BPM007579 Exhibit 6 Project Drawings_ Revised Pages.pdf
PDF 1 MB Posted
- Attached to
- ADOT Flagstaff Service Center Re-Roof
- Solicitation number
- BPM007579
- Issued by
- Cochise County, Arizona
About this file
ADOT Building Re-Roof Project - Construction Documents Summary
This file comprises construction documents for the Arizona Department of Transportation (ADOT) Building Re-Roofing Project located at 1959 SW Woodlands Village Boulevard, Flagstaff, Arizona 86001. The project involves the complete removal and replacement of the existing roof system with a new EPDM membrane roofing assembly, including installation of new roof drains, curbs, flashing details, and associated roofing components. The scope encompasses structural modifications to accommodate the new roofing system, reinstallation of existing rooftop units (RTUs) on new curbs, replacement of saddle flashing at parapet walls, infilling of existing mechanical wells, and installation of four new 24-inch by 16-inch minimum access panels. The project includes mechanical work involving relocation of RTU-29 to a new position with a 26-inch tall roof curb, removal and reinstallation of 28 existing rooftop units, 11 exhaust fans, and 2 condensing units. The roof system specifications include 6 inches of rigid polyiso insulation with tapered insulation providing minimum 1/4-inch per foot slope to roof drains, EPDM membrane roofing, and cover board installation over existing metal deck. Project drawings indicate work at multiple roof sections with various parapet heights ranging from 21 feet 6 inches to 31 feet 4 inches.
The project documents establish detailed technical requirements for materials, fastening schedules, flashing details, and coordination procedures between roofing, mechanical, and electrical trades. All roof curbs must be a minimum of 8 inches above roofing levels with tapered insulation roof saddles for drainage around curbs. No roof penetrations are permitted within 4 feet on each side of firewalls. The energy code data specifies an R-value of 36.3 for the roof assembly in IECC Climate Zone 5B (Coconino County, Arizona). Documentation includes comprehensive schedules for 28 existing packaged rooftop units with specific airflow ratings (ranging from 1,200 to 8,000 CFM), 11 exhaust fans, roof drain specifications with cast iron bodies and self-locking dome strainers, electric unit heater requirements, and grille/register schedules. The project requires coordination of mechanical equipment removal and reinstallation, including temporary disconnection and reconnection of natural gas piping, condensate drain piping, and refrigerant lines. All existing rooftop equipment requires pre-demolition airflow testing to establish baseline performance, with reinstalled units to be balanced to tested airflow values.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOF PLAN GENERAL NOTES
A. ROOF PLAN GENERAL NOTES APPLY TO ALL ROOF PLAN
SHEETS.
B. ROOF SLOPES ARE CREATED BY SLOPING THE ROOF
STRUCTURE UNLESS NOTED OTHERWISE. SEE STRUCTURAL
DRAWINGS FOR ELEVATIONS OF THE HIGH AND LOW POINTS TO
DETERMINE PROPER TAPER IN INSULATION.
C. TAPERED INSULATION SHALL PROVIDE A MINIMUM OF 1/4-INCH
PER FOOT OF SLOPE TO ROOF DRAINS, UNLESS NOTED
OTHERWISE.
D. ALL ROOF CURBS TO BE A MINIMUM OF 8 INCHES ABOVE
ROOFING LEVELS. PROVIDE TAPERED INSULATION ROOF
SADDLES AT ROOF CURBS TO PROVIDE DRAINAGE AROUND
CURB.
E. SEE STRUCTURAL DRAWINGS FOR FRAMING AROUND ROOF
PENETRATIONS.
F. COORDINATE THE SIZE AND LOCATION OF ROOF PENETRATIONS
FOR MECHANICAL AND ELECTRICAL EQUIPMENT. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS FOR PENETRATIONS
NOT SHOWN ON THIS DRAWING.
G. FLASH DRAINS, CURBS, VENTS AND STACKS PER
MANUFACTURER'S RECOMMENDATIONS IF DETAIL NOT SHOWN
ON DRAWINGS.
H. NO ROOF PENETRATIONS ALLOWED WITHIN 4'-0" EACH SIDE OF
FIREWALL.
/8
A-1
5B
A5.1
5B
A5.1
5A
A5.1
5A
A5.1
E-8
A-4
A-4
A1.3
2A
1A
A9.1
1A
A9.1
2A
A9.1
2A
A9.1
@ METAL STUD
WALL
@ METAL STUD
WALL
@ BRICK WALL
@ BRICK WALL
E-8
A-4
D-3
/2
7' - 10 3/4" V.I.F.
SCOPE OF WORK AREA
/4
A-5 A-5
A-5
A-5
EIFS
EIFS
EIFS
A-5
A-5
A-5
BRICK
B R
IC
K
EIFS
2C
A9.1
2C
A9.1
TYP.
TYP.
E-7
B R
IC
K
M E
T A
L S
ID
IN
G
W A
LL
B
E
LO
W B
R
IC
K W
A
LL
B E
LO
W
BRICK WALL BELOW
A-2
A-2
A-2
A-2
A-2
TYP.
A-1
A-1
A-1
A-7
A-2
A-2
A-2 A-2
PARAPET 21' - 6"
BRICK
E
IF
S
E
IF
S
PARAPET 31' - 4"
PARAPET 31' - 4"
E P
D M
5A
A9.3
A9.3
2B
A9.3
3A
19' - 3 3/4"
24' - 9 1/4"
A-8
1' - 0" MIN.
1/4" / 1'-0"
/4
A9.1 3A A9.14A
A9.1
5A
A9.1
5B
A-3
A-3
A-3
A-3
1B
A9.1
WALKING
PAD, TYP.
3A
A1.3
4A
A1.3
A-6
A-6
A-6
A-23
A-6
A-6A-6
A-3
A-2
3' - 0"3' - 0"
/4
/4
" / 1 '-0
/8
" / 1 '-0
/4
/4
A-2
A-2
E-7 TYP.
5B
A9.3
A-1
1/4" / 1'-0"
4A
A1.2A
4A
A1.2A
SIM.
4B
A9.1
A-1
A-9
A-9
B R
IC
K
W A
LL
B
E
LO
W
25' - 6 1/2"
PARAPET 28' - 0"
BARREL VAULT
(E) ROOF
CRICKET
BARREL VAULT
3D
A5.1
RIDGE
EIFS
A-2
A-2
A-2TYP.
EXISTING
EXISTING
EXISTING
EXISTING
PARAPET 28' - 0"
EXISTING
PARAPET 28' - 0"
EXISTING
PARAPET 31' - 4"
EXISTING
PARAPET 28' - 0"
EXISTING
PARAPET 28' - 0"
EXISTING
PARAPET 28' - 0"
EXISTING
PARAPET 28' - 0"
EXISTING
E
IF
S B
E
LO
W
EIFS
BELOW
E
IF
S B
E
LO
W
5 5/8" / 1'-0"
5 5/8" / 1'-0"
A-23
A-6
A-23
A-23
A-23
PARAPET 28' - 0"
A-23
INSTALLER TO
CONFIRM
EXISTING ROOF
AND MAINTAIN
WARRANTY OF
THAT SYSTEM
WITH THE
INSTALL OF THE
NEW TIE IN.
