SS

ST

STP

SUSP

SW

SWBD

T

TBB

TC

TCI

TELE / DATA

TEL

TELECOM

TGB

TMGB

TP

TYP

UG

UTP

UOI

V

W

WA

WAP

WP

XFMR

XR

XV

Y

ZAM

- KILOWATT

- LIGHTING PANEL

- LIMIT SWITCH

- LIGHTING

- LOW VOLTAGE

- MECHANICAL CONTRACTOR

- MINIMUM CIRCUIT AMPS

- MOTOR CONTROL CENTER

- MAIN DISTRIBUTION PANEL

- MANHOLE

- MISCELLANEOUS

- MAIN LUGS ONLY

- MOUNTED

- MOUNTING

- MANUAL TRANSFER SWITCH

- MICROWAVE

- MEDIUM VOLTAGE

- NOT APPLICABLE

- NORMALLY CLOSED

- NATIONAL ELECTRIC CODE

- NOT IN CONTRACT

- NORMALLY OPEN

- NUMBER

- NOT TO SCALE

- OUTSIDE PLANT

- POLE

- PULL BOX

- PLUMBING SYSTEM CONTRACTOR

- PHASE

- PANEL OR PANELBOARD

- POWER PANEL

- PAIR

- PRIMARY

- PROJECTOR

- POLYVINYL CHLORIDE

- RECESSED

- REUSE EXISTING CIRCUIT

- REFRIGERATOR

- RIGID STEEL CONDUIT

- SECURITY CONTRACTOR

- SECONDARY

- SOLID NEUTRAL

- SPARE

- STAINLESS STEEL

- SHUNT TRIP

- SHIELDED TWISTED PAIR

- SUSPENDED

- SWITCH

- SWITCHBOARD

- TAMPER RESISTANT SAFETY RECEPTACLE

- TELECOMMUNICATIONS BONDING BACKBONE

- TELEPHONE CABINET

- TELECOMMUNICATIONS CABLING INSTALLER

- TELEPHONE / DATA

- TELEPHONE

- TELECOMMUNICATIONS

- TELECOMMUNICATIONS GROUNDING BUSBAR

- TWISTED PAIR

- TYPICAL

- UNDERGROUND

- UNSHIELDED TWISTED PAIR

- UNLESS OTHERWISE INDICATED

- VOLT

- WATT

- WASHER

- WIRELESS ACCESS POINT

- WEATHERPROOF

- TRANSFORMER

- XRAY

- XRAY VIEWER

- WYE

- ZONE ADAPTER MODULE

- ONE POLE

- TWO POLE

- THREE POLE

- FOUR POLE

- ONE POLE, ONE WIRE

- ONE POLE, TWO WIRE

- TWO POLE, TWO WIRE

- TWO POLE, THREE WIRE

- THREE POLE, TWO WIRE

- THREE POLE, THREE WIRE

- THREE POLE, FOUR WIRE

- FOUR POLE, FOUR WIRE

- AMPERE

- ALTERNATING CURRENT

- AMPERE FRAME

- ABOVE FINISHED FLOOR

- ABOVE FINISHED GRADE

- AMPERE INTERRUPTING CAPACITY

- AMERICAN NATIONAL STANDARDS INSTITUTE

- ALUMINUM

- AMP SWITCH

- AMP TRIP

- ARCHITECT

- AUTOMATIC TRANSFER SWITCH

- AUDIO VISUAL

- AMERICAN WIRE GRADE

- PEDESTAL MOUNTED ON BENCH TOP

- BELOW FLOOR

- BELOW FINISHED FLOOR

- BELOW FINISHED GRADE

- BUILDING

- CONDUIT

- CAMERA

- CATALOG

- CABLE TELEVISION

- CIRCUIT BREAKER

- CIRCUIT

- CEILING MOUNTED

- COPIER

- CURRENT TRANSFORMER

- COPPER

- CENTERLINE

- DIRECT CURRENT

- DRYER

- DELTA

- DISCONNECT

- DISHWASHER

- DRAWING

- EMERGENCY

- ELECTRICAL CONTRACTOR

- ELECTRIC METALLIC TUBING

- EXISTING TO REMAIN

- EQUIPMENT ROOM

- EXISTING TO BE RELOCATED

- RELOCATED EQUIPMENT'S NEW LOCATION

- ELECTRIC WATER COOLER

- EXISTING

- FIRE ALARM

- FULL LOAD AMPS

- FIBER OPTIC

- FIRE PROTECTION CONTRACTOR

- GENERAL CONTRACTOR

- GROUND FAULT CIRCUIT INTERRUPTER

- GROUND FAULT PROTECTION EQUIPMENT

- GROUND

- GALVANIZED RIGID CONDUIT

- HANDHOLE

- HORSEPOWER

- HEATING, VENTILATING, AND AIR CONDITIONING

- HERTZ (CYCLE) PER SECOND

- INSIDE PLANT

- INFORMATION TECHNOLOGY

- JUNCTION BOX

- KILOVOLT AMPERE

ELECTRICAL ABBREVIATIONS

XXX

X DETAIL REFERENCE

- TOP DESIGNATES DETAIL NUMBER

- BOTTOM DESIGNATES SHEET NUMBER

GENERAL SYMBOLS

ELECTRICAL SYMBOLS AND ABBREVIATIONS

NOTE: NOT ALL SYMBOLS AND ABBREVIATIONS INDICATED HERE ARE USED IN DRAWINGS AND MAY NOT APPLY TO CURRENT PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED ON DRAWINGS.

GENERAL NOTE

THIS IS A STANDARD LEGEND. SOME SYMBOLS

MAY NOT APPEAR IN THE DRAWINGS.

NOTES/SPECS

THERE ARE ADDITIONAL NOTES AND SPECIFICATIONS FOUND ON

SUBSEQUENT SHEETS. EXCEPT FOR GENERAL SHEET NOTES AND

KEYED NOTES (E.G. PLAN KEY NOTES), THE NOTES AND

SPECIFICATIONS HERE SHALL APPLY TO ALL SHEETS.

FBCEC COMMISSIONING REQUIREMENTS

X

X

LIGHTING CONTROL

RELAY CABINET/

LIGHTING CONTROL CABINET

- (X) INDIXATES DESIGNATION

PHOTOCELL

OCCUPANCY SENSOR

- CEILING MOUNTED

- (X) INDICATES TYPE

(SEE SCHEDULE)

SWITCH STATION

- LOW VOLTAGE

- (X) INDICATES STATION

IDENTIFIER

SWITCH

- MOUNTED 3'-8" AFF, UON

- (a) INDICATES SWITCH

DESIGNATION

- SINGLE POLE, UON

- (X) INDICATES SWITCH TYPE:

(2) TWO POLE

(3) THREE WAY

(4) FOUR WAY

(DLS) DUAL LEVEL

(K) KEY OPERATED

(P) WITH PILOT LIGHT

(T) TIMER

L

AA

LIGHTING FIXTURE DESIGNATIONS

PARTIAL SHADING INDICATES FIXTURE

PARTIALLY WIRED TO EMERGENCY

OR NIGHT LIGHTING CIRCUIT

LIGHT FIXTURE DESIGNATION

WALL MOUNTED EXIT LIGHT

FIXTURE

- SHADING INDICATES FACE(S)

- ARROW(S) AND FACE(S) AS

INDICATED ON DRAWINGS

LIGHTING FIXTURES

STRIP LIGHT OR UNDER CABINET LIGHT

WALL MOUNTED

SURFACE/RECESSED

MOUNTED

EMERGENCY BATTERY DUAL

REMOTE HEAD

EMERGENCY BATTERY SINGLE

REMOTE HEAD

EMERGENCY BATTERY UNIT

MOUNT AT 8' - 0" AFF UON

RECESS MOUNTED ACCENT

- CHEVRON INDICATES DIRECTION OF

ILLUMINATION

SURFACE MOUNTED ACCENT

- CHEVRON INDICATES DIRECTION OF

ILLUMINATION

LIGHTING TRACK

- LENGTH AS INDICATED ON DRAWINGS

- NUMBER AND DIRECTION OF FIXTURES

AS INDICATED ON DRAWINGS AND / OR

SCHEDULE

CEILING MOUNTED EXIT LIGHT

FIXTURE

- SHADING INDICATES FACE(S)

- ARROW(S) AND FACE(S) AS

INDICATED ON DRAWINGS

SUSPENDED, PENDENT, CHAIN,

STEM, OR CABLE HUNG

Y

X

X

X

X

X

WIRING DEVICES

DUPLEX RECEPTACLE

- MOUNTED 1'-6" AFF, UOI

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

- (Y) INDICATES TYPE:

(WP) WEATHERPROOF

(WR) WEATHER RESISTANT MOTOR CONNECTION

- (X) INDICATES:

PANEL NAME

BREAKER SIZE/# OF POLES

- (Y) INDICATES:

MOTOR DESIGNATION

LOAD SIZE

VOLTAGE / PHASE

SPECIAL PURPOSE OUTLET

- (X) INDICATES:

PANEL NAME

BREAKER SIZE/# OF POLES

- (Y) INDICATES:

SPO DESIGNATION

LOAD SIZE

VOLTAGE / PHASE

DUPLEX RECEPTACLE

- MOUNTED FLUSH IN CEILING

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

DUPLEX RECEPTACLE

- MOUNTED FLUSH IN

COUNTERTOP

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

DUPLEX RECEPTACLE

- TOP HALF SWITCHED

- MOUNTED 1'-6" AFF, UOI

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

DUPLEX RECEPTACLE MOUNTED 6"

ABOVE COUNTER BACKSPLASH, UOI

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

TV / POWER OUTLET BOX 6' - 8"

AFF UNLESS NOTED OTHERWISE.

