This solicitation package seeks proposals for a design-build construction project to replace the high voltage air conditioning system at the U.S. Agency for Global Media transmitting station in Kuwait. The scope of work includes removing the existing HVAC system and installing new condensing units, air handling units, and associated equipment as specified in Attachment D. Proposals are due by June 4, 2021 and the period of performance is 270 calendar days from award. The estimated value of the contract is between $1 million and $10 million. The solicitation is set aside for small businesses and was issued by the U.S. Agency for Global Media.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNITED STATES AGENCY FOR GLOBAL MEDIA
KUWAIT TRANSMITTING STATION
HIGH VOLTAGE AIR CONDITIONING (HVAC)
REPLACEMENT SYSTEM
SOLICITATION NO. 951700-21-R-0013
ATTACHMENT D
PRELIMINARY HVAC EQUIPMENT SELECTION
Updated 5/12/2021
EJC International Services, LLC | 30 Galesi Drive, Suite 202B, Wayne, NJ 07470 | Tel (973) 785-4545 | Fax (973) 785-0766 | www.tse-ejc.com
KUWAIT TRANSMITTING STATION
SHORTWAVE BUILDING HVAC SYSTEMS
REPLACEMENT STUDY
Contract No. 951700-19-D-0218 Order No. 951700-20-T-0863
PRELIMINARY HVAC EQUIPMENT SELECTIONS
FINAL STUDY SUBMISSION
February 12, 2021 https://www.google.com/url?sa=i&rct=j&q=&esrc=s&source=images&cd=&ved=&url=https%3A%2F%2Fwww.usagm.gov%2F&psig=AOvVaw26oFfP1u0yxIp07UIkwhWC&ust=1575477464857424
Kuwait Transmitting Station Shortwave Building HVAC Systems Replacement Study
EJC International Services, LLC February 12, 2021 Page - 7
OPTION 3
Table 3.1 – Option 3 Condensing Units
Option 3 – Carrier DX Split Units – Condensing Units (CU)
Tag no. CU-1 CU-2 to 4
& CU-10
CU-5 CU-6 CU-7, 8 CU-9 CU-EU-1
Model 38APD 38AUD 38AUZ 38APD 38AUD 38AUD 38AUD
Size (Tons) 25 12.5 6 25 15 7.5 12.5
Refrigerant Puron Puron Puron Puron Puron Puron Puron
Ambient, F 125 125 125 125 125 125 125
EER 11.6 - - 11.6 12.2 12.6 12.0
No. of fans 2 3 2 2 3 2 3
No. of compressors
2 2 1 2 2 2 2
Compressor type Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Electrical, V/Ph/Hz
380/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
MCA 48.5 29.5 16.7 48.5 40.4 19.0 29.6
MOP 60 40 25 60 50 25 40
Dimensions LxWxH (ins)
89x41x61 87x44x51 60x46x43 89x41x61 87x68x51 60x46x51 87x44x51
Dimensions LxWxH (mm)
2260.6 x
1041.4 x 1549.4
2209.8 x
1117.6 x 1295.4
1524 x
1168.4 x 1092.2
2260.6 x
1041.4 x 1549.4
2209.8 x
1727.2 x 1295.4
1524 x
1168.4 x 1295.4
2209.8 x
1117.6 x 1295.4
Weight (lbs) 1,095 731 391 1,095 978 516 731
Appendix Reference Page no.
