5-5-CR27018-27110270 Energy Compliance Certifcate.pdf
PDF 545 KB Posted
- Attached to
- DFCM Construction - Prequalified General Stage II - General- New Storage Building - Project #27110270
- Solicitation number
- CR27018
- Issued by
- Utah
About this file
This is an Energy Compliance Certificate for a new construction project issued by the State of Utah's Division of Facilities Construction and Management (DFCM). The project involves a pre-engineered metal storage building at Southwest Technical College in Cedar City, Utah (Project #131449, Site #27110270), located at 757 W 800 S. The facility is a 2,142 square-foot nonresidential storage and workshop building designed to comply with the 2024 International Energy Conservation Code (IECC) for Climate Zone 5b. The project is designed by Straightline Architecture LLC and involves the Owner/Agent Ryan Fisher of Southwest Technical College. The mechanical system consists of two unit heaters (UH-1 and UH-2), each with a capacity of 45 kBtu/h and proposed efficiency of 83.00% (exceeding the required 80.00%). The building achieved 62.0 energy credits against a requirement of 36.0 credits through reduced lighting power (20.0 credits), increased occupancy sensors (5.0 credits), and improved envelope performance per ASHRAE 90.1 Appendix C (37.0 credits). The project qualifies for a renewable energy exception due to the building's effective floor area being less than 5,000 square feet.
The compliance certificate was reviewed and approved on September 3, 2026, by Jason Van Ausdal of DFCM. The mechanical compliance statement confirms that the proposed design meets 2024 IECC requirements and was certified by Engineer Cody Baier on July 22, 2026. The inspection checklist addresses mandatory requirements including HVAC equipment efficiency verification, duct and piping insulation compliance, thermostatic control setpoints, mechanical ventilation capabilities, and service water pressure boost systems. The associated Stage II Invitation to Bid for this project indicates a construction cost estimate of $337,481.00 and is restricted to contractors prequalified under DFCM's Stage I Prequalification process.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 1 of 12
Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Project No:
Project Sub Type:
All Electric:
Is Renewable:
Has Battery:
Has Charger:
Has Heat Pump
2024 IECC
Southwest Technical College Storage Building Cedar City, Utah 5b New Construction 131449 New Building/Complete false false false false false
Construction Site: Owner/Agent: Designer/Contractor:
757 W 800 S Cedar City , Utah 84720
Ryan Fisher Southwest Technical College 757 W 800 S Cedar City , Utah 84270
Nick Greenaway Straightline Architecture, LLC 1570 E. Westminster Ave Salt Lake City , Utah 84105 33037196925 ngreenaway@straightlinearch.com
Notes:
Energy Credits
Description Credit
L06 Reduced lighting power 20.0
L03 Increase occupancy sensor 5.0
E01 Improved envelope performance ASHRAE 90.1 Appendix C 37.0
Credits: 36.0 Required 62.0 Proposed
Renewable energy
Number of Floors:
Area of Three Largest Floors:
Proposed Capacity:
Required Capacity:
Proposed Off-site Energy:
Required Off-site Energy:
Exception:
42171 Building effective floor area is less than 5,000 ft2
Renewables Pass: Exception: Building effective floor area is less than 5,000 ft2
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
09/03/2026
REVIEWED FOR CODE
COMPLIANCE
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 2 of 12
Building Area
Description Floor Area
1-Storage (Workshop) : Nonresidential 2142
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 3 of 12
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
2024 IECC
Southwest Technical College Storage Building Cedar City, Utah 5b New Construction
Construction Site: Owner/Agent: Designer/Contractor:
757 W 800 S Cedar City , Utah 84720
Ryan Fisher Southwest Technical College 757 W 800 S Cedar City , Utah 84270
Nick Greenaway Straightline Architecture, LLC 1570 E. Westminster Ave Salt Lake City , Utah 84105 33037196925 ngreenaway@straightlinearch.com
Mechanical Systems List
Quantity Component Description
HVAC Systems
1 UH-1 (Single Zone w/ PerimeterSystem): Heating: 1 each - Unit Heater (UH-1), Gas, Capacity = 45 kBtu/h Proposed Efficiency = 83.00% Ec, Required Efficiency: 80.00 % Ec Fan System: Unspecified
1 UH-2 (Single Zone w/ PerimeterSystem): Heating: 1 each - Unit Heater (UH-2), Gas, Capacity = 45 kBtu/h Proposed Efficiency = 83.00% Ec, Required Efficiency: 80.00 % Ec Fan System: Unspecified
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2024 IECC requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Cody Baier - Engineer 7/22/2026
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 4 of 12
Inspection Checklist
Energy Code: 2024 IECC
Requirements: 3% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Plan Review
Section
& Req.ID Plan Review Complies? Comments/Assumptions
C105.2
[PR2]1
Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical and service water heating systems and document where exceptions to the standard are claimed.
