This document is an amendment to a solicitation for construction manager as constructor (CMc) services for a major building modernization project at the Silvio J. Mollo Federal Building. The amendment provides responses to 117 requests for information questions regarding project requirements. It extends the proposal due date to February 11, 2022 at 3:00PM EST. The General Services Administration is the contracting agency, and the scope of work includes modernizing building systems, replacing the HVAC plant, and adding a photovoltaic system. Services required include construction management, site work, concrete, masonry, metals, wood and plastics, thermal and moisture protection, doors and windows, finishes, equipment, furnishings, special construction, conveyance systems, and utilities.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
Please see attached.
General Services Administration Capital Construction Branch Acquisition Management Division One World Trade Center New York, NY 10007
47PC0320R0004
1 9
01/19/2022
11/18/2021
INSTRUCTIONS (Back Page):
Instructions for items other than those that are self-explanatory, are as follows:
Item 1 (Contract ID Code). Insert the contract type identification code that appears in the title block of the contract being modified.
Item 3 (Effective date).
(1)
(2)
(3)
(4)
(5)
For a solicitation amendment, change order, or administrative change, the effective date shall be the issue date of the amendment, change order, or administrative change.
For a supplemental agreement, the effective date shall be the date agreed to by the contracting parties.
For a modification issued as an initial or confirming notice of termination for the convenience of the Government, the effective date and the modification number of the confirming notice shall be the same as the effective date and modification number of the initial notice.
For a modification converting a termination for default to a termination for the convenience of the Government, the effective date shall be the same as the effective date of the termination for default.
For a modification confirming the contracting officer's determination of the amount due in settlement of a contract termination, the effective date shall be the same as the effective date of the initial decision.
(a)
(b)
(c)
(d)
(e)
(f)
Item 6 (Issued By). Insert the name and address of the issuing office. If applicable, insert the appropriate issuing office code in the code block.
Item 8 (Name and Address of Contractor). For modifications to a contract or order, enter the contractor's name, address, and code as shown in the original contract or order, unless changed by this or a previous modification.
Items 9, (Amendment of Solicitation Number - Dated), and 10, (Modification of Contract/Order Number - Dated). Check the appropriate box and in the corresponding blanks insert the number and date of the original solicitation, contract, or order.
Item 12 (Accounting and Appropriation Data).
When appropriate, indicate the impact of the modification on each affected accounting classification by inserting one of the following entries:
(2) Accounting classification Net decrease $
Include subject matter or short title of solicitation/contract where feasible.
Item 16B. The contracting officer's signature is not required on solicitation amendments. The contracting officer's signature is normally affixed last on supplemental agreements.
(i)
NOTE: If there are changes to multiple accounting classifications that cannot be placed in block 12, insert an asterisk and the words "See continuation sheet".
Item 13. Check the appropriate box to indicate the type of modification. Insert in the corresponding blank the authority under which the modification is issued. Check whether or not contractor must sign this document. (See FAR 43.103.)
Item 14 (Description of Amendment/Modification).
Organize amendments or modifications under the appropriate Uniform Contract Format (UCF) section headings from the applicable solicitation or contract. The UCF table of contents, however, shall not be set forth in this document.
Indicate the impact of the modification on the overall total contract price by inserting one of the following entries:
(i) Total contract price increased by $
(ii) Total contract price decreased by $
(iii) Total contract price unchanged.
State reason for modification.
When removing, reinstating, or adding funds, identify the contract items and accounting classifications.
(g)
(h)
When the SF 30 is used to reflect a determination by the contracting officer of the amount due in settlement of a contract terminated for the convenience of the Government, the entry in Item 14 of the modification may be limited to --
(i) A reference to the letter determination; and
(ii) A statement of the net amount determined to be due in settlement of the contract.
(1)
(2)
(3)
(4)
(5)
(6)
STANDARD FORM 30 (REV. 11/2016) BACK
(1) Accounting classification Net increase $
Solicitation No.: 47PC0320R0004, Amendment 0005 January 19, 2022
Amendment 0005--Construction Manager as Constructor (CMc) for the Major Building Modernization Project at the Silvio J. Mollo Federal Building Project
Solicitation No.: 47PC0320R0004
Amendment 0005 for Construction Manager as Constructor (CMc) for the Major Building Modernization Project at the Silvio J. Mollo Federal Building Project is issued as follows:
1. Respond to the following RFIs:
RFI
Question 58
HVAC - Drawing # M060-02 - Fan Coil Unit Schedule - Provide manufacturer and model for all FCUs
Answer 58 A quantity has been noted on riser diagrams, and "typical" 5th floor for understanding of arrangement. The BOD for horizontal ceiling-hung units is IEC model HPY. The BOD for perimeter floor-mounted units is IEC model LXA.
