FI NISHED GRADE
INSTALL NEW CLEANOUT AT
LOCATIONS DESIGN A TED
MATCH EXISTING SLOPE BUILDING
FOUNDATION
<~~~~~~~~~~~~~~~~~~~~~~~~~~ /~»~~~~~~~~~~~); ~'»>~~,>?Y,>?Y,>?Y,>?Y,>?Y/, ~~ '" ·'" ' ' /»-»>:
EXISTING
PIPE SLEEVE
Variab le
3' g u..
z ::; I \ w rJl
45°
22-1 /2' OR 45'
HDPE SWEEP
PROFILE
22-1/2' OR 45'
HDPE SWEEP
----CUT EXIS TING SANITARY
SERVICE SQUARE. CONNECT
NEW SERVICE W/ APPROVED
ADAP TOR AND REPAIR CLAMP.
6" DIAMETER HDPE
SANITARY SERVICE
BUILDING
FOUNDATION
~EXISTING
PIPE SLEEVE
~ 11 ~ ~ (~ I {... ,I I
6" DIAMETER HDPE
SANITARY SERVICE
PLAN VIEW
CUT EXISTING SANITARY
SERVICE SQUARE. CONNECT
NEW SERVICE W/ APPROVED
ADAP TOR AND REPAIR CLAMP.
INSTALL NEW CLEANOUT AT
NOTES: LOCATIONS DESIGNATED.
1. NEW CONNECTIONS TO BE 6" HOPE.
2. EXPOSE EXISTING SAN ITARY SERVICE TO CONFIRM LOCATION AND SIZE OF
EXISTING LIN E AND FITTI NGS BEFORE STARTI NG INSTALLATION.
1 \ Sanitary Sewer Pipe View 01.c2<rC41/ N TS
DE TECTABLE WARNING TAPE
5 MIL THICKNESS, FOI L
BACKED, 6" WIDE, LOCATE
24" TO 36" ABOVE PIPE
BEDDING
4" 0 D HOPE
SANITARY
SEWER PIPE
" ,._ .. __ . . .. ·· .. ··:., ": .· . .- . M' .· .. &: '' :- '·.'" ' ''.: · .. - ~yj;.
,:A .. · · .· ·· · ·.·.: .··· ·· ... v>.
PIPE EMBEDMEN
:;>>: Y, y, Y, Y, Y, )' ·' ,'( ,'2(('2((~ « «~0<.'<.r"
'-1 '-j 1---1 ·__,_, 4"
FIN ISH SURFACE PER
EXISTING CONDITIONS
BACKFILL
l()
6'
5'
EXCAVATION LI MIT
(A) TRENCH WALL SLOPES WILL VARY WI TH SOIL STRENGTH AND
CHARACTER ISTICS, AND SHALL CONFORM TO SAFETY STANDARDS.
(B) TRENCH BACKFILL SHALL MEET TH E REQUIREMENTS FOR TYPE II FILL
UNDER TRAVELED WAYS AND TYPE Ill FILL UNDER OTHER SURFACE CONDITIONS. ALL TYPE II AND TYPE Ill MA TER I AL SHALL BE COMPACTED
TO 95% OF MAXIMUM DRY DENSITY.
(C) SEE SPECIFICATIONS FOR BEDD ING REQUIREMENTS .
01-C2cl C41
Sanitary Sewer Trench View
NTS
Outside of manhole nside of manhole
Flow a
,d q
'~ • ,I
• q q
,d q
Concrete manhole walls
01-C20 C41
Watertight connection
___.-oell end of PVC pipe
__...-nDPE pipe inserted into bell end of PVC pipe
~ill void areas with low shrink hydraulic grout and form a seal between the manhole opening and the PVC pipe oncrete manhole bottom
NOTES:
1. ALL SANITARY SEWER MANHOLE
CONNECTIONS SHALL BE 100°/o
WATERTIGHT.
2. CONTRACTOR TO SUBMIT
WATERTIGHT "HOPE TO MANHOLE"
CONNECTION DETAIL TO COR FOR
APPROVAL PRIOR TO
CONSTRUCTION.
3. ALL PIPE SHALL EXTEND 2" INTO
MANHOLE.
HOPE pipe connection to manhole
NTS
CONSULTANTS
UNITID STAlI ENGINEERING O Cl~L
COAST GUAR UNIT
U. S. COAST GUARD
CIVIL ENGIN EERING UNI T
JUNEAU
CIVIL ENGINEERING UN IT - JUNEAU
709 W 9TH ST, ROOM 817
JUNEAU, AK 99802-5517
ISSUE
MARK I DA TE I DESCRIPTION
A/E PROJECT NO:
CAD FILE NAME:
DESIGNED BY: SLH
DRAWN BY: SLH
EDITED BY:
CHECKED BY: JLS
SCALE: AS SHOWN PLOT SCALE: 1" 1"
SHEET TITLE
Replace Piping LGH Housing MOQs Base Kodiak
Kodiak ALASKA Lower Government Housing
Civil
Sanitary Sewer Details
REVIEWED BY: !REVIEWED BY: !REVIEWED BY:
JLS LK BJG/LWK
DESIGN MGR. I PROJECT MGR. I BRANCH CHIEF
I
J C MCFERRAN, LCDR USCG
APPROVING OFFICER I DATE
PROJECT NUMBER I DRAWING NUMBER
9988694 024510
DISCIPLINE/SHT NO
C41 [SHEET 28 OF 32