B2505Plans.pdf

PDF 32 MB Posted

Attached to
Fire Station #83 Renovations State and local contract opportunity
Solicitation number
B-25-05
Issued by
Volusia County, Florida

About this file

The provided document is a comprehensive set of electrical engineering drawings for the City of DeLand's Fire Station 83 Addition project located in Volusia County, Florida. The electrical documentation includes multiple sheets covering electrical symbols, legends, demolition plans, lighting plans, power and systems plans, one-line electrical diagrams, and technical details. The drawings are part of a 100% construction document set dated December 20, 2024, prepared for a fire station renovation and expansion project that involves modifying the existing electrical infrastructure to accommodate a new building addition.

The electrical design encompasses a detailed retrofit of the existing electrical systems, including modifications to the main electrical service, panel upgrades, lighting replacements, and integration of new power circuits for additional spaces like bunk rooms, kitchen, fitness area, and apparatus bay. The existing electrical infrastructure includes a 450kW service with a 200A, 277/480V disconnect and a 112.5 KVA transformer, which will be adapted to support the new building addition. The electrical plans specify compliance with the Florida Building Code, National Electrical Code, and include provisions for emergency power, fire alarm systems, and technology infrastructure. The design emphasizes energy efficiency, with specifications for LED lighting, occupancy sensors, and surge protective devices across the facility's electrical systems.

View the file

Other files for this state and local contract opportunity

Other files attached to Fire Station #83 Renovations, newest first.
File Type Posted
RCA.pdf PDF
B2505Tabulation.pdf PDF
B2505Tabulation.pdf PDF
B2505ADD5.pdf PDF
B2505ADD5.pdf PDF
B2505ADD5.pdf PDF
B2505ADD5.pdf PDF
B2505ADD4.pdf PDF
B2505ADD4.pdf PDF
B2505ADD4.pdf PDF
B2505ADD4.pdf PDF
B2505ADD3.pdf PDF
B2505ADD3.pdf PDF
B2505ADD3.pdf PDF
B2505ADD3.pdf PDF
B2505ADD2.pdf PDF
B2505ADD2Attachment.pdf PDF
B2505ADD2Attachment.pdf PDF
B2505ADD2.pdf PDF
B2505ADD2Attachment.pdf PDF
B2505ADD2.pdf PDF
B2505ADD2Attachment.pdf PDF
B2505ADD2.pdf PDF
B2505ADD1.pdf PDF
B2505ADD1.pdf PDF
B2505ADD1.pdf PDF
B2505ADD1.pdf PDF
B2505Plans.pdf PDF
B2505Plans.pdf PDF
B2505Plans.pdf PDF
B2505Final.pdf PDF
B2505Final.pdf PDF
B2505Final.pdf PDF
B2505Final.pdf PDF
Show all 34

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

H

H

FS

FS

TS

F

RT

R

F

G

CII

CI

A

ELECTRICAL SYMBOL LEGEND

DN THRU-ROOF CONDUCTOR

COUNTERPOISE CONDUCTOR

BONDING CONDUCTOR

GROUND TERMINAL

AIR TERMINAL; PROVIDE PARAPET TYPE BASE WHERE MOUNTED ON PARAPET;

PROVIDE FLAT BASE FOR MECHANICAL EQUIPMENT OR ROOF PERIMETER WITH NO

PARAPET; PROVIDE BLUNT TIP WHERE MOUNTED ON INTERIOR OF ROOF, UNLESS

OTHERWISE NOTED ON LIGHTNING PROTECTION PLANS

BONDING PLATE

TEE SPLICE

CLASS II MAIN CONDUCTOR CABLE

CLASS I MAIN CONDUCTOR CABLE

FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

FIRE ALARM TERMINAL CABINET

FIRE ALARM CONTROL PANELFACP

HEAT DETECTOR 135°F FIXED TEMPERATURE, UNLESS OTHERWISE NOTED,

CEILING MOUNTED

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE

SPRINKLER WATERFLOW SWITCH CONNECTION

P

SPRINKLER TAMPER SWITCH CONNECTION

FIREMAN'S PHONE JACK

STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE NOTED

CD = CANDELA RATING

COMBINATION SPEAKER/STROBE, CEILING MOUNTED, 75CD UNLESS OTHERWISE

NOTED

HORN ONLY, WALL MOUNTED

DUCT SMOKE DETECTOR REMOTE TEST SWITCH WITH INDICATING LAMP, WALL

MOUNTED AT 48" AFF, UNLESS OTHERWISE NOTED

SUPERVISED ADDRESSABLE FIRE ALARM CONTROL RELAY

S = SUPPLY

R = RETURN

DUCT SMOKE DETECTOR

E = ELEVATOR WITH RECALL CONTACTS

I = IONIZATION

CEILING SMOKE DETECTOR, PHOTOELECTRIC TYPE UNLESS OTHERWISE

NOTED

MANUAL PULL STATION

EMERGENCY TWIN-HEAD LIGHT WITH INTEGRAL BATTERY PACK, WALL MOUNTED

TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF TRACK HEADS)

EXTERIOR POLE-MOUNTED AREA LIGHT FIXTURE, ARMS AS INDICATED ON DRAWINGS

EXIT LIGHT, LED, WALL MOUNTED

EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED;

SHADED QUADRANT INDICATES FACE(S) OF FIXTURE

LED, FLUORESCENT, HID - CEILING WALLWASHER, ACCENT LIGHT, LANDSCAPING TREE

ACCENT LIGHT, FACADE LIGHT

LED, FLUORESCENT, HID, RECESSED, PENDANT OR SURFACE CEILING

LED OR FLUORESCENT FIXTURE RECESSED, PENDANT OR SURFACE CEILING

DIAGONAL HALF SHADING INDICATE FIXTURE CONNECTED TO EMERGENCY CIRCUIT OR

PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E" AFTER FIXTURE TYPE TAG

INDICATES INTEGRAL BATTERY PACK UNLESS OTHERWISE NOTED ON LIGHT FIXTURE

SCHEDULE (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

LED OR FLUORESCENT FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

LED OR FLUORESCENT STRIP FIXTURE

LED OR FLUORESCENT FIXTURE, WALL MOUNTED

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCH

a

CIRCUIT NUMBER

LIGHTING

LIGHTNING PROTECTION SYSTEM

FIRE ALARM / DETECTION SYSTEM

F

XXCD CD = CANDELA RATING

COMBINATION SPEAKER/STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE

NOTED

CD = CANDELA RATING

STROBE, CEILING MOUNTED, 75 CD UNLESS OTHERWISE NOTED

SS SPEAKER ONLY, CEILING MOUNTED

PS PRESSURE SWITCH CONNECTION

XXCD

LED, FLUORESCENT, HID, WALL MOUNTED

LINEAR FLUORESCENT, LED, RECESSED, PENDANT OR SURFACE CEILING

ZX-X

LIGHTING CONTROL ZONE NUMBER

EXTERIOR PEDESTRIAN SIDEWALK BOLLARD OR POST-TOP LIGHT FIXTURE

B R

BEAM SMOKE DETECTOR

BT OR T = BEAM DETECTOR TRANSMITTER

BR OR R = BEAM DETECTOR RECEIVER

F

XXCD

SPEAKER ONLY, WALL MOUNTEDSS

FATC

FAA

VOICE EVACUATION PANELEVAC

MASS NOTIFICATION SYSTEM PANELMNS

FOUR-WAY SPLICE

VOICE AND DATA RACEWAY SYSTEM

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SINGLE-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR VOICE/DATA OUTLET

WITH 1" CONDUIT STUBBED UP AND INTO NEAREST ACCESSIBLE CEILING UNLESS

OTHERWISE NOTED; PROVIDE WITH NYLON PULL STRING & SMOOTH BUSHING

SINGLE-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR TELEPHONE WALL

OUTLET WITH 1" CONDUIT STUBBED UP AND INTO NEAREST ACCESSIBLE CEILING UNLESS

OTHERWISE NOTED; PROVIDE WITH NYLON PULL STRING & SMOOTH BUSHING

C = ABOVE COUNTER

W = WALL MOUNTED AT 52" AFF FOR HOUSE PHONE

W, ADA = WALL MOUNTED AT 44" AFF FOR ADA ACCESSIBLE PAY PHONE

ELV = WALL MOUNTED @ 52" AFF FOR TELEPHONE IN ELEVATOR

MACHINE ROOM

WIRELESS ACCESS POINT OUTLET, CEILING MOUNTED; ACTUAL QUANTITY AND

LOCATIONS SHALL BE BASED ON SIGNAL SURVEY BY OWNER'S WLAN VENDOR

WAP

MULTI-SERVICE FLOOR BOX WITH RECEPTACLE AND TECHNOLOGY DEVICES (REFER

TO OWNER'S VENDOR DRAWINGS FOR DEVICES); PROVIDE RACEWAY(S) AS

INDICATED ON FLOOR PLANS

MULTI-SERVICE FLOOR BOX WITH FURNITURE FEED CONNECTION; PROVIDE RACEWAY(S)

