Appendix J - Labeling Specification.docx

DOCX document 2 MB Posted

Attached to
Condenser Water Filtration System Upgrade Federal contract opportunity
Solicitation number
HC102821R0018
Issued by
Defense Information Systems Agency

About this file

This request for proposal is for upgrading an existing condenser water filtration, controls and piping system at a Defense Information Systems Agency facility in San Antonio, Texas. The contractor will enhance the cooling towers, replace piping, adjust water pumps and filtration controls, and provide temporary chillers for redundancy testing. A site visit is scheduled for March 31, 2021 to allow contractors to better understand the work. Questions are due by April 9, 2021. The contractor must improve reliability, energy use and redundancy to meet Department of Defense standards for the IT mechanical system at this Data Center facility.

View the file

Other files for this federal contract opportunity

Other files attached to Condenser Water Filtration System Upgrade, newest first.
File Type Posted
HC102821R00180009.pdf PDF
QandA.xlsx XLSX spreadsheet
HC102821R00180008.pdf PDF
HC102821R00180007.pdf PDF
HC102821R00180003.pdf PDF
Appendix R - Temporary Chiller Connection Point Drawing V2.pdf PDF
HC102821R00180002.pdf PDF
Q and A on Water Filtration Upgrade.xlsx XLSX spreadsheet
IMG_1624.JPG JPG image
IMG_1626.JPG JPG image
IMG_1625.JPG JPG image
IMG_1616.JPG JPG image
IMG_1612.JPG JPG image
IMG_1611.JPG JPG image
IMG_1606.JPG JPG image
IMG_1605.JPG JPG image
IMG_1608.JPG JPG image
IMG_1597.JPG JPG image
IMG_1591.JPG JPG image
IMG_1592.JPG JPG image
IMG_1588.JPG JPG image
IMG_1584.JPG JPG image
IMG_1582.JPG JPG image
IMG_1579.JPG JPG image
IMG_1576.JPG JPG image
IMG_1623.JPG JPG image
IMG_1621.JPG JPG image
IMG_1617.JPG JPG image
IMG_1613.JPG JPG image
IMG_1615.JPG JPG image
IMG_1599.JPG JPG image
IMG_1596.JPG JPG image
IMG_1590.JPG JPG image
IMG_1589.JPG JPG image
IMG_1585.JPG JPG image
IMG_1583.JPG JPG image
IMG_1578.JPG JPG image
IMG_1572.JPG JPG image
IMG_1577.JPG JPG image
IMG_1575.JPG JPG image
IMG_1573.JPG JPG image
encl 4_qasp - SAT CW Filtration and Upgrades.pdf PDF
Appendix R - Temporary Chiller Connection Point Drawing.pdf PDF
Appendix G - ASHRAE Standard 202 - 2013.pdf PDF
Appendix E - VFD Specification.docx DOCX document
HC102821R0018-CLIN Pricing Worksheet.xlsx XLSX spreadsheet
Appendix A - Mechanical Drawing Set (FOUO).pdf PDF
Appendix Q - Contractor NDA.docx DOCX document
Appendix P - Electrical Safety Program.pdf PDF
Appendix L - 2018 BAS Drawings (FOUO).pdf PDF
Show all 50

Condenser Water Filtration System Upgrade has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table of Contents

1.Purpose3
2.Scope3
3.Definitions3
4.General Requirements3
4.1.Labeling3
4.1.1.Materials3
4.1.2.Attachment4
4.1.3.Character Design and Size4
4.2.Color Coding5
4.2.1.Color Coding – Pipe and Conduit5
4.2.2.Color Coding – SEC Labels6
4.3.Language7
4.4.Other Identification Systems7
5.Facilities8
5.1.Load Bearing Columns8
5.1.1.Identification8
5.1.2.Labeling8
5.2.Rooms8
5.3.Computer Rooms and IT Equipment8
5.3.1.Floor Grid Designation8
5.3.2.IT Cabinets9
5.3.3.Non-IT Systems, Equipment, and Components (SECs)10
5.3.4.Power to IT Cabinets10
6.General Requirements - Systems, Equipment, and Components Labeling11
6.1.Unique Identifier (UID) Number11
6.1.1.Format13
7.Mechanical Systems, Equipment, & Components14
7.1.Labeling14
7.1.1.Valves & Dampers14
7.2.Mechanical Piping Systems, Equipment, and Components15
8.Electrical Systems, Equipment, & Components15
8.1.Labeling15
8.2.Typical Electrical Systems, Equipment, and Components15
8.3.Other Electrical Systems, Equipment, and Components16
8.3.1.Devices, and Electrical Junctions and Boxes16
8.3.2.Security Systems, Equipment, and Components16
8.3.3.BAS Systems, Equipment, and Components16
Appendix 1. Systems, Equipment, & Components Designator List17
Appendix 2. System Designator List21
Appendix 3. Switchgear, Large Switchboard, and Motor Control Labeling Example22
Appendix 4. Switchboard, and Large Panelboard Labeling Example23
Appendix 5. Panel Schedule Labeling Example24
Appendix 6. PDU and RDC Schedule Labeling Example26
Appendix 7. OTB Schedule Example28

List of Figures

Figure 1 – Compliant Piping System Marking and Labeling6
Figure 2 – Compliant Column Label8
Figure 3 – Example IT Cabinet UID9
Figure 4 – Compliant IT Cabinet Label10
Figure 5 – Compliant IT Cabinet Label10
Figure 6 – Compliant Whip/MPDU A-Feed10
Figure 7 – Compliant Whip/MPDU Feeds10
Figure 8 – Compliant Label13
Figure 9 – Compliant Electrical SEC Label13
Figure 10 – Compliant Mechanical SEC Label13
Figure 11 – Compliant Mechanical SEC Label14
Figure 12 – Compliant Mechanical SEC Label14
Figure 13 – Compliant Valve Label14
Figure 14 – Compliant Valve Label14
Figure 15 – Sample IT Power Whip Label15
Figure 16 – Compliant Electrical SEC Label15
Figure 17 – Compliant Electrical SEC Label15
Figure 18 – Essential Switchgear22
Figure 19 – Panelboard23
Figure 20 – Electrical Panel24
Figure 21 – Panel Schedule Template24
Figure 22 – PDU Panel26
Figure 23 – PDU/RDC Panel Schedule Template27
Figure 24 – RDC Panel Schedule Template27
Figure 25 – OTB Schedule Template28

List of Tables

Table 1 – Compliant Color-Coding for Piping and Conduit5
Table 2 – Compliant Color-Coding for SEC Labels6
Table 3 – SEC Designator17
Table 4 – Legacy SEC Designator20
Table 5 – System Designator21
Table 6 – Legacy SEC Designator21

Purpose This DISA (Defense Information Systems Agency, Facilities Engineering Denver) standard establishes guidance for identifying, marking and labeling structures, systems, equipment, and components (SSEC).

