BPM007579 Exhibit 7 Project Specifications.pdf

PDF 292 KB Posted

Attached to
ADOT Flagstaff Service Center Re-Roof
Solicitation number
BPM007579
Issued by
Cochise County, Arizona

About this file

ADOT Flagstaff Service Center Re-Roof Project Specifications

This document comprises construction specifications for the re-roofing renovation of the Arizona Department of Transportation (ADOT) Flagstaff Service Center, including detailed technical requirements for sheathing and ethylene-propylene-diene-monomer (EPDM) roofing systems. The project specification document outlines wall sheathing requirements using oriented-strand-board or glass-mat gypsum materials, with specific performance standards for fasteners and installation methods. The roofing system specifications require EPDM sheet roofing at 60 mils thickness in black, along with polyisocyanurate board insulation in minimum 2-inch staggered layers, glass-mat gypsum cover boards, and associated flashing and accessory materials. Installation requirements mandate compliance with FM Approvals RoofNav listings, ASTM standards, and International Building Code fastening schedules. A preinstallation roofing conference is required involving the Owner, Architect, Construction Manager, testing and inspection agency, roofing installer, and roof system manufacturer's representatives to review installation methods, construction schedules, material availability, substrate conditions, and warranty requirements.

The specifications establish rigorous quality control and field inspection requirements, including fastener-pullout testing to be submitted within 24 hours of completion and final roof inspections by the roofing system manufacturer's technical personnel in the presence of the Architect. The roofing system carries a 20-year special warranty from the manufacturer covering the membrane, base flashings, insulation, fasteners, and cover boards, excluding damages from lightning, fire, substrate failure, faulty edge construction, vapor condensation, and unauthorized roof activity. Installation must proceed only under weather conditions permitting proper application per manufacturer specifications, with coordinate protection of exposed roofing at end of workday and during rain forecasts. The specifications reference Design Document 30-25134-00 with a revision date of September 3, 2025, and require all materials to comply with Energy Star listing requirements and ASTM E108 or UL 790 Class A fire ratings.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADOT RE-ROOF 30-25134-00

FLAGSTAFF, AZ 03 SEPTEMBER, 2025

CONSTRUCTION DOCUMENTS

SHEATHING 061600 - 1

SECTION 061600 - SHEATHING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Wall sheathing.

1.3 DELIVERY, STORAGE, AND HANDLING

A. Stack panels flat with spacers beneath and between each bundle to provide air circulation.

Protect sheathing from weather by covering with waterproof sheeting, securely anchored.

Provide for air circulation around stacks and under coverings.

PART 2 - PRODUCTS

2.1 WALL SHEATHING

A. Oriented-Strand-Board Sheathing: DOC PS 2, Exposure 1, Structural I sheathing.

1. Span Rating: Not less than 32/16.

2. Nominal Thickness: Not less than 1/2 inch.

B. Glass-Mat Gypsum Sheathing: ASTM C1177/C1177M.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. GAF, DensDeck Prime

b. USG Securock

c. Prior approved equal per Division 01 requirements.

2. Type and Thickness: Type X, 5/8 inch thick.

3. Size: 48 by 96 inches for vertical installation.

REV2

http://www.specagent.com/Lookup?ulid=12071

SHEATHING 061600 - 2

2.2 FASTENERS

A. General: Provide fasteners of size and type indicated that comply with requirements specified in this article for material and manufacture.

1. For wall sheathing, provide fasteners with hot-dip zinc coating complying with

ASTM A153/A153M .

B. Nails, Brads, and Staples: ASTM F1667.

C. Power-Driven Fasteners: Fastener systems with an evaluation report acceptable to authorities having jurisdiction, based on ICC-ES AC70.

D. Screws for Fastening Sheathing to Wood Framing: ASTM C1002.

E. Screws for Fastening Wood Structural Panels to Cold-Formed Metal Framing: ASTM C954, except with wafer heads and reamer wings, length as recommended by screw manufacturer for material being fastened.

F. Screws for Fastening Gypsum Sheathing to Cold-Formed Metal Framing: Steel drill screws, in length recommended by sheathing manufacturer for thickness of sheathing to be attached.

1. For steel framing less than 0.0329 inch thick, use screws that comply with ASTM C1002.

2. For steel framing from 0.033 to 0.112 inch thick, use screws that comply with

ASTM C954.

PART 3 - EXECUTION

3.1 INSTALLATION, GENERAL

A. Do not use materials with defects that impair quality of sheathing or pieces that are too small to use with minimum number of joints or optimum joint arrangement. Arrange joints so that pieces do not span between fewer than three support members.

