4-Tyrone Township Building - FINAL PLANS - PHASE 2 - REV0 - 07-06-2026.pdf
PDF 5 MB Posted
- Attached to
- Tyrone Township Municipal Building - Phase 2
- Solicitation number
- Not on record
- Issued by
- Philadelphia County, Pennsylvania
About this file
This is a set of Final Construction Plans for Phase 2 of the Tyrone Township Municipal Building located at 3129 Shermans Valley Road, Loysville, Pennsylvania 17047, prepared by Boyle Engineering, LLC and Frederick, Seibert & Associates, Inc. Phase 2 consists of constructing the community hall portion of the township building and paving the parking lot. The project is designed in accordance with the 2018 International Building Code and includes comprehensive structural, mechanical, electrical, and plumbing systems. The building encompasses approximately 12,201 square feet across multiple functional areas including a 3,140-square-foot community hall with radiant floor heating, a 909-square-foot kitchen, 402-square-foot township office, 417-square-foot conference room, restrooms, utility and storage rooms, and a 5,691-square-foot garage area with vehicle wash bay. The plans include detailed specifications for concrete foundations, metal-framed construction with metal siding and roofing, engineered roof trusses, life safety systems with smoke detectors and fire extinguishers, and ADA-compliant accessibility features. A pre-bid meeting is scheduled for August 25, 2026 at 1:00 p.m. at the project site, and sealed proposals are due by 5:00 p.m. on September 29, 2026 through the PennBid Program, with bid opening to occur during the regularly scheduled Tyrone Township Supervisors meeting.
The successful bidder will be required to post a performance bond equal to 100 percent of the bid price, a labor and material payment bond equal to 100 percent of the bid price, and a maintenance bond equal to 10 percent of the bid price. All workmen employed on the project must be paid prevailing minimum wages in accordance with Pennsylvania's Prevailing Wage Act, which applies to all contractors and subcontractors. The construction plans specify detailed mechanical systems including HVAC with two 5-ton Rheem units, radiant floor heating with Viegapex tubing in the community hall, and exhaust ventilation systems for kitchen and bathrooms. Electrical service consists of two 200-amp panels with separate service feeds, and comprehensive LED lighting throughout with emergency lighting in all egress paths. The project design includes specification-grade commercial electrical devices, insulation requirements meeting the 2015 Pennsylvania Energy Code, and various material selections requiring owner approval for color coordination with Phase 1 construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PITTSBURGH
TURNPIKE
PA
70 81
ERIE
LEWISTOWN
CLARION
PHILADELPHIA
HARRISBURG
SCRANTON
No scale
LOCATION MAP
PROJECT
LOCATION
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1" = 1'-0"
/6
/2
:3
:0
P M
CS-101
COVER SHEET -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
TYRONE TOWNSHIP BUILDING PHASE 2
BUILDING & STRUCTUAL PLANS
LOCATED AT
3129 SHERMANS VALLEY ROAD, LOYSVILLE, PA 17047
TYRONE TOWNSHIP, PERRY COUNTY, PA
PREPARED FOR:
FREDERICK, SEIBERT & ASSOCIATES, INC.
PREPARED BY:
BOYLE ENGINEERING, LLC
130 FARM LANE, STATE COLLEGE, PA 16801
BRIDGE | STRUCTURAL | GEOTECHNICAL | CONSTRUCTION
WWW.BOYLE-ENG.COM
814-271-0770
15 EAST MAIN STREET, NEW BLOOMFIELD, PA 17068
JULY 06, 2026
SHEET INDEX
CS-101 - COVER SHEET - PHASE 2
G-101 - CODE ANALYSIS - PHASE 2
G-102 - GENERAL NOTES - PHASE 2
G-103 - LIFE SAFETY PLAN - PHASE 2
G-104 - PHASE KEY & ISOMETRIC
G-105 - ADA & EGRESS DETAILS - PHASE 2
B-101 - FLOOR PLAN - PHASE 2
B-102 - ELEVATIONS - PHASE 2
B-103 - ROOF PLAN - PHASE 2
B-104 - CROSS SECTIONS - PHASE 2
S-101 - FOOTING PLAN - PHASE 2
S-102 - ROOF FRAMING - PHASE 2
S-103 - FOOTING DETAILS - PHASE 2
MEP-101 - MANIFOLD LAYOUT - PHASE 2
MEP-102 - MECHANICAL PLAN - PHASE 2
MEP-103 - ELECTRICAL PLAN - PHASE 2
NO. DESCRIPTION DATE
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
07-06-2026
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
INTERNATIONAL BUILDING CODE - VOLUME DATE: 2018
CHAPTER 3: USE AND OCCUPANCY CLASSIFICATION
PRIMARY BUILDING USE GROUP BUSINESS, GROUP B
ADDITIONAL USE GROUPS LOW-HAZARD STORAGE, GROUP S-2 & ASSEMBLY, GROUP A-3
MOST RESTRICTIVE PROP. USE GROUPS A-3
MIXED OCCUPANCY YES
OCCUPANY SEPERATION SEPERATED
CHAPTER 4: SPECIAL REQUIREMENTS BASED ON USE AND OCCUPANCY
N/A COVERED MALL - 402 N/A HIGH RISE BUILDING - 403 N/A ATRIUM - 404
N/A UNDERGROUND BUILDING - 405 N/A MOTOR VEHICLE - 406 N/A GROUP I2 - 407
N/A GROUP I-3 - 408 N/A MOTION PICTURE PROJECT. ROOM - 409 N/A STAGES & PLATFORMS - 410
N/A SPECIAL AMUSEMENT - 411 N/A AIRCRAFT RELATED - 412 N/A COMBUSTIBLE STORAGE - 413
N/A HAZARDOUS MATERIALS -414 N/A GROUPS H1, H2, H3, H4, H5 - 415 N/A APPLICATION OF FLAMMABLE FINISHES - 416
N/A DRYING ROOMS - 417 N/A ORGANIC COATINGS - 418 N/A LIVE/WORK UNITS - 419
N/A GROUPS I1, R1, R2, R3 - 420 N/A HYDROGEN CUTOFF ROOMS - 421 N/A AMBULATORY CARE - 422
N/A STORM SHELTERS - 423 N/A CHILDRENS PLAY STRUCTURES - 424 N/A COMBUSTIBLE DUST, GRAIN PROCESSING/STORAGE - 426
SPRINKER PROTECTION X NONE NFPA
CHAPTER 5: CONSTRUCTION TYPE & HEIGHT AND AREA LIMITATIONS - TABLE 503
USE GROUP CONSTRUCTION TYPE
X SEPARATED VB
NON-SEPARATED ALLOWABLE PROVIDED
HEIGHT
STORIES
AREA HEIGHT
STORIES
AREA
MOST RESTRICTIVE USE GROUP FT SF FT SF
GROUP: S-2 40 2 13,500 25.1 1 6,133
GROUP: B 40 2 9,000 20.2 1 819
GROUP: A-3 40 1 6,000 20.2 1 5,995
504.3 HEIGHT INCREASE - SPRINKLER
506 AREA MODIFICATIONS
506.2 FRONTAGE INCREASE
TOTAL AREA INCREASE PERMITTED
MAX. PERMITTED HEIGHT & AREA 40 1 28,500 25.1 1 12,947
INCIDENTAL ACCESSORY USES - TABLE 509
ROOM OR AREA SEPARATION AND/OR PROTECTION
FURNACE ROOM > 400,000 BTUH
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
BOILER > 15 SI & 10 HP
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
REFRIGERANT MACHINERY
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
HYDROGEN CUTOFF
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
INCINERATOR ROOMS X NOT APPLICABLE
PAINT SHOPS NOT H, IN OCC. NOT F.
APPLICABLE X NOT APPLICABLE 2 HR OR 1 HR AND AUTOMATIC SPRINKLER…
LAB & VOCATIONAL NOT H IN E
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
LAB NOT H IN I-2
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
LAB NOT IN AMBULATORY CARE
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
LAUNDRY ROOMS > 100 SF
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
LAUNDRY ROOMS > 100 SF IN I-2
APPLICABLE X NOT APPLICABLE 1 HR
GROUP I3 CELLS OR GROUP I2 W/PADDED CEELS OR PATIENT ROOMS
APPLICABLE X NOT APPLICABLE 1 HR
AMBULATORY CARE OR GROUP I2 WASTE/LINEN COLLECTION W/ CONTAINERS > 10 CUBIC FEET
APPLICABLE X NOT APPLICABLE 1 HR
ALL OTHER OCCUPANCIES, WASTE/LINEN OVER 100 PSF
APPLICABLE X NOT APPLICABLE 1 HR OR AUTOMATIC FIRE EXTINGUISHING…
AMBULATORY CARE OR GROUP I2 STORAGE > 100 PSF
APPLICABLE X NOT APPLICABLE 1 HR
STATIONARY BATTERY STORAGE
APPLICABLE X NOT APPLICABLE 1 HR IN B,F,M,S, & U 2 HR IN A,E, I & E
SEPARATED OCCUPANCY - 508.4 X APPLICABLE NOT APPLICABLE
510 SPECIAL PROVISIONS
510.2 HORIZONTAL BUILDING SEPARATION ALLOWANCE
HORIZONTAL ASSEMBLY RATING: 3 HR REQUIRED 3 HR PROVIDED
PODIUM CONSTRUCTION TYPE: IA REQUIRED IA PROVIDED
TOWER CONSTRUCTION TYPE: IIIA REQUIRED IIIA PROVIDED
SHAFT, STAIR & RAMP ENCLOSURES 2 HR REQUIRED 2 HR PROVIDED
PODIUM FULLY SPRINKLERED N/A REQUIRED N/A PROVIDED
SMALLER ALLOWABLE MAX HEIGHT 75 FT REQUIRED 25.1 FT PROVIDED
PROJECT DESCRIPTION:
NEW TOWNSHIP BUILDING FOR TYRONE TOWNSHIP, LOCATED AT 3129 SHERMANS VALLEY ROAD, LOYSVILLE, PA 17047. THIS BUILDING INCLUDES THE TOWNSHIP
OFFICE, A COMMUNITY HALL, AND GARAGES/STORAGE FOR TOWNSHIP VEHICLES.