TV

X

Y

Y

X

EQUIPMENT AND PANELBOARDS

METER

CURRENT TRANSFORMER

CABINET

TRANSFORMER

- (X) INDICATES

DESIGNATION

BRANCH PANELBOARD DISTRIBUTION PANELBOARD

- (X) INDICATES

DESIGNATION

CT

ELECTRICAL BOX

- FLOOR MOUNTED

- POKE THRU

- OUTLET TYPES REQUIRED

AT EACH BOX AS INDICATED

ON DRAWINGS

JUNCTION BOX:

FLOOR MOUNTED

PULL BOX

HANDHOLE

MANHOLE

RACEWAYS AND BOXES

CABLE TAP BOX

MULTI-OUTLET RACEWAY

ASSEMBLY

- WALL MOUNTED 1'-6"

AFF, UOI

ELECTRICAL BOX

- FLOOR MOUNTED

- FLUSH

- OUTLET TYPES REQUIRED AT

EACH BOX AS INDICATED ON

DRAWINGS

BUSWAY

- RATING AND TYPE AS

INDICATED ON DRAWINGS

F

P

CTB

PB

HH

DUPLEX RECEPTACLE

(GFCI) GROUND FAULT

CIRCUIT INTERRUPTING

QUAD RECEPTACLE

- MOUNTED 1'-6" AFF, UOI

DUPLEX RECEPTACLE

- CONTROLLED VIA OCC. SENSOR

- MOUNTED 1'-6" AFF, UOI

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

X

QUAD RECEPTACLE

(GFCI) GROUND FAULT

CIRCUIT INTERRUPTING

QUAD RECEPTACLE MOUNTED 6"

ABOVE COUNTER BACKSPLASH, UOI

X

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

DUPLEX RECEPTACLE MOUNTED 6"

ABOVE COUNTER BACKSPLASH, UOI

(GFCI) GROUND FAULT

CIRCUIT INTERRUPTING

QUAD RECEPTACLE MOUNTED 6"

ABOVE COUNTER BACKSPLASH, UOI

(GFCI) GROUND FAULT

CIRCUIT INTERRUPTING

X

DUPLEX RECEPTACLE

- FLOOR MOUNTED

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

X

QUAD RECEPTACLE

- FLOOR MOUNTED

- (X) INDICATES CIRCUIT NUMBER

(PANEL BOUNDARY AS

INDICATED ON DRAWINGS)

JUNCTION BOX:

CEILING MOUNTED

JUNCTION BOX: WALL

MOUNTED

POWER PACK

LOW VOLTAGE

SWITCH

- MOUNTED 3'-8" AFF, UON

- (#) INDICATES BUTTONS

WALL OCCUPANCY

SENSOR SWITCH

- MOUNTED 3'-8" AFF, UON

EMERGENCY CONTROLLED

POWER PACK UL 924

PLUG LOAD CONTROL

POWER PACK

E-001 ELEC. SYMBOL LEGEND, NOTES, ABBREV., FIXT. SCHED., & DWG. INDEX

E-002 ELECTRICAL SPECIFICATIONS

E-100 OVERALL SITE PLAN

E-101 LIGHTING DEMOLITION PLAN

E-102 POWER DEMOLITION PLAN

E-201 LIGHTING RENOVATION PLAN

E-202 LIGHTING PHOTOMETRICS PLAN

E-301 POWER RENOVATION PLAN

E-601 ELECTRICAL DETAILS & SCHEDULES

E-602 ELECTRICAL FIXTURE DETAILS

SHEET DESCRIPTION

ELECTRICAL DRAWING INDEX

MAIN GROUND BAR

- 120/208 V

BRANCH PANELBOARD

- SURFACE MOUNTED

- (X) INDICATES

DESIGNATION

- 277/480 V

- SURFACE MOUNTED

- (X) INDICATES

DESIGNATION

X

X

X

POLE MOUNTED WITH ARM

WALL MOUNTED EMERGENCYEXIT

LIGHT COMBO

- SHADING INDICATES FACE(S)

- ARROW(S) AND FACE(S) AS

INDICATED ON DRAWINGS

(USB) USB PORT

XX-##,a

INDICATES FIXTURE TYPE

PANEL

DESIGNATION

CIRCUIT DESIGNATION

INDICATES CONTROL

DESIGNATION (IF AVAILABLE)

NL

INDICATES UNSWITCHED

NIGHT LIGHTING

VACANCY SENSOR

- CEILING MOUNTED

- (X) INDICATES TYPE

(SEE SCHEDULE)

- (a) INDICATES SWITCH

LEG (IF APPLICABLE)

a

POST TOP

ATS AUTOMATIC TRANSFER SWITCH

X

TELECOMMUNICATIONS MAIN GROUND BAR

MGB - MAIN GROUNDING BUSBAR

KVAR - KILOVOLT AMPERE REACTIVE

MOCP - MAIN OVER-CURRENT PROTECTION

1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A COMPLETE AND WORKABLE FACILITY.

2. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY BE REQUIRED FOR PROPER INSTALLATION OF THE WORK. SUCH WORK SHALL BE VERIFIED AT THE SITE. ADDITIONAL BENDS, OFFSETS, AND CONDUIT AS REQUIRED BY VERTICAL AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS, SHALL BE PROVIDED TO COMPLETE THE WORK AT NO ADDITIONAL COST

TO THE OWNER.

3. ALL WORK SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS:

3.1. FLORIDA BUILDING CODE 8TH EDITION - 2023.

3.2. FLORIDA ENERGY CONSERVATION CODE 8TH EDITION - 2023.

3.3. FLORIDA FIRE PREVENTION CODE 8TH EDITION - 2023.

3.4. NATIONAL ELECTRICAL CODE - NFPA 70 2020.

4. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC.

5. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON CURRENT CARRYING METALLIC PARTS OF ELECTRICAL

EQUIPMENT, METALLIC RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN METALLIC RACEWAYS.

6. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO ENCLOSURES, BOXES, AND EQUIPMENT WHERE

CONCENTRIC OR ECCENTRIC KNOCKOUTS ARE USED.

7. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN THIS TYPE OF WORK. THE INSTALLATION

SHALL BE MADE SO THAT THERE IS NO DEGRADATION OF THE DESIGNED FIRE RATINGS.

8. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND AT SUCH A TIME AS WILL REQUIRE A MINIMUM

OF CUTTING AND PATCHING OF THE BUILDING STRUCTURE.

9. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT EXISTING UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF THE UTILITIES OR OTHER PROPERTY

DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK.

10. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND BONDING CONNECTIONS SHALL BE SILICON

BRONZE. CONTRACTOR SHALL UTILIZE CONNECTORS TO PREVENT GALVANIC ACTION.

11. ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO MECHANICAL DAMAGE SHALL BE RIGID GALVANIZED STEEL, UNLESS NOTED OTHERWISE. ALL OTHER CONDUIT INSIDE FACILITY SHALL BE ELECTRICAL METAL TUBE (EMT).

CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR STRAPS TO PROVIDE A RIGID INSTALLATION.

12. CONDUIT SUPPORTS SHALL NOT BE FASTENED OR ATTACHED TO OTHER PIPES. PERFORATED STRAP HANGERS WILL NOT BE ALLOWED. EMPTY CONDUIT SHALL BE THOROUGHLY SWABBED OUT WITH DRY SWAB TO REMOVE MOISTURE AND DEBRIS BEFORE WIRE IS DRAWN IN. END OF CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL WIRE IS PULLED. NO CONDUIT SHALL BE LOCATED TO IMPAIR THE STRENGTH OF STRUCTURAL MEMBERS. MAKE CHANGES IN DIRECTION OF RUNS WITH SYMMETRICAL BENDS. DO NOT INSTALL CRUSHED OR DEFORMED CONDUITS. AVOID TRAPPED CONDUITS. PREVENT PLASTER, DIRT, OR TRASH FROM LODGING IN CONDUIT, BOXES, FITTINGS. FREE

CLOGGED CONDUITS OF OBSTRUCTIONS.

13. TRACE AND CONFIRM BRANCH CIRCUIT WIRE SIZE AND CIRCUIT BREAKER FEEDING EQUIPMENT AFFECTED BY THE

SCOPE OF WORK.

14. ALL WORK SHALL COMPLY WITH CODES AND STANDARDS LISTED IN THE CONTRACT DOCUMENTS.

15. THE DRAWINGS ARE DIAGRAMMATIC AND THE OMISSION OF AN ITEM NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING THAT ITEM.

16. NOTIFY ARCHITECT/ENGINEER OF ANY CONFLICTS PRIOR TO PURCHASING EQUIPMENT AND PRIOR TO CUTTING

OPENING.

17. PRIOR TO BID, COORDINATE ALL ELECTRICAL WORK WITH MECHANICAL WORK AND OTHER TRADES. SEE

SPECIFICATIONS FOR REQUIREMENTS.

18. CONTRACTOR SHALL NOT CONCEAL ANY WORK UNTIL INSPECTED BY ELECTRICAL INSPECTOR AND/OR ENGINEER.

CONTRACTOR SHALL NOTIFY ENGINEER OF A SCHEDULED INSPECTION TIME WITHIN 72 HOURS. CONTRACTORS

SHALL NOT CONCEAL WORK UNTIL APPROVED.

19. WHERE CROWDED LOCATIONS EXIST OR WHERE THERE IS A POSSIBILITY OF CONFLICT BETWEEN TRADES, CONTRACTOR SHALL MAKE COMPOSITE DRAWINGS SHOWING THE EXACT LOCATION OF DUCTS, CONDUIT AND EQUIPMENT. DRAWINGS SHALL BE BASED ON FIELD MEASUREMENTS AND, AFTER CONSULTATION AND AGREEMENT BETWEEN THE TRADES, SHALL BE APPROVED BY THE ENGINEER BEFORE INSTALLATION OF THE WORK.

20. ALL BARE METAL SURFACES SHALL BE PRIMED AND PAINTED TO PREVENT ANY RUST, INCLUDING BUT NOT LIMITED

TO ANGLE FRAMING, EQUIPMENT SUPPORTS, MOUNTING HARDWARE, ETC.

