D-18912 SH01 R00 HX CONTROL HOUSE PLAN VIEW.pdf
PDF 326 KB Posted
- Attached to
- Halls Substation Control House, Control #3853
- Solicitation number
- 3853
- Issued by
- Knox County, Tennessee
About this file
The document is a detailed control house plan view drawing for the Halls Substation, prepared for Knoxville Utilities Board (KUB) in Tennessee. The plan view provides a comprehensive layout of a control house interior, including electrical distribution panels (Panels #4-#8), safety equipment such as smoke detectors, hydrogen detection systems, eye wash station, and various electrical components like LED emergency lights, exit signs, and receptacles. The drawing specifies equipment locations, electrical specifications, and includes Class I, Group D, Division II weather-proof enclosures for hazardous environments.
The plan view indicates precise measurements and positioning of critical infrastructure components, with specific attention to electrical safety and environmental considerations. Key elements include main disconnect switches, battery racks, exhaust fans with sheet metal hoods, and outdoor wall pack lighting. The drawing is part of a procurement process for a substation control house, with delivery terms specified as FOB Destination and payment terms set at Net 30 upon delivery. The technical specifications suggest a specialized, engineered solution for a utility substation control environment that requires robust electrical and safety design to meet industrial standards.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6' -0
1'-4"
EXIT
DC PANELAC #1
PLAN VIEW
SCALE:3/8" = 1'-0"
AC #2
ATS
120V, 20A
GFCI
1'-6"
2'
2'
2'
S
S
S
SH
SMOKE DETECTORS
QTY AND LOCATIONS
PER NFPA 72
LIGHTING
TANKLESS
WATER HEATER
BELOW SINK
MIRROR ABOVE
SINK
WASTE BIN
LED EXIT SIGN
ROOM LIGHTS
LED EMER.
LIGHT (TYP)120V, 20A
RECEPT.
(TYP)
WINDOW (FIXED)
5'
LED OUTDOOR WALL PACK
"B"
CLASS I, GROUP D, DIV. II
WEATHER PROOF ENCLOSURE
120V, 20A GFCI RECEPT.
FUTURE MATRIX
BADGE READER
DESK
LED 4FT FIXTURE
(TYPICAL)
10 - 4" PVC
CONDUIT
BUSHINGS
W/PLUGS
PANEL #8
FUTURE
PANEL #7
FUTURE
HXT2
PANEL #6
HXT1
PANEL #5
HX83
PANEL #4
HX82
PANEL #3
HX81
PANEL #2
COMM
RACK #1
PANEL #1
SCADA
HVAC
UNIT
AC DIST
PANEL LED EMER.
LIGHT (TYP)
AC DIST
PANEL
SMOKE DETECTORS
QTY AND LOCATIONS
PER NFPA 72
BATTERY
CHARGER
HYDROGEN
DETECTOR
SENSOR
HYDROGEN ALARM
CONTROL UNIT
EYE WASH
TW
O
S
TE
P
BA
TT
ER
Y R
AC
K
SHEET METAL HOOD
W/BUG SCREEN
EXHAUST FAN
CLASS I, GROUP D, DIV. II
WEATHER PROOF ENCLOSURE
120V, 20A GFCI RECEPT.
SHEET METAL HOOD
W/BUG SCREEN
EXHAUST FAN
CANOPY
4' -1
1"
8' -0
'-8
36'-0"
7'-6"
SECURITY
PANEL #1
MAIN DISC
SW SSCB1
MAIN DISC
SW SSCB2
HAND
DRYER
NEMA 4
18"x12"x10"
GPS ANTENNA
PHOTOCELL
LED OUTDOOR WALL PACK
"C"
LED OUTDOOR WALL PACK
"A"
4"X ",NEMA 4-HOLE
SILVER PLATTED CU
GROUND BUS CONN.
D-D- D-
Knoxville Utilities Board
REV.
DRAWN BY: CHK.: APPV.: EST#: (INST.) JOB#: (REM.) MAXIMO#: W.F.P.I#: DATE:DESCRIPTION
SCALE: CLT: GRID:
SHEET OF
18912 18912 18912
Halls (HX) Substation Control House PlanNew Halls Substation HMO J0008436 J0008437 #### ####
1 5 8/2024
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text
ENGINEERING
| Sheets and Views |
| D-18912 SH01 R00 HX CONTROL HOUSE PLAN VIEW-Eng-D (22x34) |
File details come from the government source that posted it. Updated .