314 334 344 324 279 301 290
VPonce Rectangle
VPonce Text Box Scope of Work Preliminary Equipment Selections
Kuwait Transmitting Station Shortwave Building HVAC Systems Replacement Study
EJC International Services, LLC February 12, 2021 Page - 8
Table 3.2 – Option 3 AHU DX
Option 3 – Carrier DX Split Units – Air Handling Units DX Tag no. AHU-1 DX with heat AHU-2 to 4
DX & AHU-
10 DX
AHU-5
DX
AHU-6 DX AHU-7, 8
DX
AHU-9 DX
with heat
AHU-EU-
Model 39L 39L 39L 39L 40RUA 40RUA 40RUA
Size / tons 8 15 8 25 15 tons 7.5 tons 12.5 tons
Total capacity, MBH
Sensible capacity, MBH
CFM 3,960 6,800 3,600 12,000 6,000 3,200 4,500
ESP, in 0.55 0.50 0.55 0.45 0.65 0.65 0.5
EAT Dry/Wet, F 95/65 77/60 77/60 77/60 77/60 80/87 80/67
LAT Dry/Wet, F
Fan HP 3 5 2 7.5 5 5 5
Electrical, V/Ph/Hz 400/3/50 400/3/50 400/3/5
400/3/50 400/3/50 400/3/50 400/3/50
MCA 48 9.5 35.6 4.3
MOP 50 15 40 15
Heater, kW 25 - - - - 17.5* -
Dimensions LxWxH (ins)
76x50x61 108x65x40 57x50x6
84x77x101 89x56x29 49x57x29 89x57x2
Dimensions LxWxH (mm)
1930.4x12 70x 1549.4
2743.2x16 51x1016
1447.8x 1270x 1549.4
2209.8x19 55.8x2565.
2260.6x14 22.4x736.
1244.6x14 47.8x736.
2260.6x1 447.8x73 6.6
Weight (lbs) 1,062 1,317 863 1,902 750 425 750
Appendix Reference Page no.
218 234 248 253 279 301 290
*field installed
VPonce Rectangle
VPonce Text Box Scope of Work Preliminary Equipment Selections
AHU-7 and 8 DX Project: EJC- Kuwait 10/23/2020 Prepared By: Bryan Kurdziel 11:09AM
AHU-7 and 8 DX
Submittal Cover Sheet Unit Report
Performance Summary Report Acoustic Summary Certified Drawings
Commercial Split Systems Builder 1.39v Page 1 of 34
EJC International Services, LLC February 12, 2021 kwong Text Box kwong Text Box CU-7 and CU-8 kwong Text Box CU-7 and CU-8
Unit Report For AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Outdoor Unit Parameters Unit Quantity: 1 Unit Model: 38AUD Unit Size: 59.2 kW (15 Ton) Voltage: 400-3-50 V-Ph-Hz Condenser Coil: Cu/Cu No. of DX Circuits: 2 No. of Stages: Dual Stage
Indoor Unit Parameters Unit Model: 40RUA Unit Size: 59.2 kW (15 Ton) No. of Coils: 2 Voltage: 400-3-50 V-Ph-Hz
System Parameter System Quantity: 1 Refrigerant Type: PURON Compressor Quantity: 2 Compressor Type: Scroll Std. Capacity Steps: 50, 100 Std. Min. Outdoor Temp(Cooling): 35.0 °F No. of Outdoor fans: 3
Outdoor Unit Dimensions and Weight Unit Length: 7' 2.1'' Unit Width: 5' 7.1'' Unit Height: 4' 2.4'' Unit Shipping Weight: 978 lb Unit Operating Weight: 978 lb
Indoor Unit Dimensions and Weight Unit Length: 7' 5.0'' Unit Width: 2' 4.2'' Unit Height: 4' 8.1'' Unit Shipping Weight: 730 lb Unit Operating Weight: 730 lb
Warranty Information Outdoor (Note: for US & Canada only) First Year - Parts Only (Standard)
Warranty Information Indoor (Note: for US & Canada only) First Year - Parts Only (Standard)
NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
Base Unit - Outdoor
38AUDA25A0E9-0A0A0 1
Base Unit Cu/Cu Condensing Coil 1 Standard Refrigerant Options 1 Service Options - None 1 Electrical Options - None 1 Packaging Options - Standard 1
Base Unit - Indoor
40RUAA25A4A9-0A0A0 1
Commercial Split Systems Builder 1.39v Page 2 of 34
EJC International Services, LLC February 12, 2021
Unit Report For AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Base Unit Std Static, High Eff Motor/ Std Drive 1 Cabinet Paint - None 1
The 38AUZ/AUD are furnished with filter drier which is factory provided (field installed). Additional filter driers can be purchased separately through RCD (Replacement Components Division). See the Product Library for Replacement Filter Drier Information for more information.