AS INDICATED ON FLOOR PLANS

2-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR WALL MOUNTED FURNITURE

FEED DATA CONNECTION; PROVIDE RACEWAY(S) AS INDICATED ON FLOOR PLANS

P

MULTI-SERVICE POKE-THRU WITH RECEPTACLES AND TECHNOLOGY DEVICES OR

FURNITURE FEED CONNECTION; REFER TO POKE-THRU DETAILS AND FLOOR PLANS FOR

RACEWAY INFORMATION

3/4"THICK X 8' HIGH A/C PLYWOOD BACKBOARD MOUNTED 6" AFF FROM BOTTOM,

PAINTED WITH GRAY FIRE-RETARDANT PAINT, WIDTH AS INDICATED ON FLOOR PLAN

CABLE TRAY FOR HORIZONTAL LOW VOLTAGE CABLE, 12"W X 4" HIGH UNLESS

OTHERWISE NOTED; LADDER TYPE IN IDF/MDF/IT ROOMS, BASKET/MESH TYPE IN

OTHER AREAS, UNLESS OTHERWISE NOTED

2-POST DATA RACK

4-POST DATA RACK

AUDIO/VIDEO RACEWAY SYSTEM

TV

TELEVISION SIGNAL WALL OUTLET, MOUNTED ADJACENT TO DUPLEX RECEPTACLE

IDENTIFIED WITH "TV" ADJACENT TO DEVICE; REFER TO ARCHITECTURAL ELEVATIONS FOR

MOUNTING HEIGHT

S CEILING MOUNTED SPEAKER

S WALL MOUNTED SPEAKER

X = ZONE TO BE CONTROLLEDX

VC

WALL-MOUNTED VOLUME CONTROL; PROVIDE 3/4" C. STUBBED UP ABOVE CEILING AND

SINGLE STANDARD ELECTRICAL BOX AT 48" AFF

MC WALL-MOUNTED MASTER VOLUME CONTROL; PROVIDE 3/4" C. STUBBED UP ABOVE

CEILING AND SINGLE STANDARD ELECTRICAL BOX AT 48" AFFX

X = ZONE TO BE CONTROLLED

RCA WALL-MOUNTED DUAL RCA JACKS FOR MP3 CONNECTION

AV AUDIO/VISUAL CABINET OR RACK

POWER POLE WITH POWER & DATA FURNITURE FEED POWER CONNECTIONS; REFER

TO FLOOR PLANS FOR RACEWAY INFORMATION

PP

W

IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS

IES ILLUMINATING ENGINEERING SOCIETY

IMC INTERMEDIATE METAL CONDUIT

IN INCHES

IPCEA INSULATED POWER CABLE ENGINEERS ASSOCIATION

IT INSTANTANEOUS TRIP

JB OR J-BOX JUNCTION BOX

KCMIL ONE THOUSAND CIRCULAR MILS

KV KILOVOLT

KVA KILOVOLT AMPERES

KW KILOWATT

KWH KILOWATT HOURS

LBS POUNDS

LED LIGHT EMITTING DIODE

LP LIGHTNING PROTECTION

LT LIGHT

LTG LIGHTING

LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND

LSIA LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM

LSI LONG TIME, SHORT TIME, INSTANTANEOUS

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN SERVICE DISTRIBUTION PANEL

MIC MICROPHONE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MSB MAIN SERVICE SWITCHBOARD

MTD MOUNTED

MTG MOUNTING

MTR MOTOR

MTS MANUAL TRANSFER SWITCH

MUX MULTIPLEX (TRANSPONDER) PANEL

MVA MEGA VOLT AMPS

N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NF NON-FUSED

NL NON-LINEAR

NO NORMALLY OPEN OR NUMBER

OL OVERLOAD

OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION

P POLE

PB PULLBOX

PF POWER FACTOR

PIV POST INDICATOR VALVE

PNL PANEL

PR PAIR

PRI PRIMARY

PT POTENTIAL TRANSFORMER

PVC POLYVINYLCHLORIDE

PWR POWER

REC, RECEPT RECEPTACLE

REF REFRIGERATOR

RGS, GRC RIGID GALVANIZED STEEL CONDUIT

RLA RUNNING LOAD AMPERES

RMS ROOT-MEAN-SQUARE

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

SCA SHORT CIRCUIT AMPERES

SD SMOKE DETECTOR

SEC SECONDARY

S/N SOLID NEUTRAL

SPD SURGE PROTECTIVE DEVICE

SPKR SPEAKER

SPST SINGLE POLE SINGLE THROW

SS STAINLESS STEEL

SST SOLID STATE TRIP

STD SHORT TIME TRIP

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TVEC TELEVISION EQUIPMENT CABINET

TYP TYPICAL

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

UL UNDERWRITERS LABORATORIES

UTIL UTILITY

V VOLT

VA VOLTAMPERE

VAR VOLT AMPERE REACTIVE

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

W WIRE

WP WEATHER PROOF

XFMR TRANSFORMER

XFR TRANSFER

ABBREVIATIONS (CONT.)

NFPA / LEGACY

F

S

S

BR

S

H

DH

XXCD

F H

XXCD

C

S C

S

VS

WS

PS

FACP

FATC

FAA

EVAC

MNS

R

WALL MOUNTED DATA RACKMASS NOTIFICATION SYSTEM PANELDACTDACT

A/C AIR CONDITIONING

AC ALTERNATING CURRENT

ABV CLG ABOVE CEILING

ADA AMERICANS WITH DISABILITIES ACT

AF AMPERE FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

AMP AMPERE

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

ASA AMERICAN STANDARDS ASSOCIATION

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BIL BASIC IMPULSE LEVEL

BAS BUILDING AUTOMATION SYSTEM

BMS BUILDING MANAGEMENT SYSTEM

BRKR OR BKR BREAKER

C CONDUIT OR RACEWAY

CAB CABINET

CKT CIRCUIT

CB CIRCUIT BREAKER

CBM CERTIFIED BALLAST MANUFACTURERS

CATV CABLE TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

CLEC CLOCK EQUIPMENT CABINET

CLG CEILING

CO CONDUIT OR RACEWAY ONLY

COAX COAXIAL CABLE

COND CONDUCTOR

CONN CONNECTION

CPU CENTRAL PROCESSING UNIT

CRT CATHODE RAY TERMINAL (VIDEO DISPLAY TERMINAL)

CT CURRENT TRANSFORMER

CU COPPER

CW COLD WATER

DC DIRECT CURRENT

DDC DIRECT DIGITAL CONTROL

DEG DEGREE

DF DEMAND FACTOR

DISC DISCONNECT

DISC SW DISCONNECT SWITCH

DO DRAW OUT

DN DOWN

DPST DOUBLE POLE SINGLE THROW

EDH ELECTRIC DUCT HEATER

EMT ELECTRIC METALLIC TUBING

EO ELECTRICALLY OPERATED

EOL END OF LINE

EOR ENGINEER OF RECORD

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FATC FIRE ALARM TERMINAL CABINET

FBC FLORIDA BUILDING CODE

FCU FAN COIL UNIT

FLA FULL LOAD AMPERES

FM FACTORY MUTUAL

FPU FAN POWERED UNIT

FT FEET

GF GROUND FAULT

GFA GROUND FAULT ALARM

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFR GROUND FAULT RELAY

GND, G GROUND

HP HORSEPOWER

HOA HAND-OFF-AUTOMATIC

HORIZ HORIZONTAL

IBC INTERNATIONAL BUILDING CODE

IC INTERCOM

ICU INTENSIVE CARE UNIT

IECC INTERNATIONAL ENERGY CONSERVATION CODE

ABBREVIATIONS

DN

DN

FLAT ROOF MOUNTED OR MECHANICAL

F

P

PARAPET MOUNTED AIR TERMINAL

DOWN CONDUCTOR

PIPE CLAMP FOR PLUMBING VENT THRU ROOF.