Load calculations per acceptable engineering standards and handbooks. Hot water system sized per manufacturer's sizing guide.
Complies
Does Not Comply
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 5 of 12
Footing / Foundation Inspection
Section # & Req.ID Footing / Foundation Inspection Complies? Comments/Assumptions
C403.14.2, C403.14.3
[FO7]3
Snow/ice melting system and freeze protection systems have sensors and controls configured to limit service for pavement temperature above 50F and outdoor temperature above 40F.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 6 of 12
Plumbing Rough-In Inspection
Section # & Req.ID Plumbing Rough-In Inspection Complies? Comments/Assumptions
C404.5, C404.5.1, C404.5.2 [PL1]3
Heated water supply piping conforms to pipe length and volume requirements.
Refer to section details.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 7 of 12
Mechanical Rough-In Inspection
Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions
C403.3 [ME1]2 HVAC equipment efficiency verified. Complies
Does Not Comply
Not Observable
Not Applicable
See the Mechanical Systems list for values
C403.12.3, C403.12.3.1, C403.12.3.2
[ME13]3
Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections C403.12.3.1 and refrigeration compressor systems that comply with C403.12.3.2..
Complies
Does Not Comply
Not Observable
Not Applicable
C403.14.1
[ME14]2
Systems that heat outside the building envelope are radiant heat systems controlled by an occupancy sensing device or timer switch.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.13.1, C403.13.2
[ME15]2
HVAC ducts and plenums insulated in accordance with C403.13.1 and constructed in accordance with C403.13.3, verification may need to occur during Foundation Inspection.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.13.3
[ME16]2
HVAC piping insulation insulated in accordance with Table C403.13.3.
Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.2.2
[ME18]1
Natural or mechanical ventilation is provided in accordance with International Mechanical Code Chapter 4. Mechanical ventilation has capability to reduce outdoor air supply to minimum per IMC Chapter 4.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.1.3
[ME24]2
Where thermostatic control setpoints are adjustable by occupants or HVAC operators, the adjustments are independent for heating and cooling setpoint.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.1.5
[ME26]2
Heating for vestibules and air curtains with integral heating include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint <= 60F and cooling setpoint >= 80F.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.9 [ME3]2 Large diameter fans where installed shall be tested and labeled in accordance with AMCA 230 and meet efficacy requirements of Table C403.9.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.7
[ME35]3
Doors or operable openings from conditioned space to outdoors > 40 sq ft contain automatic controls interlocked with the heating and cooling system.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.8.1
[ME36]3
Dehumidification controls do not use mechanical cooling to reduce humidity < 60% or a dew point < 55F
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 8 of 12
Section # & Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions
C403.4.8.2
[ME37]3
Humidity controls do not use fossil fuel or electricity for a humidity > 30% in warmest zone.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.8.3
[ME38]3
Zones served by systems with both humidification and dehumification prevent simultaneous operation.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.5.5
[ME45]2
Fault detection and diagnostics installed with air-cooled unitary DX units or VRF units having economizers.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.1
[ME56]1
Demand control ventilation provided for spaces >250 ft2 and >15 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.2
[ME57]3
Enclosed parking garage ventilation has separate ventilation systems for each section, can reduce airflow < 0.05 cfm/sq ft of floor area and >20% of design capacity.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.4
[ME59]1
Exhaust air energy recovery on systems meeting Table C403.7.4(1) and C403.7.4(2).
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.5
[ME60]3
Kitchen exhaust systems comply with replacement air and conditioned supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria. Type I exhaust hoods contain demand control kitchen ventilation with > 50% reduction in exhaust.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.6
[ME61]3
HVAC systems serving guestrooms in Group R-1 buildings with > 50 guestrooms:
Each guestroom is provided with controls that automatically manage temperature setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2).
Complies
Does Not Comply
Not Observable
Not Applicable
C403.7.8, C403.7.8.1
[ME63]3
Classrooms, training rooms, conference and multipurpose rooms, lounges, enclosed offices, open office areas and corridors contain occupied standby ventilation controls.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.8.1
[ME64]3
HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp.
Complies
Does Not Comply
Not Observable
Not Applicable
See the Mechanical Systems list for values
C403.8.3
[ME66]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have an FEI
>= 0.95.
Complies
Does Not Comply
Not Observable
Location on plans/spec: M6.01
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 9 of 12
& Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions
C403.8.3
[ME66]2
Fans have a fan energy index (FEI) >=
1.00. Variable volume fans will have an FEI
>= 0.95.