SHEET NOTES - ROOF #
5B
A5.1
5A
A5.1
5C
A5.1
5D
A5.1
/4
/8
SCOPE OF WORK
AREA
HVAC UNIT, TYP.
RTU UNIT, TYP.
(E) STOREFRONT
SYSTEM
ENERGY CODE DATA VALUES ROOF R-1
MATERIAL: DEPTH R-VALUE
OUTSIDE AIR FILM 0.00" 0.25
EPDM ROOFING MEMBRANE 0.06" 0.00
COVER BOARD 0.50" 0.56
RIGID INSULATION (POLYISO) 6.00" 34.8
(E) METAL DECK 1.50" 0.00
INSIDE AIR FILM 0.00" 0.68
TOTAL: 8.06" 36.3
SOLAR REFLECTANCE INDEX: 9
IECC CLIMATE ZONE: 5B COCONINO
ROOF - INSULATION ENTIRELY ABOVE DECK R-30ci
ASHRAE 90.1-2019 R-30ci
METAL FRAMED WALLS R-20 + R-9ci
4A
A1.3
RIGID INSULATION FILL
METAL DECK AND FRAMING PER
STRUCTURAL
(E) RTU WELL
(E) DUCT
(E) CEILING
14' - 6"
A1.3
5A
TPO MEMBRANE AT BARREL VAULT
PATCH TO MATCH EXISTING
3A
A1.3 RIGID INSULATION
EXISTING ROOF
SYSTEM
EXISTING RTU WELL INFILL. INSTALL 4
NEW ACCESS HATCHES TO BE
LOCATED WITH FACILITIES TO ALLOW
MAINTENANCE ACCESS.
FRAMING SEE
STRUCTURAL DRAWINGS
NEW DUCT, RE: MECHANICAL
(E) CEILING
SYSTEM
9' - 8"
TPO MEMBRANE AT BARREL VAULT
PATCH TO MATCH EXISTING
CONNECTIONS PER
STRUCTURAL
(E) WALL FRAMING TO
REMAIN. CUT OPENINGS TO
ALLOW ACCESS PANELS TO
BE INSTALLED FOR
SPRINKLER MAINTENANCE
(E) WELL
RIGID INSULATION
TPO MEMBRANE TO MATCH EXISTING
IN THICKNESS COLOR AND TEXTURE
COVER BOARD TO MATCH
EXISTING BARREL VAULT
EXISTING
TPO ROOF
SYSTEM
INTERIOR SIDE
NEW METAL DECK AND
FRAMING PER STRUCTURAL
SHINGLE LAP NEW
MEMBRANE OVER EXISTING
WITH MFG APPROVED
SYSTEM
INSTALL 4 NEW 24"HX16"W
MINIMUM ACCESS PANELS
INTO OLD WELL. LOCATE
PANELS SO THEY CAN BE
ACCESSED BY FACILITIES
FROM BELOW.
TOUCH UP ALL
PAINT AS
NEEDED TO
MATCH BLACK
PAINT
LEAVE MINIMUM AMOUNT OF
(E) SHEATHING AS REQ.'D BY
STRUCTURAL
A5.1
3D
INSTALLER TO
CONFIRM
EXISTING ROOF
AND MAINTAIN
WARRANTY OF
THAT SYSTEM
WITH THE
INSTALL OF THE
NEW TIE IN.
D
L R
G ro u p
REVISIONS
KEY PLAN
A B C D E F
A
NORTH
/2
/2
:5
:1
P
M
A u to d e s k D o c s
/3
-2
-0
A
D O
T M
V D
R e ro o f N
/3
-2
-0
A
D O
T M
V D
R e ro o f_ A
R
.r v t
30-25134-00
09/03/2025
A D
O T
B U
IL
D
IN
G
R E
-R O
O F
P R
O J E
C T
CONSTRUCTION
DOCUMENTS
OVERALL ROOF
PLAN
A1.3
S
W o o d la n d s V ill a g e B lv d
F la g s ta ff A
Z
T R
U E
N
SCALE: 1" = 10'-0"
OVERALL ROOF PLAN
0 5 10 20
SCALE: 1" = 10'
A-1 NEW ROOF SYSTEM
A-2 NEW ROOF CRICKET
A-3 NEW HEAVY DUTY WALKING PADS, FINAL
LOCATION CONFIRMED BY OWNER TO ACCESS
PANELS ON RTU
A-4 RE-INSTALL RTU UNITS WITH NEW CURBS PER
MECHANICAL
A-5 NEW ROOF DRAIN IN EXISTING LOCATION SET TO
ELEVATION OF NEW ROOF THICKNESS
A-6 OUTLETS REINSTALLED PER ELECTRICAL
A-7 CROSS-OVER ROOF LADDER
A-8 SHINGLE LAP NEW ROOFING OVER EXISTING,
ROOFING MATERIAL AND COLOR TO MATCH
EXISTING
A-9 RE-HANG GUTTER. SLOPE TO DRAIN
A-23 REMOVE (E) SADDLE FLASHING, CLEAN WALLS
AND INSTALL NEW SADDLE FLASHING WITH HIGH
TEMP ICE AND WATER SHEILD BELOW AT
PREVIOUS AREAS OF LEAK INDICAITON
D-3 REMOVE ALL (E) ITEMS IN WELL. INFILL TO MATCH
BARREL VAULT AND INSTALL NEW ROOFING TO
MATCH MATERIAL AND COLOR OF EXISTING
E-7 (E) FAN RESET TO SAME LOCATION COORDINATE
WITH MECH AND ELECT.
E-8 (E) EIFS SYSTEM SHOWN AS DASHED
SCALE: 1/4" = 1'-0"A1.3
2A ENLARGED PLAN @ FRAMING WALL
NO SCALEA1.3
2B ISOMETRIC VIEW
A-8
E-7
A-4
A-4
A-7
0 1 2 3 4 5 10
SCALE: 1/4" = 1'=0"
SCALE: 1/4" = 1'-0"A1.3
3A ROOF SYSTEM DETAIL
SCALE: 1/8" = 1'-0"A1.3
4A ROOF SYSTEM DETAIL
SCALE: 1" = 1'-0"A1.3
5A SECTION AT NEW ROOF SYSTEM
2 03/25/26
NOTE: INSPECT AND REPAIR COPING
AT DAMAGE AREAS
(E) METAL COPING
(E) CMU WALL
REPLACE REGLET & COUNTER-FLASHING
SET INTO CMU INSTALL NEW IN HIGHER
LOCATION.
