Attachment 1- Bldg 50_51 - Replace or Refinish Flooring- SOW (All Docs).pdf

PDF 7 MB Posted

Attached to
Replace or Refinish Flooring Bldgs. 50 & 51, RAF Lakenheath Federal contract opportunity
Solicitation number
FA558720R0005
Issued by
Department of the Air Force United States Air Forces in Europe - Air Forces Africa

About this file

This document includes a statement of work and solicitation for a federal construction contract to replace or refinish flooring in buildings 50 and 51 at RAF Lakenheath in the United Kingdom. The contractor will be required to provide all labor, materials, equipment, transportation, and services to complete replacement of vinyl, carpet and tile flooring as well as refurbishment of wood sports flooring and cafeteria flooring. The work must be performed between June 11th and August 17th 2020. Questions regarding the solicitation are due by March 25th and final proposals are due by April 2nd. The estimated value of the construction is between $1 million and $5 million. The solicitation was issued by the Department of the Air Force United States Air Forces in Europe - Air Forces Africa.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work (SOW)

FA5587-20-R-0005

Replace or Refinish Flooring Bldgs. 50 & 51

WR# 70119, 70120, 70121, 70122, 70123

24 Jan 2020

Replace or Refinish Flooring WR# 70119, 70120, 70121, 70122, 70123 Bldgs. 50 & 51

1. Project Overview: Contractor shall provide all personnel, equipment, tools, materials, supervision, transportation, and all other items and services for the replacement and refurbishment of flooring in Bldgs 50 & 51 on RAF Lakenheath, IP27 9PN. The Contractor shall conform to all requirements as listed in this statement of work.

2. Project Scope

2.1. Building 51:

2.1.1. Sports Hall Flooring -

Sand wood floor surfaces with a machine using coarse, medium, and fine grades of sandpaper; the edges must be sanded to a smooth edge; the finished surface must be smooth and level, free from scratches. A final disc sanding shall be provided.

After final sanding or buffing, vacuum floors until clean. Do not walk on floors thereafter until finish has been applied and is dry.

Within one day after the final sanding, buffing, and sweeping have been completed, use a tacky rag to clean flooring with a low VOC solvent recommended by the manufacturer of the floor finish material. Follow cleaning with a coating of sealer;

when thoroughly dry, burnish with No. 2 steel wool, using a power machine. After final burnishing and prior to application of final finish coat(s), layout and mark game lines; after game lines are thoroughly dry, apply final finish coat.

Lines to be reinstated like for like, excluding the hopscotch and adding number squares. Location to be confirmed by the customer. Logo to be painted in the center of the Sports Hall. Logo size to be 8’x8’ (Attached document Eagle Logo).

2.1.2. Cafeteria Flooring –

Cafeteria Pulastic Floor to be refurbished to provide a flat seamless finish. Logo to be painted in the center of the Cafeteria Floor. Logo size to be 8’x8’ (Attached document Eagle Logo).

2.1.3. Vinyl Flooring -

Contractor shall remove all existing flooring (Vinyl, Carpet & Tile) and base boards.

Contractor shall dispose of through appropriate methods and in compliance with local regulations. All floor areas shall be “made good” by the Contractor, including, but not limited to, filling holes, levelling uneven surfaces, removing adhesives/dirt/debris. Contractor shall supply and install replacement laminate and underlay for all areas as specified in the highlighted floor plan attached.

2.1.3.1. Contractor shall ensure Vinyl Flooring is high density durable vinyl type floor system, such as VM 30 ALTRO non-slip flooring or USAFE approved equivalent and suitable for heavy traffic.

2.1.3.2. Contractor shall ensure Vinyl Flooring is the correct pile height for the application to ensure doors passes freely.

2.1.3.3. Contractor shall ensure that suitable door threshold joining strips are used.

2.1.3.4. Contractor shall ensure new stair nosing is highly durable and suitable for the facility

2.1.3.5. Contractor shall ensure all existing adhesive, dirt, debris etc. is removed prior to installing the Vinyl Flooring.

2.1.3.6. Contractor shall ensure Classrooms have a 1 meter Vinyl border around each room. (Colors to be approved by Facility manager)

Replace or Refinish Flooring WR# 70119, 70120, 70121, 70122, 70123

2.1.3.7. Contractor shall ensure that Vinyl colour options are made available to the Government prior to installation. Contractor shall provide colour samples when requested. Colour shall be determined by the Government after being provided with options. Materials shall be approved with an AF3000 and Material specifications will be provided with Material submittal.

2.1.3.8. Contractor shall remove all Skirting boards/baseboards where necessary.

All boards should be reinstalled and painted to provide a seamless finish.

2.2. Building 50:

2.2.1. Vinyl Flooring -

Contractor shall remove all existing flooring (Vinyl, Carpet & Tile) and base boards.

Contractor shall dispose of through appropriate methods and in compliance with local regulations. All floor areas shall be “made good” by the Contractor, including, but not limited to, filling holes, levelling uneven surfaces, removing adhesives/dirt/debris. Contractor shall supply and install replacement laminate and underlay for all areas as specified in the highlighted floor plan attached.

2.2.1.1. Contractor shall ensure Vinyl Flooring is high density durable vinyl type floor system, such as VM 30 ALTRO non-slip flooring or USAFE approved equivalent and suitable for heavy traffic.

2.2.1.2. Contractor shall ensure Vinyl Flooring is the correct pile height for the application to ensure doors passes freely.

2.2.1.3. Contractor shall ensure that suitable door threshold joining strips are used.

2.2.1.4. Contractor shall ensure new stair nosing is highly durable and suitable for the facility

2.2.1.5. Contractor shall ensure all existing adhesive, dirt, debris etc. is removed prior to installing the Vinyl Flooring.

2.2.1.6. Contractor shall ensure Classrooms have a 1 meter Vinyl border around each room. (Colors to be approved by Facility manager)

2.2.1.7. Contractor shall ensure that Vinyl colour options are made available to the Government prior to installation. Contractor shall provide colour samples when requested. Colour shall be determined by the Government after being provided with options. Materials shall be approved with an AF3000 and Material specifications will be provided with Material submittal.

2.2.1.8. Contractor shall remove all Skirting boards/baseboards where necessary.

All boards should be reinstalled and painted to provide a seamless finish.

2.3. Gymnasium Floor and Cafeteria Floor are the first priority. All yellow highlighted area on the floor plan (Classrooms/Offices) are the second priority. All blue highlighted areas on the attached floor plan (Common Areas & Stairways) are the third priority.

2.4. Contractor shall employ the work shift methodology best suited to complete all Contract work suitable for use NO LATER THAN (NLT) the Construction Complete Date (CCD).