Scope This standard contains instruction for uniform identification, labeling, and marking of SSEC at DISA locations. Applications include:

Identifying, labeling, and marking new SSEC when installed Uniform identification of SSEC across DISA datacenters Definitions ‘Shall’ identifies mandatory elements and requirements.

‘Should’ identifies a recommendation that is based on standard industry practice and good business policy.

‘May’ identifies when permission is granted rather than constituted as a requirement.

General Requirements All SSEC shall be labeled in accordance with this standard before being designated operable or in service.

Labeling in areas where hazards exist (i.e., high structures and confined spaces) shall be evaluated against safety requirements. For example, to reduce personnel risk, some SSEC could be labeled as site conditions permit (e.g., shutdown), or when scheduled maintenance is performed.

Labeling Labels shall be permanently attached and designed to withstand wear, moisture, erosion and corrosion. Additionally, labels shall be heat resistant in high temperature areas, corrosion resistant in acidic or caustic areas, and both UV and corrosion resistant in outdoor areas.

Position labels so they are readily visible and oriented in a horizontal position on a flat surface, where feasible. Labels shall be legible without manipulation by site personnel. Large SSEC shall be labeled in multiple locations, in close proximity to where workers perform their tasks.

Installed labels or tags shall not interfere or alter existing manufacturer’s nameplate or code information.

Labels shall be mounted to preclude accidental removal and located to eliminate any possible confusion as to the item being identified and shall not obscure other items nearby.

Label size shall be based on available lighting and anticipated reading distances. SSEC which require local operation during blackout or reduced visibility conditions shall be marked with reflective or glowinthedark tape.

Labels shall not interfere with an operator’s ability to read an instrument, display, or gauge.

Materials Plastic Labels: Flexible engraving stock (aka Lamicoid or Phenolic) with at least a two-color plastic material to obtain the required color coding combination is the preferred material for permanent systems, equipment, and components (SECs) labels. Characteristics of flexible engraving stock include abrasion, heat, wear, and chemical resistance.

Metal Labels: Metal tags are acceptable for permanent equipment SEC labels. Paints or powder coatings used on these tags shall be environmentally stable, chemically resistant, and wear resistant.

Identification Tape: Commercially available tape products may be used for labeling of common SEC where detailed unique identifiers (UIDs) and other information is not necessary; for example, labels on insulated piping indicating contents and direction of flow.

Machine-Printed Identification Tags: On SEC subject to frequent modification or replacement (for example, power whips from a power distribution unit (PDU) to an IT equipment rack or the plug in unit for an overhead track bus (OTB)), machine-printed labels are acceptable. These typically print on a flexible form of machine-generated plastic-coated material, which shall be secured to the SEC in such a manner as to protect the labeling information from degradation. Machine-printed identification information shall be indelible, environmentally stable, and chemically resistant.

Unapproved Materials: Materials which can be lost, damaged, rendered unreadable, easily removed, soiled or degraded by operating environment, or which are of a non-permanent nature shall not be used for labeling or identification purposes. This includes (but is not limited to) paper, paper in clear plastic protectors, and direct labeling of SEC with markers. Paint may only be used where specifically identified in this standard, and must be applied using a stencil which meets the font requirements.

Attachment Adhesives: Adhesives may be used to secure labels or tags to SECs. Adhesives shall securely fasten the label to the SEC without causing degradation to the SEC or the label. The adhesive shall be chemically compatible with the label material, the component material, and the environment. Adhesives shall not be used on stainless steel piping or components.

Wire: Bare wire may be used for attaching labels to SECs where use of adhesives is not practical and there is no risk of the bare wire becoming electrically energized (e.g., valve tags).

Cable Ties: Standard 50 lb cable ties (a.k.a. zip ties, nylon ties, plastic ties, tie wraps) may be used for attaching labels to SECs where use of adhesives is not practical (e.g., valve tags).

Chain: Zinc plated general utility chain may be used for attaching labels to SECs. The type of chain shall be single-jack chain of trade size 20 or 18.

Screws or Rivets: Screws or rivets may be used to secure labels to SECs as long as the attachment does not cause degradation to the SEC or label. Screws shall be metal type, with size, length, diameter, head, pitch, and axis not prescribed, but sufficient to adequately adhere labels. Rivets shall be steel, with type and dimensions not prescribed, but sufficient to adequately adhere labels.

Character Design and Size Labels shall be formed with upper and lower case letters using simple letter styles. A bold sans serif font, minimum font size 24, is standard for SEC labeling purposes. The maximum standing viewing distance for minimum font sizes is 60 inches (from label to the eye of the standing individual). With this font size, a 3 x 5 inch label is recommended.

Labels not visible from this distance shall use bold sans serif font 28. With this font size, a 4 x 6 inch label is recommended.

Handwritten labels are not permitted.

Color Coding Color Coding – Pipe and Conduit Color code mechanical piping and electrical conduit in accordance with the following table:

Table 1 – Compliant Color-Coding for Piping and Conduit

Fluid Type / System
Pipe/Conduit Color
Text Color
Flammable Piping
Yellow
Black
Combustible or Fuel Piping
Brown
White

Fire Systems Piping (all) Fire Systems Conduit (in accordance with NFPA 70)

Red
White
VESDA Piping
Orange
White
Steam Piping
Pink
Black
Boiler Hot Water Piping
Orange
Black
Domestic Hot/Cold Water Piping
White
Black
Chilled Water Supply Piping
Blue
White
Chilled Water Return Piping
Light Blue
White
Condenser Water Supply Piping
Green
White
Condenser Water Return Piping
Light Green
White
Security Systems Conduit
Purple
White
Building Automation System Conduit
Green
Black

Piping and conduit shall be color coded and labeled/stenciled in accordance with the following:

Label or stencil the system/service in accordance with Table 1, using industry standard spacing and the following

Outside Diameter
Label Height
Text Height
<1-1/4 inch
1 inch
1/2 inch
1-1/2 to 2 inch
1 inch
3/4 inch
2-1/2 to 6 inch
2 inch
1-1/4 inch
8 to 10 inch
3 inch
2-1/2 inch
>10 inch
4 inch
3-1/2 inch

Place arrows to indicate direction of flow through the piping. Where flow is bidirectional, arrows shall not be used.

