About this file
This document is an extensive set of electrical engineering drawings and specifications for the City of DeLand's Fire Station 83 Addition project in Volusia County, Florida. The electrical drawings (sheets E-001 through E-601) provide comprehensive technical details for the 797 square foot building addition, including electrical demolition plans, lighting and power systems plans, one-line electrical diagrams, and detailed electrical symbols and notes. The drawings cover the complete electrical infrastructure requirements, including receptacle layouts, lighting fixtures, fire alarm systems, and electrical panel schedules for the renovated fire station.
The electrical plans specify a complex electrical system modification involving an existing 450kW service with 208V/120V three-phase power distribution. The drawings outline specific requirements for branch circuits, panelboards, grounding systems, and device mounting heights, with particular attention to fire alarm system integration, emergency power provisions, and compliance with the National Electrical Code (NEC) and Florida Building Code. The electrical design incorporates modern features such as LED lighting, occupancy sensors, emergency lighting, and surge protective devices, ensuring the fire station meets current safety and energy efficiency standards. The project involves reconfiguring existing electrical infrastructure while maintaining the facility's operational status, with careful coordination required between electrical, architectural, and other building system components.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| RCA.pdf | ||
| B2505Tabulation.pdf | ||
| B2505Tabulation.pdf | ||
| B2505ADD5.pdf | ||
| B2505ADD5.pdf | ||
| B2505ADD5.pdf | ||
| B2505ADD5.pdf | ||
| B2505ADD4.pdf | ||
| B2505ADD4.pdf | ||
| B2505ADD4.pdf | ||
| B2505ADD4.pdf | ||
| B2505ADD3.pdf | ||
| B2505ADD3.pdf | ||
| B2505ADD3.pdf | ||
| B2505ADD3.pdf | ||
| B2505ADD2.pdf | ||
| B2505ADD2Attachment.pdf | ||
| B2505ADD2Attachment.pdf | ||
| B2505ADD2.pdf | ||
| B2505ADD2Attachment.pdf | ||
| B2505ADD2.pdf | ||
| B2505ADD2Attachment.pdf | ||
| B2505ADD2.pdf | ||
| B2505ADD1.pdf | ||
| B2505ADD1.pdf | ||
| B2505ADD1.pdf | ||
| B2505ADD1.pdf | ||
| B2505Plans.pdf | ||
| B2505Plans.pdf | ||
| B2505Plans.pdf | ||
| B2505Final.pdf | ||
| B2505Final.pdf | ||
| B2505Final.pdf | ||
| B2505Final.pdf |
Show all 34
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
H
H
FS
FS
TS
F
RT
R
F
G
CII
CI
A
ELECTRICAL SYMBOL LEGEND
DN THRU-ROOF CONDUCTOR
COUNTERPOISE CONDUCTOR
BONDING CONDUCTOR
GROUND TERMINAL
AIR TERMINAL; PROVIDE PARAPET TYPE BASE WHERE MOUNTED ON PARAPET;
PROVIDE FLAT BASE FOR MECHANICAL EQUIPMENT OR ROOF PERIMETER WITH NO
PARAPET; PROVIDE BLUNT TIP WHERE MOUNTED ON INTERIOR OF ROOF, UNLESS
OTHERWISE NOTED ON LIGHTNING PROTECTION PLANS
BONDING PLATE
TEE SPLICE
CLASS II MAIN CONDUCTOR CABLE
CLASS I MAIN CONDUCTOR CABLE
FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED
FIRE ALARM TERMINAL CABINET
FIRE ALARM CONTROL PANELFACP
HEAT DETECTOR 135°F FIXED TEMPERATURE, UNLESS OTHERWISE NOTED,
CEILING MOUNTED
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
SPRINKLER WATERFLOW SWITCH CONNECTION
P
SPRINKLER TAMPER SWITCH CONNECTION
FIREMAN'S PHONE JACK
STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE NOTED
CD = CANDELA RATING
COMBINATION SPEAKER/STROBE, CEILING MOUNTED, 75CD UNLESS OTHERWISE
NOTED
HORN ONLY, WALL MOUNTED
DUCT SMOKE DETECTOR REMOTE TEST SWITCH WITH INDICATING LAMP, WALL
MOUNTED AT 48" AFF, UNLESS OTHERWISE NOTED
SUPERVISED ADDRESSABLE FIRE ALARM CONTROL RELAY
S = SUPPLY
R = RETURN
DUCT SMOKE DETECTOR
E = ELEVATOR WITH RECALL CONTACTS
I = IONIZATION
CEILING SMOKE DETECTOR, PHOTOELECTRIC TYPE UNLESS OTHERWISE
NOTED
MANUAL PULL STATION
EMERGENCY TWIN-HEAD LIGHT WITH INTEGRAL BATTERY PACK, WALL MOUNTED
TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF TRACK HEADS)
EXTERIOR POLE-MOUNTED AREA LIGHT FIXTURE, ARMS AS INDICATED ON DRAWINGS
EXIT LIGHT, LED, WALL MOUNTED
EXIT LIGHT, LED, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED;
SHADED QUADRANT INDICATES FACE(S) OF FIXTURE
LED, FLUORESCENT, HID - CEILING WALLWASHER, ACCENT LIGHT, LANDSCAPING TREE
ACCENT LIGHT, FACADE LIGHT
LED, FLUORESCENT, HID, RECESSED, PENDANT OR SURFACE CEILING
LED OR FLUORESCENT FIXTURE RECESSED, PENDANT OR SURFACE CEILING
DIAGONAL HALF SHADING INDICATE FIXTURE CONNECTED TO EMERGENCY CIRCUIT OR
PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E" AFTER FIXTURE TYPE TAG
INDICATES INTEGRAL BATTERY PACK UNLESS OTHERWISE NOTED ON LIGHT FIXTURE
SCHEDULE (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)
LED OR FLUORESCENT FIXTURE, RECESSED, PENDANT OR SURFACE CEILING
LED OR FLUORESCENT STRIP FIXTURE
LED OR FLUORESCENT FIXTURE, WALL MOUNTED
FIXTURE TYPE
LOWER CASE LETTER INDICATES CONTROLLING SWITCH
a
CIRCUIT NUMBER
LIGHTING
LIGHTNING PROTECTION SYSTEM
FIRE ALARM / DETECTION SYSTEM
F
XXCD CD = CANDELA RATING
COMBINATION SPEAKER/STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE
NOTED
CD = CANDELA RATING
STROBE, CEILING MOUNTED, 75 CD UNLESS OTHERWISE NOTED
SS SPEAKER ONLY, CEILING MOUNTED
PS PRESSURE SWITCH CONNECTION
XXCD
LED, FLUORESCENT, HID, WALL MOUNTED
LINEAR FLUORESCENT, LED, RECESSED, PENDANT OR SURFACE CEILING
ZX-X
LIGHTING CONTROL ZONE NUMBER
EXTERIOR PEDESTRIAN SIDEWALK BOLLARD OR POST-TOP LIGHT FIXTURE
B R
BEAM SMOKE DETECTOR
BT OR T = BEAM DETECTOR TRANSMITTER
BR OR R = BEAM DETECTOR RECEIVER
F
XXCD
SPEAKER ONLY, WALL MOUNTEDSS
FATC
FAA
VOICE EVACUATION PANELEVAC
MASS NOTIFICATION SYSTEM PANELMNS
FOUR-WAY SPLICE
VOICE AND DATA RACEWAY SYSTEM
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
SINGLE-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR VOICE/DATA OUTLET
WITH 1" CONDUIT STUBBED UP AND INTO NEAREST ACCESSIBLE CEILING UNLESS
OTHERWISE NOTED; PROVIDE WITH NYLON PULL STRING & SMOOTH BUSHING
