5-2026-03-03 Hillcrest PV ARRAY.pdf
PDF 26 MB Posted
- Attached to
- RFP27-001 PV Array at Hillcrest Elementary
- Solicitation number
- RFP27-001
- Issued by
- Utah
About this file
These are construction documents for a photovoltaic (PV) array installation project at Hillcrest Elementary School for the Ogden School District in Ogden, Utah. The project involves the design and installation of a comprehensive rooftop PV system with an approximate 260 kilowatt-peak (kWp) installed DC power capacity, configured at a 10-degree angle to achieve a maximum AC power output of 240 kilowatts. The system must demonstrate a minimum annual energy production capability of 405 megawatt-hours (MWh) with an annual degradation rate not exceeding 1 percent. The scope includes solar modules, inverters, self-ballasted racking systems, power optimizers, conduits, conductors, terminations, and related electrical infrastructure. Two 120-kilowatt inverters will be installed in second-floor mechanical rooms (2320 and 2420). The project site is located at 1121 Vitt Drive, Ogden, Utah 84404. Construction documents are dated March 3, 2026, with revisions through April 24, 2026.
The contractor bears full responsibility for system design, procurement, installation, and commissioning to achieve the specified energy production requirements. All costs for a fully operational system, including engineering design stamped by a licensed Utah electrical engineer and structural certification by a licensed Utah structural engineer, must be included in the bid. The contractor must obtain Rocky Mountain Power (RMP) approval through Net Metering Level 2 application and coordinate all interconnection requirements. The system must comply with National Electrical Code 2020, International Building Code 2021, and include rapid shutdown requirements per NEC 690.12. Additionally, the contractor must provide a seamless owner portal and centralized monitoring system enabling remote access to PV production data through computers, smartphones, and building management systems, along with seven consecutive days of comprehensive performance testing and successful power delivery within 30 days of system completion.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALT LAKE CITY - HQ
524 SOUTH 600 EAST
SALT LAKE CITY, UT
801.575.8800
VCBO.COM
ST. GEORGE
20 N. MAIN ST. #103
ST. GEORGE, UT
435.522.7070
OSD HILLCREST ELEMENTARY PV SYSTEM
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
1121 VITT DRIVE, OGDEN, UT 84404
OGDEN SCHOOL DISTRICT
CONSTRUCTION DOCUMENTS
MARCH 03, 2026
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
4/23/2026 6:10:09 PM
G001
GENERAL INFORMATION +
INDEX
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
SY
ST
EM
C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
ABBREVIATIONS NOT ALL ABBREVIATIONS MAY BE USED
& AND
@ AT
ACT ACOUSTICAL CEILING TILE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
AL / ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BD BOARD
BLDG BUILDING
BLK BLOCK(ING)
BO BOTTOM OF
BRG BEARING
BSMT BASEMENT
BS BOTH SIDES
BW BOTH WAYS
CAB CABINET
CB CATCH BASIN
CCSA CUSTOM COLOR SELECTED BY
ARCHITECT
CG CORNER GUARD
CHAM CHAMFER
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
COL COLUMN
COMP COMPUTER
CONC CONCRETE
CONT CONTINUOUS
CMU CONCRETE MASONRY UNIT
CSBA COLOR SELECTED BY ARCHITECT
CT CERAMIC TILE
D DEPTH
DB DECK BEARING
DBL DOUBLE
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DRN DRAIN
DTL/DET DETAIL
DW DISHWASHER
DWG DRAWING
E EAST
(E) EXISTING
EA EACH
EIFS EXTERIOR INSULATION SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
ELEV ELEVATION
EQ EQUAL
EQUIP EQUIPMENT
EVAP EVAPORATIVE
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FG FINISH GRADE
FH FIRE HYDRANT
FIN FINISHED
FLR FLOOR
F.O. FACE OF
FT FOOT, FEET
FRP FIBER REINFORCED PANEL
FRT FIRE RETARDANT TREATED WOOD
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GFRC GLASSFIBER REINFORCED PANEL
GYP GYPSUM
GWB GYPSUM WALLBOARD
HB HOSE BIB
HC HANDICAP ACCESSIBLE
HDW HARDWARE
HDF HIGH DENSITY FIBERBOARD
HM HOLLOW METAL
H HEIGHT
HOR HORIZONTAL
ID INSIDE DIAMETER
ICF INSULATED CONCRETE FORM
IN INCH
INCL INCLUDE
INFO INFORMATION
INT INTERIOR
INSUL INSULATE, (D), (ION)
INV INVERT
JST JOIST
JT JOINT
LAV LAVATORY
LB / LBS POUND (S)
MAT MATERIAL (S)
MAX MAXIMUM
MDF MEDIUM DENSITY
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MGR MANAGER
MIN MINIMUM
MIR MIRROR
MISC MISCELANEOUS
MO MASONRY OPENING
MTD MOUNT (ED)
MTL METAL
MW MICROWAVE
N NORTH
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED/ CONTRACTOR
INSTALLED
OFD OVERFLOW DRAIN
OH OVERHEAD
OPG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OZ OUNCE
PERI PERIMETER
PERM PERMANENT
PL PLATE
PLAM PLASTIC LAMINATE
PNL PANEL
PNT PAINT (ED)
P.O. POINT OF
PR PAIR
PT POST TENSIONED
PART PARTITION
PLY PLYWOOD
QT QUARRY TILE
R / RAD RADIUS
RCP REFLECTED CEILING PLAN
REC RECESSED
REF REFERENCE
REFG REFRIGERATOR
REINF REINFORCE (ED)
REM REMOVE (ED)
REPL REPLACE
REQD REQUIRED
REV REVISION (S)
RM ROOM
RO ROUGH OPENING
S SOUTH
SALV SALVAGE (ED)
SECT SECTION
SF SQUARE FOOT
SIM SIMILAR
SLNT SEALANT
SPEC SPECIFICATION (S)
SQ SQUARE
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURE (AL)
SUSP SUSPENDED
SYM SYMMETRY (ICAL)
T THICKNESS
T & B TOP AND BOTTOM
T & G TONGUE AND GROOVE
TBD TO BE DETERMINED
TEMP TEMPORARY
THRU THROUGH
T.O. TOP OF
TRANS TRANSFORMER
TS TUBE STEEL
TYP TYPICAL
UNF UNFINISHED
UNO UNLESS OTHERWISE NOTED
VAR VARIES
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VWC VINYL WALL COVERING
W WEST
W WIDTH
W/ WITH
WC WATER CLOSET
WD WOOD
W/O WITHOUT
WSCT WAINSCOT
WWF WELDED WIRE FABRIC
PROJECT TEAM
owner
KEN CRAWFORD
OGDEN SCHOOL DISTRICT
1950 MONROE BOULEVARD
OGDEN, UT 84401
crawfordk@ogdensd.org
801.430.5054
UTILITY CONTACTS
power
ROCKY MOUNTAIN POWER
1407 W. NORTH TEMPLE
SALT LAKE CITY, UT 84116
503.813.5122 natural gas
DOMINION ENERGY
dominionenergy.com 801.324.5111 water/storm drain
OGDEN CITY
133 WEST 29TH STREET
OGDEN, UTAH 84401
801.629.8271 sewer telephone
TERESA HINTON
LUMEN
teresa.hinton@lumen.com 801.661.7041
OGDEN CITY
133 WEST 29TH STREET
OGDEN, UTAH 84401
801.629.8271
SHEET NUMBERING + NAMING
THIS IS A QUICK REFERENCE GUIDE TO THE
SHEET NUMBERING AND NAMING SYSTEM USED
IN VCBO CONSTRUCTION DOCUMENTS.
X X 0 0 0 . 0
D
IS
C
IP
LI
N
E D
E S
IG
N
A T
O R
S H
E E
T T
Y P
E
LE
V
E L
S E
Q U
E N
C E
P
LA
N T
Y P
E
PLAN TYPE
.0 SLAB PLAN
.1 ANNOTATED PLAN
.2 DIMENSION + WALL TYPE PLAN
.3 FINISH PLAN
.4 REFLECTED CEILING PLAN
SEQUENCE
DENOTES AREA SEQUENCE IN PLAN, AND NUMERIC
SEQUENCE IN NON-PLAN SHEETS
LEVEL
DENOTES LEVEL IN A MULTI-STORY BUILDING. ALSO
BECOMES A SEQUENCE NUMBER DENOTING
DIVISIONS IN NON-PLAN SHEETS
SHEET TYPE SEQUENCE
0 GENERAL NOTES + LEGENDS
1 FLOOR PLANS
2 ELEVATIONS
3 SECTIONS
4 ENLARGED PLANS, ELEVATIONS, SECTIONS
5 DETAILS
6 DOOR, WINDOW, OTHER SCHEDULES
7 SIGNAGE
8 USER DEFINED
9 3D DRAWINGS + PERSPECTIVESVICINITY MAP
ADDRESS:
OGDEN SCHOOL DISTRICT
OGDEN, UT 84404
SCALE:SCALE:
T: W?
R: W?
B: W?
L: W?