Commercial Split Systems Builder 1.39v Page 3 of 34
Performance Summary For AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
System: 38AUD025/40RUA025 No. of Stages: Dual Stage System Quantity: 1 Altitude: 0.0 f t EER @ ARI Conditions: 12.2 Suction Line Loss: 1.4 °F Condensing unit is rated in accordance with ARI 365.
Typical Liquid and Suction Line Sizing
Pipe Length Liquid Line Size Suction Line Size
0 - 25 3/8 1 1/8 26 - 50 1/2 1 1/8 51 - 75 5/8 1 3/8 76 - 100 5/8 1 3/8 101 - 125 5/8 1 3/8 126 - 150 5/8 1 3/8 151 - 175 5/8 1 3/8 176 - 200 3/4 1 3/8
Refer to the 38AU installation instructions for installation specific line sizing guidance
Outdoor Unit Parameters Unit Quantity: 1 PartNumber: 38AUDA25A0E9-0A0A0 Unit Model: 38AUD Unit Size: 59.2 kW (15 Ton) Condenser Coil: Cu/Cu No. of DX Circuits: 2 Voltage: 400-3-50 V-Ph-Hz Clg Ent Air DB: 125.0 °F
Outdoor Electrical Data Unit Voltage: 400-3-50 V-Ph-Hz Unit MCA: 40.4 Amps Unit MOCP: 50.0 Amps Total Compressor Power of Unit: NA Voltage Range Min: 360 V Voltage Range Max: 440 V Compressor RLA: 16.7/16.7 Compressor LRA: 111/111 Compressor Quantity: 2 Fan Motors Qty: 3 Fan Motor FLA: 0.7 Amps Notice: Outdoor unit elect. data is based on 400-3-50 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Indoor Unit Parameters PartNumber: 40RUAA25A4A9-0A0A0 Unit Model: 40RUA Unit Size: 59.2 kW (15 Ton) Coil Rows: 4 No. of Splits: 2 Voltage: 400-3-50 V-Ph-Hz Actual Airflow: 6000.0 CFM Standard Airflow: 6000.0 CFM Total Clg Cap.(Gross): 178.5 MBH Sensible Clg Cap.(Gross): 143.3 MBH Ent Air DB: 80.0 °F Ent Air WB: 67.0 °F
Commercial Split Systems Builder 1.39v Page 4 of 34
Prepared By: Bryan Kurdziel 11:09AM
Ent Enthalpy: 31.44 BTU/lb Lvg Air DB: 57.9 °F Lvg Air WB: 57.7 °F Lvg Enthalpy: 24.83 BTU/lb Coil Bypass Factor: NA
Indoor Supply Fan Indoor Unit External Static: 0.65 in wg Economizer Loss: 0.00 in wg Grille Loss: 0.00 in wg Plenum Loss: 0.00 in wg Acc. Heating Loss: 0.00 in wg Total Ext Static: 0.65 in wg Fan Speed: 733 RPM Fan Power: 2.19 BHP Fan Motor Max: 5.00 BHP Fan Motor FLA: 7.6 Amps Motor and Standard Drive Required.
Selected Standard Drive Range: 713 - 878 RPM
Indoor Electrical Data Unit Voltage: 400-3-50 V-Ph-Hz Unit MCA: 9.5 Amps Unit MOCP: 15.0 Amps Notice: Indoor unit elect. data is based on 400-3-50
Acoustics Sound Power Levels, db re 10E-12 Watts
A-Weighted Outdoor Unit (dB) Indoor Unit (dB,Ducted)
Total Level 85.2 96.4 63Hz 64.8 76.4 125Hz 68.9 82.5 250Hz 71.4 86.0 500Hz 82.8 92.4 1000Hz 79.0 89.6 2000Hz 74.2 88.8 4000Hz 69.0 84.6 8000Hz 61.9 NA Sound Message Sound for AUD025 Sound for RUA025
Acoustic Notes:
1. 38AUZ/D/Q units sound ratings are in accordance with AHRI 270-2008 - Sound Rating of Outdoor Unitary Equipment.
2. 40RU units sound ratings are in accordance with AHSRAE 1987 HVAC Systems and Applications handbook.
