This document provides guidance for premise wiring installations on Keesler Air Force Base. It supplements Telecommunications Industry Association and Electronic Industry Alliance commercial standards. The guidance covers racks and cabinets, cabling requirements including category ratings and color coding, termination standards, cable management best practices, and labeling conventions. Detailed specifications are provided for outlet, cable, and equipment labeling. A list of references is included specifying applicable national and military standards.

The related federal contract opportunity is a solicitation for fiber optic cable installations to various facilities on Keesler Air Force Base. The estimated value is between $500,000 and $1,000,000 and it is set aside for small businesses. The pre-proposal site visit will take place on July 12, 2021. Proposals are due based on instructions in the solicitation. The work will be awarded to a single contractor and is being issued by the Air Force Air Education and Training Command. Health and safety protocols for COVID-19 are outlined.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

This guide is supplemental in nature and not all inclusive.

PREMISE WIRING GUIDANCE

Revision B-1, Sep 2019

81st COMMUNICATIONS SQUADRON PREMISE WIRING GUIDANCE

Revision B, April 2016 Page 2 of 12

GENERAL

1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network cabling) on Keesler AFB.

2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 376- 6325 prior to implementation.

3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.

4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.

5. Contractual responsibilities:

5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.

5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.

5.3 Provide test results for new\relocated premise wiring work accomplished.

5.4 Contractors shall be responsible for restoring work areas to original condition.

5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.

Revision B, April 2016 Page 3 of 12

RACKS/CABINETS (If installed)

Cabinets/Racks will be labeled on the front and rear at the top and bottom on a permanent part of the cabinet/rack. Text on labels shall be machine printed without serifs, uppercase and large enough to be read while standing near the cabinet/rack. The label color will contrast with surface upon which it is affixed (white on a dark surface, black on a light surface)(ANSI/TIA/EIA-606-A-1 section 11).

RACK 1 RACK 1

RACK 1 RACK 1

Revision B, April 2016 Page 4 of 12

CABLING

All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated.

Cat 5e UTP

Cat 6 UTP

Cat 6 FTP

Cat 6A UTP

CABLE COLOR CODING

All installations and renovations will use the following cable color code:

Alarms/Cameras – yellow Public Address (PA) Systems – gray Secure Comm (encrypted) – red Data/Voice - blue

Revision B, April 2016 Page 5 of 12

TERMINATIONS

All premise cabling supporting a Local Area Network will be terminated using

568B standards.

Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.

Revision B, April 2016 Page 6 of 12

CABLE MANAGEMENT

The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. Metal raceways (cable ladder or wire basket) shall be installed and/or utilized in all communication rooms.

Cable trays shall be installed and/or utilized in all communication rooms.

Cables will be independently supported off the ceiling with supports no more than 60 inches apart.

Cable route should avoid fluorescent light ballasts, electrical cables and motors.

Revision B, April 2016 Page 7 of 12

CABLE MANAGEMENT (continued)

Cable jackets must not be distorted. Velcro or nylon are acceptable –

Velcro is better at protecting cable geometry. Staples will not be used.

Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.

Revision B, April 2016 Page 8 of 12

LABELING

All labeling shall be machine generated, without serifs, uppercase and large enough to be easily read (ANSI/TIA/EIA-606-A-1 section 11).

The naming scheme shall also be coordinated with the 81st Communications Squadron (81 CS/SCXP).

Outlet(s)

Patch Panel(s)

Example of a single quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Example of a second quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #5 of the patch panel

32-1

A B C D

32-2

A B C D

Example of RACK 1 PANEL 1 located in TR 110 and connecting to Room 32 Outlets 1 and 2.

Revision B, April 2016 Page 9 of 12

LABELING (continued)

Cables - All cables will be labeled on both ends with encoded identifiers per (ANSI/TIA/EIA-606-A-1 section 11).

(located within 12 inches of faceplate) (located within 12 inches of patch panel)

110-1-1-1

110-1-1-2

110-1-1-3

110-1-1-4

32-1-A

32-1-B

32-1-C

32-1-D

RACK 1

Example of a single quad data outlet located in room 32 and terminated in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Revision B, April 2016 Page 10 of 12

GROUNDING (TIA-607-B) (If installed)

All grounds will be labeled (ANSI/TIA-607-B para 7.8) (if installed).

All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).

Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-B para 7.1.4).