(E) METAL DECK
RIGID INSULATION
COVER BOARD
EPDM MEMBRANE
T.O. PARAPET
(E) INVERTED CMU
M
IN
R-2
TERM BAR
'-6
M
A X
CONTINUOUS POLYURETHANE SEALANT
(E) METAL DECK
(E) EXTERIOR INSULATION
FINISH SYSTEM (EIFS)
(E) AIR BARRIER
T.O. PARAPET
COVER BOARD
EPDM MEMBRANE
(E) CAP FLASHING
(E) SLOPE
(E) METAL STUDS
RIGID INSULATION
REMOVE ALL EIFS
AREA AT PARAPET
ROOF AREA, SHOWN
AS DASHED
COUNTER-FLASHING
CONT. SEALANT
ADD NEW LAYER OF
EXTERIOR SHEATHING
AT PARAPET/ROOF SIDE,
SHOWN AS GRAY
R-2
REMOVE AND
RELOCATE
ELECTRICAL OUTLET.
USE BUTYL SEALANT
AT ANY FASTENERS
M
IN
VAPOR BARRIER
SHOWN AS DASHED
M
IN
.NEW 5/8" GLASS-MAT
GYPSUM SHEATHING
TUCK HIGH TEMP ICE AND WATER
SHEILD, LAP OVER EPDM ON BACKSIDE
OF PARAPET
NOTE:
1. DO NOT CROSS SEAMS WITH WALKWAY PADS;
MAINTAIN 3" MIN OFF EACH SEAM.
2. HEAT-WELD EDGE OF WALKWAY ROLLS
CONTINUOUSLY.
3. REQUIRED AT ALL ROOF ACCESS POINTS.
HEAT-WELDED AREA 2"
CONTINUOUSLY AROUND PERIMETER
ROUND CORNERSWALKWAY PAD
HEAT-WELDED LAP
EPDM MEMBRANE
RIGID INSULATION
(E) ROOF DECK
6"
48"
48"
PIPE, PAINT AS SPECIFIED
LAP SEALANT
SS CLAMPING RING
EXPANDABLE FOAM INSULATION - CONT
MOLDED PIPE BOOT FLASHING
EPDM MEMBRANE
(E) BACKER ROD AND SEALANT, TYP
(E) METAL DECK
8" M
IN
CONT. PENETRATION MEMBRANE
TO VAPOR RETARDER
COVER BOARD
STAINLESS STEEL WORM GEAR CLAMP
R-2
(E) METAL DECK
ROOF DRAIN
W/ CAST IRON
DOME
(E) OVERFLOW
(E) DRAIN LEADER
OVERFLOW WATER DAM
OVERFLOW ROOF DRAIN
W/ CAST IRON DOME
2' - 0" TYP
COVER BOARD
EPDM
MEMBRANE
R-2
NOTE: INSTALLATION AT
SAME ELEVATION
PREFAB EQUIP SUPPORT ATTACH
TO ROOF DECK W/ 1/4" ⌀ SCREWS
ROOF TOP EQUIP, SEE MECH, TYP
EQUIP SUPPORT RUNNER
FURNISHED W/ EQUIP
EXTEND MEMBRANE FLASHING
TO COVER WOOD BLOCKING
PREFINISHED COUNTER FLASHING
1/
2" M
IN
(E) METAL DECK
CONT VAPOR RETARDER, RETURN
VERTICALLY AT ROOF CURB TO
HEIGHT OF ROOF INSULATION
R-2
COVER BOARD
RIGID INSULATION
CONT. SEALANT
FASTENER
22 GA x 12" ANCHOR
PLATE - 5'-0" O.C.
24 GA COPING
(E) WALL
12" WIDE SPLICE PLATE
AT COPING JOINT
OVER EPDM MEMBRANE
12"
NOTE:
• INSPECT ALL COPING
CONDITIONS FOR ANY
DAMAGE AND REPAIR AS
NEEDED
• COMPLIANCE WITH SMACNA
2'-0" 2'-0"
RIVETED LAP SEAM W/
SILICONE SEALANT CONT.
BETWEEN LAPPED PIECES
SCREW WITH WATERTIGHT
WASHER THROUGH COVER
PLATE ONLY
(E) WALL
(1) LAYERS EPDM
MEMBRANE
ROOFING SYSTEM AND
WRAP OVER TOP OF
PARAPET WALL UNDER
COPING, TYP.
GALVANIZED METAL COVER
PLATE OVER VINYL SHEET
FLASHING AND BELOW
COPING
SEALANT BELOW
COVER PLATE AT
EDGES
ROOF SIDE
SLOPE
SLOPE
CONTINUOUS
GALVANIZED CLEAT WITH
FASTENERS AT 24" O.C.NOTE:
• INSPECT ALL COPING CONDITIONS FOR ANY
DAMAGE AND REPAIR AS NEEDED
• COMPLIANCE WITH SMACNA
PIPE, PAINT AS SPECIFIED
LAP SEALANT
SS CLAMPING RING
EXPANDABLE FOAM INSULATION -
CONT
ROOF FLASHING
EPDM MEMBRANE
(E) BACKER ROD AND
SEALANT, TYP
(E) METAL DECK
1'
M
IN
CONT PENETRATION
MEMBRANE TO VAPOR
RETARDER
COVER BOARD
R-2
HEATED ROOF VENT/STACK
SEALANT - HEAT RATED
SS CLAMPING RING
EXPANDABLE FOAM INSULATION - CONT
METAL RAIN COLLAR
EPDM MEMBRANE
(E) BACKER ROD AND SEALANT, TYP
(E) METAL DECK
8" M
IN
CONT PENETRATION MEMBRANE
TO VAPOR RETARDER
COVER BOARD
STAINLESS STEEL WORM GEAR CLAMP
M
IN6
R-2
RIGID INSULATION
CONT. SEALANT
EPDM MEMBRANE
COVER BOARD
RIGID INSULATION
TERMINATION BAR
FASTENED 8" O.C.
COUNTER-FLASHING
SURFACE APPLIED REGLET
DEMO EIFS FROM INSIDE FACE OF PARAPET,
INSTALL NEW 1/2" DENSGLAS OVER
EXISTING SHEATHING. 3FT UP FROM ROOF
OR TO ALIGN WITH NEARBY PARAPET
R-2
EPDM MEMBRANE
HOT AIR WELD
SEALANT
M
IN
NEW EPDM UP
BACK SIDE OF
PARAPET
NEW GLASS-
MAT GYPSUM
SHEATHING
SHOWN AS
GRAY
(E) SHEATHING
TO REMAIN
(E) STEEL JOIST AND ROOF DECK
RIGID INSULATION
R-2
COVER BOARD
WOOD CURB
PRE-FABRICATED CURB BY MECH.