21. ALL RACEWAYS SHALL HAVE A GREEN GROUNDING CONDUCTOR.

22. CONTRACTOR SHALL FIRESTOP ALL NEW AND EXISTING (WHERE APPLICABLE) ELECTRICAL PENETRATIONS IN FIRE RATED PARTITIONS (WALLS, FLOORS OR CEILINGS) WITH AN APPROVED FIRESTOP SYSTEM RATED FOR THE APPLICATION. FIRESTOP SYSTEM SHALL BE UL LISTED AND INSTALLED IN STRICT COMPLIANCE WITH THE

MANUFACTURER'S INSTRUCTIONS.

23. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDINGS AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL EFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED, AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF

DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.

24. CAREFULLY REVIEW MECHANICAL DRAWINGS TO IDENTIFY PROPOSED ROUTING OF HVAC WORK. THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BID. THE RELOCATION OF ALL EXISTING ELECTRICAL CONDUITS, WIRING, AND BOXES AS REQUIRED TO ACCOMMODATE THE INSTALLATION OF HVAC WORK AND FIELD CONDITIONS. WHERE THE SPACE THROUGH WHICH HVAC WORK IS TO BE INSTALLED CONTAINS EXISTING CONDUIT, WIRE AND/OR BOXES THE EC SHALL RELOCATE BY INTERCEPTING AND EXTENDING THE EXISTING CONDUIT AND WIRE, AND RELOCATING JUNCTION BOXES SO THE REQUIRED NEC ACCESS AND CLEARANCE IS PROVIDED AFTER THE HVAC WORK HAS

BEEN INSTALLED.

25. THE EXISTING CONDUIT SYSTEM MAY BE RETAINED FOR WORK SHOWN ON THESE DRAWINGS. WHERE EXISTING CONDUIT IS REUSED, IT'S MATERIALS AND METHODS OF INSTALLATION WHEN THE PROJECT IS COMPLETE, SHALL CONFORM TO THE SPECIFICATIONS AS IF IT WERE NEW. ALL COUPLINGS AND CONDUCTORS SHALL BE TIGHTENED.

26. ALL DEBRIS SHALL BE REMOVED FROM THE SITE DAILY TO AN APPROVED DUMPING FACILITY WHICH MEETS FEDERAL AND LOCAL REQUIREMENTS. NO BURNING ON SITE WILL BE ALLOWED. OWNER'S DUMPSTERS SHALL NOT

BE USED.

27. WHERE CUTTING CORING OR REMOVAL OF CONDUITS, BOXES OR ANY ELECTRICAL ITEM IS REQUIRED, THE FINISHED SURFACE SHALL BE PATCHED AND PAINTED SO THAT NO EVIDENCE OF THE FORMER INSTALLATION

REMAINS.

28. THE OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL ELECTRICAL EQUIPMENT AND DEVICES INDICATED ON THE CONTRACT DOCUMENTS TO BE REMOVED. ALL ITEMS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE

JOB SITE BY THIS CONTRACTOR AND PROPERLY DISPOSED OF.

29. ALL RACEWAY TERMINATION'S SHALL HAVE BUSHINGS AND BE GROUNDED WHERE RACEWAY IS METAL.

30. COORDINATE ALL MECHANICAL LOADS, VOLTAGES AND LOCATIONS WITH MECHANICAL CONTRACTOR.

31. ALL POWER AND FIRE ALARM WIRING SHALL BE CONCEALED WHERE PRACTICAL. SURFACE MOUNTED RACEWAY SHALL BE WIREMOLD (OR EQUIVALENT) METALLIC SURFACE RACEWAY. CONTRACTOR SHALL PROVIDE AND INSTALL ALL RACEWAY, BOXES, AND FITTINGS REQUIRED FOR A COMPLETE INSTALLATION. CABLING IN NON-PUBLIC AREAS

MAY BE IN EMT.

32. ELECTRICAL OUTLETS OR BOXES SHALL NOT REDUCE THE FIRE-RESISTANT RATING OF FIRE RESISTANT RATED

WALL(S), AND SHALL COMPLY WITH 714.4, FBC 2023 REQUIREMENTS.

33. GFCI WEATHER PROOF RECEPTACLES SHALL HAVE ENCLOSURE THAT IS WEATHER PROOF WHILE IN USE.

34. COORDINATE WITH THE GENERAL CONTRACTOR SO THAT OCCUPIED BUILDINGS OR PORTIONS OF BUILDINGS ARE

NEVER WITHOUT FIRE ALARM PROTECTION THROUGHOUT ALL PHASES OF CONSTRUCTION.

35. ALL WORK SHALL BE CONSTRUCTED TO MEET THE PHASING REQUIREMENTS OF THE PROJECT AS OUTLINED IN THE

DRAWINGS, SPECIFICATIONS AND PER DIVISION 1 OF THE SPECIFICATIONS.

36. PRIOR TO BID, CHECK LEAD TIMES OF ALL EQUIPMENT IN THE PROJECT. IF NECESSARY TO MEET THE PROJECT SCHEDULE, BID SHALL INCLUDE THE COST OF QUICK SHIP PREMIUMS. ALLOW TIME FOR NORMAL SHOP DRAWING

PREPARATION AND REVIEW.

37. VERIFY MOUNTING HEIGHTS OF ALL DEVICES PRIOR TO INSTALLATION. MOUNTING HEIGHTS NOT SHOWN ON THESE

PLANS.

38. COLOR CODING:

A. BRANCH CIRCUIT AND FEEDERS:

280Y/120 VOLTS 480Y/277 VOLTS

PHASE A BLACK BROWN

PHASE B RED ORANGE

PHASE C BLUE YELLOW

NEUTRAL WHITE GRAY

GROUND GREEN GREEN

B. THE ABOVE COLORS SHALL BE USED UNLESS REQUIREMENTS OF CODE REQUIRE DIFFERENT COLORS.

VOLTAGE DROP

VOLTAGE DROP IN ACCORDANCE WITH FLORIDA BUILDING CODE

8TH EDITION (2023) ENERGY CONSERVATION CODE CHAPTER 4,

SECTION C405.5.3 WAS TAKEN INTO ACCOUNT FOR THIS PROJECT.

E-001

ELEC. SYMBOL LEGEND, NOTES,

ABBREV., FIXT. SCHED., & DWG.

INDEX

VIF - VERIFY IN FIELD

1 FWC RESPONSE 03/26/26

B

C

1 2 3 4 5

2019-4115

10/14/2025

AHP

AHP

MSA

A

B

C

1 2 3 4 5

Al ex an de r H . P ar ris h

PE

2AL

EX

ANDER H . PARR ISH

PROFESS I ONA L ENG I N

EE

R

L I CENSE

F L O R I D A

STATE OF

No. 87322

This item has been electronic signed and sealed by Alexander H. Parrish on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

CITY OF DAYTONA BEACH

MAIN STREET PIER

PARTIAL BOARDWALK AND

RAILING REPLACEMENT

SEAL:

DRAWN BY:

APPROVED BY:

SCALE:

CHECKED BY:

DATE:

PROJECT NUMBER:

PROJECT TITLE:

ISSUE:

PROJECT INFORMATION:

SHEET TITLE:

SHEET NUMBER:

www.graef-usa.com

2300 Maitland Center Parkway, Suite 210 Maitland, FL 32751 407 / 659 6500

CERT # 4270

PERMIT SET

GENERAL ELECTRICAL PROVISIONS

WORK INCLUDED IN CONTRACT

MENTION OF ANY ARTICLE, OPERATION OR METHOD REQUIRES THAT CONTRACTOR SHALL

PROVIDE SAME AND PERFORM EACH OPERATION IN COMPLETE ACCORDANCE WITH

CONDITIONS STATED. CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, EQUIPMENT,

AND TRANSPORTATION AS NECESSARY TO COMPLETE PROJECT IN COMPLIANCE WITH

CONTRACT DOCUMENTS. IN GENERAL, WORK INCLUDES EVERYTHING ESSENTIAL FOR

COMPLETE ELECTRICAL SYSTEM IN OPERATING ORDER AS SHOWN ON DRAWINGS AND

INDICATED IN SPECIFICATIONS.

ALL MATERIALS SHALL BE SUITABLY STORED AND PROTECTED PRIOR TO INSTALLATION AND

ALL WORK SHALL BE PROTECTED AFTER INSTALLATION, DURING CONSTRUCTION, AND PRIOR

TO ACCEPTANCE.

SHALL ANY CONFLICTS OCCUR WITHIN OR BETWEEN SPECIFICATIONS, DRAWINGS, OR OTHER

DOCUMENTS, CONTRACTOR SHALL INCLUDE THE MORE EXPENSIVE ALTERNATIVE.

BIDDING PROCEDURES

BASE BID SHALL INCLUDE ALL LABOR, MATERIALS AND EQUIPMENT AS SHOWN ON

CONSTRUCTION DRAWINGS AND AS REQUIRED AND SPECIFIED.

BASE BID SHALL NOT INCLUDE ANY CONDITIONS OR QUALIFYING STATEMENTS, SHALL BE IN

STRICT ACCORDANCE WITH SPECIFICATION REQUIREMENTS AND SHALL BE BASED UPON

INSTALLATION OF MATERIALS AND EQUIPMENT AS SPECIFIED.

PERMITS AND LICENSES

CONTRACTOR SHALL PREPARE AND SUBMIT REQUIRED APPLICATIONS AND DRAWINGS FOR

ALL CONSTRUCTION PERMITS AND APPROVALS TO AUTHORITIES HAVING JURISDICTION OVER

PROJECT. ALL LICENSES AND PERMITS REQUIRED SHALL BE SECURED AND PAID FOR BY

CONTRACTOR AND SHALL BE SECURED BY THE CONTRACTOR BEFORE STARTING WORK.

SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY

ELECTRICAL CONTACTOR SHALL RETAIN THE SERVICES OF A THIRD PARTY TO PERFORM A

SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY FOR THE PROJECT.