DN

UP

SYMBOL DESCRIPTION

DDC

VFD

AUTOMATIC TRANSFER SWITCH

TRANSFORMERT

DIRECT DIGITAL CONTROL PANEL

VARIABLE FREQUENCY DRIVE

MOTOR CONNECTION

NEW (HEAVY, SOLID LINE)

EXISTING TO REMAIN (LIGHT, SOLID LINE)

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUBBED OUT OR UP

CONDUIT TURNING DOWN

CONDUIT TURNING UP

GROUND OR GROUND ROD AS NOTED

CONDUIT EXPOSED

CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR

CONDUIT CONCEALED ABOVE CEILING OR IN WALL

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED

MULTI-SERVICE RACEWAY WITH 5-20R RECEPTACLES, 18" O.C. UNLESS

OTHERWISE NOTED

SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED

NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE

CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);

TYPICAL FOR ANY DEVICE IN LEGEND

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVER MOUNTED ABOVE COUNTER

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE

GFCI RECEPTACLE; "WP" INDICATES CAST METAL "IN-USE" WEATHERPROOF COVER,

WEATHER-RESISTANT LISTED

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES

(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW

VOLTAGE REQUIREMENTS)

FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE

M

F

LV

OS

a

30AR

20AF

PEDESTAL MOUNTED DUPLEX RECEPTACLE

DUPLEX RECEPTACLE

DIMMER SWITCH, LINE VOLTAGE

MOTOR RATED SWITCH

FAN SWITCH

LOW VOLTAGE SWITCH

WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR

WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH

FOUR-WAY SWITCH

THREE-WAY SWITCH

NF

30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED

SINGLE POLE SWITCH (SUBSCRIPT INDICATES ITEM CONTROLLED)

NF = NON-FUSED

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE

NOTED

30/3

3R

MCP

AMPERE

RATING

# OF POLES

NEMA STARTER SIZE

SINGLE RECEPTACLE

FUSED DISCONNECT

D

BASIC MATERIALS

S

S

S

S

S

S

S

S

MOTORIZED DAMPER CONNECTIONMD

K SINGLE POLE KEY SWITCHS

CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR

OSab WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH, DUAL RELAYS

DL DAYLIGHT SENSOR CEILING MOUNTED

DL DAYLIGHT SENSOR WALL MOUNTED

RECEPTACLE CONTROLLED PER ASHRAE 90.1 (2010); PROVIDE POWER PACK FOR

RECEPTACLE CIRCUIT, TO BE CONTROLLED THROUGH LOCAL ROOM OCCUPANCY

SENSOR(S); PROVIDE DEVICE WITH BLUE DOT OR UNIVERSAL POWER SYMBOL

RECEPTACLE MOUNTED ADJACENT TO TV OUTLET, COORDINATE HEIGHT W/ ARCHITECT

FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE

DUPLEX RECEPTACLE WITH (2) USB PORTS

DOUBLE DUPLEX RECEPTACLE WITH DEDICATED CIRCUIT FOR AV RACK OR CART

D,OS WALL MOUNTED DUAL TECHNOLOGY DIMMING/OCCUPANCY SENSOR SWITCHS

LVO

LOW VOLTAGE OVERRIDE SWITCHS

VS WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR SWITCHS

OS

C

TV

U

AV

HOSPITAL GRADE H

TAMPER RESISTANTTR

ISOLATED GROUND (ORANGE DEVICE) IG

WEATHERPROOFWP

OS

DEVICE ABBREVIATION TAGS:

DUPLEX RECEPTACLE, CEILING MOUNTED

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE, CEILING MOUNTED

J

FOUR-GANG FLOOR BOX4G

SIX-GANG FLOOR BOX6G

EIGHT-GANG FLOOR BOX8G

MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLES (QUAD) , VOICE/DATA/AV

DEVICES

GFCI RECEPTACLE MOUNTED ABOVE COUNTER

DUPLEX RECEPTACLE; EACH RECEPTACLE ON SEPARATE CIRCUIT (PROVIDE

BREAKER WITH 2-POLE COMMON TRIP HANDLE)

SPLIT-WIRED CONTROLLED DUPLEX RECEPTACLE

TWO GFCI DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE

MULTI-SERVICE POWER & DATA FLOOR BOX WITH FURNITURE FEED CONNECTION

J JUNCTION BOX WALL MOUNTED

J JUNCTION BOX MOUNTED IN OR ABOVE CEILING OR IN STRUCTURE

J WALL MOUNTED FURNITURE FEED POWER CONNECTION

P

MULTI-SERVICE POKE-THRU WITH TWO INTEGRAL DUPLEX RECEPTACLES AND

VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR

DRAWINGS FOR LOW VOLTAGE REQUIREMENTS), OR FURNITURE FEED CONNECTION;

REFER TO POKE-THRU DETAILS

PP

POWER POLE WITH POWER & DATA FURNITURE FEED POWER CONNECTIONS

POKE-THRU WITH 6" CORE DRILL6C

POKE-THRU WITH 8" CORE DRILL8C

PC PHOTOCELL, MOUNTED ON ROOF FACING NORTH

C CLOCK RECEPTACLE, WALL MOUNTED

GROUND BUS BAR, COPPERGND

CONDUIT SEAL-OFF FITTING

SPD SURGE PROTECTIVE DEVICE

ST

SHUNT-TRIP PUSHBUTTON; SEMI-FLUSH WALL MOUNTED UNLESS OTHERWISE NOTED;

NEMA 3R FOR EXTERIOR LOCATIONS

OVERHEAD DOOR PUSHBUTTON CONTROL STATION

PUSHBUTTON STATION

BAS BUILDING AUTOMATION SYSTEM CONTROL PANEL

LCP LIGHTING CONTROL PANEL

MANHOLEMH

SYMBOL DESCRIPTION

PULLBOXPB

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

3R

3R

AF = AMPERE RATING OF FUSE

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED

CONDUIT HOMERUN TO ELECTRICAL PANEL

EXISTING TO REMAIN ETR

RELOCATEDRL

PP POWER POLE WITH POWER & DATA OUTLETS

HANDHOLEHH

ATS

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL

EPO EMERGENCY POWER OFF SHUNT-TRIP PUSHBUTTON, RED MUSHROOM HEAD, CLEAR

LEXAN PROTECTIVE COVER

T DIGITAL TIMER SWITCH W/ 5 MIN. WARNING FLASHS

LVD

LOW VOLTAGE OVERRIDE SWITCH WITH DIMMINGS

VS VACANCY SENSOR CEILING MOUNTED

VS VACANCY SENSOR WALL MOUNTED

7370 Cabot Court, Suite 103 Melbourne, FL 32940 P 321.636.0274

©Copyright 2024

TLC No.:

www.tlc-engineers.com

COA 15

KUBO STUDIO

821 HERNDON AVENUE

#141126

ORLANDO, FL 32803

LLC NO. L20000333046

A R C H I T E C T U R E

F

E

D

C

B

A

F

E

D

C

B

A sh ee t t itl e:

sheet number:

IF THIS SHEET MEASURES LESS THAN 42" x 30", IT HAS BEEN REDUCED scale:

drawn by:

designed by:

project no.:

issue date:

professional license no.:

name:

pr oj ec t a dd re ss cl ie nt n am e:

pr oj ec t s ta tu s:

pr oj ec t n am e:

consultant:

client:

524103

/2

0/

:5 0:

P

M

N.T.S.

E-001

E

LE

C

TR

IC

A

L S

Y M

B O

LS

, L

E G

E N

D , A

N D

IN

D

E X

CLM

CLM

2023-P031

20 DECEMBER 2024

C

IT

Y O

F D

E

LA

N D

, F

LO

R

ID

A

E A

S T

T A

Y

LO

R R

D

D E

LA

N

D , F

L

C

IT

Y O

F D

E

LA

N D

, F

IR

E S

T A

T

IO

N

0%

C O

N S

T R

U C

T

IO

N D

O C

U M

E N

T S

Stephen B. Cotton, P.E.

