This document contains an on-call service list and related federal contract opportunity solicitation. The on-call service list details 48 service calls for heating, ventilation and air conditioning (HVAC) equipment from July 2019 to June 2020. The calls involved issues such as no cooling or heating, equipment malfunctions and alarms. The federal contract opportunity is a solicitation for preventive maintenance and repair/replacement services of heating systems for the Department of the Army. Offerors are instructed to submit priced proposals and part/service price lists through the SAM website in response to solicitation number W91QVN20R0202 by the specified due date.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Summary Attach-8. Summary of on call service (Heat Pump) (From July, 2019 to June, 2020)

NoYearMonthCall NoTotal Minutes
12019July131,100
22019Aug6590
32019Sep7740
42019Oct2180
52019Nov5450
62019Dec5250
72020Jan1250
82020Feb190
92020Mar110
102020Apr1100
112020May2310
122020June41,310
Total485,380

on call service (190701~200625)

On call service list (From 2019/07/01 to 2020/06/25) / Heat Pump
NODATEBLDG.NOSection
(Heating, A/C)PROBLEMACTION TAKENWORK STATUSREASON FOR
UNRESOLVEMENTCALLERTEL. NO.WORKERTIME
ARRIVEDTIME
COMPLETEDMinuteSO. NOQuality Assurance
17/17171
#102A/CNo A/CBO cancelled the orderResolvedMR. KIM738-8234TRANE14:4015:0020100008335853YANG, PONG KI
27/87170
#303A/CNo A/CReplaced the magnetic contactor.ResolvedMAJ WARNER010-2259-4905TRANE11:1015:30259100008353053YANG, PONG KI
37/117171
#104A/CNo A/CCleaned A/C tray up and adding refirgerantsResolvedMS. SUSON010-8433-1979TRANE9:0010:0060100008367553YANG, PONG KI
47/177171
#102HeatingA/C is not cooling downNo problem. Instructed the customer how to use the thermostat.ResolvedE5 MESTANJA010-9549-4891TRANE13:0013:4040100008387048YANG, PONG KI
57/197170
#403A/CNo A/CReplaced the capacitor.ResolvedMR. CHANG (HOUSING)738-8234
738-7736TRANE11:0011:4040100008400077YANG, PONG KI
67/207171
#403A/CNo A/CChecked and no problem
Building control unit(BCU) will be checked on 22nd, July (Mon)ResolvedMS. JENNIFER010-2374-3109TRANE14:0015:50109100008399787YANG, PONG KI
77/227171
#102A/CRepair A/C in
Rm#102 and Hallway.Replaced the capacitor and cleaned the strainer in Rm#102. Released the overflow alarm error in the hallway.ResolvedMR. MESTANZA010-9549-4891TRANE15:2016:4080100008400190YANG, PONG KI
87/257171
#302A/CNo A/CCleaned the drain line and reset the alram.ResolvedMR. JASON010-2841-1256TRANE13:0014:0060100008414311YANG, PONG KI
97/262372
#148A/CA/C is malfunctional.Cleaned the drain line.ResolvedMR. KIM010-3695-2972TRANE13:3014:2050100008400192YANG, PONG KI
107/262372
#148A/CA/C is not working.Cleaned the drain line.ResolvedSSG SAXTON722-6175TRANE13:3014:2050100008409765YANG, PONG KI
117/262372
#245A/CRepair the malfunctioned A/C.Released the communication alarm.ResolvedMR. PAK724-9813TRANE14:2015:1050100008405256YANG, PONG KI
127/307171
#204A/CNo A/CCleaned up the drain line.ResolvedMR. PATRICK010-3483-4946TRANE16:3017:4070100008427915YANG, PONG KI
137/317171

