36C26118B0618-005.pdf
PDF 10 MB Posted
- Solicitation number
- 36C26118B0618
About this file
This pre-solicitation notice provides details for an upcoming Invitation for Bid to construct a new Dermatology Outpatient Service Building. The project is located at VA Northern California Healthcare System in Mather, California, with a period of performance of 500 days from notice to proceed. The solicitation will be issued on or about July 20, 2019 via FBO and include specifications and drawings. The construction magnitude is estimated between $5-10 million. The NAICS code is 236220 and it is set aside as a total small business opportunity. The single award will be a firm-fixed price contract for all labor, materials, permits and other requirements to build the outpatient facility.
36C26118B0618 C27 - 02-12-18 - ARCHITECTURAL - MATHER - DERMATOLOGY - 10TH SUBMITTAL_Part2.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26118B0618-0004001.docx | DOCX document | |
| 36C26118B0618-0004000.docx | DOCX document | |
| 36C26118B0618-0003000.docx | DOCX document | |
| 36C26118B0618-0003001.pdf | ||
| 36C26118B0618-0003002.pdf | ||
| 36C26118B0618-0002000.docx | DOCX document | |
| 36C26118B0618-0001000.docx | DOCX document | |
| 36C26118B0618-0001001.pdf | ||
| 36C26118B0618-008.pdf | ||
| 36C26118B0618-012.pdf | ||
| 36C26118B0618-017.pdf | ||
| 36C26118B0618-007.pdf | ||
| 36C26118B0618-015.pdf | ||
| 36C26118B0618-003.pdf | ||
| 36C26118B0618-013.pdf | ||
| 36C26118B0618-010.pdf | ||
| 36C26118B0618-011.pdf | ||
| 36C26118B0618-014.pdf | ||
| 36C26118B0618-004.pdf | ||
| 36C26118B0618-006.pdf | ||
| 36C26118B0618-016.pdf | ||
| 36C26118B0618-009.pdf | ||
| 36C26118B0618-002.docx | DOCX document | |
| 36C26118B0618-001.docx | DOCX document |
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F.E.C.F.E.C.
F.E.C.
UP
UP
F .E
.C
S T
A
IR
81 SF
ELEVATOR
E1
CHECK
OUT
FUTURE
CORRIDOR
MECHANICAL YARD
CL
FUTURE
LOBBY
M A
T C
H L
IN
E
M A
T C
H L
IN
E
AAA B
151617181921 20
23 25 27
31 28
A A A A
A A A A
F .O
.F
F .O
.F
F .O
.F
F.O.F.
F.O.F.
L2
AE404
AE403
AE405
A
AE301
A
AE301
95.00'
94.98
94.98'
95.00'
F.O.F.
AE406
AE406
AE406
C
AE301
C
AE301
AE403
AE404
B
AE301
B
AE301
AE302
AE302
AE302
AE402
AE402
AE405
801 SF
WAITING
1A01
210 SF
RECEPTION
1A03
36 SF
H.A.C.
1AC2A
179 SF
HALL
1AC1
58 SF
PUBLIC
TOILET
1AC1A
59 SF
PUBLIC
TOILET
1AC1B
34 SF
ELEVATOR
CONTROL
1A01A
56 SF
STAFF
1A02D
63 SF
STAFF
1A02C
354 SF
STAFF
1193 SF
OPEN OFFICE
1A02
75 SF
SHOWER
1A13A
63 SF
PATIENT
TOILET
1AC2C
174 SF
PHOTO
1A13
102 SF
OFFICE
1A02A
170 SF
LASER
1A12
100 SF
I.T.
1A16
108 SF
MULTI
PURPOSE
1A02B
225 SF
ELECTRICAL
1A15
710 SF
MECHANICAL
1A14
123 SF
EXAM
ROOM
1A11
124 SF
EXAM
ROOM
1A10
124 SF
EXAM
ROOM
1A09
124 SF
EXAM
ROOM
1A08
124 SF
EXAM
ROOM
1A07
122 SF
EXAM
ROOM
1A06
125 SF
EXAM
ROOM
1A05
126 SF
EXAM
ROOM
1A04
213 SF
STAIR 2
S2
847 SF
CORRIDOR
1AC2
L1 4
14 14
0.9122.1367 5
A
B
C C
D D
C4 C4
D1 D1
3.1
1' - 0 7/8"14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"32' - 0"26' - 1"
A.3
A.7
B.3
AE302
C94.98'
14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"1' - 5"
1' - 5"97' - 7"24' - 0"34' - 1"
/8
/8
/8
/8
/2
7"20' - 5"1' - 5"
/8
F.O.F.
F.O.F.
F.O.F.