B? :B F? :F
NAME
REFERENCE SYMBOL LEGEND
INTERIOR ELEVATION LEVEL LINE
AX.X
DETAIL REFERENCE
ROOM NAME AND NUMBER
SECOND LEVEL
116' - 0"
A101
WALL TYPE MARK
DRAWING TAGS
5A6 - 1
REVISIONS TAG
FLOOR TRANSITIONS MARKER
CEILING TAG
ELEVATION MARKER
X X' - X"
WINDOW TAG
FINISH TAG
SHEET SYMBOLS
A
BASIC DRAWING TITLE
MATCH LINEPROJECT
NORTH
XXXX
ELEVATION
NUMBER AND
DIRECTION
SHEET WHERE
DRAWN
DETAIL NUMBER
SHEET WHEN
DRAWN, HYPEN
INDICATES DETAIL
ON SAME SHEET
REVISION NUMBER
CEILING TYPE
CEILING HEIGHT
WINDOW MARKER
SEE WALL TYPE SHEET FOR ADDITIONAL
INFORMATION
TRANSITION
SYMBOL
ROOM NAME
CONSTRUCTION TYPE - BY
CSI DIVISION
WALL TYPE
FIRE RATING
NOMINAL SIZE
# DRAWING TITLE
BUILDING SECTION
DETAIL SECTIONWALL SECTION
LAYOUT GRID LINES
SIM
A101
SIM
A101
SIM
A101
A
WALL SECTION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
ELEVATION NUMBER
AND DIRECTION
SHEET WHERE
DRAWN
WALL SECTION
NUMBER
SHEET WHERE
DRAWN
DIRECTION OF
VIEW
GRID IDENTIFICATION
A101
GENERAL NOTES
1. IT IS THE CONTRACTORS RESPONSIBILITY TO REVIEW AND COORDINATE THE WORK OF
ALL SUB-CONTRACTORS, TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE
THAT ALL PARTIES ARE AWARE OF ALL REQUIREMENTS, REGARDLESS OF WHERE THE
REQUIREMENTS OCCUR IN THE CONTRACT DOCUMENTS, WHICH MIGHT AFFECT THE
WORK OF THAT PARTY.
2. AS PART OF THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE WORK OF ALL
SUB-CONTRACTORS, TRADES AND SUPPLIERS, THE CONTRACTOR SHALL ENDEAVOR
TO IDENTIFY AND NOTIFY THE ARCHITECT OF ANY CONFLICTS BETWEEN THE WORK OF
DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS TO ALLOW REASONABLE
AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED WITHOUT DELAYING THE
WORK. ALL DEVIATIONS FROM THAT WHICH IS REQUIRED BY THE CONTRACT
DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE ARCHITECT.
3. THE ARCHITECTURAL DRAWINGS ESTABLISH AND COORDINATE THE FINISHED
APPEARANCE AND EXACT LOCATION OF ALL EXPOSED ELEMENTS OF THE WORK OF
ALL THE TRADES, INCLUDING THAT WORK WHICH IS ILLUSTRATED PRIMARILY ON
DRAWINGS OF OTHER DISCIPLINES. QUANTITIES ARE TO BE PROVIDED AS SHOWN ON
DRAWINGS OF OTHER DISCIPLINES BUT LOCATIONS SHOWN ON OTHER DRAWINGS
ARE SCHEMATIC, UNLESS OTHERWISE NOTED ON THE ARCHITECTURAL DRAWINGS.
THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE FOR THE FINISHED APPEARANCE
AND EXACT LOCATION OF ALL PARTS OF THE WORK.
4. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF WORK AT THE APPROXIMATE
LOCATION SHOWN; DO NOT SCALE DRAWINGS FOR DIMENSIONAL INFORMATION. ALL
ELEMENTS OF THE DRAWINGS MAY NOT BE DRAWN TO EXACT SCALE. ALL DIMENSIONS
REQUIRED ARE SHOWN OR MAY BE DERIVED FROM THOSE SHOWN ON THE FLOOR
PLANS, DETAIL PLANS, ELEVATIONS, SECTIONS, DETAILS, SCHEDULES AND
SPECIFICATIONS. IF DIMENSIONS ARE NOT PRESENT, THE ARCHITECT IS TO BE
NOTIFIED SO THAT A CLARIFICATION CAN BE ISSUED.
5. CONTRACTOR TO FOLLOW CURRENT ANSI 117-1 STANDARDS AS REPRESENTED ON
SHEET G301, GENERAL ACCESSIBILITY GUIDELINES. NOTIFY ARCHITECT IF THE
DESIGN DRAWINGS CONFLICT WITH THIS SHEET.
DESIGN DATA
GOVERNING BUILDING CODES:
IBC 2021, to include Appendix J; ANSI 117.1 2017; IFC 2021w/ UTAH AMENDMENTS;
IMC 2021; IPC 2021; IECC 2021; IFGC 2021; NEC 2020
OCCUPANCY TYPE - CH.3
• E - EDUCATION (305)
CONSTRUCTION TYPE - CH.6
• TYPE II-B (TABLE 601)
NOTES TO BIDDERS
1. THIS SHEET CONTAINS A LIST OF DRAWINGS WHICH COMPRISE A FULL SET OF DRAWINGS
FOR THIS PROJECT. ANY CONTRACTOR, SUBCONTRACTOR, VENDOR OR ANY OTHER
PERSON PARTICIPATING IN OR BIDDING ON THIS PROJECT SHALL BE RESPONSIBLE FOR
THE INFORMATION CONTAINED IN ANY AND ALL SHEETS OF DRAWINGS AND
SPECIFICATIONS. IF ANY PERSON, PARTY OR ENTITY ELECTS TO SUBMIT BIDS FOR ANY
PORTION, OR ALL, OF THIS PROJECT, THAT PERSON, PARTY OR ENTITY SHALL BE
RESPONSIBLE FOR ANY AND ALL INFORMATION CONTAINED IN THESE DRAWINGS AND
SPECIFICATIONS, INCLUDING, BUT NOT LIMITED TO, ANY SUBSEQUENT ADDENDUMS OR
CLARIFICATIONS THAT MAY BE ISSUED.
2. THESE DOCUMENTS SHOW THE DESIGN INTENT. IT IS THE CONTRACTORS
RESPONSIBILITY TO PROVIDE EVERYTHING SHOWN ON THE DRAWINGS OR SPECIFIED
REGARDLESS OF WHERE IT IS SHOWN ON THE DRAWINGS OR IN THE SPECIFICATIONS.
FOR EXAMPLE; SOME MILLWORK DETAILS HAVE STEEL FRAMES WHICH MAY BE PROVIDED
BY DIVISION 05 OR WITH THE MILLWORK AT THE CONTRACTOR'S DISCRETION, BUT IT
SHALL BE PROVIDED AS PART OF THE CONTRACT.
3. EVERYTHING CALLED FOR IN THESE DOCUMENTS SHALL BE "NEW" AND PROVIDED BY THE
CONTRACTOR, SUBCONTRACTOR, VENDOR OR ANY OTHER PERSON PARTICIPATING IN
OR BIDDING ON THIS PROJECT UNLESS NOTED OTHERWISE AS EXISTING (EXIST), NOT IN
CONTRACT (NIC) OR FOR REFERENCE ONLY. FURNISHINGS SHOWN DASHED SHALL BE
FOR REFERENCE ONLY.
SHEET INDEX
NOTE: SHEET INDEX REFLECTS ALL SHEETS ISSUED IN THIS AND PREVIOUS BID PACKAGES, FOR REFERENCE
5 11/16/2023 BP5-ADDENDUM 01
24 2024-08-10 FLS Review
DEFERRED SUBMITTALS
CONTRACTOR IS RESPONSIBLE TO SUBMIT DEFERRED SUBMITTALS IN ACCORDANCE WITH
IBC 107.3.4.2. AS PART OF THE SUBMITTAL PROCESS, THE CONTRACTOR IS TO SUBMIT ALL
ICC ERS REPORTS FOR ITEMS NOTED.
• ELECTRICAL SEISMIC RESTRAINTS
Sheet Number Sheet Name
GENERAL
CV COVER
G001 GENERAL INFORMATION + INDEX
ARCHITECTURAL SITE
AS101 OVERALL SITE PLAN
ARCHITECTURAL
A010 OVERALL MAIN LEVEL FLOOR PLAN
A020 OVERALL UPPER LEVEL FLOOR PLAN
A031 OVERALL ROOF PLAN PV ARRAY
ELECTRICAL
E001 ELECTRICAL SYMBOLS AND NOTES
E101. LEVEL 01 ELECTRICAL DISTRIBUTION PLAN
E102. LEVEL 02 ELECTRICAL DISTRIBUTION PLAN
E201. MAIN LEVEL ENLARGED MECH. PLAN
E202. ROOF PV SYSTEM ELECTRICAL PLAN
E203. ROOF PV STRING REPORT
E204. ROOF PV SYSTEM DIAGRAMS
E301. PV ONE-LINE DIAGRAM
E401. ELECTRICAL DIAGRAMS
Grand total: 15 construction manager
CHRIS KARTCHNER
BDK - BIG-D | KITCHELL A JOINT VENTURE
ckartchner@bdkjv.com 602.432.2535 electrical engineer architect
DAVID COX, AIA / BREANNA BONSAVAGE, AIA
VCBO ARCHITECTURE
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
dcox@vcbo.com, bbonsavage@vcbo.com 801.575.8800
ERIC SKINKIS
BNA CONSULTING
635 SOUTH STATE STREET
SALT LAKE CITY, UT 84111
eskinkis@resolutgroup.com 801.532.2196
E
C
LE
S A
V E
ELECTRICAL YARD
VITT DR
HILLCREST
ELEMENTARY
SCHOOL
A031
D4
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
4/24/2026 11:02:33 AM
AS101
OVERALL SITE PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
SY
N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE: 1" = 40'-0"
A3 PLAN - SITE - OVERALL
NORTH
SITE PLAN LEGEND
AREA TO BE UNDISTURBED DURING CONSTRUCTION
EXISTING BUILDING, PROTECT AS NECESSARY, REPAIR AS REQUIRED
DN
WR T
X
V
KINDERGARTEN
CLASSROOM
1206A
YARD
MECHANICAL
KINDERGARTEN
CLASSROOM
TEACHER
COLLABORATION
FUNCTIONAL
SKILLS
TOILET
PRE-SCHOOL
CLASSROOM
VESTIBULE
STORAGE
TOILET
1300A
STUDENT
COLLABORATION
KINDERGARTEN
CLASSROOM
TOILET
STORAGE
TOILET
KINDERGARTEN
CLASSROOM
THINK
TANK
RESOURCE
CLASSROOM
STORAGE
SENSORY
ROOM
FUNCTIONAL
SKILLS
STORAGE
TOILET
THINK
TANK
VESTIBULE
CORRIDOR
MAIN
CORRIDOR
VESTIBULE
STEAM
LAB
MULTI-PURPOSE
MUSIC
ROOM
PE
STORAGE
MDF
KITCHEN
- FRONT
SERVING
COOLER
VESTIBULE
CLASSROOM
STORAGE
CLASSROOM
TEACHER
COLLABORATION
CLASSROOM
STORAGE
CLASSROOM
STAIRS
THINK
TANK
CLASSROOM
STORAGE
CLASSROOM
STORAGE
CLASSROOM
ELEC
TELECOM
THINK
TANK
STORAGE
STEAM
LAB
OUTDOOR
STORAGE
U.1NGFCB QN.1
L S.1K P
TOILET
STORAGE
TOILET
TOILET
FAMILY
TOILET
ELEC
STEAM
STORAGE
SITE
TECH
OFFICE
MD E H JA
J.2 K.1
11.1
Q.1 S
8.1
7.1
14.1
12.1
H.1
TOILET
GIRLS
RR
BOYS
RR
DISH
WASHING
CHAIR/TABLE
STORAGE
FREEZER
DRY
STORAGE
KITCHEN
- BACK
RAMP
AFTER
SCHOOL
PROGRAM
STORAGE
MUSIC
STORAGE
RECEPTION
PRINCIPAL
CONFERENCE
ASSIST.