Place labels on the center line of pipe in accordance with Table 1, with the following exceptions:

If the piping is located above the normal line of vision, the label shall be placed below the horizontal center line of the pipe to maximize visibility If the piping is located below the normal line of vision, the label shall be placed above the horizontal center line of the pipe to maximize visibility.

Label piping and conduit, including when not normally exposed to view, at the following locations:Figure 1 – Compliant Piping System Marking and Labeling

Either side of wall or floor penetrations Near valves or flanges Adjacent to changes in direction, branches, at any line entry or reentry point Every 20 to 25 feet on straight runs.

Color code conduit and piping or insulation, including when not normally exposed to view, in accordance with one of the following:

For conduit or uninsulated piping, either use paint, or a manufacturer’s color option in accordance with Table 1.

Enclose piping insulation in colorcoded plastic (vinyl or PVC) in accordance with Table 1.

Exceptions: Do not color code piping or insulation jacketing, only label/stencil in accordance with Table 1 and place directional arrow for the following instances:

Outdoor Combustible/Fuel piping. If painted, only paint outdoor combustible/fuel piping white.

Outdoor insulated piping with aluminum jacket.

Legacy color schemes in use at DISA datacenters are authorized to remain in use. Any and all insulation replacements, projects affecting piping and conduit systems, and new installations shall use the color coding in accordance with this standard.

Color Coding – SEC Labels SEC label colors shall provide a high contrast between characters and background to enhance legibility.

Electrical and mechanical SEC labeling shall be color coded in accordance with the following table:

Table 2 – Compliant Color-Coding for SEC Labels

SEC
Background Color
Text Color
Fire Systems (including Fire Detection/Protection, Fire Alarm, VESDA) & Emergency Power Off
Red
White
“A” Bus Distribution (Critical)
White
Black
“B” Bus Distribution (Critical)
Blue
White
Building
Tan
White
Building Automation System
Green
Black
Boiler
Orange
Black

“C” Bus Distribution (Essential) & Essential (Emergency Generator) Distribution

Black
White
Compressed Air
Dark Red
White
Chilled Water Supply
Blue
White
Chilled Water Return
Light Blue
White
Condenser Water Supply
Green
White
Condenser Water Return
Light Green
White
“D” Bus Distribution (Essential)
Gray
Black

Dual-fed “A” / “B” Bus Distribution (Critical) or Dual-fed “C” / “D” Bus Distribution (Essential)

Brown
White
Direct Current
Dark Blue
White
Domestic Hot/Cold Water
Light Blue
Black
“E” Bus Distribution
Gold
White
“F” Bus Distribution
Silver
Black
Fuel Oil
Yellow
Black
Ground
Dark Green
Black
Natural Gas
Dark Gray
White
Steam
Pink
Black

Language Use of SSEC UIDs and descriptions shall be consistent among SSEC labels, equipment lists, drawings, procedures, checklists, and load lists. Checklists, procedures, and installed labels shall use UIDs to describe the name and number nomenclature for the SSEC.

Only use abstract symbols with a commonly accepted meaning for all intended users (e.g. %). Brevity should not be stressed if the results will be unfamiliar to operating personnel. Words on labels should be concise and still convey the intended meaning.

Other Identification Systems If a conflict with any other mandatory standard(s) or guidance affecting the data center environment is identified, DISA will make a determination on the governing standard(s) or guidance. This standard does not define identification, labeling, and marking standards for communications, data cabling, or computing and storage enclosures.Figure 2 – Compliant Column Label

Facilities Load Bearing Columns Identification Load-bearing columns (or posts), shall have column labels to identify the column number. This column number is uniquely defines a quadrant around the specific column and abuts quadrants of adjacent columns.

Using an alphanumeric system, column UIDs shall designate A01 as the first corner column of the building as defined by current drawings. Floor numbers are not included on column UIDs, however may be used when identifying columns on drawings, with the floor number preceding the column UID.

Labeling Column UIDs shall be a 4 inch character, semi-gloss black lettering with the UID visible from any location in the room. UIDs may be applied using paint, adhesives, or other means that meet the required dimensions and characteristics mentioned above. UIDs shall be located on at least two opposing sides of each column.

Rooms and Doors The minimum standard for these labels is a plastic label in accordance with paragraph 4.1.

Rooms All rooms within each facility shall be labeled at all entrances. Signage shall be posted immediately adjacent to the entrance designating the room.

Room numbers should be three numbers in length, with the first number designating the floor number followed by 2 sequential numbers. For example, RM-101 is on the first floor and is the first room designated. Rooms may also retain their name; e.g., Battery Room as long as the name is in line with the current room function and is included as part of the room number; e.g., Battery Room RM-103. An alpha designator may follow the number when a room has been subdivided. Areas that do not follow this convention may use a descriptor of the location, e.g., MechYard, Roof, Mezzanine, or Outside.

Doors All doors within each facility should be labeled with the door number on both sides of the door.

Door numbers should be three numbers in length, with the first number designating the floor number followed by 2 sequential numbers. For example, Door #101 is on the first floor and is the first door designated. Access description may be included, for example “Roof Access, Door #234.”

All doors which alarm when opened shall have a warning sign posted in accordance with the site standard. If the approved sign is not available for installation when the alarm on the door is activated, a similar temporary paper sign shall be posted until the permanent approved sign is available for installation.

Computer Rooms and IT Equipment Floor Grid Designation For access floors, the floor tiles are given X and Y coordinates. For solid floors, a 24 x 24 inch or 60 x 60 cm grid centered on column lines is given X and Y coordinates for layout purposes. These coordinates consist of numbers and letters.

Labeling Label floor grid coordinates on all walls, centered on the coordinate. Letter coordinates are labeled for every coordinate. Number coordinates are labeled in accordance with one of the following:

Access floor data centers:

Every coordinate, or Every fifth coordinate, and the first and last coordinate (i.e., a room with 23 numbered coordinates would have a minimum of 1, 5, 10, 15, 20, 23 labeled).