60046

ELECTRICAL DRAWING INDEX

SHEET DESCRIPTION

E-001 ELECTRICAL SYMBOLS, LEGEND, AND INDEX

E-002 ELECTRICAL GENERAL NOTES

E-100 ELECTRICAL DEMOLITION PLAN

E-101 LIGHTING PLAN

E-102 POWER AND SYSTEMS PLAN

E-401 ELECTRICAL ONE-LINE DIAGRAM & SCHEDULES

E-601 ELECTRICAL DETAILS

ET101 TEMPORARY TRAILER POWER PLAN

N O

D

E S

C R

IP

T

IO

N

D A

T E

ELECTRICAL GENERAL NOTES

ELECTRICAL DEVICES OUTLET BOXES, JUNCTION BOXES

1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED OTHERWISE.

2. RECEPTACLES, VOICE/DATA OUTLETS AND WALL FURNITURE FEEDS SHALL BE MOUNTED 18 INCHES

ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED OTHERWISE. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE, UNLESS NOTED

OTHERWISE.

3. IT IS THE INTENT THAT ALL DEVICE OUTLET BOXES (POWER AND SYSTEMS) BE FLUSH MOUNTED IN WALLS, CEILINGS OR FLOORS, AND JUNCTION BOXES FLUSH MOUNTED IN WALLS, CEILINGS, OR FLOORS, OR CONCEALED ABOVE ACCESSIBLE CEILINGS, AND NOT SURFACE MOUNTED, UNLESS SPECIFICALLY NOTED ON THE CONTRACT DRAWINGS, OR UNLESS THE ARCHITECT/ENGINEER GRANTS WRITTEN PERMISSION.

4. ALL COMPONENTS OF THE ELECTRICAL SYSTEM (INCLUDE RACEWAYS, ELECTRICAL EQUIPMENT, OUTLET BOXES, JUNCTION BOXES, ETC.) LOCATED IN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE APPROVED FOR USE IN SAID LOCATION, AS DEFINED BY THE NEC, WHETHER INDICATED ON THE CONTRACT

DOCUMENTS OR NOT.

5. ALL DEVICES SHALL BE MOUNTED VERTICALLY, UNLESS NOTED OTHERWISE.

6. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.

7. WHERE DEVICES ARE SHOWN IN WALLS BACK-TO-BACK ON OPPOSITE SIDES, INSTALL SO THAT THEY ARE

SEPARATED BY AT LEAST 12".

8. RECEPTACLES OR JUNCTION BOXES FOR ELECTRIC WATER COOLERS AND VENDING MACHINES SHALL BE

LOCATED DIRECTLY BEHIND SAID APPLIANCE, CONCEALED FROM DIRECT VIEW. RECEPTACLES AND/OR HARD WIRED EQUIPMENT CONNECTIONS SHALL BE PROTECTED BY A READILY ACCESSIBLE GFCI FEED- THRU DEVICE LOCATED IMMEDIATELY ADJACENT TO THE APPLIANCE OR BE PROTECTED BY GFCI BREAKER IN THE PANELBOARD. ALL GFCI DEVICES MUST BE READILY ACCESSIBLE PER THE NEC.

9. ALL EXTERIOR RECEPTACLES OR RECEPTACLES LOCATED IN AREAS SUBJECT TO MOISTURE (PARKING GARAGE, WASHDOWN AREAS IN KITCHEN, ETC) SHALL BE GFCI TYPE. ALL EXTERIOR RECEPTACLES

SHALL WE PROVIDED WITH CAST METAL, IN-USE COVER UNLESS NOTED OTHERWISE.

10. ALL RECEPTACLES LOCATED IN KITCHENS, BATHROOMS, MECHANICAL ROOMS, JANITOR CLOSETS, ELEVATOR SHAFTS, ELEVATOR EQUIPMENT ROOMS, FOR ELEVATOR SUMP PUMP(S) OR INSTALLED

WITHIN 6' OF THE INSIDE FACE OF A SINK, SHALL BE GFCI TYPE OR GFCI PROTECTED.

11. ALL RECEPTACLES LOCATED IN CHILD-CARE FACILITIES, DWELLING UNITS, HOTEL/MOTEL GUEST ROOMS, PEDIATRIC CLINICS OR PEDIATRIC CAREA AREAS, AND OTHER AREAS AS REQUIRED BY NEC AND LOCAL

CODE REQUIREMENTS SHALL BE TAMPER RESISTANT.

12. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL

BE MET:

A. ALL ELECTRICAL BOXES SHALL BE METALLIC.

B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.

C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.

D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED

WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).

E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE

WALL RATING SHALL BE MAINTAINED.

F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE

INCHES PER 100 SQUARE FEET.

G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE

SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.

H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.

I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH

BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.

ELECTRICAL EQUIPMENT

1. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY

ARE TO BE INSTALLED. ALL COMPONENTS OF THE ELECTRICAL SYSTEM LOCATED OUTDOORS OR

INDOORS WHERE EXPOSED TO SIGNIFICANT MOISTURE SHALL BE WEATHERPROOF, NEMA 3R, AS A

MINIMUM, WHETHER INDICATED ON THE CONTRACT DRAWINGS OR NOT.

2. TERMINATION PROVISIONS FOR ALL ELECTRICAL EQUIPMENT (PANELBOARDS, SWITCHBOARD, TRANSFORMERS, DISCONNECT SWITCHES, MOTOR CONTROLLERS, AUTOMATIC TRANSFER SWITCHES, ENCLOSED CIRCUIT BREAKERS, BUSWAYS, ETC.) SHALL BE LISTED AND IDENTIFIED FOR USE WITH

MINIMUM 75 DEG. F CONDUCTORS IN ACCORDANCE WITH NEC.

3. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC.

4. THE ELECTRICAL DEDICATED EQUIPMENT SPACE EXTENDING FROM FLOOR TO 6' ABOVE ELECTRICAL

EQUIPMENT OR TO THE STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND

DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS,

ARCHITECTURAL APPURTENANCES AND OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL

INSTALLATION IN ACCORDANCE WITH NEC.

5. PROVIDE A REINFORCED CONCRETE PAD, SIZED 4" LARGER IN ALL DIRECTIONS THAN THE FOOTPRINT OF THE EQUIPMENT, AND 4" HIGH, FOR ALL FREESTANDING, FLOOR-MOUNTED ELECTRICAL EQUIPMENT.

PROVIDE VIBRATION ISOLATORS AND/OR ANCHORS PER MANUFACTURER'S INSTRUCTIONS.

6. PROVIDE HACR RATED CIRCUIT BREAKER FOR ALL HVAC EQUIPMENT.

7. ALL PANELBOARDS OR DISCONNECT SWITCHES LOCATED IN KITCHEN AREAS SHALL BE STAINLESS

STEEL (COVER AND DOOR WHERE PANEL IS FLUSH MOUNTED; PANEL BOX, COVER & DOOR WHERE

SURFACE MOUNTED).

8. PROVIDE SURGE PROTECTION DEVICE FOR ALL MAIN SERVICE EQUIPMENT, PANELBOARDS SERVING SENSITIVE ELECTRONIC EQUIPMENT (DATA RACKS) OR COMPUTERS, EMERGENCY SWITCHBOARDS AND PANELBOARDS, LIGHTING PANELS SERVING EXTERIOR LIGHTING, POWER CIRCUITS OR LOW VOLTAGE (FIRE ALARM, TELECOMMUNICATIONS) EXITING THE BUILDING. PROVIDE MINIMUM 30A/3P BREAKER IN BRANCH CIRCUIT PANELBOARDS AND 60A/3P IN DISTRIBUTION PANELBOARDS OR SWITCHBOARDS, UNLESS NOTED OTHERWISE, OR PER THE SPD MANUFACTURER'S RECOMMENDATIONS FOR SURGE

PROTECTION DEVICE.

9. PROVIDE ARC ENERGY REDUCING MAINTENANCE SWITCH FOR ANY BREAKER RATED (OR ABLE TO BE ADJUSTED TO) 1200A OR HIGHER UNLESS OTHER ARC ENERGY REDUCTION MEANS MEETING NEC 240.87

IS INDICATED ON DRAWINGS/SPECIFICATIONS OR OTHERWISE PROVIDED.

