9-06. Attachment E Master Plan.pdf
PDF 36 MB Posted
- Attached to
- Murray Unit - Install HVAC
- Solicitation number
- 696-FD-26-Q037
- Issued by
- Texas
About this file
This is a Basis of Design Investigative Services document for the Texas Department of Criminal Justice (TDCJ) Murray Unit, prepared by Parkhill, Inc., for an HVAC installation project serving inmate housing in Gatesville, Texas. The project involves installing air conditioning systems in five dormitory buildings (J1, J2, K1, K2, and K3) with a total cooling load of approximately 450 tons. The scope includes three alternative HVAC system options: direct expansion (DX) cooling with split system condensing units, air-cooled chiller systems, and water-cooled chiller systems with cooling towers. All options utilize central station gas-fired air handlers with gas heating, new ductwork (particularly for K dorms), concrete pads for outdoor equipment, piping infrastructure, and a new emergency diesel generator to provide backup power. The document includes detailed HVAC load calculations, electrical distribution design, ductwork specifications, and equipment selections generated using IESVE modeling software.
The life cycle cost analysis (LCCA) conducted over 25 years with a 3% real discount rate identifies the water-cooled chiller option as the most economical alternative with a present value cost of $39,428,733, compared to $41,552,979 for air-cooled chillers and $42,152,219 for the DX system. The water-cooled system demonstrates superior energy performance with annual electricity consumption of 1,650,550 kW versus 1,834,307 kW for air-cooled and 2,021,554 kW for DX systems, resulting in estimated annual energy savings exceeding $150,000. First costs are estimated at $8,082,574 for the water-cooled system, $7,649,020 for air-cooled, and $4,926,064 for DX, with maintenance costs of $30,000 annually for chiller systems and $50,000 for DX. Equipment lead times range from 10 weeks for condensing units to 54 weeks for the generator. Utility rates obtained from TDCJ include electricity at $0.0909 per kWh, gas at $7.82 per MCF, and water at $0.00334 per kilogram gallon.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Basis of Design Investigative Services
Texas Department of Criminal Justice
Murray Unit
MWR #10522004
Install HVAC – Inmate Housing
Gatesville, Texas
December 2025 Parkhill
696-FD-26-Q037 Attachment E
Basis of Design Investigative Services
Texas Department of Criminal Justice
Murray Unit
MWR #10522004
Install HVAC – Inmate Housing
Gatesville, Texas
December 2025 Parkhill
This document is released on December
12, 2025 for the purpose of interim review under the authority of Carter Brown, P.E., Texas license # 149653. It is not to be used for regulatory approval, construction, bidding or permit purposes. Parkhill, Inc.
F-560
Texas Department of Criminal Justice
Murray Unit
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. TOC - i MWR # 10522004
TABLE OF CONTENTS
Page
GENERAL
DISCUSSION
Mechanical
Electrical
Life Cycle Analysis
APPENDICES
APPENDIX A – DESIGN CALCULATIONS
APPENDIX B – LIFE CYCLE COST ANALYSIS
APPENDIX C - SCOPE OF WORK
APPENDIX D – CATALOG CUTS
APPENDIX E – SCHEMATIC DRAWINGS
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. Page - 1 MWR # 10522004
GENERAL
This analysis is to consider three possible HVAC systems that could be used to condition
Buildings J1, J2, K1, K2, and K3. HVAC system alternatives include air cooled chillers, water cooled chiller plant with a cooling tower, and DX condensing units. All alternatives will utilize central station air handlers with gas heating. Electrical distribution upgrades to power the new units will also be examined. Analysis costs will include concrete pads for the outdoor equipment, piping between the air units and condensing units or chiller, and gas piping to the unit’s furnaces. A new emergency generator will provide power to the HVAC systems in the event main power goes down.
DISCUSSION
A. MECHANICAL – J AND K DORMS
This Life Cycle Analysis will look into three options to air condition Buildings J1, J2, K1, K2, and K3. All options will use similar gas fired horizontal air handling units. The
AHU’s will be installed in the existing mechanical rooms. New ductwork will be run in the K dorms to supply conditioned air into the space. J dorm air handlers will reuse the existing ductwork. The cooling mediums will be analyzed in this report. Actual energy costs for electricity and gas were obtained from TDCJ. Schematic drawings are located in Appendix F.
1. Option #1: Condensing units will be located as close to the served AHU’s as possible.
2. Option #2 and #3: The air-cooled or water-cooled chillers will be located south of the
Unit outside of the fence. Chilled water piping will be routed around the Unit to serve each J and K dorm. Future taps for extension of the chilled water system will be provided for the other buildings.
B. ELECTRICAL – J AND K DORMS
1. GENERAL
The electrical solution for the J and K Dorms will include a new normal electrical distribution as well as a new permanent standby generator to provide emergency power in the event of power loss to the new air-conditioning units. The new generator will be sized to support only the new HVAC equipment.
2. NORMAL ELECTRICAL DISTRIBUTION
The new electrical distribution system will consist of exterior rated, normal, and emergency electrical systems sized to support the new HVAC equipment.
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. Page - 2 MWR # 10522004
Option #1 Electrical Distribution:
Option #1 will provide new distribution power for new condensing units (CUs).
It is proposed that a new fenced electrical utility yard will be located to the north of the “K” and “J” dorms, configure to provide the power required for the new condensing units at each “K” and “J” dorm
The gas fired air handler units (AHUs) will remain connected to the electrical distribution systems including the existing emergency generator systems and will utilize space made available by demolition of existing Supply Fans and Heating
Ventilation Units, in the existing associated motor control centers. It may be necessary to modify the existing motor control centers to accommodate the new
HVAC AHUs. New feeders (conduits and conductors) will be provided for the new
AHUs.