INTERNATIONAL BUILDING CODE INFORMATION SUMMARY
PROJECT: TYRONE TOWNSHIP BUILDING
COUNTY: PERRY
MUNICIPALITY: TYRONE TOWNSHIP
APPLICABLE CODES:
2018 INTERNATIONAL BUILDING CODE
2018 PENNSYLVANIA FIRE CODE
2015 PENNSYLVANIA ENERGY CODE
2018 PENNSYLVANIA BUILDING PERFORMANCE CODE
2017 PENNSYLVANIA ELECTRICAL CODE
CHAPTER 6: CONSTRUCTION TYPE - TABLE 601
CONSTRUCTION TYPE TYPE: VB
REQUIRED FIRE RESISTANCE RATING
0 HR TYPE VB
0 HR TYPE VB
0 HR TYPE VB
TABLE 602 BELOW
0 HR TYPE VB
0 HR TYPE VB
0 HR TYPE VB
TABLE 602 REQUIREMENTS
FIRE RESISTANCE RATING
1 HR APPLICABLE X NOT APPLICABLE
1 HR APPLICABLE X NOT APPLICABLE
0 HR APPLICABLE X NOT APPLICABLE
0 HR X APPLICABLE NOT APPLICABLE
1 HR APPLICABLE X NOT APPLICABLE
1 HR APPLICABLE X NOT APPLICABLE
0 HR APPLICABLE X NOT APPLICABLE
0 HR X APPLICABLE NOT APPLICABLE
1 HR APPLICABLE X NOT APPLICABLE
1 HR APPLICABLE X NOT APPLICABLE
0 HR APPLICABLE X NOT APPLICABLE
0 HR X APPLICABLE NOT APPLICABLE
CHAPTER 7: FIRE & SMOKE PROTECTION FEATURES
PROPOSED MINIMUM FIRE SEPARATION…
X NONE NFPA 13
FIRE SEPERATION DISTANCE DEGREE OF OPENING PROTECTION ALLOWABLE AREA
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS NOT PERMITTED
APPLICABLE X NOT APPLICABLE UNPROTECTED - S NOT PERMITTED
APPLICABLE X NOT APPLICABLE PROTECTED NOT PERMITTED
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS NOT PERMITTED
APPLICABLE X NOT APPLICABLE UNPROTECTED - S 15%
APPLICABLE X NOT APPLICABLE PROTECTED 15%
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS 10%
APPLICABLE X NOT APPLICABLE UNPROTECTED - S 25%
APPLICABLE X NOT APPLICABLE PROTECTED 25%
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS 15%
APPLICABLE X NOT APPLICABLE UNPROTECTED - S 45%
APPLICABLE X NOT APPLICABLE PROTECTED 45%
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS 25%
APPLICABLE X NOT APPLICABLE UNPROTECTED - S 75%
APPLICABLE X NOT APPLICABLE PROTECTED 75%
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS 45%
APPLICABLE X NOT APPLICABLE UNPROTECTED - S NO LIMIT
APPLICABLE X NOT APPLICABLE PROTECTED NO LIMIT
APPLICABLE X NOT APPLICABLE UNPROTECTED - NS 70%
APPLICABLE X NOT APPLICABLE UNPROTECTED - S NO LIMIT
APPLICABLE X NOT APPLICABLE PROTECTED NO LIMIT
X APPLICABLE NOT APPLICABLE UNPROTECTED - NS NO LIMIT
APPLICABLE X NOT APPLICABLE UNPROTECTED - S NO LIMIT
APPLICABLE X NOT APPLICABLE PROTECTED NO LIMIT
CHAPTER 7: FIRE & SMOKE PROTECTION FEATURES
ITEM REFERENCE SECTION
SHAFT ENCLOSURES SECTION 712 RATING
ESCALATOR IN SPRK. BUILDING 712.1.3 APPLICABLE X NON-APPLICABLE
NON-EXIT STAIR, SPRINKLERED APPLICABLE X NON-APPLICABLE
MIN. RATING 4 OR MORE STORIES 713.4 APPLICABLE X NON-APPLICABLE
MIN. RATING < 4 STORIES 713.4 X APPLICABLE NON-APPLICABLE
REFUSE/LAUNDRY CHUTES 713 APPLICABLE X NON-APPLICABLE
ELEVATOR/DUMBWAITER SHAFT 713 APPLICABLE X NON-APPLICABLE
HOISTWAY PROTECTION - NON-HIGH RISE 3006.2 APPLICABLE X NON-APPLICABLE
EXIT ENCLOSURE 711, 1023.2
MIN RATING 4 OR MORE STORIES 711, 1023.2 APPLICABLE X NON-APPLICABLE
MIN RATING < 4 STORIES 711, 1023.2 X APPLICABLE NON-APPLICABLE
CORRIDOR WALLS 708, 1020.1 APPLICABLE NON-APPLICABLE
TABLE 1020.1 SEE CHAPTER 10 ANALYSIS BELOW
FIRE DOOR & SHUTTER
FIRE WALLS & BARRIERS > 1HR TABLE 716.1 X APPLICABLE NON-APPLICABLE
ENCLOSURES FOR SHAFTS. INTERIOR EXIT
STAIRWAYS AND INTERIOR EXIT RAMPS
TABLE 716.1 APPLICABLE X NON-APPLICABLE
FIRE PARTITIONS INCLUDING CORRIDOR WALLS TABLE 716.1 APPLICABLE NON-APPLICABLE
EXTERIOR WALLS TABLE 716.1 APPLICABLE X NON-APPLICABLE
CHAPTER 8: INTERIOR FINISHES - TABLE 803.13
USE GROUP
INTERIOR EXIT STAIRS, RAMPS AND EXIT
PASSAGEWAYS - NONSPRINKLERED
CORRIDORS AND ENCLOSURE FOR EXIT ACCESS
STAIRWAYS AND RAMPS - FULLY SPRINKLERED
ROOMS AND ENCLOSED SPACES - FULLY SPRINKLERED
A-3 CLASS A CLASS A CLASS C
B CLASS A CLASS B CLASS C
S-2 CLASS B CLASS B CLASS C
CHAPTER 9: FIRE PROTECTION SYSTEMS
REFER TO FIRE PROTECTION DRAWINGS, FIRE ALARM DRAWINGS, AND ELECTRICAL DRAWINGS
ITEM REFERENCE SECTION
FIRE EXTINGUSIHERS 906.3 (1)
ORDINARY (MODERATE) HAZARD
OCCUPANCY
MINIMUM RATED SINGLE EXTINGUISHER MAX FLOOR AREA PER UNIT A MAX FLOOR AREA PER EXTINGUISHER MAXIMUM TRAVEL DISTANCE TO FE
2-A 1,500 SF 11,250 SF 75 FT
CHAPTER 10: MEANS OF EGRESS
OCCUPANT LOAD, TABLE 1004.5
OCCUPANCY PERSON LOAD FACTOR SF
OCCUPANT LOAD PER
OCCUPANCY
KITCHEN 200 GROSS PERSONS 909 5
PRIMARY STRUCTURAL FRAME
BEARING WALL - EXTERIOR
BEARING WALL - INTERIOR
NONBEARING WALL - INTERIOR
NONBEARING WALL - EXTERIOR
FLOOR CONST. & ASS. MEMBERS
ROOF CONST. & ASS. MEMBERS
CONSTRUCTION TYPE OCCUPANCY
TYPE VB A-3
TYPE VB B
TYPE VB S-2
FIRE SEPARATION DISTANCE
X < 5b
5 ≤ X ≤ 10
10 ≤ X ≤ 30
X ≥ 30
X < 5b
5 ≤ X ≤ 10
10 ≤ X ≤ 30
X ≥ 30
X < 5b
5 ≤ X ≤ 10
10 ≤ X ≤ 30
X ≥ 30
0 TO LESS THAN 3
3 TO LESS THAN 5
5 TO LESS THAN 10
10 TO LESS THAN 15
15 TO LESS THAN 20
25 TO LESS THAN 30
20 TO LESS THAN 25
30 OR GREATER
TOWNSHIP OFFICE 150 GROSS PERSONS 402 3
X
X
LOBBY/COMMUNITY HALL 15 NET PERSONS 4213 281
UTILITY ROOM 300 GROSS PERSONS 214 1
SUPPLY ROOM 500 GROSS PERSONS 389 1
GARAGE 500 GROSS PERSONS 5691 12
TOTAL 12201 306
EXIT ACCESS TRAVEL DISTANCE, TABLE 1017.2
OCCUPANCY USE GROUP ALLOWABLE - FT ACTUAL - FT (WORST CASE)
STORAGE, GROUP S-2 300 129.33
BUSINESS, GROUP B 200 84
ASSEMBLY, GROUP A-3 200 101.67
DEAD ENDS - S-2, B, & A-2 20 0
REFERENCE FOLLOWING LIFE SAFETY PLANS AND TABLES
ACCESSIBLE MEANS OF EGRESS SECTION 1009
REQUIRED ACC. MEANS OF … SECTION 1009.1 X APPLICABLE NON-APPLICABLE
ACC. ELEVATORS > 4 STORIES SECTION 1009.2.1 APPLICABLE X NON-APPLICABLE
ELEVATOR AREA OF REFUGE SECTION 1009.4 APPLICABLE X NON-APPLICABLE
ACC. STAIRS MIN 48" W/ AREA
OF REFUGE
SECTION 1009.3 APPLICABLE X NON-APPLICABLE
MIN 48" WIDTH 1009.3 APPLICABLE X NON-APPLICABLE
AREA OF RUFUGE 1009.3 APPLICABLE X NON-APPLICABLE
CORRIDORS
RATING FOR SPRKLR BLG X SECTION 1020 0 HR REQUIRED 0 HR PROVIDED
CHAPTER 11: ACCESSIBLITY
PARKING AND PASSENGER
LOADING FACILITIES
SECTION 1106.1 70 REQUIRED 81 PROVIDED
BASED ON X
SPACES
ACCESSIBLE DWELLING AND
SLEEPING UNITS
SECTION 1107 0 REQUIRED 0 PROVIDED
SPECIAL OCCUPANCIES SECTION 1108 0 REQUIRED 0 PROVIDED
ACCESSIBLE RAMPS SECTION 1012 0 REQUIRED 0 PROVIDED
CHAPTER 29 - FIXTURE CALCULATIONS - SEE TABLE 2902.1
M
WATERCLOSETS TABLE 2902.1
2 REQUIRED 2 PROVIDED SEE IPC 2018, SECTION 424.2
F 2 REQUIRED 3 PROVIDED
TABLE 2902.1 0 REQUIRED 1 PROVIDED SEE IPC 2018, SECTION 424.2M URINALS
M
LAVATORIES TABLE 2902.1
2 REQUIRED 2 PROVIDED
F 2 REQUIRED 2 PROVIDED
N/A REQUIRED 1 PROVIDEDU
DRINKING FOUNTAINS TABLE 2902.1 1 REQUIRED 2 PROVIDED
SERVICE SINK TABLE 2902.1 1 REQUIRED 1 PROVIDED
2015 IECC REQUIREMENTS
COUNTY CLIMATE ZONE 5A
TABLE C402.1.3 REQUIREMENTS
ROOF - INSULATION ABOVE DECK
INSULATION ABOVE DECK R-30CI REQUIRED PROVIDED
WALLS ABOVE GRADE
MASS R-20 REQUIRED PROVIDED
WALLS BELOW GRADE
MASS R-7.5CI REQUIRED PROVIDED
SLAB ON GRADE
UNHEATED R-10 FOR 24" BELOW REQUIRED PROVIDED
HEATED R-15 FOR 24" BELOW REQUIRED PROVIDED
OPAQUE DOORS
NON-SWINGING R-4.75 REQUIRED PROVIDED
PERRY
N/A REQUIRED 1 PROVIDEDU
CONFERENCE ROOM 150 GROSS PERSONS 3417
R-30CI
R-20
R-7.5CI
R-10 FOR 24" BELOW
R-15 FOR 24" BELOW
R-4.75
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1/2" = 1'-0"
/6
/2
:3
:0
P M
G-101
CODE ANALYSIS -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
/6
/2
:3
:0
P M
G-102
GENERAL NOTES -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
PROPERTY OWNER:
TYRONE TOWNSHIP
P.O. BOX 116
LANDISBURG, PA 17040
CONTACT: MICHAEL SHEAFFER
PHONE: (717) 789-4377
DEFFERED SUBMISSION:
-TRUSS PLAN DESIGNED PER INDICATED LOADS, &
FOLLOWING NOTE 9.
