Electrical_Drawings_Daytona_Beach_Main_Street_Pier_Railings_Renovation_-_Revised_-_Signed.pdf
PDF 11 MB Posted
- Attached to
- 2620ITB - Main Street Pier Repairs - 2026
- Solicitation number
- 2620ITB
- Issued by
- Volusia County, Florida
About this file
This is a set of electrical drawings and specifications for the City of Daytona Beach's Main Street Pier Partial Boardwalk and Railing Replacement project (Project Number 2019-4115). The drawings, prepared by Alexander H. Parrish, P.E., and certified by GRAEF USA, detail comprehensive electrical demolition and renovation work for a waterfront pier structure. The project scope includes removal of existing lighting fixtures, conduit, and wiring; reinstallation of salvaged poles and fixtures; installation of new weather-resistant GFCI receptacles mounted in stainless steel enclosures on railing posts; and photometric analysis to verify lighting performance. The electrical work must comply with the Florida Building Code 8th Edition (2023), Florida Energy Conservation Code, Florida Fire Prevention Code, and the National Electrical Code 2020. All wiring shall be in conduit (minimum 3/4" unless otherwise noted) with solid copper #12 AWG minimum, grounding conductors in all circuits, and no shared neutral conductors. Materials specified include copper grounding conductors, copper-clad steel ground rods, Square D panelboards and circuit breakers, self-ventilated dry-type transformers, heavy-duty fused safety switches, and specification-grade receptacles from manufacturers such as Hubbell, Leviton, or Pass & Seymour.
The contractor is responsible for preparing and submitting all required construction permits and securing necessary licenses before starting work, with all fees paid by the contractor. A short circuit, coordination, and arc flash study must be performed by a third-party consultant and submitted for engineer approval prior to releasing electrical distribution equipment for manufacture. All work shall be guaranteed for a minimum of one year after final acceptance. The contractor must provide temporary service in construction areas, coordinate with mechanical and other trades, maintain fire alarm protection throughout construction phases, and document all existing conditions prior to demolition. Lighting photometric calculations for the pier boardwalk specify an average of 1.8 footcandles with a maximum of 3.9 and minimum of 0.1 footcandles, with post-installation photometric measurement and analysis required to verify design compliance. The contractor must include costs for training a minimum of eight hours of owner instruction by a factory-certified lighting control product representative. No pricing information, contract award dates, or response deadlines are detailed in the electrical drawings themselves; these details would be found in the associated solicitation documents for the Main Street Pier Repairs project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AS NOTED
A
B
C
1 2 3 4 5
2019-4115
10/14/2025
AHP
AHP
MSA
A
B
C
1 2 3 4 5
Al ex an de r H . P ar ris h
PE
2AL
EX
ANDER H . PARR ISH
PROFESS I ONA L ENG I N
EE
R
L I CENSE
F L O R I D A
STATE OF
No. 87322
This item has been electronic signed and sealed by Alexander H. Parrish on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
CITY OF DAYTONA BEACH
MAIN STREET PIER
PARTIAL BOARDWALK AND
RAILING REPLACEMENT
SEAL:
DRAWN BY:
APPROVED BY:
SCALE:
CHECKED BY:
DATE:
PROJECT NUMBER:
PROJECT TITLE:
ISSUE:
PROJECT INFORMATION:
SHEET TITLE:
SHEET NUMBER:
www.graef-usa.com
2300 Maitland Center Parkway, Suite 210 Maitland, FL 32751 407 / 659 6500
CERT # 4270
PERMIT SET
1P 2P 3P 4P 1P, 1W 1P, 2W 2P, 2W 2P, 3W 3P, 2W 3P, 3W 3P, 4W 4P, 4W A
AC
AF
AFF
AFG
AIC
ANSI
AL
AS
AT
ARCH
ATS
A / V
AWG
B
BF
BFF
BFG
BLDG
C
CAM
CAT
CATV
CB
CKT
CLG
CO
CT
CU
CL
DC
DR
DISC
DW
DWG
E
EC
EMT
ETR
ER
ERL
ERLD
EWC
EX
FA
FLA
FO
FPC
GC
GFCI
GFPE
GND
GRC
HH
HP
HVAC
HZ
ISP
IT
JB
KVA
KW
LP
LS
LTG
LV
MC
MCA
MCC
MDP
MH
MISC
MLO
MTD
MTG
MTS
MW
MV
N / A
NC
NEC
NIC
NO
NTS
OSP
P
PB
PC
PH
PNL
PP
PR
PRI
PROJ
PVC
REC
RE / CKT
REF
RSC
SC
SEC
SN
SP
SS
ST
STP
SUSP
SW
SWBD
T
TBB
TC
TCI
TELE / DATA
TEL
TELECOM
TGB
TMGB
TP
TYP
UG
UTP
UOI
V
W
WA
WAP
WP
XFMR
XR
XV
Y
ZAM
- KILOWATT
- LIGHTING PANEL
- LIMIT SWITCH
- LIGHTING
- LOW VOLTAGE
- MECHANICAL CONTRACTOR
- MINIMUM CIRCUIT AMPS
- MOTOR CONTROL CENTER
- MAIN DISTRIBUTION PANEL
- MANHOLE
- MISCELLANEOUS
- MAIN LUGS ONLY
- MOUNTED
- MOUNTING
- MANUAL TRANSFER SWITCH
- MICROWAVE
- MEDIUM VOLTAGE
- NOT APPLICABLE
- NORMALLY CLOSED
- NATIONAL ELECTRIC CODE
- NOT IN CONTRACT
- NORMALLY OPEN
- NUMBER
- NOT TO SCALE
- OUTSIDE PLANT
- POLE
- PULL BOX
- PLUMBING SYSTEM CONTRACTOR
- PHASE
- PANEL OR PANELBOARD
- POWER PANEL
- PAIR
- PRIMARY
- PROJECTOR
- POLYVINYL CHLORIDE
- RECESSED
- REUSE EXISTING CIRCUIT
- REFRIGERATOR
- RIGID STEEL CONDUIT
- SECURITY CONTRACTOR
- SECONDARY
- SOLID NEUTRAL
- SPARE
- STAINLESS STEEL
- SHUNT TRIP
- SHIELDED TWISTED PAIR
- SUSPENDED
- SWITCH
- SWITCHBOARD
- TAMPER RESISTANT SAFETY RECEPTACLE
- TELECOMMUNICATIONS BONDING BACKBONE
- TELEPHONE CABINET
- TELECOMMUNICATIONS CABLING INSTALLER
- TELEPHONE / DATA
- TELEPHONE
- TELECOMMUNICATIONS
- TELECOMMUNICATIONS GROUNDING BUSBAR
- TWISTED PAIR
- TYPICAL
- UNDERGROUND
- UNSHIELDED TWISTED PAIR
- UNLESS OTHERWISE INDICATED
- VOLT
- WATT
- WASHER
- WIRELESS ACCESS POINT
- WEATHERPROOF
- TRANSFORMER
- XRAY
- XRAY VIEWER
- WYE
- ZONE ADAPTER MODULE
- ONE POLE
- TWO POLE
- THREE POLE
- FOUR POLE
- ONE POLE, ONE WIRE
- ONE POLE, TWO WIRE
- TWO POLE, TWO WIRE
- TWO POLE, THREE WIRE
- THREE POLE, TWO WIRE
- THREE POLE, THREE WIRE
- THREE POLE, FOUR WIRE
- FOUR POLE, FOUR WIRE
- AMPERE
- ALTERNATING CURRENT
- AMPERE FRAME
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AMPERE INTERRUPTING CAPACITY
- AMERICAN NATIONAL STANDARDS INSTITUTE
- ALUMINUM
- AMP SWITCH
- AMP TRIP
- ARCHITECT
- AUTOMATIC TRANSFER SWITCH
- AUDIO VISUAL
- AMERICAN WIRE GRADE
- PEDESTAL MOUNTED ON BENCH TOP
- BELOW FLOOR
- BELOW FINISHED FLOOR
- BELOW FINISHED GRADE
- BUILDING
- CONDUIT
- CAMERA
- CATALOG
- CABLE TELEVISION
- CIRCUIT BREAKER
- CIRCUIT
- CEILING MOUNTED
- COPIER
- CURRENT TRANSFORMER
- COPPER
- CENTERLINE
- DIRECT CURRENT
- DRYER
- DELTA
- DISCONNECT
- DISHWASHER
- DRAWING
- EMERGENCY
- ELECTRICAL CONTRACTOR
- ELECTRIC METALLIC TUBING
- EXISTING TO REMAIN
- EQUIPMENT ROOM
- EXISTING TO BE RELOCATED
- RELOCATED EQUIPMENT'S NEW LOCATION
- ELECTRIC WATER COOLER
- EXISTING
- FIRE ALARM
- FULL LOAD AMPS
- FIBER OPTIC
- FIRE PROTECTION CONTRACTOR
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND FAULT PROTECTION EQUIPMENT
- GROUND
- GALVANIZED RIGID CONDUIT
- HANDHOLE
- HORSEPOWER
- HEATING, VENTILATING, AND AIR CONDITIONING
- HERTZ (CYCLE) PER SECOND
- INSIDE PLANT
- INFORMATION TECHNOLOGY
- JUNCTION BOX
- KILOVOLT AMPERE
ELECTRICAL ABBREVIATIONS
XXX
X DETAIL REFERENCE
- TOP DESIGNATES DETAIL NUMBER
- BOTTOM DESIGNATES SHEET NUMBER
GENERAL SYMBOLS
ELECTRICAL SYMBOLS AND ABBREVIATIONS
NOTE: NOT ALL SYMBOLS AND ABBREVIATIONS INDICATED HERE ARE USED IN DRAWINGS AND MAY NOT APPLY TO CURRENT PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED ON DRAWINGS.
GENERAL NOTE
THIS IS A STANDARD LEGEND. SOME SYMBOLS
MAY NOT APPEAR IN THE DRAWINGS.
NOTES/SPECS
THERE ARE ADDITIONAL NOTES AND SPECIFICATIONS FOUND ON
SUBSEQUENT SHEETS. EXCEPT FOR GENERAL SHEET NOTES AND
KEYED NOTES (E.G. PLAN KEY NOTES), THE NOTES AND
SPECIFICATIONS HERE SHALL APPLY TO ALL SHEETS.