SINGLE-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR TELEPHONE WALL
OUTLET WITH 1" CONDUIT STUBBED UP AND INTO NEAREST ACCESSIBLE CEILING UNLESS
OTHERWISE NOTED; PROVIDE WITH NYLON PULL STRING & SMOOTH BUSHING
C = ABOVE COUNTER
W = WALL MOUNTED AT 52" AFF FOR HOUSE PHONE
W, ADA = WALL MOUNTED AT 44" AFF FOR ADA ACCESSIBLE PAY PHONE
ELV = WALL MOUNTED @ 52" AFF FOR TELEPHONE IN ELEVATOR
MACHINE ROOM
WIRELESS ACCESS POINT OUTLET, CEILING MOUNTED; ACTUAL QUANTITY AND
LOCATIONS SHALL BE BASED ON SIGNAL SURVEY BY OWNER'S WLAN VENDOR
WAP
MULTI-SERVICE FLOOR BOX WITH RECEPTACLE AND TECHNOLOGY DEVICES (REFER
TO OWNER'S VENDOR DRAWINGS FOR DEVICES); PROVIDE RACEWAY(S) AS
INDICATED ON FLOOR PLANS
MULTI-SERVICE FLOOR BOX WITH FURNITURE FEED CONNECTION; PROVIDE RACEWAY(S)
AS INDICATED ON FLOOR PLANS
2-GANG 2-1/8"D ELECTRICAL BOX WITH BLANK COVER FOR WALL MOUNTED FURNITURE
FEED DATA CONNECTION; PROVIDE RACEWAY(S) AS INDICATED ON FLOOR PLANS
P
MULTI-SERVICE POKE-THRU WITH RECEPTACLES AND TECHNOLOGY DEVICES OR
FURNITURE FEED CONNECTION; REFER TO POKE-THRU DETAILS AND FLOOR PLANS FOR
RACEWAY INFORMATION
3/4"THICK X 8' HIGH A/C PLYWOOD BACKBOARD MOUNTED 6" AFF FROM BOTTOM,
PAINTED WITH GRAY FIRE-RETARDANT PAINT, WIDTH AS INDICATED ON FLOOR PLAN
CABLE TRAY FOR HORIZONTAL LOW VOLTAGE CABLE, 12"W X 4" HIGH UNLESS
OTHERWISE NOTED; LADDER TYPE IN IDF/MDF/IT ROOMS, BASKET/MESH TYPE IN
OTHER AREAS, UNLESS OTHERWISE NOTED
2-POST DATA RACK
4-POST DATA RACK
AUDIO/VIDEO RACEWAY SYSTEM
TV
TELEVISION SIGNAL WALL OUTLET, MOUNTED ADJACENT TO DUPLEX RECEPTACLE
IDENTIFIED WITH "TV" ADJACENT TO DEVICE; REFER TO ARCHITECTURAL ELEVATIONS FOR
MOUNTING HEIGHT
S CEILING MOUNTED SPEAKER
S WALL MOUNTED SPEAKER
X = ZONE TO BE CONTROLLEDX
VC
WALL-MOUNTED VOLUME CONTROL; PROVIDE 3/4" C. STUBBED UP ABOVE CEILING AND
SINGLE STANDARD ELECTRICAL BOX AT 48" AFF
MC WALL-MOUNTED MASTER VOLUME CONTROL; PROVIDE 3/4" C. STUBBED UP ABOVE
CEILING AND SINGLE STANDARD ELECTRICAL BOX AT 48" AFFX
X = ZONE TO BE CONTROLLED
RCA WALL-MOUNTED DUAL RCA JACKS FOR MP3 CONNECTION
AV AUDIO/VISUAL CABINET OR RACK
POWER POLE WITH POWER & DATA FURNITURE FEED POWER CONNECTIONS; REFER
TO FLOOR PLANS FOR RACEWAY INFORMATION
PP
W
IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
IES ILLUMINATING ENGINEERING SOCIETY
IMC INTERMEDIATE METAL CONDUIT
IN INCHES
IPCEA INSULATED POWER CABLE ENGINEERS ASSOCIATION
IT INSTANTANEOUS TRIP
JB OR J-BOX JUNCTION BOX
KCMIL ONE THOUSAND CIRCULAR MILS
KV KILOVOLT
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOURS
LBS POUNDS
LED LIGHT EMITTING DIODE
LP LIGHTNING PROTECTION
LT LIGHT
LTG LIGHTING
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND
LSIA LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM
LSI LONG TIME, SHORT TIME, INSTANTANEOUS
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN SERVICE DISTRIBUTION PANEL
MIC MICROPHONE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SERVICE SWITCHBOARD
MTD MOUNTED
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MUX MULTIPLEX (TRANSPONDER) PANEL
MVA MEGA VOLT AMPS
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NF NON-FUSED
NL NON-LINEAR
NO NORMALLY OPEN OR NUMBER
OL OVERLOAD
OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
P POLE
PB PULLBOX
PF POWER FACTOR
PIV POST INDICATOR VALVE
PNL PANEL
PR PAIR
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYLCHLORIDE
PWR POWER
REC, RECEPT RECEPTACLE
REF REFRIGERATOR
RGS, GRC RIGID GALVANIZED STEEL CONDUIT
RLA RUNNING LOAD AMPERES
RMS ROOT-MEAN-SQUARE
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SCA SHORT CIRCUIT AMPERES
SD SMOKE DETECTOR
SEC SECONDARY
S/N SOLID NEUTRAL
SPD SURGE PROTECTIVE DEVICE
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SS STAINLESS STEEL
SST SOLID STATE TRIP
STD SHORT TIME TRIP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TVEC TELEVISION EQUIPMENT CABINET
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UL UNDERWRITERS LABORATORIES
UTIL UTILITY
V VOLT
VA VOLTAMPERE
VAR VOLT AMPERE REACTIVE
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
XFR TRANSFER
ABBREVIATIONS (CONT.)
NFPA / LEGACY
F
S
S
BR
S
H
DH
XXCD
F H
XXCD
C
S C
S
VS
WS
PS
FACP
FATC
FAA
EVAC
MNS
R
WALL MOUNTED DATA RACKMASS NOTIFICATION SYSTEM PANELDACTDACT
A/C AIR CONDITIONING
AC ALTERNATING CURRENT
ABV CLG ABOVE CEILING
ADA AMERICANS WITH DISABILITIES ACT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AMP AMPERE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASA AMERICAN STANDARDS ASSOCIATION
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BIL BASIC IMPULSE LEVEL
BAS BUILDING AUTOMATION SYSTEM
BMS BUILDING MANAGEMENT SYSTEM
BRKR OR BKR BREAKER
C CONDUIT OR RACEWAY
CAB CABINET
CKT CIRCUIT
CB CIRCUIT BREAKER
CBM CERTIFIED BALLAST MANUFACTURERS
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CLEC CLOCK EQUIPMENT CABINET
CLG CEILING
CO CONDUIT OR RACEWAY ONLY
COAX COAXIAL CABLE
COND CONDUCTOR
CONN CONNECTION
CPU CENTRAL PROCESSING UNIT
CRT CATHODE RAY TERMINAL (VIDEO DISPLAY TERMINAL)
CT CURRENT TRANSFORMER
CU COPPER
CW COLD WATER
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DF DEMAND FACTOR
DISC DISCONNECT
DISC SW DISCONNECT SWITCH
DO DRAW OUT
DN DOWN
DPST DOUBLE POLE SINGLE THROW
EDH ELECTRIC DUCT HEATER
EMT ELECTRIC METALLIC TUBING
EO ELECTRICALLY OPERATED
EOL END OF LINE
EOR ENGINEER OF RECORD
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FATC FIRE ALARM TERMINAL CABINET
FBC FLORIDA BUILDING CODE
FCU FAN COIL UNIT
FLA FULL LOAD AMPERES
FM FACTORY MUTUAL
FPU FAN POWERED UNIT
FT FEET
GF GROUND FAULT
GFA GROUND FAULT ALARM
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFR GROUND FAULT RELAY
GND, G GROUND
HP HORSEPOWER
HOA HAND-OFF-AUTOMATIC
HORIZ HORIZONTAL
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
ICU INTENSIVE CARE UNIT
IECC INTERNATIONAL ENERGY CONSERVATION CODE
ABBREVIATIONS
DN
DN
FLAT ROOF MOUNTED OR MECHANICAL
F
P
PARAPET MOUNTED AIR TERMINAL
DOWN CONDUCTOR
PIPE CLAMP FOR PLUMBING VENT THRU ROOF.
