EITB_OPD260249_Real_Time_Crime_Center_Renovation_-_Exhibit_B-Building_Plans.pdf

PDF 14 MB Posted

Attached to
Real Time Crime Center Renovation
Solicitation number
ITB# OPD/260249
Issued by
Marion County, Orlando City, Florida

About this file

This file set comprises architectural and engineering construction documents for a Real Time Crime Center renovation project at the Ocala Police Department (402 South Pine Avenue, Ocala, Florida 34471), issued under ITB# OPD/260249. The scope of work involves an interior remodeling and buildout of approximately 3,500 square feet within the existing police facility to create a new Emergency Operations Center/Real Time Crime Center (EOC/RTCC) with multiple specialized rooms including command centers, conference rooms, server facilities, and administrative spaces. The project requires complete mechanical, electrical, and plumbing systems installation, fire protection modifications, access flooring systems, automatic sliding entrances, and comprehensive finishes including drywall partitions, ceiling systems, flooring, and paint. A mandatory pre-bid meeting and site visit is scheduled for Monday, December 15, 2025, at 9:00 AM at the project location. The construction documents referenced include Exhibit A (Scope of Work), Exhibit B (Building Plans), Exhibit C (HVAC Plans), and Exhibit D (Photos), with detailed specifications provided across architectural, mechanical, plumbing, electrical, and fire protection drawings.

The project design is based on the 2023 Florida Building Code (8th Edition) and applicable standards including NFPA codes, NEC 2020, and local ordinances. Key mechanical systems include four new roof-top units (RTU-11 through RTU-14) ranging from 1,300 to 3,000 CFM capacity, one outside air unit (OAU-7) providing 750 CFM, and a 225-AMP UPS battery backup system for 30-minute runtime at full load located in the server room. Electrical work includes a new 100 KW UPS system with bypass capability, three electrical panels (AL4, G4, and U4 sections), SPD surge protection, and extensive lighting and receptacle distribution utilizing occupancy sensors and dimmable LED fixtures. Plumbing scope includes a new stainless steel sink with gooseneck faucet, floor drains, and connection to existing water and sewer systems. Fire protection requires modification of the existing sprinkler system per NFPA 13 standards with relocation and addition of sprinkler heads. All contractors must submit shop drawings within 30 days of contract award, coordinate with multiple trades, and perform testing, balancing, and commissioning prior to project completion. Contractors are responsible for all demolition, patching, painting, and restoration to "like new condition."

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5 6 7 8 9 10 a

B

C

D

E

F

G

H

8A 9A

A

B

C

D

E

F

G

G1

H

1097 865

CONTROL

TABLE

A000

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A NEW EOC RTCC FOR:

OCALA POLICE DEPARTMENT

402 SOUTH PINE AVENUE,

OCALA, FLORIDA 34471

INDEX OF DRAWINGS

BUILDING DATA

CODE REFERENCE

TYPE OF CONSTRUCTION (FBC CHAPTER 6): TYPE IIIB (UNPROTECTED & SPRINKLERED)

OCCUPANCY (FBC CHAPTER 3):

RESIDENTIAL - GROUP B - BUSINESS

GENERAL BUILDING LIMITATIONS (FBC TABLE 504.3

a

, 504.4 a, b

, & 506.2 a, b

GROUP B

TYPE IIIB - UNPROTECTED & SPRINKLED

UNDER 30'-0"

ALLOWABLE:

751'-0"

PROVIDED:

MAX HEIGHT

4MAX STORIES 2

MAX AREA

76,000 PER FLOOR

AREA OF REMODEL:

TYPE IIIB

BEARING WALLS;

EXTERIOR

INTERIOR

BUILDING ELEMENT

STRUCTURAL FRAME INCLUDING COLUMNS, GIRDERS,TRUSSES

NON-BEARING WALLS AND PARTITIONS EXTERIOR

NON-BEARING WALLS AND PARTITIONS INTERIOR

FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS

FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS

FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS-TABLE 601

A NEW EMERGENCY OPERATIONS CENTER/REAL TIME CRIME CENTER FOR OCALA POLICE DEPARTMENT, CONSTRUCTION SHALL CONSIST OF METAL STUD WALL PARTITIONS. COMPLETE MECHANICAL, ELECTRICAL &

PLUMBING SHALL BE INSTALLED IN THIS NEW TENANT. BUILDING LOCATION IS 402 SOUTH PINE AVENUE, OCALA, FLORIDA.

PERMIT DOCUMENTS BY OTHERS

1) FINAL ELECTRICAL ENGINEERING DOCUMENTS ARE TO BE PREPARED BY A FLORIDA LICENSED MASTER

ELECTRICIAN SUBCONTRACTOR AND SUBMITTED WITH THESE DOCUMENTS FOR PERMITTING. ELECTRICAL

SUBCONTRACTOR SHALL CONFIRM LOADS OF EQUIPMENT, FIXTURES, RECEPTACLES, AND APPLIANCES WITH

BOTH GENERAL CONTRACTOR AND MECHANICAL SUB CONTRACTOR PRIOR TO CONSTRUCTION.

2) THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR FINAL ENGINEERING DESIGN OF THE MECHANICAL

SYSTEMS, GAS PIPING (IF APPLICABLE), ALL MANUALS 'J', 'D', & 'N' AS REQUIRED, AND FLORIDA ENERGY CODE

COMPLIANCE FORMS. FINAL MECHANICAL ENGINEERING DOCUMENTS AND ENERGY CODE CALCULATIONS ARE TO

BE SUBMITTED FOR PERMITTING WITH THESE DOCUMENTS. MECHANICAL CONTRACTOR MUST ALSO TEST AND

BALANCE HVAC SYSTEM FOR PROPER OPERATION PRIOR TO OWNER ACCEPTANCE.

3) PLUMBING FIXTURES, FAUCETS, LIGHTING FIXTURES, SHALL BE SELECTED BY OWNER WITHIN CONTRACT

ALLOWANCE.

GENERAL CONDITIONS

A000 COVER, PROJECT INFORMATION

LIFE SAFETY PLANS

LS101 LIFE SAFETY PLAN

ARCHITECTURAL PLANS

A201D FLOOR PLAN - DIMENSIONS & TAGS

WALL SECTIONS & DETAILS

A500 TYPICAL WALL SECTIONS

A500.1 TYPICAL WALL SECTIONS

A501 INTERIOR ELEVATIONS

A502 TATE ACCESS FLOOR SYSTEM DETAILS

SCHEDULES

A601 WINDOW, DOOR SCHEDULES

INTERIOR ELEVATION

REFLECTED CEILING

A801 FIRST FLOOR - REFLECTED CEILING PLAN

SPECIFICATIONS

SP101 TATE ACCESS FLOOR SYSTEM SPECIFICATIONS

SP102 STANLEY ACCESS DOOR SYSTEM SPECIFICATIONS

SP103 STANLEY ACCESS DOOR SYSTEM SPECIFICATIONS & DETAILS

SQ104 GLASS WALL PARTITION SPECIFICATIONS

MECHANICAL

M-1 MECHANICAL LEGEND, NOTES & SPECIFICATIONS

M-2 MECHANICAL PLANS

M-3 MECHANICAL SCHEDULES AND DETAILS

MS-1 MECHANICAL LEGEND, NOTES & SPECIFICATIONS

MS-2 MECHANICAL LEGEND, NOTES & SPECIFICATIONS

PLUMBING

P-1 PLUMBING LEGEND, NOTES, SPECS & SCHEDULES

FIRE PROTECTION

FP1 FIRE PROTECTION PLAN

ELECTRICAL

E-1 ELECTRICAL LEGEND, NOTES, & SPECIFICATIONS

E-2 ELECTRICAL POWER PLANS

E-3 ELECTRICAL LIGHTING PLAN

E-4 ELECTRICAL PANEL SCEDULES

APPLICABLE CODES:

FLORIDA BUILDING CODE 2023 8th EDITION

(BUILDING, PLUMBING, FUEL & GAS, MECHANICAL & ACCESSIBILITY VOLUMES)

NEC 2020 NATIONAL ELECTRICAL CODE

FFPC 2020 7th EDITION

ASCE 7-22 EDITION

FIRE ALARM REQUIREMENTS:

(FBC 907, NFPA 72)

FIRE ALARM IS REQUIRED IN THIS BUILDING PER APPLICABLE CODES.

FIRE SPRINKLER REQUIREMENTS:

(FBC 903, NFPA 101)

FIRE SPRINKLER SYSTEM IS REQUIRED PER APPLICABLE CODES.

