This document provides concept drawings and load calculations for an electrical floor plan relating to a solicitation for a High Voltage Air Conditioning (HVAC) system replacement project at the USAGM Transmitting Station in Kuwait. The existing switchboard and panels will be replaced with a new 1000A, 415/240V, 3-phase, 4-wire main switchboard located in the electrical room. Branch circuit breakers will be bolt-on style. Load calculations show an existing connected load of 673kVA reducing to a total demand load of 647kVA after applying a diversity factor of 1.08, for a total load of 599kVA or 834A. The solicitation seeks design and construction services for replacing the HVAC system at Transmitter Hall 5-6 and refers to additional attachments providing requirements, specifications and other details.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNITED STATES AGENCY FOR GLOBAL MEDIA
KUWAIT TRANSMITTING STATION
HIGH VOLTAGE AIR CONDITIONING (HVAC)
REPLACEMENT SYSTEM
SOLICITATION NO. 951700-21-R-0013
ATTACHMENT C
CONCEPT DRAWINGS
KUWAIT SHORTWAVE BUILDING
HVAC REPLACEMENT SYSTEM
11 I LJ
DD
D
PROPOSED HVAC
SWITCHBOARD & PANELS
(ALL OPTIONS)
I
11 I LJ
D D
D
�I
I ___JI [J LJ
D D □
111 111 11 1111
□ [J □ □
ELECTRICAL FLOOR PLAN
E-101 1:eo
LJ
NORTH
SENSITIVE BUT UNCLASSIFIED (SBU)
PROPERTY OF
THE UNITED STATES GOVERNMENT
FOR OFFICIAL USE ONLY
DO NOT REMOVE THIS NOTICE
PROPERLY DESTROY OR RETURN
DOCUMENTS WHEN NO LONGER NEEDED
PRELIMINARY
EJC
INTERNATIONAL ENGINEERING &
CONSULTING SERVICES, LLC
30 Galesi Drive, Suite 202B
Wayne, NJ 07470 Tel. 973-785-4545 www.TSE-EJC.com
PROJECT INFORMATION:
USAGM Kuwait
Transmission Station Short Wave HVAC Replacement
SEAL:
NO. DATE DESCRIPTION
DRAWN BY:
CJS
CHECKED BY:
RSL
PROJECT NUMBER:
DRAWING SCALE:
SHEET TITLE:
DATE:
11/30/20
DATE:
11/30/20
20C0018
AS NOTED
ELECTRICAL
FLOOR PLAN
SHEET NUMBER: OF:
X xx
DRAWING NUMBER:
E-101
EXISTING SWITCHBOARD: MDS1 (Option 3 Load Calculation) MAIN: CIRCUIT BREAKER 1000A
SWBD. LOCATION: ELECTRICAL ROOM SHORT CIRCUIT RATING: 44,000AIC
SWBD. RATING: 415/240V, 3 PHASE, 4W, 1200A BRANCH C.B. TYPE: BOLT ON
Bus LOAD C.B. CKT DEMAND CONN.
No. DESCRIPTION POLE AT AF CONFIG kVA kVA
MDS-1A EXISTING CHILLER TO BE REMOVED 3 600 3PH,4W
MDS-2A PANEL - PP1 3 200 600 3PH,4W 133 140
MDS-3A PANEL - PP2 3 200 600 3PH,4W 107 107
MDS-3B PANEL (ANT 1)* 3 600 3PH,4W 40 50
MDS-4A PANEL - RP1 VIA T5 2 45 225 3PH,4W 2 4
MDS-4B PANEL - LR1 3 100 225 3PH,4W 29 37
MDS-5A PANEL - EP1 VIA ATS-1 3 175 600 3PH,4W 77 77
MDS-5B SIS UPS 3 600 3PH,4W 30 30
MDS-6A 3 200 600 3PH,4W
MDS-6B NEW HVAC PANEL PP-2B 3 600 600 3PH,4W 227.82 227.82
TOTAL CONNECTED LOAD IN kVA 673
Estimated Load TOTAL DEMAND LOAD IN kVA 647
DIVERSITY FACTOR 1.08
TOTAL LOAD IN kVA 599
TOTAL LOAD IN AMPS 834