PRINCIPAL
RECORDS
FACULTY
LOUNGE
WORK
ROOM
QUIET
TOILET
WELLNESS
ROOM
TOILET
TOILET
BOYS
RR
GIRLS
RR
COMMUNITY
ROOM 1
COMMUNITY
ROOM 2
CORR.
NURSE
STAIRS
TELECOM
CORRIDOR1400A
STUDENT
COLLABORATION
CLASSROOM
STOR.
STOR.
LEVEL 01 F.F. = 100' - 0"
DATUM ELEVATION = 4476' - 0"
RECEIVING
CUSTODIAL
OFFICE
STORAGE
ELEC
LOCKER
ROOM
KITCHEN
OFFICE 1220
TOILET
JAN
J.1 S.2
6.1
U
JANITOR
JANITOR
GIRLS
RR
BOYS
RR
A031
D4
MIR.
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
4/24/2026 11:40:42 AM
A010
OVERALL MAIN LEVEL
FLOOR PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
SY
N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
V
IT
T
D R
IV
E
O
G D
E N
U
T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE: 1/16" = 1'-0"
A1 OVERALL MAIN LEVEL FLOOR PLAN
NORTH
NORTH
KEY PLAN - MAIN LEVEL
OVERAL FLOOR PLAN LEGEND
AREA TO BE UNDISTURBED DURING CONSTRUCTION
LINE INDICATES EXISTING BUILDING TO BE PROTECTED IN PLACE, REPAIR
AS REQUIRED
WR T
X
V
CLASSROOM
CLASSROOM
TEACHER
COLLABORATION
CLASSROOM
CLASSROOM
STORAGE
STORAGE
CONFERENCE
CLASSROOM
CORRIDOR
STORAGE
INSTRUCTIONAL
COACH
INSTRUCTIONAL
COACH
COUNSELOR
SLP/SLT
GROUP
ROOM
MULTI-PURPOSE
MUSIC
ROOM
THINK
TANK
CLASSROOM
STORAGE
CLASSROOM
CLASSROOM
STORAGE
CLASSROOM
MECHANICAL
THINK
TANK
CORRIDOR
2300A
STUDENT
COLLABORATION
CORRIDOR
CORRIDOR
MECHANICAL
CLASSROOM
STORAGE
CLASSROOM
TEACHER
COLLABORATION2412
CLASSROOM
STORAGE
CLASSROOM
THINK
TANK
CLASSROOM
STORAGE
CLASSROOM 2409
BOYS
RR
GIRLS
RR
CLASSROOM
STORAGE
CLASSROOM
WORK
ROOM
MEDIA
CENTER
STACKS
MECHANICAL
THINK
TANK
2400A
STUDENT
COLLABORATION
CORRIDOR
U.1NGFCB QN.1
L S.1K PMD E H JA
J.2 K.1
11.1
Q.1 S
8.1
7.1
14.1
12.1
H.1
GIRLS
RR
BOYS
RR
TOILET
TOILET
STORAGE
COUNSELOR
COUNSELING
GROUP
BEHAVIORAL
SPECIALIST
MECHANICAL
J.1 S.2
6.1
U
STAIRS
STAIRS
ELEVATOR
FAMILY
TOILET
QUIET
A031
D1
A031
D1
MIR.
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
4/24/2026 11:17:08 AM
A020
OVERALL UPPER LEVEL
FLOOR PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
SY
N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
V
IT
T
D R
IV
E
O
G D
E N
U
T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE: 1/16" = 1'-0"
A1 OVERALL UPPER LEVEL FLOOR PLAN
NORTH
KEY PLAN - UPPER LEVEL
1 08/28/2023 BP2 - ADDENDUM 01
OVERAL UPPER LEVEL FLOOR PLAN LEGEND
AREA TO BE UNDISTURBED DURING CONSTRUCTION
LINE INDICATES EXISTING BUILDING TO BE PROTECTED IN PLACE, REPAIR
AS REQUIRED
J
F
V F
D
C A
L
J
V F
D
T
V F
D
T
WR T
X
VU.1NGFCB QN.1
L S.1K PMD E H JA
J.2 K.1
11.1
Q.1 S
8.1
7.1
14.1
12.1
H.1
J.1 S.2
6.1
U
342' - 6 1/2"
9'
/4
8'
4'
1/ 2"
9'
/4
1'
/4
/4
7'
3/ 4"
/4
1/
4"
/2
5'
1/ 2"
/4
/4
9'
/4
1'
/2
9'
/4
4'
/2
4'
8' - 8" 12' - 8" 12' - 8 1/2" 10' - 4" 11' - 0" 10' - 4" 12' - 4" 9' - 6 3/4" 12' - 4" 12' - 1 1/2" 2' - 0"
5' - 9 1/2" 8' - 6 3/4"
4' - 4" 10' - 4" 11' - 0" 4' - 6" 5' - 10" 12' - 4" 10' - 3 1/2" 11' - 0 1/2" 28' - 2" 25' - 7" 12' - 1" 3' - 10 1/2"
8' - 7 1/2"
20' - 2 1/4" 20' - 6 1/2" 25' - 5 3/4"
TYP.
T Y
P
3'
T Y
P
3'
TYP.
226.1
TYP.
223.0
TYP.
224.1
TYP.
225.1
TYP.
225.1
TYP.
225.1
TYP.
225.1
TYP.
225.1
TYP
3' - 0"
TYP.
223.0
TYP.
227.0
TYP.
209.0
TYP.
209.1
TYP.
224.1
TYP.
224.0
TYP.
222.1
TYP.
226.1
TYP.
223.0
TYP.
224.1
TYP.
222.1
TYP.
223.0
TYP.
223.0
TYP.
209.0
TYP.
223.0
TYP.
222.1
TYP.
209.0
TYP.
226.1
TYP.
227.0
TYP.
223.0
TYP.
227.0
TYP.
227.0
TYP.
TYP.
TYP.
TYP.
213.0
TYP.
209.0
TYP
3' - 0"
T Y
P
3'
TYP
3' - 0"
T Y
P
3'
ROOF LEGEND
PVC MEMBRANE PROTECTION SHEET
EXG TAPERED INSULATION CRICKET - PROTECT IN PLACE, REPAIR AS
REQUIRED
EXG PROTECTIVE WALKABLE SURFACE - PROTECT IN PLACE, REPAIR
AS REQUIRED
EXG DECK RIDGE OR VALLEY
EXG IMAGINARY VALLEY WITH WARPED DECKING
EXG SINGLE PLY ROOF MEMBRANE - PROTECT IN PLACE, REPAIR AS
REQUIRED
EXG PRIMARY AND SECONDARY ROOF DRAINS
EXG SKYLIGHT - PROTECT IN PLACE, REPAIR AS REQUIRED
AREA TO REMAIN UNDISTURBED DURING CONSTRUCTION
RQ
Q.1
7.1
TYP.
211.0
TYP.
207.0
TYP.
202.0
TYP.
213.0
MECHANICAL
WV
11.1
12.1
TYP.
207.0
TYP.
202.0
TYP.
211.0
ELEC
1206A
YARD
TYP.
207.0
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
4/24/2026 11:49:26 AM
A031
OVERALL ROOF PLAN PV
ARRAY
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
SY
N
S T
R U
C T
IO
N
D O
C U
M E
N T
S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE: 1/16" = 1'-0"
A1 PLAN - ROOF - OVERALL PV ARRAY
KEYED NOTES
202.0 EXISTING CONCRETE SLAB, PROTECT AS NECESSARY, REPAIR AS REQUIRED
207.0 EXISTING MASONRY WALL, PROTECT AS NECESSARY, REPAIR AS REQUIRED. REPAINT TO
MATCH EXISTING FINISH WHERE OCCURS.
209.0 EXISTING ROOF LADDER, PROTECT IN PLACE, REPAIR AS REQUIRED
209.1 EXISTING RETRACTABLE STAIR, PROTECT IN PLACE, REPAIR AS REQUIRED
211.0 EXISTING ELECTRICAL, PROTECT AS NECESSARY, REPAIR AS REQUIRED
213.0 EXISTING MECHANICAL, PROTECT AS NECESSARY, REPAIR AS REQUIRED
222.1 EXISTING SKYLIGHT, PROTECT IN PLACE, REPAIR AS REQUIRED
223.0 EXISTING PRIMARY AND SECONDARY ROOF DRAINS AND DOMES TO REMAIN.
224.0 EXISTING PRE-FINISHED METAL CAP AND CLEAT, PROTECT IN PLACE, REPAIR AS REQUIRED
224.1 EXISTING PRECAST CONCRETE PARAPET CAP, PROTECT IN PLACE, REPAIR AS REQUIRED
225.1 EXISTING ROOF SYSTEM, PROTECT IN PLACE, REPAIR AS REQUIRED
226.1 EXISTING CRICKET, PROTECT IN PLACE, REPAIR AS REQUIRED
227.0 EXISTING MECHANICAL EQUIPMENT, PROTECT IN PLACE, REPAIR AS REQUIRED
723 PVC MEMBRANE PROTECTION SHEET, THICKNESS PER ROOFING MFR - 60 MIL MINIMUM,
INSTALLED UNDER THE SOLAR RACKING / MOUNTING SYSTEMS, EACH BALLAST PAN, RAIL
OR OTHER COMPONENT IN CONTACT WITH THE ROOFING MEMBRANE
2607 PV ARRAY INVERTER
2611 PV ARRAY, REFER TO ELECTRICAL DRAWINGS
2612 NEW ELECTRICAL EQUIPMENT
NORTH
GENERAL DEMOLITION NOTES
1. FIELD VERIFY DIMENSIONS AND CONDITIONS INCLUDING EXISTING UTILITIES PRIOR TO
BIDDING. BRING DIFFERING DIMENSIONS AND CONDITIONS TO ARCHITECT'S ATTENTION
PRIOR TO BIDDING.
