5-5-CR27018-27110270 Energy Compliance Certifcate.pdf

PDF 545 KB Posted

Attached to
DFCM Construction - Prequalified General Stage II - General- New Storage Building - Project #27110270
Solicitation number
CR27018
Issued by
Utah

About this file

This is an Energy Compliance Certificate for a new construction project issued by the State of Utah's Division of Facilities Construction and Management (DFCM). The project involves a pre-engineered metal storage building at Southwest Technical College in Cedar City, Utah (Project #131449, Site #27110270), located at 757 W 800 S. The facility is a 2,142 square-foot nonresidential storage and workshop building designed to comply with the 2024 International Energy Conservation Code (IECC) for Climate Zone 5b. The project is designed by Straightline Architecture LLC and involves the Owner/Agent Ryan Fisher of Southwest Technical College. The mechanical system consists of two unit heaters (UH-1 and UH-2), each with a capacity of 45 kBtu/h and proposed efficiency of 83.00% (exceeding the required 80.00%). The building achieved 62.0 energy credits against a requirement of 36.0 credits through reduced lighting power (20.0 credits), increased occupancy sensors (5.0 credits), and improved envelope performance per ASHRAE 90.1 Appendix C (37.0 credits). The project qualifies for a renewable energy exception due to the building's effective floor area being less than 5,000 square feet.

The compliance certificate was reviewed and approved on September 3, 2026, by Jason Van Ausdal of DFCM. The mechanical compliance statement confirms that the proposed design meets 2024 IECC requirements and was certified by Engineer Cody Baier on July 22, 2026. The inspection checklist addresses mandatory requirements including HVAC equipment efficiency verification, duct and piping insulation compliance, thermostatic control setpoints, mechanical ventilation capabilities, and service water pressure boost systems. The associated Stage II Invitation to Bid for this project indicates a construction cost estimate of $337,481.00 and is restricted to contractors prequalified under DFCM's Stage I Prequalification process.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 1 of 12

Compliance Certificate

Project Information

Energy Code:

Project Title:

Location:

Climate Zone:

Project Type:

Project No:

Project Sub Type:

All Electric:

Is Renewable:

Has Battery:

Has Charger:

Has Heat Pump

2024 IECC

Southwest Technical College Storage Building Cedar City, Utah 5b New Construction 131449 New Building/Complete false false false false false

Construction Site: Owner/Agent: Designer/Contractor:

757 W 800 S Cedar City , Utah 84720

Ryan Fisher Southwest Technical College 757 W 800 S Cedar City , Utah 84270

Nick Greenaway Straightline Architecture, LLC 1570 E. Westminster Ave Salt Lake City , Utah 84105 33037196925 ngreenaway@straightlinearch.com

Notes:

Energy Credits

Description Credit

L06 Reduced lighting power 20.0

L03 Increase occupancy sensor 5.0

E01 Improved envelope performance ASHRAE 90.1 Appendix C 37.0

Credits: 36.0 Required 62.0 Proposed

Renewable energy

Number of Floors:

Area of Three Largest Floors:

Proposed Capacity:

Required Capacity:

Proposed Off-site Energy:

Required Off-site Energy:

Exception:

42171 Building effective floor area is less than 5,000 ft2

Renewables Pass: Exception: Building effective floor area is less than 5,000 ft2

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

09/03/2026

REVIEWED FOR CODE

COMPLIANCE

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 2 of 12

Building Area

Description Floor Area

1-Storage (Workshop) : Nonresidential 2142

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 3 of 12

Mechanical Compliance Certificate

Project Information

Energy Code:

Project Title:

Location:

Climate Zone:

Project Type:

2024 IECC

Southwest Technical College Storage Building Cedar City, Utah 5b New Construction

Construction Site: Owner/Agent: Designer/Contractor:

757 W 800 S Cedar City , Utah 84720

Ryan Fisher Southwest Technical College 757 W 800 S Cedar City , Utah 84270

Nick Greenaway Straightline Architecture, LLC 1570 E. Westminster Ave Salt Lake City , Utah 84105 33037196925 ngreenaway@straightlinearch.com

Mechanical Systems List

Quantity Component Description

HVAC Systems

1 UH-1 (Single Zone w/ PerimeterSystem): Heating: 1 each - Unit Heater (UH-1), Gas, Capacity = 45 kBtu/h Proposed Efficiency = 83.00% Ec, Required Efficiency: 80.00 % Ec Fan System: Unspecified

1 UH-2 (Single Zone w/ PerimeterSystem): Heating: 1 each - Unit Heater (UH-2), Gas, Capacity = 45 kBtu/h Proposed Efficiency = 83.00% Ec, Required Efficiency: 80.00 % Ec Fan System: Unspecified

Mechanical Compliance Statement

Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2024 IECC requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.