ELECTRICAL CONTRACTOR SHALL PROVIDE THE THIRD PARTY WITH ALL NECESSARY

INFORMATION TO COMPLETE THE STUDY.

STUDY SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL

CONTRACTOR SHALL NOT RELEASE ANY ELECTRICAL DISTRIBUTION EQUIPMENT FOR

MANUFACTURE BEFORE THE STUDY HAS BEEN SUBMITTED, REVIEWED, AND APPROVED.

STANDARDS AND CODES

WORK SHALL BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE, AND LOCAL CODES,

ORDINANCES, LAWS, AND REGULATIONS. COMPLY WITH ALL APPLICABLE OSHA

REGULATIONS.

MATERIALS SHALL HAVE UL OR ETL LABEL WHERE UL OR ETL STANDARD AND / OR TEST

EXISTS.

ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH RECOGNIZED INDUSTRY

STANDARDS AND SHALL FOLLOW EQUIPMENT MANUACTURER'S PUBLISHED INSTRUCTIONS.

MATERIALS AND EQUIPMENT

MATERIALS AND EQUIPMENT REQUIRED SHALL BE NEW, UNLESS OTHERWISE INDICATED.

EQUIPMENT SUPPLIED SHALL BE BASED ON MATERIALS AND EQUIPMENT OF

MANUFACTURERS SPECIFIED. APPROVED EQUALS WILL BE ALLOWED.

SUBMITTALS

THE FOLLOWING EQUIPMENT SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY THE

ENGINEER:

1. SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY

2. ELECTRICAL SERVICE AND DISTRIBUTION EQUIPMENT.

3. ELECTRICAL OUTLETS.

4. LIGHTING CONTROL DEVICES

5. LIGHTING FIXTURES

6. STRUCTURED CABLING

CLEANING AND PAINTING

RUBBISH RESULTING FROM WORK SHALL BE REMOVED AND DISPOSED OF ON DAILY BASIS IN

SUCH MANNER AS TO BE ACCEPTABLE TO OWNER.

CONTRACTOR SHALL CLEAN ALL EXPOSED IRON WORK, INTERIOR AND EXTERIOR OF

CABINETS AND PULL BOXES, ETC.

WHERE PAINTED SURFACES OF EQUIPMENT HAVE BEEN DAMAGED OR RUSTED DURING

CONSTRUCTION, CONTRACTOR SHALL PAINT SAME TO MATCH FINAL.

TESTS AND ACCEPTANCE

OPERATION OF EQUIPMENT AND ELECTRICAL SYSTEMS DOES NOT CONSTITUTE

ACCEPTANCE OF WORK BY OWNER. FINAL ACCEPTANCE IS TO BE MADE AFTER CONTRACTOR

HAS ADJUSTED HIS EQUIPMENT AND DEMONSTRATED THAT IT FULFILLS REQUIREMENTS OF

DRAWINGS AND SPECIFICATIONS.

UPON COMPLETION OF INSTALLATION, CONTRACTOR SHALL FURNISH CERTIFICATES OF

APPROVAL AND OCCUPANCY PERMITS FROM AUTHORITIES HAVING JURISDICTION.

CONTRACTOR SHALL DEMONSTRATE THAT ALL WORK IS COMPLETE AND IN PERFECT

OPERATING CONDITION, WITH RACEWAY AND CONDUIT SYSTEM PROPERLY GROUNDED,

WIRING FREE FROM GROUNDS AND SHORTS, AND ENTIRE INSTALLATION IS FREE FROM ANY

PHYSICAL DEFECTS.

IN PRESENCE OF ENGINEER AND OWNER, CONTRACTOR SHALL DEMONSTRATE PROPER

OPERATION OF ALL SYSTEMS.

UNLESS OTHERWISE INDICATED, ALL WORK SHALL BE GUARANTEED FOR A MINIMUM OF ONE

(1) YEAR AFTER DATE OF FINAL ACCEPTANCE.

DEFINITIONS

1. A/E - ARCHITECT AND / OR ENGINEER.

2. PROVIDE - FURNISHED, INSTALLED, AND COMPLETELY WIRED AND CONNECTED BY

ELECTRICAL CONTRACTOR.

3. NEC - NATIONAL ELECTRICAL CODE.

4. CONTRACTOR - PERSON OR GROUP RESPONSIBLE FOR PROJECT CONSTRUCTION.

ELECTRICAL SERVICE AND DISTRIBUTION

PRODUCTS

NEW PANELBOARDS SHALL BE PROVIDED AS FOLLOWS:

1. POWER PANELS - SQUARE D I-LINE STYLE.

2. 480Y/277 VOLT LIGHTING PANELS - SQUARE D NF STYLE PANELBOARDS WITH

BOLT-ON BREAKERS.

3. 208Y/120 VOLT LIGHTING PANELS - SQUARE D NQ STYLE PANELBOARDS WITH

BOLT-ON BREAKERS.

PROVIDE NEW DISTRIBUTION / BRANCH PANELS COMPLETE WITH CIRCUIT BREAKERS AND AIC

RATING AS INDICATED.

PANELBOARD BUSSING SHALL BE COPPER.

NEW TRANSFORMERS SHALL BE SELF-VENTILATED, DRY-TYPE TRANSFORMERS WITH THE

FOLLOWING CHARACTERISTICS:

1. COPPER OR ALUMNIMUM WINDINGS.

2. PRIMARY AND SECONDARY VOLTAGES AS INDICATED ON THE PLANS.

3. MINIMUM OF SIX 2-1/2% PRIMARY SIDE TAPS. TWO OF THE SIX SHALL BE ABOVE THE

RATED PRIMARY VOLTAGE AND FOUR OF THE SIX BEING BELOW THE RATED

PRIMARY VOLTAGE.

4. RATED FOR 150° C RISE BY RESISTANCE, WITH OVERALL 220° C INULATION RATING.

SAFETY SWITCHES SHALL BE HEAVY DUTY, FUSED WITH CLASS R INDICATING TYPE FUSES.

PROVIDE THREE SPARE FUSES OF EACH FUSE TYPE TO OWNER. PROVIDE NEMA 1 SWITCHES

FOR INDOOR USE, NEMA 3R FOR OUTDOOR, AND NEMA 4X FOR CORROSIVE AREAS.

MULTI-PHASE CIRCUIT BREAKERS SHALL HAVE SINGLE HANDLE TRIPS FOR ALL PHASES.

HANDLE TIES, OR OTHER FIELD INSTALLED COMMON TRIP HARDWARE IS NOT PERMITTED.

PROVIDE ELECTRICAL DISTRIBUTION EQUIPMENT WITH SURGE PROTECTIVE DEVICES WHERE

INDICATED ON THE PLANS AND ON THE ONE-LINE DIAGRAM.

EXECUTION

PROVIDE TEMPORARY SERVICE IN AREAS OF CONSTRUCTION FOR ALL TRADES. INCLUDE

LIGHTING AND 120 VOLT POWER. COST OF TEMPORARY POWER SHALL BE PAID BY OWNER.

PROVIDE NEW UTILITY SERVICE IN ACCORDANCE WITH DRAWINGS AND AS REQUIRED BY

LOCAL UTILITY. COORDINATE AND PROVIDE ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO

CONDUITS, METER SOCKETS, TERMINATION BOXES, METER STACKS, TRANSFORMER

CONCRETE PADS, BOLLARDS, CONDUCTORS, AS REQUIRED BY LOCAL UTILITY. CONTRACTOR

IS RESPONSIBLE FOR METER APPLICATION AND PAYING ALL FEES INVOLVED.

EXISTING PERMANENT SERVICE SHALL REMAIN IN PLACE. NEW FEEDERS AND PANEL

DISTRIBUTION BOARDS SHALL BE PROVIDED IN ACCORDANCE WITH DRAWINGS.

GROUNDING SHALL BE IN ACCORDANCE WITH ALL CODES.

CONTRACTOR TO PROVIDE ALL ARC FLASH LABELING ON ELECTRICAL EQUIPMENT AS

REQUIRED BY NFPA 70E, STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE.

GROUNDING

PRODUCTS

ALL GROUNDING CONDUCTORS SHALL BE COPPER.

GROUND RODS SHALLBE COPPER-CLAD STEEL, ¾” DIAMETER, 10' LONG.

MECHANICAL CONNECTIONS SHALL BE MADE WITH EXOTHERMIC WELDS OR WITH

MECHANICAL CONNECTORS AT THE CONTRACTOR'S OPTION. MECHANICAL CONNECTORS

SHALL BE BRONZE AND SHALL BE IRREVERSIBLE.

GROUND BUSSES SHALL BE 1/4” THICK BY 2” HIGH IN CROSS SECTION. LENGTHS AS

INDICATED ON THE PLANS.

EXECUTION

REMOVE SURFACE CONTAMINANTS AT ALL CONNECTION POINTS.

GROUND ELECTRICAL SYSTEMS AND EQUIPMENT AS REQUIRED BY THE NEC, THE LOCAL

UTILITY, AND LOCAL ORDINANCES.

PROVIDE SEPARATE GROUNDING CONDUCTOR WITH EACH FEEDER CONDUIT AND BRANCH

CIRCUIT CONDUIT. DO NOT RELY ON METAL RACEWAY AS THE SOLE EQUIPMENT GROUND

FOR ELECTRICAL CIRCUITS. BOND GROUND CONDUCTOR AT BOTH ENDS OF RACWAYS WITH

BOLTED GROUNDING LUGS.

SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH THE NEC.

FIRMLY ATTACH GROUNDS BEFORE CIRCUITS ARE ENERGIZED.