STRUCTURAL DESIGN CRITERIA:
A. CODES, STANDARDS, AND REFERENCES
1. INTERNATIONAL BUILDING CODE, IBC 2018
2. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, ASCE 7-16
3. BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, ACI 318-14.
4. BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES, ACI 530-13.
B. DESIGN LOADS
1. GRAVITY LOADS:
ALL DEAD AND LIVE LOADS ARE DETERMINED IN ACCORDANCE WITH THE IBC 2018 AND ASCE 7. DEAD LOADS ARE BASED ON THE ACTUAL WEIGHT OF CONSTRUCTION AND BUILDING MATERIALS. NO REDUCTIONS TO
ROOF LIVE LOAD.
2. SNOW LOADS
THE SNOW LOADS PRESENTED HERE ARE CALCULATED BASED ON ASCE 7-16.
RISK CATEGORY: II (TABLE 1.5-1, ASCE 7-16)
IMPORTANCE FACTOR: 1.0 (TABLE 1.5-2, ASCE 7-16)
GROUND SNOW LOAD, Pg: 30 PSF (FIGURE 7.2-1, ASCE 7-16) SNOW EXPOSURE FACTOR, Ce: 0.9 (TABLE 7.3-1, ASCE 7-16) THERMAL FACTOR, Ct: 0.9 (TABLE 7.3-2, ASCE 7-16) SLOPED ROOF SNOW LOAD, Ps: 18.9 PSF ADDITIONAL LOCALIZED LOADS FROM SNOW DRIFTS ARE CONSIDERED IN THE DESIGN OF LOWER ROOFS.
3. WIND LOADS
THE WIND LOADS PRESENTED HERE ARE CALCULATED BASED ON ASCE 7-16.
RISK CATEGORY: II (TABLE 1.5-1, ASCE 7-16)
BASIC WIND SPEED (MRI = 1,700 YEARS): 115 MPH (FIGURE 26.5-1B, ASCE 7-16)
SURFACE ROUGHNESS CATEGORY: C (26.7.2, ASCE 7-16)
EXPOSURE CATEGORY: C (26.7.3, ASCE 7-16)
WIND DIRECTIONALUTY FACTOR, Kd: 0.85 (TABLE 26.6-1, ASCE 7-16)
INTERAL PRESSURE COEFFICIENT: +/- 0.18 (TABLE 26.13-1, ASCE 7-16)
4.. SEISMIC LOADS
SEISMIC LOADS ARE DETERMINED IN ACCORDANCE WITH ASCE 7-16.
RISK CATEGORY: II (TABLE 1.5-1, ASCE 7-16)
IMPORATANCE FACTOR: 1.0 (TABLE 1.5-2, ASCE 7-16)
SITE CLASS: D (20.1, ASCE 7-16)
SEISMIC DESIGN CATEGORY: A (TABLE 11.6-1 & TABLE 11.6-2, ASCE 7-16)
5.STABILITY
THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER IS FULLY COMPLETED.
CONSTRUCTION MEANS AND METHODS ARE SOLELY THE CONTRACTOR'S RESPONSIBILITY. THE
CONTRACTOR MUST DETERMINE DEMOLITION AND ERECTION PROCEDURE AND SEQUENCE, WHICH WILL ENSURE THE STABILITY OF THE BUILDING DURING ALL STAGES OF DEMOLITIION AND CONSTRUCTION. SUCH MEANS AND METHODS ARE NOT SHOWN WITHIN THE PLANS AND ARE SOLELY THE RESPONSIBILITY OF THE
CONTRACTOR.
6. FOUNDATIONS
BOTTOM OF FOOTING ELEVATION (BFE) SHALL BE AS INDICATED.
A BEARING CAPACITY OF 3,000 PSF FOR FOOTING DESIGN HAS BEEN ASSUMED. IF SOIL CAPACITY IS NOT ENCOUNTERED AT ELEVATIONS INDICATED IN THE PLANS, FOOTING SHALL BE INCREASED IN SIZE OR
LOWERED AS DIRECTED BY THE ENGINEER,
7. CONCRETE
ALL CONCRETE WORK SHALL CONFROM TO ALL REQUIREMENTS OF THE CURRENT ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE" AND ACI 117 "STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE
CONSTRUCTION AND MATERIALS" WITH THE FOLLOWING SUPPLEMENT REQUIREMENTS:
ALL CONCRETE SHALL BE NORMAL WEIGHT WITH TYPE I OF TYPE II PORTLAND CEMENT CONFORMING TO ASTM
C150 AND AGGREGATES CONFROMING TO ASTM C33.
LOCATION - FOOTING & FOUNDATION WALLS 28-DAY STRENGTH - 3,500 PSI W/C - 0.55 AIR CONTENT - 4%-6%
FIBER - NONE REBAR - AS INDICATED IN PLANS
LOCATION - SLAB 28-DAY STRENGTH - 4,000 PSI W/C - 0.55 AIR CONTENT - 4%-6%
FIBER - YES REBAR - AS INDICATED IN PLANS
MINIMUM CLEAR CONCRETE COVERS AS FOLLOWS:
CONCRETE CAST AGAINST EARTH - 3"
CONCRETE EXPOSED TO WEATHER: #5 & SMALLER, ALL WWF - 1-1/2"
#6 & LARGER - 2"
CONCRETE NOT EXPOSED TO WEATHER - 3/4"
CONCRETE SHALL BE PLACED AT THE SITE WITHIN 90 MINUTES AFTER WATER HAS BEEN ADDED TO THE CEMENT AND CONCRETE. ADDITIONAL WATER TO THE CONCRETE MIX AT THE SITE IS NOT ALLOWED. ALL WATER MUST BE
ADDED AT THE BATCH PLANT.
MAXIMUM SLUMP SHALL BE 4" ± 1", AS DETERMINED IN ACCORDANCE WITH ASTM C143.
ALL CONCRETE SURFACES SHALL BE BROOM FINISHED.
8. WOOD FRAMING
ALL WOOD CONSTRUCTION SHALL CONFORM TO ALL REQUIREMENTS OF THE "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION", ANSI/AF&PA NDS (INCLUDING SUPPLEMENT "DESIGN VALUES FOR WOOD CONSTRUCTION") AND " NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS
CONSTRUCTION", ANSI/TPI1, TRUSS PLATE INSTITUTE (TPI).
ALL WOOD FRAMING IN DIRECT CONTACT WITH CONCRETE, EXPOSED TO WEATHER, OR WITHIN 8" OF EXPOSED
GROUND SHALL BE PRESSURE TREATED.
ALL FASTENERS IN CONTACT WITH TREATED WOOD SHALL BE HOT-DIPPED GALVANIZED UNLESS STATED
OTHERWISE.
FASTERNER TYPE, NUMBER, AND NOMINAL SIZE SHALL BE PER IBC 2304.10.
9. WOOD TRUSSES
CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN, FABRICATION, & ERECTIONS OF THE WOOD TRUSSES.
TRUSS CONFIGURATIONS SHOWN ARE EXAMPLES ONLY.
TRUSS SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
STATE OF THE PROJECT.
NO INCREASE IN ALLOWABLE STRESS, PLATE INCREASE, LUMBER INCREASE, REPETITIVE STRESS INCREASE, OR
ANY OTHER TYPES OF LOAD REDUCTION OR STRESS INCREASES WILL BE PERMITTED.
TRUSS DESIGN SHALL INCLUDE ALL TEMPORARY & PERMANENT BRACING.
10. METAL PANELS
ALL ROOF & WALL SHEATHING SHALL BE 29 GAUGE (OR THICKER GAUGE) CORRUGATED METAL PANELS WITH
MAJOR RIBS SPACED AT 9" O/C.
FASTENERS SHALL BE #10 X 1-1/2" SCREWS.
TRIM PIECES AND GUTTERS SHALL BE INSTALLED PER TRIM MANUFACTURERS SPECIFICATIONS.
OWNER SHALL SELECT COLOR OF METAL PANELS, TRIM, GUTTERS, & DOWNSPOUTS.
ALL ROOF & SIDING TRIM SHALL BE METAL.
MATERIAL TESTING CRITERIA:
CONCRETE
MATERIAL TESTS SHALL CONFORM TO IBC 2018 SECTIONS 1705.3.2 & 1903.