2. PROVIDE DUSTPROOF ENCLOSURES AT PERIMETER OF CONSTRUCTION & DEMOLITION
FOR PROTECTION OF ADJACENT SPACES.
3. COORDINATE MAINTENANCE OF FIRE EGRESS FOR OCCUPANTS IN EXISTING BUILDING
WITH THE OWNER AND FIRE MARSHAL. PROVIDE NECESSARY TEMPORARY WALLS OR
ENCLOSURES, EMERGENCY LIGHTS, ETC., FOR THE DURATION OF CONSTRUCTION.
4. BRING TO ARCHITECT'S ATTENTION EXISTING CONDITIONS THAT PRESENT ANY CODE
VIOLATIONS, INCORRECT CONSTRUCTION OR SAFETY PROBLEMS.
5. MAINTAIN EXISTING FIRE RATINGS, AND ASSOCIATED FIRE PROTECTION SYSTEMS (I.E.
FIRE SPRINKLERS AND FIRE ALARM SYSTEMS) THROUGHOUT CONSTRUCTION.
COORDINATE ANY INTERRUPTION TO THESE SYSTEMS WITH THE OWNER AND FIRE
MARSHAL. PROVIDE FIRE WATCH REQUIREMENTS ASSOCIATED WITH INTERRUPTIONS TO
THESE SYSTEMS.
6. MAINTAIN EXISTING UTILITY SERVICES FOR EXISTING FACILITIES. COORDINATE
REQUIRED DISRUPTION OF THESE SERVICES WITH OWNER PRIOR TO DISCONNECTING.
PROVIDE TEMPORARY UTILITY SERVICES TO KEEP FACILITIES IN OPERATION DURING
UTILITY RELOCATION INCLUDING BUT NOT LIMITED TO FIRE WATCHES, ELECTRICAL
GENERATORS, ETC.
7. PROTECT EXISTING STRUCTURE, FINISHES, AND SITE ELEMENTS NOT SCHEDULED FOR
DEMOLITION. RESTORE DAMAGED ITEMS TO THEIR ORIGINAL CONDITION OR REPLACE AT
CONTRACTOR'S EXPENSE.
8. REMOVE AND DISPOSE SELECTIVE DEMOLITION MATERIAL PER CITY REQUIREMENTS.
9. EXISTING ROOF PENETRATIONS & EQUIPMENT ARE SHOWN FOR REFERENCE AND MAY
NOT INCLUDE ALL ROOF PENETRATIONS & EQUIPMENT THAT OCCUR, CONTRACTOR TO
VERIFY PRIOR TO CONSTRUCTION.
10. DO NOT DISTURB EXISTING FIRE RATED ELEMENTS INCLUDING FIREPROOFING.
PATCH/REPAIR DAMAGED OR DISTURBED ITEMS.
11. PATCH, REPAIR & REFINISH TO MATCH EXISTING, WHERE ANY EXISTING FINISHES ARE
DAMAGED DURING CONSTRUCTION.
SCALE: 1/8" = 1'-0"
D1 MECHANICAL ROOM 2320 & 2420 (MIR)
SCALE: 1/8" = 1'-0"
D4 ELECTRICAL ROOM 1207 & YARD
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
02/24/2026
5/4/2026 2:00:40 PM
E001
ELECTRICAL SYMBOLS AND
NOTES
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
S Y
S T
E M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SHEET INDEX
E001 ELECTRICAL SYMBOLS AND NOTES
E101 LEVEL 01 ELECTRICAL DISTRIBUTION PLAN
E102 LEVEL 02 ELECTRICAL DISTRIBUTION PLAN
E201 MAIN LEVEL ENLARGED MECH. PLAN
E202 ROOF PV SYSTEM ELECTRICAL PLAN
E203 ROOF PV STRING REPORT
E204 ROOF PV SYSTEM DIAGRAMS
E301 PV ONE-LINE DIAGRAM
E401 ELECTRICAL DIAGRAMS
X
X X
X
ARCHITECTURAL ROOM NUMBER
EQUIPMENT NUMBER
LIGHT FIXTURE (LETTER DESIGNATES TYPE)
DEVICE / EQUIPMENT (TEXT DESIGNATES TYPE) SEE
SCHEDULE
SYMBOL SCHEDULE
STANDARD MOUNTING HEIGHT UNLESS OTHERWISE NOTED ON PLANS
NOTES:
1. SEE FIXTURE SCHEDULE FOR TYPE, MOUNTING AND WATTAGE.
2. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
3. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
4. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
5. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE 'HD' 480 V.
6. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
7. PROVIDE H.O.A. AND S.S. PUSHBUTTONS AS REQUIRED.
8. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
9. DEVICES NOTED WITH AN 'A' INDICATE TO COORDINATE WITH MILLWORK SHOP
DRAWINGS AND ELEVATIONS FOR HEIGHT.
10. SUBSCRIPT INDICATES NEMA CONFIGURATION.
11. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND
DEVICE INDICATES INSTALLED IN CEILING.
12. COORDINATE WITH DOOR HARDWARE SUPPLIER.
13. FOR WATER COOLER LOCATION, SEE DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
14. ARROWS SHOWN ON DEVICE INDICATE SENSOR AIMING DIRECTION.
15. CAMERA NUMBERS ARE SHOWN INSIDE THE CAMERA SYMBOL. CAMERA TYPES ARE
INDICATED IN TAG.
16. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR
IS A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
17. INSTALL DEVICES PER MANUFACTUER'S INSTALLATION INSTRUCTIONS.
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
19. SPEAKER TO BE MOUNTED IN HORIZONTAL POSITION.
20. MOUNTING HEIGHT IS TO BOTTOM OF DISPLAY.
*TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED ON THIS SET OF DRAWINGS.
CABLE TRAY AS NOTED
CONDUIT STUB LOCATION CAP
CONDUIT
CONDUIT DOWN
CONDUIT UP
CONDUIT RUN CONCEALED IN FLOOR OR GROUND
CONDUIT RUN CONCEALED IN WALL OR CEILING
NOTES
MOUNTING
HEIGHTDESCRIPTIONSYMBOL
GENERAL
NOTES
MOUNTING
HEIGHTDESCRIPTIONSYMBOL
CONDUIT / CIRCUIT CONTINUATION
EQUIPMENT PANEL, SEE DRAWINGS +72"
F
S
C
MOTOR OUTLET
EQUIP.
TO SUIT
PUSHBUTTON +46" 2.
NON-FUSED DISCONNECT SWITCH +60" 5. 6.
FUSED DISCONNECT SWITCH
MANUAL STARTER THERMAL OVERLOAD SWITCH WITH PILOT
LIGHT
T
VARIABLE FREQUENCY DRIVEVFD
MAGNETIC STARTER / DISCONNECT COMBINATION
PANEL BOARD
MAIN DISTRIBUTION PANEL
CORD DROP SEE DIAGRAM
PLUGMOLD
+46" OR
AS NOTED
SPECIAL PURPOSE OUTLET 2. 10. W/ CAP.
AS NOTED
+18" OR
CLOCK OUTLET +90" 2.
5mA GFCI CIRCUIT BREAKER PROTECTED
RECEPTACLEG
A DUPLEX RECEPTACLE 9.
DUPLEX RECEPTACLE
WEATHERPROOF RECEPTACLEWP
GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE
DUPLEX RECEPTACLE EMERGENCY POWER (RED)
FOURPLEX RECEPTACLE
FOURPLEX RECEPTACLE EMERGENCY POWER (RED)
TOMBSTONE RECEPTACLE
UPPER OUTLET
SWITCH CONTROLLED
DUPLEX RECEPTACLE 2. 9.AS NOTED
+18" OR
SIMPLEX RECEPTACLE
ISOLATED GROUND RECEPTACLEIG PT POKE THRU - SEE SCHEDULE FLOOR
MAGNETIC STARTER
GROUND FAULT INTERRUPTER FOURPLEX RECEPT
POWER POLE
TVSS PROTECTED RECEPTACLE
CORD REEL SEE DIAGRAM
DUPLEX RECEPTACLE WITH USB OUTLETU
CONTROLLED DUPLEX RECEPTACLE
FB FLOOR BOX - SEE SCHEDULE FLOOR
SEE DIAGRAM,
SPEC.
SEE DIAGRAM,
SPEC.
DP
CP CEILING PROJECTION SYSTEM CEILING BOX
FLAT PANEL DISPLAY WALL BOX TVSS RECEPT., SEE DIAGRAM,
SPEC. 26 2726
SEE DIAGRAM,
SPEC.
AS NOTED
CEILING
ABOVE
DATA AND OTHER DEVICES, REFER TO DIAGRAMS
13.
POWER - ALL 120V RECEPTACLES SHALL BE CONSIDERED TAMPERPROOF
B BREAKER DISCONNECT SWITCH
CONTROLLED FOURPLEX RECEPTACLE
M UTILITY METER / CT CABINET
J
RECEPTACLE SWITCH PACKR
6.
6.