AREA AREA/PERSON POPULATION

BUSINESS

USE

MEANS OF EGRESS (FBC CHAPTER 10) POPULATION/ OCCUPANCY LOAD (FROM FBC - TABLE 1004.5)

REQUIRED PROVIDED

BUSINESS

300' 285'MAXIMUM TRAVEL DISTANCE FBC - TABLE 1017.2

50' N/A

2 5

MEANS OF EGRESS (FBC CHAPTER 10)

OCCUPANCY CLASSIFICATION

MAXIMUM DEAD-END CORRIDOR - FBC 1020.5

26x(0.2)=5.2"

237.5"

TOTAL # OF EXITS - TABLE 1006.3.2 & 1022 - 1027

44" 60"

EGRESS WIDTH PER PERSON LEVEL - FBC 1005.3.1 & 1005.3.2

32" 33.5" MIN

MINIMUM CORRIDOR AISLE WIDTH TABLE 1020.2

MINIMUM CLEAR OPENING OF EXIT DOORS - FBC 1010.1 - 1010.1.1

BUSINESS AREA - 3,818 ACROSS

SF OF REMODELED AREA

150 GROSS 26 PERSONS

OCCUPANT LOAD FIRE RESISTANCE RATING UNSPRINKLED

BUSINESS GREATER THAN 30 1

OCCUPANCY CLASSIFICATION

TABLE 1020.1 CORRIDOR FIRE RESISTANCE RATING

3818 SF

COMMON PATH OF EGRESS TRAVEL 75' LESS THAN 75'

AREA OF WORK

KEY PLAN

DEMOLITION

1. ROOM 300

1.1. REMOVE MOP SINK

1.2. REMOVE TRASH CHUTES (FROM SECOND TO FIRST FLOORS)

1.3. REMOVE GYP BOARD WRAP FROM COLUMNS AND ASSOCIATED FRAMING

1.4. REMOVE VIDEO LIGHT CONTROL CONTROLLER

1.5. REMOVE LIGHT FIXTURES AND STORE ONSITE FOR RELOCATION

1.6. REMOVE (2) TWO SOUNDPROOF ROOMS; STORE (1) ONE IN ROOM 300; REINSTALL (1) IN

ROOM 300

2. ROOMS 199 AND 200

2.1. REMOVE EXISTING WALL DIVIDING THE TWO ROOMS AND ALL ASSOCIATED DOOR AND

ELECTRICAL

2.2. REMOVE EXISTING CEILING IN ROOM 199

2.3. REMOVE (2) TWO EXISTING SOUNDPROOF ROOMS

2.4. REMOVE EXISTING CARPET AND STORE IN ROOM 300

PROPOSED CONSTRUCTION

3. NEW EOC/RTCC OFFICES

3.1. ROOM 300

3.1.1. ADD LEFT-HAND DOOR FROM HALL 201

3.1.2. ADD DOOR ACCESS CARD READER

3.1.3. MOVE LIGHT SWITCH FOR EXITING AREA LIGHTS (EXISTING) TO ADDED DOOR

LOCATION

3.1.4. RELOCATE FIRE STROBE LIGHT - HALL 201

3.1.5. RELOCATE CAMERA - HALL 201

3.2. 6" RAISED ACCESS FLOORING

3.2.1. ROOMS 301, 303, 304, 305, 306, 307, 308, 309, 310, 311

3.3. ROOM 301 E.O.C.

3.3.1. CARPET TILE FLOORING

3.3.2. VIDEO WALL COMPONENTS LOCATIONS SUPPLIED BY CONSTANT TECHNOLOGIES

(CAT6 POWER LOCATIONS LAYOUT)

3.3.3. FILLER WALL BY ROOM 309 ADJACENT TO ROOM 200

3.4. ROOM 302 OFFICE/STORAGE

3.4.1. SEE PLAN FOR SIZE

3.4.2. 36" RIGHT-HAND SWING DOOR

3.5. ROOM 303 CONFERENCE ROOM

3.5.1. SEE PLAN FOR SIZE

3.5.2. (2) GLASS WALLS: SOUTH AND WEST

3.5.3. 36" LEFT-HAND SWING DOOR - FULL GLASS (MATCH GLASS WALL MATERIAL) NO

MORTISE LOCK

3.6. ROOM 304 UTILITY CLOSET

3.6.1. 3'-8" DEEP ; LINE UP WITH ADJACENT WALL (1')

3.6.2. DOUBLE DOORS; NO LOCK

3.6.3. 17' X 1' WALL; COVER PIPES ADD DOOR; NO LOCK IN FRONT OF FIRE PANEL

3.7. ROOM 305 INTEL

3.7.1. SEE PLAN FOR SIZE

3.7.2. 36" RIGHT-HAND SWING DOOR

3.7.3. WALK-THRU OPENING BETWEEN ROOMS 305 AND 308

3.7.4. ADD COLUMN WALL FROM COLUMN TO WEST WALL

3.8. ROOM 306 E.O.C. SERGEANT

3.8.1. SEE PLAN FOR SIZE

3.8.2. 36" LEFT-HAND SWING DOOR WITH LOCK

3.8.3. GLASS WINDOW 4' X 6' STEEL FRAME TO MATCH EXISTING IN BUILDING

3.9. ROOM 307 E.O.C. LIEUTENANT

3.9.1. SEE PLAN FOR SIZE

3.9.2. 36" RIGHT-HAND SWING DOOR WITH LOCK

3.9.3. GLASS WINDOW 4' X 6' STEEL FRAME TO MATCH EXISTING IN BUILDING

3.10. ROOM 308 CAMERA TECHNICIAN

3.10.1. SEE PLAN FOR SIZE

3.10.2. 36" RIGHT-HAND SWING DOOR

3.11. ROOM 309 BREAK ROOM

3.11.1. SEE PLAN FOR SIZE

3.11.2. WALK-THRU OPENINGS (NO DOORS)

3.11.3. BASE AND OVERHEAD CABINETS

3.11.4. STANDARD 36" REFRIGERATOR OPENING WITH WATER

3.11.5. 8" DEEP STAINLESS STEEL SINK

3.11.6. UNDER COUNTER ICE MAKER

3.11.7. FLOOR DRAIN UNDER ICE MAKER

3.12. ROOM 310 MAIN ENTRY/FOYER

3.12.1. SEE PLAN FOR SIZE

3.12.2. A PAIR OF 24" GLASS SLIDING DOORS WITH AUTO OPEN FROM CARD ACCESS

CONTROL WITH FROSTED GLAZING

3.12.3. 4' POLICE EMBLEM IN TILE FLOOR

3.12.4. ADD DOOR ACCESS CARD READER IN ROOM 203 8' FROM DOOR ON RIGHT SIDE

WALL

3.12.5. MOTION SENSOR TO EXIT E.O.C. FROM ROOM 310

3.12.6. 6" RAISED FLOOR RAMP

3.13. ROOM 311 EXIT DOOR AREA

3.13.1. SEE PLAN FOR SIZE

3.13.2. REPLACE DOOR - CORE, KEEP CARD READER

3.13.3. FLOOR - DOWN RAMP, CARPET AT END OF RAMP TO MATCH HALL

3.13.4. REWIRE LIGHT SWITCH FOR E.O.C. LIGHTS. 3 ZONE LIGHT - CENTER, SIDES AND

VIDEO WALL - ALL DIMMABLE

3.14. ROOM 312 FOYER

3.14.1. SEE PLAN FOR SIZE

3.14.2. ADD DOOR HANDLE AND LOCK TO DOOR

3.14.3. ADD WALK THRU FOR POLYGRAPH ROOM TO SIDE UP IN 300 RM

3.14.4. ADD ACCESS CARD READER FOR THIS DOOR ON HALLWAY SIDE

3.15. ROOM 313 POLYGRAPH OFFICE

3.15.1. SEE PLAN FOR SIZE

3.15.2. LH DOOR SWING

3.16. ROOM 314 POLYGRAPH ROOMS

3.16.1. REINSTALL 1 SOUNDPROOF ROOM, STORE SECOND ROOM IN 300 ROOM-WHISPER

ROOM

3.17. ROOM 199, 200

3.17.1. NEW CEILING GRID WORK AND TILES (BLACK)

3.17.2. CEILING HEIGHT 120" APPROX

3.17.3. SINGLE LIGHT SWITCH

3.17.4. NEW CARPET

3.17.5. NEW - IN NORTH WALL 36"X60" WITH METAL FRAME-MATCH EXISTING WINDOW IN

BUILDING. IN WALL OF RM 310.

3.17.6. INSTALL SERVER RACK SEE RACK LAYOUT

3.18. CEILING

3.18.1. CEILING GRID-ACCOMMODATE FOR 24"X24" LAY IN TILE, (ALL BLACK TILES AND GRID

WORK)

3.18.2. ROOMS 301, 309 CEILING HEIGHT AT 162" APPROX. ABOVE VIDEO WALL SCREEN.

3.18.3. ROOMS 302, 303, 305, 306, 307, 308, 312, 313, CEILING HEIGHT AT 108" APPROX.

3.18.4. ROOM 312, WHITE AND GRID WORK.

3.18.5. RM 310 108" FOR 20' THEN ANGLE UP TO RM 301 AT 162" AT OR BEFORE RM 200

CORNER. APPROX.

3.19. ELECTRICAL

3.19.1. NATIONAL ELECTRICAL CODE

3.19.2. POWER VOLTAGE: 1) 460VOLT HVAC ROOF TOP UNITS, POWER FROM RM 58 TO

UNITS. 2) 208/240 VOLT 3 PHASE PANELS. 3) 120 VOLT PANELS.

3.19.3. 3 FORMS OF POWER: BUILDING POWER, GENERATOR POWER, U.P.S. BATTERY

BACKUP

3.19.4. NEW GENERATOR AND ELECTRICAL PANEL INSTALLED IN RM 304

3.19.5. NEW 225 AMP U.P.S. PANEL LOCATED IN RM 200

3.19.6. LIGHTING - ALL ROOMS: 1) ALL LED WITH DIMMABLE FIXTURES - 2'X4' LAY IN. 2) 3

LIGHTING CIRCUITS IN ROOM 301. 3) DIMMABLE SWITCHES IN ALL LOCATIONS.

3.19.7. ELECTRICAL - RECEPTACLES: 1) QUADS IN RAISED FLOOR AT EACH CENTER DESKS

(8) - RM 301. 2) STANDARD IN ALL OFFICES AND CONFERENCE ROOM. 3) ROOM 301 -

VIDEO WALL 16 QUADS - NORTH WALL. 4) 6 - DUPLEXS BETWEEN CABINETS AND

VIDEO WALL. 5) ROOM 308-4 EXTRA DUPLEX - EVENLY SPACED OUT WITH

STANDARDS.

3.20. GENERATOR POWER FOR UPS POWER BATTERY BACKUP

3.20.1. GALAXY - GVS 50K MODULAR U.P.S. BATTERY BACKUP FOR 30 MINUTES RUN TIME

AT FULL LOAD.