ELECTRICAL WIRING METHODS

ACCEPTABLE WIRING METHODS SHALL BE INDIVIDUAL CONDUCTORS IN CIRCULAR

RACEWAYS. EXCEPTIONS ARE AS FOLLOWS:

1. CONDUCTORS FOR SYSTEMS RATED 50 VOLTS AND LESS AND ROUTED 8' AFF OR

HIGHER, MAY BE INSTALLED IN FREE AIR WITHOUT RACEWAYS IN UNFINISHED

MECHANICAL ROOMS, ELECTRICAL ROOMS, TELECOM CLOSETS. CONDUCTORS

INSTALLED UNDER THIS EXCEPTION SHALL HAVE INSULATION RATINGS COMPLIANT

WITH THE NEC, APPROPRIATE TO THE CONDITIONS WHERE THE CONDUCTORS ARE

LOCATED.

2. CONDUCTORS FOR SYSTEMS RATED 50 VOLTS AND LESS AND ROUTED ABOVE

ACCESSIBLE CEILINGS CONCEALED FROM VIEW.

a. MAY BE INSTALLED IN FREE AIR WITHOUT RACEWAYS AT THE CONTRACTOR'S

OPTION.

b. REVIEW PLANS OF OTHER TRADES AND IDENTIFY ANY AIR-HANDLING PLENUMS.

CONDUCTORS INSTALLED UNDER THIS EXCEPTION SHALL HAVE INSULATION

RATINGS COMPLIANT WITH THE NEC, APPROPRIATE TO THE CONDITIONS WHERE

THE CONDUCTORS ARE LOCATED.

3. WHERE SPECIFICALLY INDICATED OTHERWISE ON THE DRAWINGS.

BUILDING WIRE AND CABLE

PRODUCTS

SINGLE CONDUCTOR INSULATED WIRE.

SOLID OR STRANDED CONDUCTOR FOR #10 AWG AND SMALLER. CONDUCTOR #8 AWG AND

LARGER SHALL BE STRANDED.

COPPER CONDUCTORS ONLY.

INSULATION VOLTAGE RATING: 600 VOLTS, RATED 75° CELSIUS, UNLESS OTHERWISE

INDICATED.

ACCEPTABLE INSULATION TYPES:

1. CONCEALED OR EXPOSED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE

TYPE THW, THHN / THWN OR XHHW INSULATION.

2. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE TYPE THW

INSULATION.

3. EXTERIOR LOCATIONS: USE ONLY BUILDING WIRE TYPE THW, OR USE INSULATION.

4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE TYPE THW, OR USE

INSULATION.

WIRING CONNECTORS FOR CONDUCTORS #10 AWG AND SMALLER. 3M SCOTCH-LOK

COMPRESSION TYPE SOLDERLESS CONNECTORS WITH PLASTIC OUTER SHELL.

WIRING CONNECTORS FOR CONDUCTORS #8 AWG AND LARGER. SOLDERLESS

COMPRESSION TYPE CONNECTORS, TOOL AND DIE APPLIED, OF TYPE THAT WILL NOT

LOOSEN UNDER VIBRATION OR NORMAL STRAINS. BURNDY “HYDENT" TYPE OR EQUIVALENT.

SPLIT BOLT CONNECTORS ARE NOT ACCEPTABLE.

RUBBER INSULATING ELECTRICAL TAPE: SCOTCH 3M MODEL 23, 30-MIL TAPE.

EXECUTION

CONDUCTOR SHALL NOT BE SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS.

CONDUCTOR SHALL NOT BE SMALLER THAN #14 AWG FOR CONTROL CIRCUITS.

ALL WIRES SHALL BE NEW, DELIVERED TO SITE IN UNBROKEN CARTONS, AND SHALL BE LESS

THAN ONE YEAR OLD OUT OF MANUFACTURER'S STOCK.

DO NOT DRAW CONDUCTORS INTO CONDUITS UNTIL BUILDING IS ENCLOSED AND

WATERTIGHT AND UNTIL WORK THAT MAY CAUSE CONDUCTOR DAMAGE HAS BEEN

COMPLETED.

EACH TAP, JOINT, OR SPLICE IN CONDUCTORS #8 AWG AND LARGER SHALL BE TAPED WITH

TWO HALF-LAP LAYERS OF VINYL PLASTIC ELECTRICAL TAPE AND FINISH WRAP OF COLOR

CODING TAPE, WHERE REQUIRED BY THE NEC OR LOCAL CODES.

CABLE SPLICES SHALL BE MADE ONLY IN DISTRIBUTION AND JUNCTION BOXES.

NEATLY TRAIN AND BUNDLE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.

SIZE CONDUIT, OUTLET BOXES, AND OTHER RACEWAY SYSTEM COMPONENTS IN

ACCORDANCE WITH NEC REQUIREMENTS AS MINIMUM.

MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED. EACH BRANCH CIRCUIT SHALL CONTAIN

A DEDICATED NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. A SINGLE NEUTRAL

SHARED BETWEEN MULTIPLE PHASE CONDUCTORS ARE NOT PERMITTED.

INSTALL WIRE COLORS IN ACCORDANCE WITH FOLLOWING:

1. BLACK AND RED FOR SINGLE PHASE CIRCUITS AT 120/ 240 VOLTS.

2. BLACK, RED, AND BLUE FOR CIRCUITS AT 120 / 208 VOLTS SINGLE OR THREE-PHASE.

3. BROWN, ORANGE, AND YELLOW FOR CIRCUITS AT 277 / 480 VOLTS SINGLE OR

THREE-PHASE.

NEUTRAL CONDUCTORS: WHITE. WHEN TWO OR MORE NEUTRALS ARE LOCATED IN ONE

CONDUIT, INDIVIDUALLY IDENTIFY EACH WITH PROPER CIRCUIT NUMBER.

RACEWAYS AND BOXES

PRODUCTS

METAL CONDUIT:

1. RIGID METAL CONDUIT (RMC).

2. INTERMEDIATE METAL CONDUIT (IMC).

3. ELECTRICAL METALLIC TUBING (EMT).

METAL CONDUIT FITTINGS (BOX TERMINATORS AND COUPLINGS):

1. STEEL OR MALLEABLE IRON, ZINC GALVANIZED, OR CADMIUM PLATED.

2. SET SCREW STYLE FASTENERS.

3. BOX CONNECTORS SHALL HAVE NON-METALLIC INSULATED THROATS.

4. DO NOT USE ALUMINUM OR DIE CAST FITTINGS.

LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC):

1. INTERLOCKED STEEL CONSTRUCTION WITH PVC SUNLIGHT RESISTANT JACKET.

2. FITTINGS: NEMA FB 1. LIQUID-TIGHT, SUITABLE FOR GROUNDING, SUITABLE FOR WET

LOCATIONS, TAPERED THREADED HUB, NON-METALLIC MATERIALS.

NON-METALLIC CONDUIT:

1. PRODUCT DESCRIPTION: NEMA TC 2: SCHEDULE 40 OR 80 PVC, UL LISTED, AND AS

REQUIRED BY NEC. SUNLIGHT RESISTANT.

2. RATED FOR 90° CELSIUS CABLE.

3. FITTINGS AND CONDUIT BODIES: NEMA TC 3, SCHEDULE 40 OR 80, TO MATCH

CONDUIT.

OUTLET BOXES:

1. INTERIOR OUTLET BOXES SHALL BE GALVANIZED STAMPED STEEL WITH

PRE-PUNCHED KNOCK OUTS. SIZE SHALL BE 4-11/16” SQUARE, 2-½” DEEP MINIMUM.

2. EXTERIOR OUTLET BOXES SHALL BE CAST FERRALLOY, TYPE FD, CAST FERALLOY.

FURNISH GASKETED COVER BY BOX MANUFACTURER.

EXECUTION

MINIMUM RACEWAY SIZE: 1/2", UNLESS OTHERWISE INDICATED.

SPLIT, CRUSHED, OR SCARRED CONDUIT IS NOT ACCEPTABLE.

WELDED CONDUIT IS NOT ACCEPTABLE.

PVC CONDUIT MAY NOT BE USED IN INTERIOR OF BUILDING.

RACEWAY AND BOXES LOCATED AS INDICATED ON DRAWINGS, AND AT OTHER LOCATIONS

REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE

WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE

LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM.

UNDERGROUND (OUTSIDE) MORE THAN 5'-0" OUTSIDE FOUNDATION WALL: PROVIDE

SCHEDULE 40 NON-METALLIC CONDUIT, UNLESS OTHERWISE INDICATED.

UNDERGROUND (OUTSIDE) WITHIN 5'-0" FROM FOUNDATION WALL TO INSIDE OF BUILDING:

PROVIDE RIGID STEEL CONDUIT. ONCE INSIDE BUILDING PROVIDE STEEL CONDUIT. PROVIDE

INTERLOCKING RUBBER GASKETS AROUND RACWAYS PASSING BELOW GRADE THROUGH

BUILDING FOUNDATION WALLS. UTILIZE LINK-SEAL TYPE GASKETS OR EQUIVALENT.

WET, DAMP, AND OUTDOOR LOCATIONS: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST

METAL JUNCTION AND PULL BOXES.

DRY LOCATIONS: PROVIDE METAL CONDUIT (RMC, IMC, OR EMT) UNLESS OTHERWISE

INDICATED. PROVIDE STAMPED STREEL OR SHEET METAL BOXES.

SUPPORT RACEWAY USING TWO-HOLE MALLEABLE IRON STRAPS, LAY-IN ADJUSTABLE

HANGERS, CLEVIS HANGERS, OR SPLIT HANGERS. PROVIDE LIGHT GAUGE STEEL FRAMING

FOR RACEWAY TRAPEZE HANGERS OR FOR OTHER RACEWAY SUPPORT AS REQUIRED.

SECURE CONDUITS IN PLACE WITH MALLEABLE CORROSION-PROOF ALLOY STRAPS OR

HANGERS. CONDUIT STRAPS USED IN CORROSIVE AREAS SHALL BE PVC COATED.

DO NOT SUPPORT RACEWAY WITH WIRE OR PERFORATED PIPE STRAPS. REMOVE WIRE USED

FOR TEMPORARY SUPPORTS.