AE101
94.98'
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
FEC
STC1
A
2 5/8"1' - 2 3/8"
/8
/8
F.O.S.
F.O.F.
F .O
.S
F .O
.F
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:53:45 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D. DIMAT
AE101
ARCHITECTURAL FIRST FLOOR
PLAN
J. ALFARO
612-501
D. DIMAT
42 151
1/8" = 1'-0"AE101
1 FIRST FLOOR PLAN PROJECT
NORTH
1 1/2" = 1'-0"AE101
2 TYPICAL EXTERIOR WALL DIMENSIONING
UP
F .E
.C
S T
A
IR
MECHANICAL YARD
26' - 1" 30' - 7"
1' - 5"
7" 8' - 0" 9"1' - 6" 8' - 0"
C
AE301
F.O.F.
F.O.F.
F.O.F.
F .O
.F
AE404
B
AE301
100 SF
I.T.
1A16
108 SF
MULTI
PURPOSE
1A02B
225 SF
ELECTRICAL
1A15
102 SF
OFFICE
1A02A
170 SF
LASER
1A12
710 SF
MECHANICAL
1A14
123 SF
EXAM
ROOM
1A11
124 SF
EXAM
ROOM
1A10
174 SF
PHOTO
1A13
F.O.F.
STC
STC
S T
C
AE201 5
AE502
4' - 10"
AE603
S T
C
3' - 0"
AE504
AE502
AE502
CL
CL
CL
AE302
AE603
67 5
A
B
C
D
C4
D1
A.3
A.7
B.3
10' - 0"
9 9 9
AE503
AE503
AE503
AE503
AE504
1' - 5"
/4
/4
/4
CL
AE508
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
STC
FEC
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:53:47 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D. DIMAT
AE101-1
ARCHITECTURAL FIRST FLOOR
ENLARGED PLAN - NORTH
J.ALFARO
612-501
D. DIMAT
43 151
1/4" = 1'-0"AE101-1
1 FIRST FLOOR ENLARGED PLAN NORTH
M A
T C
H L
IN
E
S E
E A
E -2
M A
T C
H L
IN
E
S E
E A
E -2
PROJECT
NORTH
UP
100' - 5"
FUTURE
CORRIDOR
FUTURE
CORRIDOR
A
AE301
A
AE301
1' - 6"9' - 0"11' - 5"6' - 0"10' - 6 1/2" 4' - 5"4' - 8"13' - 4"5' - 7"8' - 2 1/2"
1' - 3 1/2"
3 3/4"
1' - 3"12' - 0"2' - 6"12' - 0"9' - 9"1' - 4"8' - 5 1/4"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 9"8' - 0"10' - 7"1' - 5"
5' - 3"4' - 7"4' - 2" 1' - 4"
7' - 2"5' - 6"9' - 3"3' - 5"6' - 7 1/4"
1' - 1 1/4"
8' - 5 1/4"
4' - 3"
C
AE301
C
AE301
5' - 0"
AE403
B
AE301
AE302
AE302
AE402 12
AE402 17
AE405
801 SF
WAITING
1A01
ELEVATOR
E1
63 SF
STAFF
1A02C
56 SF
STAFF
1A02D
1193 SF
OPEN OFFICE
1A02
100 SF
I.T.
1A16
102 SF
OFFICE
1A02A
170 SF
LASER
1A12
174 SF
PHOTO
1A13
75 SF
SHOWER
1A13A
63 SF
PATIENT
TOILET
1AC2C
354 SF
STAFF
1AC2B
34 SF
ELEVATOR
CONTROL
1A01A
58 SF
PUBLIC
TOILET
1AC1A
179 SF
HALL
1AC1
210 SF
RECEPTION
1A03
36 SF
H.A.C.
1AC2A
59 SF
PUBLIC
TOILET
1AC1B
847 SF
CORRIDOR
1AC2
213 SF
STAIR 2
S2
126 SF
EXAM
ROOM
1A04
125 SF
EXAM
ROOM
1A05
122 SF
EXAM
ROOM
1A06
124 SF
EXAM
ROOM
1A07
124 SF
EXAM
ROOM
1A08
124 SF
EXAM
ROOM
1A09
124 SF
EXAM
ROOM
1A10
123 SF
EXAM
ROOM
1A11
AE603
AE504
AE504
AE503
AE502
AE604
AE603 15
8' - 6 1/2"
AE505
AE502
AE603
AE603 11
AE603
AE603
AE603
AE502
OH
AE505
AE502
AE502
7 TYP
AE505
AE504
AE603
0.9
22.13
A
B
C
D
C4
D1
3.1
3.1
EQEQ
7"1' - 0" 8' - 0"2' - 2"8' - 0"6' - 6"4' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 3"8' - 0"
7"
777777
CL
AE302
AE502
AE603
AE503
6 6
F .O
.F
3 3
CL
TYP OF 8
/4
C L R
F.O.F.