3. The acoustic center of the unit is located at the geometric center of the unit.
Commercial Split Systems Builder 1.39v Page 5 of 34
Prepared By: Bryan Kurdziel 11:09AM
Advanced Acoustics Parameters
1. Unit height above ground: 1.0 f t
2. Horizontal distance from unit to receiver: 20.0 f t
3. Receiver height above ground: 5.7 f t
4. Height of obstruction: 0.0 f t
5. Horizontal dist. from obstruction to receiver: 0.0 f t
6. Horizontal dist. from unit to obstruction: 0.0 f t
Detailed Acoustics Information
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB 91 85 80 86 79 73 68 63 93 A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
65 69 71 83 79 74 69 62 85
Sound Press. Levels at Dist. Specified above (Lp), dB 66 60 55 61 54 48 43 38 69 A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
40 44 47 58 54 50 44 37 61
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Commercial Split Systems Builder 1.39v Page 6 of 34
Prepared By: Bryan Kurdziel 11:09AM
400 RPM
500 RPM
600 RPM
700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
1200 RPM
3.70 BHP 5.00 BHP
7.50 BHP
10.00 BHP
SC
RP
40RUA025 with Standard Capacity Coil
SC - System Curve RP - Rated Point MP - Minimum Point Shaded Area - Recommended Operating Range
RPM = 733 BHP = 2.19 Maximum RPM = 1200 Maximum HP = 5.00
St at ic P re ss ur e
(in . w g.
Airflow (CFM - thousands) 0 2 4 6 8 10 12 14
Commercial Split Systems Builder 1.39v Page 7 of 34
Acoustic Summary For AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Outdoor Unit Parameters:
Tag Name: AHU-7 and 8 DX Unit Model: 38AUD Unit Size: 59.2 kW (15 Ton) System Type: Dx Cooling Only Refrigerant Type: PURON Compressor Quantity: 2 Compressor Type: Scroll
Advanced Accoustics Parameters
1. Unit height above ground: 1.0 f t
2. Horizontal distance from unit to receiver: 20.0 f t
3. Receiver height above ground: 5.7 f t
4. Height of obstruction: 0.0 f t
5. Horizontal distance from obstruction to receiver: 0.0 f t
6. Horizontal distance from unit to obstruction: 0.0 f t
Detailed Acoustics Information
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB 91 85 80 86 79 73 68 63 93 A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
65 69 71 83 79 74 69 62 85
Sound Press. Levels at Dist. Specified above (Lp), dB 66 60 55 61 54 48 43 38 69 A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
40 44 47 58 54 50 44 37 61
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Acoustic Note:
1. 38AUZ/D/Q units sound ratings are in accordance with AHRI 270-2008 - Sound Rating of Outdoor Unitary Equipment.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.
Acoustic Note:
1. Estimated Sound Power levels - dB re: 1 picowatt
2. Estimated Sound Pressure levels - dB re: 20 micropascal
3. Estimated sound levels given above are assumed to originate at the acoustic center of the unit. The acoustic center of the unit is located at the projection of the condensing unit's geometric center of its base.
4. Sound power levels shown above were determined in accordance with ARI standard 370 for large outdoor refrigeration and air conditioning equipment.
5. Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the ARI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Commercial Split Systems Builder 1.39v Page 8 of 34
Acoustic Summary For AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Indoor Unit Parameters:
Tag Name: AHU-7 and 8 DX Unit Model: 40RUA Unit Size: 59.2 kW (15 Ton) System Type: Dx Cooling Only External Static Pressure: 0.65 in wg Fan Speed: 733 RPM Fan BHP: 2.19 BHP
Detailed Acoustics Information
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total
Sound Power,dB NA 103 99 95 96 90 88 84 NA 105 A-Weighted Sound Power, dBA NA 76 83 86 92 90 89 85 NA 96
Acoustic Notes:
1. 40RU units sound ratings are in accordance with AHSRAE 1987 HVAC Systems and Applications handbook.