RFI
Question 59 HVAC - Clarify seismic requirements for all MEP systems
Answer 59 Refer to details on M70-xx series drawings for equipment support. Building is Seismic Design Category B.
RFI
Question 60 HVAC - Clarify sound treatment scope for rooftop chillers on MTA structure
Answer 60
The rooftop equipment for the MTA building poses the acoustic challenge of abiding by the NYC noise ordinance because it is located directly next to the Metropolitan Correctional Center, which qualifies as a residential property. This means that equipment noise levels cannot exceed 45dBA when measured at the neighboring property line. With no mitigation measures, the sound levels from the cooling tower would significantly exceed the noise level limits at the Correctional Center.
Though more refined design will be required to implement this rooftop equipment successfully, two mitigation measures should be included in cost estimates at this time.
First, discharge attenuators will be needed on the outlets of the cooling tower fans to lower the levels being emitted from the top of the tower. This would be a similar implementation to the attenuators being used for the ASHPs on the Silvio Mollo rooftop. Second, an enclosure around all equipment should be included, as this is likely the only way to reduce levels sufficiently on floors that are immediately adjacent at the same elevation as the rooftop equipment.
RFI
Question 61 HVAC - Clarify non-combustible requirements of equipment.
Answer 61 Cooling towers for Mollo building and MTA building are to be FM-Approved construction.
This has been at times referred to as "non-combustible" during the design review process.
RFI
Question 62
HVAC - Clarify fuel oil requirements (pumps, tanks, pipe routing, etc.) for MTA emergency generator.
Answer 62 MTA generator will have belly day tank. A fill station, 6 hrs of bulk storage, and transfer pump skid to be provided at ground level.
RFI
Question 63 HVAC - Clarify HVAC requirements for Basement Network Protection Room
Answer 63 Network protection room to be provided with ventilation per ConEd Blue Book.
Question 64
HVAC - Clarify any additional heating requirements for bathrooms located at perimeter of building.
Answer 64 Four pipe fan coil will be provided to heat/cool bathrooms.
RFI
Question 65 HVAC - Confirm if return air shall be plenum return or ducted return
Answer 65 Each floor will be plenum return (actually exhaust air, due to DOAS arrangement). A return (exhaust) air duct stub on each floor will tap into a ducted riser back to AHU.
RFI
Question 66
HVAC - Per the riser diagram, AC units serve the IT closets. These units are not shown on the HVAC floor plans or equipment schedule. Please provide this information.
Answer 66 FCU will be provided for each IDF room. Refer to floor plans (e.g. "typical" 5th floor plan FCU-5-29) and riser diagrams.
RFI
Question 67
Plumbing - Please provide plumbing requirements for the MTA building. Are there any Floor drains, Hose bibbs, trap primers, utility sinks, CW/HW requirements.
Answer 67 Makeup water connection will be needed for condenser water system and chilled water systems. A cooling water connection will be needed for the flash tank for ConEd steam rig.
Mechaincal rooms will require floor drains with trap primers.
RFI
Question 68 Plumbing - Please confirm all roof drains should have an overflow drain.
Answer 68 All drains on main roof have overflow drains. Bulkhead is served by primary drains and overflow scupper drains that drain to main roof. Pavilion roof drains to gutters and downspouts that are routed below grade to the detention tank.
RFI
Question 69 Plumbing - Please advise if the existing roof drains on the bridge have overflow drains.
Answer 69 Due to a recent re-roofing project, the bridge roofs are out of scope of this project. Existing Bridge roofs and drains are to remain.
RFI
Question 70
Electrical - There is a photovoltaic system mentioned in the narrative. This system is not shown on the electrical riser. Please provide electrical requirements.
Answer 70 Refer to the electrical and sustainability description in the report as well as the architecural layout. The concept design does not illustrate the wiring diagram for the PV system. This detail will be included in future design phases.
RFI
Question 71
Electrical - The narrative mentions two options for Electrical distribution. Option 1 pipe and wire for vertical feeders and option #2 Bus duct feeders. Please confirm option #1 is to be included in the base estimate.
