This document package includes construction documents for upgrades to freight elevators in Buildings 4 and 7 at the Thomas E. Creek Amarillo VA Health Care System in Amarillo, Texas. The project includes installing new elevator cabs, controls, and related equipment in both buildings. Building 4 will be completed in two phases to maintain elevator service. Work includes demolishing existing components and constructing barriers to maintain infection control standards. The Department of Veterans Affairs is the contracting agency overseeing the upgrades.
The package consists of 55 drawings covering site plans, demolition plans, fire and life safety plans, schedules and sections. Drawings provide dimensions, notes and details for the elevator replacements and temporary construction. Specifications and standards listed on the architectural symbols sheet will govern materials and execution of work.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
PHONE: (206) 590-2118
DESIGN TEAM
FIRE PROTECTION
STRUCTURAL
WSP GLOBAL INC.
ELECTRICAL
SPEES DESIGN BUILD
PLUMBING
MECHANICAL
DAVENERGY
10525 VISTA SORRENTO PARKWAY, SUITE 350
SAN DIEGO, CA 92121
PHONE: (858) 500-4500
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
PHONE: (619) 770-8552
625 1ST AVE, STE 301
SEATTLE, WA 98104
PHONE: (206) 590-2118
DAVENERGY
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
PHONE: (619) 770-8552
DAVENERGY
2207 GARNET AVE, SUITE I
SAN DIEGO, CA 92109
PHONE: (619) 770-8552
PROJECT INFORMATION
STATE:
COUNTY:
JURISTICTION:
OWNER:
SITE ZONING:
CONST TYPE:
OCCUPANCY:
CODE ANALYSIS
PROJECT DESCRIPTION
THREE NEW ELEVATOR CABS TO BE
INSTALLED. ADDITIONALLY, ALL SAFETY
FEATURES ARE TO BE BROUGHT UP TO CODE
AND FUNCTION WITH THE FACILITIES
CURRENT SYSTEMS.
APPLICABLE BUILDING
BUILDING 4 & 7
APPLICABLE FLOOR
BLDG 4 - GROUND, FIRST & UPPER
BLDG 7 - GROUND, FIRST & SECOND
APPLICABLE CLINIC
N/A
ICRA CLASS REQUIREMENTS
CONST TYPE:
CLINIC RISK:
CLASS REQS:
APPROX SQUARE FEET IN SCOPE
1,065 SF
TYPE C
HIGHEST
CLASS IV
TEXAS
POTTER
AMARILLO
GOV, VETERANS AFFAIRS
1A B
RESOURCE DOCUMENTS
ELEVATOR REFERENCE CUTSHEETS* PROVIDED BY NORTHBAY
* ONLY FOR USE AS A BASIS OF DESIGN. FINAL SITE-SPECIFIC DRAWINGS SHALL BE PROVIDED
BY THE VA AFTER SELECTION OF SURGICAL BOOM MFR.
GENERAL NOTES
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR AND ANY SUB CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A BID OR BEGINNING WORK. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE
TO VISIT THE SITE.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
5. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
6. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE WALK
THROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
7. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
APPLICABLE PUBLICATIONS
AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS OF CODE ENFOREMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC). THE VA
SHALL FUNCTION AS THE AUTHORITY HAVING JURISTICTION (AHJ).
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION
GUIDE AND OTHER GUIDEANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL). SEE ABOVE.
INTERNATIONAL BUILDING CODE (IBC) 2018.
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.
NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES PRECEDENCE OVER
IBC.
NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
NATIONAL ELECTRICAL CODE (NEC).
INTERNATIONAL PLUMBING CODE (IPC).
SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAL SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUE AND
COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRCUTION , LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RESE RESIDENTIAL BUILDINGS, 10 CFR
PARTS 433,434 AND 435.
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF
UNDERSTANDING (MOU)
EXECTUIVE ORDER 13423: STRENGTHEING FEDERAL ENVIRONMENTAL, ENERGY AND TRANSPORTATON
MANAGEMENT.
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS
SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2004.
SAFETY STANDARD FOR REFRIDERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.