DN
UP
SYMBOL DESCRIPTION
DDC
VFD
AUTOMATIC TRANSFER SWITCH
TRANSFORMERT
DIRECT DIGITAL CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR CONNECTION
NEW (HEAVY, SOLID LINE)
EXISTING TO REMAIN (LIGHT, SOLID LINE)
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
FLEXIBLE CONDUIT
CONDUIT CONTINUED
CONDUIT STUBBED OUT OR UP
CONDUIT TURNING DOWN
CONDUIT TURNING UP
GROUND OR GROUND ROD AS NOTED
CONDUIT EXPOSED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR
CONDUIT CONCEALED ABOVE CEILING OR IN WALL
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED
MULTI-SERVICE RACEWAY WITH 5-20R RECEPTACLES, 18" O.C. UNLESS
OTHERWISE NOTED
SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED
NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE
CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);
TYPICAL FOR ANY DEVICE IN LEGEND
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVER MOUNTED ABOVE COUNTER
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
GFCI RECEPTACLE; "WP" INDICATES CAST METAL "IN-USE" WEATHERPROOF COVER,
WEATHER-RESISTANT LISTED
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES
(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW
VOLTAGE REQUIREMENTS)
FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE
M
F
LV
OS
a
30AR
20AF
PEDESTAL MOUNTED DUPLEX RECEPTACLE
DUPLEX RECEPTACLE
DIMMER SWITCH, LINE VOLTAGE
MOTOR RATED SWITCH
FAN SWITCH
LOW VOLTAGE SWITCH
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
FOUR-WAY SWITCH
THREE-WAY SWITCH
NF
30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED
SINGLE POLE SWITCH (SUBSCRIPT INDICATES ITEM CONTROLLED)
NF = NON-FUSED
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE
NOTED
30/3
3R
MCP
AMPERE
RATING
# OF POLES
NEMA STARTER SIZE
SINGLE RECEPTACLE
FUSED DISCONNECT
D
BASIC MATERIALS
S
S
S
S
S
S
S
S
MOTORIZED DAMPER CONNECTIONMD
K SINGLE POLE KEY SWITCHS
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
OSab WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH, DUAL RELAYS
DL DAYLIGHT SENSOR CEILING MOUNTED
DL DAYLIGHT SENSOR WALL MOUNTED
RECEPTACLE CONTROLLED PER ASHRAE 90.1 (2010); PROVIDE POWER PACK FOR
RECEPTACLE CIRCUIT, TO BE CONTROLLED THROUGH LOCAL ROOM OCCUPANCY
SENSOR(S); PROVIDE DEVICE WITH BLUE DOT OR UNIVERSAL POWER SYMBOL
RECEPTACLE MOUNTED ADJACENT TO TV OUTLET, COORDINATE HEIGHT W/ ARCHITECT
FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE
DUPLEX RECEPTACLE WITH (2) USB PORTS
DOUBLE DUPLEX RECEPTACLE WITH DEDICATED CIRCUIT FOR AV RACK OR CART
D,OS WALL MOUNTED DUAL TECHNOLOGY DIMMING/OCCUPANCY SENSOR SWITCHS
LVO
LOW VOLTAGE OVERRIDE SWITCHS
VS WALL MOUNTED DUAL TECHNOLOGY VACANCY SENSOR SWITCHS
OS
C
TV
U
AV
HOSPITAL GRADE H
TAMPER RESISTANTTR
ISOLATED GROUND (ORANGE DEVICE) IG
WEATHERPROOFWP
OS
DEVICE ABBREVIATION TAGS:
DUPLEX RECEPTACLE, CEILING MOUNTED
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE, CEILING MOUNTED
J
FOUR-GANG FLOOR BOX4G
SIX-GANG FLOOR BOX6G
EIGHT-GANG FLOOR BOX8G
MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLES (QUAD) , VOICE/DATA/AV
DEVICES
GFCI RECEPTACLE MOUNTED ABOVE COUNTER
DUPLEX RECEPTACLE; EACH RECEPTACLE ON SEPARATE CIRCUIT (PROVIDE
BREAKER WITH 2-POLE COMMON TRIP HANDLE)
SPLIT-WIRED CONTROLLED DUPLEX RECEPTACLE
TWO GFCI DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
MULTI-SERVICE POWER & DATA FLOOR BOX WITH FURNITURE FEED CONNECTION
J JUNCTION BOX WALL MOUNTED
J JUNCTION BOX MOUNTED IN OR ABOVE CEILING OR IN STRUCTURE
J WALL MOUNTED FURNITURE FEED POWER CONNECTION
P
MULTI-SERVICE POKE-THRU WITH TWO INTEGRAL DUPLEX RECEPTACLES AND
VOICE/DATA/AV DEVICES (REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR
DRAWINGS FOR LOW VOLTAGE REQUIREMENTS), OR FURNITURE FEED CONNECTION;
REFER TO POKE-THRU DETAILS
PP
POWER POLE WITH POWER & DATA FURNITURE FEED POWER CONNECTIONS
POKE-THRU WITH 6" CORE DRILL6C
POKE-THRU WITH 8" CORE DRILL8C
PC PHOTOCELL, MOUNTED ON ROOF FACING NORTH
C CLOCK RECEPTACLE, WALL MOUNTED
GROUND BUS BAR, COPPERGND
CONDUIT SEAL-OFF FITTING
SPD SURGE PROTECTIVE DEVICE
ST
SHUNT-TRIP PUSHBUTTON; SEMI-FLUSH WALL MOUNTED UNLESS OTHERWISE NOTED;
NEMA 3R FOR EXTERIOR LOCATIONS
OVERHEAD DOOR PUSHBUTTON CONTROL STATION
PUSHBUTTON STATION
BAS BUILDING AUTOMATION SYSTEM CONTROL PANEL
LCP LIGHTING CONTROL PANEL
MANHOLEMH
SYMBOL DESCRIPTION
PULLBOXPB
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
3R
3R
AF = AMPERE RATING OF FUSE
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED
CONDUIT HOMERUN TO ELECTRICAL PANEL
EXISTING TO REMAIN ETR
RELOCATEDRL
PP POWER POLE WITH POWER & DATA OUTLETS
HANDHOLEHH
ATS
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL
EPO EMERGENCY POWER OFF SHUNT-TRIP PUSHBUTTON, RED MUSHROOM HEAD, CLEAR
LEXAN PROTECTIVE COVER
T DIGITAL TIMER SWITCH W/ 5 MIN. WARNING FLASHS
LVD
LOW VOLTAGE OVERRIDE SWITCH WITH DIMMINGS
VS VACANCY SENSOR CEILING MOUNTED
VS VACANCY SENSOR WALL MOUNTED
7370 Cabot Court, Suite 103 Melbourne, FL 32940 P 321.636.0274
©Copyright 2024
TLC No.:
www.tlc-engineers.com
COA 15
KUBO STUDIO
821 HERNDON AVENUE
#141126
ORLANDO, FL 32803
LLC NO. L20000333046
A R C H I T E C T U R E
F
E
D
C
B
A
F
E
D
C
B
A sh ee t t itl e:
sheet number:
IF THIS SHEET MEASURES LESS THAN 42" x 30", IT HAS BEEN REDUCED scale:
drawn by:
designed by:
project no.:
issue date:
professional license no.:
name:
pr oj ec t a dd re ss cl ie nt n am e:
pr oj ec t s ta tu s:
pr oj ec t n am e:
consultant:
client:
524103
/2
0/
:5 0:
P
M
N.T.S.
E-001
E
LE
C
TR
IC
A
L S
Y M
B O
LS
, L
E G
E N
D , A
N D
IN
D
E X
CLM
CLM
2023-P031
20 DECEMBER 2024
C
IT
Y O
F D
E
LA
N D
, F
LO
R
ID
A
E A
S T
T A
Y
LO
R R
D
D E
LA
N
D , F
L
C
IT
Y O
F D
E
LA
N D
, F
IR
E S
T A
T
IO
N
0%
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
Stephen B. Cotton, P.E.
60046
ELECTRICAL DRAWING INDEX
SHEET DESCRIPTION
E-001 ELECTRICAL SYMBOLS, LEGEND, AND INDEX
E-002 ELECTRICAL GENERAL NOTES
E-100 ELECTRICAL DEMOLITION PLAN
E-101 LIGHTING PLAN
E-102 POWER AND SYSTEMS PLAN
E-401 ELECTRICAL ONE-LINE DIAGRAM & SCHEDULES
E-601 ELECTRICAL DETAILS
ET101 TEMPORARY TRAILER POWER PLAN
N O
D
E S
C R
IP
T
IO
N
D A
T E
ELECTRICAL GENERAL NOTES
ELECTRICAL DEVICES OUTLET BOXES, JUNCTION BOXES
1. LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED OTHERWISE.
2. RECEPTACLES, VOICE/DATA OUTLETS AND WALL FURNITURE FEEDS SHALL BE MOUNTED 18 INCHES
ABOVE FINISHED FLOOR TO CENTER LINE OF DEVICE, UNLESS NOTED OTHERWISE. ABOVE COUNTER RECEPTACLES SHALL BE MOUNTED 6" ABOVE BACK SPLASH TO CENTERLINE OF DEVICE, UNLESS NOTED
OTHERWISE.