UNIT MANUF COORDINATE
W/ROOFING SUB
WEATHER PROOF SEALING STRIP
MECH EQUIPMENT W/INTEGRAL OR
SEPARATE FLASHING/DRIP EDGE
ROOF FLASHING
SAWCUT EXISTING CMU
EPDM MEMBRANE
(E) METAL DECK
COVER BOARD
EXISTING CMU WALL
RIGID INSULATION
TERMINATION BAR FASTENED
PER MFG MIN STANDARDS
FLASHING
NEW REGLET WITH COUNTER
FLASHING SET IN SEALANT
REMOVE AND RELOCATE
ELECTRICAL OUTLET AS REQUIRED
R-2
HOT AIR WELD
M
IN
36' - 2 1/4"36' - 4 1/4"
27' - 1"
R-1
R-2
R-1
METAL PANEL
1D
A5.1
6 3/4" / 1'-0"
(E) CMU WALL
BEYOND
36' - 4 1/4"
R-1
R-1
R-2
METAL PANEL
1D
A5.1
6 3/4" / 1'-0
(E) CMU WALL
BEYOND
36' - 4 1/4"
27' - 0"
R-1
R-2
A121DOOR AND
FRAME SEE
SCHEDULE
METAL
PANEL
2B
A5.1
5A
A5.1
5C
A5.1
/4
1B
A5.1
SLOPED
ROOF
EPDM MEMBRANE AT
WALL, THIS SIDE
R-2
R-1
NOTE:
NO METAL PANEL
ON THIS SIDE
OPENING
JAMB STUDS
BOTTOM TRACK
ATTACH TRACK TO SLAB W/ (2)
0.145" DIA. RAMSET SHOT PINS
W/ 1 1/2" EMBED AT INTERIOR
LOCATIONS (RAMSET ICC#
EST-1799).
SEE STRUCTURAL DETAILS FOR
ATTACHMENT @ EXTERIOR
APPLICATIONS.
#10 S.M.S. @ EA. FLANGE
3" MAX.
1-1/2" MAX.
D
IS
T A
N C
E
M
IN
E
D G
E
CONCRETE SLAB
ATTACH BOTH ENDS OF
BOTTOM TRACK TO SHORT
SECTION OF STUD w/ 3-#10
S.M.S. ON BOTH SIDES
12" LONG STUD
CENTERED ON SPLICE
BOTTOM TRACK
ALTERNATE:
0.145" DIA. RAMSET SHOT PINS W/ 1 1/2" EMBED.
EACH SIDE OF SPLICE & OMIT CAP
TRACK TYP.
METAL STUD, TYP.
#10 S.M.S @ 24", STUD TO STUD.
TYP.
TRACK TYP.
METAL STUD, TYP.
#10 S.M.S @ 24", STUD TO STUD.
TYP.
TRACK TYP.
METAL STUD, TYP.
#10 S.M.S @ 24", STUD TO STUD.
TYP.
DECK PERPENDICULAR DECK PARALLEL
INTERIOR PARTITION ONLY
4"x16 GA. @ 2'-0" O.C.
#10 S.M.S. w/STAND-OFF
WASHERS OR WAFERHEADS
@ 2'-0" O.C.
0.145 DIA. PDA W/
1" EMBED @ 2'-0"
O.C. TYP.
#10 S.M.S. w/ STAND-OFF
WASHER OR WAFERHEAD, EA.
FLANGE. INSTALL
FASTENERS AT CENTER OF 1
1/4" SLOT
DEEP LEG
SLOTTED TOP
TRACK w/ SLOTS
@ 1" O.C. 20 GA.
MIN.
FASTENERS
WALL STUD
TYP.
JAMB STUDS
PER PLAN
/2
G
A P
MINIMUM 20 GAUGE SHEET METAL
STRAPPING MINIMUM 8" HIGH
#8 SELF TAPPING PAN PHILLIPS
SCREW. MINIMUM THREE PER
STUD
STEEL STUDS AS SCHEDULED
2 x WOOD BLOCKING
MINIMUM OF 8" HIGH..
NOTE: DIMENSIONAL WOOD AND PLYWOOD BLOCKING MUST BE FIRE-RETARDANT IN CONSTRUCTION TYPES I AND II AND CAN ONLY BE PERMITTED AT NONBEARING PARTITION WALLS WITH A FIRE RATING OF 2 HOURS OR LESS AND AT NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS REQUIRED.
REFER TO CODE SHEETS FOR CONSTRUCTION TYPE.
#8 X 1" SELF TAPPING PAN
HEAD SCREW. MINIMUM
THREE PER STUD
KERF BLOCKING AT STUD RETURN
20 GAUGE GALVANIZED STEEL
ANGLE FULL HEIGHT OF
BLOCKING. ANCHOR TO STUD
WITH MINIMUM THREE #7 FRAMING
SCREWS. ANCHOR BLOCKING TO
ANGLE WITH MINIMUM OF THREE #
8 X 1" SELF TAPPING SCREWS
STEEL STUDS AS
SCHEDULED
STEEL STUDS AS SCHEDULED
KERF BLOCKING
AT STUD
RETURN
20 GAUGE GALVANIZED STEEL
ANGLE FULL HEIGHT OF
BLOCKING. ANCHOR TO STUD
WITH MINIMUM THREE #7 FRAMING
SCREWS. ANCHOR BLOCKING TO
ANGLE WITH MINIMUM OF THREE #
8 X 5/8" SELF TAPPING SCREWS
3/4" FIRE-TREATED
PLYWOOD BLOCKING
MINIMUM OF 8" HIGH.
USE WOOD BLOCKING AT DOOR STOPS, HANDRAILS AND/OR OTHER ITEMS WITH A WEIGHT OF 20 LBS
OR MORE OR IF ITEM IS CANTILEVERED FROM WALL.
USE SHEET METAL STRAPPING FOR BATHROOM ACCESSORIES, MARKER BOARDS, TACK BOARDS,
AND/OR OTHER THAN GRAB BARS WHERE ITEMS WEIGH LESS THAN 20 LBS
SHEET METAL BACKING
ANCHORS, SEE ADJACENT
PLAN VIEW FOR TYPE AND
NUMBER
STEEL STUDS AS
SCHEDULED
ANCHOR WOOD BLOCKING TO
STEEL STUDS. SEE ADJACENT
PLAN VIEW FOR TYPE AND
NUMBER
STEEL STUDS AS SCHEDULED
DIMENSIONAL WOOD BLOCKING
STEEL ANGLE, ANCHOR TO
STUDS AS NOTED IN
ADJACENT PLAN VIEW
WALL STUD PER WALL TYPES
3/4" MAX.
WHERE BRACING TERMINATES AT
BUILT-UP JAMB, EXTEND CRC INTO
PUNCH-OUT.
2"x2"x16 GA. CLIP ANGLE AT EACH
END OF WALL. ANGLE TO BE 1/2"
LESS THAN STUD WIDTH w/ 4-#10
S.M.S. TYP. CONTRACTOR OPTION
TO USE FRICTION FIT SPACER
BARS EQUAL TO DIETRICH
"SPAZZER" BAR.
LATERAL BRACING: CONT. 1
1/2"x16 GA. COLD ROLLED
CHANNEL (CRC). CONTRACTOR
OPTION TO USE FRICTION FIT
SPACER BARS EQUAL TO
DIETRICH "SPAZZER" BAR.