B. Cut panels at penetrations, edges, and other obstructions of work; fit tightly against abutting construction unless otherwise indicated.

C. Securely attach to substrate by fastening as indicated, complying with the following:

1. Table 2304.9.1, "Fastening Schedule," in the ICC's International Building Code.

2. ICC-ES evaluation report for fastener.

D. Use common wire nails unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials.

Make tight connections. Install fasteners without splitting wood.

SHEATHING 061600 - 3

E. Coordinate wall and roof sheathing installation with flashing and joint-sealant installation so these materials are installed in sequence and manner that prevent exterior moisture from passing through completed assembly.

F. Do not bridge building expansion joints; cut and space edges of panels to match spacing of structural support elements.

G. Coordinate sheathing installation with installation of materials installed over sheathing so sheathing is not exposed to precipitation or left exposed at end of the workday when rain is forecast.

3.2 WOOD STRUCTURAL PANEL INSTALLATION

A. General: Comply with applicable recommendations in APA Form No. E30, "Engineered Wood

Construction Guide," for types of structural-use panels and applications indicated.

B. Fastening Methods: Fasten panels as indicated below:

1. Wall and Roof Sheathing:

a. Nail to wood framing.

b. Screw to cold-formed metal framing.

c. Space panels 1/8 inchapart at edges and ends.

3.3 GYPSUM SHEATHING INSTALLATION

A. Comply with GA-253 and with manufacturer's written instructions.

1. Fasten gypsum sheathing to cold-formed metal framing with screws.

2. Install panels with a 3/8-inch gap where non-load-bearing construction abuts structural elements.

3. Install panels with a 1/4-inch gap where they abut masonry or similar materials that might retain moisture, to prevent wicking.

B. Apply fasteners so heads bear tightly against face of sheathing, but do not cut into facing.

C. Horizontal Installation: Abut ends over centers of studs, and stagger end joints of adjacent panels not less than one stud spacing. Attach at perimeter and within field of panel to each stud.

1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of panels.

D. Vertical Installation: Install vertical edges centered over studs. Abut ends and edges with those of adjacent panels. Attach at perimeter and within field of panel to each stud.

1. Space fasteners approximately 8 inches o.c. and set back a minimum of 3/8 inch from edges and ends of panels.

SHEATHING 061600 - 4

3.4 FIELD QUALITY CONTROL

A. Testing and Inspecting Agency: Owner will engage a qualified testing agency to perform tests and inspections.

B. Tests: As determined by testing agency from among the following tests:

1. Air-Leakage-Location Testing: Air-barrier sheathing assemblies will be tested for evidence of air leakage according to ASTM E1186, chamber pressurization or depressurization with smoke tracers.

C. Air barriers will be considered defective if they do not pass tests and inspections.

D. Repair damage to air barriers caused by testing; follow manufacturer's written instructions.

END OF SECTION 061600

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 1

SECTION 075323 - ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Ethylene-propylene-diene-terpolymer (EPDM) roofing.

2. Accessory roofing materials.

3. Substrate board.

4. Vapor retarder.

5. Roof insulation.

6. Insulation accessories and cover board.

7. Asphalt materials.

8. Walkways.

B. Related Requirements:

1. Section 061053 "Miscellaneous Rough Carpentry for wood nailers, curbs, and blocking.

2. Section 072100 "Thermal Insulation" for insulation beneath the roof deck.

3. Section 076200 "Sheet Metal Flashing and Trim" for metal roof flashings and counterflashings.

4. Section 079200 "Joint Sealants" for joint sealants, joint fillers, and joint preparation.

1.2 DEFINITIONS

A. Roofing Terminology: Definitions in ASTM D1079 and glossary of NRCA's "The NRCA

Roofing Manual: Membrane Roof Systems" apply to work of this Section.

1.3 PREINSTALLATION MEETINGS

A. Preinstallation Roofing Conference: Conduct conference at Project site.

1. Meet with Owner, Architect, Construction Manager, Owner's insurer if applicable, testing and inspecting agency representative, roofing Installer, roofing system manufacturer's representative, deck Installer, air barrier Installer, and installers whose work interfaces with or affects roofing, including installers of roof accessories and roof-mounted equipment.

2. Review methods and procedures related to roofing installation, including manufacturer's written instructions.

3. Review and finalize construction schedule, and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.

4. Examine deck substrate conditions and finishes, including flatness and fastening.

5. Review structural loading limitations of roof deck during and after roofing.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 2

6. Review base flashings, special roofing details, roof drainage, roof penetrations, equipment curbs, and condition of other construction that affects roofing system.

