RFI QA, 47PC1120R0003.pdf

PDF 485 KB Posted

Attached to
US Trustee 4th Floor Keating Renovation Federal contract opportunity
Solicitation number
47PC1120R0003
Issued by
General Services Administration Public Buildings Service Region 2

About this file

This document contains questions and answers related to a solicitation for renovations to the fourth floor of the Keating Federal Building and U.S. Courthouse in Rochester, New York. The General Services Administration seeks a contractor to furnish all materials, equipment, labor and supervision for renovations totaling approximately 2,700 square feet. Work includes hazardous material abatement, new walls, doors, casework, flooring, plumbing, electrical and mechanical. Additionally, technology, data and security infrastructure work is required. The total project cost is estimated between $500,000 to $1,000,000. The solicitation number is 47PC1120R0003. Responses are due no earlier than 15 days after posting to FedBizOpps. The procurement is set aside for small businesses and has a construction completion deadline of 192 calendar days from notice to proceed.

View the file

Other files for this federal contract opportunity

Show all 20

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Trustee 4th Floor Keating Renovation Solicitation 47PC1120R0003 RFI Questions and Answers

1. The partition details on SHT. A-001 show partitions from the Floor to the Ceiling above. What is this measurement? ±11’ – 1” to bottom of slab above – this does not account for beams which are at a lower elevation.

2. The project specifications include the section 104400 INTERIOR SIGNAGE. Please provide a signage schedule for the project. A signage schedule is provided on sheet AE600, and the associated note reads: “signage provided by tenant.” Refer to A-001 for signage tag symbol, and the floor plan on AE101 for signage locations.

3. Drawing AE101 Keyed note #9 reads as follows:

9. PROVIDE REFRIDGERATOR AND MICROWAVE. SEE SPECIFICATIONS.

Please provide specifications for the refrigerator and microwave.

Refrigerator and Microwave:

a. Top Freezer/Bottom Refrigerator: Make: GE Model: GTE21GSH Color: white (preferred) or stainless

b. Microwave: GE 1.6 Cu. Ft. Countertop Microwave Oven such as JES1657DMWW – contractor to verify the microwave fits within the microwave cabinet. i. Microwave color and style to match the refrigerator.

4. Is there an Asbestos report for this project?

Flooring to be removed per keyed note 12 on sheet AD101, and as indicate in specification section 028200. Insert attached Asbestos Survey Assessment Reports after specification section 028200 in the Project Manual. The southern end of the fourth floor, where the newer office is located, had flooring abated already, about 5 or so years ago. The 2015 report was not updated to reflect that, but we pulled up carpet to confirm. The separate old office down the hall (new UST hearing room 4180) has ACM flooring which is required to be removed.

a. Attached – 2019 Report by Colden

b. Attached – 2015 Report provided by GSA.

5. Is The Solid Surface Acrylic ( Corian ) or Quarts – and the color ? Countertop to be Plastic Laminate. Refer to the finish legend on sheet AE600 for type and color.

6. Are the PTAC covers full length of the rooms? Yes – the covers are full length – refer to sheet AE101 for the extent of the covers.

7. Is there a front elevation of the PTAC covers? Yes – it is shown for reference on the interior elevations on sheet AE300. Refer to the section details for materials and dimensions.

8.. RE: PTAC covers I could not seem to find sizes (Length) and number of Architectural Grills, for top and front of cover. Are the grills located at the unit locations only? The grilles run full length wall to wall along the units located on exterior walls – refer to sheet AE101 for locations.

File details come from the government source that posted it. Updated .