VAMC APPROVED HARDWARE LOCKING STANDARDS
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)
FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND STANDARDS FOR
TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS AND
INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI)
JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),
ENVIRONMENT OF CARE GUIDELINES AND STANDARDS
FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR THE
DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES
THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL
ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS ENCOURAGING
“ENVIRONMENTALLY RESPONSIBLE DESIGN”
APPLICABLE VA STANDARDS
DESIGN AND CONSTRUCTION PROCEDURES (PG 18-3), TOPIC 1 - CODES, STANDARDS & EXECUTIVE ORDERS
SEPTEMBER 2013
EQUIPMENT GUIDE LISTS (PG 18-5)
ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA SUPPLEMENT BARRIER
FREE DESIGN GUIDE (PG 18-13)
ELEVATOR DESIGN MANUAL PG 18-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES G-001
COVER SHEET
MK RR
CONSTRUCTION
DOCUMENTS
07/20/2022
UPGRADE FREIGHT ELEVATORS BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM, 6010 W AMARILLO BLVD, AMARILLO, TX
PROJECT #: 504-22-102
DRAWING INDEX
PAGE # SHEET # SHEET NAME
GENERAL
1 OF 55 G-001 COVER SHEET
2 OF 55 G-002 FACILITY SITE PLAN
3 OF 55 G-003 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
ARCHITECTURAL
4 OF 55 AS101 BUILDING 4 - FIRST FLOOR - ICRA PLAN
5 OF 55 AS102 BUILDING 4 - SECOND FLOOR - ICRA PLAN
6 OF 55 AS103 BUILDING 4 - UPPER LEVEL / ROOF - ICRA PLAN
7 OF 55 AS104 BUILDING 7 - LEVEL B - ICRA PLAN
8 OF 55 AS105 BUILDING 7 - LEVEL 1 - ICRA PLAN
9 OF 55 AS106 BUILDING 7 - LEVEL 2 - ICRA PLAN
10 OF 55 AS201 BUILDING 4 - FIRST FLOOR - FIRE AND LIFE SAFETY
11 OF 55 AS202 BUILDING 4 - SECOND FLOOR - FIRE AND LIFE SAFETY
12 OF 55 AS203 BUILDING 4 - UPPER LEVEL / ROOF - FIRE AND LIFE SAFETY
13 OF 55 AS204 BUILDING 7 - LEVEL B - FIRE AND LIFE SAFETY
14 OF 55 AS205 BUILDING 7 - LEVEL 1 - FIRE AND LIFE SAFETY
15 OF 55 AS206 BUILDING 7 - LEVEL 2 - FIRE AND LIFE SAFETY
16 OF 55 AD101 BUILDING 4 - FIRST FLOOR - DEMO PLAN
17 OF 55 AD102 BUILDING 4 - SECOND & UPPER FLOOR - DEMO PLANS
18 OF 55 AD103 BUILDING 7 - LEVEL B - DEMO PLAN
19 OF 55 AD104 BUILDING 7 - LEVEL 1 - DEMO PLAN
20 OF 55 AD105 BUILDING 7 - LEVEL 2 - DEMO PLAN
21 OF 55 AE101 BUILDING 4 - FIRST FLOOR - OVERALL FLOOR PLAN
22 OF 55 AE102 BUILDING 4 - SECOND FLOOR - OVERALL FLOOR PLANS
23 OF 55 AE103 BUILDING 4 - UPPER LEVEL / ROOF - OVERALL FLOOR PLAN
24 OF 55 AE104 BUILDING 7 - LEVEL B - OVERALL FLOOR PLAN
25 OF 55 AE105 BUILDING 7 - LEVEL 1 - OVERALL FLOOR PLAN
26 OF 55 AE106 BUILDING 7 - LEVEL 2 - OVERALL FLOOR PLAN
27 OF 55 AE301 BUILDING 4 - BUILDING SECTION
28 OF 55 AE302 BUILDING 7 - HOISTWAY SECTIONS
29 OF 55 AE401 BUILDING 4 - ENLARGED FLOOR PLANS
30 OF 55 AE402 BUILDING 7 - ENLARGED FLOOR PLANS
31 OF 55 AE421 INTERIOR ELEVATIONS
32 OF 55 AE422 INTERIOR ELEVATIONS
33 OF 55 AE601 ROOM FINISH & DOOR SCHEDULE
34 OF 55 AE602 DOOR SCHEDULE
MECHANICAL
35 OF 55 M-001 MECHANICAL COVER SHEET
36 OF 55 M-101 MECHANICAL FLOOR PLANS - BUILDINGS 4 + 7
37 OF 55 M-401 MECHANICAL SCHEDULES AND DETAILS BUILDINGS 4 + 7
PLUMBING
38 OF 55 P-001 PLUMBING COVER SHEET
39 OF 55 P-101 BUILDING 4 + 7 PLUMBING DESIGN
ELECTRICAL
40 OF 55 E-001 ABBREVIATION, GENERAL NOTES AND SHEET INDEX
41 OF 55 E-002 ELECTRICAL LEGENDS
42 OF 55 EP101 BUILDING 4 - FIRST FLOOR - ELECTRICAL PLAN
43 OF 55 EP102 BUILDING 4 - SECOND FLOOR - ELECTRICAL PLAN
44 OF 55 EP103 BUILDING 4 - UPPER LEVEL / ROOF - ELECTRICAL PLAN
45 OF 55 EP104 BUILDING 7 - LEVEL B - ELECTRICAL PLAN
46 OF 55 EP105 BUILDING 7 - LEVEL 1 - ELECTRICAL PLAN
47 OF 55 EP106 BUILDING 7 - LEVEL 2 - ELECTRICAL PLAN
48 OF 55 EP401 BUILDING 4 - ENLARGED ELECTRICAL PLANS
49 OF 55 EP402 BUILDING 4 - ENLARGED ELECTRICAL PLANS
50 OF 55 EP403 BUILDING 7 - ENLARGED ELECTRICAL PLANS
51 OF 55 E-601 BUILDING 4 - ONE-LINE DIAGRAM
52 OF 55 E-602 BUILDING 7 - ONE-LINE DIAGRAM
53 OF 55 E-603 ELECTRICAL SCHEDULES
54 OF 55 E-604 ELECTRICAL SCHEDULES
55 OF 55 E-605 ELECTRICAL SCHEDULES
Revisions: Date:
07/28/2022 ISSUED FOR CONSTRUCTION 7/29/2022
BUILDING 4
BUILDING 7
KEY NOTES HERE
KEY NOTES HERE
1. COORDINATE CONTRACTOR STAGING AREA WITH VA COR
AT THE PRE-CONSTRUCTION MEETING. THIS INCLUDES,
BUT IS NOT LIMITED TO, AREAS TO BE USED FOR
MATERIAL STORAGE, ACCESS FOR MATERIAL DELIVERIES
AND TRANSPORTATION ROUTES TO THE PROJECT AREA.
2. DO NOT STORE PRODUCTS, MATERIALS, TOOLS,
EQUIPMENT, VEHICLES, OR ANY OTHER NON-PERMITTED
ITEMS ON MEDICAL CENTER PROPERTY UNLESS GIVEN
PRIOR APPROVAL BY THE VA COR.
