This document is a Submittal Form for Single and Dual-metered Traffic Signal Underground Service Pedestals, issued by the Utah Department of Transportation (UDOT). The Request for Proposal (RFP) seeks to establish a single contract with a qualified vendor to provide traffic signal underground service pedestals for powering traffic signals, intersection lighting, and Intelligent Transportation Systems (ITS) throughout Utah. The contract will have a 5-year term with no renewal options. Offerors are required to submit engineer drawings, dimensions, bill of materials, schematics, warranty, lead time, and minimum order information in PDF format.

The pedestals must meet specific mandatory requirements, including precise cabinet dimensions (54 inches maximum height, 16-24 inches wide), Buy America provisions, NEMA 3R rainproof standards, and detailed electrical specifications. Electrical requirements include single-phase 120V/240V, 100A service with specific circuit breaker configurations, surge protection, and temperature ratings between -30°F and 130°F. The pedestals must have compartmentalized, padlockable designs with UV-resistant windows, permanent labels, and documentation. Vendors must provide comprehensive technical specifications, including meter socket configurations, photocell details, and compliance with Electric Utility Service Equipment Requirements Committee (EUSERC) standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 Submittal Form- Single and Dual-metered Traffic Signal Underground Service Pedestals

Responders MUST submit this form AND DOCUMENTATION CONFIRMING these MANDATORY REQUIREMENTS listed

Offerors shall provide engineer drawings (include dimensions, bill of materials and schematics) and warranty, lead time, and minimum order information electronically in .pdf format with their submission.

Vendor Name:
Non-Intrusive Freeway Data Collection Sensor Mandatory Requirements
RequirementMeets Requirement? (Y/N)
3.1 CABINET REQUIREMENTS
3.1.1Height 54 inches maximum
3.1.2For single-meter pedestals: cabinet that is approximately 16 inches wide by 17 +/- ½ inches deep.
3.1.3For dual-meter pedestals: cabinet approximately 24-inch wide.
3.1.4Meet provisions of Buy America (UDOT Standard Specification Section 01455, Article 1.11).
3.1.5Rainproof, NEMA 3R
3.1.6At least 0.125” anodized aluminum 5052-H32, continuously welded or overlapped and carriage-bolted exterior, smooth and free of any voids.
3.1.7Provide adequate clearances inside the cabinet for pulling and connecting to service and distribution (field) wiring with conduits extending into the cabinet 2 inches maximum.
3.1.7.1Front and back lips at the bottom of the pedestal shall extend no more than ¾ inch.
3.1.8Service entrance, meter, and distribution compartments with padlockable, vandal-resistant doors and covers, and corrosion resistant barriers separating each compartment. Compartments designed with stainless steel piano hinges on access panel or access door. Place hinges on left side of door when facing the pedestal.
3.1.9Meters shall be visible from the front with a clear, UV and yellowing-resistant window.
3.1.10Photo cell cover shall also have a clear, UV and yellowing-resistant window. Include photocell headlight shield.
3.1.11Cabinet shall fasten directly to pad-mount base encased in concrete, with option for attachment to anchor bolts. All mounting bolts shall be secured from inside the cabinet.
3.1.12Permanent labels (etched or engraved) mechanically fastened to the cabinet. Adhesives are not acceptable. Exterior front-door label either: “UDOT SIGNAL AND LIGHTING DISCONNECT” or “UDOT ITS DISCONNECT” as ordered. Conform to UL508A Industrial Control Panel Labels for service entrance equipment requirements.
3.1.13Provide documentation permanently and conveniently attached to the inside of the distribution section or a permanently attached interior documentation storage pocket or pouch. Documentation shall include the manufacturer’s name, address, phone number, a wiring diagram, date of manufacture, and all necessary information to order an identical pedestal and replacement parts.
3.2 ELECTRICAL REQUIREMENTS
3.2.1Single-phase, 3-wire, 120V/240V, 100A.
3.2.2200A utility landing lugs rated for 250 kCMIL wire with self-contained watt-hour meter sockets, main service disconnect, and meter bypass switch, meeting local power utility company requirements.
3.2.2.1Single-meter pedestal: provide one meter socket for signal side.
3.2.2.2Dual-meter pedestal: provide two meter sockets – one for the signal side and one for the lighting side. Per 3.1.12, label each socket “SIGNAL” and “LIGHTING” accordingly.
3.2.3Electrical components rated for temperatures between -30ºF and 130ºF.
3.2.4Meet Electric Utility Service Equipment Requirements Committee (EUSERC) requirements for all mounting hardware and installation details.
3.2.5Provide bolt-in circuit breakers that are UL approved, industrial grade, and rated for 10K AIC minimum or higher as required for available fault current.
3.2.6 Signal Side Requirements:
3.2.6.1Double pole 70-amp main bolt-in circuit breaker labeled “Signal Main”.
3.2.6.2One single-pole 20-amp bolt-in circuit breaker labeled “Traffic Signal”, secondary to the Signal Main breaker.
3.2.6.3Capacity for 4 single pole bolt-in circuit breakers, also secondary to Signal Main breaker.
3.2.6.4Surge protection device with status LED: 150 volt MCOV, 10 kA Nominal Discharge Current, 25 kA SCCR
3.2.7 Lighting Side Requirements:
3.2.7.1Double Pole 70-amp main bolt-in circuit breaker labeled “Lighting Main”.
3.2.7.2Double pole 20-amp (120/240 volt) bolt-in circuit breaker labeled “lighting”, plus breaker for photo control, both secondary to the Lighting Main breaker.
3.2.7.3Pre-wired 20-amp 120V electrically-held 2-pole contactor, Square D Part # 8903-LO60V02, or approved equivalent.
3.2.7.4Three-position rotary test switch with “On-Off-Auto” settings clearly labeled.
3.2.7.5Minimum capacity for (4) four double-pole circuit breakers.
3.2.7.6Circuit terminal bar with lugs rated for wire sizes 6 AWG to 1/0 AWG, labeled “Lighting Circuit”. Grounding terminal bar with lugs rated for 6 AWG to 1/0 AWG wire size, adjacent to circuit terminal bar.
3.2.7.7Prewired photocell socket with long-life photocell that has a minimum 12-year warranty.