LATERAL BRACING SPLICE: 12" LONG
CRC INVERTED OVER CENTER OF
SPLICE w/ (3) #10
S.M.S. EA. SIDE OF SPLICE
NOTES:
1. HEADER SHALL BE UNPUNCHED AND OF THE SIZE AND
GAUGE LISTED.
METAL STUD FRAMING
SEE PLAN FOR WALL TYPE
METAL STUD RUNNER
(SAME GAUGE AS HEADER)
METAL STUD BOX LINTEL (HEADER)
SEE SCHED
FASTENERS AT 16" OC, TYP
INTERIOR BOX LINTEL (HEADER) SCHEDULE
OPENING WIDTH
AT SECURITY OPENINGS
STUD REQUIREMENT
TWO 10" X 12 GA
A
SPAN UP
TO 10'-0"
B
SPAN >
THAN 10'-0" TO 15'-0"
(E) METAL DECK
RIGID INSULATION
COVER BOARD
EPDM MEMBRANE
(E) EIFS TO REMAIN
(E) WALL TO REMAIN
(E) ROOF SYSTEM
INTERIOR SIDE
DEMO EIFS FROM INSIDE FACE
OF PARAPET, INSTALL NEW 1/2"
DENSGLAS OVER EXISTING
SHEATHING. 3FT UP FROM
ROOF OR TO ALIGN WITH
NEARBY PARAPET
A9.1
1F
OPP.
M
IN
D
L R
G ro u p
REVISIONS
A B C D E F
/2
/2
:3
:5
A
M
A u to d e s k D o c s
/3
-2
-0
A
D O
T M
V D
R e ro o f N
/3
-2
-0
A
D O
T M
V D
R e ro o f_ A
R
.r v t
30-25134-00
09/03/2025
A D
O T
B U
IL
D
IN
G
R E
-R O
O F
P R
O J E
C T
CONSTRUCTION
DOCUMENTS
ELEVATIONS &
ROOF-FRAMING
DETAILS
A9.1
S
W o o d la n d s V ill a g e B lv d
F la g s ta ff A
Z
SCALE: 1" = 1'-0"A9.1
1A PARAPET DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
2A PARAPET DETAIL AT EXISTING EIFS
SCALE: 1" = 1'-0"A9.1
1B WALKING PAD DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
2B FLASHING BOOT DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
1C ROOF DRAIN DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
2C ROOF TOP EQUIPMENT SUPPORT
SCALE: 1 1/2" = 1'-0"A9.1
1D TYPICAL COPING SPLICE DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
2D TYPICAL CORNER COPING DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
1E CONT. PIPE FLASHING
SCALE: 1 1/2" = 1'-0"A9.1
2E HEATED VENT PIPE FLASHING
SCALE: 3" = 1'-0"A9.1
1F REGLECT/COUNTERFLASHING @ EXISTING EIFS
SCALE: 1 1/2" = 1'-0"A9.1
3F ROOF CURB DETAIL
SCALE: 1 1/2" = 1'-0"A9.1
2F REGLET/COUNTERFLASHING @ EXISTING CMU
SCALE: 1 1/2" = 1'-0"A9.1
5D TYPICAL BLOCKING IN FRAME WALLS
SCALE: 3/8" = 1'-0"A9.1
3E TYPICAL LATERAL BRACING
SCALE: 1 1/2" = 1'-0"A9.1
3B TYPICAL MTL STUD HEADER
SCALE: 3/8" = 1'-0"A9.1
4C BOTTOM TRACK SPLICE
SCALE: 3/8" = 1'-0"A9.1
3C BOTTOM TRACK AT JAMB
SCALE: 3/8" = 1'-0"A9.1
3D TOP TRACK DETAIL (OPTIONAL)
SCALE: 1" = 1'-0"A9.1
5C CORNER INTERSECTIONS
SCALE: 1/4" = 1'-0"A9.1
3A EXTERIOR ELEVATION
SCALE: 1/4" = 1'-0"A9.1
4A EXTERIOR ELEVATION
SCALE: 1/4" = 1'-0"A9.1
5A EXTERIOR ELEVATION
SCALE: 1/4" = 1'-0"A9.1
5B EXTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A9.1
4B DETAIL AT EXISTING WALL
2 03/25/26
Mezz Level M1
10' - 0"
Level 03
28' - 0"
(R) RTU-29
2" G
(E) 2" G
M8.1
(E) 26"x62" SA
G-4
44" x 38"
6000 CFM
M8.1
26" TALL ROOF CURB
PROVIDE ECCENTRIC
TRANSITIONS AS
SHOWN
20"x28" RA
20"x28" SA
H8
H11
H12
D-19
14" x 10"
200 CFM
Mezz Level M1
10' - 0"
Level 03
28' - 0"
(E) 26"x62" SA
(R) RTU-29
(E) 2" G
(D) 2" G
(D) 20"x68" RA
(D) 3" SD
DH6
DH9
DH9
(D) 26"x62" SA
(D) 3/4" CD
Mezz Level M1
10' - 0"
Level 03
28' - 0"
M8.1
(R) RTU-29
26" TALL ROOF CURB
EXISTING DECK AND
STRUCTURE ARE SLOPED
PROVIDE ECCENTRIC
TRANSITIONS AS
SHOWN
28"x20" SA28"x20" RA
Mezz Level M1
10' - 0"
Level 03
28' - 0"
M8.1
M8.1
(R) RTU-29
G-4
44" x 38"
6000 CFM
26" TALL ROOF CURB
20"x28" RA
Mezz Level M1
10' - 0"
Level 03
28' - 0"
M8.1
(R) RTU-29
26" TALL ROOF CURB
EXISTING DECK AND
STRUCTURE ARE SLOPED
PROVIDE ECCENTRIC
TRANSITIONS AS
SHOWN
28"x20" RA
TO EQUIPMENT
UNION
GAS SHUT OFF VALVE
FROM GAS MAIN
FLEXIBLE CONNECTION
D
IR
T L
E G
H"
X"
INSTALL ADDITIONAL VENT AT
INTERVALS OF 10' WHEN PIPING
DOWNSTREAM OF TRAP EXCEEDS
15'
CLEAN OUT
PITCH DOWN TOWARD DRAIN
OPEN END
CLEAN OUT
DRAIN LINE SHALL BE AT LEAST
THE SAME SIZE AS THE NIPPLE ON
THE DRAIN PAN
EQUIP DRAIN PAN, MUST BE
MOUNTED
HIGH ENOUGH TO ENSURE H AND
X
DIMENSIONS
NOTES:
1. ON DRAW-THRU UNITS, THE (X) DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING-
UNITS SUCTION PRESSURE AT OPERATING CONDITIONS, BUT IN NO CASE LESS THAN 2-INCHES.
2. ON BLOW-THRU UNITS, THE (X) DIMENSION (IN INCHES) CAN BE AS SMALL AS 2 INCHES, BUT THE
(Y) DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING UNITS TOTAL STATIC
PRESSURE BUT IN NO CASE LESS THAN 2 INCHES.