CONDUCTORS

1. ALL WIRE SHALL BE SIZED AS SHOWN ON THE DRAWINGS. IF NO WIRE SIZE IS SHOWN, THEN WIRE

SHALL BE #12 AWG.

2. BRANCH CIRCUITS SHALL BE INCREASED IN SIZE AS REQUIRED TO COMPENSATE FOR VOLTAGE DROP

FROM LENGTH OF CIRCUIT DUE TO FIELD ROUTING. FINAL INSTALLATION SHALL NOT EXCEED A MAXIMUM OF 3% VOLTAGE DROP FOR BRANCH CIRCUITS. REFER TO VOLTAGE DROP TABLE BELOW

FOR CONDUCTOR SIZES FOR BRANCH CIRCUITS AS FOLLOWS:

A. 120V, 20A CIRCUITS SHALL BE:

i. #12 FROM 0-70 FT

ii. #10 FROM 71-115FT

iii. #8 FROM 116-180FT

B. 277V, 20A CIRCUITS SHALL BE:

i. #12 FROM 0-140FT

ii. #10 FROM 141-220FT

iii. #8 FROM 221-350FT

ANYTHING LONGER THAN THE ABOVE SHALL BE SUBMITTED TO THE ENGINEER WITH CALCULATIONS

FOR APPROVAL.

3. ALL CONDUCTORS IN CABINETS MUST BE CAREFULLY FORMED AND HARNESSED SO THAT EACH

CONDUCTOR DROPS OFF DIRECTLY OPPOSITE TO TERMINAL.

4. ALL WIRE SIZES ARE BASED ON AMPACITIES FOR 60 DEG F TEMPERATURE RATING FROM 0-100A AND 75

DEG. F TEMPERATURE RATING LISTED IN NEC FOR 100A AND ABOVE.

5. ALL CONDUCTORS SHALL BE COPPER, THHN/THWN; SOLID FOR #10 AWG AND SMALLER; STRANDED FOR

#8 AWG AND LARGER.

6. CONDUCTORS USED IN WET LOCATIONS, INCLUDING BUT NOT LIMITED TO UNDERGROUND CONDUITS/ DUCTBANKS AND EXTERIOR CONDUITS SHALL COMPLY WITH NEC 310.10 AND BE LISTED FOR USE IN

WET LOCATIONS.

7.ALL POWER CIRCUITS HAVE BEEN DESIGNED TO MEET 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND

3% OR LESS VOLTAGE DROP FOR BRANCH CIRCUITS.

GROUNDING

1. FIRE PROTECTION PIPING SHALL NOT BE USED FOR GROUNDING.

2. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUND CONDUCTOR. METAL

RACEWAYS SHALL NOT BE USED AS THE SOLE EQUIPMENT GROUND.

3. WHERE A PHASE CONDUCTOR IS INCREASED IN SIZE DUE TO VOLTAGE DROP, THE EQUIPMENT

GROUND CONDUCTOR SHALL BE INCREASED IN SIZE PROPORTIONATELY.

4. PROVIDE A GROUND BUS BAR IN EACH ELECTRICAL ROOM AND TELECOMMUNICATIONS / IDF/ MDF

ROOM FOR ALL NEW CONSTRUCTION AND NEW ROOMS IN EXISTING CONSTRUCTION, AND IN EXISTING

CONSTRUCTION WHERE THERE IS NONE INSTALLED WITHIN AN EXISTING ROOM.

IDENTIFICATION

1. PROVIDE TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS, AND EXISTING PANELBOARDS

AFFECTED BY THIS PROJECT. DIRECTORIES SHALL REFLECT PROJECT AS- BUILT CONDITIONS FOR ALL BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE WHERE EACH PANEL IS FED FROM. ADDITIONALLY, EACH BRANCH CIRCUIT LOAD DESCRIPTION SHALL INCLUDE THE ROOM NUMBER(S) FOR EACH LOAD (I.E., RECEPTACLES-RMS 501,503). ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN FIELD. COORDINATE EXACT ROOM NUMBERS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO

COMPLETION OF PANEL DIRECTORIES.

2. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON EACH SWITCHBOARD, SWITCHGEAR,

DISTRIBUTION PANEL, PANELBOARD, MOTOR CONTROL CENTER, SAFETY SWITCH, ENCLOSED CIRCUIT BREAKER, CABINET, STEP-DOWN TRANSFORMER, TRANSFER SWITCH, ETC., AND ANY OTHER MAJOR

COMPONENT OF THE ELECTRICAL SYSTEM.

3. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS FOR EACH DISTRIBUTION BREAKER OR BRANCH

CIRCUIT BREAKER IN SWITCHGEAR, SWITCHBOARDS, MOTOR CONTROL CENTERS AND OTHER

DISTRIBUTION EQUIPMENT. NAME TAG SHALL INCLUDE LOAD DESCRIPTION AND ROOM NUMBER FOR

EACH LOAD.

4. ARC FLASH DANGER/WARNING LABELS SHALL BE APPLIED TO SWITCHBOARD, PANELBOARDS, AND

EQUIPMENT CONTROLLERS PER NEC.

5. PROVIDE LABELS ON THE INSIDE OF EACH DEVICE COVERPLATE, IDENTIFYING THE PANEL(S)/ CIRCUIT

NUMBER(S) DEVICE IS CONNECTED TO.

6. PROVIDE NEATLY, HANDWRITTEN IDENTIFICATION ON THE EXTERIOR COVER OF ALL JUNCTION BOXES, PULLBOXES AND WIREWAYS, IDENTIFYING THE PANEL(S)/ CIRCUIT NUMBER(S) CONTAINED WITHIN.

7. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BUILDING STATING THAT

THE MAIN SERVICE DISCONNECTING MEANS IS LOCATED INSIDE.

8. PROVIDE A PERMANENT LABEL ON ALL PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROL CENTERS AND DISTRIBUTION PANELS STATING "DO NOT WORK ON EQUIPMENT WHILE ENERGIZED. LOCK-

OUT TAG-OUT REQUIRED".

9. PROVIDE REQUIRED IDENTIFICATION PER ANSI STANDARDS, NEC REQUIREMENTS, AND OWNER'S

PUBLISHED DESIGN STANDARDS WHERE APPLICABLE.

10. PROVIDE ENGRAVED PHENOLIC LABEL ON ALL NEW SERVICE EQUIPMENT TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE THE FAULT CURRENT CALCULATION WAS PERFORMED.

PROVIDE LABEL ON ALL EXISTING SERVICE EQUIPMENT WHEN MODIFICATIONS OCCUR THAT AFFECT THE

MAXIMUM AVAILABLE FAULT CURRENT AT THE SERVICE.

11. PROVIDE ARC FLASH HAZARD ANALYSIS PER NFPA 70E FOR ANY EQUIPMENT INCLUDED WITHIN THE

SCOPE OF WORK. INCIDENT ENERGY VALUES SHALL BE INCLUDED ON THE ARC FLASH WARNING

LABELS FOR EACH EQUIPMENT .

COORDINATION:

1. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL

CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE

INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.

2. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF

ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND

EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY

ELECTRICAL REQUIRED, UNLESS NOTED OTHERWISE.

3. THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE

COORDINATION DRAWING PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION

REQUIRED TO COORDINATE ALL TRADE INFORMATION.

4. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE

COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF

WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.

5. WHERE WALLS ARE OF TILT-UP OR PRE-CAST CONSTRUCTION, PROVIDE COORDINATION FOR EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED WITHIN SUCH WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE WALLS, PRIOR TO CONSTRUCTION OF

THE WALLS.

6. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE

DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH

CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGH-IN TO ENSURE PROPER NEC

CLEARANCES AND APPROPRIATE MOUNTING SURFACE.

7. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR

DESIGN, TECHNOLOGY, STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED

INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART OF THE

WORK.

8. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN

WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE

DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE

CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.

9. CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE BEEN REASONABLY

OBSERVED WILL NOT BE RECOGNIZED.

10. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE.

PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE

REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG

LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.

11. ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND

SCHEDULED IN ADVANCE.

12. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS (ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL, EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING AND IMPACT FEES.

13. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM

INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE

NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY

LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER

AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE

ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO

PROCEEDING WITH REPAIRS.

14. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID. CONTRACTOR SHALL

NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET

BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.