ABBREV. DESCRIPTION ABBREV. DESCRIPTION
ABBREVIATIONS INDEX
# NUMBER
AC ALTERNATING CURRENT
A.F.F. ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING CAPACITY
AM AMPS METER
AMP AMPERE
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISH GRADE
C CONDUIT
CAB CABINET
CATB COMMUNITY ANTENNA TELEVISION
CATV CABLE TELEVISION
CKT CIRCUIT
CLG CEILING
CNTR CONTRACTOR
C.O. CONDUIT ONLY
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
C/W COMPLETE WITH
DB DECIBEL
DC DIRECT CURRENT
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
EG EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
EX EXPLOSION PROOF
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FOOT
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HP HORSE POWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN INCH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MNF MANUFACTURER
MAX MAXIMUM
MB MAIN BUS
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MTG MOUNTING
MTR MOTOR
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT. MANUFAC. ASSOC.
IFC INTERNATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
N.I.C. NOT IN CONTRACT
NO NORMALLY OPENED
NTS NOT TO SCALE
OS & Y OUTSIDE SCREW & YOKE
PB PUSHBUTTON
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
(R) RELOCATE
RECEP RECEPTACLE
REQ REQUIREMENT
RLA RATED LOAD AMPS
RMS ROOT MEAN SQUARE
SE SERVICE ENTRANCE
SPEC SPECIFICATIONS
SPKR SPEAKER
SS SELECTOR SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
RMP ROCKY MOUNTAIN POWER
UPS UNINTERRUPTED POWER SUPPLY
V VOLT (KV-KILOVOLT)
VA/R VOLT-AMPS/REACTIVE
VM VOLT METER
W WATTS
W/ WITH
WH WATTHOUR METER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFMR SW TRANSFER SWITCH
XP EXPLOSION PROOF
1P SINGLE-PHASE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∅ PHASE
DEVICE / EQUIPMENT (TEXT DESIGNATES TYPE) SEE
SCHEDULE / LEGEND
EQUIPMENT 4-POST RACK / CABINET
TELEVISION OUTLET
WIRELESS ACCESS POINT, TWO CABLES
DATA OUTLET, ONE CABLE 2. 9. 11.
AS NOTED
DATA OUTLET, TWO CABLES
DATA OUTLET, THREE CABLES
+18" OR
TELECOMMUNICATIONS
DATA OUTLET, "X" INDICATES QUANTITYX
W WALL PHONE 2.
AS NOTED
+60" OR
DATA OUTLET, CEILING AS NOTED
ANTENNA CEILING
SPL
VIA
SPLITTER
ABOVE
CEILING
VIA
BDA FIBER BDAWAP
EQUIPMENT 2-POST RACK
ANT
CEILING
AS NOTED
AS NOTED
CLG EQUIPMENT CEILING RACK
18. SEE SPEC.
18. SEE SPEC.
CEILING
ABOVE
CEILING
ABOVE
CEILING
XX
6.
GROUND BUS BAR
F JUNCTION BOX ('F' IN FLOOR) AS NOTEDJ
+18" 6.
CEILING
ABOVE
2. 9.AS NOTED
+18" OR
2. 9. 11.AS NOTED
+18" OR
2. 9.AS NOTED
+18" OR
2. 9.AS NOTED
+18" OR
2. 9.AS NOTED
+24" OR
2. 9.AS NOTED
+18" OR
2. 9.AS NOTED
+18" OR
2. 9. 11.AS NOTED
+18" OR
2. 9. 11.AS NOTED
+18" OR
2. 9. AS NOTED
+18" OR
2. 9. 11.AS NOTED
+18" OR
2. 9.AS NOTED
+18" OR
2. 9.AS NOTED
+18" OR
2. SEE SPEC.
+60" 5. 6.
+60" 5. 6.
+46" 2.
+60" 6. 7.
+60" 6. 7.
+66" 6.
+72"
+72"
AS NOTED
+18" OR
AS NOTED
+18" OR
AS NOTED
+18" OR
AS NOTED
+18" OR
2. 9. 11.
2. 9. 11.
2. 9. 11.
11.
9. 11.
DOORBELL CHIME +90" 2.
TELEPHONE DEMARCATION BOARD
X
X
WAP WALL /
PS = PUBLIC SAFETY
COM = CELLULAR/COMMERCIAL
GENERAL NOTES
1. CONTRACTOR IS RESPONSBILE FOR COMPLETING ALL NECESSARY RMP DOCUMENTATION, INCLUDING
NET METERING APPLICATION, FOR APPROVAL OF SYSTEM. COORDINATE ADDITIONAL REQUIREMENTS
AND INSPECTION/APPROVAL TIMELINES WITH RMP.
2. VERIFY ALL EQUIPMENT DIMENSIONS AND LOCATIONS BEFORE BEGINNING ROUGH IN. CONSULT ALL
APPLICABLE CONTRACT DRAWINGS AND SHOP DRAWINGS TO INSURE NEC CODE CLEARANCES
REQUIRED AROUND ALL ELECTRICAL EQUIPMENT.
3. CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC) OF ALL EQUIPMENT FURNISHED UNDER ALL DIVISIONS, INCLUDING ALL EXISTING EQUIPMENT TO BE RE-USED. REVIEW ALL SHOP DRAWINGS AND EXISTING EQUIPMENT BEFORE BEGINNING ROUGH-IN.
4. SEE APPLICABLE SHOP DRAWINGS FOR ROUGH IN LOCATION OF ALL EQUIPMENT, WIRING DEVICES, ETC.
WHERE APPLICABLE MOUNT ALL WIRING DEVICES ABOVE BACK SPLASH EXCEPT THOSE SERVING
UNDER COUNTER EQUIPMENT.
5. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COOPERATE WITH THE MECHANICAL CONTRACTOR SUCH THAT NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE OPERATION OF THE ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THRU ELECTRICAL ROOMS OR
SPACES, OR ABOVE OR BELOW ELECTRICAL EQUIPMENT IN OTHER AREAS.
6. ELECTRICAL BOXES SHALL NOT BE LOCATED IN MASONRY COLUMNS IN BRICK WALLS OR IN GROUTED CELLS ADJACENT TO OPENINGS. COORDINATE LOCATION OF BOXES WITH MASONRY CONTRACTOR.
7. ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS, AND CEILINGS SHALL BE SEALED WITH APPROVED
MATERIAL TO MAINTAIN FIRE RATING OF SURFACE PENETRATED.
8. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS SHALL BE RUN
WITH CONDUCTORS PER TABLE BELOW.
A. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
B. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO KEEP BRANCH
CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
C. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT STAYS
WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF NECESSARY,CONTRACTOR SHALL INCREASE
WIRE AND CONDUIT SIZE TO MEET THE STANDARD AT NO ADDITIONAL COST TO OWNER.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
ALL CONDUIT SHALL BE INSTALLED IN STRAIGHT LINES PARALLEL TO, OR AT RIGHT ANGLES TO, THE STRUCTURE OR ADJACENT BUILDING ELEMENTS. SEPARATIONS BETWEEN CONDUITS AND FASTENINGS OF CONDUITS SHALL BE NEAT AND CONSISTENT. CONDUIT SHALL BE INSTALLED AS TIGHT TO THE BOTTOM OF STRUCTURAL ELEMENTS WHEN PARALLEL TO JOISTS AS CODE WILL ALLOW. OVERALL INSTALLATION SHALL BE ACCOMPLISHED IN AN AESTHETIC AND WORKMANLIKE MANNER. NO CONDUITS SHALL BE
ALLOWED TO RUN PERPENDICULAR TO THE BOTTOM CHORD OF THE JOISTS.
DIVISION 26 SHALL VISIT SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF
EXISTING CONDITIONS. FIELD VERIFY ALL ELECTRICAL EQUIPMENT.
BIDDERS SHALL EXAMINE THE SITE AND THE COMPLETE SET OF PLANS AND SPECIFICATIONS COVERING
THE ENTIRE PROJECT. THEY SHALL BECOME FULLYCONVERSANT WITH THE TYPE OF GENERAL
CONSTRUCTION AS WELL AS ALL PERTINENT FACTS AFFECTING THE COST OF CARRYING OUT THE WORK
THEY WILL CONTRACT TO
PERFORM.
ELECTRICAL CONTRACTOR SHALL COORDINATE PROJECT PHASING WITH GENERAL CONTRACTOR AND BID AND PERFORM RESPONSIBILITIES FOR THIS PROJECT TO GENERAL CONTRACTOR EXPECTATIONS.
COORDINATE ELECTRICAL DEMOLITION WITH ARCHITECTURAL DRAWINGS AND GENERAL CONTRACTOR.
CLOSELY COORDINATE ANY REQUIRED POWER SHUTDOWNS WITH HEAD CUSTODIAN AND OWNER.
WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OF INSTALLATION OR NATURE OF WORK REQUIRED, THE CONTRACTOR WILL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT
WRITTEN PERMISSION OF THE OWNER.
SEQUENCE, COORDINATE, AND INTEGRATE INSTALLATIONS OF ELECTRICAL MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. GIVE PARTICULAR ATTENTION TO LARGE EQUIPMENT REQUIRING POSITIONING PRIOR TO CLOSING-IN THE BUILDING. COORDINATE THE CUTTING AND PATCHING OF BUILDING
COMPONENTS TO ACCOMMODATE INSTALLATION OF ELECTRICAL EQUIPMENT AND MATERIALS.
DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
DISCONNECT AND RECONNECT ANY/ALL FIXTURES, DEVICES, EQUIPMENT, ETC. REQUIRED FOR PROPER
COMPLETION OF THE WORK.
CONTRACTOR MUST CONCEAL ALL RACEWAY THROUGHOUT THE PROJECT. SURFACE MOUNT RACEWAY IS UNACCEPTABLE EXCEPT WHERE THE USE OF PAINTED SURFACE METAL RACEWAYS (EMT) IS APPROVED
SOLEY BY THE ARCHITECT. PAINT TO MATCH SURROUNDING SURFACE.
ALL CONCRETE CUT AND PATCH WORK REQUIRED FOR INSTALLATION AND/OR RELOCATION OF
ELECTRICAL DEVICES AND PANELS THAT REQUIRE WORK WITHIN THE FLOORS SHALL BE DONE BY ELECTRICAL CONTRACTOR. ALL CORE CUTTING FOR NEW SERVICE SHALL ALSO BE COVERED UNDER
ELECTRICAL CONTRACTORS REQUIRED WORK.