ROUTE INTERIOR RACEWAYS PARALLEL WITH OR PERPENDICULAR TO WALLS, CEILINGS, AND

OTHER PRIMARY ARCHITECTURAL AND STRUCTURAL ELEMENTS.

CUT CONDUIT SQUARE USING SAW OR PIPE CUTTER: DE-BURR CUT ENDS. BRING CONDUIT TO

SHOULDER OF FITTINGS. FASTEN SECURELY.

JOIN NON-METALLIC CONDUIT USING CEMENT AS RECOMMENDED BY MANUFACTURER. WIPE

NON-METALLIC CONDUIT DRY AND CLEAN BEFORE JOINING. APPLY FULL EVEN COAT OF

CEMENT TO ENTIRE AREA INSERTED IN FITTING. ALLOW JOINT TO CURE FOR MINIMUM 20

MINUTES.

INSTALL CONDUIT HUBS TO FASTEN CONDUIT TO CAST BOXES IN DAMP AND WET LOCATIONS.

INSTALL NO MORE THAN EQUIVALENT OF THREE (3) 90 DEGREE BENDS BETWEEN BOXES.

INSTALL CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS.

INSTALL HYDRAULIC ONE-SHOT BENDER TO FABRICATE OR FACTORY ELBOWS FOR BENDS IN

METAL CONDUIT LARGER THAN 2" SIZE.

AVOID MOISTURE TRAPS: INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN

CONDUIT SYSTEM.

PROVIDE WATERTIGHT CONDUIT SYSTEM WHERE INSTALLED IN WET LOCATIONS SUCH AS

UNDERGROUND, OR WHERE EMBEDDED IN CONCRETE.

CONDUIT RUNS THAT EXTEND THROUGH AREAS OF DIFFERENT TEMPERATURE OR

ATMOSPHERIC CONDITIONS OR THAT ARE PARTLY INDOORS AND PARTLY OUTDOORS SHALL

BE SEALED, DRAINED, AND INSTALLED IN MANNER THAT WILL PREVENT DRAINAGE OF

CONDENSED OR ENTRAPPED MOISTURE INTO CABINETS. MOTORS, OR EQUIPMENT

ENCLOSURES.

CONDUIT CONNECTIONS AT MOTORS AND OTHER EQUIPMENT THAT VIBRATES:

1. PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT.

2. USE DOUBLE LOCKNUTS AND INSULATED BUSHINGS WITH THREADS FULLY

ENGAGED.

EXTERIOR UNDERGROUND DIRECT BURIED CONDUITS SHALL BE BURIED AT DEPTH OF NOT

LESS THAN 30" BELOW GRADE. UNDERGROUND CONDUITS SHALL SLOPE 1/8" PER FOOT FOR

PROPER DRAINAGE. CONDUITS SHALL DRAIN TOWARD MANHOLES AND JUNCTION BOXES.

CONDUITS SHALL NOT PITCH TO ELECTRICAL EQUIPMENT.

INSTALL KNOCKOUT CLOSURES IN UNUSED OPENINGS IN BOXES.

CLEAN INTERIOR OF BOXES TO REMOVE DUST, DEBRIS, AND OTHER MATERIAL.

CLEAN EXPOSED SURFACES AND RESTORE FINISH.

MOTOR WIRING

APPLICABLE MOTORS FURNISHED UNDER GENERAL CONSTRUCTION, HVAC, AND PLUMBING

TRADES OF WORK. MOTOR STARTERS FURNISHED LOOSE (NOT INTEGRAL TO EQUIPMENT

BEING CONTROLLED) SHALL BE FURNISHED BY THE CONTRACTOR THAT PROVIDES THE

MOTOR AND INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR IN APPROVED MANNER AT

LOCATIONS ESTABLISHED BY CONTRACTOR SUPPLYING EQUIPMENT.

ALL LINE VOLTAGE WIRING FROM STARTER TO MOTOR SHALL BE BY ELECTRICAL

CONTRACTOR. CONTROL WIRING (REGARDLESS OF VOLTAGE) SHALL BE BY THE

CONTRACTOR RESPONSIBLE FOR PROVIDING THE MOTOR.

PROVIDE HORSEPOWER RATED MOTOR DISCONNECT SWITCHES AS REQUIRED BY THE NEC.

ELECTRICAL CONTRACTOR SHALL VERIFY ALL MATERIALS ARE PROVIDED FOR COMPLETE

ELECTRICAL INSTALLATION.

SPECIAL PURPOSE OUTLETS

SPECIAL PURPOSE OUTLET SHALL BE LOCATED AS REQUIRED BY EQUIPMENT BEING SERVED.

CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ELECTRICAL CHARACTERISTICS OF

ACTUAL EQUIPMENT BEING FURNISHED FOR PROJECT PRIOR TO RACEWAY ROUGH-IN.

ELECTRICAL CONTRACTOR SHALL VERIFY ALL MATERIALS ARE PROVIDED FOR COMPLETE

ELECTRICAL INSTALLATION.

ELECTRICAL RECEPTACLES

PRODUCTS

PROVIDE ALL WIRING DEVICE TYPES FROM A SINGLE MANUFACTURER.

FOR BIDDING PURPOSES, DEVICE COLOR AND DEVICE COVER PLATES IN FINISHED ARERAS

SHALL BE WHITE. VERIFY COLOR AND MATERIAL OF EXISTING DEVICES AND COVER PLATES

AND PROVIDE NEW PLATES TO MATCH EXISTING.

ACCEPTABLE MANUFACTURERS ARE:

1. HUBBELL.

2. LEVITON.

3. ARROW-HART, INC.

4. PASS & SEYMOUR/LEGRAND

RECEPTACLES

1. GENERAL USE DUPLEX CONVENIENCE RECEPTACLE: HEAVY DUTY, SPECIFICATION

GRADE, 20 AMP, 125 VOLT, NEMA 5-20R HUBBELL CAT. NO. HBL5362.

2. TAMPER-RESISTANT: COMMERCIAL SPECIFICATION GRADE, 20 AMP DUPLEX, 125

VOLT, NEMA 5-20R, HUBBELL CAT. NO. BR20TR.

3. WEATHER-RESISTANT: CORROSION RESISTANT HEAVY DUTY, SPECIFICATION

GRADE, 20 AMP DUPLEX, 125 VOLT, NEMA 5-20R, HBL53CM62 (COLOR - YELLOW)

4. GFCI RECEPTACLE: HEAVY DUTY, SPECIFICATION GRADE, SELF-TESTING, 20 AMP,

125 VOLT, NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFST20.

5. TAMPER-RESISTANT GFCI: HEAVY DUTY COMMERCIAL GRADE, 20 AMP DUPLEX, 125

VOLT, NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFTR20.

6. WEATHER-RESISTANT GFCI: EXTRA HEAVY DUTY GRADE, 20 AMP DUPLEX, 125 VOLT,

NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFR5362.

WEATHERPROOF COVERPLATE: GASKETED DIE CAST METAL PLATE WITH HINGED AND

GASKETED DEVICE COVERS. COVER SHALL ALLOW CORDS TO BE PLUGGED IN AND COVER

CLOSED. PROVIDE INTERMATIC WP1010MC FOR SINGLE DUPLEX RECEPTACLES OR

WP1030MC FOR DOUBLE (QUAD) DUPLEX RECEPTACLES.

EXECUTION

RECEPTACLES N FINISHED SPACES SHALL BE FLUSH MOUNTED.

RECEPTACLES IN UNOCCUPIED ELECTRICAL ROOMS, IT ROOMS, AND MECHANICAL ROOMS

MAY BE INSTALLED SURFACE MOUNTED IN 4” SQUARE, ROUNDED CORNER, SURFACE

MOUNTED ELECTRICAL BOXES WITH MATCHING ROUNDED CORNER, RAISED METAL COVER

PLATES.

DO NOT INSTALL DEVICES UNTIL AFTER WALL FINISHES HAVE BEEN COMPLETELY APPLIED.

RECEPTACLES SHALL NOT BE INSTALLED BACK-TO-BACK IN COMMON STUD WALL CAVITIES

SHARED BETWEEN ADJACENT ROOMS.

INSTALL DEVICES AND WALL PLATES PLUMB AND LEVEL.

INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP.

CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER

AND BRANCH CIRCUIT EQUIPMENT GROUNDING CONDUCTOR.

INSTALL GALVANIZED STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN

UNFINISHED AREAS, ABOVE ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS.

DO NOT USE TERMINALS ON WIRING DEVICES (HOT OR NEUTRAL) FOR FEED_THROUGH

CONNECTIONS, LOOPED OR OTHERWISE MAKE CIRCUIT CONNECTIONS VIA WIRE

CONNECTORS AND PIGTAILS.

PROVIDE A LAYER OF ELECTRICAL TAPE AROUND PERIMETER SIDES OF EACH WIRING DEVICE

SO THAT TERMINATIONS ARE INSULATED.

WHERE GFI PROTECTED RECEPTACLES ARE INDICATED ON DRAWINGS, EACH RECEPTACLE

INDICATED SHALL BE A GFI RECEPTACLE. STANDARD RECEPTACLES PROTECTED WITH AN

UPSTREAM GFI RECEPTACLE SHALL NOT BE APPROVED.

VERIFY EACH RECEPTACLE DEVICE IS ENERGIZED.

TEST EACH RECEPTACLE DEVICE FOR PROPER POLARITY.

TEST EACH GFCI RECEPTACLE DEVICE FOR PROPER OPERATION

MARK PANEL AND CIRCUIT NUMBER SERVING DEVICE ON BACKSIDE OF DEVICE PLATE WITH A

PERMANENT MARKING SYSTEM THAT DOES NOT SHOW THROUGH FRONT OF PLATE.

LIGHTING FIXTURES

PRODUCTS

REFER TO PLANS AND/OR TO LIGHTING FIXTURE SCHEDULE.