Solid floor data centers: Every numbered coordinate shall be labeled.

Floor grid coordinates shall be at least a 2 inch character, semi-gloss black lettering mounted in a position visible from the middle of the room at the same height, typically 7 to 9 feet above the floor. Coordinates may be applied using paint, adhesives, or other means that meet the required dimensions and characteristics.

Legacy floor grid coordinate labels in use at DISA datacenters are authorized to remain in use if the labels are readable from the middle of the room.

IT Cabinets The IT cabinets shall be assigned a UID Number based on the grid location at the front of the cabinet (cold aisle). Where the front of the cabinet is across 2 coordinates, the coordinate which is covered by the majority of the cabinet is used. Where the front of the cabinet is equally split across 2 coordinates, the left front corner, when looking at the front of the cabinet in the cold aisle, is used.

The UID Number shall have three fields:

1st Field: Floor Number, when the building has more than one floor 2nd Field: Floor grid letter coordinate at the front of the cabinet (one or more letters) 3rd Field: Floor grid number coordinate at the front of the cabinet (two numbers, including leading 0s)

Figure 3 – Example IT Cabinet UID

Assuming the IT cabinets in Figure 3 are on the third floor, the UIDs would be 3E18, 3F18, 3G18, 3E22, 3F22 and 3H22.

Labeling For IT cabinets, the cabinet shall be labeled on the front and rear exterior of each cabinet, on the on the frame above the door. The minimum standard for these labels is plastic color coded label in accordance with paragraph 4.1 and Table 2.

IT cabinet labels shall have at least 2 lines of information:

Line 1:IT Cabinet UID
Line 2:Power source circuits

For PDUs: PDU UID - pnl # - ckt #s For OTBs: Plug in Unit UID Additional Lines: similar to Line 2 until all power sources are listed.

When IT cabinets are powered by an OTB, the A & B feed plug in units shall have the same sequence number.

Figures 4 and 5 show a typical PDU powered or OTB powered IT cabinet label:

← Line 1 → ← Line 2 → ← Line 3 → ← Line 4 → ← Line 5 →

Figure 4 – Compliant IT Cabinet Label

Figure 5 – Compliant IT Cabinet Label

Non-IT Systems, Equipment, and Components (SECs) For non-IT SECs, the UID label requirements are outlined in Section 6, General Requirements - Systems, Equipment, and Components Labeling.

Power to IT Cabinets Each IT cabinet is fed from two buses. The feed and labels are color coded in accordance with Table 2.

Power Distribution Unit (PDU) Powered IT Cabinets Whips provide power from PDUs to the IT cabinet. Whip cables shall have continuous external jacketing to correspond with the feed color code.

Whip receptacles are connected to the IT cabinet metered power distribution units (MPDUs). Figures 6 and 7 show compliant labels when installed under the access floor:

Figure 6 – Compliant Whip/MPDU A-Feed

Figure 7 – Compliant Whip/MPDU Feeds

Labels for each whip receptacle shall consist of a rectangular tag imprinted with one line of information:

Line 1: PDU sequence number - pnl # - ckt #s, or PDU UID-pnl #-ckt #s For Example, if the whip is fed from PDU_2-A-04, Panel 03, Circuit 10 the label would be 04-03-10 or PDU_2-A-04-PNL 03-CKT 10. The minimum standard for these labels is machine-printed identification tags in accordance with paragraph 4.1 and Table 2.

Overhead Track Bus (OTB) Powered IT Cabinets OTBs provide plug in units with receptacles directly above the IT cabinets. Each OTB track, end feed unit, and plug in unit is color coded to correspond with the feed in accordance with Table 2, using the manufacturer’s standard color options.

Each plug in unit connected to the track is given a UID, however the sequence number may not be in order due to changes with IT cabinet layouts. When moved, the UID only changes if the receptacle is connected to a different OTB. Each plug in unit UID inherits the OTB UID and adds an additional sequence number:

1st Field: OTB UID, followed by a dash 2nd Field: Sequence Number. Two digits including leading 0s.

Labels for each plug in unit shall consist of a rectangular tag imprinted with one line of information:

Line 1: plug in unit UID Note: the A-feed and B-feed plug in units for the same rack must have the same sequence number.

For example, if the MPDU is connected to the second plug in unit on OTB_2-A-15, the label would be OTB_2-A-15-02. The minimum standard for these labels is machine-printed identification tags in accordance with paragraph 4.1 and Table 2.

Metered Power Distribution Units (MPDUs) The MPDU cords shall be marked with a minimum of four inch wide tape to demarcate the feed. The tape shall be placed in two locations:

Within one foot from where the MPDU plugs into the receptacle/socket, and Where the MPDU cord enters the IT cabinet on the inside of the cabinet.

The MPDU cord shall be labeled in the same way as the whip/plug in unit. The minimum standard for these labels is machine-printed identification tags in accordance with paragraph 4.1 and Table 2.

General Requirements - Systems, Equipment, and Components Labeling Unique Identifier (UID) Number All SECs shall be assigned a UID Number. The UID Number shall have a minimum of four fields:

1st Field: SEC Designator. Reference Appendix 1 for approved SEC Designators. The SEC Designator is followed by an underscore Note, breakers located on large switchboards (SWBDs), switchgear (SWGR), and motor control centers (MCCs) use the SEC Designator “BRKR” 2nd Field: Floor Number. For areas not given a numerical floor number, use 0 for basement, G for outside, R for roof, and M for mezzanine. The floor number is followed by a dash.

3rd Field: One of the following, followed by a dash:

System designator for the power source (bus).

If the equipment has multiple power sources connected internally, all shall be listed, with the normal power source first.

If the equipment is down-stream of a dual fed SEC, only use the normal power source.

System designator for the system in which the equipment is installed. Reference Appendix 2 for approved system designators. This is used only for any of the following equipment types or systems:

Equipment type:

Valves (VLV, RVP) Back-Flow Preventer Instrumentation (AIT, FIT, LIT, PDIT, PIT, RDSD, RDSM, TIT) Tanks (AT, BT, BFT, CAT, CRT, DT, ET, FT, WT) Chemical Shock Feeder Strainer Heat Exchanger Water Meter Grounding System Any other equipment type without a power source Systems:

Building (EML, ES, ESHR, EWASH, GATE, ID, IM, LIFT, LVR, OHDR, SHRDHD, SPK, VAV, WF, WNA, WNE, WNG) Building Automation System Fire Protection Boiler Domestic Water Fuel Oil Natural Gas Emergency Generators, after the generator and until after multiple power sources are connected.