Answer 71 Include Option #1, pipe and wire in the base estimate.
RFI
Question 72 MTA - Please confirm MTA plant is to be included in the base scope.
Answer 72 Yes, MTA plant is to be included in the base scope.
RFI
Question 73
HVAC - Please confirm access into the building and the propose pathway for the HVAC cooling plant for construction and future operational maintenance.
Answer 73 Proposed rigging path is through a floor access panel in loading dock, down Basement corridor over to mechanical room.
RFI
Question 74 Fire Protection - Please advise if the loading dock requires a dry sprinkler system
Answer 74 The loading dock will require a dry sprinkler system.
Question 75
Fire Protection - Please advise if valved and capped outlets are needed for tenant space on the ground floor.
Answer 75 A dedicated floor control valve assemblies is required for "tenant 1" on the ground floor. A valved and capped connection is required downstream of this floor control valve
RFI
Question 76
HVAC - Please advise how OA is being controlled to the FCU's on the office floors. The drawings shows a ducted connection.
Answer 76 Fixed balance devices for OA to FCU, except IAQ dampers to conference rooms.
RFI
Question 77 HVAC - Please provide sound attenuator schedule or requirements.
Answer 77
Conference room FCU to be mass loaded vinyl wrapped. Assumed each AHU and exhaust fan will have sound attenuators. Insertion losses for attenuators and detailed recommendations have not been provided at this phase but will be developed in later phases of design with the acoustic consultant.
RFI
Question 78 HVAC - Please provide Fire Smoke Damper requirements.
Answer 78 Fire/Smoke dampers will be provided at shaft exits and rated wall penetrations.
RFI
Question 79
HVAC - Please confirm if there are any MEP requirements for entrancway skylight
(FP/HVAC).
Answer 79 Unclear what is meant by entranceway skylight. Assuming question is for security pavilion, it will be provided with radiant heating/cooling in the slab, and perimeter four-pipe fan coil units. DOAS AHU-3 will provide ventilation. Refer to plans.
RFI
Question 80 General - Please advise of any system hardening or resiliency requirements.
Answer 80 Unclear the intent of comment, please re-phrase. All requirements for resiliency and hardening of the structure are included in the narratives and drawings. If additional information is required, please provide a specific question.
RFI
Question 81 Electrical - Please advise if the generator will be tier 4 compliant.
Answer 81 Generator is Tier 2.
RFI
Question 82
Fire Alarm - Please advise if the fire alarm system cables can be "free air" or will need to be completely installed in raceway.
Answer 82 Fire alarm system cables are required to be installed in conduit (Rigid metal or EMT) with a minimum size of 3/4" and compression fittings and couplings. None shall be installed in "free air".
RFI
Question 83 Electrical - Please advise if there are any requirements for a DAS system.
Answer 83 At this time the project has no requirements for a DAS system.
RFI
Question 84
Electrical - Please advise if there are any motorized shades or smart windows requirements.
Answer 84 GSA requires window shades at offices to be manual. Motorized shades are shown for drapery at the Press Lobby Area, Level-1 All Hands Meeting Room due to the height of the room.
RFI
Question 85
Electrical - Please clarify MEP plaza scope requirements as it is not shown on the drawings. I.e.. (Lighting, snow/ice melt etc.)
Answer 85 Site MEP will include, general site lighting, illuminated LED handrails, up-lighting at trees, lighting at signage and flagpole, and illuminated LED security bollards per sheet G10-02.
Snow/ice melt is not planned for at this time.
RFI
Question 86 Plumbing - Please clarify irrigration system scope.
Answer 86 Irrigation will be required at areas of plantings; details are to be developed in later phases of design.
RFI
Question 87
HVAC - Please advise how piping will be routed from MTA HVAC plant to MCC building and where connection to existing system will occur.
Answer 87 Piping will exit north wall of MTA building, route up the exterior, and intercept piping to MCC in the Thurgood-MCC bridge.
RFI
Question 88 HVAC - Please advise if drain downs of MCC chilled water sytem will be
Answer 88 Unclear if there are sufficient isolation valves where pipes enter MCC building. Full drain down most likely will be required.
RFI
Question 89 Security - Please provide raceway requirements for security system.
Answer 89
Access Control: Provide one (1) 1" conduit to a 4x4 junction box above the door, one (1) 3/4" from the JB to the Card Reader, (1) from the JB to the Door contact and Electric hinge/lock as required by Door Hardware. Video Management: Provide one (1) 1" conduit to a doble gang outlet box attached to the nearest structural element in accessible space.
RFI
Question 90
HVAC - Please confirm office floors does not require any perimeter FTR and heating will be accpmplished with overhead FCU's only.
Answer 90 Perimeter heating to be accomplished by HW FTR, except where perimeter floor-mounted FCUs are provided.
RFI
Question 91 Electrical - Please confirm any electrical floor box requirements. I.e. conference rooms.
Answer 91 Electrical floor boxes will be required in each conference room.
RFI
Question 92
Fire Protection - Please confirm if there are any specialty system requirements i.e. (water curtains or lot line sprinklers)
Answer 92 Refer to the life safety plans (sheets G1102 through G1104) and life safety narrative (report page 129) for lot line sprinkler requirements along the East facade. Water curtains are not applicable to the current design.
RFI
Question 93
MCC - Please confirm we are not including any temporary heating/cooling skids for the MCC in the base it is assumed that the MTA Heating/Cooling plant will be built first and then existing plant will be disconnected.
Answer 93 Correct, assumption is no temporary heating/cooling as the MTA heating/cooling plant will be built before disconnection of existing systems.
RFI
Question 94
HVAC- Please confirm ventilation and cooling requirements for the network protector rooms.
Answer 94 Network protection room to be provided with ventilation per ConEd Blue Book.
RFI
Question 95
Utility Work - Drawing # C40-01 - Please confirm utility piping elevation for work noted on Drawing C 40--01
Answer 95 All utilities except for the sewer main and connections shall have a minimum of 4-feet of cover. The sewer main and connections vary in depth from 10 to 15 feet depending on location.
Question 96 Stone cladding- Spec 044200 - Please provide location of Exterior stone cladding
Answer 96 Refer architectural elevation sheets A20-01 through A20-04, and note A63. Stone cladding is located along the South façade at the lower portion of the building, and at the North, East, & West faces of the building core.
RFI
Question 97
Structural Steel- Spec 051250 - Please provide the structural steel framing an allowance
LBS/SF
Answer 97 Design and documentation is at a concept level of detail. Refer to structural drawings, notes, and details on sheets S01-00 through S50-02 for scope provided and the structural narrative on pages 230 through 234 of the report.
RFI
Question 98 Metal Stairs- Spec 055116- Please. Provide details for Metal floor plate stairs
Answer 98 Documentation is at concept level, further details cannot be provided at this time until further design development takes place. Refer to sheets A10-0B, A10-10, AM10-01, AM10-02 for scope of metal stairs.
RFI
Question 99 Wood Planeling - Spec 064216 - Please, provide manufacturer for flush wood paneling
Answer 99 Flush wood paneling is to be by millworker. Veneer finish and details to be provided at later phases of design.
RFI
Question
Metal Wall Panels - Spec 074213 - Please, provide manufacturer of Insulated metal wall panels.
Answer 100 Typical manufacturers include: Pohl; Centria; Kingspan; Dri-Design
RFI
Question
Security Windows - Spec 085653 - Please provide location for security windows and type of glazing
Answer 101 Refer to south elevation on sheet A20-01, note A106 for location and information on security window glazing.
RFI
Question 102 Revolving Doors - Spec 084233 - Please provide manufacturer of revolving doors.
Answer 102 Dormakaba Crane 4000 series is listed as basis of design, refer to the report page 81.
Typical manufacturers include: Boon Edam, Inc.; Crane Revolving Doors (dormakaba USA, Inc.); and Horton Automatics (Overhead Door Corporation).
RFI
Question 103 Door hardware - Spec 087100 - Please provide an allowance for door hardware.
Answer 103 Door hardware to be estimated in accordance with concept level documents, refer to architectural plans A10-0B through A10-11 and interiors narrative on report pages 81 through 83.
RFI
Question
Decorative Glazing - Spec 088113 - Please provide decorative glass glazing type, details and location.
Answer 104
Refer to the report page 81 & 82 for the interiors narrative on interior glazing at Conference Rooms, Security Screening Pavilion, Public Corridors, Pre-function and Double Height Spaces, and All-Hands Meeting Room. Details to be provided at later phases of design.
Question
Storefront & Entrance - Spec 084126 - Please, provide all storefront and entrances type of glazing and details.
