Solicitation AG-02NV-S-10-0075

Questions 8-10-2010

Q1. One more question that has come in from our electrical subcontractors; Drawing E5 OPS room shows (4) type “L” fixtures and (4) type “KD” fixtures which are not shown on the Fixture Schedule shown on Sheet E4 does not identify these. Would you please clarify?

A1. All type "L" fixtures should be type "M". These are the (4) called for on the schedule.

Type "KD" were originally a dimmable fixture, but were changed in the design to just type "K". This should only be (15) total type "K" fixture vs. (13) shown in the schedule.