Name - Title Signature Date

Cody Baier - Engineer 7/22/2026

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 4 of 12

Inspection Checklist

Energy Code: 2024 IECC

Requirements: 3% were addressed directly in the COMcheck software

Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.

Plan Review

Section

& Req.ID Plan Review Complies? Comments/Assumptions

C105.2

[PR2]1

Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical and service water heating systems and document where exceptions to the standard are claimed.

Load calculations per acceptable engineering standards and handbooks. Hot water system sized per manufacturer's sizing guide.

Complies

Does Not Comply

Not Observable

Not Applicable

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 5 of 12

Footing / Foundation Inspection

Section # & Req.ID Footing / Foundation Inspection Complies? Comments/Assumptions

C403.14.2, C403.14.3

[FO7]3

Snow/ice melting system and freeze protection systems have sensors and controls configured to limit service for pavement temperature above 50F and outdoor temperature above 40F.

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 6 of 12

Plumbing Rough-In Inspection

Section # & Req.ID Plumbing Rough-In Inspection Complies? Comments/Assumptions

C404.5, C404.5.1, C404.5.2 [PL1]3

Heated water supply piping conforms to pipe length and volume requirements.

Refer to section details.

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 7 of 12

Mechanical Rough-In Inspection

Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions

C403.3 [ME1]2 HVAC equipment efficiency verified. Complies

Does Not Comply

Not Observable

Not Applicable

See the Mechanical Systems list for values

C403.12.3, C403.12.3.1, C403.12.3.2

[ME13]3

Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections C403.12.3.1 and refrigeration compressor systems that comply with C403.12.3.2..

Complies

Does Not Comply

Not Observable

Not Applicable

C403.14.1

[ME14]2

Systems that heat outside the building envelope are radiant heat systems controlled by an occupancy sensing device or timer switch.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.13.1, C403.13.2

[ME15]2

HVAC ducts and plenums insulated in accordance with C403.13.1 and constructed in accordance with C403.13.3, verification may need to occur during Foundation Inspection.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.13.3

[ME16]2

HVAC piping insulation insulated in accordance with Table C403.13.3.

Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.2.2

[ME18]1

Natural or mechanical ventilation is provided in accordance with International Mechanical Code Chapter 4. Mechanical ventilation has capability to reduce outdoor air supply to minimum per IMC Chapter 4.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.1.3

[ME24]2

Where thermostatic control setpoints are adjustable by occupants or HVAC operators, the adjustments are independent for heating and cooling setpoint.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.1.5

[ME26]2

Heating for vestibules and air curtains with integral heating include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint <= 60F and cooling setpoint >= 80F.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.9 [ME3]2 Large diameter fans where installed shall be tested and labeled in accordance with AMCA 230 and meet efficacy requirements of Table C403.9.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.7

[ME35]3

Doors or operable openings from conditioned space to outdoors > 40 sq ft contain automatic controls interlocked with the heating and cooling system.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.8.1

[ME36]3

Dehumidification controls do not use mechanical cooling to reduce humidity < 60% or a dew point < 55F

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 8 of 12

Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions

C403.4.8.2

[ME37]3

Humidity controls do not use fossil fuel or electricity for a humidity > 30% in warmest zone.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.8.3

[ME38]3

Zones served by systems with both humidification and dehumification prevent simultaneous operation.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.5.5

[ME45]2

Fault detection and diagnostics installed with air-cooled unitary DX units or VRF units having economizers.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.1

[ME56]1

Demand control ventilation provided for spaces >250 ft2 and >15 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.2

[ME57]3

Enclosed parking garage ventilation has separate ventilation systems for each section, can reduce airflow < 0.05 cfm/sq ft of floor area and >20% of design capacity.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.4

[ME59]1

Exhaust air energy recovery on systems meeting Table C403.7.4(1) and C403.7.4(2).

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.5

[ME60]3

Kitchen exhaust systems comply with replacement air and conditioned supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria. Type I exhaust hoods contain demand control kitchen ventilation with > 50% reduction in exhaust.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.6

[ME61]3

HVAC systems serving guestrooms in Group R-1 buildings with > 50 guestrooms:

Each guestroom is provided with controls that automatically manage temperature setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2).

Complies

Does Not Comply

Not Observable

Not Applicable

C403.7.8, C403.7.8.1

[ME63]3

Classrooms, training rooms, conference and multipurpose rooms, lounges, enclosed offices, open office areas and corridors contain occupied standby ventilation controls.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.8.1

[ME64]3

HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp.