LIGHTING:

1. LIGHT FIXTURES SUPPORTED BY CEILING GRID SHALL BE SUPPORTED AS FOLLOWS: LIGHT FIXTURES

WEIGHING LESS THAN 10 POUNDS SHALL HAVE 12-GAUGE HANGER WIRE CONNECTED FROM THE LIGHT FIXTURE TO THE STRUCTURE ABOVE. LIGHT FIXTURES WEIGHING 10 POUNDS OR MORE SHALL HAVE (2)

12- GAUGE HANGER WIRES ATTACHED AT OPPOSITE CORNERS OF THE LIGHT FIXTURE TO THE

STRUCTURE ABOVE.

2. COORDINATE EXACT LOCATIONS OF LIGHT FIXTURES IN LAY-IN AND GYPBOARD CEILINGS WITH ARCHITECTURAL REFLECTED CEILING PLANS, AND WALL MOUNTED EXTERIOR AND INTERIOR LIGHT FIXTURES WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION. WHERE THE QUANTITY OF LIGHTS DIFFERS BETWEEN THE ARCHITECTURAL RCP AND THE ELECTRICAL LIGHTING PLANS, PROVIDE THE HIGHEST QUANTITY OF FIXTURES IN THE BID PRICE. THE DISCREPANCY IN QUANTITY SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE HIGHEST QUANTITY SHALL BE CIRCUITED TO THE LOCAL ROOM OR AREA LIGHTING CIRCUITS AND LIGHTING CONTROL DEVICES, UNLESS OTHERWISE DIRECTED IN WRITING BY THE ARCHITECT/ENGINEER.

3. VERIFY ACTUAL CEILING CONSTRUCTION TYPE AS DEFINED ON THE ARCHITECTURAL DRAWINGS AND

FURNISH ALL LIGHT FIXTURES WITH THE CORRECT MOUNTING DEVICES WHETHER OR NOT SUCH

VARIATIONS ARE INDICATED BY THE LIGHT FIXTURE CATALOG NUMBER. VERIFY THE DEPTH OF ALL

RECESSED LIGHT FIXTURES WITH THE ARCHITECTURAL DRAWINGS PRIOR TO ORDERING LIGHT

FIXTURES. ANY DISCREPANCIES THAT WOULD CAUSE THE RECESSED LIGHT FIXTURES NOT TO FIT

INTO CEILING SHALL BE REPORTED TO ARCHITECT/ENGINEER PRIOR TO ORDERING.

4. LIGHT FIXTURES RECESSED IN FIRE-RATED CEILINGS SHALL BE PROVIDED WITH APPROVED FIRE- RATED ENCLOSURE WITH A FIRE RATING EQUAL TO THAT OF THE CEILING. PROVIDE A MINIMUM OF 3"

CLEARANCE FROM SIDES AND TOP OF RECESSED LIGHT FIXTURES.

5. MODIFY ALL LIGHT FIXTURE CATALOG NUMBERS AS REQUIRED TO COORDINATE WITH THE LIGHTING

BRANCH CIRCUIT VOLTAGES INDICATED. COORDINATE THE CATALOG NUMBERS WITH THE EXACT

FIXTURE MOUNTING AND TRIM REQUIRED BY THE CEILING IN WHICH EACH FIXTURE IS BEING

INSTALLED.

6. ALL LIGHT FIXTURES SHALL BE PROVIDED COMPLETE WITH LAMPS, UNLESS OTHERWISE NOTED.

7. ALL EXIT LIGHTS, LIGHT FIXTURES INDICATED WITH UNSWITCHED CIRCUIT (NIGHTLIGHT N/L), EMERGENCY TWIN-HEAD FIXTURES WITH INTEGRAL BATTERY PACKS, AND BATTERY PACKS INTEGRAL TO LIGHT FIXTURES, SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHING OR LIGHTING CONTROLS.

8. PROVIDE UL WET LABEL OR IP67 RATED LIGHT FIXTURES FOR ALL FIXTURES LOCATED OUTSIDE OR IN

PARKING GARAGES, IN SHOWERS, OR OPEN STRUCTURES.

9. EXTERIOR LIGHTING BALLASTS/DRIVERS SHALL HAVE A MINIMUM STARTING TEMPERATURE OF -40

DEGREE C, AND A NORMAL AMBIENT OPERATING TEMPERATURE OF 40 DEGREE C.

10. PROVIDE FUSING FOR ALL EXTERIOR LIGHT FIXTURES, OR FIXTURES IN PARKING GARAGES OR OPEN

STRUCTURES.

11. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNS REQUIRED

DURING THE PROJECT CONSTRUCTION PHASE.

12. COORDINATE EXACT FOUNDATION AND/OR COMPACTING REQUIREMENTS FOR ALL POLE MOUNTED LIGHT FIXTURES WITH MANUFACTURER'S AND/OR INSTALLER'S STRUCTURAL ENGINEER. POLE BASES SHALL MEET OR EXCEED ALL WIND LOAD RATINGS, GUST FACTORS, IMPORTANCE FACTORS, ETC.

REQUIRED BY NATIONAL AND/OR LOCAL CODES. SHOP DRAWINGS SHALL INCLUDE STRUCTURAL

DRAWINGS FOR ALL POLE BASES, POLE, ASSEMBLY AND OVERTURN CALCULATIONS REQUIRED IN THIS PROJECT, SIGNED AND SEALED BY A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE

PROJECT STATE.

13. REFER TO LIGHT FIXTURE SCHEDULE FOR LIGHT FIXTURE TYPES, DESCRIPTIONS, CATALOG NUMBERS AND ADDITIONAL INFORMATION PERTINENT TO THE LIGHT FIXTURE OR INSTALLATION THEREOF.

14. COORDINATE LIGHT FIXTURE TRIM TYPE AND FINISH COLOR WITH ARCHITECT PRIOR TO ORDERING.

15. EACH LIGHTING CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL.

16. PROVIDE LIGHTING CONTROLS TO AUTOMATICALLY SHUTOFF BUILDING FACADE AND LANDSCAPE

LIGHTING AS A FUNCTION OF DAWN/DUSK AND OPENING/CLOSING TIME.

17. PROVIDE LIGHTING CONTROLS TO AUTOMATICALLY REDUCE THE CONNECTED LIGHTING POWER OF

EXTERIOR SITE/AREA LIGHTING BY NOT LESS THAN 30 PERCENT FROM NOT LATER THAN MIDNIGHT

TO 6AM, FROM ONE HOUR AFTER BUSINESS CLOSING TO ONE HOUR BEFORE BUSINESS OPENING

OR DURING ANY PERIOD WHEN ACTIVITY HAS BEEN DETECTED FOR A TIME OF LONGER THAN 15

MINUTES.

18. WHERE THERE IS NO EMERGENCY GENERATOR/ LIFE SAFETY DISTRIBUTION BRANCH AVAILABLE, PROVIDE INTEGRAL BATTERY PACKS, RATED FOR A MINIMUM OF 90 MINUTES, FOR FIXTURES

SHOWN WITH SOLID SHADING AND/OR WITH "E" AFTER FIXTURE TAG, AND FOR ALL EXIT LIGHTS, OR UNLESS NOTED OTHERWISE.

19. ALL LIGHTING HAS BEEN DESIGNED IN COMPLIANCE WITH SECTION 405 OF THE FLORIDA ENERGY CONSERVATION CODE FOR LIGHTING POWER DENSITY, AUTOMATIC LIGHTING CONTROLS AND ALL

ADDITIONAL REQUIREMENTS.

20. PROVIDE AS PART OF BID PRICE FOR THE SERVICES OF AN INDEPENDENT COMMISSIONING AGENT

FOR THE LIGHTING SYSTEM FUNCTIONAL TESTING REQUIRED BY THE ENERGY CONSERVATION

CODE, INCLUDING ALL REQUIRED REPORTS. WHERE OCCUPANCY SENSORS, TIME SWITCHES,

PROGRAMMABLE SCHEDULED LIGHTING CONTROLS, PHOTOSENSORS AND DAYLIGHTING CONTROLS

ARE INSTALLED, THE SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL HARDWARE AND

SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDITION TO

ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS.

CONDUCT THE FUNCTIONAL TESTS IN ACCORDANCE WITH THE ENERGY CONSERVATION CODE.