CONTRACTOR SHALL AT ALL TIMES KEEP THE PREMISES FREE OF ALL WASTE, SURPLUS MATERIALS, RUBBISH OR DEBRIS WHICH IS CAUSED BY HIS EMPLOYEES OR RESULTING FROM HIS WORK. AFTER ALL EQUIPMENT AND DEVICES HAVE BEEN INSTALLED, REMOVE ALL LABELS, STICKERS, STAINS, TEMPORARY
COVERS, ETC. IDENTIFICATION PLATES ON ALL EQUIPMENT.
IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETE IN EVERY RESPECT AND THAT ANY MATERIAL OR WORK NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, BUT NECESSARY TO
FULLY COMPLETE THE WORK SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR.
CAREFULLY REVIEW THE ENTIRE DRAWING PACKAGE PRIOR TO PROVIDING BID, INCLUDING THE ARCHITECTURAL AND MECHANICAL DRAWINGS. NOT REVIEWING THE ENTIRE SET IS NOT ACCEPTABLE.
PROVIDE CONDUIT FROM DEVICE TO DEVICE IN OPEN AND/OR EXPOSED CEILINGS. CEILINGS WITH CLOUDS
ARE CONSIDERED OPEN/EXPOSED CEILING. NO EXPOSED CABLES SHALL BE SEEN FROM BELOW.
PROVIDE WEATHERPROOF, NEMA 3R RATED EQUIPMENT FOR ALL EXTERIOR APPLICATIONS.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
T THERMOSTAT
ROOFING GENERAL NOTES
1. CONTRACTOR SHALL NOT INSTALL ELECTRICAL CONDUIT(S) THROUGH MECHANICAL CURB AND/OR
DUCTWORK. LOCATE ELECTRICAL CONDUITS A MINIMUM OF 12" AWAY FROM MECHANICAL CURB ALONG WITH MAINTAINING A MINIMUM OF 12" BETWEEN ANY CONDUIT AND ANY OTHER OBSTACLE. CONDUITS MUST EXTEND 24" FROM DECK WITH 16"-18" OF CONDUIT PROTRUDING FROM FINISHED ROOF LINE.
PROVIDE LIQUID TIGHT CONDUIT FROM CONDUIT STUB TO FINAL CONNECTION AT EQUIPMENT.
COORDINATE ANY AND ALL OTHER REQUIRED ROOFING REQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.
DN
ES
ES
ES
ES
ES
X
11.1
WVU.1UTS.1SRQ.1QPN.1NMLK.1KJ.1JH.1HGFEDCBA
E201
'DPHD1'
'TX-DPLD1''DPLD1'
'MDP'
'CT/MS'
'RMP
XFRM/VAULT'
'GENSET'
'1LA1''1LA2'
'DPLC1'
'TX-DPLC1'
'DPHC1'
'1HB3'
'1LB1'
'TX-DPLB1'
'RMP PV
DISCONNECT'
WSR T
X
VU.1U
NGFCB QN.1
L S.1K PMD E H H.1 JA
J.1 K.1
11.1
Q.1
7.1
6.1
S.2J.2
'PCS'
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
02/24/2026
5/4/2026 2:00:48 PM
E101
LEVEL 01 ELECTRICAL
DISTRIBUTION PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
S Y
S T
E M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE = 1/16" = 1'-0"
LEVEL 01 ELECTRICAL DISTRIBUTION PLAN
GENERAL SHEET NOTES
1. NOT EVERY INSTANCE OF REQUIRED ELECTRICAL DISTRIBUTION OR TELECOM
EQUIPMENT HAVE BEEN INCLUDED WITHIN OVERALL DRAWINGS. GEAR AND EQUIPMENT
LOCATIONS ARE DIAGRAMMATICALLY SHOWN AND ARE TO SERVE AS REFERENCE ONLY.
REFER TO COMPLETE DRAWINGS AND SPECIFICATIONS FOR MORE INOFRMATION.
2. SUBMIT DIMENSIONED DRAWINGS OF ALL ELECTRICAL AND TELECOM ROOMS BASED
UPON ACTUAL BID SELECTED MANUFACTURER EQUIPMENT. SHOW PLAN VIEW OF
EQUIPMENT WITH DIMENSIONED CLEARANCES TO PROXIMATE EQUIPMENT. FAILURE TO
SUBMIT SAID PLAN VIEW SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY TO
VERIFY REQUIRED CLEARANCES BEFORE RELEASE OF EQUIPMENT FOR FABRICATION.
CONTRACTOR MAY REARRANGE EQUIPMENT WITH ROOM AS NEEEDED TO HELP
ACHIEVE OPTIMAL LAYOUT OF EQUIPMENT.
3. FINAL ROUTING OF THE CONDUITS, CIRCUITING, AND CABLING SHALL BE DETERMINED
BY THE CONTRACTOR.
4. REFER TO APPENDIX B FOR DA/ERRCS DESIGN. PROVIDE BOTH PATHWAYS,POWER,ETC
REQUIRED FOR DAS SYSTEM DEPLOYMENT DIVISION 26 RESPONSIBLE FOR
COORDINATING FINAL PATHWAYS AND INFRASTRUCTURE REQUIRED FOR ERRCS
SYSTEM INSTALLATION.
5. NOT EVERY INSTANCE OF REQUIRED ELECTRICAL DISTRIBUTION OR TELECOM
EQUIPMENT HAVE BEEN INCLUDED WITHIN THE OVERALL DRAWINGS. GEAR AND
EQUIPMENT LOCATIONS ARE DIAGRAMMATICALLY SHOWN AND ARE TO SERVE AS
REFERENCE ONLY. REFER TO COMPLETE DRAWINGS AND SPECIFICATIONS FOR MORE
INFORMATION.
6. SUBMIT DIMENSIONED DRAWINGS OF ALL ELECTRICAL AND TELECOM ROOMS BASED
UPON ACTUAL BID SELECTED MANUFACTURER EQUIPMENT. SHOW PLAN VIEW OF
EQUIPMENT WITH DIMENSIONED CLEARANCES TO PROXIMATE EQUIPMENT. FAILURE TO
SUBMIT SAID PLAN VIEW SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY TO
VERIFY REQUIRED CLEARANCES BEFORE RELEASE OF EQUIPMENT FOR FABRICATION.
CONTRACTOR MAY REARRANGE EQUIPMENT WITH ROOM AS NEEDED TO HELP ACHIEVE
OPTIMAL LAYOUT OF EQUIPMENT
NORTH
13 11
14 12
A1 A302
D3 A301
A1 A301
D1 A301
D1 A302
B1 A301
B1 A302
X
11.1
WVU.1UTS.1SRQ.1QPN.1NMLK.1KJ.1JH.1HGFEDCBA
'2LC2'
'2LC1'
'2HC1'
'2RPC1'
'2LA1'
'2MHB1'
'2LD1'
'2LD2'
'2LD3'
'2HD1'
'DPPV'
'2LC3'
WSR T
X
VU.1U
NGFCB QN.1
L S.1K PMD E H H.1 JA
J.1 K.1
11.1
Q.1
7.1
6.1
S.2J.2
'2EMH1'
'TX-2EML1'
'2EML1'
'2EMH2'
'TX-2EML2'
'2EML2'
'INV-2'
'INV-1'
4' - 6 1/8"
4' - 6 11/16"
4' - 0 13/16" HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
02/24/2026
5/4/2026 2:00:53 PM
E102
LEVEL 02 ELECTRICAL
DISTRIBUTION PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
S Y
S T
E M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE = 1/16" = 1'-0"
LEVEL 02 ELECTRICAL DISTRIBUTION PLAN
GENERAL SHEET NOTES
1. NOT EVERY INSTANCE OF REQUIRED ELECTRICAL DISTRIBUTION OR TELECOM
EQUIPMENT HAVE BEEN INCLUDED WITHIN OVERALL DRAWINGS. GEAR AND EQUIPMENT
LOCATIONS ARE DIAGRAMMATICALLY SHOWN AND ARE TO SERVE AS REFERENCE ONLY.
REFER TO COMPLETE DRAWINGS AND SPECIFICATIONS FOR MORE INOFRMATION.
2. SUBMIT DIMENSIONED DRAWINGS OF ALL ELECTRICAL AND TELECOM ROOMS BASED
UPON ACTUAL BID SELECTED MANUFACTURER EQUIPMENT. SHOW PLAN VIEW OF
EQUIPMENT WITH DIMENSIONED CLEARANCES TO PROXIMATE EQUIPMENT. FAILURE TO
SUBMIT SAID PLAN VIEW SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY TO
VERIFY REQUIRED CLEARANCES BEFORE RELEASE OF EQUIPMENT FOR FABRICATION.
CONTRACTOR MAY REARRANGE EQUIPMENT WITH ROOM AS NEEEDED TO HELP
ACHIEVE OPTIMAL LAYOUT OF EQUIPMENT.
3. FINAL ROUTING OF THE CONDUITS, CIRCUITING, AND CABLING SHALL BE DETERMINED
BY THE CONTRACTOR.
4. REFER TO APPENDIX B FOR DA/ERRCS DESIGN. PROVIDE BOTH PATHWAYS,POWER,ETC
REQUIRED FOR DAS SYSTEM DEPLOYMENT DIVISION 26 RESPONSIBLE FOR
COORDINATING FINAL PATHWAYS AND INFRASTRUCTURE REQUIRED FOR ERRCS
SYSTEM INSTALLATION.
5. NOT EVERY INSTANCE OF REQUIRED ELECTRICAL DISTRIBUTION OR TELECOM
EQUIPMENT HAVE BEEN INCLUDED WITHIN THE OVERALL DRAWINGS. GEAR AND
EQUIPMENT LOCATIONS ARE DIAGRAMMATICALLY SHOWN AND ARE TO SERVE AS
REFERENCE ONLY. REFER TO COMPLETE DRAWINGS AND SPECIFICATIONS FOR MORE
INFORMATION.
