About this file
This Statement of Objectives (SOO) outlines requirements for a contractor to engineer, furnish, install, and test fiber optic cable and infrastructure to connect three facilities at Keesler Air Force Base in Mississippi. The contractor shall install approximately 900 feet of 12-strand single-mode fiber optic cable from ITB 4223 to Building 4426 and approximately 1,300 feet of 12-strand single-mode fiber optic cable from ITB 4223 to Building 4267. The work includes installing new conduit, innerduct, pull boxes, and fiber distribution panels. The contractor must comply with TIA installation and testing standards as well as the base's wiring guide.
The related federal contract opportunity is a small business set-aside solicitation from the Air Force seeking proposals for the fiber optic cable installation described in the SOO. Proposals are due on 12 July 2021, and the site visit will be held that day. The opportunity is valued between $500,000 and $1,000,000. Offerors should review proposal preparation instructions and evaluation criteria.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF OBJECTIVES (SOO)
Fiber Optic Cable to Support Connectivity ITB 4223 to B4426 & B4267
Project #: MAHG-2020-00004-00001
KEESLER AFB MS
15 June 2021
Prepared By:
38 ES/ENII
4064 Hilltop Road Tinker AFB OK 73145-2713
Fiber Optic Cable to Support Connectivity ITB 4223 to B4426 & B4267, Keesler AFB MS
Table of Contents
1.0 SCOPE 3
2.0 SPECIFIC REQUIREMENTS 3
2.1. Outside Plant Requirements 3
2.1.1. Measurements 3
2.1.2. Fiber Optic Distribution Panel (FODP) 3
2.2. Outside Plant Installation 3
2.2.1. Infrastructure Installation 3
2.2.2. Concrete Pull Box (Quazite) 3
2.2.3. Duct bank Infrastructure 4
2.2.4. Geotextile Inner-duct (or Innerduct) 4
2.2.5. Fiber Optic Cable Installation 4
1.0 SCOPE
This SOO lists the objectives for the Contractor to engineer, furnish, install and test (EFI&T) required fiber optic cable to connect ITB 4223 to B4426 and B4267 at Keesler
AFB MS.
2.0 SPECIFIC REQUIREMENTS
As indicated in this SOO, the Contractor shall EFI&T two (2), 12 strand SM fiber optic cable (FOC) from ITB 4223 to B4426 & B4267 at Keesler AFB MS.
The Contractor shall provide a Statement of Work (SOW) as part of their proposal incorporating all equipment, tools, materials, supplies, transportation, labor, supervision, management, and other incidentals necessary to meet the requirements as stated in this
SOO.
The Contractor shall comply with the current TIA telecommunication installation and testing commercial standards and Keesler AFB Premise Wiring Guide.
All equipment, supplies, and materials provided shall be new and not refurbished.
2.1. Outside Plant Requirements
2.1.1. Measurements
Any distances provided in this SOO are approximations and should NOT be used for ordering materials or determining duct lengths.
2.1.2. Fiber Optic Distribution Panel (FODP)
The Contractor shall install the following FODPs. Coordinate with 81 CS/SCOIV for final mounting location within existing racks.
• ITB4223: Install one (1) hi-density 24 port FODP in existing rack.
• B4426: Install one (1) hi-density 12 port FODP in existing rack.
• B4267: Install one (1) hi-density 12 port FODP in existing rack.
2.2. Outside Plant Installation
Outside Plant Installation shall be accomplished in accordance with paragraph 8.0 of the Supplemental Information attachment. The Contractor is to propose their own solution and recommendations pertaining to the accomplishment of this requirement in their proposal.
The Contractor shall install underground outside plant infrastructure as described below.
2.2.1. Infrastructure Installation
The contractor shall install the following new infrastructure. All new locations and distances are approximate.
2.2.2. Concrete Pull Box (Quazite)
The existing concrete pull box QB-4267 is damaged. The contractor shall install a new concrete pull box (Quazite may be used if necessary) to replace the existing one. Coordinate with 81 CS/SCOIV prior to final placement and numbering.
2.2.3. Duct bank Infrastructure
Install the following PVC Duct banks
From Manhole
To Manhole
Qty Size Approx.
Distance (Feet)
Comment
MH-104C QB-4426 1 4” 125 Directional Bore
2.2.4. Geotextile Inner-duct (or Innerduct)
Install the following 3” 3-cell Geotextile Inner-ducts
From To Qty Approx.
Distance (Feet)
Comment
MH-104B MH-104C 3 410 Install in existing conduit
MH-104C QB-4426 3 125 Install in new conduit.
QB-4426 B4426 3 10 Install in existing conduit
QB-4426 New QB-4267 3 265 Install in existing conduit
New QB-4267 B4267 3 50 Install in existing conduit
2.2.5. Fiber Optic Cable Installation
The Contractor shall install single mode (SM), loose buffer tube, water blocked, outside plant (OSP) fiber optic (FOC) cable suitable for underground applications.
The intent is to install the cable in one continuous length, to the extent that it is practical. The cable shall meet RUS 7 CFR 1755.900 criteria; shall comply with industry standards with regard to manufacturers’ cable marking, jacket, rip cords, water blocking, fiber color coding, jacketing materials, etc. In addition, the FOC shall comply with industry standards with regard to mode field diameter, core cladding concentricity, attenuation, and dispersion characteristics at 1310 nm and 1550nm.
All fiber optic cables shall be installed in new or existing geotextile innerduct/ innerduct.
2.2.5.1. From ITB 4223 to B4426
The Contractor shall install approximately 900’ of 12 strand SM FOC from ITB 4223 to B4426 via MH-104B, MH104C, QB-4426. Terminate new 12 strand SM FOC in FODP provided per paragraph 2.1.2.
2.2.5.2. From ITB 4223 to B4267
The Contractor shall install approximately 1,300’ of 12 strand SM FOC from ITB 4223 to B4267 via MH-104B, MH-104C, QB-4426, New QB- 4267. Terminate new 12 strand SM FOC in FODP provided per paragraph 2.1.2
| 1.0 SCOPE |
| 2.0 SPECIFIC REQUIREMENTS |
| 2.1. Outside Plant Requirements |
| 2.1.1. Measurements |
| 2.1.2. Fiber Optic Distribution Panel (FODP) |
| 2.2. Outside Plant Installation |
| 2.2.1. Infrastructure Installation |
| 2.2.2. Concrete Pull Box (Quazite) |
| 2.2.3. Duct bank Infrastructure |
| 2.2.4. Geotextile Inner-duct (or Innerduct) |
| 2.2.5. Fiber Optic Cable Installation |
| 2.2.5.1. From ITB 4223 to B4426 |
| 2.2.5.2. From ITB 4223 to B4267 |