Option #2 and #3 Electrical Distribution:
Option #2 and #3 will be provided with new distribution power to power either the air-cooled chillers or water-cooled chillers. The chillers will be located south of the unit outside the fence. The new gas fired air handler units (AHU’s) will remain connected to the existing generators as described in Option #1 above.
The new electrical distribution system that will serve the new chiller plant will be located adjacent to the new chiller plant, outside the south fenced area. The new electrical distribution system will consist of a new utility transformer, new
480Y/277V, 3-phase distribution equipment, and a new standby generator system to maintain power to the chiller plant in the event of a power outage. This electrical distribution system and associated standby generator system will be sized to accommodate the new chiller loads required by the scope of this work as well as additional capacity to support future chiller plant loads expected in the future to support other buildings on the campus.
3. STANDBY EMERGENCY DISTRIBUTION
A new permanent diesel generator with an integral base fuel tank will be installed outside the main fence south of the unit with the main electrical distribution panel and the ATS. The new generator will operate at 480Y/277 volts. The genset will be furnished with a weather-proof enclosure and will have a line circuit breaker. The automatic transfer switch will be located in the generator yard as noted above and will serve the distribution panel for the new HVAC units and associated branch panels.
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. Page - 3 MWR # 10522004
The fuel supply will be as specified in the TDCJ specifications for duration and will be based on operation of 24 hours of fuel. The unit will be located as indicated on the drawings and will allow for fuel truck access.
A remote annunciator will be provided and will be located as directed by TDCJ for monitoring. Power circuits for the battery chargers and block heaters will be derived from the existing panels.
4. FIRE ALARM AND MISCELLANEOUS CONSIDERATIONS
Based on the CFM of the units, duct-mounted smoke detectors will need to be provided to provide shutdown of the units in accordance with NFPA 90A. The duct detectors will be connected to the existing fire alarm control panel.
Convenience receptacles will be located at each of the new outdoor mounted air-conditioning units. These maintenance receptacles will be served from the nearest existing 208Y/120V branch panel.
C. LIFE CYCLE ANAYLSIS (J AND K DORMS)
1. Option 1: Direct Expansion Cooling Coils
The first system will consider cooling through the use of DX coils in each air handler with split system condensing units. The ground mounted air-cooled condensing unit will be located outside each building on the ground as close to the indoor air handler units as feasible to reduce the refrigerant line runs.
2. Option 2: Chilled Water Coils w/ Air Cooled Chillers
The second system will consider cooling through the use of an air-cooled chiller with chilled water coils in each air handler. Chilled water will be piped from the chiller to each air handler. The ground mounted chillers will be located plan south of the facility outside of the unit’s security fence. The chilled water pump will be integral to the chiller.
3. Option 3: Chilled Water Coils w/ Water Cooled Chiller plant and Cooling Tower
The third system will consider cooling through the use of a modular cooling tower paired with water cooled chillers with chilled water coils in each air handler.
Condenser water will be piped from the cooling tower to each water-cooled chiller, and chilled water will be piped from the chillers to each air handler. The ground
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. Page - 4 MWR # 10522004 mounted cooling tower and water-cooled chillers will be located plan south of the facility outside of the unit’s security fence. Chilled water pumps will be integral to the chillers.
Life Cycle Cost Analysis
Alternative Analyzed
Avg. Annual Electricity
Use kW
Avg. Annual Gas Use kBtu
Materials & Installation
Cost
Energy Costs / yr
Maintenance Costs / yr
Life Cycle Cost (PV)
Dx
Cooling 2,021,554 11,389,193 $4,926,064 $1,926,656 $50,000 $42,152,219
Air
Cooled Chillers
1,834,307 11,111,913 $7,649,020 $1,587,412 $30,000 $41,552,979
Water Cooled Chillers
1,650,550 11,132,178 $8,082,574 $1,754,289 $30,000 $39,428,733
Based on the life cycle cost analysis, the most economical alternative is option 3, utilizing chilled water cooling coils paired with a water cooled chiller plant. The LCCA printouts, system assumptions, energy costs and preliminary material costs are located in the Appendices.
D. Equipment catalog cuts
Refer to Appendix D for preliminary equipment cuts.
E. Schematic Drawings
Refer to Appendix E for Schematic Drawings.
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. MWR # 10522004
APPENDIX A
DESIGN CALCULATIONS
Install HVAC – Inmate Housing
December 2025
PARKHILL, INC. Page - 1 MWR # 10522004
DESIGN CALCULATIONS:
Mechanical HVAC Load Calculations
For our load calculations, we constructed a scale model of Dorms J and K in order to properly model the building parameters. The figure below shows a plan view of our models constructed in
IESVE. Three single zone air handler systems were set up for this project, including one with DX cooling coil and two with chilled water cooling coils (one from air cooled plant and the other from a water cooled plant). All options utilized gas heat.