FBCEC COMMISSIONING REQUIREMENTS
X
X
LIGHTING CONTROL
RELAY CABINET/
LIGHTING CONTROL CABINET
- (X) INDIXATES DESIGNATION
PHOTOCELL
OCCUPANCY SENSOR
- CEILING MOUNTED
- (X) INDICATES TYPE
(SEE SCHEDULE)
SWITCH STATION
- LOW VOLTAGE
- (X) INDICATES STATION
IDENTIFIER
SWITCH
- MOUNTED 3'-8" AFF, UON
- (a) INDICATES SWITCH
DESIGNATION
- SINGLE POLE, UON
- (X) INDICATES SWITCH TYPE:
(2) TWO POLE
(3) THREE WAY
(4) FOUR WAY
(DLS) DUAL LEVEL
(K) KEY OPERATED
(P) WITH PILOT LIGHT
(T) TIMER
L
AA
LIGHTING FIXTURE DESIGNATIONS
PARTIAL SHADING INDICATES FIXTURE
PARTIALLY WIRED TO EMERGENCY
OR NIGHT LIGHTING CIRCUIT
LIGHT FIXTURE DESIGNATION
WALL MOUNTED EXIT LIGHT
FIXTURE
- SHADING INDICATES FACE(S)
- ARROW(S) AND FACE(S) AS
INDICATED ON DRAWINGS
LIGHTING FIXTURES
STRIP LIGHT OR UNDER CABINET LIGHT
WALL MOUNTED
SURFACE/RECESSED
MOUNTED
EMERGENCY BATTERY DUAL
REMOTE HEAD
EMERGENCY BATTERY SINGLE
REMOTE HEAD
EMERGENCY BATTERY UNIT
MOUNT AT 8' - 0" AFF UON
RECESS MOUNTED ACCENT
- CHEVRON INDICATES DIRECTION OF
ILLUMINATION
SURFACE MOUNTED ACCENT
- CHEVRON INDICATES DIRECTION OF
ILLUMINATION
LIGHTING TRACK
- LENGTH AS INDICATED ON DRAWINGS
- NUMBER AND DIRECTION OF FIXTURES
AS INDICATED ON DRAWINGS AND / OR
SCHEDULE
CEILING MOUNTED EXIT LIGHT
FIXTURE
- SHADING INDICATES FACE(S)
- ARROW(S) AND FACE(S) AS
INDICATED ON DRAWINGS
SUSPENDED, PENDENT, CHAIN,
STEM, OR CABLE HUNG
Y
X
X
X
X
X
WIRING DEVICES
DUPLEX RECEPTACLE
- MOUNTED 1'-6" AFF, UOI
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
- (Y) INDICATES TYPE:
(WP) WEATHERPROOF
(WR) WEATHER RESISTANT MOTOR CONNECTION
- (X) INDICATES:
PANEL NAME
BREAKER SIZE/# OF POLES
- (Y) INDICATES:
MOTOR DESIGNATION
LOAD SIZE
VOLTAGE / PHASE
SPECIAL PURPOSE OUTLET
- (X) INDICATES:
PANEL NAME
BREAKER SIZE/# OF POLES
- (Y) INDICATES:
SPO DESIGNATION
LOAD SIZE
VOLTAGE / PHASE
DUPLEX RECEPTACLE
- MOUNTED FLUSH IN CEILING
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
DUPLEX RECEPTACLE
- MOUNTED FLUSH IN
COUNTERTOP
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
DUPLEX RECEPTACLE
- TOP HALF SWITCHED
- MOUNTED 1'-6" AFF, UOI
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
DUPLEX RECEPTACLE MOUNTED 6"
ABOVE COUNTER BACKSPLASH, UOI
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
TV / POWER OUTLET BOX 6' - 8"
AFF UNLESS NOTED OTHERWISE.
TV
X
Y
Y
X
EQUIPMENT AND PANELBOARDS
METER
CURRENT TRANSFORMER
CABINET
TRANSFORMER
- (X) INDICATES
DESIGNATION
BRANCH PANELBOARD DISTRIBUTION PANELBOARD
- (X) INDICATES
DESIGNATION
CT
ELECTRICAL BOX
- FLOOR MOUNTED
- POKE THRU
- OUTLET TYPES REQUIRED
AT EACH BOX AS INDICATED
ON DRAWINGS
JUNCTION BOX:
FLOOR MOUNTED
PULL BOX
HANDHOLE
MANHOLE
RACEWAYS AND BOXES
CABLE TAP BOX
MULTI-OUTLET RACEWAY
ASSEMBLY
- WALL MOUNTED 1'-6"
AFF, UOI
ELECTRICAL BOX
- FLOOR MOUNTED
- FLUSH
- OUTLET TYPES REQUIRED AT
EACH BOX AS INDICATED ON
DRAWINGS
BUSWAY
- RATING AND TYPE AS
INDICATED ON DRAWINGS
F
P
CTB
PB
HH
DUPLEX RECEPTACLE
(GFCI) GROUND FAULT
CIRCUIT INTERRUPTING
QUAD RECEPTACLE
- MOUNTED 1'-6" AFF, UOI
DUPLEX RECEPTACLE
- CONTROLLED VIA OCC. SENSOR
- MOUNTED 1'-6" AFF, UOI
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
X
QUAD RECEPTACLE
(GFCI) GROUND FAULT
CIRCUIT INTERRUPTING
QUAD RECEPTACLE MOUNTED 6"
ABOVE COUNTER BACKSPLASH, UOI
X
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
DUPLEX RECEPTACLE MOUNTED 6"
ABOVE COUNTER BACKSPLASH, UOI
(GFCI) GROUND FAULT
CIRCUIT INTERRUPTING
QUAD RECEPTACLE MOUNTED 6"
ABOVE COUNTER BACKSPLASH, UOI
(GFCI) GROUND FAULT
CIRCUIT INTERRUPTING
X
DUPLEX RECEPTACLE
- FLOOR MOUNTED
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
X
QUAD RECEPTACLE
- FLOOR MOUNTED
- (X) INDICATES CIRCUIT NUMBER
(PANEL BOUNDARY AS
INDICATED ON DRAWINGS)
JUNCTION BOX:
CEILING MOUNTED
JUNCTION BOX: WALL
MOUNTED
POWER PACK
LOW VOLTAGE
SWITCH
- MOUNTED 3'-8" AFF, UON
- (#) INDICATES BUTTONS
WALL OCCUPANCY
SENSOR SWITCH
- MOUNTED 3'-8" AFF, UON
EMERGENCY CONTROLLED
POWER PACK UL 924
PLUG LOAD CONTROL
POWER PACK
E-001 ELEC. SYMBOL LEGEND, NOTES, ABBREV., FIXT. SCHED., & DWG. INDEX
E-002 ELECTRICAL SPECIFICATIONS
E-100 OVERALL SITE PLAN
E-101 LIGHTING DEMOLITION PLAN
E-102 POWER DEMOLITION PLAN
E-201 LIGHTING RENOVATION PLAN
E-202 LIGHTING PHOTOMETRICS PLAN
E-301 POWER RENOVATION PLAN
E-601 ELECTRICAL DETAILS & SCHEDULES
E-602 ELECTRICAL FIXTURE DETAILS
SHEET DESCRIPTION
ELECTRICAL DRAWING INDEX
MAIN GROUND BAR
- 120/208 V
BRANCH PANELBOARD
- SURFACE MOUNTED
- (X) INDICATES
DESIGNATION
- 277/480 V
- SURFACE MOUNTED
- (X) INDICATES
DESIGNATION
X
X
X
POLE MOUNTED WITH ARM
WALL MOUNTED EMERGENCYEXIT
LIGHT COMBO
- SHADING INDICATES FACE(S)
- ARROW(S) AND FACE(S) AS
INDICATED ON DRAWINGS
(USB) USB PORT
XX-##,a
INDICATES FIXTURE TYPE
PANEL
DESIGNATION
CIRCUIT DESIGNATION
INDICATES CONTROL
DESIGNATION (IF AVAILABLE)
NL
INDICATES UNSWITCHED
NIGHT LIGHTING
VACANCY SENSOR
- CEILING MOUNTED
- (X) INDICATES TYPE
(SEE SCHEDULE)
- (a) INDICATES SWITCH
LEG (IF APPLICABLE)
a
POST TOP
ATS AUTOMATIC TRANSFER SWITCH
X
TELECOMMUNICATIONS MAIN GROUND BAR
MGB - MAIN GROUNDING BUSBAR
KVAR - KILOVOLT AMPERE REACTIVE
MOCP - MAIN OVER-CURRENT PROTECTION
1. IT IS THE INTENT OF THESE CONTRACT DRAWINGS TO PROVIDE A COMPLETE AND WORKABLE FACILITY.
2. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, ELBOWS, OR OTHER SPECIFIC ELEMENTS THAT MAY BE REQUIRED FOR PROPER INSTALLATION OF THE WORK. SUCH WORK SHALL BE VERIFIED AT THE SITE. ADDITIONAL BENDS, OFFSETS, AND CONDUIT AS REQUIRED BY VERTICAL AND HORIZONTAL EQUIPMENT LOCATIONS OR OTHER JOB CONDITIONS, SHALL BE PROVIDED TO COMPLETE THE WORK AT NO ADDITIONAL COST
TO THE OWNER.
3. ALL WORK SHALL COMPLY WITH THE FOLLOWING CODES AND STANDARDS:
3.1. FLORIDA BUILDING CODE 8TH EDITION - 2023.
3.2. FLORIDA ENERGY CONSERVATION CODE 8TH EDITION - 2023.
3.3. FLORIDA FIRE PREVENTION CODE 8TH EDITION - 2023.
3.4. NATIONAL ELECTRICAL CODE - NFPA 70 2020.
4. MATERIALS SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC.
5. IN ACCORDANCE WITH NFPA 70, GROUND EXPOSED, NON CURRENT CARRYING METALLIC PARTS OF ELECTRICAL
EQUIPMENT, METALLIC RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN METALLIC RACEWAYS.
6. BONDING JUMPERS SHALL BE USED TO BOND CONDUIT TO ENCLOSURES, BOXES, AND EQUIPMENT WHERE
CONCENTRIC OR ECCENTRIC KNOCKOUTS ARE USED.
7. THE INSTALLATION SHALL BE ACCOMPLISHED BY WORKERS SKILLED IN THIS TYPE OF WORK. THE INSTALLATION
SHALL BE MADE SO THAT THERE IS NO DEGRADATION OF THE DESIGNED FIRE RATINGS.
8. THE CONTRACTOR SHALL INSTALL HIS WORK IN SUCH A MANNER AND AT SUCH A TIME AS WILL REQUIRE A MINIMUM
OF CUTTING AND PATCHING OF THE BUILDING STRUCTURE.
9. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT EXISTING UTILITIES FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSE FOR REPAIR OR REPLACEMENT OF THE UTILITIES OR OTHER PROPERTY
DAMAGED BY OPERATIONS IN CONJUNCTION WITH THE COMPLETION OF THIS WORK.