Breakers on SWBDs, SWGR, and MCCs: The 3rd field is split into two parts:

The SEC designator for the SWBD/SWGR/MCC, followed by a dash The system/power source for the SWBD/SWGR /MCC 4th Field: Sequence Number: One of the following:

Two digits including leading 0s.

Breakers on SWBD, SWGR, MCC: manufacturer’s breaker number.

5th Field: Additional Sequence Number. Two digits and includes leading 0s. This additional sequence number is only used for specifically identified SEC Designators, when required. A dash separates the first and additional sequence numbers. The additional sequence number shall be one of the following:

VAVs: the associated AHU number (AHU SEC, followed by sequence number) All other equipment: Two digits and includes leading 0s.

Examples:

CRAH_3-CD-15 (Computer room air handler on 3rd floor connected to the C & D buses, unit # 15) EDP_1-C-01 (Essential distribution panel on 1st floor connected to C bus, unit # 1) EDP_1-C-01-02 (Subpanel #2 connected to EDP_1-C-01) MTS_1-CD-01 (Manual transfer switch on 1st floor connected to both C & D buses internally, unit # 1) OTB_2-A-03 (Overhead track bus on 2nd floor connected to the A bus, unit # 3) OTB_2-A-03-05 (The 5th plug in unit connected to OTB_2-A-03) PDU_4-B-06 (Power distribution unit on the 4th Floor connected to the B bus, unit # 6) VAV_1-BL-01-AHU9 (VAV associated with an AHU with sequence number 09) ESWGR_G-EG-01 (Emergency switchgear for the emergency generator, located outside, unit # 1) BRKR_G-ESWGR-EG-UPSA2 (Breaker UPSA2 located on ESWGR_G-EG-01) Format Label SECs using materials, attachment method, and size in accordance with section 4.1. Labels shall consist of a rectangular tag or pendant engraved, embossed, or imprinted with five (5) lines of information:

Line 1:UID Number (required)
Line 2:Descriptor (Capacity) (required)
Line 3:Parent or From UID (electrical source) (required)
Line 4:“Common” or “Legacy” Name (optional)
Line 5:BAS Device Name (required when applicable)
Line 1 →

Line 2 → Line 3 → Line 4 → Line 5 →

Figure 8 – Compliant Label

Background and text color in accordance with Table 2. If the SEC has dual power sources internal to the SEC, then the dual power color is used.

Line 1: UID Number, in accordance with paragraph 6.1.

Line 2: Varies by SEC type. For most SEC, this line captures the capacity of the SEC and is a required field. For valves, it captures the normal valve position and is required.

Line 3: Parent electrical SEC. On the label, it is reflected with the Parent UID Number(s) immediately followed by the circuit or breaker when the circuit or breaker does not have a unique UID.

Line 4: “Common” or “Legacy” name (optional), and has quotes around the name. For valves, this may be used to identify the valve type.

Line 5: BAS Device name (required when applicable). If an SEC has a BAS Device name, which is not the same as the UID, then it is a required field. If a valve is located in a zone, list the zone for the BAS device name. If an SEC does not have a BAS Device name, valve zone, or the BAS Device name matches the UID, then the field is left blank.

Figures 8, 9, and 10 show examples of compliant labels.

← Line 1 →

← Line 3 →

Figure 9 – Compliant Electrical SEC Label

Figure 10 – Compliant Mechanical SEC Label

Mechanical Systems, Equipment, & Components Labeling Mechanical SECs shall be labeled with plastic labels and attached to a structural member of the SEC not normally removed during routine maintenance (e.g., base plate) in a consistent location for similar SEC, and in accordance with paragraph 6.1.1. Ensure all labels are visible after insulation is installed.

← Line 1 →

← Line 3 →

Figure 11 – Compliant Mechanical SEC Label

Figure 12 – Compliant Mechanical SEC Label

Valves & Dampers Facility valves and dampers shall be labeled separately from the associated SEC, unless part of an assembly.

Stainless steel tagging wire shall be placed in such a manner so as not to damage the valve stem or impede operation of the valve. Label plates and connecting wire shall not be threaded through the valve hand wheels, operating chains, or damper linkage.

Chain-operated valves shall be labeled at the valve body. In addition, labels shall be placed on a small piece of plastic pipe or metal ring through which the chain can easily pass, allowing the label to remain at the bottom of the chain loop.

Valves associated with a piece of equipment or component, such as backflow preventers (BFPs), do not require a separate UID; the UID of the BFP encompasses the assembly.

When numbering valves including those without an associated process and instrumentation diagram (P&ID), start numbering at the source and sequentially follow the process flow of that system.

← Line 1 →

← Line 3 →

Figure 13 – Compliant Valve Label

Figure 14 – Compliant Valve Label

Mechanical Piping Systems, Equipment, and Components Mechanical piping SEC and conveyed materials, unless otherwise noted in this standard, shall follow the current version of the Scheme for Identification of Piping Systems (ANSI/ASME A13.1). For the purposes of this standard, piping SEC shall include pipes of any kind and, in addition, fittings, valves, and pipe coverings. Supports, brackets, or other accessories are specifically excluded from applications of this standard. This standard does not apply to pipes buried in the ground.

Electrical Systems, Equipment, & ComponentsFigure 15 – Sample IT Power Whip Label

Labeling Electrical distribution SEC including, but not limited to, transformers, switchgear, switchboards, UPS modules, generators, motor control centers, distribution panels (both primary & secondary), and bus and switchyard components shall be labeled with plastic labels.

Smaller components such as breakers, switches, IT equipment power circuits (“whips”), and associated receptacle boxes shall be labeled with approved machineprinted tags secured with clear plastic or adhesive tape, cable tags or other approved methods.