X=DISTANCE BETWEEN THE DRAIN PAN OUTLET AND THE TRAP
Y=TRAP DEPTH
D
L R
G ro u p
REVISIONS
A B C D E F
/2
/2
:3
:2
A
M
A u to d e s k D o c s
/3
-2
-0
A
D O
T M
V D
R e ro o f N
/3
-2
-0
A
D O
T M
V D
R e ro o f_ M
P
.r v t
30-25134-00
09/03/2025
A D
O T
M V
F R
E R
O O
F
IN
G P
R O
J E
C T
CONSTRUCTION
DOCUMENTS
PLUMBING &
MECHANICAL
SCHEDULES,
DETAILS &
SECTIONS
M8.1
S
W O
O D
L A
N D
S V
IL
L A
G E
B L V
D F
L A
G S
T A
F F
A
Z
A R
IZ
O
N A
D E
P A
R T
M E
N T
O F
T R
A N
S P
O R
T A
T
IO
N
NOTES:
1. PERFORM AIRFLOW TEST OF EXISTING ROOFTOP UNIT TO DETERMINE SUPPLY, RETURN AND OUTDOOR AIRFLOW VALUES PRIOR TO REMOVAL. BALANCE EXISTING ROOFTOP UNIT TO TESTED AIRFLOWS. SUPPLY AND OUTDOOR AIRFLOW VALUES SHOWN WITHIN SCHEDULE
ARE FOR REFERENCE ONLY.
PACKAGED ROOFTOP UNIT SCHEDULE
ID
SERVES SUPPLY FAN DATA
WEIGHT
(LBS)
BASIS OF DESIGN
NOTESOA
AIRFLOW
(CFM)
AIRFLOW
(CFM)
ESP
(IN WG)
MANUFACTURER MODEL
(E) RTU-1 300 1,600 0.7 630 LENNOX LGH048H4ES4G 1
(E) RTU-2 300 1,200 0.7 610 LENNOX LGH036H4ES4G 1
(E) RTU-3 300 1,600 0.7 630 LENNOX LGH048H4ES4G 1
(E) RTU-4 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-5 300 3,000 0.7 1,345 LENNOX LGH094U4MS1G 1
(E) RTU-6 300 4,000 0.7 1,215 LENNOX LGH122U4MM1G 1
(E) RTU-7 300 1,200 0.7 610 LENNOX LGH036H4ES4G 1
(E) RTU-8 300 1,200 0.7 610 LENNOX LGH036H4ES4G 1
(E) RTU-9 300 1,600 0.7 670 LENNOX LGH048H4ES4G 1
(E) RTU-10 750 3,000 0.7 2,000 TRANE YSK180A4S0H02CB0C101 1
(E) RTU-11 750 3,000 0.7 1,345 LENNOX LGH094U4MS1G 1
(E) RTU-12 300 4,000 0.7 2,000 TRANE YSK180A4S0H02CB0C101 1
(E) RTU-13 600 2,400 0.7 1,020 TRANE YHK120A4S0H0AC0B0C101 1
(E) RTU-14 300 1,600 0.7 630 LENNOX LGH048H4ES4G 1
(E) RTU-15 300 2,400 0.7 805 LENNOX LGH074H4TU1G 1
(E) RTU-16 300 1,200 0.7 610 LENNOX LGH036H4ES4G 1
(E) RTU-17 300 1,600 0.7 630 LENNOX LGH048H4ES4G 1
(E) RTU-18 300 1,200 0.7 610 LENNOX LGH036H4ES4G 1
(E) RTU-19 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-20 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-21 300 1,600 0.7 630 LENNOX LGH048H4ES4G 1
(E) RTU-22 300 3,000 0.7 1,345 LENNOX LGH094U4MS1G 1
(E) RTU-23 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-24 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-25 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-26 300 2,000 0.7 705 LENNOX LGH060H4EU4G 1
(E) RTU-27 300 2,000 0.7 1,215 LENNOX LGH122U4MM1G 1
(E) RTU-28 300 8,000 0.7 2,525 LENNOX LGH240U4MM1G 1
(R) RTU-29 300 6,000 0.7 1,215 LENNOX LGH122U4MM1G 1
NOTES:
1. BALANCE EXHAUST FAN TO AIRFLOW SHOWN IN SCHEDULE.
2. PERFORM AIRFLOW TEST OF EXISTING FAN PRIOR TO REMOVAL OF FAN AND PROVIDE RESULTS TO
ENGINEER. BALANCE EXHAUST FAN TO AIRFLOWS DETERMINED AS PART OF TEST.
FAN SCHEDULE
ID
FAN DATA
WEIGHT
(LBS)
BASIS OF DESIGN
NOTESAIRFLOW
(CFM)
ESP
(IN WG)
MANUFACTURER MODEL
(E) EF-1 400 0.13 60 GREENHECK G-081 1
(E) EF-2 450 0.38 61 GREENHECK G-101 1
(E) EF-3 500 0.13 60 GREENHECK G-081 1
(E) EF-4 300 0.25 61 GREENHECK G-080-E 1
(E) EF-5 300 0.25 61 GREENHECK G-080-E 1
(E) EF-6 1,200 2 185 GREENHECK G-080-E 1
(E) EF-7 1,200 2 185 GREENHECK G-080-E 1
(E) EF-8 800 2 105 GREENHECK G-080-E 1
(E) EF-9 1,000 2 105 GREENHECK G-080-E 1
(E) EF-10 0 2 185 GREENHECK G-080-E 2
(E) EF-11 0 2 185 GREENHECK G-080-E 2
SCALE: 1/4" = 1'-0"M8.1
RTU-29 NEW WORK SECTION2
SCALE: 1/4" = 1'-0"M8.1
RTU-29 DEMOLITION SECTION1
NOTES:
1. VERIFY SIZE OF EXISTING STORM DRAINS AND MATCH EXISTING SIZE FOR NEW STORM DRAINS.
STORM DRAIN SCHEDULE
DESCRIPTION QTY
MATERIAL DESCRIPTION
PIPE SIZE SPECIFICATION
BASIS OF DESIGN
NOTES
BODY STRAINER MANUFACTURER MODEL
STORM DRAIN 6 LACQUERED CAST IRON POLYETHYLENE 6”
DEEP SUMP ROOF DRAIN WITH 15” DIAMETER ANCHOR FLANGE, 2” HIGH CAST IRON EXTERNAL COMBINED
WATER DAM AND WATERPROOFING MEMBRANE CLAMP RING, AND STANDARD SELF-LOCKING DOME
STRAINER WITH A FREE AREA OF 125 SQUARE INCHES.
MIFAB R1200-R 1
STORM DRAIN 1 LACQUERED CAST IRON POLYETHYLENE 8”
DEEP SUMP ROOF DRAIN WITH 15” DIAMETER ANCHOR FLANGE, 2” HIGH CAST IRON EXTERNAL COMBINED
WATER DAM AND WATERPROOFING MEMBRANE CLAMP RING, AND STANDARD SELF-LOCKING DOME
STRAINER WITH A FREE AREA OF 125 SQUARE INCHES.