10. ALL BOLTS, NUTS, WASHERS, ETC. USED FOR GROUNDING AND BONDING CONNECTIONS SHALL BE SILICON
BRONZE. CONTRACTOR SHALL UTILIZE CONNECTORS TO PREVENT GALVANIC ACTION.
11. ALL EXPOSED ELECTRICAL CONDUIT VULNERABLE TO MECHANICAL DAMAGE SHALL BE RIGID GALVANIZED STEEL, UNLESS NOTED OTHERWISE. ALL OTHER CONDUIT INSIDE FACILITY SHALL BE ELECTRICAL METAL TUBE (EMT).
CONDUITS SHALL BE SUPPORTED BY SUITABLE CLAMPS, HANGERS OR STRAPS TO PROVIDE A RIGID INSTALLATION.
12. CONDUIT SUPPORTS SHALL NOT BE FASTENED OR ATTACHED TO OTHER PIPES. PERFORATED STRAP HANGERS WILL NOT BE ALLOWED. EMPTY CONDUIT SHALL BE THOROUGHLY SWABBED OUT WITH DRY SWAB TO REMOVE MOISTURE AND DEBRIS BEFORE WIRE IS DRAWN IN. END OF CONDUIT SHALL BE TIGHTLY PLUGGED UNTIL WIRE IS PULLED. NO CONDUIT SHALL BE LOCATED TO IMPAIR THE STRENGTH OF STRUCTURAL MEMBERS. MAKE CHANGES IN DIRECTION OF RUNS WITH SYMMETRICAL BENDS. DO NOT INSTALL CRUSHED OR DEFORMED CONDUITS. AVOID TRAPPED CONDUITS. PREVENT PLASTER, DIRT, OR TRASH FROM LODGING IN CONDUIT, BOXES, FITTINGS. FREE
CLOGGED CONDUITS OF OBSTRUCTIONS.
13. TRACE AND CONFIRM BRANCH CIRCUIT WIRE SIZE AND CIRCUIT BREAKER FEEDING EQUIPMENT AFFECTED BY THE
SCOPE OF WORK.
14. ALL WORK SHALL COMPLY WITH CODES AND STANDARDS LISTED IN THE CONTRACT DOCUMENTS.
15. THE DRAWINGS ARE DIAGRAMMATIC AND THE OMISSION OF AN ITEM NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM DOES NOT RELIEVE THE CONTRACTOR FROM FURNISHING AND INSTALLING THAT ITEM.
16. NOTIFY ARCHITECT/ENGINEER OF ANY CONFLICTS PRIOR TO PURCHASING EQUIPMENT AND PRIOR TO CUTTING
OPENING.
17. PRIOR TO BID, COORDINATE ALL ELECTRICAL WORK WITH MECHANICAL WORK AND OTHER TRADES. SEE
SPECIFICATIONS FOR REQUIREMENTS.
18. CONTRACTOR SHALL NOT CONCEAL ANY WORK UNTIL INSPECTED BY ELECTRICAL INSPECTOR AND/OR ENGINEER.
CONTRACTOR SHALL NOTIFY ENGINEER OF A SCHEDULED INSPECTION TIME WITHIN 72 HOURS. CONTRACTORS
SHALL NOT CONCEAL WORK UNTIL APPROVED.
19. WHERE CROWDED LOCATIONS EXIST OR WHERE THERE IS A POSSIBILITY OF CONFLICT BETWEEN TRADES, CONTRACTOR SHALL MAKE COMPOSITE DRAWINGS SHOWING THE EXACT LOCATION OF DUCTS, CONDUIT AND EQUIPMENT. DRAWINGS SHALL BE BASED ON FIELD MEASUREMENTS AND, AFTER CONSULTATION AND AGREEMENT BETWEEN THE TRADES, SHALL BE APPROVED BY THE ENGINEER BEFORE INSTALLATION OF THE WORK.
20. ALL BARE METAL SURFACES SHALL BE PRIMED AND PAINTED TO PREVENT ANY RUST, INCLUDING BUT NOT LIMITED
TO ANGLE FRAMING, EQUIPMENT SUPPORTS, MOUNTING HARDWARE, ETC.
21. ALL RACEWAYS SHALL HAVE A GREEN GROUNDING CONDUCTOR.
22. CONTRACTOR SHALL FIRESTOP ALL NEW AND EXISTING (WHERE APPLICABLE) ELECTRICAL PENETRATIONS IN FIRE RATED PARTITIONS (WALLS, FLOORS OR CEILINGS) WITH AN APPROVED FIRESTOP SYSTEM RATED FOR THE APPLICATION. FIRESTOP SYSTEM SHALL BE UL LISTED AND INSTALLED IN STRICT COMPLIANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
23. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDINGS AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL EFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED, AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF
DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
24. CAREFULLY REVIEW MECHANICAL DRAWINGS TO IDENTIFY PROPOSED ROUTING OF HVAC WORK. THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BID. THE RELOCATION OF ALL EXISTING ELECTRICAL CONDUITS, WIRING, AND BOXES AS REQUIRED TO ACCOMMODATE THE INSTALLATION OF HVAC WORK AND FIELD CONDITIONS. WHERE THE SPACE THROUGH WHICH HVAC WORK IS TO BE INSTALLED CONTAINS EXISTING CONDUIT, WIRE AND/OR BOXES THE EC SHALL RELOCATE BY INTERCEPTING AND EXTENDING THE EXISTING CONDUIT AND WIRE, AND RELOCATING JUNCTION BOXES SO THE REQUIRED NEC ACCESS AND CLEARANCE IS PROVIDED AFTER THE HVAC WORK HAS
BEEN INSTALLED.
25. THE EXISTING CONDUIT SYSTEM MAY BE RETAINED FOR WORK SHOWN ON THESE DRAWINGS. WHERE EXISTING CONDUIT IS REUSED, IT'S MATERIALS AND METHODS OF INSTALLATION WHEN THE PROJECT IS COMPLETE, SHALL CONFORM TO THE SPECIFICATIONS AS IF IT WERE NEW. ALL COUPLINGS AND CONDUCTORS SHALL BE TIGHTENED.
26. ALL DEBRIS SHALL BE REMOVED FROM THE SITE DAILY TO AN APPROVED DUMPING FACILITY WHICH MEETS FEDERAL AND LOCAL REQUIREMENTS. NO BURNING ON SITE WILL BE ALLOWED. OWNER'S DUMPSTERS SHALL NOT
BE USED.
27. WHERE CUTTING CORING OR REMOVAL OF CONDUITS, BOXES OR ANY ELECTRICAL ITEM IS REQUIRED, THE FINISHED SURFACE SHALL BE PATCHED AND PAINTED SO THAT NO EVIDENCE OF THE FORMER INSTALLATION
REMAINS.
28. THE OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL ELECTRICAL EQUIPMENT AND DEVICES INDICATED ON THE CONTRACT DOCUMENTS TO BE REMOVED. ALL ITEMS NOT CLAIMED BY THE OWNER SHALL BE REMOVED FROM THE
JOB SITE BY THIS CONTRACTOR AND PROPERLY DISPOSED OF.
29. ALL RACEWAY TERMINATION'S SHALL HAVE BUSHINGS AND BE GROUNDED WHERE RACEWAY IS METAL.
30. COORDINATE ALL MECHANICAL LOADS, VOLTAGES AND LOCATIONS WITH MECHANICAL CONTRACTOR.
31. ALL POWER AND FIRE ALARM WIRING SHALL BE CONCEALED WHERE PRACTICAL. SURFACE MOUNTED RACEWAY SHALL BE WIREMOLD (OR EQUIVALENT) METALLIC SURFACE RACEWAY. CONTRACTOR SHALL PROVIDE AND INSTALL ALL RACEWAY, BOXES, AND FITTINGS REQUIRED FOR A COMPLETE INSTALLATION. CABLING IN NON-PUBLIC AREAS
MAY BE IN EMT.
32. ELECTRICAL OUTLETS OR BOXES SHALL NOT REDUCE THE FIRE-RESISTANT RATING OF FIRE RESISTANT RATED
WALL(S), AND SHALL COMPLY WITH 714.4, FBC 2023 REQUIREMENTS.
33. GFCI WEATHER PROOF RECEPTACLES SHALL HAVE ENCLOSURE THAT IS WEATHER PROOF WHILE IN USE.
34. COORDINATE WITH THE GENERAL CONTRACTOR SO THAT OCCUPIED BUILDINGS OR PORTIONS OF BUILDINGS ARE
NEVER WITHOUT FIRE ALARM PROTECTION THROUGHOUT ALL PHASES OF CONSTRUCTION.
35. ALL WORK SHALL BE CONSTRUCTED TO MEET THE PHASING REQUIREMENTS OF THE PROJECT AS OUTLINED IN THE
DRAWINGS, SPECIFICATIONS AND PER DIVISION 1 OF THE SPECIFICATIONS.
36. PRIOR TO BID, CHECK LEAD TIMES OF ALL EQUIPMENT IN THE PROJECT. IF NECESSARY TO MEET THE PROJECT SCHEDULE, BID SHALL INCLUDE THE COST OF QUICK SHIP PREMIUMS. ALLOW TIME FOR NORMAL SHOP DRAWING
PREPARATION AND REVIEW.
37. VERIFY MOUNTING HEIGHTS OF ALL DEVICES PRIOR TO INSTALLATION. MOUNTING HEIGHTS NOT SHOWN ON THESE
PLANS.
38. COLOR CODING:
A. BRANCH CIRCUIT AND FEEDERS:
280Y/120 VOLTS 480Y/277 VOLTS
PHASE A BLACK BROWN
PHASE B RED ORANGE
PHASE C BLUE YELLOW
NEUTRAL WHITE GRAY
GROUND GREEN GREEN
B. THE ABOVE COLORS SHALL BE USED UNLESS REQUIREMENTS OF CODE REQUIRE DIFFERENT COLORS.
VOLTAGE DROP
VOLTAGE DROP IN ACCORDANCE WITH FLORIDA BUILDING CODE
8TH EDITION (2023) ENERGY CONSERVATION CODE CHAPTER 4,
SECTION C405.5.3 WAS TAKEN INTO ACCOUNT FOR THIS PROJECT.
E-001
ELEC. SYMBOL LEGEND, NOTES,
ABBREV., FIXT. SCHED., & DWG.