F .O
.F
9' - 0"
3' - 0"
10' - 9"10' - 6"10' - 6"10' - 6"10' - 6"10' - 6"10' - 6"9' - 4"
/8
/4
/8
/8
/8
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER
CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
STC
FEC
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:53:50 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D. DIMAT
AE101-2
ARCHITECTURAL FIRST FLOOR
ENLARGED PLAN - SOUTH
J.ALFARO
612-501
D. DIMAT
44 151
1/4" = 1'-0"AE101-2
1 FIRST FLOOR ENLARGED PLAN SOUTH
M A
T C
H L
IN
E
S E
E A
E -1
M A
T C
H L
IN
E
S E
E A
E -1
F .E
.C
UP
F.E.C.
F.E.C.
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
FEC
STC
S T
A
IR
FUTURE
CORRIDOR
M A
T C
H L
IN
E
M A
T C
H L
IN
E
A
AE301
A
AE301
AE403
6564 66 67
45 42
B AABBAA
A
A
AE402
AE405
AE404
AE406
4 AE406
C
AE301
C
AE301
6' - 0"
AE403
AE404
B
AE301
AE302
AE302
AE302
AE405
370 SF
CONFERENCE
2A02
240 SF
PROCEDURE
WAITING
2A01
214 SF
LOUNGE
2A03
262 SF
CONFERENCE
2A04
103 SF
OFFICE
2A05A
99 SF
MULTI
PURPOSE
2A05B316 SF
IT OPEN
OFFICE
2A05
101 SF
I.T.
2A08
1078 SF
CORRIDOR
2AC1
120 SF
PROCEDURE
PREP
2A09
631 SF
CORRIDOR
2AC2
175 SF
GEN
PROCEDURE
2A10
174 SF
GEN
PROCEDURE
2A11
172 SF
DERM LAB
2A12
175 SF
GEN
PROCEDURE
2A13
293 SF
STAFF
2AC2D
370 SF
IT STORAGE
2A06
S
F E
L E
C T
R
IC
A L
A
C E
101 SF
SHAFT
183 SF
WOMEN'S
TOILET
2AC1B
188 SF
MEN'S
TOILET
2AC1A81 SF
DIRTY
2AC2B
67 SF
PATIENT
TOILET
2AC2C
19 SF
TANK STO.
80 SF
CLEAN
SUPPLY
2AC2E
49 SF
HAC
2AC1D
0.9122.1367 5
A A
B
C C
D D
C4
D1
3.1
A.3
A.7
B.3
BBBA
/8
/8
/8
/8
14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"32' - 0"
1' - 5"14' - 6"21' - 0"21' - 0"21' - 0"20' - 1"32' - 0"1' - 5"
AE302
F.O.F.
F .O
.F
F.O.F.
F.O.F.
F.O.F.
F.O.F.
F .O
.F
B
129' - 7"
C
C
FUTURE
CORRIDOR
F.O.F.
F.O.F.
F.O.F.
DN
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:53:59 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D. DIMAT
AE102
ARCHITECTURAL SECOND FLOOR
PLAN
J.ALFARO
612-501
D. DIMAT
45 151
PROJECT
NORTH
1/8" = 1'-0"AE102
1 SECOND FLOOR PLAN
STAIR 1
6' - 0"7' - 10 1/2"
73 SF
ELECTRICAL
2AC1E
370 SF
IT STORAGE
2A06
316 SF
IT OPEN
OFFICE
2A05
101 SF
I.T.
2A08
293 SF
STAFF
2AC2D
AE201 5
80 SF
CLEAN
SUPPLY
2AC2E
AE604
AE502
AE503
AE503
AE604
AE604
AE502
SIM
67 5
A A
B
C C
D D
C4 C4
D1 D1
A.3
A.7
B.3
1' - 5" 32' - 0" 20' - 1"
1' - 5" 32' - 0" 20' - 1"
AE505
AE504
SIM
AE504
SIM
AE505
1' - 5"
1' - 5"
/4
8' - 11"5' - 10 3/4"
2' - 0"
21' - 6"
F .O
.W
DN
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
FEC
STC
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:54:01 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE102-1
ARCHITECTURAL SECOND FLOOR
ENLARGED PLAN - NORTH
J.ALFARO
612-501
D.DIMAT
46 151
1/4" = 1'-0"AE102-1
1 SECOND FLOOR ENLARGED PLAN NORTH
M A
T C
H L
IN
E
S E
E A
E -2
M A
T C
H L
IN
E
S E
E A
E -2
PROJECT
NORTH
STC
.E
.C
F.E.C.