3. IT IS THE INTENT THAT ALL DEVICE OUTLET BOXES (POWER AND SYSTEMS) BE FLUSH MOUNTED IN WALLS, CEILINGS OR FLOORS, AND JUNCTION BOXES FLUSH MOUNTED IN WALLS, CEILINGS, OR FLOORS, OR CONCEALED ABOVE ACCESSIBLE CEILINGS, AND NOT SURFACE MOUNTED, UNLESS SPECIFICALLY NOTED ON THE CONTRACT DRAWINGS, OR UNLESS THE ARCHITECT/ENGINEER GRANTS WRITTEN PERMISSION.
4. ALL COMPONENTS OF THE ELECTRICAL SYSTEM (INCLUDE RACEWAYS, ELECTRICAL EQUIPMENT, OUTLET BOXES, JUNCTION BOXES, ETC.) LOCATED IN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE APPROVED FOR USE IN SAID LOCATION, AS DEFINED BY THE NEC, WHETHER INDICATED ON THE CONTRACT
DOCUMENTS OR NOT.
5. ALL DEVICES SHALL BE MOUNTED VERTICALLY, UNLESS NOTED OTHERWISE.
6. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.
7. WHERE DEVICES ARE SHOWN IN WALLS BACK-TO-BACK ON OPPOSITE SIDES, INSTALL SO THAT THEY ARE
SEPARATED BY AT LEAST 12".
8. RECEPTACLES OR JUNCTION BOXES FOR ELECTRIC WATER COOLERS AND VENDING MACHINES SHALL BE
LOCATED DIRECTLY BEHIND SAID APPLIANCE, CONCEALED FROM DIRECT VIEW. RECEPTACLES AND/OR HARD WIRED EQUIPMENT CONNECTIONS SHALL BE PROTECTED BY A READILY ACCESSIBLE GFCI FEED- THRU DEVICE LOCATED IMMEDIATELY ADJACENT TO THE APPLIANCE OR BE PROTECTED BY GFCI BREAKER IN THE PANELBOARD. ALL GFCI DEVICES MUST BE READILY ACCESSIBLE PER THE NEC.
9. ALL EXTERIOR RECEPTACLES OR RECEPTACLES LOCATED IN AREAS SUBJECT TO MOISTURE (PARKING GARAGE, WASHDOWN AREAS IN KITCHEN, ETC) SHALL BE GFCI TYPE. ALL EXTERIOR RECEPTACLES
SHALL WE PROVIDED WITH CAST METAL, IN-USE COVER UNLESS NOTED OTHERWISE.
10. ALL RECEPTACLES LOCATED IN KITCHENS, BATHROOMS, MECHANICAL ROOMS, JANITOR CLOSETS, ELEVATOR SHAFTS, ELEVATOR EQUIPMENT ROOMS, FOR ELEVATOR SUMP PUMP(S) OR INSTALLED
WITHIN 6' OF THE INSIDE FACE OF A SINK, SHALL BE GFCI TYPE OR GFCI PROTECTED.
11. ALL RECEPTACLES LOCATED IN CHILD-CARE FACILITIES, DWELLING UNITS, HOTEL/MOTEL GUEST ROOMS, PEDIATRIC CLINICS OR PEDIATRIC CAREA AREAS, AND OTHER AREAS AS REQUIRED BY NEC AND LOCAL
CODE REQUIREMENTS SHALL BE TAMPER RESISTANT.
12. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, THEY SHALL BE INSTALLED WITHOUT AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL
BE MET:
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED
WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE
WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE
INCHES PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE
SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH
BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
ELECTRICAL EQUIPMENT
1. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY
ARE TO BE INSTALLED. ALL COMPONENTS OF THE ELECTRICAL SYSTEM LOCATED OUTDOORS OR
INDOORS WHERE EXPOSED TO SIGNIFICANT MOISTURE SHALL BE WEATHERPROOF, NEMA 3R, AS A
MINIMUM, WHETHER INDICATED ON THE CONTRACT DRAWINGS OR NOT.
2. TERMINATION PROVISIONS FOR ALL ELECTRICAL EQUIPMENT (PANELBOARDS, SWITCHBOARD, TRANSFORMERS, DISCONNECT SWITCHES, MOTOR CONTROLLERS, AUTOMATIC TRANSFER SWITCHES, ENCLOSED CIRCUIT BREAKERS, BUSWAYS, ETC.) SHALL BE LISTED AND IDENTIFIED FOR USE WITH
MINIMUM 75 DEG. F CONDUCTORS IN ACCORDANCE WITH NEC.
3. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC.
4. THE ELECTRICAL DEDICATED EQUIPMENT SPACE EXTENDING FROM FLOOR TO 6' ABOVE ELECTRICAL
EQUIPMENT OR TO THE STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND
DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE CLEAR OF ALL PIPING, DUCTS,
ARCHITECTURAL APPURTENANCES AND OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL
INSTALLATION IN ACCORDANCE WITH NEC.
5. PROVIDE A REINFORCED CONCRETE PAD, SIZED 4" LARGER IN ALL DIRECTIONS THAN THE FOOTPRINT OF THE EQUIPMENT, AND 4" HIGH, FOR ALL FREESTANDING, FLOOR-MOUNTED ELECTRICAL EQUIPMENT.
PROVIDE VIBRATION ISOLATORS AND/OR ANCHORS PER MANUFACTURER'S INSTRUCTIONS.
6. PROVIDE HACR RATED CIRCUIT BREAKER FOR ALL HVAC EQUIPMENT.
7. ALL PANELBOARDS OR DISCONNECT SWITCHES LOCATED IN KITCHEN AREAS SHALL BE STAINLESS
STEEL (COVER AND DOOR WHERE PANEL IS FLUSH MOUNTED; PANEL BOX, COVER & DOOR WHERE
SURFACE MOUNTED).
8. PROVIDE SURGE PROTECTION DEVICE FOR ALL MAIN SERVICE EQUIPMENT, PANELBOARDS SERVING SENSITIVE ELECTRONIC EQUIPMENT (DATA RACKS) OR COMPUTERS, EMERGENCY SWITCHBOARDS AND PANELBOARDS, LIGHTING PANELS SERVING EXTERIOR LIGHTING, POWER CIRCUITS OR LOW VOLTAGE (FIRE ALARM, TELECOMMUNICATIONS) EXITING THE BUILDING. PROVIDE MINIMUM 30A/3P BREAKER IN BRANCH CIRCUIT PANELBOARDS AND 60A/3P IN DISTRIBUTION PANELBOARDS OR SWITCHBOARDS, UNLESS NOTED OTHERWISE, OR PER THE SPD MANUFACTURER'S RECOMMENDATIONS FOR SURGE
PROTECTION DEVICE.
9. PROVIDE ARC ENERGY REDUCING MAINTENANCE SWITCH FOR ANY BREAKER RATED (OR ABLE TO BE ADJUSTED TO) 1200A OR HIGHER UNLESS OTHER ARC ENERGY REDUCTION MEANS MEETING NEC 240.87
IS INDICATED ON DRAWINGS/SPECIFICATIONS OR OTHERWISE PROVIDED.
CONDUCTORS
1. ALL WIRE SHALL BE SIZED AS SHOWN ON THE DRAWINGS. IF NO WIRE SIZE IS SHOWN, THEN WIRE
SHALL BE #12 AWG.
2. BRANCH CIRCUITS SHALL BE INCREASED IN SIZE AS REQUIRED TO COMPENSATE FOR VOLTAGE DROP
FROM LENGTH OF CIRCUIT DUE TO FIELD ROUTING. FINAL INSTALLATION SHALL NOT EXCEED A MAXIMUM OF 3% VOLTAGE DROP FOR BRANCH CIRCUITS. REFER TO VOLTAGE DROP TABLE BELOW
FOR CONDUCTOR SIZES FOR BRANCH CIRCUITS AS FOLLOWS:
A. 120V, 20A CIRCUITS SHALL BE:
i. #12 FROM 0-70 FT
ii. #10 FROM 71-115FT
iii. #8 FROM 116-180FT
B. 277V, 20A CIRCUITS SHALL BE:
i. #12 FROM 0-140FT
ii. #10 FROM 141-220FT
iii. #8 FROM 221-350FT
ANYTHING LONGER THAN THE ABOVE SHALL BE SUBMITTED TO THE ENGINEER WITH CALCULATIONS
FOR APPROVAL.