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
FRZ
WH
WH
R a n g e
SD
SD
SD
SD
SD
SD
SD
MAX TRAVEL DISTANCE = 101'-8"
MAX ALLOWABLE TRAVEL DISTANCE = 200' (ASSEMBLY)
KITCHEN AREA
TOWNSHIP OFFICE
CONFERENCE
ROOM
MEN'S
RESTROOM
WOMEN'S
RESTROOM
UTILITY ROOM
SUPPLY ROOM
GARAGE AREA
UNISEX
RESTROOM
WASH BAY
SAFETY BOLLARD (TYP)
ACCESSIBLE ENTRANCE
ACCESSIBLE ENTRANCE
ACCESSIBLE ENTRANCE
ACCESSIBLE ENTRANCE
ACCESSIBLE ENTRANCE
ACCESSIBLE ENTRANCE
LOBBY
SD
MAX TRAVEL DISTANCE = 84'-0"
MAX ALLOWABLE TRAVEL DISTANCE
= 200' (BUSINESS)
SD
MAX TRAVEL DISTANCE = 129'-4"
MAX ALLOWABLE TRAVEL DISTANCE = 300' (STORAGE)MAX TRAVEL DISTANCE = 59'-1"
MAX ALLOWABLE TRAVEL DISTANCE = 200' (ASSEMBLY)
COMMUNITY HALL
SD
SD
LIFE SAFETY FIXTURES SPEFICIATIONS
FIXTURE DESCRIPTION
SMOKE DETECTOR
ULINE H-9466 "SMOKE DETECTOR - LITHIUM
BATTERY" OR APPROVED EQUIVALENT
SYMBOL LEGEND
SD
- SMOKE DETECTOR
- PATH OF TRAVEL
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:0
P M
G-103
LIFE SAFETY PLAN -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
LIFE SAFETY PLAN - COMMUNITY HALL
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
WH
R a n g e
PHASE 1
PHASE 2
PHASE 3
PHASE 1 - IS EXCLUDED FROM THIS PLAN SET & ASSUMED TO HAVE BEEN COMPLETED
PHASE 2 - SHOWN AND DETAILED IN THESE PLANS
PHASE 3 - IS EXCLUDED FROM THIS PLAN SET & ARE TO BE COMPLETED AT A FUTURE TIME.
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1/16" = 1'-0"
/6
/2
:3
:0
P M
G-104
PHASE KEY &
ISOMETRIC
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/16" = 1'-0"
FLOOR PLAN - PHASE KEY
PHASE 1
PHASE 1 & PHASE 2
PHASE 2
ALL PHASES
PHASE 3
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
M A
X
M A
X
10" - 24" MAX
M A
X
M A
X
10" MAX
M A
X
10" MAX
M
IN
>20 - 25" MAX
M A
X
20" MAX
M A
X
M
IN
M A
X
R E
A C
H R
A N
G E
S
S
ID
E A
P P
R O
A C
H R
E A
C H
R A
N G
E S
F
R O
N T
A P
P R
O A
C H
ACCESSIBLE REACH RANGES: REFER TO ICC/ANSI A117.1-2017, SECTION 308
NOTE:
WATER SUPPLY & DRAIN
PIPES UNDER LAVATORIES
AND SINKS SHALL BE
INSULATED OR OTHERWISE
CONFIGURED TO PROTECT
AGAINST CONTACT
11" 6"
M A
X
M A
X
IDENTIFICATION SIGNS
1. CHARACTERS AND IDENTIFICATION SYMBOLS ARE TO BE DISTINCLY DIFFERENT FROM THE BACKGROUND IN COLOR
AND CONTRAST.
2. LETTER AND NUMBERS ON SIGNS SHALL BE RAISED 1/32" MIN. SHALL BE A MIN. 5/8" HIGH AND MAX OF 2" HIGH.
CHARACTERS SHALL BE UPPERCASE AND SANS-SERIF ACCOMPANIED BY GRADE 2 BRAILLE.
3. PROVIDE IDENTIFICATION SIGN ON WALL TO LATCH SIDE OF DOOR. WHERE SIGNS ARE PROVIDED AT DOUBLE DOORS.
THE SIGN SHALL BE TO THE RIGHT OF THE RIGHT HAND DOOR. WHERE NO WALL SPACE IS AVAILABLE SIGNS SHALL BE
ON THE NEAREST ADJACENT WALL. SEE SIGN MOUNTING LOCATION AT DOORS.
4. TACTILE CHARACTERS SHALL BE 48" MIN. ABOVE THE FLOOR, MEASURED TO THE BASELINE OF THE LOWEST TACTILE CHARACTER AND 60" MAX. ABOVE THE FLOOR, MEASURED TO THE BASELINE OF THE HIGHEST TACTILE CHARACTER.
PROVIDE TACTILE SIGNS FOR ALL EGRESS EXITS AND HANDICAP ACCESSIBLE RESTROOMS
EXIT
M
IN
M
A X
TEXT
TEXT
FINISHED FLOOR
IDENTIFACTION SIGN
(SEE NOTE 3 FOR LOCATION)
12" MAX
42" MIN
54" MIN
39" - 41"
M
IN
M
IN
ACCESSIBLE
LAVATORY
GRAB BARS TOILET TISSUE
DISPENSER
GRAB BARS
WATER CLOSET
MIN
12"
MIN
24"
36" MIN
M
IN
C
L R
15" MIN
M A
X
ACCESSIBLE WATER CLOSET & MOUNTING HEIGHTS:
GENERAL ACCESSIBILITY RULES:
ENTRANCES & DOOR:
1. EVERY REQUIRED ACCESIBLE ENTRANCE OR PASSAGE DOORWAY, SHALL HAVE A MINUMUM OF 32 INCHES OF CLEAR
WIDTH.
2. DOORS SHALL BE CAPABLE OF OPENINGS AT LEAST 90 DEGREES AND SHALL BE MOUNTED SO THAT THE CLEAR
WIDTH OF THE DOORWAY IS NOT LESS THAN 32 INCHES.
3. LATCHING ON LOCKING DOORS THAT ARE HAND ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL, SHALL BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE HARDWAREOR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE
WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING HARDWARE.
4. LEVER HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 34 INCHES AND 48 INCHES
MAXIMUM ABOVE THE FLOOR.
5. THE FLOOR OR LANDING LENGTH ON EACH SIDE OF AN ENTRANCE OR PASSAGE DOOR SHALL BE LEVEL AND CLEAR AT LEAST 60 INCHES IN THE DIRECTION OF THE DOOR SWING, AND AT LEAST 48 INCHES OPPOSITE THE DIRECTION OF THE DOOR SWING AS MEASURED A RIGHT ANGLES TO THE FACE OF THE DOOR IN THE CLOSED POSITION THE SIDE OF THE LEVEL AND CLEAR AREA ON THE SIDE WHICH THE DOOR SWINGS SHALL EXTEND A MINIMUM OF 18 INCHES (24 INCHES AT EXTERIOR DOORS) PAST THE STRIKE EDGE OF THE DOOR FOR DOORS WITH FRONT APPROACH, 24 INCHES FOR DOORS REQUIRING LATCH SIDE APPROACH, AND 36 INCHES FOR DOORS WITH HINGE SIDE APPROACH REFER TO
DETAIL NO. 3 ON TIS DRAWING FOR ADDITIONAL CLEARANCE REQUIREMENTS.
6. THE FLOOR OR LANDING SHALL NOT BE MORE THAN ½ INCH LOWER THAN THE THRESHOLD OF THE DOORWAY CHANGES IN LEVEL BETWEEN ¼ INCH AND ½ INCH SHALL BE LEVELED WITH A SLOPE NOT GREATER THAN 1-2.
7. THE MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 8.5 LBS. FOR EXTERIOR DOORS AND 5 LBS. FOR INTERIOR DOORS, SUCH PULL OR PUSH EFFORT SHALL BE APPLIED AT RIGHT ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF SLIDING OR FOLDING DOORS WHEN FIRE DOORS ARE REQUIRED, THE MAXIMUM EFFORT TO
OPERATE THE DOOR MAY NOT EXCEED 15 LBS.
STAIRS, RAILINGS & HANDRAILS:
1. STAIRS MUST HAVE AT LEAST CLEAR 36 INCHES IN WIDTH AND ALL SURFACES SHALL BE SLIP-RESISTANT.
2. THE TOP OF THE HANDRAILS AT STAIRWAYS SHALL BE 34 INCHES TO 38 INCHES ABOVE THE NOSING OF THE TREADS.
3. HANDRAILS ARE REQUIRED ON RAMPS WHEN THE SLOPE EXCEEDS 1:20. HANDRAILS SHALL RUN ALONG BOTH SIDES OF A RAMP, BE CONTINUOUS THE FULL LENGTH, AND SHALL FOLLOW THE SLOPE OF THE RAMP.
4. THE GRIP SURFACE OF HANDRAILS SHALL BE BETWEEN 1 ¼” AND 2” IN CROSS SECTIONAL DIMENSION OR THE SHAPE SHALL PROVIDE AN EQUIVALENT, SMOOTH GRIPPING SURFACE WITH NO SHARP CORNERS. ALL HANDRAIL ENDS SHALL
BE RETURNED OR SHALL TERMINATE IN NEWEL POSTS.
5. RAILINGS SHALL NOT HAVE OPENINGS WHICH ALLOWS PASSAGE OF A SPHERE OF 4" IN DIAMETER.
GRAB BARS:
1. GRAB BARS SHALL BE LOCATED ON ONE SIDE AND THE BACK OF THE PHYSICALLY DISABLED TOILET STALL OR COMPARTMENT AND SHALL BE SECURELY ATTACHED 35 INCHES ABOVE AND PARALLEL TO THE FLOOR. THESE SHALL BE AT LEAST 42 INCHES LONG WITH THE FRONT END POSITIONED 24 INCHES FROM THE FRONT OF THE WATER CLOSET.
GRAB BARS AT THE BACK SHALL NOT BE LESS THAN 36 INCHES LONG.
2. THE DIAMETER OR WIDTH OF THE GRIPPING SURFACES OF A GRAB BAR SHALL BE BETWEEN 1-1/4 AND 2 INCHES OR THE SHAPE SHALL PROVIDE AN EQUIVALENT GRIPPING SURFACE. IF THE GRAB BARS ARE MOUNTED ADJACENT TO THE
WALL, THE SPACE BETWEEN THE WALL AND THE GRAB BARS SHALL BE 1-1/2 INCHES.
3. GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS AND SHALL BE DESIGNED TO SUPPORT A 250-POUND FORCE.
ELECTRICAL REQUIREMENTS:
1. THE CENTER OF RECEPTACLE OUTLETS SHALL BE NOT LESS THAN 13 INCHES ABOVE THE FLOOR OR WORKING
PLATFORM.