7. Review governing regulations and requirements for insurance and certificates if applicable.

8. Review temporary protection requirements for roofing system during and after installation.

9. Review roof observation and repair procedures after roofing installation.

1.4 ACTION SUBMITTALS

A. Product Data:

1. Ethylene-propylene-diene-terpolymer (EPDM) roofing.

2. Accessory roofing materials.

3. Substrate board.

4. Vapor retarder.

5. Roof insulation.

6. Insulation accessories and cover board.

7. Asphalt materials.

B. Product Data Submittals:

1. For insulation and roof system component fasteners, include copy of FM Approvals'

RoofNav listing.

C. Shop Drawings: Include roof plans, sections, details, and attachments to other work, including the following:

1. Layout and thickness of insulation.

2. Base flashings and membrane terminations.

3. Flashing details at penetrations.

4. Tapered insulation, thickness, and slopes.

5. Roof plan showing orientation of steel roof deck and orientation of roof membrane and fastening spacings and patterns for mechanically fastened roofing system.

6. Insulation fastening patterns for corner, perimeter, and field-of-roof locations.

7. Tie-in with air barrier.

D. Samples for Verification: For the following products:

1. Roof membrane and flashings of color required.

E. Wind Uplift Resistance Submittal: For roofing system, indicating compliance with wind uplift performance requirements.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer and manufacturer.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 3

B. Manufacturer Certificates:

1. Performance Requirement Certificate: Signed by roof membrane manufacturer, certifying that roofing system complies with requirements specified in "Performance Requirements"

Article.

a. Submit evidence of complying with performance requirements.

2. Special Warranty Certificate: Signed by roof membrane manufacturer, certifying that all materials supplied under this Section are acceptable for special warranty.

C. Product Test Reports: For components of roof membrane and insulation, for tests performed by a qualified testing agency, indicating compliance with specified requirements.

D. Field quality-control reports.

E. Sample Warranties: For manufacturer's special warranties.

1.6 CLOSEOUT SUBMITTALS

A. Maintenance Data: For roofing system to include in maintenance manuals.

B. Certified statement from existing roof membrane manufacturer stating that existing roof warranty has not been affected by Work performed under this Section.

1.7 QUALITY ASSURANCE

A. Manufacturer Qualifications: A qualified manufacturer that is listed in FM Approvals' RoofNav for roofing system identical to that used for this Project.

B. Installer Qualifications: A qualified firm that is approved, authorized, or licensed by roofing system manufacturer to install manufacturer's product and that is eligible to receive manufacturer's special warranty.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Deliver roofing materials to Project site in original containers with seals unbroken and labeled with manufacturer's name, product brand name and type, date of manufacture, approval or listing agency markings, and directions for storing and mixing with other components.

B. Store liquid materials in their original undamaged containers in a clean, dry, protected location and within the temperature range required by roofing system manufacturer. Protect stored liquid material from direct sunlight.

1. Discard and legally dispose of liquid material that cannot be applied within its stated shelf life.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 4

C. Protect roof insulation materials from physical damage and from deterioration by sunlight, moisture, soiling, and other sources. Store in a dry location. Comply with insulation manufacturer's written instructions for handling, storing, and protecting during installation.

D. Handle and store roofing materials, and place equipment in a manner to avoid permanent deflection of deck.

1.9 FIELD CONDITIONS

A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit roofing system to be installed in accordance with manufacturer's written instructions and warranty requirements.

1.10 WARRANTY

A. Special Warranty: Manufacturer agrees to repair or replace components of roofing system that fail in materials or workmanship within specified warranty period.

1. Special warranty includes roof membrane, base flashings, roof insulation, fasteners, cover boards, substrate board, roof pavers, and other components of roofing system.

2. Warranty Period: 20 years from Date of Substantial Completion.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. General Performance: Installed roofing system and base flashings to withstand specified uplift pressures, thermally induced movement, and exposure to weather without failure due to defective manufacture, fabrication, installation, or other defects in construction. Roofing and flashings to remain watertight.

1. Accelerated Weathering: Roof membrane to withstand 2000 hours of exposure when tested in accordance with ASTM G152, ASTM G154, or ASTM G155.

2. Impact Resistance: Roof membrane to resist impact damage when tested in accordance with ASTM D3746, ASTM D4272, or the "Resistance to Foot Traffic Test" in FM

Approvals 4470.