Labels installed internal to electrical or electronic components shall not provide a ground or short circuit path or interfere with the operation of components. All electrical equipment which is served by or which contains multiple sources of power shall comply with NFPA 70 standards to identify all disconnecting means. Breakers for remote shutdown equipment that is operated from the local breaker shall have an additional label fabricated from luminescent or reflective tape to aid in identification during blackout or remote shutdown. Emergency Power Off (EPO) buttons for remote emergency shutdown of SEC shall have an additional label fabricated from luminescent or reflective tape to aid in identification during blackout or remote shutdown.

Typical Electrical Systems, Equipment, and Components MCCs, power transformation and switching equipment (transformers, SWGR, SWBDs, and other SEC shall be labeled by section and compartment. See Appendix 3 (Labeling Examples) for a visual representation.

All distribution panelboards (DPs) shall have associated panel schedules or circuit directories physically located at each panel. This includes switchboards and large DPs (typically greater than 225A), which shall be physically labeled adjacent to each circuit (See Appendix 4). Individual circuit breakers inside DPs (typically rated less than or equal to 225A) shall be physically numbered adjacent to each breaker, corresponding to the panel schedule (See Appendix 5).

← Line 1 →

← Line 3 →

Figure 16 – Compliant Electrical SEC Label

Figure 17 – Compliant Electrical SEC Label

Individual circuit breakers inside PDUs and remote distribution cabinets (RDCs) shall be physically numbered adjacent to each breaker, corresponding to the PDU panel schedule (See Appendix 6). All OTBs shall have a schedule, maintained by maintenance (see Appendix 7). On Line 1, SWGR, SWBDs, RDCs, MCCs, and DPs with sections or sub-panels shall utilize the 4th Field Sequence of the UID Number to differentiate panels. RDCs inherit the sequence number from the parent PDU. Plug in units inherit the OTB UID and utilize the 4th field sequence number to identify the plug in unit. For all other electrical SECs, the 4th Field Sequence Number of the UID Number is not required.

Other Electrical Systems, Equipment, and Components Devices, and Electrical Junctions and Boxes Identification and labeling shall be made on all devices, and electrical junction and terminal boxes in accordance with facility requirements.

Security Systems, Equipment, and Components Security systems, equipment, and components, including the automated control systems, integrated security systems, public address systems, mass notification systems shall be labeled in accordance with the DISA property accountability procedures and facility property procedures. Conduit shall be color coded in accordance with Table 1.

BAS Systems, Equipment, and Components Labeling for Building Automation Systems (BAS) systems shall be in accordance with paragraph 4.1 and Table 2. Conduit shall be color coded in accordance with Table 1.

Systems, Equipment, & Components Designator List The following is a list of System, Equipment, & Component Designators (part of the first field of the UID Number). The intent of this list is to provide guidance and consistency in labeling of systems, equipment and components. UID Numbers shall be defined on a legend for new projects.

Also included in this list are the recommended System Designators that correspond with each SEC Designator.

UNCLASSIFIED – FOR OFFICIAL USE ONLY

Minimum Technical Specification for Structures, Systems, Equipment, & Components: Identification, Labeling, and Marking
DISA Facility Engineering Circular Attachment 01-02