3. ALL CONDUCTORS IN CABINETS MUST BE CAREFULLY FORMED AND HARNESSED SO THAT EACH
CONDUCTOR DROPS OFF DIRECTLY OPPOSITE TO TERMINAL.
4. ALL WIRE SIZES ARE BASED ON AMPACITIES FOR 60 DEG F TEMPERATURE RATING FROM 0-100A AND 75
DEG. F TEMPERATURE RATING LISTED IN NEC FOR 100A AND ABOVE.
5. ALL CONDUCTORS SHALL BE COPPER, THHN/THWN; SOLID FOR #10 AWG AND SMALLER; STRANDED FOR
#8 AWG AND LARGER.
6. CONDUCTORS USED IN WET LOCATIONS, INCLUDING BUT NOT LIMITED TO UNDERGROUND CONDUITS/ DUCTBANKS AND EXTERIOR CONDUITS SHALL COMPLY WITH NEC 310.10 AND BE LISTED FOR USE IN
WET LOCATIONS.
7.ALL POWER CIRCUITS HAVE BEEN DESIGNED TO MEET 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND
3% OR LESS VOLTAGE DROP FOR BRANCH CIRCUITS.
GROUNDING
1. FIRE PROTECTION PIPING SHALL NOT BE USED FOR GROUNDING.
2. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUND CONDUCTOR. METAL
RACEWAYS SHALL NOT BE USED AS THE SOLE EQUIPMENT GROUND.
3. WHERE A PHASE CONDUCTOR IS INCREASED IN SIZE DUE TO VOLTAGE DROP, THE EQUIPMENT
GROUND CONDUCTOR SHALL BE INCREASED IN SIZE PROPORTIONATELY.
4. PROVIDE A GROUND BUS BAR IN EACH ELECTRICAL ROOM AND TELECOMMUNICATIONS / IDF/ MDF
ROOM FOR ALL NEW CONSTRUCTION AND NEW ROOMS IN EXISTING CONSTRUCTION, AND IN EXISTING
CONSTRUCTION WHERE THERE IS NONE INSTALLED WITHIN AN EXISTING ROOM.
IDENTIFICATION
1. PROVIDE TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS, AND EXISTING PANELBOARDS
AFFECTED BY THIS PROJECT. DIRECTORIES SHALL REFLECT PROJECT AS- BUILT CONDITIONS FOR ALL BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE WHERE EACH PANEL IS FED FROM. ADDITIONALLY, EACH BRANCH CIRCUIT LOAD DESCRIPTION SHALL INCLUDE THE ROOM NUMBER(S) FOR EACH LOAD (I.E., RECEPTACLES-RMS 501,503). ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN FIELD. COORDINATE EXACT ROOM NUMBERS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO
COMPLETION OF PANEL DIRECTORIES.
2. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON EACH SWITCHBOARD, SWITCHGEAR,
DISTRIBUTION PANEL, PANELBOARD, MOTOR CONTROL CENTER, SAFETY SWITCH, ENCLOSED CIRCUIT BREAKER, CABINET, STEP-DOWN TRANSFORMER, TRANSFER SWITCH, ETC., AND ANY OTHER MAJOR
COMPONENT OF THE ELECTRICAL SYSTEM.
3. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS FOR EACH DISTRIBUTION BREAKER OR BRANCH
CIRCUIT BREAKER IN SWITCHGEAR, SWITCHBOARDS, MOTOR CONTROL CENTERS AND OTHER
DISTRIBUTION EQUIPMENT. NAME TAG SHALL INCLUDE LOAD DESCRIPTION AND ROOM NUMBER FOR
EACH LOAD.
4. ARC FLASH DANGER/WARNING LABELS SHALL BE APPLIED TO SWITCHBOARD, PANELBOARDS, AND
EQUIPMENT CONTROLLERS PER NEC.
5. PROVIDE LABELS ON THE INSIDE OF EACH DEVICE COVERPLATE, IDENTIFYING THE PANEL(S)/ CIRCUIT
NUMBER(S) DEVICE IS CONNECTED TO.
6. PROVIDE NEATLY, HANDWRITTEN IDENTIFICATION ON THE EXTERIOR COVER OF ALL JUNCTION BOXES, PULLBOXES AND WIREWAYS, IDENTIFYING THE PANEL(S)/ CIRCUIT NUMBER(S) CONTAINED WITHIN.
7. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BUILDING STATING THAT
THE MAIN SERVICE DISCONNECTING MEANS IS LOCATED INSIDE.
8. PROVIDE A PERMANENT LABEL ON ALL PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROL CENTERS AND DISTRIBUTION PANELS STATING "DO NOT WORK ON EQUIPMENT WHILE ENERGIZED. LOCK-
OUT TAG-OUT REQUIRED".
9. PROVIDE REQUIRED IDENTIFICATION PER ANSI STANDARDS, NEC REQUIREMENTS, AND OWNER'S
PUBLISHED DESIGN STANDARDS WHERE APPLICABLE.
10. PROVIDE ENGRAVED PHENOLIC LABEL ON ALL NEW SERVICE EQUIPMENT TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE THE FAULT CURRENT CALCULATION WAS PERFORMED.
PROVIDE LABEL ON ALL EXISTING SERVICE EQUIPMENT WHEN MODIFICATIONS OCCUR THAT AFFECT THE
MAXIMUM AVAILABLE FAULT CURRENT AT THE SERVICE.
11. PROVIDE ARC FLASH HAZARD ANALYSIS PER NFPA 70E FOR ANY EQUIPMENT INCLUDED WITHIN THE
SCOPE OF WORK. INCIDENT ENERGY VALUES SHALL BE INCLUDED ON THE ARC FLASH WARNING
LABELS FOR EACH EQUIPMENT .
COORDINATION:
1. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL
CONNECTIONS (I.E., COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS, MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT NAMEPLATE
INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY ELECTRICAL REQUIRED.
2. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR ALL MECHANICAL, PLUMBING AND FIRE PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF
ELECTRICAL EQUIPMENT. PROVIDE ALL NECESSARY RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS, CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND
EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE ALL NECESSARY
ELECTRICAL REQUIRED, UNLESS NOTED OTHERWISE.
3. THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE
COORDINATION DRAWING PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION
REQUIRED TO COORDINATE ALL TRADE INFORMATION.
4. ALL WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE
COORDINATED WITH THE WORK OF ALL OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF
WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER DIVISIONS/TRADES.
5. WHERE WALLS ARE OF TILT-UP OR PRE-CAST CONSTRUCTION, PROVIDE COORDINATION FOR EXACT DIMENSIONS AND OPENINGS REQUIRED FOR ALL ELECTRICAL COMPONENTS INSTALLED WITHIN SUCH WALLS DURING THE SHOP DRAWING REVIEW PROCESS OF THE WALLS, PRIOR TO CONSTRUCTION OF
THE WALLS.
6. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE
DIAGRAMMATIC ON THE PLAN DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH
CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGH-IN TO ENSURE PROPER NEC
CLEARANCES AND APPROPRIATE MOUNTING SURFACE.
7. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR
DESIGN, TECHNOLOGY, STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED
INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART OF THE
WORK.
8. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN
WRITTEN FORM. IN GENERAL, THE MOST STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE
DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S DESIGN STANDARDS, WHEREIN THE
CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.
9. CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE BEEN REASONABLY
OBSERVED WILL NOT BE RECOGNIZED.
10. COORDINATE ALL PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE.
PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE PREMIUM TIME AS MAY BE
REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG
LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.
11. ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND
SCHEDULED IN ADVANCE.
12. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS (ELECTRIC, TELEPHONE, CABLE TV, ETC.) AND INCLUDE ALL COSTS FOR PROVIDING TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN THE BID PRICE. BID PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL, EQUIPMENT, EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING AND IMPACT FEES.
13. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM
INTERFERENCE WITH NORMAL BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM DAMAGE OR EXCESSIVE
NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY
LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER
AND OWNER, AT NO ADDITIONAL COSTS. REPORT OF ANY SUCH OCCURRENCE TO THE
ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN DIRECTION PRIOR TO
PROCEEDING WITH REPAIRS.
14. COORDINATE THE LOCATION OF ALL LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS, GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW ALL CONTRACT DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID. CONTRACTOR SHALL
NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET
BOXES OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.