3.20.2. NEW 208/240 VOLT FEED FROM ROOM 58 (FROM MAIN ELECTRICAL ROOM)

3.20.3. 225-AMP PANEL AND DISCONNECT LOCATE IN 200 RM.

3.20.4. GENERATOR PROVIDE TO: 1) RECEPTACLES; 1 IN EACH OFFICE, 8 IN RM 305, 4 IN RM

308, RM 309 ALL AT STANDARD HEIGHT (KITCHEN)

3.20.5. HVAC FOR RM 200 - 100% BACKUP COOLING.

3.20.6. HVAC E.O.C/RTCC RM 301 THROUGH 311

3.20.7. ALL LIGHTS - EXCEPT RM 200, 301, 312, 313, 314, 310.

3.20.8. U.P.S. PROVIDE POWER TO: VIDEO WALL, RM301, 200 - ALL/ EVERYTHING.

RECEPTACLES-SINGLE GANG BOXES-MOUNTED ABOVE SERVER RACKS ON

ELECTRICAL BAR RACKS. 4- 20 AMP CIRCUITS ABOVE EACH RACK - 4 SINGLE GANG

BOX.

3.20.9. RM 310 AUTO SLIDING GLASS ENTRY DOORS, RM303 ALL, LIGHTS ROOM 301, 305,

310.

3.21. DATA AND PHONE JACKS

3.21.1. ALL CABLE - RUN ABOVE CEILING. EXCEPT RM 301 - CENTER WORKSTATION (14)

UNDER FLOOR.

3.21.2. DATA CABLES PULLED TO ROOM 200: 1) 1 CAT6 DATA CABLE - CENTER OF RM 301

CEILING TO RM 200 FOR Wi-Fi CONNECTION. 2) VIDEO WALL 32 SINGLE CAT6 - EACH

VIDEO SCREEN.

3.21.3. POHONE CABLES PULLED TO ROOM 168.

3.21.4. 1 POHONE AND 2 DATA CAT6 FOR EACH LOCATION-TERMINATED AT WALLS

OUTLETS AND FLOOR OUTLETS AND INTO SWITCH CONTRACTOR PROVIDES. 1)

ROOM 301 LOCATIONS EACH DESK AND 1 CENTER LOCATION IN FLOOR (14). 2) 2

JACK LOCATION IN ROOMS 302, 306, 307, 308, 313, 314. 3) ROOM 303 - 1 JACK IN

FLOOR, 1 JACK ON EAST WALL BEHIND VIDEO SCREEN. 4) ROOM 305-8 JACKS, WEST

AND SOUTH WALLS. 5) ROOM 301, 305-JACK AT COPIER LOCATION.

3.21.5. CABLE CHASE-CEILING TO RAISED FLOOR LOCATE IN RM 304.

3.22. CARD ACCESS READER (MORSE COMMUNICATIONS CONTRACTOR)

3.22.1. 1 CAT6 DATA CABLE - CENTER OF RM 301 CEILING TO RM200 FOR Wi-Fi

CONNECTION.

3.22.2. VIDEO WALL 32 SINGLE CAT6 - EACH VIDEO SCREEN

3.22.3. PHONE CABLES PULLED TO ROOM 168.

3.22.4. 1 PHONE AND 2 DATA CAT6 FOR EACH LOCATION-TERMINATED AT WALLS OUTLETS

AND FLOOR OUTLETS AND INTO SWITCH CONTRACTOR PROVIDES. ROOM 301

LOCATIONS EACH DESK AND 1 CENTER LOCATION IN FLOOR (14). 2) JACK LOCATION

IN ROOMS 302, 306, 307, 308, 313, 314. 3) ROOM 303 - 1 JACK IN FLOOR, 1 JACK ON

EAST WALL BEHIND VIDEO SCREEN. 4) ROOM 305 - 8 JACKS, WEST AND SOUTH

WALLS. 5) ROOM 301, 305- JACK AT COPIER LOCATION.

3.22.5. CABLE CHASE - CEILING TO RAISED FLOOR LOCATE IN RM 304.

3.23. CARD ACCESS READER (MORSE COMMUNICATION CONTRACTOR)

3.23.1. INGRATE WITH EXISTING CONTINENTAL PROGRAM CONTROL SOFTWARE.

3.23.2. ADD 1 ACCESS DOOR PANEL IN ROOM 168.

3.23.3. NEW CARD READER-ROOMS 203, 201, 312, 305, 308 WITH REMOTE DOOR OPENER

3.23.4. CONTROL WIRE FROM DOORS TO RM 168. CONTRACTOR PROVIDES CONTROLLER

PORTS.

3.24. FIRE SYSTEM - SPRINKLERS (OCALA BACKFLOW)

3.24.1. NFPA 13 CODE APPLY ACCORDING TO E.O.C. PRINT LAY-OUT.

3.25. FIRE SYSTEM - PROPRIETARY SYSTEM (JACKSONVILLE SOUND)

3.25.1. NFPA 72FIRE CODE APPLY- ACCORDING TO ECO PRINT LAY-OUT.

3.25.2. EDWARDS PANEL-EST CERTIFIED COMPANY

3.25.3. SMOKE/HEAT DETECTORS/STROBES

3.25.4. HVAC DETECTOR DUCT TEST CONTROLS SWITCHES LOCATED IN RM 304.

3.25.5. MEET ALL CITY, STATE FIRE CODE

3.25.6. MATCH EXISTING DEVICES IN THIS AREA

3.26. HVAC

3.26.1. UNITS LOCATED OVER/NEAR SUPPORT COLUMNS: MEET ALL CITY COMERCIAL

MECHANICAL CODE REQUIREMENTS. RTU UNITS LABEL PER PRINT. RTU UNITS

CURBS SEAL WITH ROOF SEALANT- SAME AS CURRENT MATERIAL- WITH ANTI-SLIP

MATERIAL AROUND. SIZE ACCORDING TO HEAT LOAD IN WORKING AREA. METAL

DUCTWORK WITH FLEX DUCT TO DIFFUSERS. ADD RETURN AND SUPPLY

DUCTWORK FOR POLYGRAPH AND ROOM FOYER.

3.26.2. SUPPLY DIFFUSERS WITH DAMPERS. DAMPERS LOCATED AT MAIN SUPPLY LINE

3.26.3. AIR RETURN IN EACH OFFICE/ROOM

3.26.4. INTEGRATE WITH EXITING HONEYWELL COMPUTER CONTROL PROGRAM

3.27. HVAC - SERVER ROOM 199, 200

3.27.1. 100% BACKUP COOLING

3.27.2. MEET ALL CITY COMMERCIAL CODE REQUIREMENTS.

3.27.3. SIZE ACCORDING TO HEAT LOAD IN SERVER AREA

3.27.4. INTEGRATE WITH EXITING HONEYWELL CONTROL PROGRAM.

3.27.5. INSTALL THE NEW UNITS GRAPHICS TO PROGRAM AND OPD 1754 COMPUTER.

3.28. DOOR LOCKS

3.28.1. YALE MORTIS LOCKS MATCH EXISTING.

3.28.2. YALE GRAND MASTER KEY SYSTEM. MUST BE A REGISTERED YALE DEALER.

3.29. CORNER WALL PROTECTORS

3.29.1. OUTSIDE CORNERS- LIGHT GREY- MATCH EXISTING

3.30. NEW CARPET AND VINYL BASE BOARDS

3.30.1. ALL ROOMS: 200, 301, 302, 303, 304, 305, 306, 307, 308, 311, 312, 313, 314

3.31. TILE FLOORS WITH TILE BASE BOARDS

3.31.1. ROOM 310 DOOR TO RAMP

3.31.2. ROOM 309

3.32. ROOM WALL PLATES

3.32.1. RM # AND INSERT FOR NAMES-MATCH EXISTING IN BUILDING

3.33. MATERIALS / DESCRIPTION

3.33.1. CARPET-MILKEN CARPET PANELS

3.33.2. MATCH EXISTING CARPET COLOR - OPEL

3.33.3. SHERWIN WILLIAMS PAINT: 1) WALLS - SATIN SUPER PAINT #1256.

2) DOOR JAMB - #PD BLUE - OIL BASE.

3.33.4. NAVY VINYL BASE BOARD - JOHNSONITE

3.33.5. 5/8" SHEETROCK

3.33.6. STEEL FRAME STUDS

3.33.7. ELECTRICAL CONDUIT

3.33.8. ANTIBACTERIAL CEILING TILE - BLACK

3.33.9. DOOR STAIN - MATCH EXISTING DOORS IN BUILDING.

3.33.10. SOLID DOOR - 3 HINGE - STEEL JAMB - MATCH EXISTING.

3.33.11. AMERICAN LOUVER COMPANY - A/C: 1) BLACK CONE DIFFUSER WITH

DAMPER FOR SUPPLY LAY-IN. 2) BLACK RETURN AIR LAY-IN GRILLS.

3.33.12. LED LIGHTING FIXTURE 2'X4' DIMMABLE WITH DIMMABLE SWITCHES

3.33.13. 7 YEAR WARRANTY OR LONGER ON LIGHTING FIXTURES

3.33.14. STAINLESS STEEL ELECTRICAL COVER PLATES - ALL.

SCOPE OF WORK

Exhibit B

1 2 3 4 5 6 7 8 9 10 a

B

C

D

E

F

G

H

8A 9A

A

B

C

D

E

F

G

G1

H

1097 865

EXISTING FLOOR

OPEN'G & STAIRS

DN

mech chase

UP

ramp up

ELEV #1

DATA

SECR.SECR.

raised comp.

flooring raised comp.

flooring

OFFICER

WINDOW

DN

6' bench typ

PLANTER

public tele

UP

PL

AN

TE

R

PL

AN

TE

R

PL

AN

TE

R planter copier/fax

637 S.F.

FUTURE

EXPANSION

FUTURE EXPANSION BAY

2390 S.F.

kit ch en et te

UP

UP

pub lic tel e

UP

UP

planter

CONTROL

TABLE

planter planter

UP

RAMP

UP

HC

DN

UP

REINSTALL POLYGRAPH EQUIPMENT

AND SOUNDPROOFING (WHISPER

ROOMS) AS SPECIFIED BY THE OWNER.

