7-2-CS27023-27071370-Approved Plans.pdf

PDF 6 MB Posted

Attached to
DFCM Construction - Prequalified Mechanical Stage II - Utah State Fairpark - Zion AC Replacement - Project #27071370
Solicitation number
CS27023
Issued by
Utah

About this file

This is an approved mechanical plans document for a Stage II Invitation to Bid issued by the State of Utah's Division of Facilities Construction and Management (DFCM) for HVAC upgrades at the Utah State Fairpark Zion Building located at 155 N 1000 W, Salt Lake City, UT. The project, designated DFCM #27071370, involves the removal and replacement of one existing air handler and one existing heat pump with a 20-ton indoor split system unit and a 20-ton outdoor heat pump unit. Additional work includes modifications to existing electrical accommodations, removal of a duct heater furnace, installation of a new duct-mounted furnace with natural gas piping, replacement of fire/smoke dampers, new refrigerant piping with R-454B refrigerant, new condensate piping, and new return ductwork with auto-dampers. The mechanical plans comply with 2024 International Building Code (IBC), International Mechanical Code (IMC), International Plumbing Code (IPC), and 2023 National Electrical Code (NEC) standards with Utah annotations. Only contractors prequalified under a Stage I Prequalification and currently listed on the DFCM Prequalified Contractors list are eligible to bid on this project.

The construction cost estimate for this project is $95,000.00. The plans specify that contractors must coordinate with a design-build electrical contractor for all electrical design and construction, including new fused disconnects, conduits, raceways, wiring, and circuit breakers. The mechanical work must include a complete test and balance report by a licensed and approved test and balance contractor, and all roofing modifications must be performed by the warranty-holding roofing contractor and approved by the DFCM roofing director. Contractors are required to field-verify all existing mechanical and architectural conditions, coordinate with the hazmat abatement contractor prior to demolition, and assume responsibility for the proper handling and disposal of refrigerants, oils, and other materials in accordance with all federal, state, and local laws. All piping, materials, and equipment must be new and domestic-made unless specifically authorized in writing prior to bid.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEF

O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

North: ______ South: ______ East: ______ West: ______

d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a

3) Three Story: A (3)______

2) Two Story: A (2)______

1) One Story: ______

c) Total Allowable Area for:

1_< Allowable Area

Actual Area

b) Sum of the Ratio Calculations for Mixed Occupancies:

a) 0.25I = 100f

F

P 30

WstA I

100100 fIA t taA = A + +

Official for Complex Buildings. Including, but not limited to:

g) Fire Stopping, Including Tested Design Number.

f) Exterior and Interior Accessibility Route.

e) Fire Assembly Locator Sheet.

a) High Rise Requirements.

b) Atriums.

c) Performance Based Criteria.

d) Means or Egress Analysis.

2) Additional Code Information shall be provided at the discretion of the Building

Code Accessibility Chapters, the more restrictive requirement shall govern.

through - ADA Guidelines and specific reference to the International Building

1) In case of conflict with the U.S. Department of Justice Federal Registers Parts

FOOTNOTES:

d) Drinking Fountains: ______ Service Sinks: ______

c) Bath Tubs or Showers: ______

b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______

a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____

M. Minimum Number of Required Plumbing Facilities:

Exit Width Required: ______ Exit Width Provided: ______

Element Hours Assembly ListingListing

Element AssemblyHours

Smoke Partitions

Fire Partitions

Exterior Bearing Walls

Interior Bearing Walls

Exterior Non-Bearing Walls

Structural Frame Partitions - Permanent

Fire Barriers

Floors - Ceiling Floors

Roofs - Ceiling Roofs

Exterior Doors and Windows

Shaft Enclosures

Fire Walls

BAHTBABABA

L. Design Occupant Load: ______

K. Fire Resistance Rating Requirements for Building Elements (hours).

Area Modifications:J:

____________________________________________Tabular Area:I:

per Floor (square feet): __________________________Actual AreaH:

Number of Stories: ______ Building Height: ______G:

Required: ______ Provided: ______ Type of Sprinkler System: ____________

Sprinklers:F:

Mixed Occupancies: ______ Nonseparated Uses: ______E.

separation distance (in hours):

Requirements for the Exterior Walls based on the fireFire Resistance RatingD.

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________

Design Wind Speed: ______ mphB. Seismic Design Category: ______

C. Type of Construction (circle one):

Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______

A. Occupancy and Group: ________ ________ ________ ________ ________

CODE ANALYSIS

Guidelines

ADA Accessibility Building Conservation

Uniform Code for

National Electrical Code

Conservation Code

International Energy International Fire Code

International Plumbing Code

International Mechanical Code

International Building Code

YearYear

APPLICABLE CODES

UTAH STATE FAIR PARK

ZION BUILDING UPGRADES

DFCM #27071370

155 N 1000 W, Salt Lake City, UT 84116

GENERAL:

G001 - TITLE SHEET

G002 - SPECIAL INSTRUCTIONS AND TESTING

MECHANICAL:

MG001 - MECHANICAL LEGEND AND GENERAL NOTES

MD101 - MECHANICAL DEMOLITION FLOOR PLAN

ME101 - MECHANICAL FLOOR PLAN

ME501 - MECHANICAL DETAILS

ME502 - MECHANICAL DETAILS

ME503 - MECHANICAL DETAILS

ME601 - MECHANICAL SCHEDULES

DRAWING INDEX:

DEFERRED SUBMITTALS: SEISMIC

SPECIAL INSPECTIONS:

1. SEE SHEET DRAWING G002.

DESIGN CRITERIA:

THESE DOCUMENTS - DRAWINGS AND

SPECIFICATIONS COMPLY WITH ALL THE

REQUIREMENTS OF THE DFCM STANDARDS FOR

MECHANICAL UPGRADES OF EXISTING BUILDING.

CODE INSPECTION REQUIREMENTS:

1. BEFORE A FINAL ACCEPTANCE CAN BE ISSUED,

THE STATE APPOINTED CODE INSPECTOR SHALL

PROVIDE A FINAL REPORT RECOMMENDING THAT

THE NEW MECHANICAL WORK IS IN COMPLIANCE

WITH THE DRAWINGS, SPECIFICATIONS AND

APPLICABLE CODES ESPECIALLY FOR THE

FOLLOWING ITEMS.

2. SEE ALSO SHEET G002.

SCOPE:

THIS PROJECT SHALL INCLUDE THE

REMOVAL AND REPLACEMENT OF ONE

EXISTING AIR HANDLER AND ONE EXISTING

HEAT PUMP. THIS SHALL ALSO INCLUDE

MODIFICATIONS TO THE EXISTING

ELECTRICAL ACCOMMODATIONS AS

NEEDED.

CODE REVIEW STAMP

N/A

N/A

N/A

X X

N/A N/A

N/A N/A N/A N/A

N/A N/A

N/A N/A

1 40'

9,500 SF

A2

G001

20232024

PROJECT SITE

08/24/26

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

THOMAS PETERSON

10/06/2026

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

G002

SPECIAL INSPECTIONS

AND TESTING

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X

X

X

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

M

M

MECHANICAL LEGEND

SYMBOL ABR, DESCRIPTION

GENERAL TERMINOLOGY

A

ME101

SECTION LETTER DESIGNATION

SECTION DRAWN ON THIS SHEET

A2

AH

DETAIL NUMBER DESIGNATION

CORRESPONDING WITH GRID

LOCATION

MECHANICAL EQUIPMENT DESIGNATION

EQUIPMENT ITEM DESIGNATION

REGISTER, GRILLE OR DIFFUSER

DESIGNATION WITH BALANCING CFM

LISTED BELOW

D-1

CFM

GRILLE OR LOUVER DESIGNATION

WHERE BALANCING NOT REQUIREDR-1

REVISION DESIGNATOR AND NUMBER

KEY NOTE DESIGNATOR AND NUMBER

POINT OF CONNECTION

POINT OF REMOVAL

ABOVE FINISHED FLOOR

ACCESS PANEL

CENTERLINE ELEVATION

GENERAL CONTRACTOR

AFF

AP

POC

POR

C EL.

GC

MECHANICAL CONTRACTORMC

CONTROLS CONTRACTORATC

ELECTRICAL CONTRACTOREC

FIRE PROTECTION CONTRACTORFPC

NOT IN CONTRACTNIC

NOT TO SCALENTS

VITRIFIED CLAY PIPEVCP

NORMALLY CLOSEDNC

COMMONC

NORMALLY OPENNO

SYMBOL ABR, DESCRIPTION

AIR SIDE

EXISTING AIR DUCT TO BE REMOVED

EXISTING AIR DUCT TO REMAIN

NEW AIR DUCT

RECT TO RECT AIR DUCT TAKE-OFF

RECT TO RND AIR DUCT TAKE-OFF

RND TO RND AIR DUCT TAKE-OFF

MEDIUM PRESSURE TAKE-OFF

FLEXIBLE AIR DUCT

SYMBOL ABR, DESCRIPTION

WET SIDE

PUMP

REGULATOR

UNION

MANUAL ACTUATOR

PNUEMATIC DIAPHRAM ACTUATOR

ELECTRIC MOTOR ACTUATOR

SOLENOID ACTUATOR

BUTTERFLY VALVE

GATE VALVE

GLOBE VALVE - STRAIGHT PATTERN

GLOBE VALVE - ANGLE PATTERN

MOTORIZED 2-WAY CONTROL VALVE

MOTORIZED 3-WAY CONTROL VALVE

CHECK VALVE

CIRCUIT BALANCING VALVE

BALL VALVE

PITCH DOWN

ELBOW UP/DN

TEE UP/DN

EXISTING PIPING TO BE REMOVED

EXISTING PIPING TO REMAIN

NEW PIPING

PIPE CAP OR PLUG

REDUCER - CONCENTRIC / ECCENTRIC

EXPANSION JOINT

FLEXIBLE CONNECTION

ANCHOR POINT

CONDENSATE DRAIN

NATURAL GAS PIPING

CHEMICAL FEED LINE

MAKE-UP WATER LINE

CULINARY COLD WATER

CULINARY HOT WATER

CULINARY HOT WATER RECIRC

CD

G

CF

MU

CW

HW

HWREC

GLYCOL FILL LINEGF

R

M

S

PRESSURE REDUCING VALVEPRV

REFRIGERANT LIQUIDL

VENT LINEV

SANITARY SEWERSS

REFRIGERANT SUCTIONS

RADIUS ELBOW

ECCENTRIC DUCT TRANSITION

CONCENTRIC DUCT TRANSITION

VOLUME DAMPER

SUPPLY AIR DIFFUSER

RETURN & TRANSFER AIR GRILLE

EXHAUST GRILLE OR CEILING EXH. FAN

RETURN & OUTSIDE AIR DUCT UP/DN

RETURN & OA ROUND DUCT UP/DN

SUPPLY AIR DUCT UP/DN

SUPPLY AIR ROUND DUCT UP/DN

EXHAUST AIR DUCT UP/DN

EXHAUST AIR ROUND DUCT UP/DN

ACCESS PANELAP

EXISTING EQUIPMENT TO BE REMOVED

EXISTING EQUIPMENT TO REMAIN

NEW EQUIPMENT

SUPPLY AIR

RETURN AIRRA

SA

EXHAUST AIREA

OUTSIDE AIROA

MIXED AIRMA

RELIEF AIRRF

FLAT OVALFO

MOTORIZED VOLUME DAMPER

BACKDRAFT DAMPER

FIRE DAMPER

SMOKE DAMPER

FIRE & SMOKE DAMPER

WALL MOUNTED THERMOSTAT

WALL MOUNTED TEMP. SENSOR

WALL MOUNTED HUMIDISTAT

WALL MOUNTED FIRESTAT

M

BD

F

S

FS

T

S

H

F

MVD

BD

FD

SD

FS

T-STAT

H-STAT

F-STAT

GENERAL NOTES

G-1 - MECHANICAL INFORMATION IS NOT LIMITED TO THE

MECHANICAL DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE

FOR INFORMATION OF THE EXISTING BUILDING AND SITE

CONDITIONS, EXISTING PIPING, EXISTING ELECTRICAL, AND

EXISTING SUPPORTS.

A - EACH DRAWING SHEET AND THE SPECIFICATIONS HAVE BEEN

PREPARED TO SUPPLEMENT EACH OTHER AND THEY SHALL BE

INTERPRETED AS AN INTEGRAL UNIT WITH ITEMS SHOWN AND

NOTED ON ONE AND NOT THE OTHER BEING FURNISHED AND

INSTALLED AS THOUGH SHOWN AND CALLED OUT IN ALL PLACES.

ITEMS IN SPECIFICATIONS OR DRAWINGS LISTED WHICH ARE

DIFFERING IN EFFICIENCY OR QUALITY SHALL BE HELD TO THE

GREATEST OF: EFFICIENCY, QUALITY OR GOVERNING CODE.

B - THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE

INSTALLATION OF THE SYSTEMS ACCORDING TO THE TRUE INTENT

AND MEANING OF THE CONTRACT DOCUMENTS.

C - THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH PROPER

SERVICE ACCESS AND CLEARANCES ACCORDING TO

MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL

REVIEW SUPPLIERS BID PACKAGES FOR COMPLETENESS AND

COMPLIANCE TO THE SPECIFICATIONS, SCHEDULES, AND DESIGN

INTENT (ALL EQUIPMENT AND METHODS). THE CONTRACTOR SHALL

REMOVE AND REINSTALL CORRECTLY AT HIS OWN EXPENSE ANY

EQUIPMENT NOT IN COMPLIANCE.

D - THE CONTRACTOR SHALL CONSULT MANUFACTURERS

INSTALLATION INSTRUCTIONS FOR SIZES, METHODS, ACCESSORIES,

AND CLEARANCES IN SPACE AVAILABLE PRIOR TO BIDDING

PROJECT.

E - ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED BY

MAKING APPLICATION TO THE ENGINEER IN WRITING.

G-2 - ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE

SUBMITTED TO THE ENGINEER PRIOR TO CHANGES FOR APPROVAL.

CONTRACTOR SHALL NOT START ANY CHANGES UNTIL NOTIFIED IN

WRITING. IF CHANGES ARE MADE PRIOR TO APPROVAL

CONTRACTOR SHALL TAKE ALL RESPONSIBILITY FOR THE CHANGES

MADE AND ALL COSTS RELATING TO FAILURE OR REPLACEMENT OF

ALTERATIONS.

G-3 - CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND

LOCATIONS.

G-4 - THE WORKING DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT

SHOW EVERY OFFSET, BEND, OR ELBOW NECESSARY FOR THE

COMPLETE INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS

FOR MECHANICAL EQUIPMENT SHALL BE FIELD VERIFIED AND

COORDINATED WITH ALL DRAWINGS. THE CONTRACTOR SHALL

PROVIDE OR COORDINATE WITH THE GENERAL CONTRACTOR

PROVISIONS FOR BLOCKOUTS OR CORE DRILLS THROUGH

STRUCTURE.

G-5 - THE INSTRUCTION TO "PROVIDE" ALSO INCLUDES

INSTALLATION.

G-6 - MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL

SMOKE AND FIRE DAMPERS AS REQUIRED BY LOCAL CODES AND

AUTHORITIES.

G-7 - SHEET METAL DUCT SIZES SHOWN ON DRAWINGS ARE FREE

AREA DIMENSIONS.

G-8 - PROVIDE AND INSTALL BALANCING DAMPERS IN ALL SUPPLY

AND EXHAUST AIR BRANCH DUCTS. BALANCE TO CFM SHOWN ON

PLAN.

G-9 - SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT

LOCATION OF DIFFUSERS AND GRILLES.

G-10 - PROVIDE TURNING VANES IN ALL ELBOWS OF RECTANGULAR

DUCT.

G-11 - THE CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY IN

HANDLING AND DISPOSING OF REFRIGERANTS, OILS, ETC. ALL SUCH

MATERIALS SHALL BE HANDLED, DISPOSED, AND USED IN

ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL LAWS.

G-12 - THE MECHANICAL CONTRACTOR SHALL VERIFY MOTOR

VOLTAGES WITH THE ELECTRICAL DRAWING BEFORE ORDERING

MOTORIZED EQUIPMENT AND CONTROLS.

G-13 - C.F.M. LISTED IS ACTUAL AIR.

G-14 - SUPPLIERS SHALL REVIEW ALL DRAWINGS AND THE

SPECIFICATIONS PRIOR TO SUBMITTING PRICES TO THE

CONTRACTOR. ALL QUESTIONS AND DISCREPANCIES SHALL BE

BROUGHT TO THE ENGINEERS ATTENTION PRIOR TO BIDDING.

G-15 - CONTRACTOR SHALL THOROUGHLY REVIEW AND SIGN

SUBMITTALS FOR COMPLETENESS AND COMPLIANCE TO THE

SPECIFICATIONS PRIOR TO ENGINEERS REVIEW. SUPPLIERS SHALL

HIGHLIGHT OR MARK ALL INFORMATION REQUIRED TO SHOW

COMPLIANCE TO THE SPECIFICATIONS. ALL REQUESTED

EXCEPTIONS TO THE SPECIFICATIONS, OR SCHEDULES SHALL BE

CLEARLY NOTED AND EXPLAINED. SUBMITTAL REVIEW AND

ACCEPTANCE IS FOR DESIGN CONCEPT ONLY, AND DOES NOT AT

ANY TIME RELIEVE THE CONTRACTOR OF RESPONSIBILITY TO MEET

SPECIFICATIONS, CAPACITIES, OR DESIGN INTENT.

G-16 - ALL MECHANICAL SHALL BE INSTALLED AND CONFORM TO THE

2024 EDITION OF THE IMC AND IPC WITH UTAH ANNOTATIONS AND

LOCAL AUTHORITY REQUIREMENTS.

G-17 - THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE

DRAINING DOWN AND RE-FILLING OF ALL SYSTEMS NECESSARY TO

COMPLETE THE WORK OUTLINED BY THIS PROJECT. THIS INCLUDES

PROVIDING THE REQUIRED CHEMICAL TREATMENT WHEN RE-

FILLING THE SYSTEM.

G-18 - ALL PIPING, MATERIALS, ETC. SHALL BE NEW AND DOMESTIC

MADE UNLESS SPECIFICALLY AUTHORIZED IN WRITING PRIOR TO

BID.

G-19 - THIS CONTRACTOR SHALL CONTRACT WITH A DESIGN BUILD

ELECTRICAL CONTRACTOR FOR THE DESIGN AND CONSTRUCTION

OF THE ELECTRICAL PORTION OF THIS PROJECT. ELECTRICAL

INSTALLATION AND DESIGN SHALL BE PER 2023 NEC.

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

MG001

MECHANICAL LEGEND &

GENERAL NOTES

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

8 8

GENERAL NOTES

1. CONTRACTOR SHALL FIELD VERIFY EXISTING

MECHANICAL AND ARCHITECTURAL CONDITIONS,

INCLUDING, BUT NOT LIMITED TO: EXISTING ROUTING

AND LOCATION OF DUCTWORK, PIPING, ELECTRICAL,

AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL

FIELD VERIFY POTENTIAL CONFLICTS BETWEEN NEW

MECHANICAL ELEMENTS AND EXISTING CONDITIONS

PRIOR TO BEGINNING FABRICATION OR ORDERING

EQUIPMENT.

2. PRIME CONTRACTOR SHALL PROVIDE ALL

COORDINATION BETWEEN SUB-TIER CONTRACTORS.

THIS SHALL INCLUDE THE COORDINATION BETWEEN

SUB-TIER CONTRACTORS, SUB-TIER CONTRACTORS

AND FACILITIES, SUB-TIER CONTRACTORS AND

ARCHITECT/ENGINEER.

3. ALL DEMOLISHED EQUIPMENT AND MATERIAL SHALL

BE BROKEN DOWN TO FIT THROUGH DESIGNATED

PATHWAYS. FIELD VERIFY EXACT SCOPE OF

DEMOLITION AND REMOVAL PATH. CONTRACTOR

SHALL BE RESPONSIBLE TO REPAIR ANY DAMAGE TO

BUILDING DURING REMOVAL OF EQUIPMENT AND

MATERIAL.

4. SOME EXISTING PIPING AND EXISTING DUCTWORK

NOT SHOWN ON THIS SHEET FOR CLARIFICATION.

FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID.

5. COORDINATE WITH DFCM PROVIDED HAZMAT REPORT

AND ABATEMENT CONTRACTOR PRIOR TO ANY

DEMOLITION.

6. CONTRACTOR SHALL MAKE PROVISIONS WITH A

DESIGN BUILD ELECTRICIAN TO VERIFY ELECTRICAL

CONDITIONS. DESIGN BUILD CONTRACTOR SHALL

PROVIDE ANY NEW WIRING, CIRCUIT BREAKERS,

PANELS, SWITCH GEAR, AND ALL NECESSARY

ELECTRICAL ACCOMMODATIONS FOR ANY NEW OR

RE-LOCATED MECHANICAL EQUIPMENT. CONTRACTOR

SHALL COORDINATE THE DEMOLITION AND REMOVAL

OF ANY ELECTRICAL ELEMENTS ASSOCIATED WITH

EXISTING MECHANICAL EQUIPMENT BEING REMOVED.

ALL ABANDONED PIPING AND WIRING SHALL BE

REMOVED BACK TO PANEL UNLESS OTHERWISE

APPROVED. ELECTRICIAN SHALL FIELD VERIFY AND

CONFIRM ELECTRICAL SCOPE AND EXISTING

CONDITIONS PRIOR TO ANY DEMOLITION WORK AND

ORDERING ANY NEW MECHANICAL EQUIPMENT.

7. PROVIDE UPDATED GRAPHICS AND PROGRAMMING

FOR ALL NEW AND EXISTING TEMPERATURE

CONTROLS AND MOTORIZED DAMPERS.

8. PROVIDE FULL TEST AND BALANCE REPORT OF ALL

IMPACTED SYSTEMS BY LICENSED AND APPROVED

TEST AND BALANCE CONTRACTOR.

9. ALL ROOFING MODIFICATIONS SHALL BE PERFORMED

BY WARRANTY HOLDING ROOFING CONTRACTOR AND

APPROVED BY DFCM ROOFING DIRECTOR.

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

MD101

MECHANICAL DEMOLITION

FLOOR PLAN

SHEET NOTES

1 REMOVE EXISTING HEAT PUMP AND ALL ASSOCIATED

ITEMS IN THIS APPROXIMATE LOCATION. REMOVE

EXISTING REFRIGERANT PIPING BACK TO INDOOR

AIR HANDLER. FIELD VERIFY EXISTING ROUTING AND

POINTS OF REMOVAL. REMOVE EXISTING

HOUSEKEEPING PAD.

2 REMOVE EXISTING NATURAL GAS PIPING BACK TO

THIS APPROXIMATE LOCATION. FIELD VERIFY

EXISTING ROUTING AND POINTS OF REMOVAL.

3 REMOVE EXISTING DUCT HEATER FURNACE, FLUE,

COMBUSTION AIR AND ALL ASSOCIATED ITEMS IN

THIS APPROXIMATE LOCATION. COORDINATE WITH

DESIGN BUILD ELECTRICIAN TO REMOVE EXISTING

ELECTRICAL BACK TO PANEL.

4 REMOVE EXISTING SUPPLY FAN AND ALL

ASSOCIATED ITEMS IN THIS APPROXIMATE

LOCATION. COORDINATE WITH DESIGN BUILD

ELECTRICIAN TO REMOVE EXISTING ELECTRICAL

BACK TO PANEL.

5 REMOVE EXISTING FLUE AND COMBUSTION AIR

PIPING BACK TO PENETRATION. PATCH AND REPAIR

EXISTING PENETRATION WEATHER TIGHT. FIELD

VERIFY EXACT ROUTING.

6 REMOVE EXISTING COOLING COIL IN THIS

APPROXIMATE LOCATION. REMOVE EXISTING

REFRIGERANT PIPING BACK TO OUTDOOR HEAT

PUMP. FIELD VERIFY EXISTING ROUTING AND POINTS

OF REMOVAL.

7 TEMPORARILY REMOVE EXISTING OUTSIDE AIR

LOUVER IN THIS APPROXIMATE LOCATION. PROVIDE

STORAGE AND SAFEKEEPING AND RE-INSTALL AFTER

NEW EQUIPMENT IS INSTALLED IN MECHANICAL

ROOM.

8 EXISTING DUCTWORK IN THIS APPROXIMATE

LOCATION SHALL REMAIN.

9 REMOVE AND REPLACE EXISTING FIRE SMOKE

DAMPER IN THIS APPROXIMATE LOCATION. FIELD

VERIFY.

10 REMOVE AND REPLACE EXISTING REFRIGERANT

PIPING SHEET METAL COVER IN THIS APPROXIMATE

LOCATION. FIELD VERIFY.

11 EXISTING FIRE SPRINKLER PIPING IN THIS

APPROXIMATE LOCATION SHALL REMAIN.

12 REMOVE AND REPLACE EXISTING THERMOSTAT IN

THIS APPROXIMATE LOCATION. FIELD VERIFY.

13 EXISTING RELIEF AIR LOUVER/AUTO DAMPER AND

ALL ASSOCIATED ITEMS IN THIS APPROXIMATE

LOCATION SHALL REMAIN.

14 COORDINATE WITH DESIGN BUILD ELECTRICIAN TO

REMOVE AND REPLACE EXISTING LIGHT FIXTURE IN

THIS APPROXIMATE LOCATION. FIELD VERIFY.

15 TEMPORARILY REMOVE EXISTING FLOOR GRATING IN

THIS APPROXIMATE LOCATION. PROVIDE STORAGE

AND SAFEKEEPING AND RE-INSTALL AFTER NEW

EQUIPMENT IS INSTALLED IN MECHANICAL ROOM.

FIELD VERIFY.

16 EXISTING MECHANICAL EQUIPMENT IN THIS

APPROXIMATE LOCATION SHALL REMAIN.

17 REMOVE AIR HANDLER WALLS IN THIS APPROXIMATE

LOCATION. FIELD VERIFY.

0'

SCALE : 1/8" = 1'-0"

8'4' 24'16'

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

IDU

ODU

EXIST

TYP. 20

12F

40"x19" SA

55"x16" SA

44"x20" RA

F S

D

A D

1"ø NG (E)

AD

AD

GENERAL NOTES

1. CONTRACTOR SHALL FIELD VERIFY EXISTING

MECHANICAL AND ARCHITECTURAL CONDITIONS,

INCLUDING, BUT NOT LIMITED TO: EXISTING ROUTING

AND LOCATION OF DUCTWORK, PIPING, ELECTRICAL,

AND STRUCTURAL ELEMENTS. CONTRACTOR SHALL

FIELD VERIFY POTENTIAL CONFLICTS BETWEEN NEW

MECHANICAL ELEMENTS AND EXISTING CONDITIONS

PRIOR TO BEGINNING FABRICATION OR ORDERING

EQUIPMENT.

2. PRIME CONTRACTOR SHALL PROVIDE ALL

COORDINATION BETWEEN SUB-TIER CONTRACTORS.

THIS SHALL INCLUDE THE COORDINATION BETWEEN

SUB-TIER CONTRACTORS, SUB-TIER CONTRACTORS

AND FACILITIES, SUB-TIER CONTRACTORS AND

ARCHITECT/ENGINEER.

3. ALL DEMOLISHED EQUIPMENT AND MATERIAL SHALL

BE BROKEN DOWN TO FIT THROUGH DESIGNATED

PATHWAYS. FIELD VERIFY EXACT SCOPE OF

DEMOLITION AND REMOVAL PATH. CONTRACTOR

SHALL BE RESPONSIBLE TO REPAIR ANY DAMAGE TO

BUILDING DURING REMOVAL OF EQUIPMENT AND

MATERIAL.

4. SOME EXISTING PIPING AND EXISTING DUCTWORK

NOT SHOWN ON THIS SHEET FOR CLARIFICATION.

FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID.

5. COORDINATE WITH DFCM PROVIDED HAZMAT REPORT

AND ABATEMENT CONTRACTOR PRIOR TO ANY

DEMOLITION.

6. CONTRACTOR SHALL MAKE PROVISIONS WITH A

DESIGN BUILD ELECTRICIAN TO VERIFY ELECTRICAL

CONDITIONS. DESIGN BUILD CONTRACTOR SHALL

PROVIDE ANY NEW WIRING, CIRCUIT BREAKERS,

PANELS, SWITCH GEAR, AND ALL NECESSARY

ELECTRICAL ACCOMMODATIONS FOR ANY NEW OR

RE-LOCATED MECHANICAL EQUIPMENT. CONTRACTOR

SHALL COORDINATE THE DEMOLITION AND REMOVAL

OF ANY ELECTRICAL ELEMENTS ASSOCIATED WITH

EXISTING MECHANICAL EQUIPMENT BEING REMOVED.

ALL ABANDONED PIPING AND WIRING SHALL BE

REMOVED BACK TO PANEL UNLESS OTHERWISE

APPROVED. ELECTRICIAN SHALL FIELD VERIFY AND

CONFIRM ELECTRICAL SCOPE AND EXISTING

CONDITIONS PRIOR TO ANY DEMOLITION WORK AND

ORDERING ANY NEW MECHANICAL EQUIPMENT.

7. PROVIDE UPDATED GRAPHICS AND PROGRAMMING

FOR ALL NEW AND EXISTING TEMPERATURE

CONTROLS AND MOTORIZED DAMPERS.

8. PROVIDE FULL TEST AND BALANCE REPORT OF ALL

IMPACTED SYSTEMS BY LICENSED AND APPROVED

TEST AND BALANCE CONTRACTOR.

9. ALL ROOFING MODIFICATIONS SHALL BE PERFORMED

BY WARRANTY HOLDING ROOFING CONTRACTOR AND

APPROVED BY DFCM ROOFING DIRECTOR.

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

ME101

MECHANICAL FLOOR PLAN

0'

SCALE : 1/8" = 1'-0"

8'4' 24'16'

SHEET NOTES

1 PROVIDE NEW 20 TON INDOOR SPLIT SYSTEM UNIT IN

THIS APPROXIMATE LOCATION. COORDINATE WITH

MANUFACTURER FOR CLEARANCES AND

INSTALLATION REQUIREMENTS. PROVIDE ALL NEW

REFRIGERANT PIPING FROM INDOOR UNIT TO

OUTDOOR HEAT PUMP. FIELD VERIFY EXACT

ROUTING AND POINTS OF CONNECTION. PROVIDE

WITH FACTORY FURNISHED LEAK DETECTION

SYSTEM AND ALARMS. PROVIDE NEW CONDENSATE

PIPING FROM AIR HANDLER TO NEAREST FLOOR

DRAIN OR MOP SINK. COORDINATE WITH DESIGN

BUILD ELECTRICIAN FOR ALL NEW ELECTRICAL

ACCOMMODATIONS INCLUDING: NEW FUSED

DISCONNECT, NEW CONDUIT AND RACEWAYS, NEW

WIRING, AND NEW BREAKERS. COORDINATE WITH

MANUFACTURER FOR CLEARANCES AND

INSTALLATION REQUIREMENTS.

2 PROVIDE NEW 20 TON OUTDOOR HEAT PUMP IN THIS

APPROXIMATE LOCATION. PROVIDE ALL NEW

REFRIGERANT PIPING FROM HEAT PUMP TO INDOOR

UNIT. FIELD VERIFY EXACT ROUTING AND POINTS OF

CONNECTION. COORDINATE WITH DESIGN BUILD

ELECTRICIAN FOR ALL NEW ELECTRICAL

ACCOMMODATIONS INCLUDING: NEW FUSED

DISCONNECT, NEW CONDUIT AND RACEWAYS, NEW

WIRING, AND NEW BREAKERS. PROVIDE NEW

HOUSEKEEPING PAD. AND ELEVATED SUPPORT

STRUCTURE. SEE DETAILS. COORDINATE WITH

MANUFACTURER FOR CLEARANCES AND

INSTALLATION REQUIREMENTS.

3 RE-INSTALL EXISTING LOUVER AND ALL ASSOCIATED

ITEMS IN THIS APPROXIMATE LOCATION. FIELD

VERIFY. SEAL PENETRATION WEATHER TIGHT. PATCH

AND PAINT TO MATCH EXISTING.

4 PROVIDE NEW REFRIGERANT PIPING SHEET METAL

COVER IN THIS APPROXIMATE LOCATION. PROVIDE

WITH UV AND CORROSION RESISTANT PAINT.

COORDINATE WITH FACILITY FOR COLOR.

5 BALANCE EXISTING DIFFUSER TO CFM AS SHOWN.

6 PROVIDE NEW OUTSIDE AIR AUTODAMPERS IN THIS

APPROXIMATE LOCATION. FIELD VERIFY. INTERLOCK

CONTROLS WITH EXISTING RELIEF AIR DAMPERS

AND NEW RETURN AIR DAMPERS.

7 INTERLOCK EXISTING RELIEF AIR DAMPER IN THIS

APPROXIMATE LOCATION WITH NEW RETURN

DAMPER AND NEW OSA DAMPERS.

8 DIFFUSER AT THIS APPROXIMATE LOCATION IS

CAPPED AND DOES NOT REQUIRE BALANCING.

9 RE-INSTALL EXISTING FLOOR GRATING IN THIS

APPROXIMATE LOCATION. FIELD VERIFY.

10 PROVIDE NEW RETURN DUCTWORK AND NEW

AUTO-DAMPER IN THIS APPROXIMATE LOCATION. TIE

INTO EXISTING BUILDING MANAGEMENT SYSTEM.

INTERLOCK NEW RETURN AIR DAMPER WITH NEW

OSA AND RELIEF DAMPERS. PROVIDE UPDATED

CONTROLS PROGRAMMING AS NEEDED. FIELD

VERIFY.

11 PROVIDE NEW FULL LENGTH AND FULL HEIGHT

GALVANIZED SHEET METAL PARTITION IN THIS

APPROXIMATE LOCATION. FIELD VERIFY. SEE

DETAILS.

12 PROVIDE NEW ACCESS DOOR IN THIS APPROXIMATE

LOCATION. FIELD VERIFY. SEE DETAILS.

13 PROVIDE NEW DUCT MOUNTED FURNACE IN THIS

APPROXIMATE LOCATION. FIELD VERIFY. PROVIDE

NEW FLUE AND COMBUSTION AIR PIPING. FIELD

VERIFY EXACT ROUTING. USE EXISTING

PENETRATIONS AS NEEDED. SEAL PENETRATIONS

WEATHER TIGHT. PROVIDE NEW GAS PIPING AND

GAS VALVE TRAIN. SEE DETAILS. COORDINATE WITH

DESIGN BUILD ELECTRICIAN FOR COORDINATE WITH

DESIGN BUILD ELECTRICIAN FOR ALL NEW

ELECTRICAL ACCOMMODATIONS INCLUDING: NEW

FUSED DISCONNECT, NEW CONDUIT AND RACEWAYS,

NEW WIRING, AND NEW BREAKERS.

14 COORDINATE WITH DESIGN BUILD ELECTRICIAN TO

PROVIDE NEW LED LIGHT FIXTURE IN THIS

APPROXIMATE LOCATION. FIELD VERIFY. PROVIDE

SINGLE POLE SWITCH, NEW CONDUIT, RACEWAYS,

AND NEW WIRING.

15 TIE INTO EXISTING NATURAL GAS PIPING IN THIS

APPROXIMATE LOCATION. FIELD VERIFY EXACT

ROUTING AND POINTS OF CONNECTION.

16 PROVIDE NEW FIRE SMOKE DAMPER IN THIS

APPROXIMATE LOCATION. FIELD VERIFY.

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

F

4"

MIN.

4"

MIN.

3'-0" 2"

2"

12"C .C

.M

AX.

2"

12"C.C.MAX.

1/

2" W

ID

E

R U N N

ER

LARGE CAPACITY

REFRIGERANT PIPING DIAGRAM

C2

DUCT STRAP HANGER DETAIL

C1

TYPICAL REFRIGERANT SCHEME

B2

DUCT LINER DETAIL

B1

SINGLE THICKNESS TURNING VANE DETAIL

C4

OUTDOOR EQUIPMENT PAD DETAIL

A1

PIPE HANGER DETAIL

C4

B4

FLUE THRU ROOF DETAIL

L

S

LS

F

LS

L S

HEAT PUMP

AIR HANDLER

SCALE: NONE

SUCTION LINE

ACCUMULATOR

DOUBLE OPENING

SIGHT GLASS (TYP.)

DOUBLE SUCTION RISER SIZE PER

CONDENSING UNIT MANUFACTURER'S

RECOMMENDATIONS

REFRIGERANT

SUCTION

HOT GAS SOLENOID

VALVE

HOT GAS DISCHARGE

BY-PASS VALVE

REFRIGERANT

SOLENOID VALVE

REFRIGERANT

EXPANSION VALVE

THERMAL BULB @

45° BELOW HORIZ.

SIDE CONNECTION

DISTRIBUTOR OR ASC

EXTERNAL

EQUALIZER

REFRIGERANT TYPE

VALVE (TYPICAL)

FLEXIBLE

CONNECTIONS

REFRIGERANT TYPE

STRAINER

REFRIGERANT LIQUID

REPLACEABLE

CARTRIDGE DRIER

CHARGING VALVE

PROVIDE FLEXIBLE

CONNECTION IN

PIPING AT UNIT

#10 x 3/4" SELF

TAPPING CADMIUM PLATED

SHEET METAL SCREWS TO

ANCHOR STRAPS TO DUCT.

ALL STRAPS TO BE TIGHT

AGAINST DUCT AND SUPPORT

MEMBERS. (TYPICAL)

SCALE: NONE

1"

1" x 18 GAUGE STRAP

HANGERS AT 8'-0"

SPACING.

1" x 18 GAUGE STRAP

HANGERS AT 8'-0"

SPACING.

NO POP RIVETS

ALLOWED

NOTES:

1. SEE SPECIFICATIONS FOR

SEISMIC RESTRAINT

REQUIREMENTS.

ATTACH SECURELY TO

STRUCTURE.

SCALE: NONE

SL

AIR

FLOW

SLEEVE THROUGH WALL

VIBRATION ISOLATORS

UNDERNEATH UNITS.

(ONE EACH CORNER)

FLEXIBLE

CONNECTION

(TYP)

SIGHT GLASS

FILTER DRIER

CONTINUOUS SLOPE

BACK TO CONDENSING

UNIT.

PROVIDE 20 GAUGE SHEET METAL PAN

AROUND REFRIGERANT PIPING. PAINT PAN

TO MATCH BUILDING COLOR WITH PRIMER

AND TWO COATS OF OIL BASED PAINT.

COLOR TO BE SELECTED BY ARCHITECT.

GRIP NAILS SHALL BE

INSTALLED BY AIR

HAMMER OR BY

AUTOMATIC FASTENER

EQUIPMENT.

INSULATED PINS, FASTENERS

OR GRIP NAILS.

SCALE: NONE

METAL FASTENERS

ENDS OF LINER SHALL BE

BUTTED FIRMLY TOGETHER.

ALL JOINTS, SEAMS, AND

TEARS SHALL BE COATED W/

ADHESIVE DURING

INSTALLATION.

MINIMUM OF 1-1/2" LINER.

SEE SPECIFICATION FOR

INSULATION REQUIREMENT

SHEET METAL

DUCT

TOP AND BOTTOM

SECTIONS OF LINER

SHALL OVERLAP THE

SIDES

DUCTLINER

ONE INCH THICK 1-1/2 LB

DENSITY FIBERGLASS.ALL ENDS OF LINER TO

BE COATED W/ ADHESIVE

NOT MORE THAN 2"

FROM EDGE OF LINER.

F L O

W

A

IR

SCALE: NONE

LEADING AND

TRAILING

EDGE TO BE PARALLEL

WITH SIDE OF DUCT.

SINGLE THICKNESS

TURNING VANES

1" LONG MINIMUM

TRAILING EDGE

DETAIL NOTES:

PROVIDE 12" OF COMPACTED STRUCTURAL FILL MINIMUM. COMPACTED LIFTS TO AT LEAST 95% OF THE DRY DENSITY IN

ACCORDANCE WITH ASTM D-1557.

4" COMPACTED LAYER OF COMPACTED GRAVEL. GRAVEL MAY CONSIST OF TYPE I OR TYPE II AGGREGATE BASE, OR PIT RUN

GRAVEL WITH A 2-INCH MAXIMUM PARTICLE SIZE AND NO MORE THAN 12% FINES PASSING THE NO. 200 SIEVE.

4" THICK REINFORCED CONCRETE PAD.

#4 @16 BOTHWAYS

12"4"

See Plan

SCALE: NONE

4"

2 3

HANGER ROD

PIPE

HANGER

SUPPORT NUT

LOCKING NUT

CALCIUM SILICATE BLOCK

16 GA. ZINC COATED SHEET

STEEL SHEILD AT LEAST 12" LONG

(TYP)

MOUNT PIPING TO UNISTRUT

PROVIDE PIPE CLAMPS

WITH BOLTS AND NUTS

CALCIUM SILICATE

BLOCK

CALCIUM SILICATE

BLOCK

BOLT UNISTRUT TO EXISTING

WALL AND CONCRETE USING

EXPANSION ANCHOR BOLTS

ATTACH TO ROOM

OVERHEAD STRUCTURE

SPRING TYPE ISOLATOR

FOR INSTALLATION

NEAR HOT WATER

PUMPS

CLEVIS HANGER

INSULATION

16 GAGE ZINC

COATED SHEET

STEEL SHIELD AT

LEAST 12" LONG.

HEAVY DUTY

CLEVIS HANGER

HANGER ROD

SUPPORT NUT

LOCKING NUT

HEAVY DUTY

CLEVIS HANGER

PIPE

SINGLE HORIZONTAL RUN

WITHOUT INSULATION

CLEVIS HANGER

ATTACH TO EXISTING

CEILING

INSULATION WITH OR WITHOUT

VAPOR BARRIER

NOTE:

PROVIDE WITH VAPOR BARRIER

ON CHILLED WATER AND

DOMESTIC COLD WATER PIPING

SCALE: NONE

BACK-DRAFT

PREVENTER

NON-HARDENING

CAULK

FLASHING

SHEATHING

DOUBLE

WALL FLUE

2" MIN. CLEAR

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

ME501

MECHANICAL DETAILS

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

1. R-454 REFRIGERANT.

2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

3. PROVIDE WITH INDIVIDUAL ZONE THERMOSTAT.

4. PROVIDE NEW PHASE AND VOLTAGE MONITORS.

5. PROVIDE WITH NEW SUPPLY AIR DUCT DETECTOR AND RETURN AIR DUCT DETECTORS.

6. PROVIDE WITH BACNET CAPABILITY AND TIE INTO EXISTING BMS.

7. PROVIDE WITH FACTORY FURNISHED LEAK DETECTION SYSTEM.

8. PROVIDE NEW REFRIGERANT PIPING FROM INDOOR UNIT TO OUTDOOR UNIT PER MANUFACTURERS RECOMMENDATIONS.

9. PROVIDE WITH INTEGRAL FILTER SECTION.

10. COORDINATE WITH MANUFACTURER FOR FLUE AND COMBUSTION AIR REQUIREMENTS.

11. PROVIDE WITH DUAL CIRCUITS.

12. PROVIDE WITH DUAL FANS.

13. PROVIDE WITH FACTORY FURNISHED 2-SPEED VFD.

14. PROVIDE WITH SINGLE POINT POWER.

1. R-454 REFRIGERANT.

2. SEE SPECIFICATIONS FOR OTHER APPROVED MANUFACTURERS.

3. PROVIDE NEW PHASE AND VOLTAGE MONITORS.

4. PROVIDE WITH HAIL GUARDS.

5. PROVIDE WITH NEW FUSED DISCONNECT.

6. PROVIDE NEW HOUSEKEEPING.

7. PROVIDE WITH BACNET CAPABILITY AND TIE INTO EXISTING BMS.

8. PROVIDE WITH FACTORY FURNISHED LEAK DETECTION SYSTEM.

9. PROVIDE WITH LOW AMBIENT KIT.

10. PROVIDE NEW REFRIGERANT PIPING FROM INDOOR UNIT TO OUTDOOR UNIT PER MANUFACTURERS RECOMMENDATIONS.

11. PROVIDE WITH CRANKCASE HEATER FOR EACH COMPRESSOR.

12. PROVIDE WITH DUAL COMPRESSORS AND DUAL CIRCUITS.

13. PROVIDE WITH FACTORY FURNISHED LEAK DETECTION SYSTEM.

1. PROVIDE WITH HIGH ALTITUDE KIT.

2. PROVIDE WITH LOW AMBIENT KIT.

3. #409 STAINLESS STEEL HEAT EXCHANGER.

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

ME601

MECHANICAL SCHEDULES

SPLIT SYSTEM - INDOOR UNIT SCHEDULE

TAG

SUPPLY

AIR CFM

OUTSIDE AIR

CFM

ESP

COOLING HEATING ELECTRICAL DIMENSIONS

MANUF. AND MODEL

SCHEDULE

NOTESTYPE #

TOTAL CLG

LOAD

EAT DB EAT WB LAT

TOTAL HTG

LOAD @47°F

TOTAL HTG

LOAD @5°F

EAT DB LAT V PH HZ MCA MOP IEER COP L W H WT

IDU 1 8,000 CFM 1,600 CFM 1.00 in-wg 243,160 Btu/h 80 °F 62 °F 52 °F 229,440 Btu/h 114,530 Btu/h 70 °F 103 °F 208 V 3 60 Hz 29 A 50 A 12.5 3.2 32 in 93 in 72 in 904 lb

TRANE

TWE240K3BAA

1, 2, 3, 4, 5, 6, 7, 8

9, 10, 11, 12, 13, 14

SPLIT SYSTEM - OUTDOOR UNIT SCHEDULE

TAG CAPACITY

REFRIGERANT

TYPE

ELECTRICAL DIMENSIONS

MANUF. AND MODEL

SCHEDULE

NOTESTYPE #

COOLING LOAD

TOTAL

HEATING LOAD

TOTAL

V PH HZ MCA MOP L W H WT

ODU 1 243,160 Btu/h 232,000 Btu/h R-454B 208 V 3 60 Hz 93 A 125 A 46" 96" 45" 914 lb

TRANE

TWA240K3DAB

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13

FURNACE SCHEDULE

TAG

HEATING

ELECTRICAL

DIMENSI

ONS MANUF. AND MODEL

SCHEDULE

NOTES

TYPE NUMBER HTG INPUT HTG OUTPUT TYPE V PH HZ WT

F 1 300,000 Btu/h 294,000 Btu/h

NATURAL

GAS

115 V 1 60 Hz 312 lb TRANE GIXC 1, 2, 3

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

DX COIL

S

L

THERMOSTATIC BULB

TO BE AS CLOSE TO

COIL AS POSSIBLE NOT

ALLOWED ON VERTICAL

LINES.

SCALE: NONE

45°THERMOSTATIC

BULB

4" MINIMUM

TRAP

TRAP

EQUALIZING

LINE

THERMOSTATIC

EXPANSION VALVE

CLAMP

SUCTION

LINE

THERMAL BULB

LOCATION

V E

R T

IC

A

L

MIN 10

PIPE

DIAMETERS

M

IN

2" MIN

VARIES

2" MIN

2" MIN 2" MIN

PIPE AND CONDUIT FLASHING DETAIL

A1 A3

GAS LINE CONNECTION DETAIL

B3

FURNACE SUPPORT DETAIL #1

SINGLE REFRIGERANT COIL

CONNECTION DETAIL

D3

TYPICAL

TYPICAL

PIPE / CONDUIT

FLASHING MEMBRANE AND

SEALANT

STAINLESS STEEL CLAMPING

RING

SPM MEMBRANE PRE-FABRICATED

BOOT WITH MINIMUM 1" TURN-UP

CONTINUOUS WELDHEAT WELDED FLASHING

ROOFING MEMBRANE -

VARIES BY PROJECT

RIGID INSULATION -

VARIES BY PROJECT

ROOF DECK VARIES

BY PROJECT

PLUMBING VENT / STACK

FLASHING MEMBRANE

AND SEALANT

STAINLESS STEEL

CLAMPING RING

ADHERED FIELD

FLASHED MEMBRANE

HEAT WELDED

FLASHING

ROOFING MEMBRANE

- VARIES BY PROJECT

RIGID INSULATION -

VARIES BY PROJECT

ROOF DECK VARIES

BY PROJECT

NOTE THAT PITCH POCKETS

ARE NOT AN ACCEPTABLE

METHOD OF WATER-PROOFING

BASE OF PIPES

NOTE:

IF THE TOP OF THE EXISTING VENT IS

LESS THAN 12" ABOVE THE NEW

FINISHED ROOF SURFACE, THE VENT

MUST BE EXTENDED

NOTE THAT WHERE A PIPE IS CAPABLE OF

BEING FLASHED USING A ROOFING

MANUFACTURERS PRE-FABRICATED BOOT

(SUCH AS SHOWN ABOVE), THAT OPTION IS

REQUIRED AND SHOULD BE USED OVER A FIELD

FLASHED DETAIL (SUCH AS SHOWN BELOW)

SCALE: NONE

GAS

SUPPLY.

MANUAL

SHUT-OFF

VALVE.

GAS

PRESSURE

REGULATOR

(2 PSI TO 4 OZ).

DRIP LEG.

SCALE: NONE

GROUND

JOINT

UNION.

EQUIPMENT

CONNECTION.

FLEXIBLE GAS

CONNECTOR

18" MAX.

CAP.

SCALE: NONE

FURNACE ONLY

AIR FLOW

WIDE RADIUS

ELBOW (TYPICAL)

FLEX CONNECTION

VENT 7" ABOVE

TRAP LEVEL

DRAIN PAN 2" BEYOND

EQUIPMENT HUNG FROM

SUPPORT FRAMING.

FURNACE CONDENSATE

TRAP & DRAIN

NOTE: ALL CHANNELS

FOR SUPPORT ARE

1-5/8" UNISTRUT P1000

PIPE TO FLOOR DRAIN

12" MINIMUM HORIZONTAL

OFFSET ON BOTH PIPES

MAINTAIN FURNACE OUTLET

PIPE SIZE TO THIS POINT

SEE UPPER ATTACHMENT

DETAILS ?/M??? AND ?/M???.

VIBRATION ISOLATOR

TYPICAL

FILTER FRAME EXTERNAL OF

FURNACE. SEE DETAIL ?/M???.

DO NOT BLOCK FILTER

ACCESS PANEL OR

FURNACE ACCESS DOORS

WITH HANGER RODS.

FLEX CONNECTION

CHANNEL CROSS MEMBER

SUPPORT. TYP. OF 2.

CHANNEL CONTINUOUS SUPPORT

UNDER ENTIRE LENGTH OF FURNACE.

TYPICAL OF 2.

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

ME502

MECHANICAL DETAILS

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

2- 1/

2" Ø

X S

C H

E D

U

LE

P

IP

E

OUTDOOR VRF UNIT SUPPORT DETAIL

A1

SUSPENDED REFRIGERANT

PIPE SUPPORT AT CEILING

A4

UNISTRUT

4"X3"X1/4" STEEL ANGLE

1/4

TYP

4"X3"X1/4" STEEL ANGLE

STRUCTURE

FRONT OF UNIT

SCALE: NONE

SIDE OF UNIT

SPRING ISOLATORS.

TYPICAL

8"X8"X3/8"

STEEL PLATE 1/2"ANCHORS

X 3" EMBED

DRILL 1" EXPANSION

HOLE FOR

GALVANIZING

ALL STEEL ABOVE

ROOF TO BE

GALVANIZED

VIBRATION

ELIMINATOR RISER

SEISMIC / VIBRATION

ISOLATOR. TYPICAL.

UPPER RAIL

MOUNT REFRIGERANT

PIPING UNDER. UNITS.

NOTE:

TYPICAL CEILING SPACE. ADAPT

TO SITE CONDITIONS IN A

PROFESSIONAL MANNER.

SCALE: NONE

3/8" X 3" LAG

SCREW WITH

WASHER.

HANGER RODS

ROOF OR

CEILING JOIST

TYPICAL PIPE IN MECHANICAL

ROOM OR CEILING SPACE. WRAP

UNINSULATED PIPE WITH 2 LAYERS

SCOTCH #33 TAPE FOR 3" EITHER

SIDE AND THROUGH CLAMP.

GYPSUM BOARD

1" CHANNEL

"UNISTRUT" OR

EQUAL

RUN INSULATION THRU

CLAMP ASSEMBLY

SECURE PIPING TO

SUPPORTS WITH "UNISTRUT"

PIPE CLAMP OR EQUAL.

1-5/8" P-1001

"UNISTRUT" CHANNEL

OR EQUAL. (TYPICAL)

S E

F O

R P

H

ATUFOETAT

S

R E

E

NI

GNELANOIS

WINWARD M.

PACKER

No. 375080

A

LL

ID

E

A S

D

E S

IG

N

S , A

R R

A N

G E

M E

N T

S A

N D

P

LA

N S

IN

D

IC

A

T E

D O

R R

E P

R E

S E

N T

E D

B Y

T H

IS

D

R A

W

IN

G A

R E

O W

N E

D B

Y A

N D

T H

E P

R O

P E

R T

Y O

F W

H W

E N

G

IN

E E

R

IN

G

IN

C . A

N D

W E

R E

C R

E A

T E

D , E

V O

LV

E

D , A

N D

D E

V E

LO

P

E D

F O

R U

S E

O N

A N

D

IN

C O

N N

E C

T

IO

N W

IT

H

T H

E S

P E

C

IF

IE

D

P R

O

JE

C T

N

O N

E O

F T

H E

ID

E

A S

,D E

S

IG

N S

, A R

R A

N G

E M

E N

T S

O R

P

LA

N S

S H

A

LL

B E

U S

E D

B Y

O R

D

IS

C

LO

S E

D T

O A

N Y

P E

R S

O N

, F

IR

M

O R

C O

R P

O R

A T

IO

N

F O

R A

N Y

P U

R P

O S

E W

H A

T S

O E

V E

R W

IT

H

O U

T W

R

IT

T E

N C

O N

S E

N T

O F

W H

W E

N G

IN

E

E R

IN

G

IN

C

W

R

IT

T E

N D

IM

E

N S

IO

N

S O

N T

H E

S E

D R

A W

IN

G

S S

H A

LL

H

A V

E P

R E

C E

D E

N C

E O

V E

R S

C A

LE

D

IM

E

N S

IO

N

S

C O

N T

R A

C T

O R

S S

H A

LL

V

E R

IF

Y

A N

D B

E R

E S

P O

N S

IB

LE

F O

R A

LL

D

IM

E

N S

IO

N

S A

N D

C O

N D

IT

IO

N S

O N

T H

E J

O B

A N

D T

H

IS

O F

FI

C

E M

U S

T B

E N

O T

IF

IE

D O

F A

N Y

V A

R

IA

T

IO

N F

R O

M T

H E

D

IM

E N

S

IO

N S

A N

D C

O N

D

IT

IO

N

S S

H O

W N

B Y

T H

E S

E D

R A

W

IN

G S

W

A R

N

IN

G : R

E P

R O

D U

C T

IO

N

H E

R E

O F

IS

A

C R

IM

IN

A L

O

FF

E N

S E

U N

D E

R

U

.S .C

. S E

C . 5

. U

N A

U

TH

O R

IZ

E

D D

IS

C

LO

S

U R

E M

A Y

C O

N S

T

IT

U

TE

T R

A D

E S

E C

R E

T M

IS

A

P P

R O

P R

IA

T

IO

N

IN

V

IO

LA

TI

O

N O

F I.

C .2

4- 2-

-1

E T.

S E

Q . A

N D

O T

H E

R L

A W

S

CONSULTANTS

PROJECT NAME & ADDRESS

CODE REVIEW STAMP

SHEET NO.

PROJECT MANAGER:

DATE:

CHECKED BY:

DRAWN BY:

REVISIONDATEMARK

08/24/2026

WHW JOB NO.:

26059

A

B

C

D

1 2 3

1 2 3

A

B

C

D

SHEET TITLE

CL

UTAH STATE FAIR

PARK ZION BUILDING

HVAC UPGRADES

DFCM # 27071370

155 N 1000 W, Salt Lake City, UT 84116

MO 08/24/26

ME503

MECHANICAL DETAILS

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

File details come from the government source that posted it. Updated .