LIGHTING:
1. LIGHT FIXTURES SUPPORTED BY CEILING GRID SHALL BE SUPPORTED AS FOLLOWS: LIGHT FIXTURES
WEIGHING LESS THAN 10 POUNDS SHALL HAVE 12-GAUGE HANGER WIRE CONNECTED FROM THE LIGHT FIXTURE TO THE STRUCTURE ABOVE. LIGHT FIXTURES WEIGHING 10 POUNDS OR MORE SHALL HAVE (2)
12- GAUGE HANGER WIRES ATTACHED AT OPPOSITE CORNERS OF THE LIGHT FIXTURE TO THE
STRUCTURE ABOVE.
2. COORDINATE EXACT LOCATIONS OF LIGHT FIXTURES IN LAY-IN AND GYPBOARD CEILINGS WITH ARCHITECTURAL REFLECTED CEILING PLANS, AND WALL MOUNTED EXTERIOR AND INTERIOR LIGHT FIXTURES WITH ARCHITECTURAL ELEVATIONS PRIOR TO INSTALLATION. WHERE THE QUANTITY OF LIGHTS DIFFERS BETWEEN THE ARCHITECTURAL RCP AND THE ELECTRICAL LIGHTING PLANS, PROVIDE THE HIGHEST QUANTITY OF FIXTURES IN THE BID PRICE. THE DISCREPANCY IN QUANTITY SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE HIGHEST QUANTITY SHALL BE CIRCUITED TO THE LOCAL ROOM OR AREA LIGHTING CIRCUITS AND LIGHTING CONTROL DEVICES, UNLESS OTHERWISE DIRECTED IN WRITING BY THE ARCHITECT/ENGINEER.
3. VERIFY ACTUAL CEILING CONSTRUCTION TYPE AS DEFINED ON THE ARCHITECTURAL DRAWINGS AND
FURNISH ALL LIGHT FIXTURES WITH THE CORRECT MOUNTING DEVICES WHETHER OR NOT SUCH
VARIATIONS ARE INDICATED BY THE LIGHT FIXTURE CATALOG NUMBER. VERIFY THE DEPTH OF ALL
RECESSED LIGHT FIXTURES WITH THE ARCHITECTURAL DRAWINGS PRIOR TO ORDERING LIGHT
FIXTURES. ANY DISCREPANCIES THAT WOULD CAUSE THE RECESSED LIGHT FIXTURES NOT TO FIT
INTO CEILING SHALL BE REPORTED TO ARCHITECT/ENGINEER PRIOR TO ORDERING.
4. LIGHT FIXTURES RECESSED IN FIRE-RATED CEILINGS SHALL BE PROVIDED WITH APPROVED FIRE- RATED ENCLOSURE WITH A FIRE RATING EQUAL TO THAT OF THE CEILING. PROVIDE A MINIMUM OF 3"
CLEARANCE FROM SIDES AND TOP OF RECESSED LIGHT FIXTURES.
5. MODIFY ALL LIGHT FIXTURE CATALOG NUMBERS AS REQUIRED TO COORDINATE WITH THE LIGHTING
BRANCH CIRCUIT VOLTAGES INDICATED. COORDINATE THE CATALOG NUMBERS WITH THE EXACT
FIXTURE MOUNTING AND TRIM REQUIRED BY THE CEILING IN WHICH EACH FIXTURE IS BEING
INSTALLED.
6. ALL LIGHT FIXTURES SHALL BE PROVIDED COMPLETE WITH LAMPS, UNLESS OTHERWISE NOTED.
7. ALL EXIT LIGHTS, LIGHT FIXTURES INDICATED WITH UNSWITCHED CIRCUIT (NIGHTLIGHT N/L), EMERGENCY TWIN-HEAD FIXTURES WITH INTEGRAL BATTERY PACKS, AND BATTERY PACKS INTEGRAL TO LIGHT FIXTURES, SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHING OR LIGHTING CONTROLS.
8. PROVIDE UL WET LABEL OR IP67 RATED LIGHT FIXTURES FOR ALL FIXTURES LOCATED OUTSIDE OR IN
PARKING GARAGES, IN SHOWERS, OR OPEN STRUCTURES.
9. EXTERIOR LIGHTING BALLASTS/DRIVERS SHALL HAVE A MINIMUM STARTING TEMPERATURE OF -40
DEGREE C, AND A NORMAL AMBIENT OPERATING TEMPERATURE OF 40 DEGREE C.
10. PROVIDE FUSING FOR ALL EXTERIOR LIGHT FIXTURES, OR FIXTURES IN PARKING GARAGES OR OPEN
STRUCTURES.
11. PROVIDE ALL TEMPORARY NORMAL LIGHTING, EMERGENCY LIGHTING AND EXIT SIGNS REQUIRED
DURING THE PROJECT CONSTRUCTION PHASE.
12. COORDINATE EXACT FOUNDATION AND/OR COMPACTING REQUIREMENTS FOR ALL POLE MOUNTED LIGHT FIXTURES WITH MANUFACTURER'S AND/OR INSTALLER'S STRUCTURAL ENGINEER. POLE BASES SHALL MEET OR EXCEED ALL WIND LOAD RATINGS, GUST FACTORS, IMPORTANCE FACTORS, ETC.
REQUIRED BY NATIONAL AND/OR LOCAL CODES. SHOP DRAWINGS SHALL INCLUDE STRUCTURAL
DRAWINGS FOR ALL POLE BASES, POLE, ASSEMBLY AND OVERTURN CALCULATIONS REQUIRED IN THIS PROJECT, SIGNED AND SEALED BY A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE
PROJECT STATE.
13. REFER TO LIGHT FIXTURE SCHEDULE FOR LIGHT FIXTURE TYPES, DESCRIPTIONS, CATALOG NUMBERS AND ADDITIONAL INFORMATION PERTINENT TO THE LIGHT FIXTURE OR INSTALLATION THEREOF.
14. COORDINATE LIGHT FIXTURE TRIM TYPE AND FINISH COLOR WITH ARCHITECT PRIOR TO ORDERING.
15. EACH LIGHTING CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL.
16. PROVIDE LIGHTING CONTROLS TO AUTOMATICALLY SHUTOFF BUILDING FACADE AND LANDSCAPE
LIGHTING AS A FUNCTION OF DAWN/DUSK AND OPENING/CLOSING TIME.
17. PROVIDE LIGHTING CONTROLS TO AUTOMATICALLY REDUCE THE CONNECTED LIGHTING POWER OF
EXTERIOR SITE/AREA LIGHTING BY NOT LESS THAN 30 PERCENT FROM NOT LATER THAN MIDNIGHT
TO 6AM, FROM ONE HOUR AFTER BUSINESS CLOSING TO ONE HOUR BEFORE BUSINESS OPENING
OR DURING ANY PERIOD WHEN ACTIVITY HAS BEEN DETECTED FOR A TIME OF LONGER THAN 15
MINUTES.
18. WHERE THERE IS NO EMERGENCY GENERATOR/ LIFE SAFETY DISTRIBUTION BRANCH AVAILABLE, PROVIDE INTEGRAL BATTERY PACKS, RATED FOR A MINIMUM OF 90 MINUTES, FOR FIXTURES
SHOWN WITH SOLID SHADING AND/OR WITH "E" AFTER FIXTURE TAG, AND FOR ALL EXIT LIGHTS, OR UNLESS NOTED OTHERWISE.
19. ALL LIGHTING HAS BEEN DESIGNED IN COMPLIANCE WITH SECTION 405 OF THE FLORIDA ENERGY CONSERVATION CODE FOR LIGHTING POWER DENSITY, AUTOMATIC LIGHTING CONTROLS AND ALL
ADDITIONAL REQUIREMENTS.
20. PROVIDE AS PART OF BID PRICE FOR THE SERVICES OF AN INDEPENDENT COMMISSIONING AGENT
FOR THE LIGHTING SYSTEM FUNCTIONAL TESTING REQUIRED BY THE ENERGY CONSERVATION
CODE, INCLUDING ALL REQUIRED REPORTS. WHERE OCCUPANCY SENSORS, TIME SWITCHES,
PROGRAMMABLE SCHEDULED LIGHTING CONTROLS, PHOTOSENSORS AND DAYLIGHTING CONTROLS
ARE INSTALLED, THE SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL HARDWARE AND
SOFTWARE ARE CALIBRATED, ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDITION TO
ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTRUCTIONS.