E.O.C.

CAMERA TECH.

E.O.C. LT.

INTEL SGT.

INTEL

UTILITY CLOSET

EXIT CORR.

ELEV EQUIP

ELEV #2

ALTN #2

27r @ 7.11 t @ 10"

SERVER ROOM

CONFERENCE ROOM

OFFICE/STORAGE

302 FISCAL MANAGER

FISCAL TECHS

FILE ROOM

CONFERENCE ROOM

DEPUTY CHIEF

CONFERENCE ROOM

POLICE CHIEF

SECR AREA

FILES

CHIEF'S SECT

SCHOOL RESOURCE/

YOUTH SERVICES

WORKROOM/ STOR

CONFERENCE

CORR.

ADMIN LOBBY

SECR RECEP.

ADMIN

SERVICES

MAJOR

CRIME

PREVENTION/

WORKROOM

100D

COVERED

EMPLOYEE

ENTRANCE

PUBLIC COMMUNITY

ACTIVITY ROOM (150)

MAIN ENTRY

SECR AREA

ADMIN

SERVICES

LIEUT

EXEC OFFICER

FUTURE

EXPANSION

1512 S.F.

FOYER

POLIGRAPH BOOTH

BREAK ROOM

PROFESS

STANDARDS

OFFICER

PROFESS

STANDARDS

ASSIST

MAIL RM

CORRIDOR

CORR

WORK STATION

LIBRARY

WORK STATION

RESOURCE SECT

CORR

STOR

STOR

166A

LOGG'G/

RECORD'G

LOCKERS/COPY RM

STOR

800 MG

COORD

EMERGENCY

OPERATION

CENTER

RESOURCE

DEVELOP

SUPERV

STOR

SERVICE

COUNTER

STOR

DRESS'G

DRESS'G

TEST TRAP

ARMORY

E.S.U. LOCKERS

E.S.U. AMMO

STOR

EMPLOYEE LOUNGE

CORR

160A

FIREARMS

TRAINING

AMMO STOR

COV SMOKING TERRACE

100A

LOADING DOCK

100B

RECEIVING RM

SUPPLY RM STORAGE

SUPPLY SUPERVISOR

SUPPLY FILES

SUPPLY CLERK

FIREARMS

TRAINING

STOR

ASSMT. RM

ASSMT. RM

ASSMT. RM

CORR

A/V STOR

CONFERENCE/

WEAPONS

SIM. RM.

LIEUT OFFICE

INVEST SERV. MAJOR

CORR

INVEST

RECEP/ SECT

WAIT

VICTIM/

WITNESS

ADVOCATE

WAIT

CORR

CORR

SGT. OFFICE

C.V.S.A.

FUTURE

SOFT RM

OBSERV

'SOFT' RM

COMMUNITY

AFFAIRS

OFFICE

CORR

COPY ROOM

PRINTERS

RECORDS

SUPERVISOR

RECEPT/ SERV CTR

RECORDS WAITING

FINGER PRINT

RECORD'S

CLERK

WORKROOM

CORR

INTERVIEW

INTERVIEW

INTERVIEW

INTERVIEW

LARGE CONFERENCE RM

MAJOR CASE WORKROOM

EQUIP STOR

ARCHIVAL RECORDS STORAGE

COV RECORDS PICK-UP

100C

STAGE

U.P.S./ TELEPH/

911 EQUIP RM

LOUNGE

CONFERENCE/

C.A.D. TRAIN'G

INFO. SYS.

OFFICE

SUPPLY ROOM/

WORKROOM

COMPUTER ROOM

FIREPROOF LOCKER

INFO. SYSTEMS

MAIN WORKROOM

W

VEST

M

VEST

W

M

SUPPLY STOR.

DISP. STOR.

FILE STOR.

CORR

PREP CTR

STOR

FOYER

JAN

PUBLIC

MEN

PUBLIC

WOMEN

PUBLIC

VIEWING

COVERED

ENTRY

DETECTIVE

WORKROOM

TRAINING ROOM 136

TIERED SEATING W/ DESKS

SECURITY CONSOLE

COMMUNICATIONS CENTER

X-IMAGE RM

COMM

SUPERVISOR

COMMUN

ADMIN OFFICE

PERSONNEL WORKROOM

WIRING CLOS

PUBLIC LOBBY ROTUNDA

SPECIAL OPS.

TESTING CARRELS

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

AREA OF WORK

214' TTD

244' TTD

191' TTD

FE

33.5" CLR.

(167) PERSONS

3'-0"

36" - 2.5" =

33.5" CLR.

2.5" = 1.75" DOOR

+ .75" STOP

33.5" / 0.2 =

167.5

167 PERSONS

DOOR CAPACITY

DOOR CAPACITY

OCCUPANT LOAD

MAXIMUM ALLOWABLE TRAVEL

DISTANCE ALLOWABLE 200'

NEW EMERGENCY LIGHT ON BATTERY

PACK - UNLESS NOTED OTHERWISE

NEW FIRE EXTINGUISHER WALL MOUNTED

10LB. 4A:80B:C - UNLESS NOTED

OTHERWISE

TTD = TOTAL TRAVEL DISTANCE

(EGRESS PATH)

82' TTD

DIRECTION

OF TRAVEL

68.5" CLR.

(342) PERSONS

6'-0"

72" - 3.5" = 68.5"

CLR.

3.5" = 1.75" DOOR x 2

68.5" / 0.2 =

342.5

342 PERSONS

NEW 2' X 2' EMERGENCY LED LIGHTING FIXTURE

WITH INTEGRAL 90 MINUTE BATTERY PACK -

UNLESS NOTED OTHERWISE

SEE REFLECTED CEILING PLAN FOR LOCATIONS

SYMBOL LEGEND

SQ. FT. DATA

REMODELED AREA: 2491 SQ. FT.

EXISTING AREA TO REMAIN 5787 SQ. FT.

GRAND TOTAL 8278 SQ. FT.

NEW EXIT LIGHT W/ BATTERY PACK CHECK

FOR PROPER OPERATION REPLACE AS

REQUIRED - UNLESS NOTED OTHERWISE

NEW COMBINATION EXIT SIGN &

EMERGENCY LIGHT WITH BATTERY PACK -

UNLESS NOTED OTHERWISE

GENERAL NOTES

1. PROVIDE CORRECT EGRESS PATH DIRECTION AND CLEAR

EGRESS VISIBILITY OF ALL EXIT SIGNAGE LIGHTING. PROVIDE

NEW EXIT SIGNAGE, EMERGENCY LIGHTING AND FIRE

EXTINGUISHERS AS SHOWN ON PLAN.

2. ALL NEW FIRE EXTINGUISHERS TO BE CLASS "ABC" UNLESS

SPECIFIED OTHERWISE BY FIRE MARSHAL ALL NEW & EXISTING

FIRE EXTINGUISHERS TO BE TESTED, WORKING PROPERLY AND

WITHIN CORRECT OPERATIONAL DATE, TYPICAL.

3. IF APPLICABLE EXISTING FIRE EXTINGUISHERS SHALL BE

TESTED & TAGGED PRIOR TO C.O. OR REPLACE IF REQUIRED

TYP.

4. IF APPLICABLE VERIFY ALL EXISTING EMERGENCY EMMER LT

LIGHTS & EXIT SIGNS ARE IN WORKING CONDITION REPLACE AS

REQUIRED TYP.

5. IF APPLICABLE FIXED SEATING DIAGRAM SHALL BE POSTED IN A

CONSPICUOUS LOCATION. A SEATING CHANGE CAN'T BE MADE

WITHOUT PRIOR APPROVAL FROM THE FIRE MARSHAL.

6. OCCUPANT LOAD SIGN SHALL BE PLACED IN A CONSPICUOUS

LOCATION.

167 16

FE

EX

EX

EM

EM

45.5" CLR.

(227) PERSONS

4'-0"

48" - 2.5" =

45.5" CLR.

2.5" = 1.75" DOOR

+ .75" STOP

45.5" / 0.2 =

227 PERSONS

AREA NOT IN CONTRACT HATCH

FLOOR PLAN HATCH LEGEND

ACCESS FLOOR SYSTEM. SEE

SP101 FOR SPECIFICATIONS

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

LS101

SCALE: 3/16" = 1'-0" (PRINTED @ 24X36)

LIFE SAFETY PLAN -

SCALE: NTS = (PRINTED @ 11X17)

D1

1 2 3 4 5 6 7

E

F

G

H

DN

UP

REF

ICE

REINSTALL POLYGRAPH EQUIPMENT

AND SOUNDPROOFING (WHISPER

ROOMS) AS SPECIFIED BY THE OWNER.

E.O.C.

CAMERA TECH.

E.O.C. LT.

INTEL SGT.

INTEL

UTILITY CLOSET

EXIT CORR.

ELEV EQUIP

ELEV #2

ALTN #2

27r @ 7.11 t @ 10"

SERVER ROOM

CONFERENCE ROOM

OFFICE/STORAGE

302 FISCAL MANAGER

FISCAL TECHS

ADMIN

SERVICES

MAJOR

MAIN ENTRY

SECR AREA

ADMIN

SERVICES

LIEUT

FUTURE

EXPANSION

1512 S.F.

FOYER

POLIGRAPH BOOTH

BREAK ROOM

PROFESS

STANDARDS

OFFICER

PROFESS

STANDARDS

ASSIST

MAIL RM

CORRIDOR

CORR

CONFERENCE/

INFO. SYS.