2. The acoustic center of the units is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.
Commercial Split Systems Builder 1.39v Page 9 of 34
Certified Drawing for AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Commercial Split Systems Builder 1.39v Page 10 of 34
Certified Drawing for AHU-7 and 8 DX
Prepared By: Bryan Kurdziel 11:09AM
Commercial Split Systems Builder 1.39v Page 11 of 34
AHU-9 DX
Project: EJC- Kuwait 10/26/2020 Prepared By: Bryan Kurdziel 10:02AM
AHU-9 DX
Submittal Cover Sheet Unit Report
Performance Summary Report Acoustic Summary Certified Drawings
Commercial Split Systems Builder 1.39v Page 1 of 13
EJC International Services, LLC February 12, 2021 kwong Text Box
CU-9
kwong Text Box kwong Text Box
CU-9
Unit Report For AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
Outdoor Unit Parameters Unit Quantity: 1 Unit Model: 38AUD Unit Size: 29.1 kW (7.5 Ton) Voltage: 400-3-50 V-Ph-Hz Condenser Coil: Cu/Cu No. of DX Circuits: 2 No. of Stages: Dual Stage
Indoor Unit Parameters Unit Model: 40RUA Unit Size: 29.1 kW (7.5 Ton) No. of Coils: 2 Voltage: 400-3-50 V-Ph-Hz
System Parameter System Quantity: 1 Refrigerant Type: PURON Compressor Quantity: 2 Compressor Type: Scroll Std. Capacity Steps: 50, 100 Std. Min. Outdoor Temp(Cooling): 35.0 °F No. of Outdoor fans: 2
Outdoor Unit Dimensions and Weight Unit Length: 4' 11.4'' Unit Width: 3' 9.9'' Unit Height: 4' 2.4'' Unit Shipping Weight: 516 lb Unit Operating Weight: 516 lb
Indoor Unit Dimensions and Weight Unit Length: 4' 1.0'' Unit Width: 2' 4.2'' Unit Height: 4' 8.1'' Unit Shipping Weight: 425 lb Unit Operating Weight: 425 lb Add Service Clearance for Accy Heater: 2' 6.0''
Warranty Information Outdoor (Note: for US & Canada only) First Year - Parts Only (Standard)
Warranty Information Indoor (Note: for US & Canada only) First Year - Parts Only (Standard)
NOTE: Please see Warranty Catalog 808-218 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
Base Unit - Outdoor
38AUDA12A0E9-0A0A0 1
Base Unit Cu/Cu Condensing Coil 1 Standard Refrigerant Options 1 Service Options - None 1 Electrical Options - None 1 Packaging Options - Standard 1
Base Unit - Indoor
Commercial Split Systems Builder 1.39v Page 2 of 13
Unit Report For AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
40RUAA12A2A9-0A0A0 1
Base Unit Std Motor / Medium Drive 1 Cabinet Paint - None 1
CAELHEAT011A00 25.0 kW, 480-3-60 and 17.5 kW, 400-3-50 Electric Heater 1
The 38AUZ/AUD are furnished with filter drier which is factory provided (field installed). Additional filter driers can be purchased separately through RCD (Replacement Components Division). See the Product Library for Replacement Filter Drier Information for more information.
Commercial Split Systems Builder 1.39v Page 3 of 13
Performance Summary For AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
System: 38AUD012/40RUA012 No. of Stages: Dual Stage System Quantity: 1 Altitude: 0.0 f t EER @ ARI Conditions: 12.6 Suction Line Loss: 1.4 °F
Typical Liquid and Suction Line Sizing
Pipe Length Liquid Line Size Suction Line Size
0 - 25 3/8 3/4 26 - 50 3/8 7/8 51 - 75 3/8 7/8 76 - 100 1/2 1 1/8 101 - 125 1/2 1 1/8 126 - 150 1/2 1 1/8 151 - 175 5/8 1 1/8 176 - 200 5/8 1 1/8
Refer to the 38AU installation instructions for installation specific line sizing guidance
Outdoor Unit Parameters Unit Quantity: 1 PartNumber: 38AUDA12A0E9-0A0A0 Unit Model: 38AUD Unit Size: 29.1 kW (7.5 Ton) Condenser Coil: Cu/Cu No. of DX Circuits: 2 Voltage: 400-3-50 V-Ph-Hz Clg Ent Air DB: 125.0 °F