2. THE CENTER OF THE GRIP OF THE OPERATING HANDLE OF SWITCHES INTENDED TO BE USED BY OCCUPANTS OF A ROOM OR AREA TO CONTROL LIGHTING AND RECEPTACLE OUTLETS, APPLIANCES, OR COOLING, HEATING, AND VENTILATION EQUIPMENT, SHALL BE NOT LESS THAN 36 INCHES NOR MORE THAN 48 INCHES ABOVE THE FLOOR OR
WORKING PLATFORM.
6" MAX
24" MIN
PAPER TOWEL DISPENSER
SOAP DISPENSER
(T Y
P
42" MIN
42" MAX
FINISHED FLOOR4
M
A X
T
O C
/T O
F C
O N
T R
O L
M
IN
FINISHED GRADE
E X
T E
R
IO
R W
A L L
2' - 0"
E X
T E
R
IO
R W
A L L
18" MIN
M
IN
CENTERED ON TACTILE
CHARACTERS
RAMPS WALKING
SURFACES
STAIRS
HANDRAIL HEIGHTS:
HANDRAIL CLEARANCE:
1 1/2" MIN
HANDRAIL EXTENSIONS:
TOP HANDRAIL
EXTENSIONS AT STAIRS
12" MIN 12" MIN
TOP & BOTTOM HANDRAIL
EXTENSIONS AT RAMPS
X= TREAD DEPTH
BOTTOM HANDRAIL
EXTENSIONS AT STAIRS
REFER TO ICC/ANSI A117.1-2017
1 1/4" - 2"
FIG. 505.5 & 505.7 FIG. 505.10.2 FIG. 505.10.1 FIG. 505.10.3FIG. 505.4
12" MIN
X X
HANDRAIL CROSS
SECTION
(MAX)
0' - 11"
(M A
X
" OPENINGS SHALL NOT ALLOW PASSAGE OF A 6"
DIAMETER SPHERE
OPENINGS SHALL NOT ALLOW PASSAGE
OF A SPHERE 4-3/8" IN DIAMETER
(ABOVE HANDAIL)
OPENINGS SHALL NOT ALLOW PASSAGE OF A
4" DIAMETER SPHERE (BELOW HANDRAIL)
M
IN
T
O
HANDRAIL
M
IN
30" MIN
3 1/2" MAX
PARALLEL APPROACH
(FOR FOUNTAINS PRIMARILY FOR
CHILDREN'S USAGE)
FORWARD APPROACH
52" MIN
M
IN
5" MAX 15" MIN
DRINKING FOUNTAIN NOTES:
SPOUT OUTLET:
SPOUTS OF WHEELCHAIR ACCESSIBLE DRINKING FOUNTAINS SHALL BE
36" MAX ABOVE THE FINISHED FLOOR ELEVATION. SPOUTS OF
STANDING DRINKING FOUNTAINS SHALL BE 38" MIN TO 43" MAX ABOVE
FLOOR.
SPOUT LOCATION:
THE SPOUT IS TO BE LOCATED 15" MIN FROM THE VERTICAL SUPPORT
AND 5" MAX FROM THE FRONT EDGE OF THE DRINKING FOUNTAIN,
INCLUDING ALL BUMPERS. WHERE PARALLEL APPROACH IS THE
APPROACH PROVIDED, THE SPOUT SHALL BE LOCATED 3-1/2" MAX
FROM THE FRONT EDGE OF THE DRINKING FOUNTAIN, INCLUDING ALL
BUMPERS.
WATER FLOW:
THE SPOUT SHALL PROVIDE WATER FLOW OF 4" MIN IN HEIGHT. THE
ANGLE OF THE WATER STREAM FROM THE SPOUT WITHIN 3" OF THE
FRONT OF THE DRINKING FOUNTAIN SHALL BE 30 DEG MAX AND FROM
SPOUTS BETWEEN 3" AND 5" FROM THE FRONT OF THE DRINKING
FOUNTAIN SHALL BE 15 DEG MAX, MEASURED HORIZONTALLY RELATIVE
TO THE FRONT FACE OF THE DRINKING FOUNTAIN.
SIGN LEGEND
SIGN 1 (EXIT SIGN WITH
TACTILE CHARACTERS)
SIGN 2 (ADA ACCESIBLE RESTROOM /
MEN'S RESTROOM)
SIGN 3 (ADA ACCESIBLE RESTROOM /
WOMEN'S RESTROOM)
SIGN 4 (ADA ACCESIBLE RESTROOM /
UNISEX RESTROOM)
SIGN 5 (ADA ACCESIBLE SHOWER /
UNISEX SHOWER-ROOM)
M
IN
60" MIN
FLOOR MOUNTED
WATER CLOSET
M
IN
4" MAX 56" MIN
FLOOR MOUNTED
WATER CLOSET
M
IN
35" - 37"
M
IN
17" - 19"
FORWARD APPROACH
52" MIN
M
IN 1
CLEAR FLOOR SPACE - NEW BUILDINGS:
IN NEW BUILDINGS AND FACILITIES, THE CLEAR FLOOR SPACE SHALL
BE 52" MIN IN LENGTH AND 30" MIN IN WIDTH
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:0
P M
G-105
ADA & EGRESS
DETAILS
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/2" = 1'-0"
IDENTIFICATION SIGNS ELEVATION -
PHASE 2
1/2" = 1'-0"
FIRE EXTINGUISHER MOUNTING -
PHASE 2
1/2" = 1'-0"
BOLLARD DETAIL - PHASE 2
1/2" = 1'-0"
ANSI SIGNAGE DETAIL - PHASE 2
1/2" = 1'-0"
IBC GUARDS ON STAIRS & STAIRS -
PHASE 2
1/2" = 1'-0"
ADA WATER FOUNTAIN APPROACH -
PHASE 2
ANSI 117.1-703.10 "HEIGHT ABOVE FLOOR"
1. TACTILE CHARACTERS SHALL BE 48" MIN
ABOVE THE FLOOR MEASURED TO THE BASELINE
OF THE LOWEST TACTILE CHARACTER AND 60"
MAX ABOVE THE FLOOR MEASURED TO THE
BASELINE OF THE HIGHEST TACTILE CHARACTER.
ANSI 117.1-703.11 "LOCATION"
1. WHERE A TACTILE SIGN IS PROVIDED AT A
DOOR, THE SIGN SHALL BE ALONGSIDE THE
DOOR AT THE LATCH SIDE.
2. WHERE A TACTILE SIGN IS PROVIDED AT
DOUBLE DOORS WITH ONE ACTIVE LEAF. THE
SIGN SHALL BE LOCATED ON THE INACTIVE LEAF.
3. WHERE A TACTILE SIGN IS PROVIDED AT
DOUBLE DOORS WITH ACTIVE LEAVES. THE SIGN
SHALL BE TO THE RIGHT OF THE RIGHT-HAND
DOOR.
4. WHERE THERE IS NO WALL SPACE ON THE
LATCH SIDE OF THE SIGNAL DOOR, OR ON THE
RIGHT SIDE OF DOUBLE DOORS SIGNS SHALL BE
ON THE NEAREST ADJACENT WALL.
5. SIGNS CONTAINING TACTILE CHARACTERS
SHALL BE LOCATED SO THAT A CLEAR FLOOR
AREA 18" MIN BY 18" MIN CENTERED ON TACTILE
CHARACTERS IS PROVIDED BEYOND THE ARC OF
ANY DOOR SWING BETWEEN CLOSED POSITION
AND 45 DEGREE OPEN POSTION.
GUARDRAIL NOTES:
1. GUARDRAILS AND HANDRAILS SHALL BE THE PRODUCT OF A COMPANY NORMALLY ENGAGED IN THE MANUFACTURE OF PIPE RAILING.
RAILING SHALL BE SHOP ASSEMBED IN LENGTHS NOT TO EXCEED 24 FEET FOR FIELD ERECTION.
2. THE HANDRAIL SHALL BE MADE OF PIPES JOINED TOGETHER WITH COMPONENT FITTINGS. SAMPLES OF ALL COMPONENTS, BASES, TOE PLATES, AND PIPE SHALL BE SUBMITTED FOR APPROVAL AT THE REQUEST OF THE ENGINEER. COMPONENTS THAT ARE POP-RIVETED OR GLUED AT THE JOINTS WILL NOT BE ACCEPTABLE. ALL COMPONENTS MUST BE MECHANICALLY FASTENED WITH STAINLESS STEEL
HARDWARE.
3. RAILINGS SHALL BE 1 1/4" SCHEDULE 40 ALUMINUM PIPE ALLOY 6105-T5, ASTM-B-429 OR ASTM-B-221.
4. GUARDRAILS AND HANDRAILS SHALL BE DESIGNED TO WITHSTAND A 200 LB CONCENTRATED LOAD APPLIED IN ANY DIRECTION AND AT ANY POINT ON THE TOP RAIL. GUARDRAILS AND HANDRAILS SHALL ALSO BE DESIGNED TO WITHSTAND A UNIFORM LOAD OF 50 LB/FT APPLIED HORIZONTALLY TO THE TOP RAIL. UNIFORM LOADS ARE NOT TO BE APPLIED SIMULTANEOUSLY WITH THE CONCENTRATED LOADS.
5. BALLASTS AND INTERMEDITATE RAILING SHALL BE DESIGNED TO WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50 LB ON AN
AREA NOT TO EXCEED 1 SQFT INCLUDING OPENINGS AND SPACE BETWEEN RAILS.
6. THE MANUFACTURER SHALL SUBMIT CALCULATIONS FOR APPROVAL AT THE REQUEST OF THE ENGINEER. TESTING OF BASE CASTINGS OR BASE EXTRUSIONS BY AN INDEPENDENT LAB OR MANUFACTURER'S LAB (IF THE LAB MEETS THE REQUIREMENTS OF THE ALUMINUM ASSOC.) WILL BE AN ACCEPTABLE SUBSTITUTE FOR CALCULATIONS. CALCULATIONS WILL BE REQUIRED FOR APPROVAL OF ALL OTHER
DESIGN ASPECTS.
7. POSTS SHALL NOT INTERRUPT THE CONTINUATION OF THE TOP RAIL AT ANY POINT ALONG THE RAILING, INCLUDING CORNERS AND END TERMINATIONS (OSHA 1910.23). THE TOP SURFACE OF THE TOP RAILING SHALL BE SMOOTH AND SHALL NOT BE INTERRRUPTED BY
PROJECTED FITTINGS.