Answer 105 Refer to architectural elevation sheets A20-01 through A20-04, glazing types are listed in the legend at the bottom of the page. Details to be provided at later phases of design.
RFI
Question 106 Wood Ceiling - Spec 095426 - Please, provide manufacturer and details at wood ceiling
Answer 106 Details to be provided at later phases of design. See report page 81: Wood veneer torsion spring panelized ceiling (Rulon: Aluratone paneled ceiling with custom veneer, perforation pattern and technical zone)
RFI
Question 107 Terrazzo Floor - Spec 096623 - Please, provide type of terrazzo floor.
Answer 107 See report page 81: Epoxy terrazzo flooring: 3/8” matrix with (5) #0-#2 aggregates (including marble & glass) and custom zinc strips
RFI
Question 108 Fabric Panels - Spec 097723 - Please, provide manufacturer for fabric-wrapped panels.
Answer 108 Typical manufacturers include: Armstrong; Conwed; Decoustics; Sound Concepts;
Wegner Corp
RFI
Question 109 Roof equipment - Spec 108213 - Please provide manufacturer of exterior roof equipment
Answer 109 Refer to MEP Schedules for manufacturers listed. Spec section referenced is for roof equipment screens - to be issued at later date. Reference Accurate Perforating for basis of design manufacturer.
RFI
Question 110 Fire Curtain - Spec 083344 - Please provide manufacturer of overhead coiling fire curtain
Answer 110 Basis of design for manufacturer of overhead coiling fire curtain is Fire Curtain Technologies.
RFI
Question 111 Curtain and Drapes - Spec 122200 - Please provide manufacturer of curtain and drapes.
Answer 111 Lutron is listed as basis of design, refer to the report page 81. Typical manufacturers include Mechoshade, Lutron, Silent Gliss. Knoll Textiles is listed as basis of design for drapery fabric.
RFI
Question
Blast Design - Spec 1303000 - Please, provide narrative with quantitative information for the blast design requirement.
Answer 112
Blast design performance criteria is incorporated into the drawings and details provided.
Refer to structural drawings, notes, and details on sheets S01-00 through S50-02. Also refer to the structural & façade narratives of the report, pages 230 through 244 for applicable information.
RFI
Question
Vertical Transportation - Spec 142100 - Please provide narrative( capacity, speed, etc.)
passenger elevators and one service elevator
Answer 113 Refer to the report page 323 through 330 for vertical transportation narrative.
Question
Partitions - Spec 092116.23 - Provide confirm wall types: for Fire rated and not fire rated partitions on floor plans Cellar thru 9th floor
Answer 114 Partition plans have yet to be developed as documentation is at concept level. Please refer to the life safety plans (sheets G11-03 and G11-04), and acoustic narrative for partition types & requirements table (report page 286 through 300)
RFI
Question
Ceilings - Spec 095113 - Accoustical panel ceilings and Wood ceiling in lobby provide manufacturer.
Answer 115
"See report page 81: Wood veneer torsion spring panelized ceiling (Rulon: Aluratone paneled ceiling with custom veneer, perforation pattern and technical zone) is listed as basis of design for wood ceiling. Typical manufacturers are Rulon, Armstrong, Certainteed, and 9Wood.
Armstrong is listed as basis of design for acoustical ceiling tiles. Typical manufacturers are Armstrong, Certainteed, and Rockfon."
RFI
Question 116 We were wondering if logistics plans could be included in the proposals as 17 x 11 pages.
Answer 116 Yes
RFI
Question
Kindly provide GSA's Fiscal Year 2022 subcontracting goals for Small Business Utilization for the following:
- Small Business
- Small disadvantaged business
- Women owned small businesses
- HUB Zone small businesses
- Service disabled veteran owned small businesses
Answer 117
FY2022 subcontracting goals have not yet been finalized. Please use GSA's Fiscal Year 2021 Subcontracting Goals as follows:
- 20 percent of subcontracts for small businesses
- 5 percent of subcontracts for small disadvantaged businesses
- 5 percent of subcontracts for women-owned small businesses
- 3 percent of subcontracts for HUBZone small businesses
- 3 percent of subcontracts for service-disabled veteran-owned small businesses
2. The due date for proposals is extended to February 11, 2022 at 3:00PM EST.
3. All other terms and conditions of the Solicitation remain unchanged.
End of Amendment 0005