It is the Contractor’s responsibility to manage their work practices in a manner that will allow them to meet the CCD including but not limited to multiple work shifts. If multiple shifts are necessary to complete all Construction works, the Contractor will ensure that their Site Supervision, Site Safety and Health Officer (SSHO), and Contractor Quality Control Specialist or Manager (CQC Specialist or Manager) roles are fully represented during 100% of their site construction time.

Replace or Refinish Flooring WR# 70119, 70120, 70121, 70122, 70123

3. Furniture/Equipment Removal/Replacement: Contractor shall be required to remove all furniture/equipment/fixtures from the work area and place it in a designated area to be determined prior to start date. Contractor shall be responsible for dismantling furniture where required. Once the refurbishment works have been completed, contractor shall be responsible for placing all furniture/equipment back, in the same location/condition as they were when removed. Contractor shall re-assemble furniture as required. Contractor shall ensure all necessary precautions are taken to avoid causing damage to the furniture/equipment

4. Installation Requirements

4.1. Buildings 50 and 51 are school facilities the customer has highlighted that the works must be completed during Summer Recess. The Summer Recess dates are 11th June 2020 to 17th August 2020.

5. Project Deliverables

5.1. Contractor shall provide a separate Risk Assessment and Methods Statement (RAMS) within 15 days after contract award

5.2. Contractor shall provide documentation of all materials and equipment to be utilized on this project for Government review using AF3000

5.2.1. 48 CES must review all submittals

5.2.2. Contracting Officer approval must be granted before commencing work

5.2.3. Initial submittals must be received by the Government within 15 days after date of contract award

5.3. Contractor shall provide a completed asset change form upon project completion, but prior to project closeout (template to be provided by the Customer)

5.3.1. Asset change shall be in the form of UNIFORMAT II (example to be provided by the Customer)

5.4. Contractor shall provide at least 2 disks of O&Ms prior to project closeout

5.5. Contractor shall provide all warranty information

6. Project Completion

6.1. Pre-Final Inspection: A pre-inspection will be conducted in which the government will create a “snag list” of any deviations found. The Contractor shall be required to complete those items prior to a final inspection.

6.2. Final Inspection: Upon completion of the snag list, a final inspection will be completed.

6.3. Contractor shall request an inspection in writing to the Contracting Officer at least 5 days in advance

6.4. Project will be documented on a project evaluation form.

7. Hours of Operation

7.1. The Contractor shall perform all works under this contract during the following dates

11th June 2020 – 17th August 2020. Normal base hours 7:00 to 17:00. Weekend work and extended work hours are approved if required.

7.2. The Contractor shall understand that escort flight is ONLY available normal weekdays 7:00-17:00. The Contractor shall provide all internal escorts for any works deemed necessary to be completed outside these hours.

Replace or Refinish Flooring WR# 70119, 70120, 70121, 70122, 70123

7.3. Escort Flight need a min of 2 weeks’ notice (ideally 3)

7.4. The Contractor may find it necessary to deviate from these hours to ensure timely completion of the work at no additional cost to the Government. If it is deemed necessary, the Contractor shall inform the Construction Inspector and Contracting Officer at least two days prior.

7.5. Holidays: If schedule works falls on an observed U.K. or U.S holiday, prior approval is required from the Construction Inspector and Contracting Officer at least two days prior.

8. Terminology

8.1. Contracting Officer: The Contracting Officer refers to a person with authority to enter into, administer, change and/or terminate contracts, and make related determinations and findings. The term includes certain authorized representatives of the Contracting Officer acting within the limits of their authority.

8.2. Maintenance Management: The contractor is responsible for inspecting surfaces to be worked on to determine condition and material quantities needed. The contractor is also responsible for scheduling resources to accomplish all requirements.

8.3. Government Quality Assurance: The Government will rely on the contractor’s quality control program and the performance management approach to assess performance whenever possible. However, the Government reserves the right to perform additional inspections as necessary, utilizing the inspection/acceptance provisions in the clauses FAR 52.213-4 Terms and Conditions—Simplified Acquisitions (Other than Commercial Items) and FAR 52.246-12 Inspection of Construction.

9. General Information

9.1. Project Manager/Site Superintendent: The Contractor is responsible for providing a fully qualified Project Manager or designated individual (telephone number and email address) who shall be physically present during contract performance. The designated individual must possess equal or higher skills comparable to the qualified Project Manager. Project Manager or designated individual shall be responsible for management and coordination of the contract and shall be the point of contact with Government representatives. The Contractor shall provide names of the Project Manager or designated individual to the CO in writing before contract performance begins. The Project Manager or designated individual must possess good command of the English language in both reading and writing and must be able to speak fluently and coherently. The Project Manager or designated individual shall be available to respond to inquiries issued from the CO during any period when work operations are being performed on RAF Lakenheath/Mildenhall/Feltwell and associated Geographically Separated Units (GSU). The project manager/alternate shall have full authority to act for the contractor on matters relating to the daily operation of the contract. Project manager and alternate must have complete knowledge and basic skills of the SOW and all facets of works. The alternate project manager shall have full supervisory authority during the absences of the project manager.

9.2. Roster: Contractor shall provide a complete roster of all personnel working on these requirements prior to commencing work. Roster must include names, trade specialty, date of birth, phone number, and official identification number. The contractor shall notify the Contracting Officer and Construction Inspector of any changes to the list in writing. All new personnel must possess and demonstrate the qualifications that are equal or above the qualifications of the personnel being replaced.

Replace or Refinish Flooring WR# 70119, 70120, 70121, 70122, 70123

10. Task Order Performance

10.1. Performance Evaluation Meetings: The Contracting Officer, Construction Inspector and other government personnel as deemed appropriate will meet periodically with the Contractor to review the contractor’s performance. The CO will apprise the contractor of the government’s views of the project performance. The contractor will apprise the government of any problems being experienced. Appropriate actions shall be taken to resolve any outstanding issues. The contractor may also request a meeting at any time during contract period.

10.2. The COR/PM will visit the job site at an appropriate interval to inspect the project. If desired, the COR will document performance, weather conditions, personnel on site, and level of effort. If documentation is made, the Contractor shall be allowed to view the documentation to validate and dispute any information.

11. Environmental and Utility Concerns

11.1. Selections of Materials: Environmentally friendly materials are preferred when possible. Environmentally friendly paints are those which do not contain metals such as lead, chromium, cadmium, barium, arsenic, mercury, selenium, or silver. They will also not contain hazardous/flammable solvents such as methyl ethyl ketone, xylene, or toluene. Latex or water-based paints are the preferred type of paint. The decision to use an environmentally friendly paint should not result in an unacceptably short life of painted surface or should it be applied in a poor manner.

11.2. Environmental, Health, and Safety: the Contractor shall ensure all employees receive the necessary environmental, health, and safety training to ensure compliance with all Occupational Safety and Health Acts (OSHA) and federal and local laws of the United Kingdom. The more restrictive of the guidance’s will apply. The contractor shall protect the health and safety of the employees and the community.

