Attachments 26QA072.pdf
PDF 12 MB Posted
- Solicitation number
- W912WJ26QA072
About this file
This document contains technical and regulatory information regarding the potable water system for Buffumville Lake Park, operated by the U.S. Army Corps of Engineers in Charlton, Massachusetts (PWS ID #2054052).
The facility maintains a registered transient non-community (TNC) public water system serving approximately 250 persons during the operational season (May 1 through September 30). Water is sourced from a 6-inch bedrock well (Well #1) drilled to 675 feet with a 2-horsepower submersible pump approved by MassDEP for a withdrawal rate of 3,000 gallons per day. Three potable water sampling locations have been established: the interior of the pump house, the exterior of the restroom building, and the exterior of the storage barn. The system includes a 300-gallon storage tank, treatment equipment, pressure tank, and filtration housing located at the pump house.
The Massachusetts Department of Environmental Protection Drinking Water Program has issued a 2026 Certificate of Registration requiring compliance with 310 CMR 22.00 regulations. The required water quality sampling schedule for 2026-2028 specifies testing for bacteria (April-September, 3 samples per month), iron, manganese, nitrate, nitrite, secondary contaminants, sodium, and volatile organic compounds at the finished well. The 2025 Drinking Water Quality Report covering January 1-December 31, 2024 documents monitoring results showing no violations, with nitrate <0.026 mg/L, nitrite <0.006 mg/L, and sodium at 26.5 mg/L, all below maximum contaminant levels.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING STRONG
U.S. ARMY CORPS OF ENGINEERSBUFFUMVILLE DAM
FIGURE 1
POTABLE WATER
SAMPLING LOCATIONS
BUFFUMVILLE DAM
U.S. ARMY CORPS OF ENGINEERS
NEW ENGLAND DISTRICT
FEB 2026
0 100 20050
Feet
Oxfo rd R oad
F ulling M ill D r
Potable Water Sample Point Locations
Buffumville Lake
BUFFUMVILLE LAKE PARK
229 OXFORD ROAD
CHARLTON, MA 01507
SAMPLE POINT 1
Interior of Pump House
SAMPLE POINT 2
Exterior of Restroom Building
SAMPLE POINT 3
Exterior of Storage Barn
Commonwealth of Massachusetts Department of Environmental Protection
Drinking Water Program 100 Cambridge Street, Suite 900, Boston, MA 02114; (617) 292-5770
Certificate of Registration
The Department of Environmental Protection Drinking Water Program hereby recognizes the
BUFFUMVILLE PARK
PWS ID # 2054052
as a registered public water system in Massachusetts. Public water systems must comply with the Massachusetts Drinking Water Regulations, 310 CMR
22.00.
Yvette DePeiza, Program Director
Drinking Water Program
Certificate expires December 31, 2026
Please contact the Drinking Water Program if there are any changes in this system.
MassDEP: https://www.mass.gov/massdep-contacts-service-center https://www.mass.gov/massdep-contacts-service-center
Required Water Quality Sampling Schedule Frequency ForDecember 18, 2025
PWS ID#: 2054052 PWS Name: BUFFUMVILLE PARK
BACTERIA SAMPLING
Apr - Sep:
NCClass:
3 MONTH
Oct - Mar: per per
Page 1 of 12026 To 2028
Refer to your MassDEP Coliform Sampling Plan for approved coliform sample locations. Systems open before or beyond the start/end dates must collect samples during these extra months.
Season Start Date: 05/01
Season End Date: 09/30
Town: CHARLTON
Loc ID # SAMPLE LOCATION NAME M/S
QTR1
R/F D/S WAIVER
Y / N QTR1 QTR1QTR2 QTR2 QTR2QTR3 QTR3 QTR3QTR4 QTR4 QTR4
2026 2027 2028
Compliance Period
POP: 250
IRON
01G FINISHED: WELL #1 S F S X
2054052-01G ROCK WELL
MANGANESE
01G FINISHED: WELL #1 S F S X
2054052-01G ROCK WELL
NITRATE
01G FINISHED: WELL #1 S F S N X X X
2054052-01G ROCK WELL
NITRITE
01G FINISHED: WELL #1 S F S N X
2054052-01G ROCK WELL
SECONDARY CONTAMINANTS
[DEP recommends annual testing]01G FINISHED: WELL #1 S F S N
2054052-01G ROCK WELL
SODIUM
01G FINISHED: WELL #1 S F S N X
2054052-01G ROCK WELL
VOLATILE ORGANIC COMPOUNDS
[Next Sampling due in 2029]01G FINISHED: WELL #1 S F S N
2054052-01G ROCK WELL
R/F = (R)aw or (F)inished water D/S = (D)istribution or (S)ource sample Waiver = (Y)es or (N)oM/S= (M)ultiple/Manifold sources or a (S)ingle source Important Notes:
M = Monthly This monitoring schedule is based on the system's current inventory and is subject to change. The system is responsible for promptly reporting errors or omissions.
Errors or omissions on the schedule do not prohibit MassDEP from enforcing monitoring requirements set forth by the Regulations.
POSTED FOR CUSTOMER REVIEW AS REQUIRED BY THE MASSACHUSETTS DEP/DWP
Massachusetts Drinking Water Regulations 310 CMR 22.16A (23)
2025 DRINKING WATER QUALITY REPORT
For the period January 1, 2024 to December 31, 2024
BUFFUMVILLE PARK
PWS ID: 2054052
229 OXFORD RD
CHARLTON, MA 01507
The drinking water system at the facility noted above is registered in the Commonwealth as a transient non-community (TNC) public water system because it owns and/or controls its source of water and supplies potable water to 25 or more persons at least 60 days of the year.
Examples of TNCs include restaurants, motels, campgrounds, parks, golf courses, ski areas and community centers.
All drinking water, including bottled water, may contain small amounts of some contaminants. The presence of contaminants does not necessarily indicate that water poses a health risk.
The drinking water quality monitoring results on file with the Massachusetts Department of Environmental Protection Drinking Water
Program (MassDEP/DWP) for this public water system and the most recent monitoring period are as follows:
MONITORING RESULTS TABLE
CONTAMINANT HIGHEST
DETECT
VALUE
MCL
MCLG
VIOLATION 4
(YES or NO)
POSSIBLE SOURCES OF
CONTAMINATION
FAILURE TO
MONITOR **
MCL
Total Coliform NO DATA 0 0 N N Naturally present in the environment.
Runoff from fertilizer use; leaching from septic tanks, sewage; and erosion of natural deposits.
Nitrate < 0.026 10 10 N N
(MG/L)
Runoff from fertilizer use; leaching from septic tanks, sewage; and erosion of natural deposits. Nitrite < 0.006 1 1 N N
(MG/L)
Naturally present in the environment; may also be due to salt runoff from deicing practices.
Sodium 26.5 N/A N/A N/A N(MG/L)
Other Contaminant
Violations5 N/A N/A N/A N/A N/A
Detect – any levels found at or above the detection limits in the Massachusetts Drinking Water Regulations, 310 CMR 22.00.
Maximum Contaminant Level (MCL) – the highest level of a contaminant that is allowed in drinking water.
Maximum Contaminant Level Goal (MCLG) – the level of a contaminant in drinking water below which there is no known or expected risk to health.
For any violations, Refer to the following health effects language listed below and contact the system’s contact person for information on corrective actions taken by the system to return to compliance and stay in compliance in the future:
Total Coliform – Coliforms are bacteria that are naturally present in the environment and are used as an indicator that other, potentially harmful, bacteria are present. Coliforms were found in more samples than allowed and this was a warning of potential problems.
Nitrate – Infants below the age of six months who drink water containing nitrate in excess of the MCL could become seriously ill and, if untreated, may die. Symptoms include shortness of breath and blue-baby syndrome.
Nitrite - Infants below the age of six months who drink water containing nitrite in excess of the MCL could become seriously ill and, if untreated, may die. Symptoms include shortness of breath and blue-baby syndrome.
Other Contaminant Violations – If applicable, contact the owner or the MassDEP at the numbers listed below for information on the other contaminants.
** If “Y”, one or more times during the reporting period this system did not monitor and/or report to the MassDEP as required.
“ We are required to monitor your drinking water for specific contaminants on a regular basis. Results of the regular monitor ing are an indicator of whether or not our drinking water meets health standards. During the above noted reporting period we did not monitor or test and/or did not complete all monitoring or testing for contaminant(s) noted above and therefore cannot be sure of the quality of our drinking water during that time. “
The posting of this report meets the public notification Tier 3 requirements of 310 CMR 22.16(4).
Massachusetts Department of Environmental Protection
Bureau of Resource Protection – Drinking Water Program
2002 DRINKING WATER QUALITY REPORT
For the period January 1, 2001 to December 31, 2001
For more information, or the complete monitoring results for this system:
Owner/responsible party name Signature of owner/responsible party Telephone #
Certified Operator Name Signature of certified operator License #
If you have any questions on the Massachusetts Drinking Water Program contact the MassDEP, Drinking Water Program at (617)
292-5770, email program.director-dwp@mass.gov (subject: TNC CCR) or visit the MassDEP web site at www.mass.gov/orgs/massachusetts-department-of-environmental-protection. Contact the EPA Safe Drinking Water Hotline at (800)
426-4791 for more information about contaminants and potential health effects.
Date Drinking Water Quality Report posted______________ Location posted__________________________________________
| BVL Park Utilities Design 2022.pdf |
| BVL Park Sampling Map |
| BVL Park Waterlines 2022 |
File details come from the government source that posted it. Updated .