Outdoor Electrical Data Unit Voltage: 400-3-50 V-Ph-Hz Unit MCA: 19.0 Amps Unit MOCP: 25.0 Amps Total Compressor Power of Unit: NA Voltage Range Min: 360 V Voltage Range Max: 440 V Compressor RLA: 7.8/7.8 Compressor LRA: 52/52 Compressor Quantity: 2 Fan Motors Qty: 2 Fan Motor FLA: 0.7 Amps Notice: Outdoor unit elect. data is based on 400-3-50 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Indoor Unit Parameters PartNumber: 40RUAA12A2A9-0A0A0 Unit Model: 40RUA Unit Size: 29.1 kW (7.5 Ton) Coil Rows: 4 No. of Splits: 2 Voltage: 400-3-50 V-Ph-Hz Actual Airflow: 3200.0 CFM Standard Airflow: 3200.0 CFM Total Clg Cap.(Gross): 86.4 MBH Sensible Clg Cap.(Gross): 72.7 MBH Ent Air DB: 80.0 °F Ent Air WB: 67.0 °F Ent Enthalpy: 31.44 BTU/lb
Commercial Split Systems Builder 1.39v Page 4 of 13
Prepared By: Bryan Kurdziel 10:02AM
Lvg Air DB: 59.0 °F Lvg Air WB: 58.6 °F Lvg Enthalpy: 25.44 BTU/lb Coil Bypass Factor: NA
Accessory Heating Heating Type: Electric Acc Htg Capacity: 59.03 MBH Acc Htg Ent. Air Temp: 60.0 °F Acc Htg Lvg. Air Temp: 77.1 °F Acc Heater Nominal Voltage: 400-3-50 Acc Heater Nominal kW: 17.5 kW Acc Heater Actual Voltage: 400-3-50 Acc Heater FLA: 25.1 amps Acc Stage 1 Actual kW: 10.4 kW Acc Stage 2 Actual kW: 6.9 kW
Indoor Supply Fan Indoor Unit External Static: 0.65 in wg Economizer Loss: 0.00 in wg Grille Loss: 0.00 in wg Plenum Loss: 0.00 in wg Acc. Heating Loss: 0.11 in wg Total Ext Static: 0.76 in wg Fan Speed: 808 RPM Fan Power: 1.37 BHP Fan Motor Max: 2.90 BHP Fan Motor FLA: 3.4 Amps Motor and Medium Static Drive Required.
Selected Medium Static Drive Range: 808 - 1045 RPM
Indoor Electrical Data Unit Voltage: 400-3-50 V-Ph-Hz Unit MCA: 35.6 Amps Unit MOCP: 40.0 Amps Notice: Indoor unit elect. data is based on 400-3-50
Acoustics Sound Power Levels, db re 10E-12 Watts
A-Weighted Outdoor Unit (dB) Indoor Unit (dB,Ducted)
Total Level 80.1 91.7 63Hz 49.8 72.4 125Hz 63.8 78.5 250Hz 71.2 82.0 500Hz 74.2 86.4 1000Hz 75.6 85.6 2000Hz 71.0 84.8 4000Hz 68.8 80.6 8000Hz 65.3 NA Sound Message Sound for AUD012 Sound for RUA012
Acoustic Notes:
1. 38AUZ/D/Q units sound ratings are in accordance with AHRI 270-2008 - Sound Rating of Outdoor Unitary Equipment.
2. 40RU units sound ratings are in accordance with AHSRAE 1987 HVAC Systems and Applications handbook.
3. The acoustic center of the unit is located at the geometric center of the unit.
Commercial Split Systems Builder 1.39v Page 5 of 13
Prepared By: Bryan Kurdziel 10:02AM
Advanced Acoustics Parameters
1. Unit height above ground: 1.0 f t
2. Horizontal distance from unit to receiver: 20.0 f t
3. Receiver height above ground: 5.7 f t
4. Height of obstruction: 0.0 f t
5. Horizontal dist. from obstruction to receiver: 0.0 f t
6. Horizontal dist. from unit to obstruction: 0.0 f t
Detailed Acoustics Information
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB 76 80 80 77 76 70 68 66 85 A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
50 64 71 74 76 71 69 65 80
Sound Press. Levels at Dist. Specified above (Lp), dB 52 56 55 53 51 45 43 42 61 A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
25 39 47 50 51 47 44 41 56
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Commercial Split Systems Builder 1.39v Page 6 of 13
Prepared By: Bryan Kurdziel 10:02AM
400 RPM
500 RPM
600 RPM
700 RPM
800 RPM
900 RPM
1000 RPM
1100 RPM
1200 RPM
2.00 BHP 2.40 BHP
2.90 BHP
3.00 BHP
3.70 BHP
5.00 BHP
7.50 BHP
SC
RP
40RUA012 with Standard Capacity Coil
SC - System Curve RP - Rated Point MP - Minimum Point Shaded Area - Recommended Operating Range
RPM = 808 BHP = 1.37 Maximum RPM = 1200 Maximum HP = 2.90
St at ic P re ss ur e
(in . w g.