RECESSED FIXTURES SHALL INCLUDE THERMAL CUTOFF PROTECTION IN ACCORDANCE WITH

THE NEC OR LOCAL CODES, WHICHEVER APPLICATION DICTATES. PROVIDE IC RATED

FIXTURES WHEN REQUIRED BY THE NEC.

LIGHT FIXTURES WITH INTEGRAL LED'S SHALL BE PROVIDED WITH THE FOLLOWING COLOR

CHARACTERISTICS. SEE LIGHTING FIXTURE SCHEDULE FOR ANY EXCEPTIONS.

1. LED'S WITH A COLOR RENDERING INDEX OF 80 OR HIGHER.

2. LED COLOR TEMPERATURE:

a. GENERAL INTERIOR LIGHT FIXTURES- 3500° K.

b. TOILET ROOM LIGHT FIXTURES - 3000° K.

c. EXTERIOR LIGHT FIXTURES - 4000° K.

PROVIDE LED LIGHT FIXTURES WITH 0-10 VDC DIMMING CAPABILITY WITH INTEGRAL DRIVERS

UNLESS NOTED OTHERWISE IN THE LIGHTING FIXTURE SCHEDULE.

EXECUTION

WHERE LAMPS ARE NEEDED, PROVIDE FIXTURES COMPLETE WITH INITIAL FILL OF LAMPS AS

SCHEDULED. PROVIDE BALLASTS AS SPECIFIED.

CONTRACTOR SHALL VERIFY CEILING CONSTRUCTION PRIOR TO ORDERING FIXTURES.

PROVIDE RECESSED FIXTURES WITH TRIM CHARACTERISTICS COMPATIBLE WITH CEILING

TYPES WHERE FIXTURES ARE TO BE INSTALLED.

LIGHTING CONTROLS

PRODUCTS

DEVICE COLORS AND DEVICE COVER PLATES SHALL BE WHITE, UNLESS NOTED OTHERWISE.

MANUAL CONTROLS

UNLESS OTHERWISE INDICATED ACCEPTABLE MANUFACTURERS FOR MANUAL SWITCHES

ARE:

1. HUBBELL.

2. LEVITON.

3. ARROW-HART, INC.

4. PASS & SEYMOUR.

MANUAL SWITCHES:

1. SINGLE POLE SWITCH: 20 AMPS, 120-277 VOLT, SPECIFICATION GRADE, BACK OR

SIDE WIRED EQUAL TO HUBBELL CAT. NO. HBL1221.

2. THREE-WAY SWITCH: 20 AMPS, 120-277 VOLT, SPECIFICATION GRADE, BACK OR SIDE

WIRED EQUAL TO HUBBELL CAT. NO. HBL1223.

HARD-WIRED OCCUPANCY / VACANCY SENSORS

APPROVED MANUFACTURERS:

1. WATTSTOPPER.

2. LEVITON.

3. MYTECH.

4. HUBBELL.

5. SENSOR SWITCH.

6. LUTRON.

LINE VOLTAGE DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR:

1. SENSOR SHALL USE PASSIVE INFRARED AND ULTRASONIC DETECTION METHOD FOR

DETECTING ROOM OCCUPANCY. UNIT SHALL FIT IN/ON A STANDARD SINGLE GANG

OPENING AND REQUIRE ONLY TWO WIRES AND A GROUNDED BOX FOR OPERATION.

2. RATED CAPACITY: 1000 WATTS MINIMUM AT 120 VOLTS, 60 HZ, 1200 WATTS MINIMUM

AT 277 VOLTS, 60 HZ, LARGER SIZE TO ACCOMMODATE LOAD AS SHOWN ON

DRAWINGS.

3. SWITCH SHALL HAVE MANUAL ON/OFF BUTTON.

4. BASIS OF DESIGN MODEL WATTSTOPPER: DSW-301 SERIES.

LINE VOLTAGE CEILING-MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR:

1. SENSOR SHALL EMPLOY BOTH INFRARED AND ULTRASONIC SENSING METHODS TO

DETECT ROOM OCCUPANCY. UNIT SHALL FIT ON A STANDARD, RECESSED,

OCTAGON BOX, DESIGNED FOR CEILING MOUNTING.

2. RATED CAPACITY SHALL BE 20 AMPS AT 120 OR 277 VOLTS.

3. AREA OF COVERAGE SHALL BE 1000 SQUARE FOOT MINIMUM. UNIT SHALL BE

PROVIDED WITH A DIP SWITCH TO ALLOW EITHER DETECTION TECHNOLOGY TO BE

INDEPENDENTLY CONFIGURED.

4. UNIT SHALL BE PROVIDED WITH A DIP SWITCH TO SELECT ONE OF FIVE DIFFERENT

SENSING MODES AS DICTATED BY ENVIRONMENTAL FACTORS.

5. PROGRAMMABLE RESPONSE TIME, 5 TO 30 MINUTES.

6. BASIS OF DESIGN MODEL: WATTSTOPPER: DT-355.

LOW VOLTAGE OCCUPANCY/VACANCY SENSORS. LOW VOLTAGE SENSORS SHALL BE USED

IN CONJUNCTION WITH POWER PACKS THAT CONTACT LINE VOLTAGE LOAD SWITCHING

CONTACTS AND CONTROL POWER FOR OPERATING ASSOCIATED SENSORS. POWER PACKS

SHALL HAVE THE FOLLOWING CHARACTERISTICS:

1. LINE VOLTAGE LOAD CONTROL CONTACTS RATED AT 20 AMPS.

2. RATED FOR 120 AND 277 VOLTS AC.

3. PLENUM RATED.

4. PROVIDES 24 VOLTS DC CONTROL POWER TO OPERATE ASSOCIATED SENSORS.

5. BASIS OF DESIGN: WATTSTOPPER BZ SERIES.

LOW VOLTAGE DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR:

1. SENSOR SHALL USE PASSIVE INFRARED AND ULTRASONIC DETECTION METHOD FOR

DETECTING ROOM OCCUPANCY.

2. UNIT SHALL FIT IN/ON A STANDARD SINGLE GANG OPENING AND REQUIRE ONLY TWO

WIRES AND A GROUNDED BOX FOR OPERATION.

3. SWITCH SHALL HAVE MANUAL ON/OFF BUTTON.

LOW VOLTAGE CEILING-MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR:

1. SENSOR SHALL EMPLOY BOTH INFRARED AND ULTRASONIC SENSING METHODS TO

DETECT ROOM OCCUPANCY.

2. UNIT SHALL FIT ON A STANDARD, RECESSED, OCTAGON BOX, DESIGNED FOR

CEILING MOUNTING.

3. AREA OF COVERAGE SHALL BE 1000 SQUARE FOOT MINIMUM. UNIT SHALL BE

PROVIDED WITH A DIP SWITCH TO ALLOW EITHER DETECTION TECHNOLOGY TO BE

INDEPENDENTLY CONFIGURED.

4. UNIT SHALL BE PROVIDED WITH A DIP SWITCH TO SELECT ONE OF FIVE DIFFERENT

SENSING MODES AS DICTATED BY ENVIRONMENTAL FACTORS.

5. PROGRAMMABLE RESPONSE TIME, 5 TO 30 MINUTES

6. BASIS OF DESIGN MODEL: WATTSTOPPER: DT-300.

DIGITAL LIGHTING CONTROLS

DIGITAL LIGHTING CONTROLS. DIGITAL LIGHTING CONTROLS ARE THOSE SYSTEMS THAT USE

DIGITAL COMMUNICATIONS BETWEEN LIGHTING CONTROL AND SENSING DEVICES TO

CONTROL BUILDING LIGHTING SYSTEMS. IN ORDER TO ENSURE COMPATIBILITY, ALL SYSTEM

DEVICES SHALL BE BY THE SAME MANUFACTURER UNLESS SPECIFICALLY NOTED

OTHERWISE.

DIGITAL LIGHTING CONTROL SYSTEM SHALL CONSIST OF INDIVIDUAL SYSTEM COMPONENT

THAT COMMUNICATE WITH EACH OTHER OVER SIGNAL VOLTAGE DATA COMMUNICATIONS

STYLE CABLE.

ACCEPTABLE MANUFACTURERS:

1. ACUITY BRANDS NLIGHT SYSTEM.

2. WATTSTOPPER DLM SERIES.

POWER/RELAY PACKS:

1. 16 AMP POWER CAPACITY.

2. PROVIDES POWER FOR SYSTEM COMMUNICATIONS BUS.

3. TWO RJ45 COMMUNICATIONS PORTS.

4. 120/277 VOLT RATING.

5. PUSHBUTTON PROGRAMMABLE.

6. PLENUM RATED.

7. PROVIDE WITH 0-10 VDC DIMMING CAPABILITY.

8. BASIS OF DESIGN: ACUITY NLIGHT NPP16 SERIES.

DIGITAL SWITCH STATIONS:

1. MULTIPLE PUSHBUTTONS WILL COMPROMISE A SINGLE SWITCH STATION LOCATION.

2. CONFIGURED AS INDICATED ON THE PLANS, DESIGNED TO MOUNT IN A SINGLE

GANG BOX OPENING.

3. SHALL CONTAIN RJ-45 NETWORK PORTS FOR COMMUNICATIONS CABLING

TERMINATIONS/BUS CONNECTION.

4. FURNISH INDIVIDUAL BUTTONS WITH REMOVABLE CLEAR COVER FOR LABELING

CONTROLLED LOADS.

5. WHITE BUTTONS AND WHITE COVER-PLATES.

6. BASIS OF DESIGN ACUITY NPODM SERIES.

DIGITAL OCCUPANCY SENSORS:

1. CEILING MOUNTED SENSORS.

2. DUAL TECHNOLOGY PASSIVE INFRARED AND MICROPHONIC TECHNOLOGIES.

3. TWO RJ45 COMMUNICATIONS PORTS.

4. PROVIDE WITH AUXILIARY RELAY FOR INTERFACE TO HVAC DEVICES.

5. MATTE WHITE COLOR.

6. BASIS OF DESIGN: ACUITY NLIGHT NCM XX RJB SERIES.

DIGITAL DAYLIGHT SENSORS:

1. PHOTO-CELL SENSOR FOR ON/OFF AND DIMMING CONTROL OF ASSOCIATED LIGHT

FIXTURES.