B. Material Compatibility: Roofing materials to be compatible with one another and adjacent materials under conditions of service and application required, as demonstrated by roof membrane manufacturer based on testing and field experience.

C. FM Approvals' RoofNav Listing: Roof membrane, base flashings, and component materials comply with requirements in FM Approvals 4450 or FM Approvals 4470 as part of a roofing system, and are listed in FM Approvals' RoofNav for Class 1 or noncombustible construction, as applicable. Identify materials with FM Approvals Certification markings.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 5

1. Fire/Windstorm Classification: Class 1A-90.

2. Wind Uplift Classification: Class 1-90.

D. Energy Star Listing: Roofing system to be listed on the DOE's Energy Star "Roof Products

Qualified Product List" for low -slope roof products.

E. Exterior Fire-Test Exposure: ASTM E108 or UL 790, Class A; for application and roof slopes indicated; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

F. Fire-Resistance Ratings: Comply with fire-resistance-rated assembly designs indicated. Identify products with appropriate markings of applicable testing agency.

2.2 ETHYLENE-PROPYLENE-DIENE-TERPOLYMER (EPDM) ROOFING

A. EPDM Sheet: ASTM D4637/D4637M, Polyester-Reinforced, EPDM sheet.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Holcim Elevate, RubberGard Max EPDM

b. Carlisle Syntec Systems, Sure-Tough EPDM

c. Johns Manville, Inc.

d. Versico Roofing Systems

e. GenFlex

f. Mule-Hide Products Co., Inc.

2. Thickness: 60 mils (1.5 mm), nominal.

3. Exposed Face Color: Black.

4. Source Limitations: Obtain components for roofing system from manufacturers approved by roof membrane manufacturer.

2.3 ACCESSORY ROOFING MATERIALS

A. General: Accessory materials recommended by roofing system manufacturer for intended use and compatible with other roofing components.

1. Adhesive and Sealants: Comply with VOC limits of authorities having jurisdiction.

B. Sheet Flashing: 60-mil- (1.5-mm-) thick EPDM, partially cured or cured, according to application.

C. Prefabricated Pipe Flashings: As recommended by roof membrane manufacturer.

D. Bonding Adhesive: Manufacturer's standard.

http://www.specagent.com/LookUp/?ulid=12785&mf=&src=wd

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 6

E. Seaming Material: Manufacturer's standard, synthetic-rubber polymer primer and 3-inch- (75-mm-) wide minimum, butyl splice tape with release film.

F. Lap Sealant: Manufacturer's standard, single-component sealant, colored to match membrane roofing.

G. Water Cutoff Mastic: Manufacturer's standard butyl mastic sealant.

H. Metal Termination Bars: Manufacturer's standard, predrilled stainless steel or aluminum bars, approximately 1 by 1/8 inch (25 by 3 mm) thick; with anchors.

I. Metal Battens: Manufacturer's standard, aluminum-zinc-alloy-coated or zinc-coated steel sheet, approximately 1 inch wide by 0.05 inch thick (25 mm wide by 1.3 mm thick), prepunched.

J. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening components to substrate, and acceptable to roofing system manufacturer.

K. Miscellaneous Accessories: Provide pourable sealers, preformed cone and vent sheet flashings, molded pipe boot flashings, preformed inside and outside corner sheet flashings, reinforced

EPDM securement strips, T-joint covers, in-seam sealants, termination reglets, cover strips, and other accessories.

2.4 SUBSTRATE BOARD

A. Glass-Mat Gypsum Roof Substrate Board: ASTM C1177/C1177M, water-resistant gypsum board.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. GAF, DensDeck Roof Board

b. Georgia-Pacific Gypsum LLC

c. National Gypsum Company

d. USG Securock

e. Prior approved equal per Division 01 requirements.

2. Thickness: 1/2 inch (13 mm).

B. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening substrate panel to roof deck.

2.5 VAPOR RETARDER

A. Butyl-Rubber-Sheet Vapor Retarder, Self-Adhering: Polyethylene film laminated to layer of butyl rubber adhesive, minimum 30-mil (0.76-mm) total thickness; maximum permeance rating

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 7

of 0.1 perm (6 ng/Pa x s x sq. m); cold applied, with slip-resisting surface and release paper backing. Provide primer when recommended by vapor retarder manufacturer.

2.6 ROOF INSULATION

A. General: Preformed roof insulation boards manufactured or approved by EPDM roof membrane manufacturer, approved for use in FM Approvals' RoofNav-listed roof assemblies.