6. SUBMIT DIMENSIONED DRAWINGS OF ALL ELECTRICAL AND TELECOM ROOMS BASED
UPON ACTUAL BID SELECTED MANUFACTURER EQUIPMENT. SHOW PLAN VIEW OF
EQUIPMENT WITH DIMENSIONED CLEARANCES TO PROXIMATE EQUIPMENT. FAILURE TO
SUBMIT SAID PLAN VIEW SHALL NOT RELIEVE CONTRACTOR OF RESPONSIBILITY TO
VERIFY REQUIRED CLEARANCES BEFORE RELEASE OF EQUIPMENT FOR FABRICATION.
CONTRACTOR MAY REARRANGE EQUIPMENT WITH ROOM AS NEEDED TO HELP ACHIEVE
OPTIMAL LAYOUT OF EQUIPMENT
NORTH
24 22
A1 A302
D3 A301
A1 A301
D1 A301
D1 A302
B1 A301
B1 A302
DIV. 26 SHALL FIELD
VERIFY CLEARANCES
DIV. 26 SHALL FIELD
VERIFY CLEARANCES
T
T
J
T
ESES
J
V
FD
'2EML1'
'2HC1'
'2EMH1'
'2LC1'
'2LC2'
'TX-2EML1'
'INV-1'
'2RPC1'
NEW INVERTER #1 LOCATION
(FIELD VERIFY FINAL LOCATION)
P54
'2LD1'
'2LD2'
'2EML2'
'2EMH2'
'2HD1'
'TX-2EML2'
'INV-2'
'DPPV'
'2RPD1'
2LD1-20
ATC PANEL
NEW DPPV (FIELD
VERIFY FINAL
LOCATION)
NEW INVERTER #2 (FIELD
VERIFY FINAL LOCATION)
P53
P53
P54
'RMP
XFRM/VAULT'
'CT/MS'
'MDP'
'1LB1'
DUCT BANK
U006
E401
Q015
E401
'ATS-EMDP'
'EMDP''1EMHF'
'ATS-OEMHF''TX-OEMLF'
'OEMLF'
'1RPB1'
CONCRETE PAD
(SIZE AS REQUIRED)
'RMP PV
DISCONNECT'
'DPLB1'
'TX-DPLB1'
'1MLB1' '1MHB1'
'1HB3'
'TX-1EML1'
'1EML1'
'PCS'
1LB1-1
1LB1-5
WP
BLAST WALL
1LB1-9
1LB1-9
U008
E401
REFER TO ONE-LINE
1LB1-11
EMB HUB A8810
GENSET EPO
WP
'1MHB1'
(SEC 1) (SEC 2)
1MLB1-29
1MLB1-29 1MLB1-29
NEW POWER CONDITIONING SYSTEM
P55
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
02/24/2026
5/4/2026 2:00:56 PM
E201
MAIN LEVEL ENLARGED
MECH. PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
S Y
S T
E M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE = 1/4" = 1'-0"
ENLARGED MAIN ELECTRICAL ROOM
& YARD
SCALE = 1/4" = 1'-0"
LEVEL 02 MECHANICAL ELECTRICAL
PLAN - AREA 23
3 SCALE = 1/4" = 1'-0"
LEVEL 02 MECHANICAL ELECTRICAL
PLAN - AREA 24
SHEET KEYNOTES
P53 FIELD COORDINATE FINAL ELECTRICAL EQUIPMENT LOCATIONS WITHIN MECHANICAL ROOM. LOCATE
EQUIPMENT AWAY FROM ALL MECHANICAL PIPING/DUCTWORK WITHIN THE SPACE WHERE POSSIBLE.
P54 PROVIDE NEW CAT6A (HUBBELL C6ASPDSBK BLACK JACKET) FROM INVERTER TO NEAREST DATA ROOM LOCATED ON FLOOR BELOW. PROVIDE ALL NECESSARY PATCH CABLES, CONNECTORS, CONDUIT, AND
CABLING SUPPORTS.
P55 PROVIDE NEW POWER CONDITIONING SYSTEM AS SHOWN. REWORK EXISTING AND EXTEND DATA OUTLET
AND 120V RECEPTACLE AS NEEDED TO CONNECT TO NEW POWER CONDITIONING SYSTEM.
/A2.1 A2.1
1'
1'
"1'
1'
/4
1'
/4
1'
1' - 4"
1'
1'
1'
PRE-FABRICATED FIXED SKYLIGHT:
MAINTAIN ACCESS
PRIMARY AND SECONDARY ROOF DRAINS:
MAINTAIN ACCESS [TYP.]
SELF-BALLASTED RACKING
SYSTEM (SOUTH FACING 10
DEGREE TILT) (TYP.)
485W BIFACIAL DUAL GLASS
MONOCRYSTALLINE MODULE
ROOF HATCH:
MAINTAIN ACCESS [TYP.]
ROOF HATCH:
MAINTAIN ACCESS [TYP.]
REQUIRED RMP PV
DISCONNECT
WP
WP
WP
'INV-1'
LOCATED WITHIN
LEVEL 2
MECHANICAL 2320
'DPPV'
'INV-2'
LOCATED
WITHIN
LEVEL 2
MECHANICAL
2LD2-3
2LD2-3
2LC1-1
EXHAUST FAN [TYP.]
/8
14' - 6 7/16"
/1 6"
/8
/4
14' - 2 1/16"
14' - 9 7/8"
10' - 5 3/8"
'CT/MS'
'RMP
XFRM/VAULT'
ROOF LEGEND
SINGLE PLY ROOFING MEMBRANE
TAPERED INSULATION CRICKET MINIMUM SLOPES: 1/8" ALONG VALLEY,
1/4" ACROSS CRICKET
PROTECTIVE WALKABLE SURFACE
DECK RIDGE OR VALLEY
IMAGINARY VALLEY WITH WARPED DECKING
AREAS HATCHED AS SUCH SHALL NOT HAVE ANY PENETRATIONS THRU
THE ROOF IN ORDER TO MAINTAIN THE 2 HOUR FIRE WALL ASSEMBLY
LOCATED BELOW THE DECK (AS PER 2015 IBC SECTION 706.6).
PRIMARY AND SECONDARY ROOF DRAINS
PRE-FABRICATED FIXED SKYLIGHT
TYPICAL SIZE: 60x72
DIMENSIONED TO THE CENTERS
PHOTOVOLTAIC PANEL + RACKING
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
REV DATE DESCRIPTION
SALT LAKE CITY, UT - HQ
ST. GEORGE, UT
LAIE, HI
524 SOUTH 600 EAST
SALT LAKE CITY, UT 84102
801.575.8800
VCBO.COM
E
1 2 3 4 5
E
C
A
B
D D
C
B
A
1 2 3 4 5 6
02/24/2026
5/4/2026 2:01:03 PM
E202
ROOF PV SYSTEM
ELECTRICAL PLAN
O S
D H
IL
L
C R
E S
T E
L E
M E
N T
A R
Y P
V
S Y
S T
E M
C O
N S
T R
U C
T
IO
N D
O C
U M
E N
T S
V
IT
T D
R
IV
E , O
G D
E N
, U T
VCBO NUMBER: 22785.101
CLIENT NUMBER: -
DATE: MARCH 03, 2026
SCALE = 1/16" = 1'-0"
OVERALL ROOF ELECTRICAL/PV PLAN
PV INSTALLER/DIVISION 26 COORDINATE
FINAL ROOF EQUIPMENT AND
PENETRATIONS WITH ALL TRADES.
ADJUST LAYOUT ACCORDINGLY
ROOFING GENERAL NOTES
1. CONTRACTOR SHALL NOT INSTALL ELECTRICAL CONDUIT(S) THROUGH MECHANICAL CURB AND/OR DUCTWORK. LOCATE ELECTRICAL CONDUITS A MINIMUM OF 12" AWAY FROM MECHANICAL CURB ALONG WITH MAINTAINING A MINIMUM OF 12" BETWEEN ANY CONDUIT AND ANY OTHER OBSTACLE. CONDUITS MUST EXTEND 24" FROM DECK WITH 16"-18" OF CONDUIT PROTRUDING FROM FINISHED ROOF LINE.
PROVIDE LIQUID TIGHT CONDUIT FROM CONDUIT STUB TO FINAL CONNECTION AT EQUIPMENT.
COORDINATE ANY AND ALL OTHER REQUIRED ROOFING REQUIREMENTS WITH OWNER PRIOR TO ROUGH-IN.
GENERAL SHEET NOTES
1. WORKMANSHIP THROUGHOUT THE INSTALLATION SHALL BE CONSISTENT FROM ONE PV ARRAY/RACK
TO THE NEXT. INSTALLATION IS EXPECTED TO BE NEAT, HAVE A GOOD MECHANICAL APPEARANCE AND CONFORM TO BEST ELECTRICAL CONSTRUCTION PRACTICES. WHEREVER POSSIBLE, SUPPORT AND SECURE ALL PV WIRING TO RACKING BENEATH MODULES IN MANNER THAT WIRING IS PROTECTED FROM PHYSICAL DAMAGE. CONTRACTOR SHALL SUBMIT CONDUIT ROUTING DETAIL TO ENGINEER FOR REVIEW
PRIOR TO ROUGH-IN/INSTALLATION. GROUP PANELS TO MINIMIZE ROOF PENETRATIONS WHERE
POSSIBLE.
2. PV WIRING BETWEEN ROWS SHALL BE INSTALLED IN MINIMUM 3/4" IMC CONDUIT MOUNTED A MINIMUM OF 2" ABOVE THE ROOF. IMC CONDUIT SHALL BE SECURELY FASTENED AT INTERVALS NOT TO EXCEED
10 FEET AND WITHIN 3 FEET OF BOX OR TERMINATION POINT.
3. PROVIDE PROPER ELECTRICAL IDENTIFICATION AND LABELING OF PV EQUIPMENT AS REQUIRED BY THE LATEST VERSION OF THE NEC 690 AND 705. REFER SPECIFICATION SECTION 26 0553, 26 3100, NEC, AND RMP E.G. EQUIPMENT IDENTIFICATION LABELS OF ENGRAVED PLASTIC-LAMINATE (RED BACKGROUND
WITH WHITE ENGRAVING), ETC.