8. CONCRETE ANCHORS SHALL BE STAINLESS STEEL TYPE 303 OR 304 WEDGE ANCHORS AND SHALL BE FURNISHED BY THE HANDRAIL MANUFACTURER. THE ANCHOR DESIGN SHALL INCLUDE THE APPROPRIATE REDUCTION FACTORS FOR SPACING AND EDGE DISTANCES IN
ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED DATA.
9. OPENINGS IN THE RAILING SHALL BE GUARDED BY A SELF-CLOSING GATE (OSHA 1910.23). SAFETY CHAINS SHALL NOT BE USED UNLESS
SPECIFICALLY SHOWN ON THE DRAWINGS.
10. FINISH SHALL BE ALUMINUM ASSOCIATION M10-C22-A41 (215-R1). THE PIPE SHALL BE PLASTIC-WRAPPED. THE PLASTIC WRAP IS TO BE
REMOVED AFTER ERECTION.
11. ALUMINUM SURFACES IN CONTACT WITH CONCRETE, GROUT OR DISSIMILAR METALS WILL BE PROTECTED WITH A COAT OF BITUMINOUS
PAINT, MYLAR ISOLATORS OR OTHER APPROVED MATERIAL.
1/4" = 1'-0"
SIGN LEGEND - PHASE 2
NTS
NTS NTS
NTS NTS NTS
NTS
1/2" = 1'-0"
WHEELCHAIR ACCESSIBLE TOILET
COMPARTMENT - PHASE 2
NTS 1/2" = 1'-0"
AMBULATORY ACCESSIBLE TOILET
COMPARTMENT - PHASE 2
NTS
1/2" = 1'-0"
ADA CLEAR FLOOR SPACE - PHASE 2
NTS
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
WH
R a n g e
KITCHEN AREA*
909 SQUARE FEET
± 14' - 0" ± 22' - 0" ± 14' - 0"
± 50' - 0"
/2
/2
/2
/2
± 48' - 9 1/4"
50' - 0"
LOBBY
1073 SQUARE FEET
D8
D6
P R
O P
O S
E D
E X
H A
U S
T H
O O
D
FLOOR GREASE TRAP
25 GPM / 50 LBS
GARAGE AREA
5691 SQUARE FEET
W
ID
E X
L O
N G
X
D E
E P
F L O
O R
D R
A
IN
P
IT
11' - 8 1/8"
OHD1OHD1OHD1OHD1OHD1OHD1OHD1
D9
2 2
84' - 9 5/8"
A T
T
IC
A C
C E
S S
D O
O R
.5
X
WASH BAY
A T
T
IC
A C
C E
S S
D O
O R
.5
X
A T
T
IC
A C
C E
S S
D O
O R
.5
X
D9
/8
D6
EXHAUST VENT
14'X5' ISLAND
D6
UTILITY ROOM
214 SQUARE FEET
ELECTRICAL PANELS
PT
D3
2 2
MANA-BLOC
SUPPLY ROOM
389 SQUARE FEET
8' - 8"
D2D6
UNISEX
RESTROOM
/2
127' - 6 7/8"
/8
24' - 0" 63' - 1 1/2"
48' - 9 1/4"
20' - 10 3/4"
/8
/4
2' - 0 3/8" 22' - 6 1/4" 17' - 6 1/4"
/8
EXHAUST VENT
4' - 6 3/8" 13' - 5" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 16' - 0" 10' - 6 7/8" 3' - 0 5/8"
FLOOR GREASE TRAP
25 GPM / 50 LBS
TOWNSHIP OFFICE
402 SQUARE FEET
CONFERENCE
ROOM
417 SQUARE FEET
MEN'S
RESTROOM
WOMEN'S
RESTROOM
/8
2' - 9 5/8"
5' - 8 3/4"
2' - 9 5/8"
D2 D3
D3
D5
D4
D3
D3
H A
L L W
A Y
D5
A
T T
IC
A
C C
E S
S W
IT
H
P U
L L D
O W
N S
T A
IR
S
D1
/2
27' - 8 1/8"
/2
27' - 8 1/8"
16' - 6 3/8" 14' - 9 1/4" 17' - 4 7/8"
/8
/4
12' - 1 1/8"
/8
/8
33' - 1 7/8"
8' - 3"
RFG
/8
MW
BF
DW
ATTIC ACCESS WITH
PULL DOWN STAIRS
W1 W1
W1
W1
W1
W1
W1
W1
5 5
COMMUNITY HALL
3140 SQUARE FEET
B-104
ATTIC ACCESS WITH
PULL DOWN STAIRS ATTIC ACCESS TABLE
ACCESS POINT DESCRIPTION
PULL DOWN STAIRS
PRECISION LADDERS, LLC, SUPER SIMPLEX DISAPPEARING STAIRWAY, MODEL 1000 OR
APPROVED EQUIVALENT
ATTIC DOOR
FRAME THE ACCESS HOLE WITH 2X FRAMING & COVER OPENING WITH REMOVABLE 3/4"
OSB. PLACE INSULATION OVER REMOVABLE 3/4" OSB.
NOTES:
(1) - ALL PRODUCTS SHALL BE INSTALLED PER MANUFACTURERS REQUIREMENTS.
(2) - PROVIDE AVAILABLE COLOR SAMPLES FOR TOWNSHIP APPROVAL.
(3) - PRIMER SHALL BE SHERWIN-WILLIAMS PVA DRYWALL PRIMER & SEALER OR APPROVED EQUIVALENT.
(4) - PAINT SHALL BE HIGH QUALITY THAT IS COMPATIBLE WITH PRIMER. COLOR & FINISH PER TOWNSHIP APPROVAL. APPLY 2 COATS (MIN), ENSURE EVEN & UNIFORM APPERANCE.
(5) - EPOXY FLOOR COATING SHALL BE WESTCOAT TEMPER-CRETETM SLC SYSTEM. BASE COLOR - CAPE COD GREY. TC-60 COLOR CHIPS -
GRANITE 104.
(6) - CONCRETE FLOOR SEALER SHALL BE SIKAFLOOR R -959SC OR APPROVED EQUIVALENT.
(7) - BASEBOARD TRIM SHALL BE FLEXCO-VCB 4" COVE OR APPROVED EQUIVALENT.
(8) - FR = FIRE RATED
COMMUNITY HALL GYPSUM, PRIMER, & PAINTED BASEBOARD TRIMEPOXY COATEDGYPSUM, PRIMER, & PAINTED
ROOM FINISH SCHEDULE
ROOM WALLS CEILING FLOOR TRIM WALL LEGEND
#2 2X6 STUDS
7/16" OSB (EACH SIDE)
1" METAL SHEATHING (1 SIDE)
1/2" GYPSUM WALL BOARD (1 SIDE)
EXT
INT
DOOR & WINDOW SCHEDULE
MARK
WIDTH X
HEIGHT
MATERIAL TYPE FINISH HARDWARE OPERATION REMARKS DESCRIPTION
TYPE:
DH - DOUBLE HUNG WINDOW
W1 INSULATED VINYL DH - MANUAL -2'-6" X 3'-10" FACTORY PELLA 250 SERIES, WITH GRILLES
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:4
:5
P M
B-101
FLOOR PLAN -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
LEVEL 1 - PHASE 2
NOTES:
1: CONCRETE TO BE EPOXY COATED IN COMMUNITY HALL.
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
CONTINUOUS RIDGE VENT
METAL ROOFING
METAL SIDING
METAL WAINSCOTING W/ TRIM
CONTINUOUS RIDGE VENT
GUTTER
DOWNSPOUT
CONTINUOUS RIDGE VENT CONTINUOUS RIDGE VENT
METAL ROOFING
GUTTER
DOWNSPOUT
METAL SIDING
METAL WAINSCOTING W/ TRIM
CONTINUOUS RIDGE VENT CONTINUOUS RIDGE VENT CONTINUOUS RIDGE VENT CONTINUOUS RIDGE VENT
CONTINUOUS RIDGE VENT CONTINUOUS RIDGE VENT
METAL ROOFING
METAL ROOFING
METAL ROOFING
METAL SIDING
METAL WAINSCOTING W/ TRIM
EXHAUST FANEXHAUST FAN
DOWNSPOUT
GUTTER
(PHASE 2 NOT VISIBLE IN THIS ELEVATION)
CONTINUOUS RIDGE VENT
CONTINUOUS RIDGE VENT
METAL ROOFING
METAL ROOFING
CONTINUOUS RIDGE VENT
CONTINUOUS RIDGE VENTCONTINUOUS RIDGE VENT
BOLLARD (TYP)
40"X60" ACCESS DOOR
(RE-USE FROM PHASE 1)
METAL SIDING
METAL WAINSCOTING
W/ TRIM
CONTINUOUS RIDGE VENT
GUTTER
DOWNSPOUT
PAINTED STEEL ROOFING
AC UNITSMETAL SIDING
CONTINUOUS RIDGE VENT
METAL WAINSCOTING
W/ TRIM
CONTINUOUS RIDGE VENT
4 12
GUTTER
DOWNSPOUT
CONTINUOUS RIDGE VENT
GUTTER
DOWNSPOUT
METAL SIDING METAL WAINSCOTING W/ TRIM
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1/8" = 1'-0"
/6
/2
:4
:5
P M
B-102
ELEVATIONS -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
East - Phase 2
1/8" = 1'-0"
North - Phase 2
1/8" = 1'-0"
South - Phase 2
1/8" = 1'-0"
West - Phase 2
NOTE:
MATCH COLOR SELECTION FROM PHASE 1 FOR
ALL ROOFING , SIDING, WAINSCOTING, TRIM, ROOF
GUTTERS, DOWNSPOUTS, WINDOWS, FASCIA,
SOFFIT, ETC.
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
4/12 ROOF PITCH 4/12 ROOF PITCH
ALUMINUM GUTTER
7" (MIN)
ALUMINUM GUTTER
7" (MIN)
ALUMINUM GUTTER
7" (MIN)
ALUMINUM GUTTER
7" (MIN)
4' OVERHANG
ALUMINUM GUTTER
7" (MIN)
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
/1
R
O O
F P
IT
C
H
2' OVERHANG
' O
V E
R H
A N
G
' O
V E
R H
A N
G
' O
V E
R H
A N
G
2' OVERHANG
2' OVERHANG
' O
V E
R H
A N
G
4/12 ROOF PITCH 4/12 ROOF PITCH
4/12 ROOF PITCH 4/12 ROOF PITCH
2' OVERHANG
ALUMINUM GUTTER
7" (MIN)
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1" = 10'-0"
/6
/2
:3
:1
P M
B-103
ROOF PLAN - PHASE
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1" = 10'-0"
LEVEL 1 - PHASE 2 - ROOF VIEW
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
7/16" OSBTOP METAL PANEL
BOTTOM METAL PANEL
ZEE/DOUBLE ANGLE
SIMPSON
STRONG-TIE
TBE6
7" K-STYLE GUTTER W/ 7"
NOMINAL RECTANGULAR
DOWNSPOUT
GUTTER APRON/EAVE EDGE
METAL ROOF
2X PURLINS
TRUSS
FASICA TRIM
CONT. VENTED SOFFIT
F&J CHANNEL
METAL PANEL
2X FRAMING
RAKE TRIM
FASCIA TRIM
2X FASCIA
BOARD
METAL ROOF PANEL
CONT. VENTED SOFFIT
7/16" OSB
SHEATHING
F&J CHANNEL
METAL SIDING
TRUSS TOP CHORD
2X PURLIN
7/16" OSB SHEETING &
METAL SIDING
(EXTERIOR FINISH)
1/2" GYPSUM (INTERIOR FINISH)
2X6 @ 16" OC FRAMING
SINGLE 2X6 BOTTOM PLATES (PT)
DOUBLE 2X6 TOP PLATES
INSULATION
CONCRETE FLOOR
2" THICK R-10 DOW BOARD
INSULATED FOAM BOARD
UNDER ENTIRE SLAB
6MIL. PLASTIC
VAPOR BARRIER
SIMPSON STRONG
TIE'S TBE6
ALUMINUM
GUTTER
2X6 FACE BOARD
2X6 PT SILL PLATE
TREATED MATERIAL .60 CCA
3/4" OSB SUBFLOOR
UTILITY ROOM WIDTH
12' - 0"
C E
IL
IN
G H
E
IG
H T
C
E
IL
IN
G
H E
IG
H
T
APPROX. FINISH
GRADE
6" BELOW TOP
OF WALL
GRADE TO SLOPE
AWAY FROM
FOUNDATION MIN 6"
WITHIN THE 1ST 10'
SOLID CONCRETE WALL
ANCHOR BOLT
METAL ROOFING
(2) 2X6 TOP PLATE
INSULATION
SPACED @ 24"
2X4 GIRTS
VAPOR BARRIER
METAL SIDING
7/16" OSB SHEETING
1/2" GYPSUM
G R
A D
E M
IN
B
E L
O W
ENGINEERED ATTIC TRUSSES
SPACED @ 24" OC
7/16" OSB SHEETING 7/16" OSB SHEETING
INSULATION
CONCRETE FOOTING
2X6 BLOCKING @ 5'
6" 2B STONE
STUDS: 2X6 @ 16" OC
SEE ROOF PLAN
OVERHANG VARIES,
CONTINUOUS VENT
SOFFIT
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:1
P M
B-104
CROSS-SECTIONS -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/2" = 1'-0"
WAINSCOATING TRANSITION DETAIL -
PHASE 2
1/2" = 1'-0"
HURRICANE STRAP DETAIL - PHASE 2
3/4" = 1'-0"
TYPICAL EAVE DETAIL - PHASE 2
3/4" = 1'-0"
TYPICAL GABLE DETAIL - PHASE 2
1" = 1'-0"
CORNER SECTION - PHASE 2
3/8" = 1'-0"
CROSS SECTION COMMUNITY HALL
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
14' - 6"
1' - 6"
14' - 6"
1' - 6"
14' - 6"
1' - 6"
14' - 6"
1' - 6"
14' - 6"
1' - 6"
14' - 6"
1' - 6"
14' - 6"
W
ID
E X
' L
O N
G X
D E
E P
M
IN
D R
A
IN
P
IT
CONTROL JOINT
(TYP)
COORDINATE
WITH HVAC
EXTEND FOOTING 2'-0" AT MARKED LOCATIONS,
FOR FUTURE CONSTRUCTION (FOR PHASE 3)
S1
S1
S1
S2 S2
S2
S2
F1/W1
F1/W1
F
/W
F
/W
F1/W1
F
/W
S3
F1/W1
F1 F1
FFE = 650.0'
SLOPE SLAB 1/8" PER FOOT TO CREATE POSITIVE
DRAINAGE FOR DRAIN PIT.
FLOOR DRAIN
(-0',1-7/8")
(TYP)
S1
2' - 8 5/8"
3' - 3"
4' - 6 1/2" 1' - 8 1/8"
3' - 3"
1' - 5 1/2"
2' - 6" 12' - 4 1/2"
/8
S2
F2
S2
24' - 0" 61' - 6 1/8" 3' - 3" 88' - 10 3/8"
/2
/8
F2
F
/W
F
/W
F1/W1
/4
50' - 0"
/4
CONTROL JOINT
(TYP) (ALIGN WITH
PHASE 1 CONTROL
JOINTS)
S1
EXISTING
FOOTER FROM
PHASE 1
FLOOR SLAB SCHEDULE
MARK DESCRIPTION
S1
6" CONCRETE SLAB WITH FIBER MESH & 6X6-W1.4XW1.4 WWF, ON 6"-8" STONE
BASE, COVERED WITH 6 MIL PLASTIC VAPOR BARRIER, 2" THICK R-10 DOW BOARD
INSULATED FOAM BOARD UNDER SLAB WITH 1/2" THERMAL BRAKE BETWEEN WALL
& SLAB.
FOOTING WALL SCHEDULE
MARK THICKNESS (TW) REINFORCEMENT
W1* 8" #4 CONT. REBAR WITHIN 12" FROM TOP
SILL PLATE ANCHORS
ANCHOR BOLT SHALL CONFORM TO ASTM A153 CLASS C.
ANCHOR BOLT AND ALL HARDWARE SHALL BE HOT-DIPPED GALVANIZED.
ANCHOR BOLTS SIZED AND LOCATED PER IBC 2308.3.1.
FOOTING SCHEDULE
MARK WIDTH (W) THICKNESS (T) REINFORCEMENT
F1 24" 10" 3 ROWS #4 CONT. REBAR
W1* - THERE IS A BID ALTERNATE USING CMU AND GROUT FOR FOOTING WALLS
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:4
:5
P M
S-101
FOOTING PLAN -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
FOUNDATION PLAN - PHASE 2
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
H1H1H1H1H1H1H1 H2H2
H
H2
A T
T
IC
A C
C E
S S
D O
O R
.5
X
A T
T
IC
A C
C E
S S
D O
O R
.5
X
A T
T
IC
A C
C E
S S
W
L L D
O W
N S
T A
IR
S
4' OVERHANG
A T
T
IC
A C
C E
S S
D O
O R
.5
X
H2
H2
2' OVERHANG
' O
V E
R H
A N
G
2' OVERHANG
H2
ATTIC ACCESS WITH
PULL DOWN STAIRS
2' OVERHANG
2' OVERHANG
' O
V E
R H
A N
G
' O
V E
R H
A N
G
ATTIC ACCESS WITH
PULL DOWN STAIRS
2' (MAX) 4
' O
V E
R H
A N
G
4' OVERHANG
2' OVERHANG
H
H
H
H
H
H
TOP CHORD OF TRUSS
2X4 FLATWISE PURLIN (MUST SPAN
FIRST TWO TRUSSES)
VARIES
HEADER SCHEDULE
MARK SIZE
GRADE/
MATERIAL
H3 2"x6" SPF GR 2
REMARKS
2-PLY
LOCATION
ABOVE COMM.
HALL WINDOWS
JACK STUD KING STUD
1 1
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:1
P M
S-102
ROOF FRAMING -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
FLOOR PLAN - PHASE 2 - ROOF
FRAMING
1 1/2" = 1'-0"
OUTLOOKER DETAIL - PHASE 2
E N
G
IN
E E
R E
D A
T T
IC
T
R U
S S
O C
S
IZ
E D
B Y
O T
H E
R S
E N
G
IN
E E
R E
D A
T T
IC
T
R U
S S
O C
S
IZ
E D
B Y
O T
H E
R S
E N
G
IN
E E
R E
D T
R U
S S
O C
S
IZ
E D
B Y
O T
H E
R S
ENGINEERED ATTIC TRUSS @ 24" OC
SIZED BY OTHERS
RIDGE LINERIDGE LINE
RIDGE LINE
ENGINEERED TRUSS
FOR ROOF OVER BUILD
ENGINEERED ATTIC TRUSS @ 24" OC
SIZED BY OTHERS
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
WIRE MESH
5/8" TO 3/4" VIEGAPEX TUBING:
KEEP 4" FROM WALL
RIGID INSULATION
CONCRETE SLAB:
MINIMUM 3/4" CONCRETE COVER
OVER VIEGAPEX TUBING.
EDGE RIGID INSULATION
GRAVEL
COMPACT SUBGRADE
6 MIL (MIN)
POLYTHYLENE FILM
FASTEN TUBING EVERY 2 FEET AND 3
TIMES AT EVERY U-TURN WITH PLASTIC
ZIP-TIES TO HOLD DOWN RETURN
BENDS OR OTHER SHAPES CREATED BY
THE TUBING.
12" SPACING (TYP)
12" SPACING (TYP)
WIRE MESH
5/8" VIEGAPEX TUBING:
KEEP 4" FROM WALL
RIGID INSULATION
FASTEN TUBING EVERY 2 FEET AND 3 TIMES
AT EVERY U-TURN WITH PLASTIC ZIP-TIES
TO HOLD DOWN RETURN BENDS OR OTHER
SHAPES CREATED BY THE TUBING.
GRAVEL
COMPACT SUBGRADE
6 MIL (MIN)
POLYTHYLENE FILM
CONCRETE SLAB:
MINIMUM 3/4" CONCRETE COVER
OVER VIEGAPEX TUBING.
EDGE RIGID INSULATION
LINOLEUM OR VINYL FLOOR
X
TUBE SPACING
TUBING SIZE WITH THE COIL
5/16" 7"
3/8" 8"
1/2" 10"
5/8" 12"
3/4" 14"
1" 18"
1 1/4" 22"
1 1/2" 26"
2" 34"
NOTE:
WHEN THE TUBE SPACING IS LESS THAN
THE MINIMUM BENDING DIMENSION, THE
LOOP ENDS SHALL BE SWEPT OUT TO AT
LEAST THE DIMENSION SHOWN.
OTHERWISE, IF TUBE SPACING IS EQUAL OR
GRATER THAN DIMENSION "X", STANDARD
LOOP MAY BE USED.