B. Polyisocyanurate Board Insulation: ASTM C1289, Type II, Class 1, Grade 2 felt facer on both major surfaces.

1. Basis of Design: Subject to compliance with the requirements, provide Johns Manville R-

Panel Roof Insulation, or comparable product by one of the following manufacturers:

a. Holcim Elevate

b. Carlisle Syntec Systems

c. Versico Roofing Systems

d. GenFlex

e. Mule-Hide Products Co., Inc.

2. Compressive Strength: 20 psi (138 kPa).

3. Thickness: Minimum 2 staggered layers

a. Base Layer: 1-1/2 inches (38 mm).

b. Upper Layer: As required for overall system thickness indicated on Drawings.

C. Tapered Insulation: Provide factory-tapered insulation boards.

1. Material: Match roof insulation.

2. Minimum Thickness: 1/4 inch (6.35 mm).

3. Slope:

a. Roof Field: 1/4 inch per foot (1:48) unless otherwise indicated on Drawings.

b. Saddles and Crickets: 1/2 inch per foot (1:24) unless otherwise indicated on

Drawings.

2.7 INSULATION ACCESSORIES AND COVER BOARD

A. General: Roof insulation accessories recommended by insulation manufacturer for intended use and compatibility with other roofing system components.

B. Fasteners: Factory-coated steel fasteners and metal or plastic plates complying with corrosion-resistance provisions in FM Approvals 4470, designed for fastening roof insulation and cover boards to substrate, and acceptable to roofing system manufacturer.

C. Insulation Adhesive: Insulation manufacturer's recommended adhesive formulated to attach roof insulation to substrate or to another insulation layer as follows:

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 8

1. Full-spread, spray-applied, low-rise, two-component urethane adhesive.

D. Glass-Mat Gypsum Cover Board: ASTM C1177/C1177M, water-resistant gypsum substrate.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. GAF, DensDeck Roof Board

b. Georgia-Pacific Gypsum LLC

c. National Gypsum Company

d. USG Securock

e. Prior approved equal per Division 01 requirements.

2. Thickness: 1/2 inch (13 mm).

E. Protection Mat: Woven or nonwoven polypropylene, polyolefin, or polyester fabric; water permeable and resistant to UV degradation; type and weight as recommended by roofing system manufacturer for application.

2.8 WALKWAYS

A. Flexible Walkways: Factory-formed, nonporous, heavy-duty, slip-resisting, surface-textured walkway pads, approximately 3/16 inch (5 mm) thick and acceptable to roofing system manufacturer.

1. Size: Approximately 36 by 60 inches (914 by 1524 mm).

2. Color: Contrasting with roof membrane.

B. Locations: Refer to Architectural Roof Plans.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements and other conditions affecting performance of the Work.

1. Verify that roof openings and penetrations are in place, curbs are set and braced, and roof-drain bodies are securely clamped in place.

2. Verify that wood blocking, curbs, and nailers are securely anchored to roof deck at penetrations and terminations and that nailers match thicknesses of insulation.

3. Verify that surface plane flatness and fastening of steel roof deck complies with requirements in Section 053100 "Steel Decking."

B. Proceed with installation only after unsatisfactory conditions have been corrected.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 9

3.2 PREPARATION

A. Clean substrate of dust, debris, moisture, and other substances detrimental to roofing system installation in accordance with roofing system manufacturer's written instructions. Remove sharp projections.

B. Prevent materials from entering and clogging roof drains and conductors and from spilling or migrating onto surfaces of other construction. Remove roof-drain plugs when no work is taking place or when rain is forecast.

C. Perform fastener-pullout tests in accordance with roof system manufacturer's written instructions.

1. Submit test result within 24 hours of performing tests.

a. Include manufacturer's requirements for any revision to previously submitted fastener patterns required to achieve specified wind uplift requirements.

3.3 INSTALLATION OF ROOFING, GENERAL

A. Install roofing system in accordance with roofing system manufacturer's written instructions, FM Approvals' RoofNav assembly requirements, and FM Global Property Loss Prevention Data

Sheet 1-29.

B. Complete terminations and base flashings and provide temporary seals to prevent water from entering completed sections of roofing system at end of workday or when rain is forecast.

Remove and discard temporary seals before beginning work on adjoining roofing.

C. Install roof membrane and auxiliary materials to tie in to existing roofing to maintain weathertightness of transition and to not void warranty for existing roofing system.

D. Coordinate installation and transition of roofing system component serving as an air barrier with air barrier(s) specified under Division 7.