OFFICE

SUPPLY ROOM/

WORKROOM

COMPUTER ROOM

FIREPROOF LOCKER

INFO. SYSTEMS

MAIN WORKROOM

W

VEST

M

VEST

W

M

SUPPLY STOR.

SPECIAL OPS.

TESTING CARRELS

10'-0"

10'-8" 5'-5" 9'-2" 22'-8"

22'-4"

9'-4"

5'-0"

2'-4"3'-0"3'-4"

1'-4"

7'-6"

4'-0" OPENING

VERIFY WITH

POLYGRAPH

BOOTH DOOR

LOCATION

RAMP UP

1:12 SLOPE MAX

R A

M P

U

S

L O

M

A X

3'-8" 3'-0"

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

F R O N T

A/ V

RA

CK

AREA NOT IN CONTRACT

ACCESS FLOOR SYSTEM. SEE

SP101 FOR SPECIFICATIONS

FLOOR PLAN HATCH LEGEND

1 2 3 4 5 6 7 8 9 10 a

B

C

D

E

F

G

H

8A 9A

A

B

C

D

E

F

G

G1

H

1097 865

CONTROL

TABLE WALL TYPE LEGEND

GRAND TOTAL

3,500

SQ. FT.

INTERIOR NON-LOAD BEARING PARTITION WALL

CONSISTING OF:

5/8" TEXTURED PRIMED & PAINTED GYP BD. ON EA.

SIDE OF 3-5/8" 20ga METAL STUDS AT 16" O.C. W/ (1)

3-5/8" METAL TOP PLATES AND (1) 3-5/8" GALV METAL

BASE PLATE SECURED TO CONC. SLAB

NOTE: SHADING INDICATES NEW WALLS

EXISTING WALLS TO REMAIN SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A201D

SCALE: 3/16" = 1'-0" (PRINTED @ 24X36)

FLOOR PLAN - DIMENSIONS

SCALE: NTS = (PRINTED @ 11X17)

NOTE:

CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS,

DEMOLITION CONTRACTOR MUST COORDINATE WITH PLUMBING CONTRACTOR PRIOR TO

CONSTRUCTION AS TO VERIFY EXACT PIPING ROUTING, ALSO REVIEW PLUMBING

ENGINEERS DRAWINGS.

D1

D3

D5

D4

D6

D2

D7 D8

D9

A500

NOT IN CONTRACT

D10

D11

A501

A500.1

A501

A501

AREA OF WORK

KEY PLAN

A501 SIM

A501

A501

W1

W1

SP104

A501

A500.1

A500

W1

24" X 24" ACOUSTICAL LAY-IN

CEILING TILES AND GRID

(SEE REFLECTED CEILING PLAN)

EL. + 109'-6" CLG HT.

EXISTING ROOF DECK

EL. +100'-0" ASSUMED FIN. FLR.

CONC. SLAB - SEE STRUCTURAL PLANS

FINISHED FLOOR SEE FINISH SCHEDULE

(2) 3-5/8" x 1-5/8" x 20GA. METAL "C" STUD

MECHANICALLY ATTACHED TO BAR JOISTS @

48" O.C. W/ L30 CLIP BY SIMPSON STRONG TIE

ATTACHED TO BAR JOIST AS PER MANUF.

INSTRUCTIONS

MAX TRACK® SLOTTED DEFLECTION

TRACK SECURED TO ROOF DECK WITH

FAST CLIP DEFLECTION SCREWS

MAINTAIN 1/2" GAP BETWEEN ROOF

DECK & TOP OF METAL STUD

5/8" TEXTURED & PAINTED

GYP. BD. ON EA. SIDE

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT APPROVED

EQUAL

L30 CLIP BY SIMPSON STRONG TIE ATTACHED

TO EXISTING BAR JOISTS AS PER MANUF.

INSTRUCTIONS

EXISTING BAR JOISTS

45° KNEE BRACE STAGGERED @ 48" O.C.

NOTE:

ALL LIGHT GAUGE METAL FRAMING

SHALL BE GALVANIZED

EXISTING ROOF SYSTEM

EL. + 100'-6" FIN.

ACCESS FLOOR SYSTEM

ACCESS FLOOR SYSTEM

1-1/2" CRC LATTERAL BRIDGING

(2) ROWS MIN. TYP. SECURE @ EA.

END & @ EA. STUD TYP. (LOAD

BEARING WALLS ONLY)

EL. + 113'-6" CLG HT.

T.O. BEAM (V.I.F.)

GLASS WALL BY

STEELCASE; SEE

SPECIFICATIONS ON

SP104

SECURE GALV. METAL BOTTOM CHANNEL TRACK

W/ 3/4" PIN ANCHORS AS PER ASTM STANDARDS

FOR NON LOAD BEARING WALLS

3-5/8" X 1-5/8" 20 GA. GALV.

METAL BOTTOM CHANNEL

TRACK BY CLARK DIETRICH

OR ARCHITECT APPROVED

EQUAL

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT

APPROVED EQUAL

5/8" TEXTURED & PAINTED

GYP BD.

BASE SELECTED BY OWNER

24" X 24" ACOUSTICAL LAY-IN

CEILING TILES AND GRID

(SEE REFLECTED CEILING PLAN)

EL. + 109'-6" CLG HT.

EXISTING ROOF DECK

EL. +100'-0" ASSUMED FIN. FLR.

CONC. SLAB - SEE STRUCTURAL PLANS

FINISHED FLOOR SEE FINISH SCHEDULE

(2) 3-5/8" x 1-5/8" x 20GA. METAL "C" STUD

MECHANICALLY ATTACHED TO BAR JOISTS @

48" O.C. W/ L30 CLIP BY SIMPSON STRONG TIE

ATTACHED TO BAR JOIST AS PER MANUF.

INSTRUCTIONS

MAX TRACK® SLOTTED DEFLECTION

TRACK SECURED TO ROOF DECK WITH

FAST CLIP DEFLECTION SCREWS

MAINTAIN 1/2" GAP BETWEEN ROOF

DECK & TOP OF METAL STUD

5/8" TEXTURED & PAINTED

GYP. BD. ON EA. SIDE

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT APPROVED

EQUAL

L30 CLIP BY SIMPSON STRONG TIE ATTACHED

TO EXISTING BAR JOISTS AS PER MANUF.

INSTRUCTIONS

EXISTING BAR JOISTS

45° KNEE BRACE STAGGERED @ 48" O.C.

A

A302

NOTE:

ALL LIGHT GAUGE METAL FRAMING

SHALL BE GALVANIZED

EXISTING ROOF SYSTEM

EL. + 100'-6" FIN.

ACCESS FLOOR SYSTEM

ACCESS FLOOR SYSTEM

1-1/2" CRC LATTERAL BRIDGING

(2) ROWS MIN. TYP. SECURE @ EA.

END & @ EA. STUD TYP. (LOAD

BEARING WALLS ONLY)

A

EL. + 113'-6" CLG HT.

T.O. BEAM (V.I.F.)

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A500

SCALE: 3/4" = 1'-0"

TYPICAL WALL SECTION1

SCALE: 3/4" = 1'-0"

TYPICAL WALL SECTION2

SECURE GALV. METAL BOTTOM CHANNEL TRACK

W/ 3/4" PIN ANCHORS AS PER ASTM STANDARDS

FOR NON LOAD BEARING WALLS

3-5/8" X 1-5/8" 20 GA. GALV.

METAL BOTTOM CHANNEL

TRACK BY CLARK DIETRICH

OR ARCHITECT APPROVED

EQUAL

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT

APPROVED EQUAL

5/8" TEXTURED & PAINTED

GYP BD.

BASE SELECTED BY OWNER

24" X 24" ACOUSTICAL LAY-IN

CEILING TILES AND GRID

(SEE REFLECTED CEILING PLAN)

EL. + 109'-0" CLG HT.

T.O. BEAM (V.I.F.)

EXISTING ROOF DECK

EL. +100'-0" ASSUMED FIN. FLR.

CONC. SLAB - SEE STRUCTURAL PLANS

(2) 3-5/8" x 1-5/8" x 20GA. METAL "C" STUD

MECHANICALLY ATTACHED TO BAR JOISTS @

48" O.C. W/ L30 CLIP BY SIMPSON STRONG TIE

ATTACHED TO BAR JOIST AS PER MANUF.

INSTRUCTIONS

MAX TRACK® SLOTTED DEFLECTION

TRACK SECURED TO ROOF DECK WITH

FAST CLIP DEFLECTION SCREWS

MAINTAIN 1/2" GAP BETWEEN ROOF

DECK & TOP OF METAL STUD

5/8" TEXTURED & PAINTED

GYP. BD. ON EA. SIDE

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT APPROVED

EQUAL

L30 CLIP BY SIMPSON STRONG TIE ATTACHED

TO EXISTING BAR JOISTS AS PER MANUF.

INSTRUCTIONS

EXISTING BAR JOISTS

45° KNEE BRACE STAGGERED @ 48" O.C.

A

A301

NOTE:

ALL LIGHT GAUGE METAL FRAMING

SHALL BE GALVANIZED

EXISTING ROOF SYSTEM

EL. + 109'-6" CLG HT.

FROM FINISHED FLOOR

EL. + 100'-6" FIN.

ACCESS FLOOR SYSTEM

EL. + 100'-0" FIN. FLR.

FINISHED FLOOR SEE FINISH

SCHEDULE

1-1/2" CRC LATTERAL BRIDGING

(2) ROWS MIN. TYP. SECURE @ EA.