3. A LIMITED AMOUNT OF SUPPLIES MAY BE STORED IN THE
CONSTRUCTION AREA AS LONG AS SAFETY AND
CLEANLINESS ARE NOT COMPROMISED. VA COR HAS
AUTHORITY TO REQUEST RELOCATION OF ANY AND
ALL STORED ITEMS TO A DIFFERENT LOCATION.
4. VERIFY CONTRACTOR STAGING AREA AND MATERIAL /
PRODUCT DELIVERY LOCATION WITH VA COR, PRIOR TO
BRINGING OR DELIVERING ITEMS TO THE MEDICAL
CENTER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES G-002
FACILITY SITE PLAN
MK RR
CONSTRUCTION
DOCUMENTS
07/20/2022
1" = 1'-0"
FACILITY SITE PLAN
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
Revisions: Date:
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
NORTH
AB
ABA
AC(T)
ACM
ACW
ADA
ADJ
A/E
AF
AFF
AGG
ALT
ALUM
APPROX
ARCH
ASPH
A/V
BARR
BATH
BB
BLDG
BLK
BLKG
BLW
BM
BMTU
BO
BOC
BOS
BRC
BRKT
BRNG
BTM
BTWN
CAB
CC
CD
CJ
CLG
CLR
CMU
CO
COL
COMP
CONC
CONN
CONST
CONT
COORD
COR
CORR
CS
CT
CTR
CV
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ARCHITECTURAL BARRIERS ACT
ACOUSTICAL CEILING (TILE)
ASBESTOS CONTAINING MATERIAL
ACOUSTICAL WALL
AMERICANS W/ DISABILITIES ACT
ADJACENT
ARCHITECT/ENGINEER
ACCESS FLOOR
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT(URAL)
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BACKER BOARD
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BOTTOM OF
BOTTOM OF CURB
BOTTOM OF SLAB
BRACE, BRACING
BRACKET
BEARING
BOTTOM
BETWEEN
CABINET
CONTRACTOR FURN, CONTRACTOR INST
CONSTRUCTION/CONTRACT DOCUMENTS
CONTROL JOINT
CEILING
CLEAR(ANCE)
CONCRETE MASONRY UNIT
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CONTRACTING OFFICER REPRESENTATIVE
CORRIDOR
CONCRETE SEALER
CERAMIC TILE
CENTER
CONTRACTOR FURNISHED, VA INSTALLED
HDR
HDWE
HM
HORZ
HPDL
HR
HT
HVAC
ICRA
ID
ILSM
INCL
INST
INSUL
INT
JT
KV
LAM
LAV
LCM
LT
MAT
MAX
MDF
MECH
MEP
MFR
MIN
MISC
MOD
MTL
N N/A
NEG
NO.
NOM
NTS
O.C.
OPNG
OPP
OPT
OVHD
P
PCONC
PCRA
PL
PLAM
PLY(WD)
PNL
PR
PRFB
PS
PT
PTN(S)
PVMT
QTY
HEADER
HARDWARE
HOLLOW METAL
HORIZONTAL
HIGH PRESSURE DECORATIVE LAM
HOUR
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INFECTIOUS CONTROL RISK ASSESSMENT
INSIDE DIAMETER OR DIM
INTERIM LIFE SAFETY MEASURES
INCLUDE(D,ING)
INSTALL
INSULATION
INTERIOR
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LEAD CONTAINING MATERIAL(S)
LIGHT
MATERIAL(S)
MAXIMUM
MEDIUM-DENSITY FIBREBOARD
MECHANIC(AL)
MECHANICAL, ELECTRICAL, PLUMBING
MANUFACTURE(R)
MINIMUM
MISCELLANEOUS
MODIFIED
METAL
NORTH
NOT APPLICABLE
NEGATIVE
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER(S)
OPENING
OPPOSITE
OPTION(AL)
OVERHEAD
PAINT
PRECAST CONCRETE
PRE-CONSTRUCTION RISK ASSESSMENT
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAIR
PREFABRICATED
PLASTIC
PRESSURE TREATED
PARTITION(S)
PAVEMENT
QUANTITY
RAD
RCP
REF
REINF
REP
REQ(s,(')D)
RESIL
REV
RF
RM
RMV
RO
S
SCHED
SD
SECT
SF
SFRM
SHG
SHT(G)
SIM
SM
SOW
SPEC
SQ
SS
ST
STDG
STL
STOR
STRUCT
SUSP
SV
SYS
TEMP
T&G
THK
THRESH
TOC
TOS
TPH
TRANS
TS
TYP
UON
VA
VAR
VB
VC
VERT
VIF
VV
W W/
WD
WDW
WGHT
W/O
WP
WR
RADIUS
REFLECTED CEILING PLAN
REFERENCE
REINFORCE(D,ING)
REPRESENTATIVE
REQUIRE(D,S,MENT(S))
RESILIENT
REVERSE
RADIO FREQUENCY / ROOF
ROOM
REMOVE
ROUGH OPENING
SOUTH
SCHEDULE
SCHEMATIC DESIGN
SECTION
SQUARE FEET
SPRAY APPLIED FIRE-RESISTIVE MATERIAL
SHINGLES
SHEET (SHEATHING)
SIMILAR
SEAM
SCOPE OF WORK
SPECIFICATION
SQUARE
STAINLESS STEEL
STAIN
STANDING
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SHEET VINYL
SYSTEM
TEMPORARY
TONGUE AND GROOVE
THICK(NESS)
THRESHOLD
TABLE OF CONTENTS
TOP OF SLAB
TOILET PAPER HOLDER
TRANSITION
TUBE STEEL
TYPICAL
UNLESS OTHERWISE NOTED
VETERANS AFFAIRS
VARIES
VAPOR BARRIER