Complies

Does Not Comply

Not Observable

Not Applicable

See the Mechanical Systems list for values

C403.8.3

[ME66]2

Fans have a fan energy index (FEI) >=

1.00. Variable volume fans will have an FEI

>= 0.95.

Complies

Does Not Comply

Not Observable

Location on plans/spec: M6.01

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 9 of 12

& Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions

C403.8.3

[ME66]2

Fans have a fan energy index (FEI) >=

1.00. Variable volume fans will have an FEI

>= 0.95.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: M6.01

C403.15

[ME69]2

Dehumidification systems for plant growth and maintenance are tested in accordance with DOE 10 CFR 430, has on-site heat recovery > 75% of dehumidification energy or ha a solid or liquid desiccant.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.16

[ME70]2

Service water pressure boost systems contain pressure sensors for pump control, no devices used to reduce pressure and booster pumps do not operate when there is no service water flow.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.17

[ME71]2

Clean water pumps achieve a pump energy index (PEI) <= 1.0.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.2.1

[ME73]3

Air outlets and zone terminal devices have means for air balancing.

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 10 of 12

Rough-In Electrical Inspection

Section # & Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions

C405.7

[EL3]2

Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6.

Complies

Does Not Comply

Not Observable

Not Applicable

C405.8

[EL4]2

Electric motors meet the minimum efficiency requirements of Tables C405.7(1) through C405.7(4). Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer (where certification programs do not exist).

Complies

Does Not Comply

Not Observable

Not Applicable

C405.10

[EL1]2

Total voltage drop across the combination of feeders and branch circuits <= 5%.

Complies

Does Not Comply

Not Observable

Not Applicable

C405.10.1, C405.10.2

[EL5]2

Escalators and moving walks comply with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.

Complies

Does Not Comply

Not Observable

Not Applicable

C405.12, C405.12.1

[EL6]2

50% of 15/20 amp receptacles installed in enclosed offices, conference rooms, copy rooms, break rooms, classrooms and workstations and > 25% of branch circuit feeders for modular furniture will have automatic receptacle control in accordance with C405.12.1.

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 11 of 12

Final Inspection

Section # & Req.ID Final Inspection Complies? Comments/Assumptions

C403.1.1

[FI12]3

HVAC systems and equipment design loads calculated in accordance with ANSI/ASHRAE/ACCA Standard 183 or by an approved equivalent computational procedure

Complies

Does Not Comply

Not Observable

Not Applicable

C403.3.1

[FI13]3

HVAC systems and equipment capacity does not exceed calculated loads.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.1

[FI14]3

Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.1.2

[FI16]3

Thermostatic controls have a 5 °F deadband. Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.1.4

[FI17]3

Temperature controls have setpoint overlap restrictions.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.2

[FI18]3

Each zone equipped with setback controls using automatic time clock or programmable control system.

Complies

Does Not Comply

Not Observable

Not Applicable

C403.4.2.1, C403.4.2.2

[FI19]3

Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hour backup

Complies

Does Not Comply

Not Observable

Not Applicable

C405.15.1, C405.15.2

[FI25]3

Buildings in climate zones 0 - 7 comply with the on-site and/or off-site renewable energy requirements of Section C405.15.

Complies

Does Not Comply

Not Observable

Not Applicable

C406.2.5.3

[FI43]1

Lighting energy credit measure L03 has been selected for energy credit - increased occupancy sensor control in accordance with C406.2.5.3.1 through C406.2.5.3.3.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.1.1

[FI58]1

Building operations and maintenance documents will be provided to the owner.

Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating to owner how building, equipment and systems are intended to be installed, maintained, and operated.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.1

[FI59]1

Commissioning plan developed by registered design professional or approved agency.

Complies

Does Not Comply

Not Observable

Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 12 of 12

& Req.ID Final Inspection Complies? Comments/Assumptions

C408.2.3.1

[FI60]1

HVAC equipment, systems and system-to-system relationships have been tested to ensure proper operation.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.3.2

[FI74]1

HVAC and service water heating control systems have been tested to ensure proper operation, calibration and adjustment of controls.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.4

[FI61]1

Preliminary commissioning report completed and certified by registered design professional or approved agency.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.5

[FI75]3

Furnished HVAC as-built drawings submitted within 90 days of system acceptance.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.5.1

[FI62]1

An air and/or hydronic system balancing report is provided for HVAC systems.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.2.5.2

[FI76]1

Final commissioning report due to building owner within 90 days of receipt of certificate of occupancy.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.3.2.2

[FI77]3

Furnished O&M instructions for systems and equipment to the building owner or designated representative.

Complies

Does Not Comply

Not Observable

Not Applicable

C408.3.2.2

[FI63]3

Furnished O&M manuals for HVAC systems within 90 days of system acceptance.

Complies

Does Not Comply

Not Observable

Not Applicable