INDEX
VIF - VERIFY IN FIELD
1 FWC RESPONSE 03/26/26
B
C
1 2 3 4 5
2019-4115
10/14/2025
AHP
AHP
MSA
A
B
C
1 2 3 4 5
Al ex an de r H . P ar ris h
PE
2AL
EX
ANDER H . PARR ISH
PROFESS I ONA L ENG I N
EE
R
L I CENSE
F L O R I D A
STATE OF
No. 87322
This item has been electronic signed and sealed by Alexander H. Parrish on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
CITY OF DAYTONA BEACH
MAIN STREET PIER
PARTIAL BOARDWALK AND
RAILING REPLACEMENT
SEAL:
DRAWN BY:
APPROVED BY:
SCALE:
CHECKED BY:
DATE:
PROJECT NUMBER:
PROJECT TITLE:
ISSUE:
PROJECT INFORMATION:
SHEET TITLE:
SHEET NUMBER:
www.graef-usa.com
2300 Maitland Center Parkway, Suite 210 Maitland, FL 32751 407 / 659 6500
CERT # 4270
PERMIT SET
GENERAL ELECTRICAL PROVISIONS
WORK INCLUDED IN CONTRACT
MENTION OF ANY ARTICLE, OPERATION OR METHOD REQUIRES THAT CONTRACTOR SHALL
PROVIDE SAME AND PERFORM EACH OPERATION IN COMPLETE ACCORDANCE WITH
CONDITIONS STATED. CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, EQUIPMENT,
AND TRANSPORTATION AS NECESSARY TO COMPLETE PROJECT IN COMPLIANCE WITH
CONTRACT DOCUMENTS. IN GENERAL, WORK INCLUDES EVERYTHING ESSENTIAL FOR
COMPLETE ELECTRICAL SYSTEM IN OPERATING ORDER AS SHOWN ON DRAWINGS AND
INDICATED IN SPECIFICATIONS.
ALL MATERIALS SHALL BE SUITABLY STORED AND PROTECTED PRIOR TO INSTALLATION AND
ALL WORK SHALL BE PROTECTED AFTER INSTALLATION, DURING CONSTRUCTION, AND PRIOR
TO ACCEPTANCE.
SHALL ANY CONFLICTS OCCUR WITHIN OR BETWEEN SPECIFICATIONS, DRAWINGS, OR OTHER
DOCUMENTS, CONTRACTOR SHALL INCLUDE THE MORE EXPENSIVE ALTERNATIVE.
BIDDING PROCEDURES
BASE BID SHALL INCLUDE ALL LABOR, MATERIALS AND EQUIPMENT AS SHOWN ON
CONSTRUCTION DRAWINGS AND AS REQUIRED AND SPECIFIED.
BASE BID SHALL NOT INCLUDE ANY CONDITIONS OR QUALIFYING STATEMENTS, SHALL BE IN
STRICT ACCORDANCE WITH SPECIFICATION REQUIREMENTS AND SHALL BE BASED UPON
INSTALLATION OF MATERIALS AND EQUIPMENT AS SPECIFIED.
PERMITS AND LICENSES
CONTRACTOR SHALL PREPARE AND SUBMIT REQUIRED APPLICATIONS AND DRAWINGS FOR
ALL CONSTRUCTION PERMITS AND APPROVALS TO AUTHORITIES HAVING JURISDICTION OVER
PROJECT. ALL LICENSES AND PERMITS REQUIRED SHALL BE SECURED AND PAID FOR BY
CONTRACTOR AND SHALL BE SECURED BY THE CONTRACTOR BEFORE STARTING WORK.
SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY
ELECTRICAL CONTACTOR SHALL RETAIN THE SERVICES OF A THIRD PARTY TO PERFORM A
SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY FOR THE PROJECT.
ELECTRICAL CONTRACTOR SHALL PROVIDE THE THIRD PARTY WITH ALL NECESSARY
INFORMATION TO COMPLETE THE STUDY.
STUDY SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL
CONTRACTOR SHALL NOT RELEASE ANY ELECTRICAL DISTRIBUTION EQUIPMENT FOR
MANUFACTURE BEFORE THE STUDY HAS BEEN SUBMITTED, REVIEWED, AND APPROVED.
STANDARDS AND CODES
WORK SHALL BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE, AND LOCAL CODES,
ORDINANCES, LAWS, AND REGULATIONS. COMPLY WITH ALL APPLICABLE OSHA
REGULATIONS.
MATERIALS SHALL HAVE UL OR ETL LABEL WHERE UL OR ETL STANDARD AND / OR TEST
EXISTS.
ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH RECOGNIZED INDUSTRY
STANDARDS AND SHALL FOLLOW EQUIPMENT MANUACTURER'S PUBLISHED INSTRUCTIONS.
MATERIALS AND EQUIPMENT
MATERIALS AND EQUIPMENT REQUIRED SHALL BE NEW, UNLESS OTHERWISE INDICATED.
EQUIPMENT SUPPLIED SHALL BE BASED ON MATERIALS AND EQUIPMENT OF
MANUFACTURERS SPECIFIED. APPROVED EQUALS WILL BE ALLOWED.
SUBMITTALS
THE FOLLOWING EQUIPMENT SHALL BE SUBMITTED FOR REVIEW AND APPROVAL BY THE
ENGINEER:
1. SHORT CIRCUIT / COORDINATION / ARC FLASH STUDY
2. ELECTRICAL SERVICE AND DISTRIBUTION EQUIPMENT.
3. ELECTRICAL OUTLETS.
4. LIGHTING CONTROL DEVICES
5. LIGHTING FIXTURES
6. STRUCTURED CABLING
CLEANING AND PAINTING
RUBBISH RESULTING FROM WORK SHALL BE REMOVED AND DISPOSED OF ON DAILY BASIS IN
SUCH MANNER AS TO BE ACCEPTABLE TO OWNER.
CONTRACTOR SHALL CLEAN ALL EXPOSED IRON WORK, INTERIOR AND EXTERIOR OF
CABINETS AND PULL BOXES, ETC.
WHERE PAINTED SURFACES OF EQUIPMENT HAVE BEEN DAMAGED OR RUSTED DURING
CONSTRUCTION, CONTRACTOR SHALL PAINT SAME TO MATCH FINAL.
TESTS AND ACCEPTANCE
OPERATION OF EQUIPMENT AND ELECTRICAL SYSTEMS DOES NOT CONSTITUTE
ACCEPTANCE OF WORK BY OWNER. FINAL ACCEPTANCE IS TO BE MADE AFTER CONTRACTOR
HAS ADJUSTED HIS EQUIPMENT AND DEMONSTRATED THAT IT FULFILLS REQUIREMENTS OF
DRAWINGS AND SPECIFICATIONS.
UPON COMPLETION OF INSTALLATION, CONTRACTOR SHALL FURNISH CERTIFICATES OF
APPROVAL AND OCCUPANCY PERMITS FROM AUTHORITIES HAVING JURISDICTION.
CONTRACTOR SHALL DEMONSTRATE THAT ALL WORK IS COMPLETE AND IN PERFECT
OPERATING CONDITION, WITH RACEWAY AND CONDUIT SYSTEM PROPERLY GROUNDED,
WIRING FREE FROM GROUNDS AND SHORTS, AND ENTIRE INSTALLATION IS FREE FROM ANY
PHYSICAL DEFECTS.
IN PRESENCE OF ENGINEER AND OWNER, CONTRACTOR SHALL DEMONSTRATE PROPER
OPERATION OF ALL SYSTEMS.
UNLESS OTHERWISE INDICATED, ALL WORK SHALL BE GUARANTEED FOR A MINIMUM OF ONE
(1) YEAR AFTER DATE OF FINAL ACCEPTANCE.
DEFINITIONS
1. A/E - ARCHITECT AND / OR ENGINEER.
2. PROVIDE - FURNISHED, INSTALLED, AND COMPLETELY WIRED AND CONNECTED BY
ELECTRICAL CONTRACTOR.
3. NEC - NATIONAL ELECTRICAL CODE.
4. CONTRACTOR - PERSON OR GROUP RESPONSIBLE FOR PROJECT CONSTRUCTION.
ELECTRICAL SERVICE AND DISTRIBUTION
PRODUCTS
NEW PANELBOARDS SHALL BE PROVIDED AS FOLLOWS:
1. POWER PANELS - SQUARE D I-LINE STYLE.
2. 480Y/277 VOLT LIGHTING PANELS - SQUARE D NF STYLE PANELBOARDS WITH
BOLT-ON BREAKERS.
3. 208Y/120 VOLT LIGHTING PANELS - SQUARE D NQ STYLE PANELBOARDS WITH
BOLT-ON BREAKERS.
PROVIDE NEW DISTRIBUTION / BRANCH PANELS COMPLETE WITH CIRCUIT BREAKERS AND AIC
RATING AS INDICATED.
PANELBOARD BUSSING SHALL BE COPPER.
NEW TRANSFORMERS SHALL BE SELF-VENTILATED, DRY-TYPE TRANSFORMERS WITH THE
FOLLOWING CHARACTERISTICS:
1. COPPER OR ALUMNIMUM WINDINGS.
2. PRIMARY AND SECONDARY VOLTAGES AS INDICATED ON THE PLANS.
3. MINIMUM OF SIX 2-1/2% PRIMARY SIDE TAPS. TWO OF THE SIX SHALL BE ABOVE THE
RATED PRIMARY VOLTAGE AND FOUR OF THE SIX BEING BELOW THE RATED
PRIMARY VOLTAGE.
4. RATED FOR 150° C RISE BY RESISTANCE, WITH OVERALL 220° C INULATION RATING.
SAFETY SWITCHES SHALL BE HEAVY DUTY, FUSED WITH CLASS R INDICATING TYPE FUSES.
PROVIDE THREE SPARE FUSES OF EACH FUSE TYPE TO OWNER. PROVIDE NEMA 1 SWITCHES
FOR INDOOR USE, NEMA 3R FOR OUTDOOR, AND NEMA 4X FOR CORROSIVE AREAS.
MULTI-PHASE CIRCUIT BREAKERS SHALL HAVE SINGLE HANDLE TRIPS FOR ALL PHASES.
HANDLE TIES, OR OTHER FIELD INSTALLED COMMON TRIP HARDWARE IS NOT PERMITTED.
PROVIDE ELECTRICAL DISTRIBUTION EQUIPMENT WITH SURGE PROTECTIVE DEVICES WHERE
INDICATED ON THE PLANS AND ON THE ONE-LINE DIAGRAM.
EXECUTION
PROVIDE TEMPORARY SERVICE IN AREAS OF CONSTRUCTION FOR ALL TRADES. INCLUDE
LIGHTING AND 120 VOLT POWER. COST OF TEMPORARY POWER SHALL BE PAID BY OWNER.