END & @ EA. STUD TYP. (LOAD

BEARING WALLS ONLY)

A

ROOM 169

LOCKERS / COPY ROOM

SECURE GALV. METAL BOTTOM CHANNEL TRACK

W/ 3/4" PIN ANCHORS AS PER ASTM STANDARDS

FOR NON LOAD BEARING WALLS

3-5/8" X 1-5/8" 20 GA. GALV.

METAL BOTTOM CHANNEL

TRACK BY CLARK DIETRICH

OR ARCHITECT APPROVED

EQUAL

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT

APPROVED EQUAL

5/8" TEXTURED & PAINTED

GYP BD.

BASE SELECTED BY OWNER

24" X 24" ACOUSTICAL LAY-IN

CEILING TILES AND GRID

(SEE REFLECTED CEILING PLAN)

EL. + 109'-6" CLG HT.

EXISTING ROOF DECK

EL. +100'-0" ASSUMED FIN. FLR.

CONC. SLAB - SEE STRUCTURAL PLANS

FINISHED FLOOR SEE FINISH SCHEDULE

(2) 3-5/8" x 1-5/8" x 20GA. METAL "C" STUD

MECHANICALLY ATTACHED TO BAR JOISTS @

48" O.C. W/ L30 CLIP BY SIMPSON STRONG TIE

ATTACHED TO BAR JOIST AS PER MANUF.

INSTRUCTIONS

MAX TRACK® SLOTTED DEFLECTION

TRACK SECURED TO ROOF DECK WITH

FAST CLIP DEFLECTION SCREWS

MAINTAIN 1/2" GAP BETWEEN ROOF

DECK & TOP OF METAL STUD

5/8" TEXTURED & PAINTED

GYP. BD. ON EA. SIDE

3-5/8"X 1-5/8" 20 GA. GALV. MTL.

STUDS @ 16" O.C. BY CLARK

DIETRICH OR ARCHITECT APPROVED

EQUAL

L30 CLIP BY SIMPSON STRONG TIE ATTACHED

TO EXISTING BAR JOISTS AS PER MANUF.

INSTRUCTIONS

EXISTING BAR JOISTS

45° KNEE BRACE STAGGERED @ 48" O.C.

A

A302

NOTE:

ALL LIGHT GAUGE METAL FRAMING

SHALL BE GALVANIZED

EXISTING ROOF SYSTEM

EL. + 100'-6" FIN.

ACCESS FLOOR SYSTEM

ACCESS FLOOR SYSTEM

1-1/2" CRC LATTERAL BRIDGING

(2) ROWS MIN. TYP. SECURE @ EA.

END & @ EA. STUD TYP. (LOAD

BEARING WALLS ONLY)

A

EL. + 109'-6" CLG HT.

T.O. BEAM (V.I.F.)

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A500.1

SCALE: 3/4" = 1'-0"

TYPICAL WALL SECTION3

SCALE: 3/4" = 1'-0"

TYPICAL WALL SECTION4

M A

X

S P

A C

I N

G

A

SLOPE

1:12

1 2

FLOOR FINISH PER

OWNER SPECS

2X BLOCKING AT

ENDS & MID POINT

2X61/2" PLYWOOD

SLOPE UP

1:12 MAX

8'-8"

2'-0" 2'-0" 2'-0" 2'-8"

2'-6" 2'-0"

2'-8" CLR VERIFY WITH

APPLIANCE SELECTION

PLASTIC LAMINATE

COUNTERTOP w/

BACKSPLASH AND

ENDWALL SPLASH

DOOR PULL (TYP.)

1'-4

" CLR

VERIFY WITH

APPLIANCE

SELECTION

7'-6"

(ASSUMED) FIN. FLOOR

0"

WINDOW & DOOR HT.

7'-0"

CLG. HT.

13'-0"

A601

A601

A601

7'-6"

(ASSUMED) FIN. FLOOR

0"

WINDOW & DOOR HT.

7'-0"

CLG. HT.

13'-0"

A601

A601

A601

3'-0"

(ASSUMED) FIN. FLOOR

0"

WINDOW & DOOR HT.

7'-0"

CLG. HT.

13'-0"

A601

A601

A601

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A501

SCALE: 1/2" = 1'-0"

INTERIOR ELEVATION1

SCALE: 3/4" = 1'-0"

RAMP SECTION2

SCALE: 3/4" = 1'-0"

RAMP SECTIONA

SCALE: 3/4" = 1'-0"

INTERIOR ELEVATION5

SCALE: 1/2" = 1'-0"

INTERIOR ELEVATION6

SCALE: 1/2" = 1'-0"

INTERIOR ELEVATION7

LEGEND

1. Access floor panel

2. Roll formed galvannealed steel stringer

3. 1/4" - 20 X 1 3/4" screw

4. 11 ga. die formed galv.

steel head

5. Steel stud

3/4" - 10 UNC

6. Nut with vibration proof locking device

(6" FFH and up)

7. Type 1 base with

7/8" sq. x 17ga. wall galv.

tubing

8. Die formed embossed galv. steel base

9. Resistance Weld

Bolted Stringer Understructure for ConCore and

All Steel Access Floor Panels-24". Type 1A Pedestal

PEDESTAL SPECIFICATIONS

11 ga. die formed galvanized steel pedestal head and projection welded stud with adjustment nut. Head and installed stringers shall provide full perimeter edge support for panel.

Standard finished floor heights from 6" to 36". For other finished floor heights please contact the Tate

Technical Hotline @ 800-231-7788. For seismic conditions, refer to seismic submittal details.

Assembly shall provide a 2" total adjustment with a floor height of 7" or greater.

Assembly up to 36" FFH shall provide an 5,000 lb.

axial load without permanent deformation.

Pedestal Head

Pedestal Assembly

Overturning moment of 1,000 in./lbs. when Tate recommended pedestal adhesive is utilized.

Stringers shall be attached with 1/4" - 20 flat-head screws.

Pedestal head shall be tapped for engagement of stringer screws.

Steel stud shall be 3/4" - 10 UNC.

Nut shall be 3/4" - 10 UNC and galvanized.

Stud shall provide an anti-rotation feature when engaged with the pedestal base assembly.

Base to be at least 16" square and galvanized steel.

Pedestal Base

Pedestal tube shall be 7/8" x 17 ga. wall square galvanized tubing.

Heavy duty roll formed steel stringer will withstand

450 lb. mid-span load.

Stringers

Galvannealed stringer construction to prevent corrosion.

Stringer shall be 1-1/4" deep x 3/4" wide.

Stringer grid pattern shall be 2'/2', 2'4', or 4'/4' basketweave.

Perimeter pedestal shall provide support for panels around columns, at walls and in corners.

Perimeter

Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

© 2003 Tate Access Floors, Inc.

Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

System Performance Criteria

PANEL CRITERIA

SPECIFICATIONS

General information

COVERING OPTIONS

UNDERSTRUCTURE OPTIONS

ConCore : CC1000 Panel-24"

© 2003 Tate Access Floors, Inc.

© 2003 Tate Access Floors, Inc.Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

© 2003 Tate Access Floors, Inc.Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

ConCore/All Steel Stringer System ConCore/All Steel Stringer System

49" (FULL PANELS) OR 48" (FULL & CUT PANEL)

5"

22"

1"

STRINGER CUTTING INSTRUCTIONS FOR PANEL RESTRAINT

2. BEND STRINGER SIDES BACK TO 90° WITH PLIERS.

1. BAND SAW STRINGER SIDES BACK 1/2".

1/4-20 SCREW

1/2

1/2

INSTRUCTIONS FOR CUT PANEL

SAME AS ABOVE BUT USE STANDARD STRINGER

INSTRUCTIONS FOR FULL PANEL

3/8

1/2

1/2

FASCIA PLATE

M

I N

M

A X

SUB-FLOOR

SECTION AT THRU WALL

WALL

SUB-FLOOR

WALL

TYPICAL SECTION AT FIELD

SECTION AT CURB

F I N

I S

H E

D

F

L O

O R

H

I G

H T

FACE OF WALL

PEDESTAL ASSEMBLY

SECTION WITH SURFACE PARTITION

PEDESTAL ASSEMBLY

EXPANSION JOINT

SECTION AT EXTERIOR WALLSECTION AT FASCIA

FACE OF WALL

COVE BASE (BY OTHERS)

CONCORE/ALL-STEEL ACCESS

FLOOR PANEL

CONCORE/ALL-STEEL ACCESS

FLOOR PANEL. FULL SIZE OR CUT.

COVE BASE (BY OTHERS)

STRINGER WITH

COATING

STRINGER WITH

COATING

USE FULL PANELS OR, TO MAINTAIN 24"

MODULE, CUT 1" OFF PANEL AND 1/2" OFF

STRINGER.

6" WIDE ALUMINUM THRESHOLD PLATE (BY OTHERS).

SECURE THIS SIDE WITH #8 FHSMS AT 12" O.C.

FULL PANELS AND STRINGERS

THIS SIDE.

1/4-20 PAN HEAD SCREW. LEAVE LOOSE ENOUGH TO

ALLOW PANEL AND STRINGER TO SLIDE ON

PEDESTAL CAP FREELY.

STANDARD EXPANSION JOINT WITH 1" MAX.

EXPANSION

CONCORE/ALL-STEEL ACCESS FLOOR PANEL. FULL SIZE

OR CUT TO FIT AGAINST WALL. USE WOOD SHIM IF

NECESSARY TO ARREST SHIFTING.

STRINGER WITH

COATING

FOR CUT PANEL (SHOWN) CUT STRINGER AS

SHOWN AND USE 1/4-20 X 3/4" PHMS. FOR FULL

PANEL (NOT SHOWN) USE STANDARD

FASTENER.

GAPS NOT TO EXCEED MARGIN SET BY

WIDTH OF WALL BASE OR THRESHOLD

MOLDING

BUTT BASEPLATE AGAINST

WALL OR CUT AS REQUIRED

FOR CUT PANEL (SHOWN) CUT STRINGER AS

SHOWN AND USE 1/4-20 X 3/4" PHMS. FOR FULL

PANEL (NOT SHOWN) USE STANDARD

FASTENER.