Complies
Does Not Comply
Not Observable
Not Applicable
Location on plans/spec: M6.01
C403.15
[ME69]2
Dehumidification systems for plant growth and maintenance are tested in accordance with DOE 10 CFR 430, has on-site heat recovery > 75% of dehumidification energy or ha a solid or liquid desiccant.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.16
[ME70]2
Service water pressure boost systems contain pressure sensors for pump control, no devices used to reduce pressure and booster pumps do not operate when there is no service water flow.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.17
[ME71]2
Clean water pumps achieve a pump energy index (PEI) <= 1.0.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.2.1
[ME73]3
Air outlets and zone terminal devices have means for air balancing.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 10 of 12
Rough-In Electrical Inspection
Section # & Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.7
[EL3]2
Low-voltage dry-type distribution electric transformers meet the minimum efficiency requirements of Table C405.6.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.8
[EL4]2
Electric motors meet the minimum efficiency requirements of Tables C405.7(1) through C405.7(4). Efficiency verified through certification under an approved certification program or the equipment efficiency ratings shall be provided by motor manufacturer (where certification programs do not exist).
Complies
Does Not Comply
Not Observable
Not Applicable
C405.10
[EL1]2
Total voltage drop across the combination of feeders and branch circuits <= 5%.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.10.1, C405.10.2
[EL5]2
Escalators and moving walks comply with ASME A17.1/CSA B44 and have automatic controls configured to reduce speed to the minimum permitted speed in accordance with ASME A17.1/CSA B44 or applicable local code when not conveying passengers.
Complies
Does Not Comply
Not Observable
Not Applicable
C405.12, C405.12.1
[EL6]2
50% of 15/20 amp receptacles installed in enclosed offices, conference rooms, copy rooms, break rooms, classrooms and workstations and > 25% of branch circuit feeders for modular furniture will have automatic receptacle control in accordance with C405.12.1.
Complies
Does Not Comply
Not Observable
Not Applicable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 11 of 12
Final Inspection
Section # & Req.ID Final Inspection Complies? Comments/Assumptions
C403.1.1
[FI12]3
HVAC systems and equipment design loads calculated in accordance with ANSI/ASHRAE/ACCA Standard 183 or by an approved equivalent computational procedure
Complies
Does Not Comply
Not Observable
Not Applicable
C403.3.1
[FI13]3
HVAC systems and equipment capacity does not exceed calculated loads.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.1
[FI14]3
Heating and cooling to each zone is controlled by a thermostat control. Minimum one humidity control device per installed humidification/dehumidification system.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.1.2
[FI16]3
Thermostatic controls have a 5 °F deadband. Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.1.4
[FI17]3
Temperature controls have setpoint overlap restrictions.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.2
[FI18]3
Each zone equipped with setback controls using automatic time clock or programmable control system.
Complies
Does Not Comply
Not Observable
Not Applicable
C403.4.2.1, C403.4.2.2
[FI19]3
Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hour backup
Complies
Does Not Comply
Not Observable
Not Applicable
C405.15.1, C405.15.2
[FI25]3
Buildings in climate zones 0 - 7 comply with the on-site and/or off-site renewable energy requirements of Section C405.15.
Complies
Does Not Comply
Not Observable
Not Applicable
C406.2.5.3
[FI43]1
Lighting energy credit measure L03 has been selected for energy credit - increased occupancy sensor control in accordance with C406.2.5.3.1 through C406.2.5.3.3.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.1.1
[FI58]1
Building operations and maintenance documents will be provided to the owner.
Documents will cover manufacturers' information, specifications, programming procedures and means of illustrating to owner how building, equipment and systems are intended to be installed, maintained, and operated.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.1
[FI59]1
Commissioning plan developed by registered design professional or approved agency.
Complies
Does Not Comply
Not Observable
Report Title: Southwest Technical College Storage Building Report Date: Jul 22, 2026, 07:40 AM (PDT) 12 of 12
& Req.ID Final Inspection Complies? Comments/Assumptions
C408.2.3.1
[FI60]1
HVAC equipment, systems and system-to-system relationships have been tested to ensure proper operation.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.3.2
[FI74]1
HVAC and service water heating control systems have been tested to ensure proper operation, calibration and adjustment of controls.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.4
[FI61]1
Preliminary commissioning report completed and certified by registered design professional or approved agency.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.5
[FI75]3
Furnished HVAC as-built drawings submitted within 90 days of system acceptance.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.5.1
[FI62]1
An air and/or hydronic system balancing report is provided for HVAC systems.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.2.5.2
[FI76]1
Final commissioning report due to building owner within 90 days of receipt of certificate of occupancy.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.3.2.2
[FI77]3
Furnished O&M instructions for systems and equipment to the building owner or designated representative.
Complies
Does Not Comply
Not Observable
Not Applicable
C408.3.2.2
[FI63]3
Furnished O&M manuals for HVAC systems within 90 days of system acceptance.
Complies
Does Not Comply
Not Observable
Not Applicable