PROVIDE NEW UTILITY SERVICE IN ACCORDANCE WITH DRAWINGS AND AS REQUIRED BY
LOCAL UTILITY. COORDINATE AND PROVIDE ALL EQUIPMENT INCLUDING BUT NOT LIMITED TO
CONDUITS, METER SOCKETS, TERMINATION BOXES, METER STACKS, TRANSFORMER
CONCRETE PADS, BOLLARDS, CONDUCTORS, AS REQUIRED BY LOCAL UTILITY. CONTRACTOR
IS RESPONSIBLE FOR METER APPLICATION AND PAYING ALL FEES INVOLVED.
EXISTING PERMANENT SERVICE SHALL REMAIN IN PLACE. NEW FEEDERS AND PANEL
DISTRIBUTION BOARDS SHALL BE PROVIDED IN ACCORDANCE WITH DRAWINGS.
GROUNDING SHALL BE IN ACCORDANCE WITH ALL CODES.
CONTRACTOR TO PROVIDE ALL ARC FLASH LABELING ON ELECTRICAL EQUIPMENT AS
REQUIRED BY NFPA 70E, STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE.
GROUNDING
PRODUCTS
ALL GROUNDING CONDUCTORS SHALL BE COPPER.
GROUND RODS SHALLBE COPPER-CLAD STEEL, ¾” DIAMETER, 10' LONG.
MECHANICAL CONNECTIONS SHALL BE MADE WITH EXOTHERMIC WELDS OR WITH
MECHANICAL CONNECTORS AT THE CONTRACTOR'S OPTION. MECHANICAL CONNECTORS
SHALL BE BRONZE AND SHALL BE IRREVERSIBLE.
GROUND BUSSES SHALL BE 1/4” THICK BY 2” HIGH IN CROSS SECTION. LENGTHS AS
INDICATED ON THE PLANS.
EXECUTION
REMOVE SURFACE CONTAMINANTS AT ALL CONNECTION POINTS.
GROUND ELECTRICAL SYSTEMS AND EQUIPMENT AS REQUIRED BY THE NEC, THE LOCAL
UTILITY, AND LOCAL ORDINANCES.
PROVIDE SEPARATE GROUNDING CONDUCTOR WITH EACH FEEDER CONDUIT AND BRANCH
CIRCUIT CONDUIT. DO NOT RELY ON METAL RACEWAY AS THE SOLE EQUIPMENT GROUND
FOR ELECTRICAL CIRCUITS. BOND GROUND CONDUCTOR AT BOTH ENDS OF RACWAYS WITH
BOLTED GROUNDING LUGS.
SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH THE NEC.
FIRMLY ATTACH GROUNDS BEFORE CIRCUITS ARE ENERGIZED.
ELECTRICAL WIRING METHODS
ACCEPTABLE WIRING METHODS SHALL BE INDIVIDUAL CONDUCTORS IN CIRCULAR
RACEWAYS. EXCEPTIONS ARE AS FOLLOWS:
1. CONDUCTORS FOR SYSTEMS RATED 50 VOLTS AND LESS AND ROUTED 8' AFF OR
HIGHER, MAY BE INSTALLED IN FREE AIR WITHOUT RACEWAYS IN UNFINISHED
MECHANICAL ROOMS, ELECTRICAL ROOMS, TELECOM CLOSETS. CONDUCTORS
INSTALLED UNDER THIS EXCEPTION SHALL HAVE INSULATION RATINGS COMPLIANT
WITH THE NEC, APPROPRIATE TO THE CONDITIONS WHERE THE CONDUCTORS ARE
LOCATED.
2. CONDUCTORS FOR SYSTEMS RATED 50 VOLTS AND LESS AND ROUTED ABOVE
ACCESSIBLE CEILINGS CONCEALED FROM VIEW.
a. MAY BE INSTALLED IN FREE AIR WITHOUT RACEWAYS AT THE CONTRACTOR'S
OPTION.
b. REVIEW PLANS OF OTHER TRADES AND IDENTIFY ANY AIR-HANDLING PLENUMS.
CONDUCTORS INSTALLED UNDER THIS EXCEPTION SHALL HAVE INSULATION
RATINGS COMPLIANT WITH THE NEC, APPROPRIATE TO THE CONDITIONS WHERE
THE CONDUCTORS ARE LOCATED.
3. WHERE SPECIFICALLY INDICATED OTHERWISE ON THE DRAWINGS.
BUILDING WIRE AND CABLE
PRODUCTS
SINGLE CONDUCTOR INSULATED WIRE.
SOLID OR STRANDED CONDUCTOR FOR #10 AWG AND SMALLER. CONDUCTOR #8 AWG AND
LARGER SHALL BE STRANDED.
COPPER CONDUCTORS ONLY.
INSULATION VOLTAGE RATING: 600 VOLTS, RATED 75° CELSIUS, UNLESS OTHERWISE
INDICATED.
ACCEPTABLE INSULATION TYPES:
1. CONCEALED OR EXPOSED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE
TYPE THW, THHN / THWN OR XHHW INSULATION.
2. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE TYPE THW
INSULATION.
3. EXTERIOR LOCATIONS: USE ONLY BUILDING WIRE TYPE THW, OR USE INSULATION.
4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE TYPE THW, OR USE
INSULATION.
WIRING CONNECTORS FOR CONDUCTORS #10 AWG AND SMALLER. 3M SCOTCH-LOK
COMPRESSION TYPE SOLDERLESS CONNECTORS WITH PLASTIC OUTER SHELL.
WIRING CONNECTORS FOR CONDUCTORS #8 AWG AND LARGER. SOLDERLESS
COMPRESSION TYPE CONNECTORS, TOOL AND DIE APPLIED, OF TYPE THAT WILL NOT
LOOSEN UNDER VIBRATION OR NORMAL STRAINS. BURNDY “HYDENT" TYPE OR EQUIVALENT.
SPLIT BOLT CONNECTORS ARE NOT ACCEPTABLE.
RUBBER INSULATING ELECTRICAL TAPE: SCOTCH 3M MODEL 23, 30-MIL TAPE.
EXECUTION
CONDUCTOR SHALL NOT BE SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS.
CONDUCTOR SHALL NOT BE SMALLER THAN #14 AWG FOR CONTROL CIRCUITS.
ALL WIRES SHALL BE NEW, DELIVERED TO SITE IN UNBROKEN CARTONS, AND SHALL BE LESS
THAN ONE YEAR OLD OUT OF MANUFACTURER'S STOCK.
DO NOT DRAW CONDUCTORS INTO CONDUITS UNTIL BUILDING IS ENCLOSED AND
WATERTIGHT AND UNTIL WORK THAT MAY CAUSE CONDUCTOR DAMAGE HAS BEEN
COMPLETED.
EACH TAP, JOINT, OR SPLICE IN CONDUCTORS #8 AWG AND LARGER SHALL BE TAPED WITH
TWO HALF-LAP LAYERS OF VINYL PLASTIC ELECTRICAL TAPE AND FINISH WRAP OF COLOR
CODING TAPE, WHERE REQUIRED BY THE NEC OR LOCAL CODES.
CABLE SPLICES SHALL BE MADE ONLY IN DISTRIBUTION AND JUNCTION BOXES.
NEATLY TRAIN AND BUNDLE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
SIZE CONDUIT, OUTLET BOXES, AND OTHER RACEWAY SYSTEM COMPONENTS IN
ACCORDANCE WITH NEC REQUIREMENTS AS MINIMUM.
MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED. EACH BRANCH CIRCUIT SHALL CONTAIN
A DEDICATED NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR. A SINGLE NEUTRAL
SHARED BETWEEN MULTIPLE PHASE CONDUCTORS ARE NOT PERMITTED.
INSTALL WIRE COLORS IN ACCORDANCE WITH FOLLOWING:
1. BLACK AND RED FOR SINGLE PHASE CIRCUITS AT 120/ 240 VOLTS.
2. BLACK, RED, AND BLUE FOR CIRCUITS AT 120 / 208 VOLTS SINGLE OR THREE-PHASE.
3. BROWN, ORANGE, AND YELLOW FOR CIRCUITS AT 277 / 480 VOLTS SINGLE OR
THREE-PHASE.
NEUTRAL CONDUCTORS: WHITE. WHEN TWO OR MORE NEUTRALS ARE LOCATED IN ONE
CONDUIT, INDIVIDUALLY IDENTIFY EACH WITH PROPER CIRCUIT NUMBER.
RACEWAYS AND BOXES
PRODUCTS
METAL CONDUIT:
1. RIGID METAL CONDUIT (RMC).
2. INTERMEDIATE METAL CONDUIT (IMC).
3. ELECTRICAL METALLIC TUBING (EMT).
METAL CONDUIT FITTINGS (BOX TERMINATORS AND COUPLINGS):
1. STEEL OR MALLEABLE IRON, ZINC GALVANIZED, OR CADMIUM PLATED.
2. SET SCREW STYLE FASTENERS.
3. BOX CONNECTORS SHALL HAVE NON-METALLIC INSULATED THROATS.
4. DO NOT USE ALUMINUM OR DIE CAST FITTINGS.
LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC):
1. INTERLOCKED STEEL CONSTRUCTION WITH PVC SUNLIGHT RESISTANT JACKET.
2. FITTINGS: NEMA FB 1. LIQUID-TIGHT, SUITABLE FOR GROUNDING, SUITABLE FOR WET
LOCATIONS, TAPERED THREADED HUB, NON-METALLIC MATERIALS.
NON-METALLIC CONDUIT:
1. PRODUCT DESCRIPTION: NEMA TC 2: SCHEDULE 40 OR 80 PVC, UL LISTED, AND AS
REQUIRED BY NEC. SUNLIGHT RESISTANT.
2. RATED FOR 90° CELSIUS CABLE.
3. FITTINGS AND CONDUIT BODIES: NEMA TC 3, SCHEDULE 40 OR 80, TO MATCH
CONDUIT.
OUTLET BOXES:
1. INTERIOR OUTLET BOXES SHALL BE GALVANIZED STAMPED STEEL WITH
PRE-PUNCHED KNOCK OUTS. SIZE SHALL BE 4-11/16” SQUARE, 2-½” DEEP MINIMUM.
2. EXTERIOR OUTLET BOXES SHALL BE CAST FERRALLOY, TYPE FD, CAST FERALLOY.
FURNISH GASKETED COVER BY BOX MANUFACTURER.
EXECUTION
MINIMUM RACEWAY SIZE: 1/2", UNLESS OTHERWISE INDICATED.
SPLIT, CRUSHED, OR SCARRED CONDUIT IS NOT ACCEPTABLE.
WELDED CONDUIT IS NOT ACCEPTABLE.