Airflow (CFM - thousands) 0 1 2 3 4 5 6 7
Commercial Split Systems Builder 1.39v Page 7 of 13
Acoustic Summary For AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
Outdoor Unit Parameters:
Tag Name: AHU-9 DX Unit Model: 38AUD Unit Size: 29.1 kW (7.5 Ton) System Type: Dx Cooling Only Refrigerant Type: PURON Compressor Quantity: 2 Compressor Type: Scroll
Advanced Accoustics Parameters
1. Unit height above ground: 1.0 f t
2. Horizontal distance from unit to receiver: 20.0 f t
3. Receiver height above ground: 5.7 f t
4. Height of obstruction: 0.0 f t
5. Horizontal distance from obstruction to receiver: 0.0 f t
6. Horizontal distance from unit to obstruction: 0.0 f t
Detailed Acoustics Information
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k 8k Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB 76 80 80 77 76 70 68 66 85 A-Wgted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
50 64 71 74 76 71 69 65 80
Sound Press. Levels at Dist. Specified above (Lp), dB 52 56 55 53 51 45 43 42 61 A-Wgted Sound Press. Levels at Dist. Specified above (LpA), dBA
25 39 47 50 51 47 44 41 56
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Acoustic Note:
1. 38AUZ/D/Q units sound ratings are in accordance with AHRI 270-2008 - Sound Rating of Outdoor Unitary Equipment.
2. The acoustic center of the unit is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.
Acoustic Note:
1. Estimated Sound Power levels - dB re: 1 picowatt
2. Estimated Sound Pressure levels - dB re: 20 micropascal
3. Estimated sound levels given above are assumed to originate at the acoustic center of the unit. The acoustic center of the unit is located at the projection of the condensing unit's geometric center of its base.
4. Sound power levels shown above were determined in accordance with ARI standard 370 for large outdoor refrigeration and air conditioning equipment.
5. Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the ARI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.
Commercial Split Systems Builder 1.39v Page 8 of 13
Acoustic Summary For AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
Indoor Unit Parameters:
Tag Name: AHU-9 DX Unit Model: 40RUA Unit Size: 29.1 kW (7.5 Ton) System Type: Dx Cooling Only External Static Pressure: 0.76 in wg Fan Speed: 808 RPM Fan BHP: 1.37 BHP
Detailed Acoustics Information
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total
Sound Power,dB NA 99 95 91 90 86 84 80 NA 101 A-Weighted Sound Power, dBA NA 72 79 82 86 86 85 81 NA 92
Acoustic Notes:
1. 40RU units sound ratings are in accordance with AHSRAE 1987 HVAC Systems and Applications handbook.
2. The acoustic center of the units is located at the geometric center of the unit.
3. All estimated sound power levels, dB re 1 Picowatt should not be guaranteed or certified as being the actual sound power levels.
Commercial Split Systems Builder 1.39v Page 9 of 13
Certified Drawing for AHU-9 DX
Prepared By: Bryan Kurdziel 10:02AM
Commercial Split Systems Builder 1.39v Page 10 of 13
Prepared By: Bryan Kurdziel 10:02AM
Commercial Split Systems Builder 1.39v Page 11 of 13
Prepared By: Bryan Kurdziel 10:02AM
Commercial Split Systems Builder 1.39v Page 12 of 13
Prepared By: Bryan Kurdziel 10:02AM
Commercial Split Systems Builder 1.39v Page 13 of 13