Effective Date: 12 August 2020

UNCLASSIFIED – FOR OFFICIAL USE ONLYPage 2 of 28
Table 3 – SEC Designator
ACSP
Access Control System Panel
ACT
Actuator
AC
Air Compressor
ACU
Air Conditioning Unit
ACA
Air Cooled Aftercooler
AD
Air Dryer
AHU
Air Handler Unit
AS
Air Separator
AT
Air Tank (Captive)
AIT
Analytical Transmitter (includes humidity, pH, conductivity)
AED
Automated External Defibrillator (AED)
ATS
Automatic Transfer Switch
BFP
Back-Flow Preventer
BH
Basin Heater
BC
Battery Charger
BCC
Battery Charger Controller
BDS
Battery Disconnect Switch (UPS System)
BMS
Battery Monitoring System (UPS System)
BAT
Battery String (UPS System)
BT
Belly Tank
BLR
Boiler
BRKR
Breaker
BFT
Buffer Tank
BASM
Building Automation System Monitor
BASP
Building Automation System Panel
CAP
Capacitor
CVS
Central Vacuum System
CFSC
Chemical Feed Sys Controller
CFSP
Chemical Feed Sys Pump
CSF
Chemical Shock Feeder
CHWP
Chilled Water Pump
CHWRP
Chilled Water Return Pump
CHWSP
Chilled Water Supply Pump
CH
Chiller (generic, including water, air, & DX)
CHCS
Chiller Compressor Starter
CABP
Clean Agent Booster Panel
CACP
Clean Agent Control Panel
CAEF
Clean Agent Exhaust Fan
CAIAF
Clean Agent Intake Air Fan
CANG
Clean Agent Nitrogen Generator
CANT
Clean Agent Nitrogen Test
CAT
Clean Agent Tank
CACPD
Cold Aisle Containment Pod
CRAC
Computer Room Air Conditioner
CRAH
Computer Room Air Handler
CWP
Condenser (Cooling Tower) Water Pump
CRP
Condensate Return Pump
CRT
Condensate Return Tank
CRU
Condensate Return Unit
CTC
Contactor
*CP
Control Panel
CTLR
Controller
CT
Cooling Tower
CTBH
Cooling Tower Basin Heater
CTP
Cooling Tower Pump
CUB
Cubical Furniture
DT
Day Tank
*DISC
Disconnect
*DP
Distribution Panel
DHWRP
Domestic Hot Water Return Pump
DHWSP
Domestic Hot Water Supply Pump
ELMTR
Electric Meter
EFORK
Electric Forklift
ELJ
Electric Pallet Jack
EMIF
Electromagnetic Interference Filter
ELEV
Elevator
EGEN
Emergency Generator
EML
Emergency Light
EPOS
Emergency Power Off System
ESHR
Emergency Shower
ENCL
Enclosures
ENG
Engine Fire Pump
EQLT
Equipment Lift
EF
Exhaust Fan
ES
Exit Signs
ET
Expansion Tank
EWASH
Eyewash
FCU
Fan Coil Unit
FIL
Filter
FABP
Fire Alarm Booster Panel
FACP
Fire Alarm Control Panel
FASD
Fire Alarm Smoke Detector
FOP
Fuel Oil Pump
FX
Fire Extinguisher
FP
Fire Pump
FAK
First Aid Kit
FIT
Flow Transmitter
FRK
Forklift
FMS
Fuel Monitoring System
FPOL
Fuel Polisher
FT
Fuel Tank
FTP
Fuel Transfer Pump
F
Furnace
GMTR
Gas Meter
GATE
Gate, Electric
GNDBR
Ground Bar/Rods
GNDSYS
Grounding System
SHRDHD
Hard Drive Shredder
HB
Heat Box
HX
Heat Exchanger (all types)
HP
Heat Pump
HT
Heat Trace
HTCS
Heat Trace Control System
HC
Heating Coil
HTIE
Hot Tie
HWP
Hot Water Pump
HUM
Humidifier
HUMCU
Humidifier Control Unit
HDS
Hydrogen Detection System
HDSC
Hydrogen Detection Sys Controller
HDSD
Hydrogen Detection System Detector
ID
Ice Dispenser
IM
Ice Maker
IRC
In Row Cooler
IDSP
Intrusion Detection System Panel
JBOX
Junction Box
LDSD
Leak Detection System Detector
LDSM
Leak Detection System Monitor
LIT
Level Transmitter
*LP
Lighting Panelboard
LPS
Lightning Protection System
LB
Load Bank
LIFT
Loading Dock Lift
LVR
Louver
MTS
Manual Transfer Switch
MNG
Masking Noise Generator
MTR
Meter
*MCC
Motor Control Center
MTRSTR
Motor Starter
OAI
Outside Air Intake
OHDR
Overhead Door
OTB
Overhead Track Bus
PDU
Power Distribution Unit
PRV
Pressure Reduction Valve
PDIT
Pressure Transmitter, Differential
PIT
Pressure Transmitter
P
Pump (Generic)
RW
Raceway
RECT
Rectifier
RDSD
Refrigerant Detection System Detector
RDSM
Refrigerant Detection System Monitor
REFER
Refrigerator
RVP
Relief Valve Pressure
RDC
Remote Distribution Cabinet
RMSP
Remote Monitoring System Panel
RF
Return Fan
ROS
Reverse Osmosis System
RTU
Roof Top Unit
RM
Room
SSD
Security System Detector
SSP
Security System Panel
SRG
Signal Reference Grid
SIM
Simulator
SPK
Spill Kit
SPCS
Spill Kit Containment Shed
SBP
Standby Booster Pump
SBM
Static Bypass Module (UPS system)
STS
Static Transfer Switch
STRNR
Strainer
STRTR
Starter
SUB
Substation
SUMP
Sump/Ejector Pump
SF
Supply Fan
SPD
Surge Protective Device
*SWBD
Switchboard
*SWGR
Switchgear (generic, includes utility switchgear)
TIT
Temperature Transmitter
TGEN
Temporary Generator
TUPS
Temporary UPS
*XFMR
Transformer
ULTSNC
Ultra Sonic
USFSI
Ultra Sonic Flow Sensor Inlet
USFSO
Ultra Sonic Flow Sensor Outlet
UPS
Uninterruptible Power Supply
USTS
Uninterruptible Static Transfer Switch
UH
Unit Heater
UTIL
Utility
UTILXFMR
Utility Transformer
VLV
Valve (generic)
VAV
Variable Air Volume
VFD
Variable Frequency Drive
VRV
Variable Refrigerant Volume
VESDA
Very Early Smoke Detection (VESDA)
WDU
Water Distribution Unit
WTS
Water (Softener) Treatment System
WF
Water Fountain
WH
Water Heater
WMTR
Water Meter
WT
Water Tank (generic)
WNA
White Noise AMP
WNE
White Noise Equalizer
WNG
White Noise Generator

* If a System, Equipment, or Component is part of a Critical electrical/UPS bus, then the SEC Designator shall be preceded by the letter ‘U’; if part of an Essential system, then the SEC Designator shall be preceded by the letter ‘E’; e.g., Critical SWBD = USWBD and Essential Distribution Panel = EDP. For Switchgear, ESWGR is used before the UPS, USWGR is used after the UPS.

The following are legacy SED designators. These designators are no longer used, however equipment with these designators do not require relabeling.

Table 4 – Legacy SEC Designator

CWF
Condenser Water Filter
CWRV
Condenser Water Return Valve
CWSV
Condenser Water Supply Valve
CWV
Condenser Water Valve
CHWRV
Chilled Water Return Valve
CHWSV
Chilled Water Supply Valve
CHWV
Chilled Water Valve
DPXMIT
Differential Pressure Transmitter

System Designator List The following is a list of System Designators. The power source is used for the system designator unless the component does not have a power source, or as defined in paragraph 6.1. The intent of this list is to provide guidance and consistency in labeling of systems, equipment and components.

UNCLASSIFIED – FOR OFFICIAL USE ONLY

Minimum Technical Specification for Structures, Systems, Equipment, & Components: Identification, Labeling, and Marking
DISA Facility Engineering Circular Attachment 01-02

Effective Date: Draft

UNCLASSIFIED – FOR OFFICIAL USE ONLYPage 21 of 28
Table 5 – System Designator
A
A Bus
B
B Bus
BO
Boiler
BL
Building
BAS
Building Automated System
C
C Bus
CHW
Chilled Water, Chilled Water Supply
CHWR
Chilled Water Return
CA
Compressed Air
CW
Condenser Water, Condenser Water Supply
CWR
Condenser Water Return
D
D Bus
DC
Direct Current
DW
Domestic Water
AB*
Dual Bus (A & B)
BA*
Dual Bus (B & A)
CD*
Dual Bus (C & D)
DC*
Dual Bus (D & C)
EG
Emergency Generator & Paralleling Switchgear
EL
Emergency Lighting
FP
Fire Protection
FO
Fuel Oil
GD
Ground
NG
Natural Gas
X
Not Installed
E
PGS1 (B Bus)
F
PGS2 (A Bus)
REM
Removed
ST
Steam Distribution
ULTSNC
Ultra Sonic

* Dual bus is only used when the equipment has multiple feeds internal to the equipment. The normal power source for dual fed power is listed first. The normal power source is used for downstream equipment.

The following are legacy system designators. These designators are no longer used, however equipment with these designators do not require relabeling.

Table 6 – Legacy SEC Designator

CH
Chilled Water, Chilled Water Supply
CHR
Chilled Water Return

Switchgear, Large Switchboard, and Motor Control Labeling Example All switchgear, large switchboards and motor control centers shall be labeled by section as well as compartment. Each compartment will be labeled both with a numeric-alpha number and a downstream designator.