Revision B, April 2016 Page 11 of 12

Premise Wiring References

NUMBER TITLE WEBSITE OR LOCATION

BICSI TDM Manual Building Industries Consulting Services International (BICSI) Telecommunications Distribution Methods (TDM) Manual http://www.bicsi.org/

NFPA 70 (2008) National Fire Protection Association (NFPA), National Electric Code (NEC) http://www.nfpa.org/

29 CFR 1910.268 Occupational Safety and Health Standards, Telecommunications http://www.osha.gov

ANSI American National Standards Institute (ANSI) and Internet Standards Resources http://www.ansi.org/

EIA/TIA Engineering: EIA/TIA Standards See Commodity Specific Appendices and Individual Task Orders http://www.eia.org/ http://www.tiaonline.org/

TIA/EIA-526-7 (Feb 2002)

Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant – OFSTP-7 http://www.eia.org/ http://www.tiaonline.org/

ANSI/TIA-568-C.0

(Feb2009)

Generic Telecommunications Cabling for Customer Premises http://www.eia.org/ http://www.tiaonline.org/

ANSI/TIA-568-C.1

(Feb 2009)

Commercial Building Telecommunications Cabling Standard http://www.eia.org/ http://www.tiaonline.org/

TIA/EIA-568-B.2-10

(Mar 2008)

Transmission Performance Specifications for 4-Pair 100 Ohm Augmented Category 6 Cabling http://www.eia.org/ http://www.tiaonline.org/

ANSI/TIA-568-C.3

(Jun 2008)

Optical Cabling Components Standard http://www.eia.org/ http://www.tiaonline.org/

ASTM D4566 (2008) Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable http://webstore.ansi.org/

TIA/EIA-569-B (Oct 2004)

Commercial Building Standards for Telecommunications Pathways and Spaces http://www.eia.org/ http://www.tiaonline.org/

TIA/EIA-570-B (Apr 2004)

Residential Telecommunications Cabling Standard http://www.eia.org/ http://www.tiaonline.org/

TIA/EIA-598-C (Jan 2005)

Optical Fiber Cable Color Coding http://www.eia.org/ http://www.tiaonline.org/ http://www.bicsi.org/ http://www.nfpa.org/ http://www.osha.gov/ http://www.ansi.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://webstore.ansi.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/

Revision B, April 2016 Page 12 of 12

TIA/EIA-606-A (May 2002)

Administration Standard for the Telecommunications Infrastructure of Commercial Buildings http://www.eia.org/ http://www.tiaonline.org/

J-STD-607-A

(Oct 2002)

Commercial Building Grounding and Bonding Requirements for Telecommunications http://www.eia.org/ http://www.tiaonline.org/

TIA/EIA-758-A (Aug 2004)

Customer-Owned Outside Plant Telecommunications Infrastructure Standard http://www.eia.org/ http://www.tiaonline.org/

EIA-310-D (Sep 1992)

Racks, Panels and Associated Equipment http://www.eia.org/ http://www.tiaonline.org/

ICEA S-80-576 (2002) Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems http://www.icea.net/Public_Pages/ Documents/Communications_Cab le_Standards.html --http://store.ihs.com/

ICEA S-83-596

(2001)

Fiber Optic Premises Distribution Cable http://www.icea.net/Public_Pages/ Documents/Communications_Cab le_Standards.html --http://store.ihs.com/

GR-409, Issue 2 (Nov 2008)

Generic Requirements for Indoor Fiber Optic Cable http://telecom-info.telcordia.com/site-cgi/ido/index.html

GR-20, Issue 3 (May 2008)

Generic Requirements for Optical Fiber and Optical Fiber Cable http://telecom-info.telcordia.com/site-cgi/ido/index.html

NEMA TC 2 (2003) Electrical Polyvinyl Chloride (PVC) Tubing and Conduit http://www.nema.org/stds/tc2.cfm

NEMA TC 6&8

(2003)

PVC Plastic Utilities Duct for Underground Installations http://www.nema.org/stds/tc6_8.c fm

NEMA TC 9 (2004) Fittings for PVC Plastic Utilities Duct for Underground Installation http://www.nema.org/stds/tc9.cfm

RUS Bulletin 1751F-

Underground Plant Design http://www.usda.gov/rus/telecom/ publications/bulletins.htm

RUS Bulletin 1753F-

801(PC-5A)

RUS Standard for Service Installations at Customer Access Locations http://www.usda.gov/rus/telecom/ publications/bulletins.htm

RUS Bulletin 345-54

(PE-52)

RUS Specification for Telephone Cable Splicing Connectors http://www.usda.gov/rus/telecom/ publications/bulletins.htm

RUS Bulletin 1753F-

RUS Specifications for Filled Fiber Optic Cables (PE-90) http://www.usda.gov/rus/telecom/ publications/bulletins.htm http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.eia.org/ http://www.tiaonline.org/ http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://store.ihs.com/ http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://www.icea.net/Public_Pages/Documents/Communications_Cable_Standards.html http://store.ihs.com/ http://telecom-info.telcordia.com/site-cgi/ido/index.html http://telecom-info.telcordia.com/site-cgi/ido/index.html http://telecom-info.telcordia.com/site-cgi/ido/index.html http://telecom-info.telcordia.com/site-cgi/ido/index.html http://telecom-info.telcordia.com/site-cgi/ido/index.html http://telecom-info.telcordia.com/site-cgi/ido/index.html http://www.nema.org/stds/tc2.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc9.cfm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm http://www.usda.gov/rus/telecom/publications/bulletins.htm