PVC CONDUIT MAY NOT BE USED IN INTERIOR OF BUILDING.
RACEWAY AND BOXES LOCATED AS INDICATED ON DRAWINGS, AND AT OTHER LOCATIONS
REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE
WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE
LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM.
UNDERGROUND (OUTSIDE) MORE THAN 5'-0" OUTSIDE FOUNDATION WALL: PROVIDE
SCHEDULE 40 NON-METALLIC CONDUIT, UNLESS OTHERWISE INDICATED.
UNDERGROUND (OUTSIDE) WITHIN 5'-0" FROM FOUNDATION WALL TO INSIDE OF BUILDING:
PROVIDE RIGID STEEL CONDUIT. ONCE INSIDE BUILDING PROVIDE STEEL CONDUIT. PROVIDE
INTERLOCKING RUBBER GASKETS AROUND RACWAYS PASSING BELOW GRADE THROUGH
BUILDING FOUNDATION WALLS. UTILIZE LINK-SEAL TYPE GASKETS OR EQUIVALENT.
WET, DAMP, AND OUTDOOR LOCATIONS: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST
METAL JUNCTION AND PULL BOXES.
DRY LOCATIONS: PROVIDE METAL CONDUIT (RMC, IMC, OR EMT) UNLESS OTHERWISE
INDICATED. PROVIDE STAMPED STREEL OR SHEET METAL BOXES.
SUPPORT RACEWAY USING TWO-HOLE MALLEABLE IRON STRAPS, LAY-IN ADJUSTABLE
HANGERS, CLEVIS HANGERS, OR SPLIT HANGERS. PROVIDE LIGHT GAUGE STEEL FRAMING
FOR RACEWAY TRAPEZE HANGERS OR FOR OTHER RACEWAY SUPPORT AS REQUIRED.
SECURE CONDUITS IN PLACE WITH MALLEABLE CORROSION-PROOF ALLOY STRAPS OR
HANGERS. CONDUIT STRAPS USED IN CORROSIVE AREAS SHALL BE PVC COATED.
DO NOT SUPPORT RACEWAY WITH WIRE OR PERFORATED PIPE STRAPS. REMOVE WIRE USED
FOR TEMPORARY SUPPORTS.
ROUTE INTERIOR RACEWAYS PARALLEL WITH OR PERPENDICULAR TO WALLS, CEILINGS, AND
OTHER PRIMARY ARCHITECTURAL AND STRUCTURAL ELEMENTS.
CUT CONDUIT SQUARE USING SAW OR PIPE CUTTER: DE-BURR CUT ENDS. BRING CONDUIT TO
SHOULDER OF FITTINGS. FASTEN SECURELY.
JOIN NON-METALLIC CONDUIT USING CEMENT AS RECOMMENDED BY MANUFACTURER. WIPE
NON-METALLIC CONDUIT DRY AND CLEAN BEFORE JOINING. APPLY FULL EVEN COAT OF
CEMENT TO ENTIRE AREA INSERTED IN FITTING. ALLOW JOINT TO CURE FOR MINIMUM 20
MINUTES.
INSTALL CONDUIT HUBS TO FASTEN CONDUIT TO CAST BOXES IN DAMP AND WET LOCATIONS.
INSTALL NO MORE THAN EQUIVALENT OF THREE (3) 90 DEGREE BENDS BETWEEN BOXES.
INSTALL CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS.
INSTALL HYDRAULIC ONE-SHOT BENDER TO FABRICATE OR FACTORY ELBOWS FOR BENDS IN
METAL CONDUIT LARGER THAN 2" SIZE.
AVOID MOISTURE TRAPS: INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN
CONDUIT SYSTEM.
PROVIDE WATERTIGHT CONDUIT SYSTEM WHERE INSTALLED IN WET LOCATIONS SUCH AS
UNDERGROUND, OR WHERE EMBEDDED IN CONCRETE.
CONDUIT RUNS THAT EXTEND THROUGH AREAS OF DIFFERENT TEMPERATURE OR
ATMOSPHERIC CONDITIONS OR THAT ARE PARTLY INDOORS AND PARTLY OUTDOORS SHALL
BE SEALED, DRAINED, AND INSTALLED IN MANNER THAT WILL PREVENT DRAINAGE OF
CONDENSED OR ENTRAPPED MOISTURE INTO CABINETS. MOTORS, OR EQUIPMENT
ENCLOSURES.
CONDUIT CONNECTIONS AT MOTORS AND OTHER EQUIPMENT THAT VIBRATES:
1. PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT.
2. USE DOUBLE LOCKNUTS AND INSULATED BUSHINGS WITH THREADS FULLY
ENGAGED.
EXTERIOR UNDERGROUND DIRECT BURIED CONDUITS SHALL BE BURIED AT DEPTH OF NOT
LESS THAN 30" BELOW GRADE. UNDERGROUND CONDUITS SHALL SLOPE 1/8" PER FOOT FOR
PROPER DRAINAGE. CONDUITS SHALL DRAIN TOWARD MANHOLES AND JUNCTION BOXES.
CONDUITS SHALL NOT PITCH TO ELECTRICAL EQUIPMENT.
INSTALL KNOCKOUT CLOSURES IN UNUSED OPENINGS IN BOXES.
CLEAN INTERIOR OF BOXES TO REMOVE DUST, DEBRIS, AND OTHER MATERIAL.
CLEAN EXPOSED SURFACES AND RESTORE FINISH.
MOTOR WIRING
APPLICABLE MOTORS FURNISHED UNDER GENERAL CONSTRUCTION, HVAC, AND PLUMBING
TRADES OF WORK. MOTOR STARTERS FURNISHED LOOSE (NOT INTEGRAL TO EQUIPMENT
BEING CONTROLLED) SHALL BE FURNISHED BY THE CONTRACTOR THAT PROVIDES THE
MOTOR AND INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR IN APPROVED MANNER AT
LOCATIONS ESTABLISHED BY CONTRACTOR SUPPLYING EQUIPMENT.
ALL LINE VOLTAGE WIRING FROM STARTER TO MOTOR SHALL BE BY ELECTRICAL
CONTRACTOR. CONTROL WIRING (REGARDLESS OF VOLTAGE) SHALL BE BY THE
CONTRACTOR RESPONSIBLE FOR PROVIDING THE MOTOR.
PROVIDE HORSEPOWER RATED MOTOR DISCONNECT SWITCHES AS REQUIRED BY THE NEC.
ELECTRICAL CONTRACTOR SHALL VERIFY ALL MATERIALS ARE PROVIDED FOR COMPLETE
ELECTRICAL INSTALLATION.
SPECIAL PURPOSE OUTLETS
SPECIAL PURPOSE OUTLET SHALL BE LOCATED AS REQUIRED BY EQUIPMENT BEING SERVED.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ELECTRICAL CHARACTERISTICS OF
ACTUAL EQUIPMENT BEING FURNISHED FOR PROJECT PRIOR TO RACEWAY ROUGH-IN.
ELECTRICAL CONTRACTOR SHALL VERIFY ALL MATERIALS ARE PROVIDED FOR COMPLETE
ELECTRICAL INSTALLATION.
ELECTRICAL RECEPTACLES
PRODUCTS
PROVIDE ALL WIRING DEVICE TYPES FROM A SINGLE MANUFACTURER.
FOR BIDDING PURPOSES, DEVICE COLOR AND DEVICE COVER PLATES IN FINISHED ARERAS
SHALL BE WHITE. VERIFY COLOR AND MATERIAL OF EXISTING DEVICES AND COVER PLATES
AND PROVIDE NEW PLATES TO MATCH EXISTING.
ACCEPTABLE MANUFACTURERS ARE:
1. HUBBELL.
2. LEVITON.
3. ARROW-HART, INC.
4. PASS & SEYMOUR/LEGRAND
RECEPTACLES
1. GENERAL USE DUPLEX CONVENIENCE RECEPTACLE: HEAVY DUTY, SPECIFICATION
GRADE, 20 AMP, 125 VOLT, NEMA 5-20R HUBBELL CAT. NO. HBL5362.
2. TAMPER-RESISTANT: COMMERCIAL SPECIFICATION GRADE, 20 AMP DUPLEX, 125
VOLT, NEMA 5-20R, HUBBELL CAT. NO. BR20TR.
3. WEATHER-RESISTANT: CORROSION RESISTANT HEAVY DUTY, SPECIFICATION
GRADE, 20 AMP DUPLEX, 125 VOLT, NEMA 5-20R, HBL53CM62 (COLOR - YELLOW)
4. GFCI RECEPTACLE: HEAVY DUTY, SPECIFICATION GRADE, SELF-TESTING, 20 AMP,
125 VOLT, NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFST20.
5. TAMPER-RESISTANT GFCI: HEAVY DUTY COMMERCIAL GRADE, 20 AMP DUPLEX, 125
VOLT, NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFTR20.
6. WEATHER-RESISTANT GFCI: EXTRA HEAVY DUTY GRADE, 20 AMP DUPLEX, 125 VOLT,
NEMA 5-20R, UL 2006 COMPLIANT, HUBBELL CAT. NO. GFR5362.
WEATHERPROOF COVERPLATE: GASKETED DIE CAST METAL PLATE WITH HINGED AND
GASKETED DEVICE COVERS. COVER SHALL ALLOW CORDS TO BE PLUGGED IN AND COVER
CLOSED. PROVIDE INTERMATIC WP1010MC FOR SINGLE DUPLEX RECEPTACLES OR
WP1030MC FOR DOUBLE (QUAD) DUPLEX RECEPTACLES.
EXECUTION
RECEPTACLES N FINISHED SPACES SHALL BE FLUSH MOUNTED.
RECEPTACLES IN UNOCCUPIED ELECTRICAL ROOMS, IT ROOMS, AND MECHANICAL ROOMS
MAY BE INSTALLED SURFACE MOUNTED IN 4” SQUARE, ROUNDED CORNER, SURFACE
MOUNTED ELECTRICAL BOXES WITH MATCHING ROUNDED CORNER, RAISED METAL COVER
PLATES.
DO NOT INSTALL DEVICES UNTIL AFTER WALL FINISHES HAVE BEEN COMPLETELY APPLIED.
RECEPTACLES SHALL NOT BE INSTALLED BACK-TO-BACK IN COMMON STUD WALL CAVITIES
SHARED BETWEEN ADJACENT ROOMS.
INSTALL DEVICES AND WALL PLATES PLUMB AND LEVEL.
INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP.
CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER
AND BRANCH CIRCUIT EQUIPMENT GROUNDING CONDUCTOR.
INSTALL GALVANIZED STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN
UNFINISHED AREAS, ABOVE ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS.