4. MAINTAIN A MINIMUM OF AT LEAST 10' BETWEEN PV SYSTEM COMPONENTS AND ROOF EDGE.
5. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING RMP NET METERING REQUEST FOR COMMERCIAL
SOLAR APPLICATION. COORDINATE ALL REQUIREMENTS WITH RMP.
GENERAL PHOTOVOLTAIC NOTES
PREVIOUS WORK INSTALLED:
CONDUIT PATHWAYS FOR HAVE PREVIOUSLY BEEN INSTALLED FOR THE FOLLOWING PATHWAYS. CONTRACTOR SHALL SCOPE EXISTING CONDUITS PRIOR TO USE TO ENSURE CONDUITS ARE IN GOOD CONDITION. REFER TO
ONE-LINE FOR REQUIRED CABLING SIZES TO BE INSTALLED IN EXISTING CONDUIT.
• 'CT/MS' TO RMP PV DISCONNECT
• RMP PV DISCONNECT TO 'DPPV'
• 'DPPV' TO INVERTERS #1 AND #2
NEW WORK GENERAL NOTES:
SPECIFICATIONS: REFER TO ELECTRICAL SPECIFICATION AND SECTION 26 3100, TURNKEY PHOTOVOLTAIC (PV) RENEWABLE ENERGY SYSTEM FOR MORE INFORMATION. ANY ALTERNATE PROPOSED EQUIPMENT MUST BE
SUBMITTED A MINIMUM OF 5 WORKING DAYS PRIOR TO BID CLOSE FOR REVIEW.
SYSTEM OUTPUT REQUIREMENTS: THE CONTRACTOR TO FURNISH A COMPREHENSIVE DECENTRALIZED ROOFTOP PHOTOVOLTAIC SYSTEM. THIS SYSTEM MUST DEMONSTRATE A MINIMUM ANNUAL PRODUCTION CAPABILITY OF 405 MWh, WITH AN ANNUAL DEGRADATION RATE NOT EXCEEDING 1%. THE ALL-ENCOMPASSING SYSTEM MUST ENCOMPASS VARIOUS COMPONENTS, INCLUDING, BUT NOT LIMITED TO, SOLAR MODULES, INVERTERS, SELF-BALLASTED RACKING SYSTEMS, POWER OPTIMIZERS, CONDUITS, CONDUCTORS, TERMINATIONS, ETC.
THE CONTRACTOR BEARS THE RESPONSIBILITY OF EXECUTING THE FINAL DESIGN, PROCUREMENT, INSTALLATION, AND COMMISSIONING PROCEDURES NECESSARY TO ESTABLISH A FULLY OPERATIONAL PHOTOVOLTAIC SYSTEM THAT ALIGNS WITH THE SPECIFICATIONS DELINEATED THROUGHOUT THE CONSTRUCTION DOCUMENTS. ACCORDING TO PRELIMINARY CALCULATIONS, THE SYSTEM SHOULD BE SIZED AT APPROXIMATELY 260 kWp INSTALLED DC POWER, WITH PANELS INCLINED AT A 10-DEGREE ANGLE, RESULTING IN A MAXIMUM ACHIEVED AC POWER OUTPUT OF 240.00 kW. THE DEFINITIVE CONFIGURATION OF THE SYSTEM WILL BE DETERMINED BY THE CONTRACTOR TO MEET THE SPECIFIED ENERGY PRODUCTION GOAL AS PREVIOUSLY INDICATED. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING RMP NET METERING REQUEST FOR COMMERCIAL
SOLAR APPLICATION. COORDINATE ALL REQUIREMENTS WITH RMP.
INVERTER, RACKING AND PV MODULE REQUIREMENTS:
1. LOCATE INVERTERS WITHIN 2ND-FLOOR ELECTRICAL ROOMS OR AS INDICATED IN THE PLANS. CONTRACTOR IS
RESPONSIBLE FOR FIELD VERIFYING FINAL LOCATION.
2. MOUNT THE PHOTOVOLTAIC (PV) PANELS ON THE ROOF USING AN ENGINEERED BALLASTED ROOF MOUNT SYSTEM ENGINEERD TO OGDEN CITY WIND SPEED RECOMMENDATIONS (120 MPH 3 SECOND GUST). PROVIDE THE NECESSARY MOUNTING SYSTEM, FRAMES, AND RACKS TO SUPPORT THE PV PANELS, MAINTAINING AN ANGLE
BETWEEN 10 TO 20 DEGREES FROM THE HORIZONTAL.
3. INCLUDE ALL NECESSARY COMPONENTS AND APPURTENANCES TO SECURELY MOUNT THE PV PANELS ONTO THE ROOFING MATERIAL, ENSURING THEY ARE POSITIONED AT LEAST 10 INCHES ABOVE THE ROOF SURFACE.
4. WHENEVER POSSIBLE, ROUTE FEEDERS TO THE INVERTERS IN THE CEILING SPACE BELOW THE ROOF DECK.
5. INSTALL ROOF FLASHING FOR ALL CONDUITS THAT PENETRATE THE ROOF MEMBRANE TO MAINTAIN
WATERTIGHT INTEGRITY.
6. USE IMC CONDUIT FOR ALL WIRING FROM THE INVERTERS TO THE SOLAR MODULES AND ENSURE THAT THE
WIRING IS OF THE 1000-VOLT TYPE PV-WIRE CU."
ROOF PV LAYOUT AND ZONING: THE PRESENTED LAYOUT IS A PRELIMINARY PROPOSED PV ARRAY LAYOUT WITH SPECIFIC PARAMETERS (AZIMUTH: 180°, TILT: 10°). IT IS IMPERATIVE FOR THE CONTRACTOR TO COLLABORATE AND COORDINATE THE PRECISE POSITIONING OF ALL ROOFTOP EQUIPMENT WITH OTHER TRADES AND EXISTING CONDITIONS BEFORE PROCEEDING WITH THE SYSTEM DESIGN. IN CASES WHERE OBSTACLES OR POTENTIAL SHADING ISSUES ARE IDENTIFIED, THE CONTRACTOR SHOULD CONDUCT A SHADING STUDY TO SUBSTANTIATE
AND VALIDATE THE PROPOSED PANEL LOCATIONS.
POWER COMPANY COORDINATION: THE SELECTED PROPOSER/CONTRACTOR SHALL COMPLETE AND SUBMIT ALL REQUIRED ROCKY MOUNTAIN POWER SOLAR DEPARTMENT (RMP) INTERCONNECTION AND NET-METERING LEVEL 2 APPLICATION FORMS AND ASSOCIATED REQUIREMENTS. CONTRACTOR RESPONSIBLE TO MEET ALL
REQUIREMENTS OF THE (RMP).
a. APPROVED EXTERIOR AC DISCONNECT AND PRODUCTION METER.
b. RMP NET METER AT MAIN
c. RMP APPROVED PRODUCTION METER AND ENCLOSURE
c. NEC 2020 690.12 RAPID SHUTDOWN REQUIREMENTS
PROJECT FINAL PLANS: THE SELECTED PROPOSER/CONTRACTOR WILL BE RESPONSIBLE FOR DEVELOPING PV SYSTEM PROJECT PLANS, WHICH WILL BE SUBJECTED TO A PROCESS OF JOINT AGREEMENT, PLAN CHECKS, AND DESIGN REVIEWS INVOLVING VARIOUS STAKEHOLDERS, INCLUDING THE OWNER, THE GENERAL CONTRACTOR, THE ARCHITECT, ELECTRICAL ENGINEER, THE LOCAL AUTHORITY HAVING JURISDICTION, AND OTHER RELEVANT LOCAL PARTIES. THE FINAL DRAWINGS AND SPECIFICATIONS MUST BEAR THE STAMP AND SIGNATURE OF AN ELECTRICAL ENGINEER LICENSED IN THE STATE OF UTAH, AND ALL STRUCTURAL MOUNTING DETAILS MUST BE CERTIFIED WITH THE STAMP AND SIGNATURE OF A STRUCTURAL ENGINEER LICENSED IN THE STATE OF UTAH.
SUBMITTALS: SUBMIT SUPPORT DESIGN DOCUMENTATION WITH FINAL PLANS FOR REVIEW INCLUDING SHADE ANALYSIS, VOLTAGE DROP CALCULATIONS, ENERGY ANALYSIS, INCLUDING EFFECTS OF SHADING, AND SHOP
DRAWINGS OF PROPOSED PV AND MOUNTING EQUIPMENT.
INSTALLATION OF PV SYSTEM: DIVISION 26 AND ITS SUB-CONTRACTOR ARE ENTIRELY RESPONSIBLE FOR ALL EXPENSES RELATED TO THE CONSTRUCTION OF THE PV SYSTEM, ENCOMPASSING INSURANCE COVERAGE, LABOR, MATERIALS, PERMITS, BONDING, ENGINEERING/DESIGN, TRANSPORTATION, STORAGE, AND EQUIPMENT RENTAL COSTS. THIS SHALL COVER THE COMPREHENSIVE SCOPE OF WORK REQUIRED TO BUILD THE PV SYSTEM
IN STRICT COMPLIANCE WITH THE FINAL APPROVED PLANS.
OWNER PORTAL AND CENTRALIZED MONITORING SYSTEM: PROVIDE A SEAMLESS OWNER PORTAL AND A CENTRALIZED MONITORING SYSTEM FOR THIS PROJECT. THE CONTRACTOR SHALL ENSURE NETWORK CONNECTIVITY AND BMS INTEGRATION WITH ALL INVERTERS ACROSS THE ENTIRE PROJECT. IN ADDITION, THE CONTRACTOR IS RESPONSIBLE FOR REGISTERING AND CONFIGURING AN ONLINE PORTAL. THIS PORTAL WILL GRANT BUILDING AND PROJECT OWNERS THE ABILITY TO ACCESS COMPREHENSIVE PV AND PRODUCTION DATA FOR EVERY BUILDING AND CANOPY SYSTEM ACROSS THE SCHOOL DISTRICT.