PROVIDE COMMISSIONING REPORT TO ENGINEER NOT LATER THAN 60 DAYS FROM THE DATE OF

RECEIPT OF THE CERTIFICATE OF OCCUPANCY. DOCUMENTS CERTIFYING THAT THE INSTALLED

LIGHTING CONTROLS MEET DOCUMENTED PERFORMANCE CRITERIA OF THE ENERGY

CONSERVATION CODE ARE TO BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS FROM THE

DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.

MISCELLANEOUS CIRCUIT INSTALLATION REQUIREMENTS:

1. PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER

AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE IS

TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.

2. PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS ARE TO BE

PROVIDED AS SHOWN ON FIRE SMOKE DAMPER DETAIL ON THE DETAILS SHEET.

3. COORDINATE RECEPTACLE LOCATIONS WITH TECHNOLOGY DRAWINGS OR OWNER'S VENDOR

DRAWINGS SO THAT A 120V 20A 5-20R RECEPTACLE IS LOCATED ADJACENT TO EACH VOICE/DATA OUTLET AND TV OUTLET INDICATED ON PLANS. RECEPTACLE IS TO BE CONNECTED TO NEAREST

120V RECEPTACLE CIRCUIT, UNLESS OTHERWISE NOTED ON PLANS.

FIRE ALARM SYSTEM NOTES

1. ALL FIRE ALARM EQUIPMENT IS TO BE NEW, UL LISTED FOR FIRE SERVICE, AND SHALL BE

COMPATIBLE WITH THE SYSTEM BEING USED.

2. ALL WIRING AND CONDUIT IS TO CONFORM TO NEC ARTICLE 760. WIRING SHALL BE UL LISTED, MINIMUM 300V TYPE FPLP PLENUM RATED SOLID COPPER OR STRANDED COPPER WITH MAXIMUM 19

STRANDS.

3. LOW VOLTAGE CONDUCTORS: PROVIDE CONDUCTORS IN ACCORDANCE WITH NFPA 70 AND NFPA 72, AND AS RECOMMENDED BY THE FIRE ALARM SYSTEM MANUFACTURER. CONDUCTORS SHALL BE

COPPER, MINIMUM NO. 14 AWG, TWISTED SHIELDED PAIR.

4. SURVIVABILITY: A 2-HOUR RATED CABLE ASSEMBLY SHALL BE PROVIDED FOR NOTIFICATION

APPLIANCE CIRCUITS AND ANY OTHER CIRCUITS NECESSARY FOR THE OPERATION OF THE

NOTIFICATION APPLIANCE CIRCUITS FROM THE POINT AT WHICH THEY EXIT THE CONTROL UNIT

UNTIL THE POINT THAT THEY ENTER THE NOTIFICATION ZONE THAT THEY SERVE.

5. MANUAL PULL STATIONS ARE TO BE INSTALLED AT 42" TO BOTTOM OF DEVICE AND NO HIGHER THAN

48" TO HANDLE ABOVE FINISHED FLOOR.

6. PROVIDE MINIMUM 3/4" CONDUIT AND WIRING BETWEEN EACH FIRE ALARM DEVICE AND FROM LAST

DEVICE TO FACP UNLESS OTHERWISE NOTED.

7. PROVIDE DUCT DETECTOR (AND FIRE ALARM RELAY WHERE APPLICABLE) CONNECTED TO FIRE ALARM SYSTEM, WITHIN 5' OF ALL DUCT PENETRATIONS THROUGH FIRE/SMOKE WALLS, WHETHER

INDICATED ON ELECTRICAL OR MECHANICAL PLANS OR NOT.

8. FIRE ALARM CONTROL PANEL IS TO BE PROVIDED WITH DEDICATED 120V CIRCUIT WITH EQUIPMENT

GROUND CONNECTION PER MANUFACTURER'S RECOMMENDATIONS AND ARTICLE 760 OF THE NEC.

PROVIDE MINIMUM #12 AWG FOR GROUND CONNECTION. NOTE: PANEL NEUTRAL OR CONDUIT

GROUND IS NOT ACCEPTABLE. 120V CIRCUIT SHALL BE FROM EMERGENCY/LIFE SAFETY BRANCH

WHERE AVAILABLE.

9. SECONDARY BACK-UP POWER SHALL BE PROVIDED BY INTEGRAL BATTERIES WITHIN THE FIRE

ALARM CONTROL PANEL TO SUPPLY POWER TO THE SYSTEM UNDER QUIESCENT LOAD FOR A

MINIMUM OF 24 HOURS, AND THEN BE CAPABLE OF AN ADDITIONAL 15 MINUTES (5 MINUTES FOR NON

VOICE SYSTEMS) ALARM OPERATION AT MAXIMUM CONNECTED LOAD.

10. ALL FIRE ALARM POWER CIRCUITS SHALL HAVE A DEDICATED 120V 20A BREAKER THAT SHALL BE RED IN COLOR AND MECHANICALLY PROTECTED (LOCKABLE IN THE "ON" POSITION), MARKED AS

"FIRE ALARM CIRCUIT".

11. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ANY TAMPER SWITCH ACTIVATION. FAILURE

OR REMOVAL OF ANY DETECTION OR MANUAL DEVICE SHALL ACTIVATE A TROUBLE SIGNAL.

12. A CERTIFICATION OF COMPLETION AND UL LISTING SHALL BE ISSUED AND INSTALLED ON THE FIRE

ALARM CONTROL PANEL. SUBMIT NFPA RECORD OF COMPLETION FORM ALONG WITH SMOKE

DETECTOR SENSITIVITY REPORT FOR ALL DETECTORS WITHIN THE PROJECT AREA TO ENGINEER

AND MAKE AVAILABLE AT FINAL INSPECTION.

13. MINIMUM CANDELA RATING OF STROBES IS 75; "110" ADJACENT TO DEVICE INDICATES 110 CANDELA RATING. PROVIDE SYNCHRONIZATION OF STROBES IN ALL ADJACENT AREAS WHERE STROBES ARE

VISIBLE TO EACH OTHER.

14. ALL STROBES SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM.

15. ALL STROBES SHALL BE INSTALLED PER ADA MOUNTING HEIGHT REQUIREMENTS. WALL MOUNTED

STROBES SHALL BE INSTALLED SO THAT THE BOTTOM OF THE STROBE LENS IS 80" AFF.

16. STROBES SHALL BE INSTALLED WITHIN 15' OF THE ENDS OF ALL CORRIDORS.

17. FIRE ALARM DEVICES INSTALLED OUTSIDE OR IN AREAS OPEN TO THE EXTERIOR SHALL BE

WEATHERPROOF DEVICES IN APPROVED BACKBOXES.

18. SMOKE DETECTORS SHALL BE PHOTO-ELECTRIC ADDRESSABLE TYPE, UNLESS SPECIFICALLY

NOTED OTHERWISE.

19. SMOKE DETECTORS ARE TO BE INSTALLED PER NFPA 72. WALL MOUNTED SMOKE DETECTORS

SHALL BE MOUNTED 4"-12" BELOW THE CEILING AND AWAY FROM CORNERS.

20. SMOKE DETECTORS LOCATED IN ELEVATOR LOBBIES, ELEVATOR HOISTWAYS AND ELEVATOR

MACHINE ROOMS SHALL INITIATE ELEVATOR RECALL, ACTIVATE ELEVATOR WARNING LIGHTS AND CAUSE SEPARATE AND DISTINCT VISIBLE ANNUNCIATION AT THE FIRE ALARM CONTROL PANEL AND

FIRE ALARM ANNUNCIATORS.

21. DUCT DETECTORS SHALL BE PHOTO-ELECTRIC ADDRESSABLE TYPE, AND RATED FOR VELOCITIES

UP TO 5000 FT/MIN.

22. HEAT DETECTORS SHALL BE ADDRESSABLE, FIXED TYPE @ 135 DEG F, UNLESS OTHERWISE NOTED.

23. FOR PROJECTS WITH AN ELEVATOR, THE ELEVATOR CONTROL PANEL SHALL HAVE TWO SIGNALS

FROM THE FIRE ALARM CONTROL PANEL/ ASSOCIATED SMOKE DETECTORS - ONE FROM THE

"DESIGNATED FLOOR" SMOKE DETECTOR AND ANOTHER COMBINED SIGNAL FROM THE SMOKE

DETECTORS AT THE OTHER LOBBY LANDINGS AND IN THE ELEVATOR EQUIPMENT ROOM.