W
T
FLOOR SLAB
2" RIGID FOAM
TW
FFE
-0'-6"
-3'-6"
REBAR
REBAR
d
CONCRETE SLAB - SEE PLAN
1/8" WIDE SAWCUT. CUT WHEN SLAB IS
FIRM ENOUGH SO THAT IT IS NOT
DAMAGED BY BLADE. FILL JOINT WITH
JOINT FILLER IN ACCORDANCE WITH
GENERAL STRUCTURAL NOTES
d
CONCRETE SLAB - SEE PLAN
1/4" WIDE X 1" DEEP SAWCUT. CUT
SLAB JOINT AFTER JOINT HAS
OPENING. FILL JOINT WITH JOINT
FILLER.
d /2
PROVIDE 1/4"X4 1/2" SQUARE
DIAMOND DOWELS AT 18" OC.
PROVIDE 3/4" X 1'-4" SMOOTH
SQUARE DOWEL @18" OC
1/8" WIDE SAWCUT. CUT WHEN SLAB
IS FIRM ENOUGH SO THAT IT IS NOT
DAMAGED BY BLADE. FILL JOINT
WITH JOINT FILLER.
d d /2
EXISTINGNEW
8"
DRILL & GROUT INTO EXISTING
SLAB WITH ADHESIVE, PER
MANUFACTUER'S SPECS.
GREASE DOWEL IN NEW SLAB.
C L E
A R
F O
O T
IN
G
T H
IC
K
N E
S S
TO BE INSPECTED AND APPROVED BY
OWNER'S SOIL TESTING AGENCY
COMPACTED SUBGRADE
MEETING MINIMUM ALLOWABLE
BEARING PRESSURE
BEARING SURFACE AND CAPACITY TO BE INSPECTED AND
APPROVED BY OWNER'S SOIL TESTING AGENCY
CONTINUOUS
WATER STOP. TYP.
E Q
E Q
E Q
E Q
E Q
CLASS B TENSION LAP SPLICE (MINIMUM) OR CONTINOUS
2" C
LEAR
EDGE OF SLAB OR
CONSTRUCTION JOINT
(2) #4 X 2'-6" LONG CENTERED IN SLAB (TYPICAL)
NOTES:
1. FOR SLABS 6" THICK AND GREATER, PLACE (2) #4 BARS VERTICALLY IN SLAB.
1/2" THERMAL
BREAK A
A
SLAB
2" RIGID FOAM
1/2" THERMAL BREAK
FOOTING WALL
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:1
P M
S-103
FOOTING DETAILS -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1" = 1'-0"
SLAB SECTION 1 - PHASE 2
1" = 1'-0"
SLAB SECTION 2 - PHASE 2
1 1/2" = 1'-0"
MANIFOLD TUBING DETAIL - PHASE 2
1" = 1'-0"
TUBE SPACING TABLE - PHASE 2
1" = 1'-0"
F1 DETAIL - PHASE 2
1 1/2" = 1'-0"
TYPICAL SAWCUT CONTROL JOINT
DETAIL - PHASE 2
1 1/2" = 1'-0"
TYPICAL CONSTURCTION JOINT DETAIL
- PHASE 2
1 1/2" = 1'-0"
TYPICAL CONSTRUCTION JOINT DETAIL
(PHASE TO PHASE) - PHASE 2
1" = 1'-0"
TYPICAL CONTINIOUS WALL FOOTING
CONSTUCTION JOINT - PHASE 2
1 1/2" = 1'-0"
TYPICAL SLAB REINFORCING AT WALL
OPENING - PHASE 2
1" = 1'-0"
SECTION A-A - FOOTING TO SLAB
DETAIL - PHASE 2
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
KITCHEN AREA
TOWNSHIP OFFICE
CONFERENCE
ROOM
MEN'S
RESTROOM
WOMEN'S
RESTROOM
UTILITY ROOM
SUPPLY ROOM
GARAGE AREA
LOBBY
COMMUNITY HALL
MANIFOLD CABINET
VIEGAPEX BARRIER TUBING,
SPACING AND SIZE PER DESIGN
BEND SUPPORTS
(USE THE APPROPRIATE
SUPPORTS FOR THE SELECTED
TUBE SIZE)
1 1/4" STAINLESS STEEL
MANIFOLD.
(MOUNTED APPROX 3' FROM THE
FINISHED FLOOR, OR A MORE
CONVENIENT HEIGHT PER
PROJECT RESTRICTIONS)
MANIFOLD DIMENSIONS
STOCK CODE OUTSIDE WIDTH OUTSIDE HEIGHT
15800 22 5/8" 28"-31"
15801 28 3/8" 28"-31"
15802 46" 28"-31"
NAME MANIFOLD TYPE # CIRCUITS
MANIFOLD
TUBING SIZE
SUPPLY TEMP
(F°)
TOTAL LOAD
(BTU/HR)
TOTAL FLOW
(USGPM)
HEAD LOSS
(FT WATER)
NAME HEATING ZONE
ROOMS
AREA (FT2)
HEATING ROOM
TEMP (F°)
COOLING ROOM
TEMP (F°)
FLOOR COVER R
(R)
PANEL TYPE
SURFACE TEMP
(F°)
TOTAL LOAD
(BTU/HR)
PANEL
BACKLOSS
SUPPLEMENTAL
MANIFOLD 2 STAINLESS STEEL - SHUT OFF/BALANCING/FLOW METERS, 1-1/4" 6 5/8"
COMMUNITY HALL 102 3140 70 0.0 EMBEDDED SLAB 82 0
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
As indicated
/6
/2
:3
:1
P M
MEP-101
MANIFOLD LAYOUT -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
FLOOR PLAN - PHASE 2 - MANIFOLD
KITCHEN AREA
2 CIRCUITS
CONFERENCE ROOM
1 CIRCUIT
RESTROOM / HALL
2 CIRCUITS
UTILITY ROOM
1 CIRCUIT
GARAGE AREA
4 CIRCUITS
TOWNSHIP OFFICE
3 CIRCUITS
LOBBY
2 CIRCUITS
MANIFOLD 2
(112.4 F°)
(6 CIRCUITS)
MANIFOLD 1
(112.4 F°)
(12 CIRCUITS)
MANIFOLD 4
(112.4 F°)
(4 CIRCUITS)
MANIFOLD 3
(112.4 F°)
(10 CIRCUITS)
COMMUNITY HALL
4 CIRCUITS
1" = 1'-0"
MANIFOLD CABINET - PHASE 2
NTS
GENERAL MECHANICAL NOTES:
1. THIS DRAWING IS A SCHEMATIC ONLY & SHALL BE VERIFIED BY THE CONTRACTOR.
2. HVAC CONTRACTOR (HAC) SHALL PROVIDE ALL LABOR, MATERIALS, TOOLS, &
EQUIPMENT TO FURNISH & INSTALL A COMPLETE & OPERATING SYSTEM.
3. HAC SHALL VERIFY ALL EQUIPMENT SIZES.
NO. DESCRIPTION DATE
PHASE 1 INFORMATION PROVIDED FOR
INFORMATION ONLY, CONTRACTOR TO
VERIFY AS-BUILT CONDITION
NICOLAS PAIRICK BOYLE
馴GINE巨R
No, PEO85521
NICOLAS PAIRICK BOYLE
WH
R a n g e
RHEEM 5 TON
(13 SEER)
OUTSIDE UNITS
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
RHEEM 5 TON
(13 SEER)
OUTSIDE UNITS
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L
Y
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
14"X14"X12' SUPPLY 14"X12"X16' SUPPLY 14"X10"X16' SUPPLY
8" FLEX
12" FLEX
5" FLEX
8" FLEX
8" FLEX
8" FLEX
8" FLEX
7" FLEX
8" FLEX
8" FLEX
7" FLEX
7" FLEX
7" FLEX7" FLEX
P R
O P
O S
E D
E X
H A
U S
T H
O O
D
INSTALL 2 HOUR FIRE RATED
PENETRATION SLEEVE
KITCHEN AREA
TOWNSHIP
OFFICE
CONFERENCE
ROOM
MEN'S
RESTROOM
WOMEN'S
RESTROOM
UTILITY ROOM
SUPPLY ROOM
GARAGE AREA
UNISEX
RESTROOM
LOBBY
WASH BAY
R H
E E
M
T O
N (1
S
E E
R
O U
T S
ID
E
U N
IT
S
F L
F L
F L
F L
110 CFM FAN TO BE VENTED TO
EXTERIOR WITH DAMPERED
VENT THROUGH ROOF OR WALL
WITH FLEX PIPE UL-181 TESTED.
110 CFM FAN TO BE VENTED TO
EXTERIOR WITH DAMPERED
VENT THROUGH ROOF OR WALL
WITH FLEX PIPE UL-181 TESTED.
EXHAUST FAN WITH SHUTTER
8,000 CFM, 1/4 HP, 1 PHASE
EXHAUST FAN WITH SHUTTER
8,000 CFM, 1/4 HP, 1 PHASE
F
L14'X5' ISLAND
7" FLEX
8" FLEX
7" FLEX
P R
O P
O S
E D
E X
H A
U S
T
O
O D
8" FLEX
INSTALL 2 HOUR FIRE RATED
PENETRATION SLEEVE
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
"X
"X
R
E T
U R
N
"X
"X
S
U P
P L Y
7" FLEX7" FLEX
7" FLEX7" FLEX
7" FLEX7" FLEX
7" FLEX7" FLEX
COMMUNITY HALL
MECHANICAL LEGEND
- RETURN
- SUPPLY
- FAN/LIGHTF
L
SCALE
PROJECT NUMBER
DATE
DRAWN BY
CHECKED BY
130 FARM LANE
STATE COLLEGE, PA
(814)-271-0770
OFFICE@BOYLE-ENG.COM
WWW.BOYLE-ENG.COM
15 EAST MAIN STREET
NEW BLOOMFIELD, PA
(717)-275-7531
1/8" = 1'-0"
/6
/2
:3
:1
P M
MEP-102
MECHANICAL PLAN -
PHASE 2
2023-051
TWP BUILDING
TYRONE TOWNSHIP
07/06/2026
H.WELCH
N.BOYLE
1/8" = 1'-0"
LEVEL 1 - PHASE 2 - MECH PLAN
HVAC GENERAL NOTES:
MECHANICAL NOTES:
1. THIS DRAWING IS SCHEMATIC ONLY & SHALL BE VERIFIED BY THE CONTRACTOR.
2. HVAC CONTRACTOR (HAC) SHALL PROVIDE ALL LABOR,…