DO NOT USE TERMINALS ON WIRING DEVICES (HOT OR NEUTRAL) FOR FEED_THROUGH
CONNECTIONS, LOOPED OR OTHERWISE MAKE CIRCUIT CONNECTIONS VIA WIRE
CONNECTORS AND PIGTAILS.
PROVIDE A LAYER OF ELECTRICAL TAPE AROUND PERIMETER SIDES OF EACH WIRING DEVICE
SO THAT TERMINATIONS ARE INSULATED.
WHERE GFI PROTECTED RECEPTACLES ARE INDICATED ON DRAWINGS, EACH RECEPTACLE
INDICATED SHALL BE A GFI RECEPTACLE. STANDARD RECEPTACLES PROTECTED WITH AN
UPSTREAM GFI RECEPTACLE SHALL NOT BE APPROVED.
VERIFY EACH RECEPTACLE DEVICE IS ENERGIZED.
TEST EACH RECEPTACLE DEVICE FOR PROPER POLARITY.
TEST EACH GFCI RECEPTACLE DEVICE FOR PROPER OPERATION
MARK PANEL AND CIRCUIT NUMBER SERVING DEVICE ON BACKSIDE OF DEVICE PLATE WITH A
PERMANENT MARKING SYSTEM THAT DOES NOT SHOW THROUGH FRONT OF PLATE.
LIGHTING FIXTURES
PRODUCTS
REFER TO PLANS AND/OR TO LIGHTING FIXTURE SCHEDULE.
RECESSED FIXTURES SHALL INCLUDE THERMAL CUTOFF PROTECTION IN ACCORDANCE WITH
THE NEC OR LOCAL CODES, WHICHEVER APPLICATION DICTATES. PROVIDE IC RATED
FIXTURES WHEN REQUIRED BY THE NEC.
LIGHT FIXTURES WITH INTEGRAL LED'S SHALL BE PROVIDED WITH THE FOLLOWING COLOR
CHARACTERISTICS. SEE LIGHTING FIXTURE SCHEDULE FOR ANY EXCEPTIONS.
1. LED'S WITH A COLOR RENDERING INDEX OF 80 OR HIGHER.
2. LED COLOR TEMPERATURE:
a. GENERAL INTERIOR LIGHT FIXTURES- 3500° K.
b. TOILET ROOM LIGHT FIXTURES - 3000° K.
c. EXTERIOR LIGHT FIXTURES - 4000° K.
PROVIDE LED LIGHT FIXTURES WITH 0-10 VDC DIMMING CAPABILITY WITH INTEGRAL DRIVERS
UNLESS NOTED OTHERWISE IN THE LIGHTING FIXTURE SCHEDULE.
EXECUTION
WHERE LAMPS ARE NEEDED, PROVIDE FIXTURES COMPLETE WITH INITIAL FILL OF LAMPS AS
SCHEDULED. PROVIDE BALLASTS AS SPECIFIED.
CONTRACTOR SHALL VERIFY CEILING CONSTRUCTION PRIOR TO ORDERING FIXTURES.
PROVIDE RECESSED FIXTURES WITH TRIM CHARACTERISTICS COMPATIBLE WITH CEILING
TYPES WHERE FIXTURES ARE TO BE INSTALLED.
LIGHTING CONTROLS
PRODUCTS
DEVICE COLORS AND DEVICE COVER PLATES SHALL BE WHITE, UNLESS NOTED OTHERWISE.
MANUAL CONTROLS
UNLESS OTHERWISE INDICATED ACCEPTABLE MANUFACTURERS FOR MANUAL SWITCHES
ARE:
1. HUBBELL.
2. LEVITON.
3. ARROW-HART, INC.
4. PASS & SEYMOUR.
MANUAL SWITCHES:
1. SINGLE POLE SWITCH: 20 AMPS, 120-277 VOLT, SPECIFICATION GRADE, BACK OR
SIDE WIRED EQUAL TO HUBBELL CAT. NO. HBL1221.
2. THREE-WAY SWITCH: 20 AMPS, 120-277 VOLT, SPECIFICATION GRADE, BACK OR SIDE
WIRED EQUAL TO HUBBELL CAT. NO. HBL1223.
HARD-WIRED OCCUPANCY / VACANCY SENSORS
APPROVED MANUFACTURERS:
1. WATTSTOPPER.
2. LEVITON.
3. MYTECH.
4. HUBBELL.
5. SENSOR SWITCH.
6. LUTRON.
LINE VOLTAGE DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR:
1. SENSOR SHALL USE PASSIVE INFRARED AND ULTRASONIC DETECTION METHOD FOR
DETECTING ROOM OCCUPANCY. UNIT SHALL FIT IN/ON A STANDARD SINGLE GANG
OPENING AND REQUIRE ONLY TWO WIRES AND A GROUNDED BOX FOR OPERATION.
2. RATED CAPACITY: 1000 WATTS MINIMUM AT 120 VOLTS, 60 HZ, 1200 WATTS MINIMUM
AT 277 VOLTS, 60 HZ, LARGER SIZE TO ACCOMMODATE LOAD AS SHOWN ON
DRAWINGS.
3. SWITCH SHALL HAVE MANUAL ON/OFF BUTTON.
4. BASIS OF DESIGN MODEL WATTSTOPPER: DSW-301 SERIES.
LINE VOLTAGE CEILING-MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR:
1. SENSOR SHALL EMPLOY BOTH INFRARED AND ULTRASONIC SENSING METHODS TO
DETECT ROOM OCCUPANCY. UNIT SHALL FIT ON A STANDARD, RECESSED,
OCTAGON BOX, DESIGNED FOR CEILING MOUNTING.
2. RATED CAPACITY SHALL BE 20 AMPS AT 120 OR 277 VOLTS.
3. AREA OF COVERAGE SHALL BE 1000 SQUARE FOOT MINIMUM. UNIT SHALL BE
PROVIDED WITH A DIP SWITCH TO ALLOW EITHER DETECTION TECHNOLOGY TO BE
INDEPENDENTLY CONFIGURED.
4. UNIT SHALL BE PROVIDED WITH A DIP SWITCH TO SELECT ONE OF FIVE DIFFERENT
SENSING MODES AS DICTATED BY ENVIRONMENTAL FACTORS.
5. PROGRAMMABLE RESPONSE TIME, 5 TO 30 MINUTES.
6. BASIS OF DESIGN MODEL: WATTSTOPPER: DT-355.
LOW VOLTAGE OCCUPANCY/VACANCY SENSORS. LOW VOLTAGE SENSORS SHALL BE USED
IN CONJUNCTION WITH POWER PACKS THAT CONTACT LINE VOLTAGE LOAD SWITCHING
CONTACTS AND CONTROL POWER FOR OPERATING ASSOCIATED SENSORS. POWER PACKS
SHALL HAVE THE FOLLOWING CHARACTERISTICS:
1. LINE VOLTAGE LOAD CONTROL CONTACTS RATED AT 20 AMPS.
2. RATED FOR 120 AND 277 VOLTS AC.
3. PLENUM RATED.
4. PROVIDES 24 VOLTS DC CONTROL POWER TO OPERATE ASSOCIATED SENSORS.
5. BASIS OF DESIGN: WATTSTOPPER BZ SERIES.
LOW VOLTAGE DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR:
1. SENSOR SHALL USE PASSIVE INFRARED AND ULTRASONIC DETECTION METHOD FOR
DETECTING ROOM OCCUPANCY.
2. UNIT SHALL FIT IN/ON A STANDARD SINGLE GANG OPENING AND REQUIRE ONLY TWO
WIRES AND A GROUNDED BOX FOR OPERATION.
3. SWITCH SHALL HAVE MANUAL ON/OFF BUTTON.
LOW VOLTAGE CEILING-MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR:
1. SENSOR SHALL EMPLOY BOTH INFRARED AND ULTRASONIC SENSING METHODS TO
DETECT ROOM OCCUPANCY.
2. UNIT SHALL FIT ON A STANDARD, RECESSED, OCTAGON BOX, DESIGNED FOR
CEILING MOUNTING.
3. AREA OF COVERAGE SHALL BE 1000 SQUARE FOOT MINIMUM. UNIT SHALL BE
PROVIDED WITH A DIP SWITCH TO ALLOW EITHER DETECTION TECHNOLOGY TO BE
INDEPENDENTLY CONFIGURED.
4. UNIT SHALL BE PROVIDED WITH A DIP SWITCH TO SELECT ONE OF FIVE DIFFERENT
SENSING MODES AS DICTATED BY ENVIRONMENTAL FACTORS.
5. PROGRAMMABLE RESPONSE TIME, 5 TO 30 MINUTES
6. BASIS OF DESIGN MODEL: WATTSTOPPER: DT-300.
DIGITAL LIGHTING CONTROLS
DIGITAL LIGHTING CONTROLS. DIGITAL LIGHTING CONTROLS ARE THOSE SYSTEMS THAT USE
DIGITAL COMMUNICATIONS BETWEEN LIGHTING CONTROL AND SENSING DEVICES TO
CONTROL BUILDING LIGHTING SYSTEMS. IN ORDER TO ENSURE COMPATIBILITY, ALL SYSTEM
DEVICES SHALL BE BY THE SAME MANUFACTURER UNLESS SPECIFICALLY NOTED
OTHERWISE.
DIGITAL LIGHTING CONTROL SYSTEM SHALL CONSIST OF INDIVIDUAL SYSTEM COMPONENT
THAT COMMUNICATE WITH EACH OTHER OVER SIGNAL VOLTAGE DATA COMMUNICATIONS
STYLE CABLE.
ACCEPTABLE MANUFACTURERS:
1. ACUITY BRANDS NLIGHT SYSTEM.
2. WATTSTOPPER DLM SERIES.
POWER/RELAY PACKS:
1. 16 AMP POWER CAPACITY.
2. PROVIDES POWER FOR SYSTEM COMMUNICATIONS BUS.
3. TWO RJ45 COMMUNICATIONS PORTS.
4. 120/277 VOLT RATING.
5. PUSHBUTTON PROGRAMMABLE.
6. PLENUM RATED.
7. PROVIDE WITH 0-10 VDC DIMMING CAPABILITY.
8. BASIS OF DESIGN: ACUITY NLIGHT NPP16 SERIES.
DIGITAL SWITCH STATIONS:
1. MULTIPLE PUSHBUTTONS WILL COMPROMISE A SINGLE SWITCH STATION LOCATION.
2. CONFIGURED AS INDICATED ON THE PLANS, DESIGNED TO MOUNT IN A SINGLE
GANG BOX OPENING.