2. DESIGNED FOR CEILING MOUNTING.

3. WHITE COLOR

4. FIELD ADJUSTABLE SET POINTS.

5. REAR RJ45 PATCH CABLE AND SPLITTER

6. BASIS OF DESIGN: ACUITY NLIGHT NCM ADCX RJB SERIES.

DIGITAL COMMUNICATIONS/CONTROL WIRING AS REQUIRED BY DEVICE MANUFACTURER.

EXECUTION

INSTALL ALL DEVICES IN ACCORDANCE WITH INDUSTRY STANDARDS AND IN COMPLIANCE

WITH DEVICE MANUFACTURER'S RECOMMENDATIONS.

SEE SECTION ON WIRING METHODS. THESE REQUIREMENTS SHALL BE FOLLOWED FOR ALL

LINE VOLTAGE WIRING AND FOR LOW VOLTAGE SIGNAL WIRING.

ALL LIGHTING CONTROLS SHALL BE PROGRAMMED AS DESIRED BY THE OWNER, COMPLIANT

WITH APPLICABLE ENERGY CODE REQUIREMENTS. CONTRACTOR SHALL INCLUDE IN THEIR

BASE BID ANY COSTS ASSOCIATED WITH TRAINING PROVIDED BY A FACTORY AUTHORIZED

LIGHTING CONTROL AGENT. INCLUDE A MINIMUM OF 8 HOURS OF OWNER TRAINING, USING A

FACTORY CERTIFIED LIGHTING CONTROL PRODUCT REPRESENTATIVE.

STRUCTURED CABLING

PRODUCTS

SHIELDED TWISTED-PAIR CAT 6 CABLE SHALL MEET ALL THE REQUIREMENTS FOR

ANSI/TIA/EIA-568-C - COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD,

PART 2: TRANSMISSION PERFORMANCE SPECIFICATIONS FOR 4 PAIN 100 OHM CATEGORY 6

CABLING.

JACKS SHALL BE MODULAR RJ-45.

ALL JACKS AND CONNECTORS SHALL BE CERTIFIED TO CATEGORY 6 (CAT 6 CABLE) / 6A (CAT

6A CABLE) STANDARDS, COMPONENT RATED.

EXECUTION

HORIZONTAL CABLE LINKS TELECOMMUNICATIONS OUTLET IN WORK AREA TO

TELECOMMUNICATIONS ROOM (TR) OR EQUIPMENT ROOM (ER).

HORIZONTAL CABLES CONNECT TO VOICE (CAT 6), DATA (CAT 6), CAMERA (CAT 6) AND

WIRELESS ACCESS POINTS (WAP) ((2) CAT 6A).

ALL HORIZONTAL CABLES SHALL UTILIZE RJ-45 MODULAR JACKS, TERMINATED TO T-568B

WIRING SCHEME.

1. PROVIDE MULTIPLE JACKS INA SINGLE “OUTLET” AS INDICATED ON THE PLANS.

2. AN OUTLET IS DEFINED AS A SINGLE ELECTRICAL OUTLET BOX WITH A SINGLE-GANG

FACEPLATE.

DEMOLITION

CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY EXISTING CODE VIOLATIONS OBSERVED

DURING THE COURSE OF PERFORMING HIS WORK. THE ENGINEER WILL DECIDE IF

CORRECTIVE ACTION NEEDS TO BE TAKEN. CORRECTIVE ACTIONS THAT CHANGE THE SCOPE

OF THE WORK WILL BE CONSIDERED A CHANGE ORDER AND WILL BE PROCESSED

ACCORDINGLY.

EXISTING BUILDINGS SHALL REMAIN IN SERVICE DURING CONSTRUCTION.

PRIOR TO DEMOLITION OR ALTERATION OF STRUCTURES, THE FOLLOWING SHALL BE

ACCOMPLISHED:

1. OWNER RELEASE OF SUCH STRUCTURE.

2. DISCONNECTION OF ELECTRICAL POWER TO EQUIPMENT AND CIRCUITS REMOVED

OR AFFECTED BY DEMOLITION WORK.

3. ELECTRICAL SERVICES REROUTED OR SHUT OFF OUTSIDE AREA OF DEMOLITION.

4. COORDINATE SEQUENCING WITH OWNER AND OTHER CONTRACTORS.

5. SURVEY AND RECORD CONDITION OF EXISTING FACILITIES TO REMAIN IN PLACE

THAT MAY BE AFFECTED BY DEMOLITION OPERATIONS.

POWER OUTAGES AND INTERRUPTIONS IN BUILDING SYSTEMS SHALL BE HELD TO A MINIMUM

AND SHALL BE DONE AT A TIME CONVENIENT TO OWNER. TIME OF ALL OUTAGES SHALL BE

SCHEDULED WITH OWNER AND ALL OTHER TRADES AFFECTED BY OUTAGE AT LEAST TEN

WORKING DAYS IN ADVANCE.

IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. OWNER MAY KEEP ANY

EQUIPMENT IN DEMOLITION AREAS. CONTRACTOR SHALL DELIVER EQUIPMENT OWNER

WANTS SALVAGED TO AREA IN BUILDING DESIGNATED BY OWNER. CONTRACTOR SHALL

REMOVE ALL MATERIALS IN DEMOLISHED AREA NOT SALVAGED FROM SITE. CONTRACTOR

SHALL OBTAIN RELEASE OF ALL MATERIALS BEFORE DISPOSITION.

AFTER DEMOLITION OPERATIONS ARE COMPLETED, SURVEY CONDITIONS AND RESTORE

EXISTING FACILITIES TO THEIR PRE-DEMOLITION CONDITION.

REMOVE ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE

CEILINGS. CUT CONDUIT CAST INTO CONCRETE STRUCTURS FLUSH WITH WALLS AND

FLOORS. PATCH SURFACES AROUND CONDUITS.

REMOVE CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE

WITH NEW INSTALLATION.

DE-ENERGIZE AND DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS

SCHEDULED FOR REMOVAL.

DISCONNECT OR SHUT OFF POWER TO AREAS WHERE ELECTRICAL WORK IS TO BE

REMOVED. REMOVE ELECTRICAL FIXTURES, EQUIPMENT AND RELATED SWITCHES, OUTLETS,

CONDUIT AND WIRING WHICH ARE NOT PART OF FINAL PROJECT.

REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW

CONSTRUCTION.

REMOVE ABANDONED GROUNDING AND BONDING COMPONENTS, FASTENERS AND

SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ABANDONED

COMPONENTS ABOVE ACCESSIBLE CEILINGS.

CUT EMBEDDED SUPPORT ELEMENTS FLUSH WITH WALLS AND FLOORS.

FEEDERS, BRANCH CIRCUITS, AND OTHER SYSTEM WIRING WHICH ARE TO REMAIN IN

SERVICE BUT WHICH ARE PRESENTLY ROUTED THROUGH AREAS BEING DEMOLISHED SHALL

BE REROUTED AROUND DEMOLITION AREA.

WHERE EXISTING BRANCH CIRCUITS ARE TO BE EXTENDED OR MODIFIED, EXISTING CONDUIT

THAT HAS NOT BEEN REMOVCED MAY BE REUSED AT CONTRACTOR'S DISCRETION.

EXISTING CONDUITS THAT ARE REMOVED FROM THEIR EXISTING LOCATION SHALL NOT BE

REUSED.

EXISTING WIRING MAY BE SPLICED AND USED TO EXTENT THAT IT WAS NOT REMOVED.

EXISTING CONDUCTORS THAT HAVE BEEN REMOVED SHALL NOT BE RE-USED.

REMOVE AND PROTECT ITEMS REQUESTED BY OWNER TO BE SALVAGED AND TRANSPORT

TO LOCATION ON SITE DESIGNATED BY OWNER.

CONTRACTOR SHALL TOUR DEMOLITION AREAS WITH OWNER TO DETERMINE STATUS OF ALL

EQUIPMENT TO BE REMOVED DURING DEMOLITION.

ALL EQUIPMENT THAT IS TO BE SALVAGED FOR REUSE BY THE OWNER SHALL BE REMOVED

BY CONTRACTOR AND TRANSPORTED TO AN OWNER DESIGNATED STORAGE AREA ON SITE.

RACEWAY, BOXES, AND SUPPORTING DEVICES SHALL BECOME PROPERTY OF CONTRACTOR

AND SHALL BE REMOVED FROM SITE AND DISPOSED OF BY THE CONTRACTOR.

REMOVED EQUIPMENT SHALL BE DISPOSED OF BY CONTRACTOR UNLESS SPECIFICALLY

OTHERWISE INDICATED ON DRAWINGS OR REQUESTED BY OWNER. CONTRACTOR SHALL

PROVIDE TRANSPORT FOR DISPOSAL.

ANY HAZARDOUS MATERTIALS REMOVED FROM SERVICE AS PART OF THIS PROJECT SHALL

BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR IN COMPLETE COMPLIANCE WITH ALL

FEDERAL, STATE, AND LOCAL ENVIRONMENTAL LAWS. EXAMPLES OF SUCH MATERIALS

WOULD INCLUDE LIGHT FIXTURE LAMPS AND LIGHT FIXTURE BALLASTS THAT CONTAIN

REGULATED ELEMENTS.

ELECTRICAL SPECIFICATIONS

E-002

ELECTRICAL SPECIFICATIONS

E-101

A E-102

A E-201

B E-101

B E-102

B E-201

A E-202

A E-301

B E-202

B E-301

MATCHLINE

MATCHLINE

MATCHLINE

M…