3.4 INSTALLATION OF SUBSTRATE BOARD

A. Install substrate board with long joints in continuous straight lines, with end joints staggered not less than 24 inches (610 mm) in adjacent rows.

1. At steel roof decks, install substrate board at right angle to flutes of deck.

a. Locate end joints over crests of steel roof deck.

2. Tightly butt substrate boards together.

3. Cut substrate board to fit tight around penetrations and projections, and to fit tight to intersecting sloping roof decks.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 10

4. Fasten substrate board to top flanges of steel deck in accordance with recommendations in FM Approvals' RoofNav listed roof assembly requirements for specified Windstorm

Resistance Classification and FM Global Property Loss Prevention Data Sheet 1-29.

5. Fasten substrate board to top flanges of steel deck to resist uplift pressure at corners, perimeter, and field of roof in accordance with roofing system manufacturers' written instructions.

3.5 INSTALLATION OF VAPOR RETARDER

A. Self-Adhering-Sheet Vapor Retarder: Prime substrate if required by manufacturer. Install self-adhering-sheet vapor retarder over area to receive vapor retarder, side and end lapping each sheet a minimum of 3-1/2 and 6 inches (90 and 150 mm), respectively.

1. Extend vertically up parapet walls and projections to a minimum height equal to height of insulation and cover board.

2. Seal laps by rolling.

B. Completely seal vapor retarder at terminations, obstructions, and penetrations to prevent air movement into roofing system.

3.6 INSTALLATION OF INSULATION

A. Coordinate installing roofing system components so insulation is not exposed to precipitation or left exposed at end of workday.

B. Comply with roofing system and insulation manufacturer's written instructions for installing roof insulation.

C. Installation Over Metal Decking:

1. Install base layer of insulation with joints staggered not less than 24 inches (610 mm) in adjacent rows.

a. Locate end joints over crests of decking.

b. Where installing composite and noncomposite insulation in two or more layers, install noncomposite board insulation for bottom layer and intermediate layers, if applicable, and install composite board insulation for top layer.

c. Trim insulation neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.

d. Make joints between adjacent insulation boards not more than 1/4 inch (6 mm) in width.

e. At internal roof drains, slope insulation to create a square drain sump with each side equal to the diameter of the drain bowl plus 24 inches (610 mm).

1) Trim insulation so that water flow is unrestricted.

f. Fill gaps exceeding 1/4 inch (6 mm) with insulation.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 11

g. Cut and fit insulation within 1/4 inch (6 mm) of nailers, projections, and penetrations.

h. Mechanically attach base layer of insulation and substrate board using mechanical fasteners specifically designed and sized for fastening specified board-type roof insulation to metal decks.

1) Fasten insulation in accordance with requirements in FM Approvals'

RoofNav for specified Windstorm Resistance Classification.

2) Fasten insulation to resist specified uplift pressure at corners, perimeter, and field of roof.

2. Install upper layers of insulation and tapered insulation with joints of each layer offset not less than 12 inches (305 mm) from previous layer of insulation.

a. Staggered end joints within each layer not less than 24 inches (610 mm) in adjacent rows.

b. Install with long joints continuous and with end joints staggered not less than

12 inches (305 mm) in adjacent rows.

c. Trim insulation neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.

d. Make joints between adjacent insulation boards not more than 1/4 inch (6 mm) in width.

e. At internal roof drains, slope insulation to create a square drain sump with each side equal to the diameter of the drain bowl plus 24 inches (610 mm).

f. Trim insulation so that water flow is unrestricted.

g. Fill gaps exceeding 1/4 inch (6 mm) with insulation.

h. Cut and fit insulation within 1/4 inch (6 mm) of nailers, projections, and penetrations.

i. Adhere each layer of insulation to substrate using adhesive in accordance with FM

Approvals' RoofNav listed roof assembly requirements for specified Windstorm

Resistance Classification and FM Global Property Loss Prevention Data Sheet 1-

29, as follows:

1) Set each layer of insulation in a uniform coverage of full-spread insulation adhesive, firmly pressing and maintaining insulation in place.

3.7 INSTALLATION OF COVER BOARDS

A. Install cover boards over insulation with long joints in continuous straight lines with end joints staggered between rows. Offset joints of insulation below a minimum of 6 inches (150 mm) in each direction.

1. Trim cover board neatly to fit around penetrations and projections, and to fit tight to intersecting sloping roof decks.

2. At internal roof drains, conform to slope of drain sump.

a. Trim cover board so that water flow is unrestricted.

3. Cut and fit cover board tight to nailers, projections, and penetrations.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 12

4. Adhere cover board to substrate using adhesive in accordance with FM Approvals'

RoofNav listed roof assembly requirements for specified Windstorm Resistance

Classification and FM Global Property Loss Prevention Data Sheet 1-29, as follows:

a. Set cover board in a uniform coverage of full-spread insulation adhesive, firmly pressing and maintaining insulation in place.

3.8 INSTALLATION OF ADHERED ROOF MEMBRANE

A. Adhere roof membrane over area to receive roofing in accordance with roofing system manufacturer's written instructions.

B. Unroll membrane roof membrane and allow to relax before installing.

C. Start installation of roofing in presence of roofing system manufacturer's technical personnel and Owner's testing and inspection agency.

D. Accurately align roof membrane, and maintain uniform side and end laps of minimum dimensions required by manufacturer. Stagger end laps.

E. Bonding Adhesive: Apply to substrate and underside of roof membrane at rate required by manufacturer, and allow to partially dry before installing roof membrane. Do not apply to splice area of roof membrane.

F. In addition to adhering, mechanically fasten roof membrane securely at terminations, penetrations, and perimeters.

G. Apply roof membrane with side laps shingled with slope of roof deck where possible.

H. Adhesive Seam Installation: Clean both faces of splice areas, apply splicing cement.

1. Firmly roll side and end laps of overlapping roof membrane to ensure a watertight seam installation.

2. Apply lap sealant and seal exposed edges of roofing terminations.

3. Apply a continuous bead of in-seam sealant before closing splice if required by roofing system manufacturer.

I. Tape Seam Installation: Clean and prime both faces of splice areas, apply splice tape.

1. Firmly roll side and end laps of overlapping roof membrane to ensure a watertight seam installation.

2. Apply lap sealant and seal exposed edges of roofing terminations.

J. Factory-Applied Seam Tape Installation: Clean and prime surface to receive tape.

1. Firmly roll side and end laps of overlapping roof membrane to ensure a watertight seam installation.

2. Apply lap sealant and seal exposed edges of roofing terminations.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 13

K. Repair tears, voids, and lapped seams in roof membrane that do not comply with requirements.

L. Spread sealant or mastic bed over deck-drain flange at roof drains, and securely seal roof membrane in place with clamping ring.

M. Adhere protection sheet over roof membrane at locations indicated.

3.9 INSTALLATION OF BASE FLASHING

A. Install sheet flashings and preformed flashing accessories, and adhere to substrates in accordance with roofing system manufacturer's written instructions.

B. Apply bonding adhesive to substrate and underside of sheet flashing at required rate, and allow to partially dry. Do not apply to seam area of flashing.

C. Flash penetrations and field-formed inside and outside corners with cured or uncured sheet flashing.

D. Clean splice areas, apply splicing cement, and firmly roll side and end laps of overlapping sheets to ensure a watertight seam installation. Apply lap sealant and seal exposed edges of sheet flashing terminations.

E. Terminate and seal top of sheet flashings and mechanically anchor to substrate through termination bars.

3.10 INSTALLATION OF COATINGS

A. Apply coatings to roof membrane and base flashings in accordance with manufacturer's written recommendations, by spray, roller, or other suitable application method.

3.11 INSTALLATION OF WALKWAYS

A. Flexible Walkways: Install walkway products in accordance with manufacturer's written instructions.

1. Install flexible walkways at locations indicated on the Drawings, but no less than the following locations:

a. Perimeter of each rooftop unit.

b. Between each rooftop unit location, creating a continuous path connecting rooftop unit locations.

c. Between each roof hatch and each rooftop unit location or path connecting rooftop unit locations.

d. Top and bottom of each roof access ladder.

e. Between each roof access ladder and each rooftop unit location or path connecting rooftop unit locations.

f. Other locations indicated on Drawings.

REV2

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 14

g. As required by roof membrane manufacturer's warranty requirements.

2. Provide 6-inch (76-mm) clearance between adjoining pads.

3. Adhere walkway products to substrate with compatible adhesive in accordance with roofing system manufacturer's written instructions.

a. Provide manufacturer’s recommended protection layer underneath walkway pads.

3.12 FIELD QUALITY CONTROL

A. Testing Agency: Owner will engage a qualified testing agency to inspect substrate conditions, surface preparation, roof membrane application, sheet flashings, protection, and drainage components, and to furnish reports to Architect.

B. Final Roof Inspection: Arrange for roofing system manufacturer's technical personnel to inspect roofing installation on completion, in presence of Architect, and to prepare inspection report.