11.3. Pollution Prevention: “Pollution Prevention” and “Source Reduction” are defined in the Pollution Prevention Act of 1990, 42 U.S.C 13101-13109. This is to identify pollution prevention opportunities and shall not be construed to require the contractor to conduct actives not otherwise required by the program.

11.4. Hazardous Materials/Chemical Management: All hazardous material use requires authorization prior to bringing the material on base. “Hazardous Material” includes many materials for which is there a manufacturer SDS, such as and not limited to:

cleaning supplies, paints, solvents, sealants, lead acid batteries, fuels, and herbicides.

12. List of Attachments

12.1. Attachment 1 - Building 50 GF_FF Floor Plan – Dims

12.2. Attachment 2 - Building 51 GF_FF Floor Plan - Dims

12.3. Attachment 3 - Building 50, 51 Highlighted Floor Plans

12.4. Attachment 4 - Stair Nosing Example Photo

12.5. Attachment 5 - Classroom Border Example Photo

12.6. Attachment 6 - Cafeteria & Sports Hall Logo

12.7. Attachment 7 - Replace and Refurbish Flooring Bldg. 50 & 51 - DODEA Asbestos Survey

B

L D

G

G

R O

U N

D

F

L O

O R

P

A

N

Attachment 1 - Building 50 GF_FF Floor Plan – Dims

D

G

F

I R

S T

F

O

A

Attachment 1 - Building 50 GF_FF Floor Plan – Dims

1 1

U S

A F

E

P H

A S

E

I

B L D

G

F

L O

A

N

IMAGE ONLY

IMAGE ONLY

TEAM:

iNTERVIEW SHEET:

CATCODE:

EXTERIOR WALL:

INTERIOR WALL:

NORTH ARROW:

ADJOINING STR.:

LIST UNIT/FLIGHT & ROOM#S:

F

F

I

C

I

A

L

U

E

L

Y

Attachment 2 - Building 51 GF_FF Floor Plan - Dims

AutoCAD SHX Text Project Number:

AutoCAD SHX Text Plot Date:

AutoCAD SHX Text Plot Scale:

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DESIGN BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

REVIEWED BY:

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

SEQUENCE NO.

AutoCAD SHX Text

OF

AutoCAD SHX Text

MM/DD/YY

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text H

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text H

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

REV

AutoCAD SHX Text

COMMENT

AutoCAD SHX Text

DATE

AutoCAD SHX Text

AutoCAD SHX Text TETRATECH 800 OAK RIDGE TURNPIKE SUITE A-600 OAK RIDGE, TN 37830 PH:(865)483-9900/FAX:(865)482-6647

AutoCAD SHX Text

TETRA TECH

AutoCAD SHX Text

RAF LAKENHEATH SUFFOLK, ENGLAND SPACE UTILIZATION STUDY

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text R

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text U

AutoCAD SHX Text 100-ten-t98781 TO 0114

D

G

F

I R

O

A

Attachment 2 - Building 51 GF_FF Floor Plan - Dims

Attachment 3 - Building 50, 51 Highlighted Floor Plans

Lakenheath Elementary School 2017 AHERA Asbestos Management Plan

A-1

Appendix A: Laboratory Sample Results

A-2

This page intentionally left blank

RJ Lee Group, Inc.

350 Hochberg Road, Monroeville, PA 15146

Tel: 724-325-1776 | Fax: 724-733-1799

ALPHA Facilities Solutions 2716 Mission Street

Attention: Thomas Valli Telephone: 412-979-6139

AOH1046821-0

Pittsburgh, PA 15203

09/26/2017

09/19/2017

Lakenheath E.S.

Laboratory Report

Report Date

Sample Receipt Date

Authorization/P.O. No.

RJ Lee Group Job No.

Client Job No./Name

Method: EPA/600/R-93/116

Analysis: Asbestos in Bulk Samples

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

10415387.HPL UK17-LAE-263A Yes LKS-09/26/2017

Description:

1 Q, CA, M

White Plaster

ND 100

10415388.HPL UK17-LAE-263B Yes LKS-09/26/2017

Description:

1 Q, CA, M

White Plaster

ND 100

10415389.HPL UK17-LAE-264A Yes LKS-09/26/2017

Description:

1 Q, CA, B, M

Green Tile

ND <1 CE 100

10415390.HPL UK17-LAE-264B Yes LKS-09/26/2017

Description:

1 Q, CA, B, M

Green Tile

ND <1 CE 100

Client Job No./Name: Lakenheath E.S. RJ Lee Group Job No: AOH1046821-0

Laboratory Report (Cont)

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

10415391.HPL UK17-LAE-265A Yes LKS-09/26/2017

Description:

1 Q, CA, B, M

Brown Material

2 CH 98

10415392.HPL UK17-LAE-265B Yes AKB-09/26/2017

Description:

1 B, M

Black Mastic

4 CH 2 CE 94

10415393.HPL UK17-LAE-266A Yes AKB-09/26/2017

Description:

1 B, M

Gray Fibrous Material

ND 60 MW 40

10415394.HPL UK17-LAE-266B Yes AKB-09/26/2017

Description:

1 B, M

Gray Fibrous Material

ND <1 CE 60 MW 40

10415395.HPL UK17-LAE-267A Yes AKB-09/26/2017

Description:

1 B, M

Gray Strips

ND 5 CE 3 FG 92

10415396.HPL UK17-LAE-267B Yes AKB-09/26/2017

Description:

1 B, M

Gray Strips

ND 5 CE 95

10415397.HPL UK17-LAE-268A Yes AKB-09/26/2017

Description:

1 B, M

Gold Glue

ND <1 CE <1 SF 100

10415398.HPL UK17-LAE-268B Yes AKB-09/26/2017

Description:

1 B, M

Gold Glue

ND 100

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

10415399.HPL UK17-LAE-269A Yes AKB-09/26/2017

Description:

1 B, M

Off White Woven Material

ND 95 CE 5

10415400.HPL UK17-LAE-269B Yes AKB-09/26/2017

Description:

1 M

Off White Woven Material

ND 99 CE 1

10415401.HPL UK17-LAE-269C Yes AKB-09/26/2017

Description:

1 B, M

Off White Woven Material

ND <1 CE <1 MW 100

10415402.HPL UK17-LAE-270A Yes EB-09/26/2017

Description:

1 CA, B, OP, M

Tan Mastic

ND 10 CE 90

10415403.HPL UK17-LAE-270B Yes EB-09/26/2017

Description:

1 CA, B, OP, M

Tan Mastic

ND 10 CE 90

10415404.HPL UK17-LAE-271A Yes EB-09/26/2017

Description:

1 Q, CA, OP,

M

Gray Material

ND 100

10415405.HPL UK17-LAE-271B Yes EB-09/26/2017

Description:

1 CA, OP, MI,

M

Gray Material

ND <1 CE 100

10415406.HPL UK17-LAE-272A Yes EB-09/26/2017

Description:

1 CA, OP, M

Brown Putty

ND <1 FG 100

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

10415407.HPL UK17-LAE-272B Yes EB-09/26/2017

Description:

1 CA, OP, M

Brown Putty

ND 2 CE 98

10415408.HPL UK17-LAE-273A Yes EB-09/26/2017

Description:

1 CA, B, OP, M

Black Material

ND 100

10415409.HPL UK17-LAE-273B Yes EB-09/26/2017

Description:

1 CA, B, OP,

MI, M

Black Material

ND 100

10415410.HPL UK17-LAE-274A Yes EB-09/26/2017

Description:

1 CA, OP, MI,

M

Blue Tile

ND <1 CE 100

10415411.HPL UK17-LAE-274B Yes EB-09/26/2017

Description:

1 CA, OP, MI,

M

Blue Tile

ND 5 FG 95

10415412.HPL UK17-LAE-275A Yes EB-09/26/2017

Description:

1 CA, B, OP, M

Tan Mastic

ND 10 CE 90

10415413.HPL UK17-LAE-275B Yes EB-09/26/2017

Description:

1 CA, B, OP, M

Tan Mastic

ND 15 CE 85

10415414.HPL UK17-LAE-276A Yes EB-09/26/2017

Description:

1 OP, M

Gray Material

ND 2 CE 90 MW 8

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

10415415.HPL UK17-LAE-276B Yes EB-09/26/2017

Description:

1 CA, OP, MI,

M

Gray Material

ND 1 CE 90 MW 9

10415416.HPL UK17-LAE-277A Yes EB-09/26/2017

Description:

1 OP

White Fabric

ND 100 SF <1

10415417.HPL UK17-LAE-277B Yes EB-09/26/2017

Description:

1 OP, M

White Fabric

ND 100 SF <1

10415418.HPL UK17-LAE-277C Yes EB-09/26/2017

Description:

1 OP, M

White Fabric

ND 100 SF <1

10415419.HPL UK17-LAE-278A Yes EB-09/26/2017

Description:

1 OP, M

Gray Fabric

ND 100 SF <1

10415420.HPL UK17-LAE-278B Yes EB-09/26/2017

Description:

1 OP, M

Gray Fabric

ND 100 SF <1

Non-Fibrous Materials(%)Homogeneous

Client Sample Number

Asbestos Detected(%)

Analyst - Analysis Date

Non-Asbestos Fibers(%)

Matrix Material

RJLG Sample Number

# of Layers

Authorized Signature:

Elizabeth Brown

DISCLAIMER NOTES

· "ND" indicates no asbestos was detected; the method detection limit is 1%.

· "Trace" or "<" indicates asbestos was identified in the sample, but the concentration is less than the method quantitation limit. PLM coefficients of variance range from approximately 1.8 at the quantitation limit of 1% to 0.1 at high fiber concentrations.

· Samples are archived for three months following analysis and are then properly discarded.

· These results are submitted pursuant to RJ Lee Group's current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions. No responsibility or liability is assumed for the manner in which these results are used or interpreted.

· This test report relates to the items tested.

· This report is not valid unless it bears the name of a NVLAP Lab Code 101208-0 approved signatory.

· Any reproduction of this document must be in full in order for the report to be valid.

· This report may not be used to claim product endorsement by NVLAP Lab Code 101208-0, any agency of the U.S. Government or any other laboratory accrediting agency.

· Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar nonfriable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as "non-asbestos-containing."

· Sample(s) for this project were analyzed at our: Monroeville, PA (AIHA #100364, NY ELAP #10884) facility.

· If RJ Lee Group, Inc. did not collect the samples analyzed, the verifiability of the laboratorys results are limited to the reported values.

· ((((100-A)/B)*C*100)+0.99)/100 = Asbestos Detected (%), where A=weight loss, B=total # of points counted, and C=total # of asbestos fibers counted.

ASBESTOS

= Amosite

= Actinolite

= Anthophyllite

= Chrysotile

= Crocidolite

= Tremolite

NON-ASBESTOS

= Cellulose

= Mineral Wool

= Fibrous Glass

= Synthetic Fibers = Hair

= Wollastonite

= Other Fibers

NON-FIBROUS MATERIALS

= Amphibole

= Binder

= Carbonates

= Clay

= Feldspar

= Gypsum

= Hydromagnesite

= Miscellaneous

= Mica

= Opaque = Organic

= Perlite

= Quartz

= Tar

= Vermiculite

AM

AC

AN

CH

CR

TR

CE

MW

FG

SF

H

W

OF

AM

B

CA

CL

F

G

HY

M

MI

OP

OR

P

Q

V

RJ Lee Group, Inc 350 Hochberg Road

Monroeville, PA 15146 Tel: (724) 325-1776 | Fax (724) 733-1799

NOTES

1. “<” indicates results less than analytical sensitivity. “---” indicates that sample was not analyzed.

2. Sample(s) for this project were analyzed at our: Monroeville, PA (AIHA #100364, NVLAP #101208-0, NY ELAP #10884) facility.

3. If RJ Lee Group, Inc. did not collect the samples analyzed, the verifiability of the laboratory's results are limited to the reported values.

4. Trace indicates <1% asbestos was identified.

5. Abbreviations: N/A-Not Applicable, Chry-Chrysotile Asbestos, Amph-Amphibole Asbestos, Asb-Asbestos Amphibole, Cleavage-Cleavage Amphibole.

6. Samples will be held for 90 days and then disposed of per Federal regulations.

7. These results are submitted pursuant to RJ Lee Group’s current terms and conditions of sale, including the company’s standard warranty and limitation of liability provisions. No responsibility or liability is assumed for the manner in which these results are used or interpreted.

DISCLAIMER

RJ Lee Group, Inc. is accredited by the New York Department of Health Environmental Laboratory Program (NY ELAP) for the bulk analysis by TEM of non-friable organically bound materials. This report may not be used to claim product endorsement by NY ELAP, or any other regulatory or laboratory accrediting agency. Any reproduction of this document must be in full in order for the report to be valid. This report is not valid unless it bears the name of a NVLAP approved signatory.

These results are submitted pursuant to RJ Lee Group's current terms and conditions of sale, including the company's standard warranty and limiting provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, RJ Lee Group will store the samples for a period of ninety (90) days before discarding. A shipping and handling fee will be assessed for the return of any sample.

Final Laboratory Report TEM Compositional Analysis

Attention: Thomas Valli ALPHA Facilities Solutions 2716 Mission Street Pittsburgh, PA 15203

Report Date:

Sample Receipt Date:

RJ Lee Group Job No.:

Authorization/P.O. No.:

Samples Received:

Client Job No.:

09/29/2017 09/19/2017

AOH1046821-1

Lakenheath E.S.

Method: Chatfield Technical Consulting Limited, SOP-1988-02.Rev1.

------------------------Weight Percent-------------------------

Client Sample Number RJLG Sample Number Sample Description Starting Weight

(gm) Organic Acid Soluble Residue Chry Amph Total

Asbestos Amphibole

Type

UK17-LAE-264C* 10415421.HT 0.16870 24 67 4 5 0 5

UK17-LAE-265C* 10415422.HT 0.10330 74 4 11 11 0 11

UK17-LAE-267C* 10415423.HT 0.19050 56 30 14 0 0 0

UK17-LAE-268C* 10415424.HT 0.08940 95 4 1 0.04 0 0.04

UK17-LAE-270C* 10415425.HT 0.04040 39 58 3 0 0 0

UK17-LAE-272C* 10415426.HT 0.15740 59 31 10 0 0 0

RJ Lee Group, Inc. Final Laboratory Report (contʹd) RJ Lee Group Job No: AOH1046821-1 Client: ALPHA Facilities Solutions Client Job No/Name: Lakenheath E.S. Report Date: 09\29\2017

NOTES

1. “<” indicates results less than analytical sensitivity. “---” indicates that sample was not analyzed.

2. Sample(s) for this project were analyzed at our: Monroeville, PA (AIHA #100364, NVLAP #101208-0, NY ELAP #10884) facility.

3. If RJ Lee Group, Inc. did not collect the samples analyzed, the verifiability of the laboratory's results are limited to the reported values.

4. Trace indicates <1% asbestos was identified.

5. Abbreviations: N/A-Not Applicable, Chry-Chrysotile Asbestos, Amph-Amphibole Asbestos, Asb-Asbestos Amphibole, Cleavage-Cleavage Amphibole.

6. Samples will be held for 90 days and then disposed of per Federal regulations.

7. These results are submitted pursuant to RJ Lee Group’s current terms and conditions of sale, including the company’s standard warranty and limitation of liability provisions. No responsibility or liability is assumed for the manner in which these results are used or interpreted.

DISCLAIMER

RJ Lee Group, Inc. is accredited by the New York Department of Health Environmental Laboratory Program (NY ELAP) for the bulk analysis by TEM of non-friable organically bound materials. This report may not be used to claim product endorsement by NY ELAP, or any other regulatory or laboratory accrediting agency. Any reproduction of this document must be in full in order for the report to be valid. This report is not valid unless it bears the name of a NVLAP approved signatory.

These results are submitted pursuant to RJ Lee Group's current terms and conditions of sale, including the company's standard warranty and limiting provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, RJ Lee Group will store the samples for a period of ninety (90) days before discarding. A shipping and handling fee will be assessed for the return of any sample.

------------------------Weight Percent-------------------------

Client Sample Number RJLG Sample Number Sample Description Starting Weight

(gm) Organic Acid Soluble Residue Chry Amph Total

Asbestos Amphibole

Type

UK17-LAE-273C* 10415427.HT 0.02170 37 41 22 0 0 0

UK17-LAE-274C* 10415428.HT 0.13170 72 22 5 0 0 0

UK17-LAE-275C* 10415429.HT 0.09010 96 4 Trace 0 0 0

Authorized Signature:

Monica McGrath

D-1

Appendix D: Summary of Materials

Table D-1 - Summary of Asbestos-Containing Materials for Lakenheath ES

Table D-2 - Summary of Non-Asbestos Materials for Lakenheath ES

Table D-3 - Summary of Other Materials for Lakenheath ES

D-2

This page intentionally left blank

Quantities are approximate and not intended for abatement bidding purposes. 1 2018

Bldg.

No.

Homo.

Mtl.

No.

Material Description

AHERA

CAT Locations Quantity Friable Overall

Condition Type of Damage Accessibility Potential for

Air Erosion Potential for

Vibration Potential for

Damage EPA Ass.

CAT

Cleaning Required

Recommended Management Actions

Begin Date

End Date

Material Management Procedure Unit Cost Est. Qty.

(Unit) Est. Cost Comments

Number Date Result

Building: 50

50 062

SUBFLOOR

MATERIAL,

LIGHT GRAY

CEMENT BOARD MISC.

102, 104, 106, 111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 132, 133, 134, 101/103, 105A, 121B 60 SF

0696-LES-062A

0696-LES-062B

0696-LES-062C

30-Jun-96 30-Jun-96 30-Jun-96

CH 25-30%

CH 25-30%

CH 25-30% NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN. SUBFLOOR MATERIAL 1.5

THIS MATERIAL IS LOCATED

WHERE PIPES PASS

THROUGH THE FLOOR

BENEATH A CEMENTITIOUS

SUBFLOOR LOCATED UNDER

CARPETS. THIS MATERIAL

WAS NOT ACCESSIBLE FOR

ADEQUATE INSPECTION

BECAUSE IT IS LOCATED

UNDER EXISTING FLOOR

MATERIALS.

50 070

SHEET GASKET,

4" - 6"

DIAMETER, RED,

ON PIPE FLANGE

CONNECTIONS MISC.

A301, A302, A303, A304, A305, CRAWLSPACE 1,

CRAWLSPACE 2,

CRAWLSPACE 3,

CRAWLSPACE 4,

CRAWLSPACE 5 318 EA

0797-LKE-070A

0797-LKE-070B

0797-LKE-070C

30-Jul-97 30-Jul-97 30-Jul-97

CH 30-40%

CH 40%

CH 40% NO UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 4.5

NOT ALL THIS MATERIAL

WAS ACCESSIBLE FOR

ADEQUATE INSPECTION DUE

TO CONFINED SPACE

LOCATIONS.

50 118

FLOOR

ADHESIVE,

WHITE, UNDER

LIGHT GRAY

WITH BLACK

SPECKS

RESILIENT

FLOOR

SHEETING MISC.

C101, C103, C104, C105, C106, C201, C203, C204, C205, J103, S101.1, S101.2, S102.1, S102.2, 200A 9,000 SF

0500-LAE-118A

0500-LAE-118B

0500-LAE-118C

UK12-LAE-118D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

CH 1.02% NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

FLOOR ADHESIVE

(MASTIC) 24

*SAMPLE WAS ANALYZED BY

TEM AND RESULT WAS

>0.1% ASBESTOS. THIS

MATERIAL IS CONSIDERED

TO BE ACM. MN 118 AND MN

200 ARE SIMILAR IN

APPEARANCE BUT WERE

INSTALLED AT DIFFERENT

TIMES. THIS IS THE

ADHESIVE FOR MN 115.

50 241

FLOOR

ADHESIVE,

YELLOW AND

BLACK, UNDER

GRAY CARPET MISC. 106A 315 SF

UK12-LAE-241A

UK12-LAE-241A*

UK12-LAE-241B

UK12-LAE-241C*

23-Jan-12 23-Jan-12 23-Jan-12 23-Jan-12

CH 2%

CH 21%

CH 2%

ND NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

FLOOR ADHESIVE

(MASTIC) 6

*SAMPLE WAS ANALYZED BY

TEM AND RESULT WAS

>0.1% ASBESTOS. THIS

MATERIAL IS CONSIDERED

TO BE ACM.

Building: 51

51 055

FLOOR

ADHESIVE,

BLACK, UNDER

1' X 1' GRAY

RESILIENT

FLOOR TILE MISC. J101 140 SF

0396-LES-055A

0396-LES-055B

0396-LES-055C

19-Mar-96 19-Mar-96 19-Mar-96

CH <1%

CH 1-3%

CH 3-5% NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

FLOOR ADHESIVE

(MASTIC) 3

THIS IS THE ADHESIVE FOR

MN 009.

51 056

SHEET GASKET,

8" DIAMETER,

RED, ON BOILER

TANK PIPE

FLANGE

CONNECTIONS MISC. M109 4 EA

0396-LES-056A

0396-LES-056B

0396-LES-056C

19-Mar-96 19-Mar-96 19-Mar-96

CH 35-40%

CH 55-60%

CH 50-55% NO UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 1.5

THIS MATERIAL IS

ENCLOSED WITH METAL

JACKETS.

51 057

SHEET GASKET,

4" DIAMETER,

RED, ON PIPE

FLANGE

CONNECTIONS MISC. 171, M109 50 EA

0396-LES-057A

0396-LES-057B

0396-LES-057C

19-Mar-96 19-Mar-96 19-Mar-96

CH 60-65%

CH 85-90%

CH 75-80% NO UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 1.5

SOME OF THIS MATERIAL IS

ENCLOSED WITH METAL

JACKETS. THIS MATERIAL

MAY BE LOCATED IN OTHER

AREAS THROUGHOUT THE

BUILDING AND/OR IN PIPE

RUNS LEADING TO THIS

BUILDING. DURING THE

2017 SURVEY, THIS

MATERIAL WAS

INACCESSIBLE FOR

ADEQUATE INSPECTION.

Table D-1 - Summary of Asbestos-Containing Materials for Lakenheath ES

Sample Information

Quantities are approximate and not intended for abatement bidding purposes. 2 2018

No.

Homo.

Mtl.

No.

Material Description

AHERA

CAT Locations Quantity Friable Overall

Condition Type of Damage Accessibility Potential for

Air Erosion Potential for

Vibration Potential for

Damage EPA Ass.

CAT

Cleaning Required

Recommended Management Actions

Begin Date

End Date

Material Management Procedure Unit Cost Est. Qty.

(Unit) Est. Cost Comments

Number Date Result

Table D-1 - Summary of Asbestos-Containing Materials for Lakenheath ES

Sample Information

51 059

SUBFLOOR

MATERIAL,

WHITE CEMENT

BOARD MISC.

153, 155, 156, 157, 158, 159, 160, 161, 169 35 SF

0396-LES-059A

0396-LES-059B

0396-LES-059C

27-Jun-96 27-Jun-96 27-Jun-96

CH 60-75%

CH 60-75%

CH 60-75% NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN. SUBFLOOR MATERIAL 1.5

THIS MATERIAL IS LOCATED

BELOW THE HEAT PIPING

ACCESS PANELS. IT IS

COVERED WITH A

CEMENTITIOUS SUBFLOOR

AND RESILIENT FLOOR TILE.

THIS MATERIAL WAS NOT

ACCESSIBLE FOR ADEQUATE

INSPECTION BECAUSE IT IS

COVERED BY EXISTING

FLOORING MATERIALS.

51 060

THERMAL TAPE,

BLACK,

ASPHALTIC, ON

FLOOR

RADIATOR PIPES TSI

155, 157, 158, 159, 160, 161, 169 15 LF

0396-LES-060A

0396-LES-060B

0396-LES-060C

27-Jun-96 27-Jun-96 27-Jun-96

CH 30-35%

CH 30-35%

CH 30-35% NO UNDAMAGED NONE HIGH LOW LOW

SIGNIFICANT

POTENTIAL 6 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

PIPE OR PIPE FITTING

INSULATION 1.5

THIS MATERIAL IS LOCATED

ON PIPE STUBS NEAR THE

EXIT DOORS IN EACH OF

THE LISTED ROOMS. THE

PIPE STUBS ARE LESS THAN

2" IN LENGTH.

51 067

SUBFLOOR

MATERIAL,

WHITE ROPE

PADS BELOW

WOOD FLOOR MISC. 180 2,000 SF ASSUMED ACM 27-Jun-96 - NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN. SUBFLOOR MATERIAL 15

THIS MATERIAL IS USED FOR

SHOCK ABSORPTION FOR

THE GYMNASIUM FLOORING.

THIS MATERIAL WAS NOT

ACCESSIBLE FOR ADEQUATE

INSPECTION BECAUSE IT IS

LOCATED UNDER EXISTING

FLOORING MATERIALS.

51 264

RESILIENT

FLOOR TILE, 9"

X 9" DARK

GREEN WITH

WHITE STREAKS MISC. T203A 40 SF

UK17-LAE-264A

UK17-LAE-264B

UK17-LAE-264C*

08-Sep-17 08-Sep-17 08-Sep-17

ND

ND

CH 5% NO DAMAGED

DETERIORA

TION MEDIUM LOW LOW POTENTIAL 8 NO

1. REPAIR THIS MATERIAL

WITHIN ONE YEAR OF RECEIPT

OF THIS REPORT.

2. MINIMUM QUALIFICATIONS

TO CONDUCT THIS ACTION ARE

MAINTENANCE PERSONNEL

WHO HAVE RECEIVED

TRAINING IN REPAIR OF

DAMAGED ACM.

3. AFTER REPAIR IS

COMPLETED, CONSULT THE

O&M MANUAL CONCERNING

SAFE CUSTODIAL PROCEDURES

FOR THIS MATERIAL.

4. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

RESILIENT FLOOR

TILE OR SHEETING 5.5

*SAMPLE WAS ANALYZED BY

TEM AND RESULT WAS

>0.1% ASBESTOS. THIS

MATERIAL IS CONSIDERED

TO BE ACM. 3 SF OF THIS

MATERIAL IS DAMAGED IN

ROOM T203A AND NEEDS TO

BE REPAIRED. THE

ADHESIVE FOR THIS

MATERIAL IS MN 265.

51 265

FLOOR

ADHESIVE,

BLACK, UNDER

9" X 9" DARK

GREEN WITH

WHITE STREAKS

RESILIENT

FLOOR TILE MISC. T203A 40 SF

UK17-LAE-265A

UK17-LAE-265B

UK17-LAE-265C*

08-Sep-17 08-Sep-17 08-Sep-17

CH 2%

CH 4%

CH 11% NO UNDAMAGED NONE LOW LOW LOW

LOW

POTENTIAL 8 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

FLOOR ADHESIVE

(MASTIC) 1.5

*SAMPLE WAS ANALYZED BY

TEM AND RESULT WAS

>0.1% ASBESTOS. THIS

MATERIAL IS CONSIDERED

TO BE ACM. THIS IS THE

ADHESIVE FOR MN 264.

Building: 52

52 215

SHEET GASKET,

18" SQUARE,

BLACK PAINTED,

WHITE CORE,

ON BOILER

BURNER PLATE MISC. M101 3 EA

0306-LAE-215A

0306-LAE-215B

0306-LAE-215C

13-Mar-06 13-Mar-06 13-Mar-06

CH 75%

CH 85%

CH 85% NO UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 1.5

52 216

ROPE GASKET,

42" DIAMETER,

WHITE, ON

BOILER DOOR MISC. M101 3 EA

0306-LAE-216A

0306-LAE-216B

0306-LAE-216C

13-Mar-06 13-Mar-06 13-Mar-06

CH 90%

CH 90%

CH 90% YES UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 YES

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 1.5

Quantities are approximate and not intended for abatement bidding purposes. 3 2018

No.

Homo.

Mtl.

No.

Material Description

AHERA

CAT Locations Quantity Friable Overall

Condition Type of Damage Accessibility Potential for

Air Erosion Potential for

Vibration Potential for

Damage EPA Ass.

CAT

Cleaning Required

Recommended Management Actions

Begin Date

End Date

Material Management Procedure Unit Cost Est. Qty.

(Unit) Est. Cost Comments

Number Date Result

Table D-1 - Summary of Asbestos-Containing Materials for Lakenheath ES

Sample Information

52 217

SHEET GASKET,

4" - 6"

DIAMETER, RED

SURFACE,

WHITE CORE,

ON PIPE FLANGE

CONNECTIONS MISC. M101 2 EA

0306-LAE-217A

0306-LAE-217B

0306-LAE-217C

13-Mar-06 13-Mar-06 13-Mar-06

CH 36%

ND

CH 39% NO UNDAMAGED NONE MEDIUM LOW LOW POTENTIAL 5 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

GASKET MATERIAL

AND FLEX

CONNECTORS 1.5

Building: 55

55 001

CEMENT

ROOFING

PANEL, GRAY,

CORRUGATED MISC. 101, 102, 103, C101, T101 2,400 SF 06528 23-Sep-87 CH 30% NO UNDAMAGED NONE HIGH LOW LOW

SIGNIFICANT

POTENTIAL 6 NO

1. NO IMMEDIATE ABATEMENT

REQUIRED.

2. CONSULT THE O&M MANUAL

CONCERNING SAFE CUSTODIAL

PROCEDURES FOR THIS

MATERIAL.

3. CONTINUE SURVEILLANCE

OF THIS MATERIAL UNDER THE

ASBESTOS MANAGEMENT PLAN.

EXTERIOR

WEATHERPROOFING

MATERIALS 9

THIS MATERIAL IS EXPOSED

IN SOME LISTED LOCATIONS.

1 2018

No.

Homo.

Mtl. No.

Material Description

AHERA

CAT Locations Comments

Number Date Result

Building: 50

50 005

WALL TILE, 1' X 1'

WHITE, PINHOLE,

FISSURED, GLUED-

ON MISC. M205

06541 06542 06543 06544 06545 06546 06547 06548

01-Jul-88 01-Jul-88 01-Jul-88 01-Jul-88 01-Jul-88 01-Jul-88 01-Jul-88 01-Jul-88

ND

ND

ND

ND

ND

ND

ND

ND

THE ADHESIVE FOR THIS MATERIAL

IS MN 077.

50 052

WALL PLASTER,

PINK, SMOOTH

SURFACE SURF.

102, 104, 105, 106, 110, 111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 130, 131, 132, 133, 134, 200, 201, 201, 202, 203, 204, 205, 206, 209, 210, 211, 212, 213, 214, 215, 220, 222, 223, 224, 225, 226, 230, 232, 233, 234, 235, 236, 237, C101, C102, C103, C104, C105, C106, C201, C202, C203, C204, C205, J103, M205, S101.1, S101.2, S102.1, S102.2, T132A, T133A, 101/103, 105A, 106A, 111A, 111B, 111C, 121A, 121B, 124A, 127A, 127B, 133B, 200A, 211A, 211B, 211C, 221A, 221B

0511-LKE-023A

0511-LKE-023B

0511-LKE-023C

0511-LKE-023D

0511-LKE-023E

0511-LKE-023F

0511-LKE-023G

23-Jun-89 23-Jun-89 23-Jun-89 23-Jun-89 23-Jun-89 23-Jun-89 23-Jun-89

ND

ND

ND

ND

ND

ND

ND

50 076

WALLBOARD, 1/2"

THICK, TAN

PAPER, LIGHT

PINK CORE MISC. T127B, 127A, 127B

0797-LKE-076A

0797-LKE-076B

0797-LKE-076C

30-Jul-97 30-Jul-97 30-Jul-97

ND

ND

ND

THE JOINT COMPOUND FOR THIS

MATERIAL IS MN 135.

50 077

WALL TILE

ADHESIVE,

YELLOW, UNDER

1' X 1' WHITE,

PINHOLE,

FISSURED, WALL

TILE MISC. M205

0797-LKE-077A

0797-LKE-077B

0797-LKE-077C

30-Jul-97 30-Jul-97 30-Jul-97

ND

ND

ND

THIS IS THE ADHESIVE FOR MN

005.

50 080

CEILING BOARD,

1/2" THICK, GRAY

CORE MISC. C204

0797-LKE-080A

0797-LKE-080B

0797-LKE-080C

30-Jul-97 30-Jul-97 30-Jul-97

ND

ND

ND

NO ASSOCIATED JOINT COMPOUND

COULD BE FOUND FOR THIS

MATERIAL.

50 114

CEILING TILES, 2'

X 2' WHITE,

PINHOLE,

FISSURED,

SUSPENDED MISC.

110, 113, 131, 200, 220, 230, C101, C103, C105, C106, C201, C203, C204, C205, S101.1, S101.2, S102.1, S102.2, 106A

0500-LAE-114A

0500-LAE-114B

0500-LAE-114C

03-May-00 03-May-00 03-May-00

ND

ND

ND

50 115

RESILIENT FLOOR

SHEETING, LIGHT

GRAY WITH

BLACK SPECKS MISC.