System Loads Report 4558025 05 e Variable Air Volume Reheat - Basic
Controls [AHU K1-2]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,545 - 5,545 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 19,359 - 19,359 3.7 External Doors 0 - 0 0.0 Windows Conduction 1,630 - 1,630 0.3 Skylights Conduction 0 - 0 0.0 Solar 976 - 976 0.2 Infiltration 185,488 - 185,488 35.1 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 5,677 - 5,677 1.1 Internal Floors/Air/Furn. -36 - -36 0.0 Ceilings 14,156 - 14,156 2.7 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 232,794 0 232,794
Internal Gains Lights 32,322 - 32,322 6.1 People 50,796 - 50,796 9.6 Misc, Computers, Equip 28,775 - 28,775 5.4
Sub Total 111,892 0 111,892
Mechanical Gains/Losses Ventilation (sensible) 72,133 - 72,133 13.7 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 25,929 - 25,929 4.9 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 85,494 - 85,494 16.2 Dehumid Oversizing † 0 - - -
Sub Total 183,556 0 183,556
TOTAL 528,242 0 528,242 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,545 1.6
0 0.0 19,359 5.6
0 0.0 1,630 0.5
0 0.0 976 0.3
185,488 53.8 0 0.0
5,677 1.6 -36 0.0
14,156 4.1 0 0.0 0 0.0
232,794
32,322 9.4 50,796 14.7 28,775 8.3
111,892
344,686 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 50.6 607.5 509.2 15,818 80.6 64.2 40.8 55.0 52.8 86.8 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 50.6 607.5 509.2
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,821 - -11,821 - Roofs 0 - 0 - Ground/Exposed Floors -58,361 - -58,361 - External Doors 0 - 0 - Windows Conduction -2,227 - -2,227 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -273,693 - -273,693 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -11,718 - -11,718 - Internal Floors/Air/Furn. 175 - 175 - Ceilings -31,041 - -31,041 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -388,685 0 -388,685
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -110,167 - -110,167 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,663 - 26,663 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 472,189 - 472,189 -
Sub Total 388,685 0 388,685
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 16,267 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,452.4 100.0 2.9 Roof 0.0 0.0 - External Floor 13,086.6 - - Door 0.0 - - Partition/Door 9,407.1 - - Internal Ceiling 13,086.6 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 74.9 68.2 Plenum (actual) - - Mixed Air (actual) 79.6 62.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 16,267 16,267 Supply (design, non-coin.) 17,920 18,980 Supply (actual at coil peak) 15,818 16,267 Supply (actual maximum) 15,818 16,267 Reheat Minimum (design) 10,469 10,469 Leakage at Design Flow 0 0 Return (actual) 13,633 14,082 Exhaust and Relief (actual) 2,298 2,298 Ventilation (requirement) 2,298 2,298 Ventilation (actual) 13,520 13,969 Infiltration 5,795 5,795
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 193.34 193.35 ft²/Person* 67.69 67.68 Btu/h/ft² - Cooling* 28.34 46.42 Btu/h/ft² - Heating 30.29 0.00 ft²/ton - Cooling* 423.45 258.51 ft²/ton - Heating 396.17 4,602,377.30 cfm/ft² - Cooling* 1.37 1.21 cfm/ft² - Heating 1.45 1.24 % Outside Air - Cooling* 12.19 85.47 % Outside Air - Heating 11.51 85.87 Outdoor Air cfm/ft²* 0.17 1.03 Outdoor Air cfm/person* 11.30 69.93 Peak Latent Load (MBh)* 15.87 98.32 Sensible Heat Ratio* 0.96 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 1 of 12 Document Page: 56
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column ‡ Blow-through fan configuration
Paragraph 56 of 1
Controls [AHU K2-2]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,545 - 5,545 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 19,359 - 19,359 3.7 External Doors 0 - 0 0.0 Windows Conduction 1,630 - 1,630 0.3 Skylights Conduction 0 - 0 0.0 Solar 976 - 976 0.2 Infiltration 185,488 - 185,488 35.1 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 5,677 - 5,677 1.1 Internal Floors/Air/Furn. -36 - -36 0.0 Ceilings 14,153 - 14,153 2.7 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 232,791 0 232,791
Internal Gains Lights 32,322 - 32,322 6.1 People 50,796 - 50,796 9.6 Misc, Computers, Equip 28,775 - 28,775 5.4
Sub Total 111,892 0 111,892
Mechanical Gains/Losses Ventilation (sensible) 72,133 - 72,133 13.7 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 25,929 - 25,929 4.9 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 85,494 - 85,494 16.2 Dehumid Oversizing † 0 - - -
Sub Total 183,556 0 183,556
TOTAL 528,239 0 528,239 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,545 1.6
0 0.0 19,359 5.6
0 0.0 1,630 0.5
0 0.0 976 0.3
185,488 53.8 0 0.0
5,677 1.6 -36 0.0
14,153 4.1 0 0.0 0 0.0
232,791
32,322 9.4 50,796 14.7 28,775 8.3
111,892
344,683 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 50.6 607.5 509.2 15,818 80.6 64.2 40.8 55.0 52.8 86.8 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 50.6 607.5 509.2
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,821 - -11,821 - Roofs 0 - 0 - Ground/Exposed Floors -58,363 - -58,363 - External Doors 0 - 0 - Windows Conduction -2,227 - -2,227 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -273,697 - -273,697 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -11,721 - -11,721 - Internal Floors/Air/Furn. 172 - 172 - Ceilings -31,041 - -31,041 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -388,698 0 -388,698
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -110,142 - -110,142 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,662 - 26,662 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 472,178 - 472,178 -
Sub Total 388,698 0 388,698
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 16,268 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,452.4 100.0 2.9 Roof 0.0 0.0 - External Floor 13,086.6 - - Door 0.0 - - Partition/Door 9,407.1 - - Internal Ceiling 13,086.6 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 74.9 68.2 Plenum (actual) - - Mixed Air (actual) 79.6 62.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 16,268 16,268 Supply (design, non-coin.) 17,920 18,980 Supply (actual at coil peak) 15,818 16,268 Supply (actual maximum) 15,818 16,268 Reheat Minimum (design) 10,469 10,469 Leakage at Design Flow 0 0 Return (actual) 13,633 14,083 Exhaust and Relief (actual) 2,298 2,298 Ventilation (requirement) 2,298 2,298 Ventilation (actual) 13,520 13,970 Infiltration 5,795 5,795
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 193.34 193.35 ft²/Person* 67.69 67.68 Btu/h/ft² - Cooling* 28.34 46.42 Btu/h/ft² - Heating 30.29 0.00 ft²/ton - Cooling* 423.45 258.51 ft²/ton - Heating 396.17 4,602,377.30 cfm/ft² - Cooling* 1.37 1.21 cfm/ft² - Heating 1.45 1.24 % Outside Air - Cooling* 12.19 85.47 % Outside Air - Heating 11.51 85.87 Outdoor Air cfm/ft²* 0.17 1.03 Outdoor Air cfm/person* 11.30 69.93 Peak Latent Load (MBh)* 15.87 98.32 Sensible Heat Ratio* 0.96 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 2 of 12 Document Page: 57
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 57 of 1
Controls [AHU K3-2]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,527 - 5,527 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 19,358 - 19,358 3.7 External Doors 0 - 0 0.0 Windows Conduction 1,624 - 1,624 0.3 Skylights Conduction 0 - 0 0.0 Solar 978 - 978 0.2 Infiltration 185,488 - 185,488 35.1 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 5,677 - 5,677 1.1 Internal Floors/Air/Furn. -36 - -36 0.0 Ceilings 14,152 - 14,152 2.7 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 232,769 0 232,769
Internal Gains Lights 32,322 - 32,322 6.1 People 50,796 - 50,796 9.6 Misc, Computers, Equip 28,775 - 28,775 5.4
Sub Total 111,892 0 111,892
Mechanical Gains/Losses Ventilation (sensible) 72,133 - 72,133 13.7 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 25,927 - 25,927 4.9 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 85,493 - 85,493 16.2 Dehumid Oversizing † 0 - - -
Sub Total 183,553 0 183,553
TOTAL 528,214 0 528,214 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,527 1.6
0 0.0 19,358 5.6
0 0.0 1,624 0.5
0 0.0 978 0.3
185,488 53.8 0 0.0
5,677 1.6 -36 0.0
14,152 4.1 0 0.0 0 0.0
232,769
32,322 9.4 50,796 14.7 28,775 8.3
111,892
344,661 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 50.6 607.4 509.1 15,817 80.6 64.2 40.8 55.0 52.8 86.8 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 50.6 607.4 509.1
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,831 - -11,831 - Roofs 0 - 0 - Ground/Exposed Floors -58,363 - -58,363 - External Doors 0 - 0 - Windows Conduction -2,228 - -2,228 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -273,697 - -273,697 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -11,722 - -11,722 - Internal Floors/Air/Furn. 172 - 172 - Ceilings -31,041 - -31,041 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -388,709 0 -388,709
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -110,145 - -110,145 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,663 - 26,663 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 472,191 - 472,191 -
Sub Total 388,709 0 388,709
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 16,269 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,452.4 100.0 2.9 Roof 0.0 0.0 - External Floor 13,086.6 - - Door 0.0 - - Partition/Door 9,407.1 - - Internal Ceiling 13,086.6 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 74.9 68.2 Plenum (actual) - - Mixed Air (actual) 79.6 62.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 16,269 16,269 Supply (design, non-coin.) 17,919 18,980 Supply (actual at coil peak) 15,817 16,269 Supply (actual maximum) 15,817 16,269 Reheat Minimum (design) 10,469 10,469 Leakage at Design Flow 0 0 Return (actual) 13,632 14,084 Exhaust and Relief (actual) 2,298 2,298 Ventilation (requirement) 2,298 2,298 Ventilation (actual) 13,519 13,971 Infiltration 5,795 5,795
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 193.34 193.35 ft²/Person* 67.69 67.68 Btu/h/ft² - Cooling* 28.34 46.42 Btu/h/ft² - Heating 30.29 0.00 ft²/ton - Cooling* 423.47 258.52 ft²/ton - Heating 396.16 4,602,377.30 cfm/ft² - Cooling* 1.37 1.21 cfm/ft² - Heating 1.45 1.24 % Outside Air - Cooling* 12.19 85.47 % Outside Air - Heating 11.51 85.88 Outdoor Air cfm/ft²* 0.17 1.03 Outdoor Air cfm/person* 11.30 69.92 Peak Latent Load (MBh)* 15.87 98.32 Sensible Heat Ratio* 0.96 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 3 of 12 Document Page: 58
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 58 of 1
Controls [AHU J1-1]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,881 - 5,881 1.4 Roofs 1,502 - 1,502 0.4 Ground/Exposed Floors 11,045 - 11,045 2.6 External Doors 0 - 0 0.0 Windows Conduction 6,363 - 6,363 1.5 Skylights Conduction 0 - 0 0.0 Solar 3,724 - 3,724 0.9 Infiltration 197,908 - 197,908 46.9 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 382 - 382 0.1 Internal Floors/Air/Furn. 164 - 164 0.0 Ceilings 8,884 - 8,884 2.1 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 235,854 0 235,854
Internal Gains Lights 22,984 - 22,984 5.4 People 22,771 - 22,771 5.4 Misc, Computers, Equip 17,004 - 17,004 4.0
Sub Total 62,760 0 62,760
Mechanical Gains/Losses Ventilation (sensible) 40,148 - 40,148 9.5 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 22,263 - 22,263 5.3 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 61,330 - 61,330 14.5 Dehumid Oversizing † 0 - - -
Sub Total 123,740 0 123,740
TOTAL 422,353 0 422,353 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,881 2.0 1,502 0.5
11,045 3.7 0 0.0
6,363 2.1 0 0.0
3,724 1.2 197,908 66.3
0 0.0
382 0.1 164 0.1
8,884 3.0 0 0.0 0 0.0
235,854
22,984 7.7 22,771 7.6 17,004 5.7
62,760
298,613 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 40.5 485.7 415.2 13,616 79.2 63.5 42.0 55.0 52.9 87.2 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 40.5 485.7 415.2
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -13,008 - -13,008 - Roofs -2,278 - -2,278 - Ground/Exposed Floors -33,366 - -33,366 - External Doors 0 - 0 - Windows Conduction -8,677 - -8,677 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -292,250 - -292,250 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -1,595 - -1,595 - Internal Floors/Air/Furn. -188 - -188 - Ceilings -15,275 - -15,275 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -366,637 0 -366,637
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -61,378 - -61,378 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 24,892 - 24,892 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 403,124 - 403,124 -
Sub Total 366,637 0 366,637
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 15,238 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 4,021.8 384.0 9.5 Roof 1,106.5 0.0 0.0 External Floor 7,420.8 - - Door 0.0 - - Partition/Door 13,644.9 - - Internal Ceiling 8,572.6 - - Internal Floor 2,258.3 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 75.0 68.0 Plenum (actual) - - Mixed Air (actual) 78.2 64.8 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 15,238 15,238 Supply (design, non-coin.) 15,510 17,961 Supply (actual at coil peak) 13,616 15,238 Supply (actual maximum) 13,616 15,238 Reheat Minimum (design) 7,077 7,077 Leakage at Design Flow 0 0 Return (actual) 12,330 13,952 Exhaust and Relief (actual) 1,286 1,286 Ventilation (requirement) 1,286 1,286 Ventilation (actual) 12,330 13,952 Infiltration 6,209 6,209
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 91.08 91.05 ft²/Person* 106.27 106.30 Btu/h/ft² - Cooling* 31.87 50.18 Btu/h/ft² - Heating 38.75 0.00 ft²/ton - Cooling* 376.50 239.13 ft²/ton - Heating 309.65 3,403,991.68 cfm/ft² - Cooling* 1.60 1.41 cfm/ft² - Heating 1.86 1.57 % Outside Air - Cooling* 8.29 90.55 % Outside Air - Heating 7.16 91.56 Outdoor Air cfm/ft²* 0.13 1.27 Outdoor Air cfm/person* 14.12 135.42 Peak Latent Load (MBh)* 0.00 70.53 Sensible Heat Ratio* 1.00 0.85 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 4 of 12 Document Page: 59
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 59 of 1
Controls [AHU J2-1]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,872 - 5,872 1.4 Roofs 1,495 - 1,495 0.4 Ground/Exposed Floors 11,231 - 11,231 2.7 External Doors 0 - 0 0.0 Windows Conduction 6,344 - 6,344 1.5 Skylights Conduction 0 - 0 0.0 Solar 3,723 - 3,723 0.9 Infiltration 197,894 - 197,894 46.7 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 1,456 - 1,456 0.3 Internal Floors/Air/Furn. 204 - 204 0.0 Ceilings 8,870 - 8,870 2.1 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 237,089 0 237,089
Internal Gains Lights 22,984 - 22,984 5.4 People 22,771 - 22,771 5.4 Misc, Computers, Equip 17,004 - 17,004 4.0
Sub Total 62,760 0 62,760
Mechanical Gains/Losses Ventilation (sensible) 40,145 - 40,145 9.5 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 22,352 - 22,352 5.3 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 61,401 - 61,401 14.5 Dehumid Oversizing † 0 - - -
Sub Total 123,899 0 123,899
TOTAL 423,748 0 423,748 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,872 2.0 1,495 0.5
11,231 3.7 0 0.0
6,344 2.1 0 0.0
3,723 1.2 197,894 66.0
0 0.0
1,456 0.5 204 0.1
8,870 3.0 0 0.0 0 0.0
237,089
22,984 7.7 22,771 7.6 17,004 5.7
62,760
299,849 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 40.6 487.3 416.7 13,671 79.2 63.5 42.0 55.0 52.9 87.2 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 40.6 487.3 416.7
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -12,999 - -12,999 - Roofs -2,258 - -2,258 - Ground/Exposed Floors -33,518 - -33,518 - External Doors 0 - 0 - Windows Conduction -8,673 - -8,673 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -292,251 - -292,251 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -3,728 - -3,728 - Internal Floors/Air/Furn. -330 - -330 - Ceilings -15,215 - -15,215 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -368,974 0 -368,974
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -61,417 - -61,417 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 25,061 - 25,061 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 405,330 - 405,330 -
Sub Total 368,974 0 368,974
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 15,335 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 4,021.8 384.0 9.5 Roof 1,106.5 0.0 0.0 External Floor 7,420.8 - - Door 0.0 - - Partition/Door 13,644.9 - - Internal Ceiling 8,572.6 - - Internal Floor 2,258.3 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 75.0 68.0 Plenum (actual) - - Mixed Air (actual) 78.2 64.8 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 15,335 15,335 Supply (design, non-coin.) 15,571 18,075 Supply (actual at coil peak) 13,671 15,335 Supply (actual maximum) 13,671 15,335 Reheat Minimum (design) 7,077 7,077 Leakage at Design Flow 0 0 Return (actual) 12,385 14,049 Exhaust and Relief (actual) 1,286 1,286 Ventilation (requirement) 1,286 1,286 Ventilation (actual) 12,385 14,049 Infiltration 6,209 6,209
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 91.08 91.05 ft²/Person* 106.27 106.30 Btu/h/ft² - Cooling* 32.00 50.35 Btu/h/ft² - Heating 39.00 0.00 ft²/ton - Cooling* 375.02 238.35 ft²/ton - Heating 307.68 3,403,991.68 cfm/ft² - Cooling* 1.61 1.41 cfm/ft² - Heating 1.87 1.58 % Outside Air - Cooling* 8.26 90.59 % Outside Air - Heating 7.12 91.61 Outdoor Air cfm/ft²* 0.13 1.28 Outdoor Air cfm/person* 14.12 136.02 Peak Latent Load (MBh)* 0.00 70.61 Sensible Heat Ratio* 1.00 0.86 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 5 of 12 Document Page: 60
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 60 of 1
Controls [AHU K1-1]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,064 - 5,064 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 16,029 - 16,029 3.1 External Doors 0 - 0 0.0 Windows Conduction 1,608 - 1,608 0.3 Skylights Conduction 0 - 0 0.0 Solar 1,515 - 1,515 0.3 Infiltration 212,857 - 212,857 40.5 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 4,712 - 4,712 0.9 Internal Floors/Air/Furn. -33 - -33 0.0 Ceilings 11,659 - 11,659 2.2 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 253,410 0 253,410
Internal Gains Lights 27,257 - 27,257 5.2 People 46,772 - 46,772 8.9 Misc, Computers, Equip 25,356 - 25,356 4.8
Sub Total 99,386 0 99,386
Mechanical Gains/Losses Ventilation (sensible) 62,603 - 62,603 11.9 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,372 - 26,372 5.0 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 83,388 - 83,388 15.9 Dehumid Oversizing † 0 - - -
Sub Total 172,362 0 172,362
TOTAL 525,158 0 525,158 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,064 1.4
0 0.0 16,029 4.5
0 0.0 1,608 0.5
0 0.0 1,515 0.4
212,857 60.3 0 0.0
4,712 1.3 -33 0.0
11,659 3.3 0 0.0 0 0.0
253,410
27,257 7.7 46,772 13.3 25,356 7.2
99,386
352,796 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 43.8 525.2 441.8 16,101 80.1 64.0 41.4 55.0 52.8 87.0 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 43.8 525.2 441.8
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,801 - -11,801 - Roofs 0 - 0 - Ground/Exposed Floors -49,337 - -49,337 - External Doors 0 - 0 - Windows Conduction -2,228 - -2,228 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -314,372 - -314,372 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -9,877 - -9,877 - Internal Floors/Air/Furn. 149 - 149 - Ceilings -25,989 - -25,989 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -413,454 0 -413,454
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -95,905 - -95,905 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 28,192 - 28,192 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 481,168 - 481,168 -
Sub Total 413,454 0 413,454
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 17,208 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,446.4 100.0 2.9 Roof 0.0 0.0 - External Floor 11,123.5 - - Door 0.0 - - Partition/Door 7,383.4 - - Internal Ceiling 11,123.5 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 75.0 68.0 Plenum (actual) - - Mixed Air (actual) 79.1 63.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 17,208 17,208 Supply (design, non-coin.) 18,290 20,255 Supply (actual at coil peak) 16,101 17,208 Supply (actual maximum) 16,101 17,208 Reheat Minimum (design) 8,899 8,899 Leakage at Design Flow 0 0 Return (actual) 14,097 15,205 Exhaust and Relief (actual) 2,004 2,004 Ventilation (requirement) 2,004 2,004 Ventilation (actual) 14,097 15,205 Infiltration 6,674 6,674
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 187.09 187.09 ft²/Person* 59.46 59.46 Btu/h/ft² - Cooling* 32.95 47.21 Btu/h/ft² - Heating 38.03 0.00 ft²/ton - Cooling* 364.22 254.18 ft²/ton - Heating 315.54 3,911,983.95 cfm/ft² - Cooling* 1.64 1.45 cfm/ft² - Heating 1.82 1.55 % Outside Air - Cooling* 10.95 87.56 % Outside Air - Heating 9.89 88.36 Outdoor Air cfm/ft²* 0.18 1.27 Outdoor Air cfm/person* 10.71 75.35 Peak Latent Load (MBh)* 2.97 83.39 Sensible Heat Ratio* 0.99 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 6 of 12 Document Page: 61
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 61 of 1
Controls [AHU K2-1]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,096 - 5,096 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 16,028 - 16,028 3.1 External Doors 0 - 0 0.0 Windows Conduction 1,644 - 1,644 0.3 Skylights Conduction 0 - 0 0.0 Solar 1,500 - 1,500 0.3 Infiltration 212,856 - 212,856 40.5 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 4,712 - 4,712 0.9 Internal Floors/Air/Furn. -33 - -33 0.0 Ceilings 11,655 - 11,655 2.2 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 253,458 0 253,458
Internal Gains Lights 27,257 - 27,257 5.2 People 46,772 - 46,772 8.9 Misc, Computers, Equip 25,356 - 25,356 4.8
Sub Total 99,386 0 99,386
Mechanical Gains/Losses Ventilation (sensible) 62,603 - 62,603 11.9 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,375 - 26,375 5.0 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 83,391 - 83,391 15.9 Dehumid Oversizing † 0 - - -
Sub Total 172,369 0 172,369
TOTAL 525,213 0 525,213 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,096 1.4
0 0.0 16,028 4.5
0 0.0 1,644 0.5
0 0.0 1,500 0.4
212,856 60.3 0 0.0
4,712 1.3 -33 0.0
11,655 3.3 0 0.0 0 0.0
253,458
27,257 7.7 46,772 13.3 25,356 7.2
99,386
352,844 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 50.3 604.0 508.1 16,103 80.1 64.0 41.4 55.0 52.8 87.0 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 50.3 604.0 508.1
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,764 - -11,764 - Roofs 0 - 0 - Ground/Exposed Floors -49,354 - -49,354 - External Doors 0 - 0 - Windows Conduction -2,220 - -2,220 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -314,394 - -314,394 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -9,913 - -9,913 - Internal Floors/Air/Furn. -16 - -16 - Ceilings -26,008 - -26,008 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -413,668 0 -413,668
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -95,709 - -95,709 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 28,193 - 28,193 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 481,185 - 481,185 -
Sub Total 413,668 0 413,668
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 17,220 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,446.4 100.0 2.9 Roof 0.0 0.0 - External Floor 11,123.5 - - Door 0.0 - - Partition/Door 7,383.4 - - Internal Ceiling 11,123.5 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 75.0 68.0 Plenum (actual) - - Mixed Air (actual) 79.1 63.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 17,220 17,220 Supply (design, non-coin.) 18,292 20,253 Supply (actual at coil peak) 16,103 17,220 Supply (actual maximum) 16,103 17,220 Reheat Minimum (design) 8,899 8,899 Leakage at Design Flow 0 0 Return (actual) 14,100 15,216 Exhaust and Relief (actual) 2,004 2,004 Ventilation (requirement) 2,004 2,004 Ventilation (actual) 14,100 15,216 Infiltration 6,674 6,674
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 187.09 187.09 ft²/Person* 59.46 59.46 Btu/h/ft² - Cooling* 32.95 54.30 Btu/h/ft² - Heating 38.03 0.00 ft²/ton - Cooling* 364.17 221.00 ft²/ton - Heating 315.57 3,911,983.95 cfm/ft² - Cooling* 1.64 1.45 cfm/ft² - Heating 1.82 1.55 % Outside Air - Cooling* 10.95 87.56 % Outside Air - Heating 9.89 88.36 Outdoor Air cfm/ft²* 0.18 1.27 Outdoor Air cfm/person* 10.71 75.36 Peak Latent Load (MBh)* 2.97 95.90 Sensible Heat Ratio* 0.99 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 7 of 12 Document Page: 62
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 62 of 1
Controls [AHU K3-1]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,096 - 5,096 1.0 Roofs 0 - 0 0.0 Ground/Exposed Floors 16,028 - 16,028 3.1 External Doors 0 - 0 0.0 Windows Conduction 1,644 - 1,644 0.3 Skylights Conduction 0 - 0 0.0 Solar 1,500 - 1,500 0.3 Infiltration 212,856 - 212,856 40.5 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 4,712 - 4,712 0.9 Internal Floors/Air/Furn. -33 - -33 0.0 Ceilings 11,654 - 11,654 2.2 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 253,457 0 253,457
Internal Gains Lights 27,257 - 27,257 5.2 People 46,772 - 46,772 8.9 Misc, Computers, Equip 25,356 - 25,356 4.8
Sub Total 99,386 0 99,386
Mechanical Gains/Losses Ventilation (sensible) 62,603 - 62,603 11.9 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 26,375 - 26,375 5.0 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 83,391 - 83,391 15.9 Dehumid Oversizing † 0 - - -
Sub Total 172,369 0 172,369