CONDUCT THE FUNCTIONAL TESTS IN ACCORDANCE WITH THE ENERGY CONSERVATION CODE.
PROVIDE COMMISSIONING REPORT TO ENGINEER NOT LATER THAN 60 DAYS FROM THE DATE OF
RECEIPT OF THE CERTIFICATE OF OCCUPANCY. DOCUMENTS CERTIFYING THAT THE INSTALLED
LIGHTING CONTROLS MEET DOCUMENTED PERFORMANCE CRITERIA OF THE ENERGY
CONSERVATION CODE ARE TO BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS FROM THE
DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.
MISCELLANEOUS CIRCUIT INSTALLATION REQUIREMENTS:
1. PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER
AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE IS
TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.
2. PROVIDE 120V CONNECTION TO ALL MOTORORIZED DAMPERS INDICATED ON MECHANICAL PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS ARE TO BE
PROVIDED AS SHOWN ON FIRE SMOKE DAMPER DETAIL ON THE DETAILS SHEET.
3. COORDINATE RECEPTACLE LOCATIONS WITH TECHNOLOGY DRAWINGS OR OWNER'S VENDOR
DRAWINGS SO THAT A 120V 20A 5-20R RECEPTACLE IS LOCATED ADJACENT TO EACH VOICE/DATA OUTLET AND TV OUTLET INDICATED ON PLANS. RECEPTACLE IS TO BE CONNECTED TO NEAREST
120V RECEPTACLE CIRCUIT, UNLESS OTHERWISE NOTED ON PLANS.
FIRE ALARM SYSTEM NOTES
1. ALL FIRE ALARM EQUIPMENT IS TO BE NEW, UL LISTED FOR FIRE SERVICE, AND SHALL BE
COMPATIBLE WITH THE SYSTEM BEING USED.
2. ALL WIRING AND CONDUIT IS TO CONFORM TO NEC ARTICLE 760. WIRING SHALL BE UL LISTED, MINIMUM 300V TYPE FPLP PLENUM RATED SOLID COPPER OR STRANDED COPPER WITH MAXIMUM 19
STRANDS.
3. LOW VOLTAGE CONDUCTORS: PROVIDE CONDUCTORS IN ACCORDANCE WITH NFPA 70 AND NFPA 72, AND AS RECOMMENDED BY THE FIRE ALARM SYSTEM MANUFACTURER. CONDUCTORS SHALL BE
COPPER, MINIMUM NO. 14 AWG, TWISTED SHIELDED PAIR.
4. SURVIVABILITY: A 2-HOUR RATED CABLE ASSEMBLY SHALL BE PROVIDED FOR NOTIFICATION
APPLIANCE CIRCUITS AND ANY OTHER CIRCUITS NECESSARY FOR THE OPERATION OF THE
NOTIFICATION APPLIANCE CIRCUITS FROM THE POINT AT WHICH THEY EXIT THE CONTROL UNIT
UNTIL THE POINT THAT THEY ENTER THE NOTIFICATION ZONE THAT THEY SERVE.
5. MANUAL PULL STATIONS ARE TO BE INSTALLED AT 42" TO BOTTOM OF DEVICE AND NO HIGHER THAN
48" TO HANDLE ABOVE FINISHED FLOOR.
6. PROVIDE MINIMUM 3/4" CONDUIT AND WIRING BETWEEN EACH FIRE ALARM DEVICE AND FROM LAST
DEVICE TO FACP UNLESS OTHERWISE NOTED.
7. PROVIDE DUCT DETECTOR (AND FIRE ALARM RELAY WHERE APPLICABLE) CONNECTED TO FIRE ALARM SYSTEM, WITHIN 5' OF ALL DUCT PENETRATIONS THROUGH FIRE/SMOKE WALLS, WHETHER
INDICATED ON ELECTRICAL OR MECHANICAL PLANS OR NOT.
8. FIRE ALARM CONTROL PANEL IS TO BE PROVIDED WITH DEDICATED 120V CIRCUIT WITH EQUIPMENT
GROUND CONNECTION PER MANUFACTURER'S RECOMMENDATIONS AND ARTICLE 760 OF THE NEC.
PROVIDE MINIMUM #12 AWG FOR GROUND CONNECTION. NOTE: PANEL NEUTRAL OR CONDUIT
GROUND IS NOT ACCEPTABLE. 120V CIRCUIT SHALL BE FROM EMERGENCY/LIFE SAFETY BRANCH
WHERE AVAILABLE.
9. SECONDARY BACK-UP POWER SHALL BE PROVIDED BY INTEGRAL BATTERIES WITHIN THE FIRE
ALARM CONTROL PANEL TO SUPPLY POWER TO THE SYSTEM UNDER QUIESCENT LOAD FOR A
MINIMUM OF 24 HOURS, AND THEN BE CAPABLE OF AN ADDITIONAL 15 MINUTES (5 MINUTES FOR NON
VOICE SYSTEMS) ALARM OPERATION AT MAXIMUM CONNECTED LOAD.
10. ALL FIRE ALARM POWER CIRCUITS SHALL HAVE A DEDICATED 120V 20A BREAKER THAT SHALL BE RED IN COLOR AND MECHANICALLY PROTECTED (LOCKABLE IN THE "ON" POSITION), MARKED AS
"FIRE ALARM CIRCUIT".
11. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ANY TAMPER SWITCH ACTIVATION. FAILURE
OR REMOVAL OF ANY DETECTION OR MANUAL DEVICE SHALL ACTIVATE A TROUBLE SIGNAL.
12. A CERTIFICATION OF COMPLETION AND UL LISTING SHALL BE ISSUED AND INSTALLED ON THE FIRE
ALARM CONTROL PANEL. SUBMIT NFPA RECORD OF COMPLETION FORM ALONG WITH SMOKE
DETECTOR SENSITIVITY REPORT FOR ALL DETECTORS WITHIN THE PROJECT AREA TO ENGINEER
AND MAKE AVAILABLE AT FINAL INSPECTION.
13. MINIMUM CANDELA RATING OF STROBES IS 75; "110" ADJACENT TO DEVICE INDICATES 110 CANDELA RATING. PROVIDE SYNCHRONIZATION OF STROBES IN ALL ADJACENT AREAS WHERE STROBES ARE
VISIBLE TO EACH OTHER.
14. ALL STROBES SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM.
15. ALL STROBES SHALL BE INSTALLED PER ADA MOUNTING HEIGHT REQUIREMENTS. WALL MOUNTED
STROBES SHALL BE INSTALLED SO THAT THE BOTTOM OF THE STROBE LENS IS 80" AFF.
16. STROBES SHALL BE INSTALLED WITHIN 15' OF THE ENDS OF ALL CORRIDORS.
17. FIRE ALARM DEVICES INSTALLED OUTSIDE OR IN AREAS OPEN TO THE EXTERIOR SHALL BE
WEATHERPROOF DEVICES IN APPROVED BACKBOXES.
18. SMOKE DETECTORS SHALL BE PHOTO-ELECTRIC ADDRESSABLE TYPE, UNLESS SPECIFICALLY
NOTED OTHERWISE.
19. SMOKE DETECTORS ARE TO BE INSTALLED PER NFPA 72. WALL MOUNTED SMOKE DETECTORS
SHALL BE MOUNTED 4"-12" BELOW THE CEILING AND AWAY FROM CORNERS.
20. SMOKE DETECTORS LOCATED IN ELEVATOR LOBBIES, ELEVATOR HOISTWAYS AND ELEVATOR
MACHINE ROOMS SHALL INITIATE ELEVATOR RECALL, ACTIVATE ELEVATOR WARNING LIGHTS AND CAUSE SEPARATE AND DISTINCT VISIBLE ANNUNCIATION AT THE FIRE ALARM CONTROL PANEL AND
FIRE ALARM ANNUNCIATORS.
21. DUCT DETECTORS SHALL BE PHOTO-ELECTRIC ADDRESSABLE TYPE, AND RATED FOR VELOCITIES
UP TO 5000 FT/MIN.
22. HEAT DETECTORS SHALL BE ADDRESSABLE, FIXED TYPE @ 135 DEG F, UNLESS OTHERWISE NOTED.
23. FOR PROJECTS WITH AN ELEVATOR, THE ELEVATOR CONTROL PANEL SHALL HAVE TWO SIGNALS
FROM THE FIRE ALARM CONTROL PANEL/ ASSOCIATED SMOKE DETECTORS - ONE FROM THE
"DESIGNATED FLOOR" SMOKE DETECTOR AND ANOTHER COMBINED SIGNAL FROM THE SMOKE
DETECTORS AT THE OTHER LOBBY LANDINGS AND IN THE ELEVATOR EQUIPMENT ROOM.