C. Repair or remove and replace components of roofing system where inspections indicate that they do not comply with specified requirements.

D. Additional testing and inspecting, at Contractor's expense, will be performed to determine if replaced or additional work complies with specified requirements.

3.13 PROTECTING AND CLEANING

A. Protect roofing system from damage and wear during remainder of construction period. When remaining construction does not affect or endanger roofing system, inspect roofing system for deterioration and damage, describing its nature and extent in a written report, with copies to

Architect and Owner.

B. Correct deficiencies in or remove roofing system that does not comply with requirements, repair substrates, and repair or reinstall roofing system to a condition free of damage and deterioration at time of Substantial Completion and in accordance with warranty requirements.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 15

3.14 ROOFING INSTALLER'S WARRANTY

A. WHEREAS _______________________________ of ___________________________, herein called the "Roofing Installer," has performed roofing and associated work ("work") on the following project:

1. Owner:_________________________________________________________________.

2. Owner Address: _________________________________________________________.

3. Building Name/Type: _____________________________________________________.

4. Building Address: ________________________________________________________.

5. Area of Work: ___________________________________________________________.

6. Acceptance Date: ________________________________________________________.

7. Warranty Period: ________________________________________________________.

8. Expiration Date: _________________________________________________________.

B. AND WHEREAS Roofing Installer has contracted (either directly with Owner or indirectly as a subcontractor) to warrant said work against leaks and faulty or defective materials and workmanship for designated Warranty Period, C. NOW THEREFORE Roofing Installer hereby warrants, subject to terms and conditions herein set forth, that during Warranty Period Roofing Installer will, at Roofing Installer's own cost and expense, make or cause to be made such repairs to or replacements of said work as are necessary to correct faulty and defective work and as are necessary to maintain said work in a watertight condition.

D. This Warranty is made subject to the following terms and conditions:

1. Specifically excluded from this Warranty are damages to work and other parts of the building, and to building contents, caused by:

a. lightning;

b. fire;

c. failure of roofing system substrate, including cracking, settlement, excessive deflection, deterioration, and decomposition;

d. faulty construction of parapet walls, copings, chimneys, skylights, vents, equipment supports, and other edge conditions and penetrations of the work;

e. vapor condensation on bottom of roofing; and

f. activity on roofing by others, including construction contractors, maintenance personnel, other persons, and animals, whether authorized or unauthorized by

Owner.

2. When work has been damaged by any of foregoing causes, Warranty shall be null and void until such damage has been repaired by Roofing Installer and until cost and expense thereof have been paid by Owner or by another responsible party so designated.

3. Roofing Installer is responsible for damage to work covered by this Warranty but is not liable for consequential damages to building or building contents resulting from leaks or faults or defects of work.

ETHYLENE-PROPYLENE-DIENE-MONOMER (EPDM) ROOFING 075323 - 16

4. During Warranty Period, if Owner allows alteration of work by anyone other than

Roofing Installer, including cutting, patching, and maintenance in connection with penetrations, attachment of other work, and positioning of anything on roof, this

Warranty shall become null and void on date of said alterations, but only to the extent said alterations affect work covered by this Warranty. If Owner engages Roofing Installer to perform said alterations, Warranty shall not become null and void unless Roofing

Installer, before starting said work, shall have notified Owner in writing, showing reasonable cause for claim, that said alterations would likely damage or deteriorate work, thereby reasonably justifying a limitation or termination of this Warranty.

5. During Warranty Period, if original use of roof is changed and it becomes used for, but was not originally specified for, a promenade, work deck, spray-cooled surface, flooded basin, or other use or service more severe than originally specified, this Warranty shall become null and void on date of said change, but only to the extent said change affects work covered by this Warranty.

6. Owner shall promptly notify Roofing Installer of observed, known, or suspected leaks, defects, or deterioration and shall afford reasonable opportunity for Roofing Installer to inspect work and to examine evidence of such leaks, defects, or deterioration.

7. This Warranty is recognized to be the only warranty of Roofing Installer on said work and shall not operate to restrict or cut off Owner from other remedies and resources lawfully available to Owner in cases of roofing failure. Specifically, this Warranty shall not operate to relieve Roofing Installer of responsibility for performance of original work according to requirements of the Contract Documents, regardless of whether Contract was a contract directly with Owner or a subcontract with Owner's General Contractor.

E. IN WITNESS THEREOF, this instrument has been duly executed this ___________ day of

1. Authorized Signature: _______________________________________.

2. Name: ______________________________________.

3. Title: _______________________________________.

END OF SECTION 075323