STRINGER WITH

COATING

CONCORE/ALL-STEEL ACCESS FLOOR PANEL. FULL SIZE

OR CUT TO FIT AGAINST WALL. USE WOOD SHIM IF

NECESSARY TO ARREST SHIFTING.

OMIT IF FINISHED FLOOR IS TO BE

CARPETED

SHIELDED CONCRETE ANCHOR

(32" O.C.)

ALUMINUM THRESHOLD

MOLDING

#8 X 3/4" FHSMS (32" O.C.)

GAPS NOT TO EXCEED MARGIN SET

BY WIDTH OF WALL BASE OR

THRESHOLD MOLDING

BUTT BASEPLATE AGAINST

WALL OR CUT AS REQUIRED

STRINGER WITH

COATING

CONCORE/ALL-STEEL ACCESS

FLOOR PANEL

STEEL PEDESTAL

CAP

LEVELING NUT

WELDED

CONNECTION

PEDESTAL ATTACHMENT PER JOB

SPECIFICATION

THREADED STEEL

STUD

1/4-20 FHMS

STEEL PEDESTAL

TUBE

STEEL BASE PLATE

9/16 DIAMETER

CLEARANCE HOLE

FASCIA TRIM ANGLE SECURED TO PANEL

WITH #8 FHSMS (2 PLACES)

CONCORE/ALL-STEEL ACCESS

FLOOR PANEL. FULL SIZE OR CUT.

STRINGER WITH

COATING

1/4 - 20 X .75 PHMS

CUT BASEPLATE AS REQUIRED

PEDESTAL ATTACHMENT METHOD PER

JOB SPECIFICATION

#8 PHSMS OR 1/8" BLIND RIVETS

6" O.C.

FASCIA ANGLE SECURED TO

SUBFLOOR WITH ADHESIVE

FASCIA ANGLE SECURED TO SUBFLOOR WITH

ADHESIVE

1. ORDER A 4' STRINGER FOR A 2' FASCIA CONDITION

2. CUT STRINGER TO 23-1/2"

3. BAND SAW STRINGER SIDES BACK 1/2"

4. BEND STRINGER SIDES BACK TO 90 DEG WITH PLIERS.

5. DRILL 9/16" HOLE IN TOP OF STRINGER

6. ATTACH STRINGER TO PEDESTAL HEAD WITH 1/4 - 20 PAN HEAD SCREW.

Tate Access Floors, Inc.

7510 Montevideo Road

Jessup, MD 20794

Tel (410) 799-4200 Fax (410) 799-4207

© 2003 Tate Access Floors, Inc.

3 4

5 6

SECTION AT THRU WALL SECTION WITH SURFACE PARTITION

7 8

SECTION WITH SURFACE PARTITION

1 2 3 4 5 6 7 8 9 10 a

B

C

D

E

F

G

H

8A 9A

A

B

C

D

E

F

G

G1

H

1097 865

UP

DN

UP

UP

UP

UP

UP

CONTROL

TABLE

UP

RAMP

UP

HC

DN

UP

SEAL UNUSED DUPLEX OPENINGS

POWER, VOICE, AND DATA SERVICENTER BOX

ATTACH BLANK INTERFACE PLATES TO

UNUSED OPENINGS

NOTE: PROVIDE AND INSTALL 36 PVD

SERVICENTER BOXES, LOCATIONS AND

QUANTITIES AND TYPE OF PVD SERVICENTER

BOXES, VERIFY WITH OWNER.

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A502

EXTENT OF ACCESS

FLOORING: 2,823 S.F.

G.C. TO VERIFY IN FIELD

KEY PLAN

MARK LOCATION

DOOR SCHEDULE

D5

MARK LOCATION

SIZE (W x H)

DOOR MAT'L REMARKS

DOOR SCHEDULE

EXIT CORRIDOR 3'-0" X 6'-8" WD

D1

UTILITY CLOSET WD INTERIOR

D2

INTEL SGT. WD INTERIOR

D3

INTEL WD

D4

E.O.C. LT. WD INTERIOR

CAMERA TECH. WD INTERIOR

D6

CONFERENCE ROOM WD INTERIOR

D7

OFFICE/STORAGE WD INTERIOR

D8

MAIN ENTRY GL

INTERIOR, SLIDING

D9

3'-0" X 6'-8"

(PR) 2'-0" X 6'-8"

3'-0" X 6'-8"

HDW

GROUP

GLAZING

MAT'L

-HM -

G1

G1

G1

G1

G1

HM

HM

HM

HM

HM

HM

HM

DOOR

TYPE

A7

A1

A1

A1

A5

A5

A5

A5

A5

ROOM #:

(PR) 3'-0" X 6'-8"

INTERIOR

INTERIOR

3'-0" X 6'-8"

3'-0" X 6'-8"

3'-0" X 6'-8"

3'-0" X 6'-8"

FUTURE EXPANSION WD

INTERIOR

D10

G1HM A5300

FOYER WD

INTERIOR

D11

G1HM A5312

3'-0" X 6'-8"

3'-0" X 6'-8"

FRAME

TYPE

WINDOW SCHEDULE

WINDOW MODEL # MANUFACTURER WINDOW DIMENSIONS

WINDOW ROUGH

OPENING

REMARKS

· ALL WINDOWS IN EXISTING TOWER AREA TO BE TINTED TO MATCH THE REST OF THE BUILDING OR AS SELECTED BY

OWNER

· ALL WINDOWS TO BE ALUM. STOREFRONT SYSTEM; 'TRI-FAB' VG 451 T LOW-E, CENTER GLAZED STL. REINF. SYSTEM;

OR ARCHITECT APPROVED EQUAL.

· ALL WINDOW UNITS SHALL BE HANDLED, STORED, INSTALLED AND FINISHED AS PER THE MANUFACTURER'S

SPECIFICATIONS.

· ALL WINDOW ROUGH OPENINGS SHALL BE SITE VERIFIED BEFORE FABRICATION.

· ALL INTERIOR WINDOWS SHALL BE 3/8" THICK CLEAR TEMPERED GLAZING SET IN HOLLOW METAL FRAME.

WINDOW NOTES:

W1 - per manufacturer CUSTOM FIXED TEMPERED GLASS

SET INTO HOLLOW METAL FRAME

See interior window elevations on sht. A501STEELCRAFT

HOLLOW METAL HEAD - INTERIOR1 HOLLOW METAL JAMB - INTERIOR2 HOLLOW METAL SILL - INTERIOR3

8" MAX.

TYP.

S E

E

W

I N

D O

W

E

L E

V A

T I O

N S

O N

S

H E

T

A

1. ALL GLAZING SHALL BE INSULATED & TINTED, SELECTED BY OWNER.

2. GC SHALL SUBMIT SHOP DRAWINGS OF ALL GLAZING AND WINDOW SYSTEMS FOR

ARCHITECT & OWNER REVIEW AND APPROVAL PRIOR TO MANUFACTURING OR

ORDERING

3. ALL ROUGH OPENING SIZES SHALL BE FIELD VERIFIED PRIOR TO MANUFACTURING

AND ORDERING

4. ALL WINDOWS SHALL BE HANDLED, STORED, INSTALLED AND FINISHED PER THE

MANUFACTURER'S SPECIFICATIONS.

WINDOW NOTES

WD - STANDARD WOOD FINISH (FACTORY PRE-FINISHED,

OWNER SELECTED)

GL - GLAZING FINISH - (SEE GLAZING LEGEND)

HM - GALV. HOLLOW METAL (PRIMED & PAINTED, OWNER

SELECTED)

PK - POCKET DOOR

PR - PAIR OF DOORS

C - CUSTOM DOOR SEE OWNER

SD - SLIDING DOOR

SC - SOLID CORE DOOR

DOOR FINISHES

DOOR NOTES

MATERIAL ABBREVIATIONS:ROOM FINISH SCHEDULE

#: LOCATION: MAT'L BASE: N S E W MAT'L: HGT.:

REMARKS:CEILINGWALLSFLOORAREA

FINISHES SELECTED BY OWNER

1. VERIFY ALL HARDWARE W/ OWNER

2. VEIFY ALL DOOR TYPES W/ OWNER

3. VERIFYY ALL DOOR FRAME MATERIALS W/ OWNER

4. SEE WINDOW/DOOR BUCK DETAIL A/501

WD = WOOD (SOLID CORE) HM - HOLOW METAL (GAVANIZED) AL = ALUMINUM

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A601

CEILING TYPE LEGEND

ACOUSTICAL DROP CEILING - SEE INTERIO

CEILING CONDITION SECTION ON THE FINISH

SCHEDULE ON SHEET A601 FOR ADDITIONAL

INFORMATION

SYMBOL LEGEND

NOT IN CONTRACT

NEW EMERGENCY LIGHT ON BATTERY

PACK - UNLESS NOTED OTHERWISE

NEW 2' X 2' EMERGENCY LED LIGHTING FIXTURE

WITH INTEGRAL 90 MINUTE BATTERY PACK -

UNLESS NOTED OTHERWISE

SEE REFLECTED CEILING PLAN FOR LOCATIONS

NEW EXIT LIGHT W/ BATTERY PACK CHECK

FOR PROPER OPERATION REPLACE AS

REQUIRED - UNLESS NOTED OTHERWISE

NEW COMBINATION EXIT SIGN &

EMERGENCY LIGHT WITH BATTERY PACK -

UNLESS NOTED OTHERWISE

EX

EX

EM

EM

1 2 3 4 5 6 7

F

G

H

EXISTING FLOOR

OPEN'G & STAIRS

DN

mech chase copier/fax

SEE ELARGED RESTRM

FOR THESE WINDOWS

SEE DOOR SCHD

REINSTALL POLYGRAPH EQUIPMENT

AND SOUNDPROOFING (WHISPER

ROOMS) AS SPECIFIED BY THE OWNER.

E.O.C.

CAMERA TECH.

E.O.C. LT.

INTEL SGT.

INTEL

UTILITY CLOSET

EXIT CORR.

ELEV EQUIP

ELEV #2

ALTN #2

27r @ 7.11 t @ 10"

SERVER ROOM

CONFERENCE ROOM

OFFICE/STORAGE

302 FISCAL MANAGER

FISCAL TECHS

ADMIN

SERVICES

MAJOR

MAIN ENTRY

SECR AREA

ADMIN

SERVICES

LIEUT

FUTURE

EXPANSION

1512 S.F.

FOYER

POLIGRAPH BOOTH

BREAK ROOM

PROFESS

STANDARDS

OFFICER

PROFESS

STANDARDS

ASSIST

MAIL RM

CORRIDOR

VEST

VEST

EXPOSED STRUCTURE ABOVE

MATCH EXISTING

CLG. HT.

1 2 3 4 5 6 7 8 9 10 a

B

C

D

E

F

G

H

8A 9A

A

B

C

D

E

F

G

G1

H

1097 865

CONTROL

TABLE

MATCH EXISTING

CLG. HT.

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

A801

SCALE: 3/16 = 1'-0" (PRINTED @ 24X36)

REFLECTED CEILING PLAN

SCALE: NTS = (PRINTED @ 11X17)

NOTE:

CONTRACTOR MUST FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS.

AREA OF WORK

KEY PLAN

SP101

SHEET NO.

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

SP102

PROJECT NO.DRAWN

CHECKED DATE

AL

L R

IGH

TS

RE

SE

RV

ED

, TH

ES

E

PL

AN

S A

RE

PR

OT

EC

TE

D B

Y

CO

PY

RIG

HT

LA

W S.

UN

AU

TH

OR

IZE

D U

SE

M

AY

RE

SU

LT

IN

LEG

AL

AC

TIO

N.

CO

PY

RIG

HT

RE

VI

SI

O

N S

10.01.25

2446RAA

RAA

CO

N

ST

RU

CT

IO

N D

O

CU

M

EN

TS

SO

U

TH

M

AG

N

O

LI

A

AV

EN

U

E, O

CA

LA

, F

LO

RI

DA

(3

) 6

-0

W W

W .R

IS

PO

LI

AR

CH

IT

EC

T.

CO

M

JO

E@

RI

SP

O

LI

AR

CH

IT

EC

T.

CO

M

AN

IN

TE

RI

OR

R

EM

OD

EL

IN

G

FO

R:

OCA

LA P

OLI

CE D

EPA

RTM

ENT

- RE

AL T

IME

CRI

ME

CEN

TER

S

O U

T H

P

IN

E A

V E

N U

E O

C A

L A

F

L O

R

ID

A

JOSEPH A. RISPOLI, AIA

ARCHITECT, FL. LICENSE: AR95439

DIGITAL SIGNATURE

Ocala PD Real Time Crime Center

Ocala, FL

SLIDING AUTOMATIC ENTRANCES

SECTION 08 42 29.23

SECTION 08 42 29.23

SLIDING AUTOMATIC ENTRANCES

PART 1 -

1.1

GENERAL

RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 1 Specification Sections, apply to this Section.

1.2

A.

SUMMARY

This Section includes the following types of automatic entrances:

1.

2.

Interior, single slide, sliding automatic entrances, with automatic locking.

Sliding and fixed panels shall be all glass with top and bottom rail.

B. Related Sections:

1. Division 7 Sections for caulking to the extent not specified in this section.

2. Division 8 Section "Aluminum-Framed Entrances and Storefronts" for entrances furnished and installed separately in Division 8 Section.

3. Division 8 Section "Door Hardware" for hardware to the extent not specified in this

Section.

4. Division 26 Sections for electrical connections provided separately including conduit and wiring for power to, and control of, sliding automatic entrances.

5. Division 28 Sections for systems not specified in this section.

1.3 REFERENCES

A. General: Standards listed by reference, including revisions by issuing authority, form a part of this specification section to extent indicated. Standards listed are identified by issuing authority, authority abbreviation, designation number, title or other designation established by issuing authority. Standards subsequently referenced herein are referred to by issuing authority abbreviation and standard designation.

B. Underwriters Laboratories (UL):

1. UL 325 – Standard for Door, Drapery, Gate, Louver, and Window Operators and

Systems.

C. American National Standards Institute (ANSI) / Builders’ Hardware Manufacturers Association

(BHMA):

1.

2.

3.

ANSI/BHMA A156.10: Standard for Power Operated Pedestrian Doors.

ANSI/BHMA A156.5: Standard for Auxiliary Locks and Associated Products

ANSI Z97.1: Standard for Safety Glazing Materials Used In Buildings - Safety

Performance Specifications And Methods Of Test.

D. Consumer Product Safety Commission (CPSC):

1. CPSC 16 CFR 1201: Safety Standard for Architectural Glazing Materials

E. American Society for Testing and Materials (ASTM):

1.

2.

F.

ASTM B221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.

ASTM B209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

American Association of Automatic Door Manufacturers (AAADM):

June 27,2025 Page 1 of 10

Ocala PD Real Time Crime Center

Ocala, FL

SLIDING AUTOMATIC ENTRANCES

SECTION 08 42 29.23

G. National Fire Protection Association (NFPA):

1. NFPA 101 – Life Safety Code.

2. NFPA 70 – National Electric Code.

H.

I.

International Code Council (ICC):

1. IBC: International Building Code

International Organization for Standardization (ISO):

1. ISO 9001 - Quality Management Systems

J. National Association of Architectural Metal Manufacturers (NAAMM):

1. Metal Finishes Manual for Architectural and Metal Products.

K. American Architectural Manufacturers Association (AAMA):

1.

2.

3.

1.4

AAMA 607.1 - Clear Anodic Finishes for Architectural Aluminum.

AAMA 611 Voluntary Specification for Anodized Architectural Aluminum.

AAMA 701 Voluntary Specification for Pile Weatherstripping and Replaceable

Fenestration Weatherseals.

DEFINITIONS

A. Activation Device: Device that, when actuated, sends an electrical signal to the door operator to open the door.

B. Knowing act: Consciously initiating the opening of a power operated door using acceptable methods including wall mounted switches such as push plates and controlled access devices such as keypads, card readers and key switches.

1.5

C. Safety Device: Device that prevents a door from opening or closing, as appropriate.

PERFORMANCE REQUIREMENTS

A. General: Provide automatic entrance door assemblies capable of withstanding loads and thermal movements based on testing manufacturer's standard units in assemblies similar to those indicated for this Project.

B. Operating Range: Minus 30 deg F (Minus 34 deg C) to 130 deg F (54 deg C).

C. Opening-Force Requirements for Egress Doors: Force shall be adjustable; but, not more than

50 lbf (222 N) required to manually set swinging egress door panel(s) in motion.

D. Closing-Force Requirements: Not more than 30 lbf (133 N) required to prevent door from closing.

E. Sliding automatic entrances specified with automatic locking shall be designed to function as follows when set for secure operation:

1. Entrances shall be normally closed and locked by automatic locking system with exterior motion activation system disabled. Interior motion activation system to remain enabled;

free egress.

2. Upon signal from exterior secure activation device, sliding automatic entrances will unlock and open enabling motion activation system. Entrance will be held open as long as an object or pedestrian remains in the activation or safety zones.

3. Once all activation and safety zones have cleared the entrance will close and re-lock, returning to normal state.

June 27,2025 Page 2 of 10

Ocala PD Real Time Crime Center

Ocala, FL

SLIDING AUTOMATIC ENTRANCES

SECTION 08 42 29.23

4.

1.6

At any time during the cycle emergency egress can be achieved by utilizing the emergency breakaway feature.

SUBMITTALS

A. General: Submit the following in accordance with Conditions of the Contract and Division 1

Specification Sections.

B. Shop Drawings: Include plans, elevations, sections, details, hardware mounting heights, and attachments to other work.

C. Color Samples for selection of factory-applied color finishes.

D. Closeout Submittals:

1. Owner’s Manual.

2. Warranties.

1.7

A.

QUALITY ASSURANCE

Installer Qualifications: Manufacturer's authorized representative, with certificate issued by

AAADM, who is trained for installation and maintenance of units required for this Project.

B. Manufacturer Qualifications: A qualified manufacturer with a manufacturing facility compliant with ISO 9001.

C. Manufacturer shall have in place a national service dispatch center providing 24 hours a day, 7 days a week, emergency call back service.

D. Certifications: Automatic sliding door systems shall be certified by the manufacturer to meet performance design criteria in accordance with the following standards:

1. ANSI/BHMA A156.10.

2. NFPA 101.

3. UL 325 listed.

4. IBC.

E. Source Limitations: Obtain automatic entrance door assemblies through one source from a single manufacturer.

F. Product Options: Drawings indicate sizes, profiles, and dimensional requirements of automatic entrance door assemblies and are based on the specific system indicated. Refer to Division 1

Section "Product Requirements."

G. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

H. Emergency-Exit Door Requirements: Comply with requirements of authorities having jurisdiction for automatic entrances serving as a required means of egress.

1.8

A.

PROJECT CONDITIONS

Field Measurements: General Contractor shall verify openings to receive automatic entrance door assemblies by field measurements before fabrication and indicate measurements on Shop

Drawings.

June 27,2025 Page 3 of 10

Ocala PD Real Time Crime Center

Ocala, FL

SLIDING AUTOMATIC ENTRANCES

SECTION 08 42 29.23

B. Mounting Surfaces: General…