24. ACTIVATION OF ANY SMOKE DETECTOR IN THE ELEVATOR LOBBY OF THE DESIGNATED PRIMARY
RECALL LEVEL OR ELEVATOR MACHINE ROOM SHALL ACTIVATE ALTERNATE LEVEL RECALL.
25. PRIOR TO INSTALLATION OF ELEVATOR HOISTWAY HEAT DETECTORS, VERIFY WITH LOCAL
AUTHORITY HAVING JURISDICTION IF THEY ARE REQUIRED.
26. HEAT DETECTORS SHALL BE LOCATED WITHIN 24" OF SPRINKLER HEADS LOCATED IN THE ELEVATOR
MACHINE ROOM AND ALL HOISTWAY SPRINKLER HEADS LOCATED 24" ABOVE THE ELEVATOR PIT
FLOOR. THESE HEAT DETECTORS SHALL HAVE BOTH A LOWER TEMPERATURE RATING AND HIGHER
SENSITIVITY THAN THE SPRINKLER HEADS. HEAT DETECTORS SHALL OPEN THE MAIN
DISCONNECT/POWER SUPPLY TO THE ELEVATOR CONTROLLER. CONTROL CIRCUITS TO SHUT OFF
ELEVATOR POWER SHALL BE MONITORED BY THE FIRE ALARM CONTROL PANEL. CONTROL MODULE
SHALL BE WITHIN 3 FEET OF THE ELEVATOR CONTROLLER.
27. WHERE THERE IS A GENERATOR ON THE PROJECT, PROVIDE RELAYS AS REQUIRED FOR THE FIRE
ALARM SYSTEM TO MONITOR THE FOLLOWING THREE CONDITIONS: GENERATOR RUNNING;
GENERATOR FAULT; GENERATOR SWITCH NOT IN AUTO.
28. WHERE THERE IS A FIRE PUMP ON THE PROJECT, PROVIDE RELAYS AS REQUIRED FOR THE FIRE ALARM SYSTEM TO MONITOR THE FOLLOWING THREE CONDITIONS: FIRE PUMP RUNNING; FIRE PUMP
LOSS OF POWER; FIRE PUMP POWER PHASE REVERSAL.
29. PROVIDE AN ADDRESSABLE FIRE ALARM SYSTEM PER NFPA AND ALL STATE AND LOCAL CODE
REQUIREMENTS. COMPLY WITH NFPA 72 AND ADA REQUIREMENTS.
30. FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF AN HVAC DIFFUSER (SUPPLY OR RETURN), IN DIRECT AIR FLOW PATH, OR WITHIN 24"
OF A SPRINKLER HEAD UNLESS NOTED OTHERWISE. SMOKE DETECTORS FOR DOOR RELEASE
SHALL BE LOCATED ON THE CENTERLINE OF THE DOOR AND A MAXIMUM OF FIVE FEET FROM THE
DOOR. THE MINIMUM DISTANCE FROM THE DOOR SHALL BE THE DEPTH OF THE WALL SECTION
ABOVE THE DOOR, BUT NOT LESS THAN 12".
31. PROVIDE LABELS FOR REMOTE ALARM INDICATORS FOR DUCT MOUNTED SMOKE DETECTORS (I.E., AHU-1 SUPPLY, AHU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT DETECTORS SHOULD BE
LOCATED WITHIN 6 TO 10 EQUIVALENT DIAMETERS OF STRAIGHT, UNINTERRUPTED DUCTWORK.
DUCT DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD BE LOCATED BETWEEN THE LAST INLET OR
OUTLET UPSTREAM OF THE DAMPER AND THE FIRE INLET OR OUTLET DOWNSTREAM OF THE
DAMPER, AND WITHIN FIVE FEET OF THE FIRE/SMOKE WALL.
32. EQUIPMENT SHUT DOWN FIRE ALARM RELAYS SHALL BE LOCATED WITHIN THREE (3) FEET OF THE EQUIPMENT CONTROLS AND THE WIRING TO THE RELAY SHALL BE MONITORED BY THE FIRE ALARM
SYSTEM.
33. ALL FIRE ALARM CABLE SHALL BE INSTALLED IN CONDUIT; NO FIRE ALARM CONDUIT SHALL BE
INSTALLED UNDER SLAB. PROVIDE MANUFACTURED RED CONDUIT UNLESS OTHERWISE NOTED.
34. MINIMIZE EXPOSURE OF DETECTORS TO DIRT AND DUST FROM CONSTRUCTION. PROVIDE PLASTIC
COVERS DURING CONSTRUCTION.
35. STATE CERTIFIED AND LICENSED FIRE ALARM CONTRACTOR SHALL PREPARE AND SUBMIT SIGNED
AND SEALED DRAWINGS FOR THE LOCAL AUTHORITY HAVING JURISDICTION/ FIRE MARSHALL.
36. ALL NOTIFICATION DEVICES SHALL BE RED.
37. FIRE ALARM CIRCUIT CLASS SHALL MATCH THAT OF EXISTING SYSTEM.
38. NOTIFICATION DEVICES SHALL BE ADDRESSABLE ELECTRIC-VIBRATING-POLARIZED HORNS, SELECTABLE FOR HIGH OR LOW dBA OUTPUT. THEY SHALL HAVE A SOUND PRESSURE LEVEL OF 90dBA MEASURED 10 FEET FROM HORN, USING CODED SIGNAL PER NFPA 72.
39. FIRE ALARM CONTRACTOR/VENDOR SHALL PREPARE FLORIDA LICENSE P.E. WORKING DRAWINGS
INCORPORATING THE FIRE ALARM CRITERIA DESIGN AND CONFIRMING TO AHJ REQUIREMENTS.
CONTRACTOR SHALL PROVIDE ALL MATERIAL REQUIRED PER AHJ AND DESIGN CRITERIA FOR A
FULLY FUNCTIONING AND PERMITTABLE FIRE ALARM SYSTEM. SUBMIT TO DESIGN PROFESSIONAL AS A SHOP DRAWING FOR REVIEW. SUBMIT COMPLETE SIGNED & SEALED DRAWINGS TO PERMITTING AGENCY AND FOR CERTIFICATE OF OCCUPANCY. COMPLETED FIRE ALARM CERTIFICATION SHALL BE
PROVIDED TO OWNER AT COMPLETION OF CONSTRUCTION.
40. FIRE ALARM DESIGN IS IN ACCORDANCE WITH FLORIDA STATUTES CHAPTER 61G15-32. WHERE A
FIRE ALARM RISER IS INDICATED, IT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO
REPRESENT A COMPLETE WIRING AND DEVICE DISPLAY. ALL WIRING AND DEVICES SHALL BE IN
ACCORDANCE WITH SELECTED VENDOR'S POINT-BY-POINT WIRING DIAGRAM. REFER TO FLOOR
PLAN FOR DESIGN INTENT AND PROPOSED QUANTITY OF FIRE ALARM SYSTEM COMPONENTS.
GENERAL REQUIREMENTS
1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO
THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS". ALL WORKMANSHIP, METHODS
AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL
DIVISIONS AS A WHOLE.
2. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF
CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE
EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL AND STRUCTURAL CONTRACT
DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS AND WORK OF ALL OTHER
DIVISIONS/TRADES.
3. THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY
NOTED OTHERWISE
4. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL
TESTING AGENCY
5. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE
CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND
WORKMANLIKE MANNER, TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER.
6. CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR
THE DURATION OF THIS PROJECT
7. GUARANTEE ALL MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF
ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.
8. INCLUDE ALL COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND
TEMPORARY POWER IN THE BID PRICE, UNLESS NOTED OTHERWISE.
9. IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH ALL APPLICABLE RULES, REGULATIONS
AND GUIDELINES CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST
ENVIRONMENTAL EXPOSURE OR POLLUTION. PROVIDE DOCUMENTATION OF SAID COMPLIANCE.
10. PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT
OF THE ELECTRICAL SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR
COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO, RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. ALL SUBMITTALS ARE TO BE REVIEWED AND APPROVED BY THE CONTRACTOR
FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE
ARCHITECT/ENGINEER. ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY
ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN DIVISION 1.
11. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS
ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE CONTRACTOR SHALL MAKE ALL
CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND
OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS.