This solicitation is for electrical upgrades to freight elevators in Buildings 4 and 7 at a Veterans Affairs medical center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17 is seeking proposals to replace the keying system for Project 671-22-196. Offerors should respond by the deadline of November 15, 2022, as indicated in the signed PDF file titled 504-22-102_ELECTRICAL_CD_Signed_11.15.22. Upgrades are needed for freight elevators in two buildings, and the project involves replacing the keying system. The solicitation number is 36C25723B0003 and is titled J056--504-22-102 Upgrade Freight Elevators Buildings 4 & 7.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S H E E T I N D E XG E N E R A L N O T E SA B B R E V I A T I O N S

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFCI ARC-FAULT CURRENT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

Ah AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

C/B CIRCUIT BREAKER

CL CONNECTOR LIGHTING

CLF CURRENT LIMITING FUSE

CLG CEILING

CO CONDUIT ONLY

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

Cu COPPER

CUR CURRENT

dB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DDC DIRECT DIGITAL CONTROLS

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DP DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EL ELEVATION OR EXISTING TO BE RELOCATED

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER/EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

EN EXISTING IN NEW LOCATION

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ER EXISTING TO REMAIN

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST(E) EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCIO FURNISHED BY CONTRACTOR,

INSTALLED BY OWNER

FOIC FURNISHED BY OWNER,

INSTALLED BY CONTRACTOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT

CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IG ISOLATED GROUND

IESNA ILLUMINATION ENGINEERING

SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MS MOTOR STARTER

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CABINET

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT, N NEUTRAL

NFC NOT FOR CONSTRUCTION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

OS OCCUPANCY SENSOR

P POLE

PB PULL BOX

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PIV POST INDICATOR VALVE

PF POWER FACTOR

PH PHASE

PNL PANEL

PS POWER SUPPLY

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

R EXISTING TO BE REMOVED

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RM ROOM

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

REQD REQUIRED

SAC SMALL APPLIANCE CIRCUIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SM SMART METER

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD OR SB SWITCHBOARD

SWGR OR SG SWITCHGEAR

TEL TELEPHONE

TR TAMPER RESISTANT

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT/WEATHERPROOF

(WHILE IN USE)

WH WATER HEATER

WP/W WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.

2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.

3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED OR MODIFIED UNLESS OTHERWISE NOTED.

4. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.

5. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY THE CONTRACTOR AND APPROVED BY THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO BE

ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.

6. PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.

7. LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.

8. WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. CONDUCTOR SIZE SHALL BE INCREASED TO COMPENSATE FOR DERATING REQUIRED PER NEC 310.15 WHERE MORE THAN THREE CURRENT CARRYING CONDUCTORS WITHIN ONE RACEWAY; CONDUCTOR AMPACITIES SHALL BE TAKEN FROM THE 75°C COLUMN. INDIVIDUAL CIRCUITS SHALL NOT SHARE

NEUTRAL CONDUCTORS.

9. MINIMUM CONDUIT SIZE SHALL BE 1” FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4” FOR INTERIOR CONDUIT. ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINAIRES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS OTHERWISE NOTED ON THE DRAWINGS.

10. EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.

11. PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES

FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS REQUIRED.

12. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO COMMENCING WORK.

13. COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF THE SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE LIGHTING CONTROL SYSTEM SHALL BE PROVIDED

TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.

14. ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS. ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER MOUNTING SURFACE TO ALL EQUIPMENT; RECEPTACLES SHALL BE INSTALLED FLUSH.

15. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES LOCATED IN

FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.

16. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.

17. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND INSTALLATION LOCATIONS PRIOR

TO INSTALLATION.

18. ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE LOCATION WITHOUT CONDUIT.

19. GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6’ OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED OUTDOORS/EXTERIOR TO THE BUILDING.

20. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.

21. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.

22. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S) CONTROLLED BY A SECOND SWITCH.

23. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON Cu COPPER PER NEC TABLE 310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS.

24. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

25. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY

FROM THE ABANDONED CONDUITS.

26. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED WIRING.

27. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

E-001 - ABBREVIATIONS, GENERAL NOTES, AND SHEET

INDEX

E-002 - ELECTRICAL LEGENDS

EP101 - BUILDING 4 - LEVEL 0 - ELECTRICAL PLAN

EP102 - BUILDING 4 - LEVEL 1 - ELECTRICAL PLAN

EP103 - BUILDING 4 - LEVEL 2 - ELECTRICAL PLAN

EP104 - BUILDING 7 - LEVEL B - ELECTRICAL PLAN

EP105 - BUILDING 7 - LEVEL 1 - ELECTRICAL PLAN

EP106 - BUILDING 7 - LEVEL 2 - ELECTRICAL PLAN

EP401 - BUILDING 4 - ENLARGED ELECTRICAL PLANS

EP402 - BUILDING 4 - ENLARGED ELECTRICAL PLANS

EP403 - BUILDING 7 - ENLARGED ELECTRICAL PLANS

E-601 - BUILDING 4 - ONE-LINE DIAGRAM

E-602 - BUILDING 7 - ONE LINE DIAGRAM

E-603 - ELECTRICAL SCHEDULES

E-604 - BUILDING 4 - ELECTRICAL LOAD SCHEDULES

E-605 - BUILDING 7 - ELECTRICAL LOAD SCHEDULES

28. PRIOR TO EQUIPMENT PROCUREMENT, CONTRACTOR SHALL PROVIDE DETAILED AND DIMENSIONED SHOP DRAWINGS INDICATING PROPOSED ELECTRICAL DISTRIBUTION EQUIPMENT LAYOUT FOR ALL ELECTRICAL EQUIPMENT INSTALLATIONS DURING THE SUBMITTAL PROCESS FOR VA AND ENGINEER REVIEW AND APPROVAL.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

E-001

ABBREVIATIONS, GENERAL NOTES,

AND SHEET INDEX

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

11/15/2022

SECTION A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

A

XXX

SECTION LETTER

SHEET WHERE

SECTION IS TAKEN

FROM

XXX

DETAIL NUMBER

SHEET ON WHICH

DETAIL APPEARS

DETAIL AREA

SCALE

XXXNG

CONDUIT & WIRE TAG

(REFER TO CONDUIT

AND WIRE SCHEDULE)

XX FAULT CURRENT TAG

(3 PH, SYM AMPS)

1 KEY NOTE

XXX

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW

DENOTES DIRECTION

TAKEN

SHEET WHERE DETAIL

IS TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

G E N E R A L S Y M B O L

D I V 2 6 - L E G E N D D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D

G

PE

DS

X

X

X

ALL INTERIOR AREAS TO HAVE MANUAL 0N/AUTO OFF LIGHTING

CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY

SENSORS.

EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR IS NOTED.

PHOTO ELECTRIC SENSOR

DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING

CONTROL. SENSOR SHALL BE CEILING MOUNTED.

SWITCH, MULTIPOSITION

SWITCH, SINGLE BREAK

FUSE WITH RATING

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

CIRCUIT BREAKER

DRAWOUT AIR CIRCUIT BREAKER

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

DELTA CONNECTION

TRANSFORMER

WYE CONNECTION

EARTH GROUND

JUNCTION BOX

PULL BOX

GENERATOR, POWER

BATTERY

CAPACITOR

RELAY; NUMBER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE

51 = AC-TIME OVER CURRENT

67 = AC-DIRECTIONAL OVER CURRENT

86 = LOCKING OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

METER

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

JUNCTION BOX

TRANSFORMER, PLAN

MOTOR

WYE CONNECTION

EARTH GROUND

LADDER CABLE TRAY

PULL BOX

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE, QUADRUPLEX

RECEPTACLE

SINGLE

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

RECEPTACLE, SWITCHED DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]

CENTERS OR AS DESIGNATED ON DRAWINGS), MTD

3'-6" [1067mm] AFF OR AS INDICATED.

SWITCH

F = FUSED SWITCH K = KEY OPERATED

L = LOCK LM= LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT

MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT

(THERMAL TYPE)

PB= PUSH BUTTON STATION RC= REMOTE CONTROL

WP= WEATHER PROOF X = EXPLOSION PROOF

SWITCH, CEILING MOUNTED PULL

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DIMMER K = KEY OPERATED

LV= LOW VOLTAGE P = WITH PILOT LIGHT

LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL

PB= PUSH BUTTON STATION WP= WEATHER PROOF

T = TIMER OPERATED Mo= OCCUPANCY SENSOR

RECESSED DOWNLIGHT FIXTURE, LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED, 2'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED, 1'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED,1'x8'; LETTER INDICATES

TYPE.

LIGHT FIXTURE, SURFACE MOUNTED,2'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED, 1'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED,(1'x8');

LETTER INDICATES TYPE.

LIGHT FIXTURE,

EMERGENCY;

LETTER INDICATES

TYPE.

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

STREET LIGHT WITH BRACKET

LIGHT POLE, ONE LUMINAIRE

LIGHT POLE, TWO LUMINAIRES

LIGHT POLE, POST TOP MOUNT LUMINAIRE

LIGHTING WALL PACK, EXTERIOR BUILDING

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH

DIRECTIONAL ARROWS AND FACES AS SHOWN

LIGHT FIXTURE, RECESSED,2'x2'; LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED, 2'x2';

LETTER INDICATES TYPE.

LIGHT TRACK WITH HEADS AS SHOWN

STRIP LIGHTING, 4' LONG

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE, BOLLARD

OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT

FIBEROPTICS LINE = FO

FLOOR RECEPTACLE, TELEPHONE

OUTLET TELEPHONE; LETTER INDICATES ASFOLLOWS:

J = JACK TYPE W = WALL TYPE

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON

LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE

ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.

OUTLET DATA ONLY

TELEPHONE LINE = T

INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.

SOUND LINE = S

NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM

RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE

NOTED.

SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.

OUTLET, TELEVISION

BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK

COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF

M = MONITOR (CTTV SYSTEM).

NURSE'S CALL MASTER STATION MTD ON

NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS AT MASTER

STATION) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.

D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED OTHERWISE.

E = MTD 6'-0" [1829mm] AFF FOR SHOWER LOCATION, MTD 4'-6" [1372mm] AFF FOR

TUB LOCATION, & MTD 3'-0" [914mm] AFF FOR TOILET LOCATION.

P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" [1524mm] AFF UNLESS

OTHERWISE NOTED.

U = UTILITY CALL STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.

NURSE CALL STATION.

2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF

LAMP) MTD 6" [152mm] ABOVE DOOR.

D = CORRIDOR DOME LIGHT.

I = AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm] AFF.

REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED).

INTERCOM STAFF STATION.

TELECOMMUNICATIONS MANHOLE

POWER

LIGHTING

DATA/COMMUNICATION

x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER

BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

I-INFRARED M-MICROWAVE

F=FUNCTION

RX-RECEIVE TX-TRANSMIT

BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS

R-EYE RETINA V-VOICE

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALLCALL

M-MAG STRIP P-PROXIMITY S-SMART CARD

T-TOKEN

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH

H-HIDDEN M-MULLIONP-PEDESTAL R-RACK

S-SURFACE W-WALLCENTRAL PROCESSING UNIT

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE

EXIT DEVICE; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY

FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

R-RECEIVERT-TRANSCEIVER TX-TRANSMITTER

FIELD PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-ALARM C-CARD READER

GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO S-SHOCK

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

KEYBOARD

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLIONP-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO D-DIGITAL V-VIDEO

SECURITY ACCESS, ANNUNCIATOR PANEL

SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF

UNLESS OTHERWISE NOTED

SECURITY ACCESS, CONTROL UNIT WITH

CLOSED CIRCUIT TELEVISION CAMERA

SECURITY ACCESS, GENERIC "X" INDICATES THE

TYPE, PROVIDE SCHEDULE OR LEGEND

SECURITY ACCESS, HORN OR SIREN

SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT

SECURITY ACCESS, PANIC ALARM

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM

SECURITY ACCESS, VOLUMETRIC SENSOR

SECURITY SCREEN WITH ALARM; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND S-SHADE

SECURITY WINDOW SCREEN; LETTER INDICATES ASFOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND

VIDEO CONTROL KEYBOARD

VIDEO MOTION DETECTOR

SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE

SECURITY ACCESS, SENSOR, BURIED VEHICULAR

SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL

SECURITY ACCESS, TELEPHONE HANDSET

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

ALARM, CHECK VALVE

ALARM, FIRE, COMMUNICATOR

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

FACC = CENTRAL CONSOLE FACP = CONTROL PANEL

MFACP= MASTER CONTROL PANELFAAP = ANNUNCIATOR PANEL

ALARM, FIRE, MANUAL PULL STATION

ALARM, GONG

ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME

ALARM, HORN/LIGHT, SEPARATE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

ALARM, MANUAL CONTROL

ALARM, MINI

HORN

ALARM, SPRINKLER SYSTEM WATER FLOW BELL

ALARM, TAMPER SWITCH

DETECTION, GAS

DETECTION, SMOKE CONTROL AND PRESSURE PANEL

DETECTION SWITCH, ABORT

DETECTION SWITCH, VALVE TAMPER

DETECTOR, FLAME FLICKER

DETECTOR, FLOW SWITCH

DETECTOR, HEAT

DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:

R/T = COMBINATION F = FIXED TEMPERATURE RISE

R/C = RATE COMPENSATION R = RATE OF

DETECTOR; LETTER INDICATES AS FOLLOWS:

BLANK = SMOKE DETECTOR

H = HEAT SMOKE

I = IONIZATION SMOKE

P = PHOTOELECTRIC SMOKE

IH = IONIZATION AND HEAT SMOKE

IP = IONIZATION AND PHOTOELECTRIC SMOKE

PH = PHOTOELECTRIC AND HEAT SMOKE

IPH = IONIZATION, PHOTOELECTRIC, AND HEAT

DETECTOR, SMOKE, FOR DUCT

DETECTOR, SWITCH LEVEL

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE

X-REQUEST-FOR-EXIT

CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"

AFF UNLESS OTHERWISE NOTED.

CODE ONE TERMINAL CABINET.

CODE ONE ANNUNCIATOR PANEL.

CODE ONE BEDSIDE STATION.

CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:

BATT =BATTERIESCHR = CHARGER FAR = RECORDER

ALARM, FIRE, VALVE SUPERVISORY SWITCH.

ALARM, FIRE, TERMINAL CABINET.

ALARM, FIRE, POST INDICATOR VALVE.

ALARM, TRANSPONDER OR TRANSMITTER

ALARM, VOICE COMMUNICATION PANEL

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM LINE = FA

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS

NOTED.

FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.

FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS DENOTE

CODE.

ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME

360°

40°

X

M PTZ

FAT

2-4-6

FAT

2-4-6

AP

NIP

NIT

NIA

NI

NID

FAC

FACP

P

C

BATT

OSY

FATC

PIV

M

TS

FTR

SCCP

HD

R/T

HD

H

FS

N

TTB

A

J

S X

S X

M

N

R M

C

DH

S

A

B

C

A

B

C

D

E

E

PB

T

PB

S

S

R

R M

NCS

NCT

S

WB

M

T

M

T

M

F

T

M

T

T

M

M

M

M

T

T

M

T

M

T

M

T

M

T

M

M

T

M

T

M

T

M

T

T

T

CP

EPO

CONDUIT OR EQUIPMENT TO BE REMOVED

CONDUIT HOME RUN 3/4"C, 2#12 & 1#12 GND. UNLESS SHOWN

OTHERWISE. (EXAMPLE SHOWN: TO PANEL P1, CIRCUIT 3)

CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE

CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN

FLOOR

SLAB, OR ROUTED UNDERGROUND

CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED

EXTRA-HARD USAGE FLEXIBLE CORD

FLEXIBLE CONDUIT

CONDUIT TURNED UP OR TOWARD

CONDUIT TURNED DOWN OR AWAY

CONDUIT CAPPED

XXXX

P1-3

OS

FA FA

CATV

CCTV

FO

T

I

S

NC

R

J

M

A

V

W

WH

J

P

A

J

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022 LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

11/15/2022

E-002

ELECTRICAL LEGENDS

SWITCHBOARD

NO. 2

EXISTING ELEVATOR FEED FROM

480V EMERGENCY PANEL "1-BC13EC"

IN BUILDING 1 TO BE REPLACED.

EXISTING FEED TO

PENTHOUSE MCC

ELV

E F

G H J K L M N O

A B C D

ELECTRICAL

STORAGE

STORAGE

STORAGE

STORAGE

TE

LP

H O

N E

STEAM

1019A

STORAGE

MAILROOM

COPY ROOM

1016A

UNIFORMS

ELEC

1014A

OFFICE

1012A

PATIENT LIBRARY

DAV COUNCIL

1010C

DVA

1010B

TEXAS VET COMM

1010A

TRAINING

1008B

EMS OFFICE

STORAGE

1008A

KITCHEN

EMS EQUIPMENT

STORAGE

1009B

STORAGE

1009A

POLICE STORAGE

STORAGE

1005A

STORAGE

1005B

CANTEEN

STORAGE

1005D

MECHANICAL

DRUG CACHE

RESTROOM

RESTROOM

RECEIVING

OFFICE

1021B STORAGE

1009C STORAGE

1005C

ELEV 1

STORAGE

1000D

WAITING

CORRIDOR

ELEVATOR

MACHINE

ELEV 2

EP401

EP402

EP402

EP401

SWITCHBOARD NO. 1

XFMR 4-T2

TS-9

TS-10

MTS #14-1

PANEL 4-12

XFMR-4T1

ELV3

TO ELEVATOR 2

CONTROL SWITCH

"ECS-B4-2"

4B11EL2

4EQ2-9,11

CU-2

4EQ2-6

CONTINUE TO FC-2,

REFERENCE SHEET EP402

180°

4-B10EC

360°

360°

KEY PLAN

GENERAL NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK,

PROMPTLY NOTIFY VA AND ENGINEER OF SAID

DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT

PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN

CIRCUITS IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (806.379.7700).

KEY NOTES

REPLACE ELEVATOR LOBBY CONTROLS. COORDINATE WITH

ELEVATOR CONTRACTOR AND VENDOR AS REQUIRED.

PANEL TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM

ON SHEET E-601 FOR ADDITIONAL INFORMATION.

PROVIDE RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE POE; PROVIDE ALL

POWER SUPPLIES AND/OR AMPLIFIERS AS REQUIRED FOR

A COMPLETE AND FULLY FUNCTIONAL SYSTEM. CAMERA

SHALL BE AXIS P3727-PLE.

EXISTING SWITHCHBOARD TO BE MODIFIED. REFERENCE

ONE-LINE DIAGRAM ON SHEET E-601 FOR ADDITIONAL

INFORMATION.

SCALE : 1/8" = 1'-0"

BUILDING 4 - LEVEL 0 - ELECTRICAL PLAN1

0 4' 8' 16'

PROJECT

NORTH

PROJECT

NORTH

AREA OF WORK

BLDG.4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP101

BUILDING 4 - LEVEL 0 - ELECTRICAL

PLAN

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

E F

G H J K L M N O

A B C D

8' -1

/6

4"

8' -0

KITCHEN

POT WASH

CENTER

SOILED

CAR WASH

CLEAN

PA

TI

EN

T

C

EN

TE

R

TR

A

Y

SE

R

VI

C E

CART STORAGE

ELEV 2

COOK'S COOLER

FOOD STORAGE

CONFERENCE

SECRETARY /

WAITING

CLINICAL

DIETITIANS

CLINICAL

DIETITIANS

SECTION CHIEF

NUTRITION

TECHNICIANS /

CLERKS

CONFERENCE

SUPERVISORS

NON-FOOD

STORAGE

C.E.F.

HAC

C O

R R

ID

O

R

SANITATION

SUPPLY

CHIEF

C H

IE

F

PR

O

G R

A M

M A

N A

G

EM

EN

T

CORRIDOR

STAFF LOCKERS

TOILET

TOILET

CORRIDOR

115CORRIDOR

NOURISHMENT

PREP

116 EP402

EP402

EP401

EP401

ELV

ELV

360°2

PTZM 1

SCALE : 1/8" = 1'-0"

BUILDING 4 - LEVEL 1 - ELECTRICAL PLAN1

0 4' 8' 16'

PROJECT

NORTH

PROJECT

NORTH

BLDG.4

AREA OF WORK

KEY PLAN

GENERAL NOTES

KEY NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF DISCREPANCIES

ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA

AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWING

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (PH:

806.379.7700).

REPLACE ELEVATOR LOBBY CONTROLS. COORDINATE WITH

ELEVATOR CONTRACTOR AND VENDOR AS REQUIRED.

PROVIDE RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE AXIS M5065(PTZ).

PROVIDED RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE AXIS P3727-PLE.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP102

BUILDING 4 - LEVEL 1 - ELECTRICAL

PLAN

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

E F

G H J K L M N O

A B C D

ACCESS HATCH

ELEVATOR 1

MACHINE ROOM

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK,

PROMPTLY NOTIFY VA AND ENGINEER OF SAID

DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT

PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN

CIRCUITS IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (806.379.7700).

EXISTING MOTOR CONTROL CENTER "MCC-4" PROVIDING

POWER TO ELEVATOR 1 (BUILDING 4) TO BE MODIFIED

FOR ELEVATOR REPLACEMENT. SEE ONELINE DIAGRAM ON

SHEET E-601 FOR ADDITIONAL INFORMATION.

SCALE : 1/8" = 1'-0"

BUILDING 4 - LEVEL 2 - ELECTRICAL PLAN1

0 4' 8' 16'

PROJECT

NORTH

PROJECT

NORTH

EXISTING FEEDER

FOR ELEVATOR 1

BLDG.4

EP401

EP401

AREA OF WORK

CONTINUE TO ELEVATOR

CONTROL SWITCH "ECS-B4-1"

KEY PLAN

GENERAL NOTES

KEY NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP103

BUILDING 4 - LEVEL 2 - ELECTRICAL

PLAN

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

E F G H

A B C D

STORAGE

MECHANICAL

4A

STORAGE

OFFICE

STORAGE

OFFICE

ELECTRICAL

MECHANICAL

B03A

ELEVATOR 1

PARTIALLY

EXCAVATED

PARTIALLY

EXCAVATED

PARTIALLY

EXCAVATED

OFFICE

2A

OFFICE

2PNL 7-B3EC

SPLICE BOX

PNL 7B2

PNL 7B3

PNL 7-B1EQ

PNL 73BL

GROUNDING BAR

T

7-B2EQ

TX-7B2EQ

CARD READER

CONTROL PANELS

180°

ELV

SCALE : 1/4" = 1'-0"

BUILDING 7 - LEVEL B - ELECTRICAL PLAN1

PROJECT

NORTH

EP403

EP403

3360°

2'0 4' 8'

KEY PLAN

GENERAL NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK,

PROMPTLY NOTIFY VA AND ENGINEER OF SAID

DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT

PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN

CIRCUITS IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (806.379.7700).

KEY NOTES

REPLACE ELEVATOR LOBBY CONTROLS. COORDINATE WITH

ELEVATOR CONTRACTOR AND VENDOR AS REQUIRED.

PANEL TO BE MODIFIED. REFERENCE ONE-LINE DIAGRAM

ON SHEET E-601 FOR ADDITIONAL INFORMATION.

PROVIDE RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE POE; PROVIDE ALL

POWER SUPPLIES AND/OR AMPLIFIERS AS REQUIRED FOR

A COMPLETE AND FULLY FUNCTIONAL SYSTEM. CAMERA

SHALL BE AXIS P3727-PLE.

INSTALL MODULES AS NEEDED TO SERVE CARD READER

FOR BUILDING 7 ELEVATOR MACHINE ROOM. COORDINATE

WITH VA AS REQUIRED.

PROJECT

NORTH

AREA OF WORK

BLDG.7

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP104

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

11/15/2022

BUILDING 7 - LEVEL B - ELECTRICAL

PLAN

A B C 108B D E F G H

110A

106B

111A

108A 114

ELEVATOR 1

106A

111B REPLACE ELEVATOR LOBBY CONTROLS. COORDINATE WITH

ELEVATOR CONTRACTOR AND VENDOR AS REQUIRED.

PROVIDE RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE POE; PROVIDE ALL

POWER SUPPLIES AND/OR AMPLIFIERS AS REQURED FOR A

COMPLETE AND FULLY FUNCTIONAL SYSTEM. CAMERA

SHALL BE AXIS P3727-PLE.

ELV 1

SCALE : 1/4" = 1'-0"

BUILDING 7 - LEVEL 1 - ELECTRICAL PLAN1

0 2' 4' 8'

PROJECT

NORTH

PROJECT

NORTH

AREA OF WORK

360°

360° 2

KEY PLAN

GENERAL NOTES

KEY NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF DISCREPANCIES

ARE FOUND THAT MAY IMPACT WORK, PROMPTLY NOTIFY VA

AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWING

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL

DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS

IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (PH:

806.379.7700).

BLDG.7

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP105

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

11/15/2022

BUILDING 7 - LEVEL 1 - ELECTRICAL

E F G H

A B C D

ELEVATOR

CHIEF

SECRETARY

ISC

203 PROGRAM

COMPUTER

ROOM

RESTROOM

MECHANICAL

207A

HAC

HALL

PRIVATE ROOM

208A

ELV 1

SCALE : 1/4" = 1'-0"

BUILDING 7 - LEVEL 2 - ELECTRICAL PLAN1

PROJECT

NORTH

EP403

EP403

360° 2 360°

2'0 4' 8'

REPLACE ELEVATOR LOBBY CONTROLS. COORDINATE WITH

ELEVATOR CONTRACTOR AND VENDOR AS REQUIRED.

PROVIDE RACEWAY, CABLING, AND TERMINATIONS AS

REQUIRED FROM CAMERA TO EXISTING VA SURVEILLANCE

NETWORK SWITCH. CAMERA SHALL BE POE; PROVIDE ALL

POWER SUPPLIES AND/OR AMPLIFIERS AS REQURED FOR A

COMPLETE AND FULLY FUNCTIONAL SYSTEM. CAMERA

SHALL BE AXIS P3727-PLE.

KEY PLAN

GENERAL NOTES

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE

INVESTIGATIONS AND RECORD DRAWINGS. IF

DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK,

PROMPTLY NOTIFY VA AND ENGINEER OF SAID

DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL

CONTRACTOR DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL

ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL

LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN

ACCESSIBLE AFTER INSTALLATION OF MILLWORK.

4. CONTRACTOR SHALL DISPOSE OF REMOVED DEVICES.

DISPOSAL OF DEVICES SHALL COMPLY WITH ALL

APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND

INSTALLATIONS PRIOR TO PERFORMING WORK.

7. CONTRACTOR TO COORDINATE NORMAL/ESSENTIAL

ELECTRICAL SYSTEM SHUTDOWNS AND PHASING WITH THE

VA PRIOR TO PERFORMING REQUIRED EQUIPMENT

UPGRADES. CONTRACTOR TO PROVIDE BACKUP EMERGENCY

POWER AND DETERMINE TIE-IN/CONNECTION PLAN WITH

EXISTING EQUIPMENT. BACKUP POWER AND TIE-IN SHALL

CONFORM WITH VA STANDARDS.

8. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS

AS REQUIRED.

9. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT

PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN

CIRCUITS IMPACTED BY THIS PROJECT.

10. COORDINATE RACEWAY AND CABLING TERMINATION

LOCATIONS OF FIRE ALARM DEVICES IN FIELD WITH VA.

11. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

12. ALL SECURITY CAMERA INSTALLATIONS AND PROGRAMMING

SHALL BE PERFORMED BY AMARILLO VA SECURITY

CONTRACTOR "A-V CORP" OF AMARILLO, TX (806.379.7700).

KEY NOTES

PROJECT

NORTH

AREA OF WORK

BLDG.7

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

Project Director

Revisions: Date:

UPGRADE FREIGHT ELEVATORS

BLDG 4 & 7

THOMAS E. CREEK, AMARILLO VA HEATLH CARE SYSTEM

6010 W AMARILLO BLVD, AMARILLO, TX

504-22-102

SPEES DESIGN BUILD

625 1ST AVE, STE 301

SEATTLE, WA 98104

(206) 590-2118

RAY SPEES

REVISION 1 11.15.2022

EP106

LRL/WNM JPS/FEB

CONSTRUCTION

DOCUMENTS

11/15/2022

BUILDING 7 - LEVEL 2 - ELECTRICAL

G H

SWITCH

ELEVATOR 1

MACHINE ROOM

THRESHOLD.

M J

G H

ELEVATOR 1

MACHINE ROOM

SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 0 - ELEVATOR 1 PIT

ENLARGED DEMOLITION PLAN1

EP101 SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 1 - ELEVATOR 1 TOP OF

HOISTWAY ENLARGED DEMOLITION PLAN2

EP102

PROJECT

NORTH

SHOWN AREA

EXISITING ELECTRICAL EQUIPMENT AND ASSOCIATED

CONDUIT AND WIRE TO BE DEMOLISHED BACK TO

SOURCE, UNLESS NOTED OTHERWISE.

1. PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND

RECORD DRAWINGS. IF DISCREPANCIES ARE FOUND THAT

MAY IMPACT WORK, PROMPTLY NOTIFY VA AND ENGINEER

OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR

CLARITY. CONTRACTOR SHALL FIELD VERIFY ALL POWER

AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED

WITH DEMOLISHED BACK TO THEIR SOURCE, UNLESS

OTHERWISE NOTED.

3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING

CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS,

COMPONENTS, FINISHES THE LIKE, SHALL BE REPAIRED OR

REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

4. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO

MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWING

AS REQUIRED.

5. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT

PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN

CIRCUITS IMPACTED BY THIS PROJECT.

6. ALL FIRE ALARM FIELD DEVICES SHALL INTERFACE WITH

EXISTING FIRE ALARM ZONE AS REQUIRED.

7. ALL SURVEILLANCE CAMERAS SHALL BE NETWORKED WITH

EXISTING IT NETWORK.

8. REFERENCE ONE-LINE DIAGRAM FOR ALL EQUIPMENT AND

PANEL FEEDER SIZING.

9. SECURITY CAMERA, CAMERA INSTALLATION, AND

SURVEILLANCE SYSTEM PROGRAMMING SHALL BE

PERFORMED BY AMARILLO VA SECURITY CONTRACTOR "A-V

CORP" OF AMARILLO, TX (PH: 806.379.7700).

SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 0 - ELEVATOR 1 PIT

ENLARGED ELECTRICAL PLAN4

EP101 SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 1 - ELEVATOR 1 TOP OF

HOISTWAY ENLARGED ELECTRICAL PLAN5

EP102

SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 2 - ELEVATOR 1 MACHINE

ROOM ENLARGED DEMOLITION PLAN3

EP103

SCALE : 1/2" = 1'-0"

BUILDING 4 - LEVEL 2 - ELEVATOR 1 MACHINE

ROOM ENLARGED ELECTRICAL PLAN6

EP103

H

H

G

G

HG

HG

DISCONNECT

MITSUBISHI

CONTROL PANELCOURION CONTROL

PANEL

DOOR POWER RESET

DISCONNECT SWITCH

HYDRAULIC UNIT

J

EXISTING ELEVATOR CAB AND ALL RELATED ELECTRICAL

EQUIPMENT TO BE DEMOLISHED AND REMOVED, UNLESS

SHOWN OTHERWISE.

EXISTING NON-GFCI RECEPTACLE AND BOX TO BE

REPLACED WITH 20A, 120V, DUPLEX, GFCI, TR, WR

RECEPTACLE WITH WHILE-IN-USE DIE-CAST ALUMINUM

COVER. EXISTING CONDUIT AND WIRING TO BE REUSED

AND EXTENDED AS REQUIRED. REFERENCE DETAIL '4' ON

THIS SHEET FOR ADDITIONAL INFORMATION.

PROVIDE (5) JUNCTION BOXES (MINIMUM) AND REQUIRED

CONDUIT AND WIRING FOR ELEVATOR AND FIRE ALARM

SYSTEM INTERFACING. JUNCTION BOXES SHALL PROVIDE

INTERFACING RECALLS INCLUDING, BUT NOT LIMITED TO,

THE FOLLOWING: PRIMARY, ALTERNATE, MACHINE ROOM,

HOISTWAY, AND SHUNT TRIP. COORDINATE WITH ELEVATOR

MANUFACTURER, INSTALLER, AND AHJ FOR A FULLY

FUNCTIONAL SYSTEM AS REQUIRED.

CIRCUIT TO EXISTING PIT RECEPTACLE AND LIGHTING