C101, C103, C104, C105, C106, C201, C203, C204, C205, J103, S101.1, S101.2, S102.1, S102.2, 200A

0500-LAE-115A

0500-LAE-115B

0500-LAE-115C

UK12-LAE-115D*

03-May-00 03-May-00 03-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM. MN 115

AND MN 199 ARE SIMILAR IN

APPEARANCE BUT WERE INSTALLED

AT DIFFERENT TIMES. THE

ADHESIVE FOR THIS MATERIAL IS

MN 118.

50 116

CEILING TILES, 2'

X 2' WHITE, SAND

TEXTURE WITH

PINHOLE,

SUSPENDED MISC.

111, 112, 114, 115, 116, 124, 125, 126, 127, 130, 132, 133, 134, 209, 210, 211, 212, 213, 214, 215, 222, 223, 224, 225, 226, 232, 233, 234, 235, 236, 237, T124A, T132A, T133A, T134A, T134B, 111B, 111C, 121A, 121B, 124A, 124B, 132B, 133B, 211A, 211B, 211C, 221A, 221B

0500-LAE-116A

0500-LAE-116B

0500-LAE-116C

03-May-00 03-May-00 03-May-00

ND

ND

ND

MN 116 AND MN 193 ARE SIMILAR

IN APPEARANCE BUT WERE

INSTALLED AT DIFFERENT TIMES.

Table D-2 - Summary of Non-Asbestos Materials for Lakenheath ES

2 2018

No.

Homo.

Mtl. No.

Material Description

AHERA

CAT Locations Comments

Number Date Result

Table D-2 - Summary of Non-Asbestos Materials for Lakenheath ES

Sample Information

50 117

SINK COATING,

ASPHALTIC, 6" X

6" BLACK PAD,

UNDER

STAINLESS STEEL

BOWL, SET IN

WOOD PATTERN

LAMINATE

COUNTERTOP MISC.

111, 112, 113, 114, 115, 116, 124, 126, 132, 133, 134, 232, 233, 234, 235, 236, 237, 105A, 221B

0500-LAE-117A

0500-LAE-117B

0500-LAE-117C

UK12-LAE-117D*

06-May-00 06-May-00 06-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM.

50 119

FLOOR ADHESIVE,

WHITE, UNDER

20" X 20" GRAY

RAISED DOT

RUBBER FLOOR

TILE MISC.

111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 132, 133, 134, 209, 210, 212, 213, 214, 215, 222, 223, 224, 225, 226, 232, 233, 234, 235, 236, 237, M205, T124A, T132A, T133A, T134A, T134B, 121A, 121B, 124A, 124B, 132B, 133B, 221A, 221B

0500-LAE-119A

0500-LAE-119B

0500-LAE-119C

UK12-LAE-119D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM. MN 119

AND MN 195 ARE SIMILAR IN

APPEARANCE BUT WERE INSTALLED

AT DIFFERENT TIMES.

50 120

FLOOR ADHESIVE,

YELLOW, UNDER

BLUE CARPETS MISC.

111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 209, 210, 211, 212, 213, 214, 215, 233, 111B, 111C, 121A, 121B, 211A, 211B, 211C

0500-LAE-120A

0500-LAE-120B

0500-LAE-120C

UK12-LAE-120D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM.

50 121

FLOOR ADHESIVE,

YELLOW, UNDER

OLIVE CARPET MISC. 110, 130, 131, 106A

0500-LAE-121A

0500-LAE-121B

0500-LAE-121C

04-May-00 04-May-00 04-May-00

ND

ND

ND

THE 2017 AHERA INSPECTION

TEAM CONFIRMED THE EXISTENCE

OF THIS MATERIAL AND UPDATED

THE INFORMATION BASED UPON

CURRENT CONDITIONS.

50 122

RESILIENT FLOOR

TILE, 1' X 1' GRAY MISC. 111A

0500-LAE-122A

0500-LAE-122B

0500-LAE-122C

UK12-LAE-122D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM. THE

ADHESIVE FOR THIS MATERIAL IS

MN 123.

50 123

FLOOR ADHESIVE,

YELLOW, UNDER

1' X 1' GRAY

RESILIENT FLOOR

TILE MISC. 111A

0500-LAE-123A

0500-LAE-123B

0500-LAE-123C

UK12-LAE-123D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM. THIS IS

THE ADHESIVE FOR MN 122.

50 124

FLOOR ADHESIVE,

YELLOW, UNDER

TAN CARPET MISC.

132, 133, 134, 232, 233, 234, 235, 236, 237

0500-LAE-124A

0500-LAE-124B

0500-LAE-124C

UK12-LAE-124D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM.

50 125

WALLBOARD, 1/2"

THICK, GRAY

PAPER, WHITE

CORE MISC.

111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 131, 132, 133, 134, 200, 209, 210, 211, 212, 213, 214, 215, 220, 222, 223, 224, 225, 226, 230, 232, 233, 234, 235, 236, 237, C103, C105, C201, C203, S101.1, S101.2, S102.1, S102.2, T132A, T134B, 111A, 111B, 111C, 121A, 121B, 132B, 211A, 211B, 211C, 221A, 221B

0500-LAE-125A

0500-LAE-125B

0500-LAE-125C

04-May-00 04-May-00 04-May-00

ND

ND

ND

THE JOINT COMPOUND FOR THIS

MATERIAL IS MN 126.

3 2018

No.

Homo.

Mtl. No.

Material Description

AHERA

CAT Locations Comments

Number Date Result

Table D-2 - Summary of Non-Asbestos Materials for Lakenheath ES

Sample Information

50 126

JOINT

COMPOUND,

WHITE MISC.

111, 112, 113, 114, 115, 116, 124, 125, 126, 127, 131, 132, 133, 134, 200, 209, 210, 211, 212, 213, 214, 215, 220, 222, 223, 224, 225, 226, 230, 232, 233, 234, 235, 236, 237, C103, C105, C201, C203, S101.1, S101.2, S102.1, S102.2, T132A, T134B, 111A, 111B, 111C, 121A, 121B, 132B, 211A, 211B, 211C, 221A, 221B

0500-LAE-126A

0500-LAE-126B

0500-LAE-126C

UK12-LAE-126D*

04-May-00 04-May-00 04-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED TO BE ACM. THIS IS

THE JOINT COMPOUND FOR MN

125.

50 135

JOINT

COMPOUND,

WHITE MISC. T127B, 127A, 127B

0500-LAE-135A

0500-LAE-135B

0500-LAE-135C

UK12-LAE-135D*

08-May-00 08-May-00 08-May-00 23-Jan-12

ND

ND

ND

ND

*SAMPLE WAS ANALYZED BY TEM

AND RESULT WAS NO ASBESTOS

DETECTED. THIS MATERIAL IS NOT

CONSIDERED…

This is the start of the file's text. The full file is on GovTribe.