Section Labeling In the example below, the manufacturer provided the switchgear in five (5) sections. Therefore, each section shall be labeled following the standard labeling convention.

Compartment Labeling Each compartment shall be labeled in a sequential order. If the manufacturer labels the compartments, then their standard shall be followed. If not provided by the manufacturer, then the compartments shall be labeled using a numeric-alpha convention; numerically left to right, alpha top to bottom, as shown in Figure 18. The label itself shall be placed on the bottom right of each compartment and be in accordance with this document, with an exception of a font size of 48.

Each compartment shall also be labelled with its Child or ‘To’ UID Number in place of the parent power source on line 3 of the label, designating the downstream system, equipment, or component that it feeds. This label shall be placed on or immediately above the compartment. This label shall be in accordance with paragraph 4.1 and Table 2. All sections shall be labelled. Empty sections shall be labeled as Empty and Spare sections shall be labeled as spare.

Figure 18 – Essential Switchgear

Switchboard, and Large Panelboard Labeling Example

Figure 19 – Panelboard

Notes:

Circuit identifier labels shall be located to eliminate any possible confusion as to the item being identified and shall not obscure other items nearby Circuit identifier label colors shall provide a high contrast between characters and background to enhance legibility in accordance with paragraph 4.1 and Table 2. For example, Blue field with White letters for “B” Bus Distribution SEC.

Circuit identifier label size is approximate Circuit identifier labels shall be permanently attached and designed to withstand wear, erosion, and corrosion Circuit identifier labels shall be mounted in such a manner to preclude accidental removal The panel schedule will follow guidance under Appendix 5

Panel Schedule Labeling Example

Figure 20 – Electrical Panel

Distribution Panel Schedule

UID #:
Location:
From:
Updated:
Voltage:
Rating (Amps):
Frequency:
KAIC:
CKT #
Amps
Description
Description
Amps
CKT #

Panel Notes:

Figure 21 – Panel Schedule Template

Circuit number labels shall be located along the outside edge of their respective breakers Circuit identifier label colors shall provide a high contrast between characters and background to enhance legibility in accordance with paragraph 4.1 and Table 2.

For inline or single distribution panels, circuit numbers shall start with one and proceed sequentially. For split distribution systems, as shown in Figure 20, circuit numbers shall start with odd numbers on the left hand breakers and even numbers on the right hand breakers.

Circuit number label size is approximate Circuit number labels shall be permanently attached and designed to withstand wear, erosion, and corrosion, and preclude accidental removal The panel schedule shall mirror the numbering convention on the circuit number labels The panel schedule shall include a Description of each circuit, providing necessary detail for maintenance personnel The heading of the panel schedule shall include the panel UID, location (room and general location within the room where the panel is installed), from (power source), date (when the schedule was updated), incoming voltage (ie, 480Y/277), rating (include at a minimum voltage, phase, and wire, ie, 400 VAC, 3 phase 4W), and KAIC.

Circuit labeling shall include all available distribution circuits whether used, spare, or space. The panel schedule shall also capture this detail.

When known, include the following in general notes: panel manufacturer and model number Figure 21 reflects the standard panel schedule template

PDU and RDC Schedule Labeling Example

Figure 22 – PDU Panel

Appendix 6 applies to PDUs and RDCs Circuit number labels shall be located along the outside edge of their respective breakers Circuit identifier label colors shall provide a high contrast between characters and background to enhance legibility and will match the color code for their respective electrical feed.

For inline or single panels, circuit numbers shall start with one and proceed sequentially. For split systems, as pictured above, circuit numbers shall start with odd numbers on the left hand breakers and even numbers on the right hand breakers.

Each panel shall be numbered separately and sequentially, as shown above Circuit number label size is approximate Circuit number labels shall be permanently attached and designed to withstand wear, erosion, and corrosion, and to preclude accidental removal The panel schedule shall mirror the numbering convention on the circuit number labels The heading of the panel schedule shall include the UID and Panel # The panel schedule shall include a Rack Name (Grid Location) and Date (when rack was installed) for each circuit, providing necessary detail for maintenance personnel Circuit labeling shall include all available distribution circuits whether used, spare, or space. The panel schedule shall also capture this detail.

PDU/RDC Panel Schedule

Updated:
UID #:
From:
Panel #
Voltage:
Rating (Amps):
Frequency:
KAIC:
CKT #
Amps
Rack Name
Date Installed
Receptacle #
Receptacle #
Date Installed
Rack Name
Amps
CKT #

Panel Notes:

Figure 23 – PDU/RDC Panel Schedule Template

RDC Panel Schedule

Updated:
UID #:
From:
Panel #
Voltage:
Rating (Amps):
Frequency:
KAIC:
CKT #
Amps
Rack Name
Date Installed
Receptacle #

Panel Notes:

Figure 24 – RDC Panel Schedule Template

OTB Schedule Example

Appendix 7 applies to OTBs Each OTB plug in unit shall be numbered separately and sequentially, however the actual installation may not be sequential.

Plug in unit labels shall be permanently attached and designed to withstand wear, erosion, and corrosion, and to preclude accidental removal The heading of the schedule shall include the UID of the OTB.

The OTB schedule shall include the plug in unit UID, associated Rack Name (Grid Location) and Date (when rack was installed) for each plug in unit connected to the OTB , providing necessary detail for maintenance personnel

OTB Schedule

Updated:
OTB UID #:
From:
Voltage:
Rating (Amps):
Frequency:
KAIC:
Plug In Unit UID
Amps
Rack Name
Date Installed
Grid Location
Receptacle #

Notes:

Figure 25 – OTB Schedule Template

- - End of Document - -image1.jpeg image2.jpeg image3.jpeg image4.jpeg image5.emf

Microsoft_Visio_Drawing.vsdx image6.jpeg image7.jpeg image8.jpeg image9.jpeg image10.emf

Microsoft_Visio_Drawing1.vsdx image11.emf

Microsoft_Visio_Drawing2.vsdx image12.emf

Microsoft_Visio_Drawing3.vsdx image13.jpeg image14.emf

Microsoft_Visio_Drawing4.vsdx

Microsoft_Visio_Drawing5.vsdx

File details come from the government source that posted it. Updated .