24. ACTIVATION OF ANY SMOKE DETECTOR IN THE ELEVATOR LOBBY OF THE DESIGNATED PRIMARY

RECALL LEVEL OR ELEVATOR MACHINE ROOM SHALL ACTIVATE ALTERNATE LEVEL RECALL.

25. PRIOR TO INSTALLATION OF ELEVATOR HOISTWAY HEAT DETECTORS, VERIFY WITH LOCAL

AUTHORITY HAVING JURISDICTION IF THEY ARE REQUIRED.

26. HEAT DETECTORS SHALL BE LOCATED WITHIN 24" OF SPRINKLER HEADS LOCATED IN THE ELEVATOR

MACHINE ROOM AND ALL HOISTWAY SPRINKLER HEADS LOCATED 24" ABOVE THE ELEVATOR PIT

FLOOR. THESE HEAT DETECTORS SHALL HAVE BOTH A LOWER TEMPERATURE RATING AND HIGHER

SENSITIVITY THAN THE SPRINKLER HEADS. HEAT DETECTORS SHALL OPEN THE MAIN

DISCONNECT/POWER SUPPLY TO THE ELEVATOR CONTROLLER. CONTROL CIRCUITS TO SHUT OFF

ELEVATOR POWER SHALL BE MONITORED BY THE FIRE ALARM CONTROL PANEL. CONTROL MODULE

SHALL BE WITHIN 3 FEET OF THE ELEVATOR CONTROLLER.

27. WHERE THERE IS A GENERATOR ON THE PROJECT, PROVIDE RELAYS AS REQUIRED FOR THE FIRE

ALARM SYSTEM TO MONITOR THE FOLLOWING THREE CONDITIONS: GENERATOR RUNNING;

GENERATOR FAULT; GENERATOR SWITCH NOT IN AUTO.

28. WHERE THERE IS A FIRE PUMP ON THE PROJECT, PROVIDE RELAYS AS REQUIRED FOR THE FIRE ALARM SYSTEM TO MONITOR THE FOLLOWING THREE CONDITIONS: FIRE PUMP RUNNING; FIRE PUMP

LOSS OF POWER; FIRE PUMP POWER PHASE REVERSAL.

29. PROVIDE AN ADDRESSABLE FIRE ALARM SYSTEM PER NFPA AND ALL STATE AND LOCAL CODE

REQUIREMENTS. COMPLY WITH NFPA 72 AND ADA REQUIREMENTS.

30. FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF AN HVAC DIFFUSER (SUPPLY OR RETURN), IN DIRECT AIR FLOW PATH, OR WITHIN 24"

OF A SPRINKLER HEAD UNLESS NOTED OTHERWISE. SMOKE DETECTORS FOR DOOR RELEASE

SHALL BE LOCATED ON THE CENTERLINE OF THE DOOR AND A MAXIMUM OF FIVE FEET FROM THE

DOOR. THE MINIMUM DISTANCE FROM THE DOOR SHALL BE THE DEPTH OF THE WALL SECTION

ABOVE THE DOOR, BUT NOT LESS THAN 12".

31. PROVIDE LABELS FOR REMOTE ALARM INDICATORS FOR DUCT MOUNTED SMOKE DETECTORS (I.E., AHU-1 SUPPLY, AHU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT DETECTORS SHOULD BE

LOCATED WITHIN 6 TO 10 EQUIVALENT DIAMETERS OF STRAIGHT, UNINTERRUPTED DUCTWORK.

DUCT DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD BE LOCATED BETWEEN THE LAST INLET OR

OUTLET UPSTREAM OF THE DAMPER AND THE FIRE INLET OR OUTLET DOWNSTREAM OF THE

DAMPER, AND WITHIN FIVE FEET OF THE FIRE/SMOKE WALL.

32. EQUIPMENT SHUT DOWN FIRE ALARM RELAYS SHALL BE LOCATED WITHIN THREE (3) FEET OF THE EQUIPMENT CONTROLS AND THE WIRING TO THE RELAY SHALL BE MONITORED BY THE FIRE ALARM

SYSTEM.

33. ALL FIRE ALARM CABLE SHALL BE INSTALLED IN CONDUIT; NO FIRE ALARM CONDUIT SHALL BE

INSTALLED UNDER SLAB. PROVIDE MANUFACTURED RED CONDUIT UNLESS OTHERWISE NOTED.

34. MINIMIZE EXPOSURE OF DETECTORS TO DIRT AND DUST FROM CONSTRUCTION. PROVIDE PLASTIC

COVERS DURING CONSTRUCTION.

35. STATE CERTIFIED AND LICENSED FIRE ALARM CONTRACTOR SHALL PREPARE AND SUBMIT SIGNED

AND SEALED DRAWINGS FOR THE LOCAL AUTHORITY HAVING JURISDICTION/ FIRE MARSHALL.

36. ALL NOTIFICATION DEVICES SHALL BE RED.

37. FIRE ALARM CIRCUIT CLASS SHALL MATCH THAT OF EXISTING SYSTEM.

38. NOTIFICATION DEVICES SHALL BE ADDRESSABLE ELECTRIC-VIBRATING-POLARIZED HORNS, SELECTABLE FOR HIGH OR LOW dBA OUTPUT. THEY SHALL HAVE A SOUND PRESSURE LEVEL OF 90dBA MEASURED 10 FEET FROM HORN, USING CODED SIGNAL PER NFPA 72.

39. FIRE ALARM CONTRACTOR/VENDOR SHALL PREPARE FLORIDA LICENSE P.E. WORKING DRAWINGS

INCORPORATING THE FIRE ALARM CRITERIA DESIGN AND CONFIRMING TO AHJ REQUIREMENTS.

CONTRACTOR SHALL PROVIDE ALL MATERIAL REQUIRED PER AHJ AND DESIGN CRITERIA FOR A

FULLY FUNCTIONING AND PERMITTABLE FIRE ALARM SYSTEM. SUBMIT TO DESIGN PROFESSIONAL AS A SHOP DRAWING FOR REVIEW. SUBMIT COMPLETE SIGNED & SEALED DRAWINGS TO PERMITTING AGENCY AND FOR CERTIFICATE OF OCCUPANCY. COMPLETED FIRE ALARM CERTIFICATION SHALL BE

PROVIDED TO OWNER AT COMPLETION OF CONSTRUCTION.

40. FIRE ALARM DESIGN IS IN ACCORDANCE WITH FLORIDA STATUTES CHAPTER 61G15-32. WHERE A

FIRE ALARM RISER IS INDICATED, IT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO

REPRESENT A COMPLETE WIRING AND DEVICE DISPLAY. ALL WIRING AND DEVICES SHALL BE IN

ACCORDANCE WITH SELECTED VENDOR'S POINT-BY-POINT WIRING DIAGRAM. REFER TO FLOOR

PLAN FOR DESIGN INTENT AND PROPOSED QUANTITY OF FIRE ALARM SYSTEM COMPONENTS.

GENERAL REQUIREMENTS

1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO

THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS

AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL

DIVISIONS AS A WHOLE.

2. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF

CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE

EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL AND STRUCTURAL CONTRACT

DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS AND WORK OF ALL OTHER

DIVISIONS/TRADES.

3. THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY

NOTED OTHERWISE

4. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL

TESTING AGENCY

5. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE

CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND

WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER.

6. CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR

THE DURATION OF THIS PROJECT

7. GUARANTEE ALL MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF

ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.

8. INCLUDE ALL COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND

TEMPORARY POWER IN THE BID PRICE, UNLESS NOTED OTHERWISE.

9. IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH ALL APPLICABLE RULES, REGULATIONS

AND GUIDELINES CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST

ENVIRONMENTAL EXPOSURE OR POLLUTION. PROVIDE DOCUMENTATION OF SAID COMPLIANCE.

10. PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT

OF THE ELECTRICAL SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR

COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO, RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. ALL SUBMITTALS ARE TO BE REVIEWED AND APPROVED BY THE CONTRACTOR

FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE

ARCHITECT/ENGINEER. ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY

ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN DIVISION 1.

11. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS

ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE CONTRACTOR SHALL MAKE ALL

CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND

OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.