MIFAB R1200-R 1
STORM DRAIN 6 LACQUERED CAST IRON POLYETHYLENE 6”
DEEP SUMP ROOF DRAIN WITH 15” DIAMETER ANCHOR FLANGE, LARGE CAST IRON WATERPROOFING MEMBRANE CLAMP RING WITH INTEGRAL GRAVEL STOP, AND STANDARD SELF-LOCKING DOME STRAINER
WITH A FREE AREA OF 125 SQUARE INCHES.
MIFAB R1200 1
STORM DRAIN 1 LACQUERED CAST IRON POLYETHYLENE 8”
DEEP SUMP ROOF DRAIN WITH 15” DIAMETER ANCHOR FLANGE, LARGE CAST IRON WATERPROOFING MEMBRANE CLAMP RING WITH INTEGRAL GRAVEL STOP, AND STANDARD SELF-LOCKING DOME STRAINER
WITH A FREE AREA OF 125 SQUARE INCHES.
MIFAB R1200 1
NOTES:
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
ID DESCRIPTION
MAX
STATIC
PRESSURE
DROP
(IN WG)
MAX
NC
PRESSURE
DROP
SHOWN
DAMPER
FRAME
TYPE
PANEL
SIZE
FACE
(W" x H")
MATERIAL FINISH
BASIS OF DESIGN
NOTESINCLUDED
(Y / N)
DESCRIPTION MANUFACTURER MODEL
D-19 LOUVERED DOUBLE DEFLECTION GRILLE 0.1 30 N --- SURFACE --- SEE PLANS STEEL WHITE ENAMEL TITUS 300RL
G-4 LOUVERED GRILLE 0.1 30 N --- SURFACE --- SEE PLANS STEEL CUSTOM COLOR, BY ARCHITECT TITUS 350RL
SCALE: 1/4" = 1'-0"M8.1
RTU-29 SUPPLY SECTION3
SCALE: 1/4" = 1'-0"M8.1
RTU-29 RETURN SECTION4
SCALE: 1/4" = 1'-0"M8.1
RTU-29 RETURN SECTION 25
NOTES:
1. PROVIDE WITH UNIT MOUNTED DISCONNECT.
ELECTRIC UNIT HEATER SCHEDULE
ID TYPE ARRANGEMENT
FAN DATA HEATING COIL DATA ELECTRICAL DATA
WEIGHT
(LBS)
BASIS OF DESIGN
NOTESAIRF LOW (CFM) AIR TEMP DB (°F) HEATING ELEMENT MOCP
(A)
VOLT
(V)
PH MANUFACTURER MODEL
DESIGN MIN ENT LVG QTY KW SCR
EUH-1 ELECTRIC VERTICAL 625 625 70 110 1 7.5 No 30 208 3 70 REZNOR EGEB 1
SHEET NOTES
DH6 REMOVE EXISTING SUPPLY AND RETURN AIR DUCTWORK
AS REQUIRED TO FACILITATE INSTALLATION OF
RELOCATED ROOFTOP UNIT AND ASSOCIATED NEW
DUCTWORK.
DH9 REMOVE EXISTING PRIMARY AND SECONDARY ROOF
DRAINS AND ASSOCIATED PIPING TO ALLOW FOR THE
MECHANICAL WELL SPACE TO BE FILLED IN AS PART OF
NEW ROOF. PATCH AND REPAIR EXISTING, EXTERIOR
DECK AND WALL TO REMAIN TO MATCH ADJACENT.
H8 INSTALL PREVIOUSLY REMOVED ROOFTOP UNIT IN NEW
LOCATION AS INDICATED. PROVIDE WITH 26" TALL ROOF
CURB AND EXTEND NEW DUCTWORK FROM UNIT AND
CONNECT TO EXISTING DUCTWORK AS INDICATED.
PROVIDE NEW NATURAL GAS PIPING AND CONNECT TO
RELOCATED UNIT AS INDICATED. PROVIDE NEW
CONDENSATE PIPE PORTAL AT ROOF PENETRATION AND
PROVIDE NEW CONDENSATE PIPING AS NECESSARY TO
CONNECT TO ROOFTOP UNIT. TEST AND BALANCE
ROOFTOP UNIT TO AIRFLOWS SHOWN ON SCHEDULE ON
M8.1.
H11 CONNECT 62"X26" SUPPLY AIR DUCT TO EXISTING 62"X26"
SUPPLY AIR DUCT AS SHOWN. CAP OPEN PORTION OF
DUCT CREATED DURING DEMOLITION TO CREATE SUPPLY
AIR PLENUM AND PROVIDE SUPPLY AIR TO EXISTING
DUCTWORK.
H12 EXPOSED DUCTWORK IN THIS AREA TO BE PAINTGRIP
FINISH AND PAINTED TO MATCH EXISTING.
NO SCALEM8.1
6 GAS CONNECTION DETAIL
SCALE: 3/8" = 1'-0"M8.1
CONDENSATE DRAIN P-TRAP7
2 03/25/26
DH1 DH1 DH1 DH1
DH1
DH1 DH1 DH1 DH1 DH1 DH1 DH1 DH1
DH1
DH1
DH1
DH1
DH1
DH1
DH1 DH1 DH1
DH1
DH1
DH1
DH1
DH1
DH1
DH2DH2
DH2
DH2
DH2
DH2
DH2
DH2
DH2
DH2
DH3
DH3
DH3
DH2
(E) CRAC-1
(E) RTU-28
(E) RTU-27
(E) RTU-26
(E) RTU-25
(E) RTU-24
(E) CRAC-2
(E) RTU-22
(E) RTU-21(E) RTU-20
(E) RTU-19
(E) ECU-1
(E) RTU-18
(E) RTU-17
(E) RTU-16
(E) RTU-15
(E) RTU-14
(E) RTU-13
(E) RTU-12(E) RTU-11(E) RTU-10
(E) RTU-9(E) RTU-8(E) RTU-7
(E) RTU-6
(E) RTU-5
(E) RTU-4(E) RTU-3(E) RTU-2(E) RTU-1
(E) EF-9
(E) EF-8
(E) EF-1
(E) EF-6
(E) EF-5
(E) EF-7
(E) EF-4
(E) EF-3
(E) EF-2
(E) RTU-23
(E) 2" G
(E) 2" G
(E) 2" G
(E) 1 1/2" G
(E) 1 1/2" G
(E) 1 1/4" G
(E) 1 1/4" G
(E) 2" G
(E) 1 1/2" G
(E) 1 1/4" G(E) 1" G
(E) 1 1/4" G
(E) 4" G
(E) 3" G
(E) 4" G
(E) 6" G
(E) 1 1/4" G
(E) 2" G
(E) 1 1/4" G
(E) 6" G (E) 6" G (E) 4" G (E) 1 1/4" G
DH5
DH5 DH5 DH5
DH5
DH5
DH5
DH5
M8.1
DH7 DH7
(R) RTU-29 DH4
(E) EF-10
(E) EF-11
DH8
DH8
DH9
DH9
DH7
DH7
DH7
DH7
DH7
(D) 3/4" CD
(D) 3/4" CD DN
DH10
(D) 2" G DN
D
L R
G ro u p
REVISIONS
A B C D E F
/2
/2
:3
:1
A
M
A u to d e s k D o c s
/3
-2
-0
A