3. SHALL CONTAIN RJ-45 NETWORK PORTS FOR COMMUNICATIONS CABLING
TERMINATIONS/BUS CONNECTION.
4. FURNISH INDIVIDUAL BUTTONS WITH REMOVABLE CLEAR COVER FOR LABELING
CONTROLLED LOADS.
5. WHITE BUTTONS AND WHITE COVER-PLATES.
6. BASIS OF DESIGN ACUITY NPODM SERIES.
DIGITAL OCCUPANCY SENSORS:
1. CEILING MOUNTED SENSORS.
2. DUAL TECHNOLOGY PASSIVE INFRARED AND MICROPHONIC TECHNOLOGIES.
3. TWO RJ45 COMMUNICATIONS PORTS.
4. PROVIDE WITH AUXILIARY RELAY FOR INTERFACE TO HVAC DEVICES.
5. MATTE WHITE COLOR.
6. BASIS OF DESIGN: ACUITY NLIGHT NCM XX RJB SERIES.
DIGITAL DAYLIGHT SENSORS:
1. PHOTO-CELL SENSOR FOR ON/OFF AND DIMMING CONTROL OF ASSOCIATED LIGHT
FIXTURES.
2. DESIGNED FOR CEILING MOUNTING.
3. WHITE COLOR
4. FIELD ADJUSTABLE SET POINTS.
5. REAR RJ45 PATCH CABLE AND SPLITTER
6. BASIS OF DESIGN: ACUITY NLIGHT NCM ADCX RJB SERIES.
DIGITAL COMMUNICATIONS/CONTROL WIRING AS REQUIRED BY DEVICE MANUFACTURER.
EXECUTION
INSTALL ALL DEVICES IN ACCORDANCE WITH INDUSTRY STANDARDS AND IN COMPLIANCE
WITH DEVICE MANUFACTURER'S RECOMMENDATIONS.
SEE SECTION ON WIRING METHODS. THESE REQUIREMENTS SHALL BE FOLLOWED FOR ALL
LINE VOLTAGE WIRING AND FOR LOW VOLTAGE SIGNAL WIRING.
ALL LIGHTING CONTROLS SHALL BE PROGRAMMED AS DESIRED BY THE OWNER, COMPLIANT
WITH APPLICABLE ENERGY CODE REQUIREMENTS. CONTRACTOR SHALL INCLUDE IN THEIR
BASE BID ANY COSTS ASSOCIATED WITH TRAINING PROVIDED BY A FACTORY AUTHORIZED
LIGHTING CONTROL AGENT. INCLUDE A MINIMUM OF 8 HOURS OF OWNER TRAINING, USING A
FACTORY CERTIFIED LIGHTING CONTROL PRODUCT REPRESENTATIVE.
STRUCTURED CABLING
PRODUCTS
SHIELDED TWISTED-PAIR CAT 6 CABLE SHALL MEET ALL THE REQUIREMENTS FOR
ANSI/TIA/EIA-568-C - COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD,
PART 2: TRANSMISSION PERFORMANCE SPECIFICATIONS FOR 4 PAIN 100 OHM CATEGORY 6
CABLING.
JACKS SHALL BE MODULAR RJ-45.
ALL JACKS AND CONNECTORS SHALL BE CERTIFIED TO CATEGORY 6 (CAT 6 CABLE) / 6A (CAT
6A CABLE) STANDARDS, COMPONENT RATED.
EXECUTION
HORIZONTAL CABLE LINKS TELECOMMUNICATIONS OUTLET IN WORK AREA TO
TELECOMMUNICATIONS ROOM (TR) OR EQUIPMENT ROOM (ER).
HORIZONTAL CABLES CONNECT TO VOICE (CAT 6), DATA (CAT 6), CAMERA (CAT 6) AND
WIRELESS ACCESS POINTS (WAP) ((2) CAT 6A).
ALL HORIZONTAL CABLES SHALL UTILIZE RJ-45 MODULAR JACKS, TERMINATED TO T-568B
WIRING SCHEME.
1. PROVIDE MULTIPLE JACKS INA SINGLE “OUTLET” AS INDICATED ON THE PLANS.
2. AN OUTLET IS DEFINED AS A SINGLE ELECTRICAL OUTLET BOX WITH A SINGLE-GANG
FACEPLATE.
DEMOLITION
CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY EXISTING CODE VIOLATIONS OBSERVED
DURING THE COURSE OF PERFORMING HIS WORK. THE ENGINEER WILL DECIDE IF
CORRECTIVE ACTION NEEDS TO BE TAKEN. CORRECTIVE ACTIONS THAT CHANGE THE SCOPE
OF THE WORK WILL BE CONSIDERED A CHANGE ORDER AND WILL BE PROCESSED
ACCORDINGLY.
EXISTING BUILDINGS SHALL REMAIN IN SERVICE DURING CONSTRUCTION.
PRIOR TO DEMOLITION OR ALTERATION OF STRUCTURES, THE FOLLOWING SHALL BE
ACCOMPLISHED:
1. OWNER RELEASE OF SUCH STRUCTURE.
2. DISCONNECTION OF ELECTRICAL POWER TO EQUIPMENT AND CIRCUITS REMOVED
OR AFFECTED BY DEMOLITION WORK.
3. ELECTRICAL SERVICES REROUTED OR SHUT OFF OUTSIDE AREA OF DEMOLITION.
4. COORDINATE SEQUENCING WITH OWNER AND OTHER CONTRACTORS.
5. SURVEY AND RECORD CONDITION OF EXISTING FACILITIES TO REMAIN IN PLACE
THAT MAY BE AFFECTED BY DEMOLITION OPERATIONS.
POWER OUTAGES AND INTERRUPTIONS IN BUILDING SYSTEMS SHALL BE HELD TO A MINIMUM
AND SHALL BE DONE AT A TIME CONVENIENT TO OWNER. TIME OF ALL OUTAGES SHALL BE
SCHEDULED WITH OWNER AND ALL OTHER TRADES AFFECTED BY OUTAGE AT LEAST TEN
WORKING DAYS IN ADVANCE.
IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. OWNER MAY KEEP ANY
EQUIPMENT IN DEMOLITION AREAS. CONTRACTOR SHALL DELIVER EQUIPMENT OWNER
WANTS SALVAGED TO AREA IN BUILDING DESIGNATED BY OWNER. CONTRACTOR SHALL
REMOVE ALL MATERIALS IN DEMOLISHED AREA NOT SALVAGED FROM SITE. CONTRACTOR
SHALL OBTAIN RELEASE OF ALL MATERIALS BEFORE DISPOSITION.
AFTER DEMOLITION OPERATIONS ARE COMPLETED, SURVEY CONDITIONS AND RESTORE
EXISTING FACILITIES TO THEIR PRE-DEMOLITION CONDITION.
REMOVE ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE
CEILINGS. CUT CONDUIT CAST INTO CONCRETE STRUCTURS FLUSH WITH WALLS AND
FLOORS. PATCH SURFACES AROUND CONDUITS.
REMOVE CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE
WITH NEW INSTALLATION.
DE-ENERGIZE AND DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS
SCHEDULED FOR REMOVAL.
DISCONNECT OR SHUT OFF POWER TO AREAS WHERE ELECTRICAL WORK IS TO BE
REMOVED. REMOVE ELECTRICAL FIXTURES, EQUIPMENT AND RELATED SWITCHES, OUTLETS,
CONDUIT AND WIRING WHICH ARE NOT PART OF FINAL PROJECT.
REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW
CONSTRUCTION.
REMOVE ABANDONED GROUNDING AND BONDING COMPONENTS, FASTENERS AND
SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ABANDONED
COMPONENTS ABOVE ACCESSIBLE CEILINGS.
CUT EMBEDDED SUPPORT ELEMENTS FLUSH WITH WALLS AND FLOORS.
FEEDERS, BRANCH CIRCUITS, AND OTHER SYSTEM WIRING WHICH ARE TO REMAIN IN
SERVICE BUT WHICH ARE PRESENTLY ROUTED THROUGH AREAS BEING DEMOLISHED SHALL
BE REROUTED AROUND DEMOLITION AREA.
WHERE EXISTING BRANCH CIRCUITS ARE TO BE EXTENDED OR MODIFIED, EXISTING CONDUIT
THAT HAS NOT BEEN REMOVCED MAY BE REUSED AT CONTRACTOR'S DISCRETION.
EXISTING CONDUITS THAT ARE REMOVED FROM THEIR EXISTING LOCATION SHALL NOT BE
REUSED.
EXISTING WIRING MAY BE SPLICED AND USED TO EXTENT THAT IT WAS NOT REMOVED.
EXISTING CONDUCTORS THAT HAVE BEEN REMOVED SHALL NOT BE RE-USED.
REMOVE AND PROTECT ITEMS REQUESTED BY OWNER TO BE SALVAGED AND TRANSPORT
TO LOCATION ON SITE DESIGNATED BY OWNER.
CONTRACTOR SHALL TOUR DEMOLITION AREAS WITH OWNER TO DETERMINE STATUS OF ALL
EQUIPMENT TO BE REMOVED DURING DEMOLITION.
ALL EQUIPMENT THAT IS TO BE SALVAGED FOR REUSE BY THE OWNER SHALL BE REMOVED
BY CONTRACTOR AND TRANSPORTED TO AN OWNER DESIGNATED STORAGE AREA ON SITE.
RACEWAY, BOXES, AND SUPPORTING DEVICES SHALL BECOME PROPERTY OF CONTRACTOR
AND SHALL BE REMOVED FROM SITE AND DISPOSED OF BY THE CONTRACTOR.
REMOVED EQUIPMENT SHALL BE DISPOSED OF BY CONTRACTOR UNLESS SPECIFICALLY
OTHERWISE INDICATED ON DRAWINGS OR REQUESTED BY OWNER. CONTRACTOR SHALL
PROVIDE TRANSPORT FOR DISPOSAL.
ANY HAZARDOUS MATERTIALS REMOVED FROM SERVICE AS PART OF THIS PROJECT SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR IN COMPLETE COMPLIANCE WITH ALL
FEDERAL, STATE, AND LOCAL ENVIRONMENTAL LAWS. EXAMPLES OF SUCH MATERIALS
WOULD INCLUDE LIGHT FIXTURE LAMPS AND LIGHT FIXTURE BALLASTS THAT CONTAIN
REGULATED ELEMENTS.
ELECTRICAL SPECIFICATIONS
E-002
ELECTRICAL SPECIFICATIONS
E-101
A E-102
A E-201
B E-101
B E-102
B E-201
A E-202
A E-301
B E-202
B E-301
MATCHLINE
MATCHLINE
MATCHLINE
M…