1st floor

(Elevator)OtherWater leakage
from the ceilingCompleted water drainage work on the first-floor corridorResolvedMR. MESTANZA010-9549-4891TRANE13:0016:30210100008400191YANG, PONG KI
148/17171
#405A/CRepair leaking A/CMain drain line in the mechanical room was clogged and cleaned the drain lineResolvedMS. EURROWS010-5693-6605TRANE16:1016:4030100008436953YANG, PONG KI
158/77171
#102A/CNo A/CRemoved the frozen part on the evaporator.
Increased the air volume.ResolvedMR. JONATHAN010-9549-4891TRANE9:0011:30150100008450879YANG, PONG KI
168/127171
#505A/CNo A/CUnlocked the alarmed & ResetResolvedMS. VANCLEEF010-2678-7848TRANE9:2010:4080100008467458YANG, PONG KI
178/147171
#505A/CNo A/CTurn up the blower's air amount and reset the alarmResolvedMS. VANCLEEF010-2678-7848TRANE19:3020:3060100008482115YANG, PONG KI
188/167171
#505A/CNo A/CChecked the alarm and reset.ResolvedMR.KIM (COR)736-3024TRANE15:3016:2050DIRECT CALLYANG, PONG KI
198/237171
#102A/CRepair A/C
(Not cooling down)Melted the frozen part of the compressor and replaced the thermostat.ResolvedE5 MESTANZA010-9549-4891TRANE11:2015:00219100008507255YANG, PONG KI
209/57171
#401A/CNO A/CHad the water supply work properly in the cooling tower.ResolvedMRS. HWANG010-5781-7166TRANE14:3016:30120100008540582YANG, PONG KI
219/67171
#404A/CNo A/CA/C did not work temporarily while checking cooling tower. Informed the caller it would be operating soon.ResolvedCPT. GONZALES010-2476-1810TRANE8:409:1030100008544227YANG, PONG KI
229/67171
#204A/CNo A/CChecked and no problem. Explained the caller A/C did not work this morning due to the cooling tower check up.ResolvedMAJ. PATRICK WACHEKA010-3483-4946TRANE15:0015:3030100008544685YANG, PONG KI
239/67171
#102A/CNo A/CChecked and no problem.ResolvedSGT. MESTANGA010-9549-4891TRANE16:0016:2020100008544694YANG, PONG KI
249/87171
#404A/CNo A/CReplaced the inverter and relay.ResolvedMR. ROSALEF010-2476-1810TRANE10:4016:30349100008548565YANG, PONG KI
259/117171
#204A/CNo A/CChecked and reset the electric systemResolvedMRS. KATE010-3431-9636SHIM, JAE CHEON19:0019:3030FIRE STATIONYANG, PONG KI
269/127171
#404A/CNo A/CAdjusted the inverter setting.ResolvedMR. ROSALES010-2476-1810TRANE12:2015:00160100008570110YANG, PONG KI
2710/27171
#401A/CNo A/CChecked and filled up the refrigerantResolvedMS. HWANG010-5781-7166TRANE10:4011:3050100008619557YANG, PONG KI
2810/182372
#135HeatingNo hot waterChecked and reset the boiler.ResolvedMR. HONG010-3630-5249TRANE11:2013:30129100008669830KIM, CHONG U
2911/42372
#135HeatingNo hot waterReplaced the dryer and expansion valve.ResolvedCPL BYON724-3415TRANE10:0015:30330100008717680YANG, PONG KI
3011/77171
#204Heating& A/CRequest for rescheduling maintenanceReschedued PM 11/8 Fri 10:00A.M.ResolvedMRS. KATE010-3431-9636TRANE17:0017:1010DIRECT CALLYANG, PONG KI
3111/137170
#501HeatingHeating system is not workingUnlocked the alarm because pressure was lowResolvedMS. DAVIDSON010-5749-4214TRANE3:304:3060100008744739YANG, PONG KI
3211/157047 AHeatingReplace the filter
for the heaterTrane's own contract. Asked B.O. Desk to transfer DMO to the Reefer shopResolvedLTC WON010-2408-7943TRANE9:309:4010100008754400YANG, PONG KI
3311/152372HeatingHeating is not workingFixed the thermostat settings.ResolvedLTC PARK723-2196TRANE13:0013:4040100008754671YANG, PONG KI
3412/94431HeatingNo heatThe H/P worked properly this morning. Revisited at 14:15 and cleaned the auxiliary heater, tightened the loose wiring.ResolvedMR. YANG736-4381TRANE8:108:4030DIRECT CALLKIM, CHONG U
3512/94431HeatingNo heatTechnician will visit on 10th Dec at 08:00 by the caller's request.PendingCaller's requestCOL WASHINGTON738-7441
738-5506TRANE18:0018:1010100008819978KIM, CHONG U
3612/104431HeatingNo heatRevisited there for checking, found out that heating is OK by the CallerResolvedCOL WASINGTON738-5506
010-2010-6952TRANE
MR. SHIM7:408:2040100008819978KIM, CHONG U
3712/194431HeatingNo heatReplaced the blower fan, module and motorResolvedCOL WASHINGTON010-2010-6952TRANE7:3010:00150100008846079KIM, CHONG U
3812/311380HeatingNo heatWe transferred that issue to TRANE, as there's no our EquipmentResolvedREEFER SHOP736-4401TRANE & MAXERVE9:209:4020100008865584KIM, CHONG U
391/237170
#501HeatingNoise from the heating systemChecked the equipment. No more noise from the duct.ResolvedMS. DAVIDSON010-5749-4214TRANE11:3015:40249100008927924KIM, CHONG U
402/267171
#401HeatingNo heatReplace the thermostatResolvedMS. HWANG010-5781-7166TRANE14:0015:3090DIRECT CALLYANG, PONG KI
413/227047
#AHeatingNo heatTRANE'S own contract. Notified TRANE worker by fire station. Transferred the service order to Reefer shop.ResolvedLTC WON010-2790-7943TRANE20:3020:4010FIRE STATIONYANG, PONG KI
424/177171HeatingWater leaking from
the pipes outside bldgDrained water on the roof of the building.ResolvedMR. DAVISON010-5749-4214TRANE
MAXERVE13:0014:40100100009150674YANG, PONG KI
435/47171
#401HeatingNo A/CCleared the cooling tower's locked alarmResolvedMS. HWANG010-5781-7166TRANE" "13":"00" "15":"10129DIRECT CALLYANG, PONG KI
445/277170
#302A/CA/C is not workingChecked and adjusted the valveResolvedMR. CHRISTIANSEN010-2856-9829TRANE" "16":"00" "19":"00180100009244960YANG, PONG KI
456/77170
#302A/CA/C is not workingTemporarily stabilized an overflowing-issue
between the cooling towersResolvedMRS. CHRISTIA
MAJ. CHRISTIANSE010-2637-1487
010-2856-9829TRANE" "2":"20" "18":"50990100009265102YANG, PONG KI
466/137170
#501A/CA/C is not workingUnlocked the alarm and cool downed its coolantResolvedMS. DAVISON010-5749-4214TRANE" "10":"00" "13":"00180DIRECT CALLYANG, PONG KI
476/257170
#501A/CNO A/CReset the system after mometary power failureResolvedMS. DAVISON010-5749-4214TRANE" "17":"50" "19":"1080DIRECT CALLYANG, PONG KI
486/257170
#401A/CNO A/CReset the system after mometary power failureResolvedMS. HWANG010-5781-7166TRANE" "18":"10" "19":"1060DIRECT CALLYANG, PONG KI