D O
T M
V D
R e ro o f N
/3
-2
-0
A
D O
T M
V D
R e ro o f_ M
P
.r v t
30-25134-00
09/03/2025
A D
O T
M V
F R
E R
O O
F
IN
G P
R O
J E
C T
CONSTRUCTION
DOCUMENTS
LEVEL 03 - HVAC
DEMOLITION
PLAN
MD1.3
S
W O
O D
L A
N D
S V
IL
L A
G E
B L V
D F
L A
G S
T A
F F
A
Z
A R
IZ
O
N A
D E
P A
R T
M E
N T
O F
T R
A N
S P
O R
T A
T
IO
N
SHEET NOTES
DH1 IDENTIFY, LABEL AND PERFORM AIRFLOW TEST TO
DETERMINE SUPPLY, RETURN AND OUTDOOR AIRFLOW
VALUES OF EXISTING ROOFTOP UNITS PRIOR TO
REMOVAL. TEMPORARILY REMOVE EXISTING ROOFTOP
UNIT TO ALLOW FOR THE EXISTING ROOFING ASSEMBLY
TO BE REMOVED AND REINSTALLED. REMOVE EXISTING
CURB AND PREPARE FOR INSTALLATION OF NEW CURB IN
THE SAME LOCATION. TEMPORARILY CAP AND PROTECT
DUCT PENETRATIONS. TEMPORARILY DISCONNECT AND
CAP EXISTING GAS PIPING AND PREPARE FOR
RECONNECTION TO ROOFTOP UNIT AS PART OF NEW
WORK. REMOVE EXISTING CONDENSATE PIPE PORTAL
AND CONDENSATE PIPING AS NECESSARY TO FACILITATE
INSTALLATION OF NEW ROOF. PREPARE EXISTING
CONDENSATE PIPING TO REMAIN FOR CONNECTION TO
NEW CONDENSATE PIPING AS PART OF NEW WORK.
DH2 TEMPORARILY REMOVE EXISTING EXHAUST FAN TO
ALLOW FOR THE EXISTING ROOFING ASSEMBLY TO BE
REMOVED AND REINSTALLED. REMOVE EXISTING CURB
AND PREPARE FOR INSTALLATION OF NEW CURB IN THE
SAME LOCATION. TEMPORARILY CAP AND PROTECT DUCT
PENETRATIONS.
DH3 TEMPORARILY REMOVE EXISTING CONDENSING UNIT TO
ALLOW FOR THE EXISTING ROOFING ASSEMBLY TO BE
REMOVED AND REINSTALLED. REMOVE EXISTING RAILS
AND PREPARE FOR INSTALLATION OF NEW RAILS IN THE
SAME LOCATION. REMOVE EXISTING REFRIGERANT PIPE
PORTAL AND PREPARE FOR INSTALLATION OF NEW
REFRIGERANT PIPE PORTAL IN THE SAME LOCATION.
TEMPORARILY STORE THE EXISTING REFRIGERANT
PIPING BELOW THE ROOF AND CAP AND PROTECT THE
EXISTING ROOF PENETRATIONS.
DH4 TEMPORARILY REMOVE EXISTING ROOFTOP UNIT AND
CURB TO ALLOW FOR THE MECHANICAL WELL SPACE TO
BE FILLED IN AS PART OF NEW ROOF. PREPARE EXISTING
DUCTWORK TO REMAIN FOR CONNECTION TO NEW
DUCTWORK AS PART OF NEW WORK. REMOVE EXISTING
NATURAL GAS PIPING AS INDICATED AND PREPARE
EXISTING NATURAL GAS PIPING TO REMAIN FOR
CONNECTION TO RELOCATED ROOFTOP UNIT. REMOVE
EXISTING CONDENSATE PIPE PORTAL AND ASSOCIATED
CONDENSATE PIPING.
DH5 TEMPORARILY REMOVE ROOF-MOUNTED NATURAL GAS
PIPING SUPPORTS TO ALLOW FOR THE EXISTING
ROOFING ASSEMBLY TO BE REMOVED AND REINSTALLED.
PROVIDE TEMPORARY PIPING SUPPORTS AS NECESSARY.
DH7 REMOVE EXISTING PRIMARY AND SECONDARY ROOF
DRAINS AS NECESSARY TO ALLOW FOR THE EXISTING
ROOFING ASSEMBLY TO BE REMOVED AND REINSTALLED.
PREPARE EXISTING PRIMARY AND SECONDARY PIPING TO
REMAIN FOR CONNECTION TO NEW ROOF DRAIN AS PART
OF NEW WORK. FIELD VERIFY EXISTING PIPE SIZING AS
PART OF DEMOLITION WORK.
DH8 PERFORM PRE-DEMOLITION TEST AND BALANCE OF
EXISTING EXHAUST FAN AND PROVIDE AIRFLOW REPORT
TO ENGINEER.
DH9 REMOVE EXISTING PRIMARY AND SECONDARY ROOF
DRAINS AND ASSOCIATED PIPING TO ALLOW FOR THE
MECHANICAL WELL SPACE TO BE FILLED IN AS PART OF
NEW ROOF. PATCH AND REPAIR EXISTING, EXTERIOR
DECK AND WALL TO REMAIN TO MATCH ADJACENT.
DH10 REMOVE EXISTING CONDENSATE PIPING PORTAL AND
CONDENSATE PIPING AS INDICATED AND PREPARE
EXISTING CONDENSATE TO REMAIN FOR CONNECTION TO
NEW CONDENSATE PIPING AS PART OF NEW WORK.
N
SCALE: 3/32" = 1'-0"
LEVEL 03 - HVAC DEMOLITION PLAN
2 03/25/26
| 30-25134-00 ADOT_ A1-3 - OVERALL ROOF PLAN_Rev2 |
| Sheets |
| A1.3 - OVERALL ROOF PLAN |
| 30-25134-00 ADOT_A9-1 - ELEVATIONS & ROOF-FRAMING DETAILS_Rev2 |
| Sheets |
| A9.1 - ELEVATIONS & ROOF-FRAMING DETAILS |
| 30-25134-00 ADOT_M8-1 - PLUMBING & MECHANICAKL SCHEDULES, DETAILS & SECTIONS_Rev2 |
| Sheets |
| M8.1 - PLUMBING & MECHANICAL SCHEDULES, DETAILS & SECTIONS |
| 30-25134-00 ADOT_MD1-3 - LEVEL 03 - HVAC DEMOLITION PLAN_Rev2 |
| Sheets |
| MD1.3 - LEVEL 03 - HVAC DEMOLITION PLAN |
File details come from the government source that posted it. Updated .