Attachment_4_142010-26-0153.pdf

PDF 470 KB Posted

Attached to
NWS HVAC PREVENTIVE MAINTENANCE (PM) ML in Ohio
Solicitation number
1305M326Q0387
Issued by

About this file

This is an Installation, Operation and Maintenance Manual for Carnes electronically controlled steam humidifiers, Design Series "E," along with a Unit Nomenclature specification guide. The document provides comprehensive technical specifications for steam humidifier models ranging from 5 to 200 pounds per hour (Lb/Hr) output capacity.

The manual details installation requirements including unpacking procedures, mounting specifications with maximum operating weights ranging from 80 to 185 pounds depending on model, water supply connections using ordinary tap water at 20-120 psi, and drain line configurations. Key installation elements include proper ductwork placement with minimum clearances (6 feet minimum, 14 inches minimum from cabinet to distributor pipe, 16 inches minimum from cabinet bottom to floor), steam distributor pipe mounting on plumb surfaces, and condensate return line management. Electrical specifications cover voltage options from 115V single-phase through 575V three-phase with detailed power requirements, circuit breaker recommendations, and maximum line amperage ratings. The nomenclature guide defines model selection codes including cabinet type (stainless steel with or without breakers), unit type (single or dual steam cylinders), voltage configurations, nominal steam output capacity, agency listings (UL/cUL), and communication protocol options (BACnet MS/TP, Modbus RTU, Metasys M2, Siemens FLN). Operation sections cover startup procedures, steam output rate adjustment, automatic drain cycles, and low conductivity water operation. Maintenance guidance includes routine visual inspection at two-week intervals, water strainer cleaning procedures, cylinder replacement instructions, and troubleshooting protocols addressing common issues such as water in duct, arcing/sparking, continuous draining, and fill failures. Cylinder life averages 1150 hours at maximum output with 150 ppm water hardness, with correction factors provided for varying water hardness levels and operating percentages.

View the file

Other files

File Type Posted
Sol_1305M326Q0387_Amd_0001.pdf PDF
Attachment_8_142010-26-0153.pdf PDF
Attachment_3_142010-26-0153.pdf PDF
Sol_1305M326Q0387.pdf PDF
Attachment_9_142010-26-0153.pdf PDF
Attachment_5_142010-26-0153.docx DOCX document
Attachment_6_142010-26-0153.pdf PDF
Attachment_1_142010-26-0153.pdf PDF
Attachment_2_142010-26-0153.pdf PDF
Attachment_7_142010-26-0153.pdf PDF
Wage_Determination_No__2015_4769.txt TXT text file
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Humidifiers | Unit Nomenclature

H um idifiers

G-22 www.carnes.com

DesignNominal SteamComm.
ModelSeriesElectricalOutput CapacityOptionsOptions
1234567891011

H S A J A U 0 1 0

H - Humidifier

S -Stainless Steel (304)
Cabinet (w/o Breakers)
T -Stainless Steel (304)
Cabinet (w/ Breakers)

Unit Type A - 1 “AX” Cylinder D - 1 “B” Cylinder G - 1 “C” Cylinder H - 2 “C” Cylinders

AGENCY

LISTING

U - UL

C - cUL

VOLTAGE

A - 115V, 1 Ph.

B - 208V, 1 Ph.

C - 208V, 3 Ph.

D - 230V, 1 Ph.

E - 230V, 3 Ph.

F - 277V, 1 Ph.

L - 380V, 1 Ph.

T - 380V, 3 Ph.

Q - 415V, 1 Ph.

W - 415V, 3 Ph.

G - 460V, 3 Ph.

H - 575V, 3 Ph.

M - 460V, 1 Ph.

N - 575V, 1 Ph.

B - Blower Package R - Wired for Remote Blower

Lb/Hr 005 - 5#/Hr 010 - 10#/Hr 020 - 20#/Hr 030 - 30#/Hr 040 - 40#/Hr 050 - 50#/Hr 060 - 60#/Hr 080 - 80#/Hr 100 - 100#/Hr 125 - 125#/Hr 150 - 150#/Hr 175 - 175#/Hr 200 - 200#/Hr

*NOTE: AN EXTERNAL FUSED DISCONNECT SWITCH, OR OTHER SIMILAR PROTECTION, AS REQUIRED BY LOCAL, AND NATIONAL ELECTRICAL CODES MUST BE SUPPLIED AND INSTALLED BY OTHERS. An optional circuit breaker (except for select models over 48 amps) is available in the unit to reduce the risk of costly damage in the event of internal failure. It is not meant to be the primary protection as may be required by local and national electrical codes. All units include electronic overload protection as a standard feature.

q UNIT VOLTAGE CHARACTERISTICS Humidifiers may be ordered with the voltage nameplate ratings shown below. The units may be operated at nominal system voltage shown in Table 6.

Table 7 q CYLINDER LIFE Cylinders have an average life of 1150 hours when operating at maximum output with a water supply hardness of 150 ppm. Approximate cylinder life for other water hardness may be determined by multiplying 1150 by the correction factor shown in Table 7.

Table 8

Cylinder life will be extended if operated at less than maximum output. Multiply the cylinder life calculated in Table 7 by the correction factory shown in Table 8.

Table 9

Water Hardness (ppm)Correction Factor
503.00
1001.50
1501.00
2000.75
2500.60
3000.50
% of Maximum OutputCorrection Factor
1001.00
751.33
502.00
Suitable Nominal
Unit Nameplate VoltageSystem Voltages
120115, 120

208 208

230 220, 230, 240

277 277

380 380

415 400, 415

460 440, 460, 480

575 550, 575, 600

A - BACnet MS/TP C - Modbus RTU D - Metasys M2 E - Siemens FLN