VA FURNISHED, CONTRACTOR INSTALLED
VERTICAL
VERIFY IN FIELD
VA FURNISHED, VA INSTALLED
WEST
WITH
WOOD
WINDOW
WEIGHT
WITHOUT
WATERPROOF(ING)
WATER RESISTANT
DBL
DC
DD
DEMO
DEPT
DG
DIA
DIM
DWN
DR
DTL
DWG
E
EA
EJ
ELEC
ELEV
ENG
EOC
EOP
EPDM
EQ
EQUIP
ES
ETS
EX(IST)
EXP
EXT
FA
FD
FE(C)
FF
FFB
FFL
FIN
FLASH
FLR
FLRSNT
FNDN
FOC
FOF
FOS
FP
FR
FRM
FT
FTG
FUR
FURN
GA
GALV
GE
G(W)B
GC
GL
GLB
GMU
GOV(T)
GYP
DOUBLE
DIRECT CURRENT
DESIGN DEVELOPMENT
DEMOLISH(ION)
DEPARTMENT
DESIGN GUIDE
DIAMETER
DIMENSION
DOWN
DOOR
DETAIL
DRAWING(S)
EAST
EACH
EXPANSION JOINT
ELECTRIC(AL)
ELEVATION OR ELEVATOR
ENGINEER(ING)
EDGE OF CURB
EDGE OF PAVEMENT
ETHYLENE PROPYLENE DIENE TERPOLYMER
EQUAL
EQUIPMENT
EACH SIDE
EXPOSED TO STRUCTURE
EXISTING
EXPANSION
EXTERIOR
FIRE ALARM
FLOOR DRAIN
FIRE EXTINGUISHER (CABINET)
FACTORY FINISH
FINISH FLOOR BREAK
FINISH FLOOR LINE
FINISH(ED)
FLASHING
FLOOR(ING)
FLORESCENT
FOUNDATION
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIRE PROOF
FIRE RATED
FRAME
FOOT, FEET
FOOTING
FURRING
FURNISHED
GAGE, GAUGE
GALVANIZED
GENERAL ELECTRIC
GYPSUM (WALL) BOARD
GENERAL CONTRACTOR
GRID LINE
GLUE LAMINATED BEAM
GLASS MASONRY UNIT
GOVERNMENT
GYPSUM BOARD
A101
1 TYP
101.1
A-101
SIM
EXTERIOR ELEVATION
INTERIOR ELEVATION
BUILDING SECTION FLAG
WALL SECTION FLAG
CALLOUT FLAG
VERTICAL GRID LINE
HORIZONTAL GRID LINE
TRUE NORTH ARROW
PROJECT NORTH ARROW
(TRUE NORTH DASHED)
ELEVATION MARKER
KEY NOTE
ROOM TAG (SF OPTIONAL)
CEILING HEIGHT TAG
ROOM NAME
150 SF
A
A-101
SIM
01A
TRUE
NORTH
W1
A-101
NORTH
WALL TAG
FLOOR TAG
ROOF TAG
DOOR TAG
WINDOW TAG
SPECIALTY EQUIPMENT TAG
SIGNAGE TAG
SIGNAGE KEY NOTE
(AW SHEETS ONLY)
SIGNAGE MATERIAL TAG
(AW SHEETS ONLY)
EXISTING TO REMAIN
NEW CONSTRUCTION
TO DEMOLISH
HIDDEN ABOVE OR BELOW
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
SMOKE ZONE
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 1 HR FIRE RATED WALL
FIRE EXTINGUISHER CABINET
AREA OF WORK / AREA SHOWN
CONSTRUCTION ZONE, ( - - )
PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
PATH OF TRAVEL
EMERGENCY EGRESS PATHWAY
SEISMIC JOINT
BATT INSULATION
RIGID INSULATION
GYPSUM BOARD, TYPE X
ACOUSTICAL CEILING TILE, 2' x 2'
CONCRETE
STEEL
PLYWOOD, FIRE RATED
EARTH
SUPPLY GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
RETURN GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
LIGHTING PER ELECTRICAL
(SIZE & PROPORTIONS MAY VARY)
A-101
A01
D88
A5175SOAP DISH
IN-04.02-01
AFF
GYP ON MTL STUD
9' - 0"
FEC
F-1
R-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES G-003
ARCHITECTURAL SYMBOLS &
ABBREVIATIONS 4
MK AK
CONSTRUCTION
DOCUMENTS
07/20/2022
SYMBOLS ABBREVIATIONS
GENERAL NOTES
APPLICABLE PUBLICATIONS
1. ALL WORK DONE BY THE CONTRACTOR OR SUB-CONTRACTORS SHALL BE PERFORMED WITH
A HIGH LEVEL OF WORKMANSHIP.
2. MAINTAIN A SAFE, CLEAN CONSTRUCTION ZONE AT ALL TIMES.
3. DO NOT SCALE DRAWINGS.
4. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL
INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS
INDICATED.
5. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT
ENCROACHMENTS.
6. FURNISH ALL MATERIALS & PRODUCTS TO COMPLY WITH THE CONTRACT DOCUMENTS.
7. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH FLOOR ELEVATION, UON.
8. ANY AND ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN WALL BEHIND, THIS
INCLUDES BACKING FOR WALL MOUNTED DOOR STOPS. ENSURE THAT ALL REQUIRED
BACKING IS INSTALLED IN WALLS PRIOR TO INSTALLING DRYWALL.
9. IN TOILET ROOMS PROVIDE STAINLESS STEEL FILLER BEHIND ANY MIRRORS AND OTHER
WALL MOUNTED ACCESSORIES WHEN ITEM IS INSTALLED PARTIALLY OVER CERAMIC TILE.
APPLICABLE PUBLICATIONS ARCHITECTURAL NOTES
AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS
OF CODE ENFOREMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS,
FEES, ETC). THE VA SHALL FUNCTION AS THE AUTHORITY HAVING JURISTICTION (AHJ).
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD
APPLICATION GUIDE AND OTHER GUIDEANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL).
INTERNATIONAL BUILDING CODE (IBC) 2018.
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.
NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES
PRECEDENCE OVER IBC.
NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
NATIONAL ELECTRICAL CODE (NEC).
INTERNATIONAL PLUMBING CODE (IPC).
SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAL SOCIETY OF MECHANICAL
ENGINEERS (ASME) A 17.1.
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA SUPPLEMENT
BARRIER FREE DESIGN GUIDE (PG-18-3)
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUE
AND COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRCUTION , LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL
AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RESE RESIDENTIAL
BUILDINGS, 10 CFR PARTS 433,434 AND 435.
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF
UNDERSTANDING (MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY AND
TRANSPORTATON MANAGEMENT.
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL
REQUIREMENTS SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2004.
SAFETY STANDARD FOR REFRIDERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.
VAMC APPROVED HARDWARE LOCKING STANDARDS
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)
FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND
STANDARDS FOR TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS AND
INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI)
JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),
ENVIRONMENT OF CARE GUIDELINES AND STANDARDS
FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR THE
DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES
THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL
ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS ENCOURAGING
“ENVIRONMENTALLY RESPONSIBLE DESIGN”
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
CONTRACTOR PATH OF TRAVEL
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
1 TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. USE STARC BARRIER SYSTEM WHERE POSSIBLE.
OTHERWISE, CONSTRUCT WITH MTL STUDS AND 5/8" TYPE
X GYP EACH SIDE AND PER REQUIREMENTS IN THE
INFECTION CONTROL SECTION OF SPECIFICATION
01 35 26 - SAFETY REQUIREMENTS.
TEMPORARY ICRA DOOR AND FRAME COMPLYING WITH
REQUIREMENTS IN THE INFECTION CONTROL SECTION OF
SPECIFICATION 01 35 26 - SAFETY REQUIREMENTS.
ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
ELECTRICAL
STORAGE
STORAGE
1013STORAGE
STORAGE
TELPHONE
STEAM
1019A
STORAGE
MAILROOM
COPY ROOM
1016A
UNIFORMS
ELEC
1014A
OFFICE
1012A
PATIENT LIBRARY
DAV COUNCIL
1010C
DVA
1010B TEXAS VET COMM
1010A
TRAINING
1008B
EMS OFFICE
STORAGE
1008A
KITCHEN
EMS EQUIPMENT
STORAGE
1009B
STORAGE
1009A POLICE STORAGE
STORAGE
1005A
STORAGE
1005B
CANTEEN
STORAGE
1005D
MECHANICAL
DRUG CACHE
RESTROOM
RESTROOM
RECEIVING
OFFICE
1021B
STORAGE
1009C
CORRIDOR
STORAGE
1005C
ELEV 1
STORAGE
1000D
WAITING
CORRIDOR
ELEVATOR
MACHINE
ELEV 2
ICRA CLASS IV REQUIREMENTS ICRA CLASS IV REQUIREMENTS
GROUND FLOOR ACCESS
FIRST FLOOR ACCESS
UPPER LEVEL /
ROOF ACCESS
SHOWN AREA
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS101
BUILDING 4 - FIRST FLOOR - ICRA
PLAN 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/8" = 1'-0"
BUILDING 4 - FIRST FLOOR - ICRA PLAN
CLASS IV ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIRE FILTRATION UNITS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTE ROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE, OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME
THEY LEAVE THE WORK SITE.
6. ALL PERSONNEL ENTERING THE WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME
THE WORKER EXITS THE WORK AREA.
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES DEPARTMENT.
UPON COMPLETION OF THE PROJECT:
1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
5. WET MOP AREA WITH DISINFECTANT.
6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
ROTATED FROM KEY PLAN
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
KITCHEN
POT WASH
CENTER
SOILED
CAR WASH
CLEAN
PATIENT CENTER
TRAY SERVICE
CART STORAGE
105ELEV 2
COOK'S COOLER
FOOD STORAGE
CONFERENCE
SECRETARY /
WAITING
CLINICAL
DIETITIANS
CLINICAL
DIETITIANS
SECTION CHIEF
NUTRITION
TECHNICIANS /
CLERKS
CONFERENCE
SUPERVISORS
NON-FOOD
STORAGE
C.E.F.
HAC
CORRIDOR
SANITATION
SUPPLY
CHIEF
CHIEF PROGRAM
MANAGEMENT
CORRIDOR
STAFF LOCKERS
TOILET
TOILET
CORRIDOR
CORRIDOR
NOURISHMENT
PREP
ICRA CLASS IV REQUIREMENTS ICRA CLASS IV REQUIREMENTS
SEE BUILDING 4 - GROUND FLOOR -
ICRA PLAN FOR CONTINUATION
ELEV 1
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
CONTRACTOR PATH OF TRAVEL
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
1 TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. USE STARC BARRIER SYSTEM WHERE POSSIBLE.
OTHERWISE, CONSTRUCT WITH MTL STUDS AND 5/8" TYPE
X GYP EACH SIDE AND PER REQUIREMENTS IN THE
INFECTION CONTROL SECTION OF SPECIFICATION
01 35 26 - SAFETY REQUIREMENTS.
TEMPORARY ICRA DOOR AND FRAME COMPLYING WITH
REQUIREMENTS IN THE INFECTION CONTROL SECTION OF
SPECIFICATION 01 35 26 - SAFETY REQUIREMENTS.
ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
SHOWN AREA
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS102
BUILDING 4 - SECOND FLOOR -
ICRA PLAN 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
1/8" = 1'-0"
BUILDING 4 - SECOND FLOOR - ICRA PLAN
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
CLASS IV ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS I.E. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR
VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIRE FILTRATION UNITS.
4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTE ROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE, OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME
THEY LEAVE THE WORK SITE.
6. ALL PERSONNEL ENTERING THE WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME
THE WORKER EXITS THE WORK AREA.
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL DEPARTMENT AND THOROUGHLY CLEANED BY THE OWNER'S ENVIRONMENTAL SERVICES DEPARTMENT.
UPON COMPLETION OF THE PROJECT:
1. REMOVE BARRIER MATERIAL CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.
3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.
4. VACUUM WORK AREA WITH HEPA FILTERED VACUUMS.
5. WET MOP AREA WITH DISINFECTANT.
6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
NORTH
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
ELEVATOR 1
MACHINE ROOM
SEE BUILDING 4 - GROUND FLOOR -
ICRA PLAN FOR CONTINUATION
CONSTRUCTION ZONE, ( - - ) PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
CONTRACTOR PATH OF TRAVEL
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
SHOWN AREA
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS103
BUILDING 4 - UPPER LEVEL / ROOF
- ICRA PLAN 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
1/8" = 1'-0"
BUILDING 4 - UPPER LEVEL / ROOF - ICRA PLAN
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
CLASS II ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM
DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE
CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
UPON COMPLETION OF PROJECT:
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3. WET MOP AND/OR VACUUM WITH HEPA
FILTERED VACUUM BEFORE LEAVING WORK
AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED.
Revisions: Date:
ROTATED FROM KEY PLAN
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
CONTRACTOR PATH OF TRAVEL
1 HOUR FIRE RATED WALL
TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. USE STARC BARRIER SYSTEM WHERE POSSIBLE.
OTHERWISE, CONSTRUCT WITH MTL STUDS AND 5/8" TYPE
X GYP EACH SIDE AND PER REQUIREMENTS IN THE
INFECTION CONTROL SECTION OF SPECIFICATION
01 35 26 - SAFETY REQUIREMENTS.
TEMPORARY ICRA DOOR AND FRAME COMPLYING WITH
REQUIREMENTS IN THE INFECTION CONTROL SECTION OF
SPECIFICATION 01 35 26 - SAFETY REQUIREMENTS.
ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
SHOWN AREA
NORTH
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
STORAGE
MECHANICAL
4A
ELECTRICAL
OFFICE
2A
OFFICE
MECHANICAL
B03A
B08
STORAGE
OFFICE
OFFICE
STORAGE
ELEVATOR 1
3PARTIALLY
EXCAVATED
PARTIALLY
EXCAVATED
PARTIALLY
EXCAVATED
BUILDING ACCESS
(ALL LEVELS)
CONTINUE TO
LEVELS ABOVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS104
BUILDING 7 - LEVEL B - ICRA PLAN
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/4" = 1'-0"
BUILDING 7 - LEVEL B - ICRA PLAN
CLASS II ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM
DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE
CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
UPON COMPLETION OF PROJECT:
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3. WET MOP AND/OR VACUUM WITH HEPA
FILTERED VACUUM BEFORE LEAVING WORK
AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED.
TEMPORARY ICRA DOOR
CONTRACTOR PATH OF TRAVEL
1 HOUR FIRE RATED WALL
TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. USE STARC BARRIER SYSTEM WHERE POSSIBLE.
OTHERWISE, CONSTRUCT WITH MTL STUDS AND 5/8" TYPE
X GYP EACH SIDE AND PER REQUIREMENTS IN THE
INFECTION CONTROL SECTION OF SPECIFICATION
01 35 26 - SAFETY REQUIREMENTS.
TEMPORARY ICRA DOOR AND FRAME COMPLYING WITH
REQUIREMENTS IN THE INFECTION CONTROL SECTION OF
SPECIFICATION 01 35 26 - SAFETY REQUIREMENTS.
ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
SHOWN AREA
NORTH
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
OFFICE
106B OFFICE
VISTA TEAM
106A
OFFICE
OFFICE
B03F
OFFICE
WORKSPACE
106A /
OFFICE
OFFICE
111A
OFFICE
111B
ISO OFFICE
HALL
RESTROOM
MECHANICAL
110A
HAC
ELEVATOR 1
SEE BUILDING 7 -
LEVEL B ICRA
PLAN FOR
CONTINUATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS105
BUILDING 7 - LEVEL 1 - ICRA PLAN
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN1/4" = 1'-0"
BUILDING 7 - LEVEL 1 - ICRA PLAN NORTH
CLASS II ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM
DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE
CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
UPON COMPLETION OF PROJECT:
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3. WET MOP AND/OR VACUUM WITH HEPA
FILTERED VACUUM BEFORE LEAVING WORK
AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED.
TEMPORARY ICRA DOOR
CONTRACTOR PATH OF TRAVEL
1 HOUR FIRE RATED WALL
TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. USE STARC BARRIER SYSTEM WHERE POSSIBLE.
OTHERWISE, CONSTRUCT WITH MTL STUDS AND 5/8" TYPE
X GYP EACH SIDE AND PER REQUIREMENTS IN THE
INFECTION CONTROL SECTION OF SPECIFICATION
01 35 26 - SAFETY REQUIREMENTS.
TEMPORARY ICRA DOOR AND FRAME COMPLYING WITH
REQUIREMENTS IN THE INFECTION CONTROL SECTION OF
SPECIFICATION 01 35 26 - SAFETY REQUIREMENTS.
ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
SHOWN AREA
NORTH
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
CHIEF
SECRETARY
ISC
203 PROGRAM
COMPUTER
ROOM
RESTROOM
MECHANICAL
207A
HAC
HALL
PRIVATE ROOM
208A
ELEVATOR 1
SEE BUILDING 7 -
LEVEL B ICRA
PLAN FOR
CONTINUATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS106
BUILDING 7 - LEVEL 2 - ICRA PLAN
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
1/4" = 1'-0"
BUILDING 7 - LEVEL 2 - ICRA PLAN
NORTH
CLASS II ICRA REQUIREMENTS
DURING CONSTRUCTION PROJECT:
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM
DISPERSING INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE
CUTTING.
3. SEAL UNUSED DOORS WITH DUCT TAPE.
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
UPON COMPLETION OF PROJECT:
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE
TRANSPORT IN TIGHTLY COVERED
CONTAINERS.
3. WET MOP AND/OR VACUUM WITH HEPA
FILTERED VACUUM BEFORE LEAVING WORK
AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN
AREAS WHERE WORK IS BEING PERFORMED.
SHOWN AREA
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
ELECTRICAL
STORAGE
STORAGE
1013STORAGE
STORAGE
TELPHONE
STEAM
1019A
STORAGE
MAILROOM
COPY ROOM
1016A
UNIFORMS
ELEC
1014A
OFFICE
1012A
PATIENT LIBRARY
DAV COUNCIL
1010C
DVA
1010B TEXAS VET COMM
1010A
TRAINING
1008B
EMS OFFICE
STORAGE
1008A
KITCHEN
EMS EQUIPMENT
STORAGE
1009B
STORAGE
1009A POLICE STORAGE
STORAGE
1005A
STORAGE
1005B
CANTEEN
STORAGE
1005D
MECHANICAL
DRUG CACHE
RESTROOM
RESTROOM
RECEIVING
OFFICE
1021B
STORAGE
1009C
CORRIDOR
STORAGE
1005C
ELEV 1
STORAGE
1000D
WAITING
CORRIDOR
ELEVATOR
MACHINE
ELEV 2
MAX ALLOWABLE 300' - 0"
PROVIDED 92' - 7"
MAX ALLOWABLE 300' - 0"
PROVIDED 98' - 1"
3 3
14' - 3" TO POINT OF TWO EGRESS OPTIONS
1. NFPA BUILDING CONSTRUCTION: EXISTING
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS.
3. # OF REQ'D EGRESS OPENINGS: 2.
4. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS201
BUILDING 4 - FIRST FLOOR - FIRE
AND LIFE SAFETY 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/8" = 1'-0"
BUILDING 4 - GROUND FLOOR - FIRE & LIFE SAFETY PLAN
EGRESS START POINT
POINT OF TWO EGRESS OPTIONS
EGRESS END POINT
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
1. NFPA BUILDING CONSTRUCTION: EXISTING
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS.
3. # OF REQ'D EGRESS OPENINGS: 2.
4. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS.
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
MAX ALLOWABLE 300' - 0"
PROVIDED 110' - 2"
M A
X A
L L O
W A
B L E
P R
O V
ID
E
D
22' - 6" TO POINT OF
TWO EGRESS OPTIONS
KITCHEN
POT WASH
CENTER
SOILED
CAR WASH
CLEAN
PATIENT CENTER
TRAY SERVICE
CART STORAGE
ELEV 2
COOK'S COOLER
FOOD STORAGE
CONFERENCE
SECRETARY /
WAITING
CLINICAL
DIETITIANS
CLINICAL
DIETITIANS
SECTION CHIEF
NUTRITION
TECHNICIANS /
CLERKS
CONFERENCE
SUPERVISORS
NON-FOOD
STORAGE
C.E.F.
HAC
CORRIDOR
SANITATION
SUPPLY
CHIEF
CHIEF PROGRAM
MANAGEMENT
CORRIDOR
STAFF LOCKERS
TOILET
TOILET
CORRIDOR
CORRIDOR
NOURISHMENT
PREP
ELEV 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS202
BUILDING 4 - SECOND FLOOR -
FIRE AND LIFE SAFETY 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/8" = 1'-0"
BUILDING 4 - SECOND FLOOR - FIRE & LIFE SAFETY PLAN
EGRESS START POINT
POINT OF TWO EGRESS OPTIONS
EGRESS END POINT
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
2 HR FIRE RATED WALL
SMOKE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
1. NFPA BUILDING CONSTRUCTION: EXISTING
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS.
3. # OF REQ'D EGRESS OPENINGS: 2.
4. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS.
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
M A
X A
L L O
W A
B L E
P R
O V
ID
E
D
ELEVATOR 1
MACHINE ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS203
BUILDING 4 - UPPER LEVEL / ROOF
- FIRE AND LIFE SAFETY 4
MK MC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/8" = 1'-0"
BUILDING 4 - UPPER LEVEL / ROOF - FIRE & LIFE SAFETY PLAN
EGRESS START POINT
EGRESS END POINT
ROOF ACCESS HATCH
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
1. NFPA BUILDING CONSTRUCTION: TYPE IIA
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS
3. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
STORAGE
MECHANICAL
4A
STORAGE
OFFICE
STORAGE
OFFICE
ELECTRICAL
B08
OFFICE
2A
MECHANICAL
B03A
ELEVATOR 1
OFFICE
MAX ALLOWABLE 125' - 0"
PROVIDED 50' - 0"
10'-6" TO POINT OF TWO
EGRESS OPTIONS
EXIT
MAX ALLOWABLE 125' - 0"
PROVIDED 20' - 7"
EXIT STAIR
PARTIALLY
EXCAVATED
PARTIALLY
EXCAVATED
PARTIALLY
EXCAVATED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS204
BUILDING 7 - LEVEL B - FIRE AND
LIFE SAFETY PLAN 7
MK EC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
1/4" = 1'-0"
BUILDING 7 - LEVEL B - FIRE & LIFE SAFETY PLAN
NORTH
EGRESS START POINT
POINT OF TWO EGRESS OPTIONS
EGRESS END POINT
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
1. NFPA BUILDING CONSTRUCTION: TYPE IIA
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS
3. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
OFFICE
106B OFFICE
VISTA TEAM
106A
OFFICE
OFFICE
B03F
OFFICE
WORKSPACE
106A /
OFFICE
OFFICE
111A
OFFICE
111B
ISO OFFICE
HALL
RESTROOM
MECHANICAL
110A
HAC
ELEVATOR 1
MAX ALLOWABLE 125' - 0"
PROVIDED 27' - 2"
EXIT STAIR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS205
BUILDING 7 - LEVEL 1 - FIRE AND
LIFE SAFETY PLAN 7
MK EC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
NORTH
1/4" = 1'-0"
BUILDING 7 - LEVEL 1 - FIRE & LIFE SAFTY PLAN
EGRESS START POINT
POINT OF TWO EGRESS OPTIONS
EGRESS END POINT
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
1. NFPA BUILDING CONSTRUCTION: TYPE IIA
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS
3. SEE ELECTRICAL FOR EXIT SIGNAGE LOCATIONS &
REQUIREMENTS
E
F
F
G
G
H
H
A
A
B
B
C
C D
C.1 D.1
CHIEF
SECRETARY
ISC
203 PROGRAM
COMPUTER
ROOM
RESTROOM
MECHANICAL
207A
HAC
HALL
PRIVATE ROOM
208A
ELEVATOR 1
MAX ALLOWABLE 125' - 0"
PROVIDED 32' - 2"
EXIT STAIR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AS206
BUILDING 7 - LEVEL 2 - FIRE AND
LIFE SAFETY PLAN 7
MK EC
CONSTRUCTION
DOCUMENTS
07/20/2022
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
1/4" = 1'-0"
BUILDING 7 - LEVEL 2 - FIRE & LIFE SAFETY PLAN
NORTH
EGRESS START POINT
POINT OF TWO EGRESS OPTIONS
EGRESS END POINT
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
ELECTRICAL
STORAGE
STORAGE
1013STORAGE
STORAGE
TELPHONE
STEAM
1019A
STORAGE
MAILROOM
COPY ROOM
1016A
UNIFORMS
ELEC
1014A
OFFICE
1012A
PATIENT LIBRARY
DAV COUNCIL
1010C
DVA
1010B TEXAS VET COMM
1010A
TRAINING
1008B
EMS OFFICE
STORAGE
1008A
KITCHEN
EMS EQUIPMENT
STORAGE
1009B
STORAGE
1009A POLICE STORAGE
STORAGE
1005A
STORAGE
1005B
CANTEEN
STORAGE
1005D
MECHANICAL
DRUG CACHE
RESTROOM
RESTROOM
RECEIVING
OFFICE
1021B
STORAGE
1009C
Room
STORAGE
1005C
ELEV 1
STORAGE
1000D
WAITING
CORRIDOR
ELEVATOR
MACHINE
ELEV 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
UPGRADE FREIGHT ELEVATORS
BLDG 4 + 7
THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM
6010 W AMARILLO BLVD, AMARILLO, TX
504-22-102
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES AD101
BUILDING 4 - FIRST FLOOR - DEMO
PLAN 4
MK RR
CONSTRUCTION
DOCUMENTS
07/20/2022
NORTH
1/8" = 1'-0"
OVERALL FIRST FLOOR DEMO PLAN
DEMO DOOR. DOOR FRAMES TO REMAIN.
DEMO EXISTING ELEVATOR CAB AND RELATED
EQUIPMENT, SEE SPEC SECTION 14 24 10
DEMO DOOR AND FRAME, TO BE REPLACED WITH NEW.
SEE ELECTRICAL DRAWINGS FOR EQUIPMENT
DEMOLITION.
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
Revisions: Date:
NOTE: BUILDING 4 TO BE DONE IN 2 PHASES IN ORDER TO KEEP ONE ELEVATOR OPERATIONAL AT ALL TIMES.
E F
G H J K L M N O
6.1
5.1
4.1
3.1
A B C D
KITCHEN
POT WASH
CENTER
SOILED
CAR WASH
CLEAN
PATIENT CENTER
TRAY SERVICE
CART STORAGE
ELEV 2
COOK'S COOLER
FOOD STORAGE
CONFERENCE
SECRETARY /
WAITING
CLINICAL
DIETITIANS
CLINICAL
DIETITIANS
SECTION CHIEF
NUTRITION
TECHNICIANS /
CLERKS
CONFERENCE
SUPERVISORS
NON-FOOD
STORAGE
C.E.F.
Room
CORRIDOR
SANITATION
SUPPLY
CHIEF
CHIEF PROGRAM
MANAGEMENT
CORRIDOR
STAFF LOCKERS
TOILET
TOILET
CORRIDOR
CORRIDOR
NOURISHMENT
PREP
ELEV 1
TO DEMOLISH
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
G H
(E) CEILING @ 7'-6 5/8" AFF
ELEVATOR 1
MACHINE ROOM
11' - 6"
2' - 5 1/4"
3' - 9 1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date…