TOTAL 525,212 0 525,212 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,096 1.4
0 0.0 16,028 4.5
0 0.0 1,644 0.5
0 0.0 1,500 0.4
212,856 60.3 0 0.0
4,712 1.3 -33 0.0
11,654 3.3 0 0.0 0 0.0
253,457
27,257 7.7 46,772 13.3 25,356 7.2
99,386
352,842 100
COOLING COILS
Total Capacity Sensible Cap Airflow Enter DB / WB / RH Leave DB / WB / RH ton MBh MBh cfm °F °F % °F °F % System Cooling ‡ 50.3 604.0 508.1 16,103 80.1 64.0 41.4 55.0 52.8 87.0 Ventilation - - - - - - - - - - Indirect Evap - - - - - - - - - - Direct Evap - - - - - - - - - -
TOTAL 50.3 604.0 508.1
AHU HEATING COIL PEAK
Time of Peak (Mo/Hr:Mn) Heating Design
Outside Air (DBT/WBT/RH) °F and %RH 25.0 / 20.7 / 49.8
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls -11,765 - -11,765 - Roofs 0 - 0 - Ground/Exposed Floors -49,359 - -49,359 - External Doors 0 - 0 - Windows Conduction -2,220 - -2,220 - Skylights Conduction 0 - 0 - Solar 0 - 0 - Infiltration -314,397 - -314,397 - Nat/Aux Vent 0 - 0 -
Internal Building Gains/Losses Internal Walls/Openings -9,910 - -9,910 - Internal Floors/Air/Furn. 97 - 97 - Ceilings -26,008 - -26,008 - Duct Conduction 0 - 0 - Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total -413,563 0 -413,563
Internal Gains Lights 0 - 0 - People 0 - 0 - Misc, Computers, Equip 0 - 0 -
Sub Total 0 0 0
Mechanical Gains/Losses Ventilation (sensible) -95,734 - -95,734 - Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 28,187 - 28,187 - SA Duct (conduction) 0 - 0 - Supply Air Plenum - - - - Room Units, Coils, etc. 481,110 - 481,110 -
Sub Total 413,563 0 413,563
TOTAL 0 0 0 0
HEATING COILS
Total Capacity Airflow Enter Leave
MBh cfm °F °F System Heating 0.0 17,216 55.0 55.0 Ventilation - - - - Pre-Heat - - - -
TOTAL 0.0
AREAS
Gross Glass Glass ft² ft² % Wall 3,446.4 100.0 2.9 Roof 0.0 0.0 - External Floor 11,123.5 - - Door 0.0 - - Partition/Door 7,383.4 - - Internal Ceiling 11,123.5 - - Internal Floor 0.0 - -
TEMPERATURES
Cooling Heating
°F °F Supply Air (design) 55.0 55.0 Supply Air (actual) 55.0 55.0 Return Air (actual) 75.0 68.0 Plenum (actual) - - Mixed Air (actual) 79.1 63.5 Fan Blade Temperature Rise (dT) 0.9 0.9 Fan Motor Temperature Rise (dT) 0.1 0.1 Fan Configuration Blow-through Blow-through
AIRFLOW
Cooling Heating cfm cfm Supply fan design max airflow 17,216 17,216 Supply (design, non-coin.) 18,292 20,253 Supply (actual at coil peak) 16,103 17,216 Supply (actual maximum) 16,103 17,216 Reheat Minimum (design) 8,899 8,899 Leakage at Design Flow 0 0 Return (actual) 14,100 15,212 Exhaust and Relief (actual) 2,004 2,004 Ventilation (requirement) 2,004 2,004 Ventilation (actual) 14,100 15,212 Infiltration 6,674 6,674
DESIGN ENGINEERING CHECKS
Non-coincident Coincident
Number of People* 187.09 187.09 ft²/Person* 59.46 59.46 Btu/h/ft² - Cooling* 32.95 54.30 Btu/h/ft² - Heating 38.03 0.00 ft²/ton - Cooling* 364.17 221.00 ft²/ton - Heating 315.57 3,911,983.95 cfm/ft² - Cooling* 1.64 1.45 cfm/ft² - Heating 1.82 1.55 % Outside Air - Cooling* 10.95 87.56 % Outside Air - Heating 9.89 88.36 Outdoor Air cfm/ft²* 0.18 1.27 Outdoor Air cfm/person* 10.71 75.36 Peak Latent Load (MBh)* 2.97 95.90 Sensible Heat Ratio* 0.99 0.84 Non-coincident loads are the sum of room (not zone) peaks.
Coincident values are those seen by coil, incl. OA vent loads.
* Coincident values are at time of cooling coil peak load.
4558025wc_f3 | 2025/11/26 11:55 | System loads - Page 8 of 12 Document Page: 63
Coil capacities, room unit capacities, and coincident values in Design Engineering Checks include oversizing † Not carried across to the Net Value column
Paragraph 63 of 1
Controls [AHU J1-2]
IES VIRTUAL ENVIRONMENT
VE 2025
AHU COOLING COIL PEAK
Time of Peak (Mo/Hr:Mn) 8 / 15:30
Outside Air (DBT/WBT/RH) °F and %RH 104.2 / 72.7 / 21.6
Zones RA Plenum Net Percent Value of Total
Envelope Gains/Losses Btu/h Btu/h Btu/h % External Walls 5,973 - 5,973 1.4 Roofs 0 - 0 0.0 Ground/Exposed Floors 9,047 - 9,047 2.1 External Doors 0 - 0 0.0 Windows Conduction 6,357 - 6,357 1.5 Skylights Conduction 0 - 0 0.0 Solar 7,244 - 7,244 1.7 Infiltration 198,359 - 198,359 46.5 Nat/Aux Vent 0 - 0 0.0
Internal Building Gains/Losses Internal Walls/Openings 3,348 - 3,348 0.8 Internal Floors/Air/Furn. -95 - -95 0.0 Ceilings 8,827 - 8,827 2.1 Duct Conduction 0 - 0 0.0 Duct Leakage † 0 - - - Non-Principal Spaces - - - -
Sub Total 239,060 0 239,060
Internal Gains Lights 21,445 - 21,445 5.0 People 24,660 - 24,660 5.8 Misc, Computers, Equip 17,397 - 17,397 4.1
Sub Total 63,502 0 63,502
Mechanical Gains/Losses Ventilation (sensible) 39,467 - 39,467 9.2 Transfer Air † 0 - - - SA Duct Leakage † 0 - - - Fans 22,547 - 22,547 5.3 SA Duct (conduction) 0 - 0 0.0 Supply Air Plenum - - - - Room Units, Coils, etc. 0 - 0 0.0 Latent Cooling 62,296 - 62,296 14.6 Dehumid Oversizing † 0 - - -
Sub Total 124,310 0 124,310
TOTAL 426,872 0 426,872 100
SYSTEM PEAK
8 / 15:30
104.2 / 72.7 / 21.6
Zones Percent (Sensible) of Total
Btu/h % 5,973 2.0
0 0.0 9,047 3.0
0 0.0 6,357 2.1
0 0.0 7,244 2.4
198,359 65.6 0 0.0
3,348 1.1 -95 0.0
8,827 2.9 0 0.0 0 0.0
239,060
21,445 7.1 24,660 8.2 17,397 5.8
63,502
302,563 100
COOLING COILS
To…