STAIR 1
FUTURE
CORRIDOR
A
AE301
A
AE301
14' - 9 1/2"29' - 1 1/2"14' - 6 3/4"
9' - 7"6' - 2"4' - 0"13' - 0"8' - 0"6' - 6"4' - 0"2' - 6"4' - 0"6' - 6"8' - 0"2' - 3"8' - 0"7"
15' - 0"11' - 6"11' - 6"10' - 9 15/16"1' - 5"
8' - 6"5' - 8"13' - 6 1/4"11' - 10 3/4"7' - 1 1/4"7' - 2 1/2"6' - 0"9' - 0"4' - 0"
C
AE301
C
AE301
AE403
B
AE301
AE302
AE402 4
AE4026
AE405
370 SF
CONFERENCE
2A02
214 SF
LOUNGE
2A03
262 SF
CONFERENCE
2A04
103 SF
OFFICE
2A05A
99 SF
MULTI
PURPOSE
2A05B
316 SF
IT OPEN
OFFICE
2A05
101 SF
I.T.
2A08
370 SF
IT STORAGE
2A06
293 SF
STAFF
2AC2D
67 SF
PATIENT
TOILET
2AC2C
175 SF
GEN
PROCEDURE
2A13
172 SF
DERM LAB
2A12 174 SF
GEN
PROCEDURE
2A11
175 SF
GEN
PROCEDURE
2A10
120 SF
PROCEDURE
PREP
2A09
240 SF
PROCEDURE
WAITING
2A01188 SF
MEN'S
TOILET
2AC1A
183 SF
WOMEN'S
TOILET
2AC1B
101 SF
SHAFT
81 SF
DIRTY
2AC2B
631 SF
CORRIDOR
2AC2
1078 SF
CORRIDOR
2AC1
19 SF
TANK STO.
2AC2A
ST
AE604
AE604
AE505
AE505
AE505
AE504
AE604
AE604
AE604
AE604
80 SF
CLEAN
SUPPLY
2AC2E
AE504
OH
AE504
AE504
SIM.
AE504
AE502
AE502
49 SF
HAC
2AC1D
0.9
22.1
A
B
C
D
C4
D1
3.1
3.1
AE302
6 67
AE60411
TYP OF 3
FUTURE
CORRIDOR
F.O.F.
F.O.F.
9' - 4"
/4
1' - 3"12' - 0"2' - 6"12' - 0"9' - 9"3' - 3"4' - 0"6' - 6"4' - 0"2' - 6"4' - 0"6' - 6"4' - 0"6' - 6"8' - 0"10' - 10"
3' - 9 3/4" 9' - 2 1/4"
7 7
DN
SYMBOL
2-HOUR FIRE RATED PARTITION
1-HOUR FIRE RATED PARTITION
SOUND RATED PARTITION
FULL HEIGHT PARTITION
CEILING HEIGHT PARTITION
CORNER GUARD/END WALL GUARD
HANDRAIL/WALL GUARD COMBINATION
CHAIR RAIL
FULLY RECESSED FIRE EXTINGUISHER CABINET
FURRING
SOUND TRANSMISSION COEFFICIENT
RATING
LEGEND
CG EG
STC
FEC
GENERAL NOTES
1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.
1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.
4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.
SHELF FURRING AT BRACE. SEE DETAIL 9/AE503
AUTOMATED SUPPLY STORAGE UNIT (CELL).
120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES
(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED
EQUAL).
PROVIDE ROLLER SHADES.
PROVIDE ROLLER LIGHT ROOF SHADES.
COLLECTION AND STORAGE OF RECYCLABLES. (VV)
SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE
DETAIL 12/AE604.
MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR
REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL
CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR
MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE
GOVERNMENT.
RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.
CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.
(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.
45 MINUTE FIRE RATED GLAZING.
WORKSTATION - TYP.
ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.
3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.
FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR
CONNECTION (S.S.D. C/SS004).
FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION
AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET
12" ABOVE TOP OF METAL ROOF).
PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401
FURNITURE (VV)
SHEET NOTES
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:54:04 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE102-2
ARCHITECTURAL SECOND FLOOR
ENLARGED PLAN - SOUTH
J.ALFARO
612-501
D.DIMAT
47 151
1/4" = 1'-0"AE102-2
1 SECOND FLOOR ENLARGED PLAN SOUTH
M A
T C
H L
IN
E
S E
E A
E -1
M A
T C
H L
IN
E
S E
E A
E -1
9'-0"
ELEVATOR
7'-6"
801 SF
WAITING
56 SF
STAFF
63 SF
STAFF
1193 SF
OPEN OFFICE
100 SF
I.T.
225 SF
ELECTRICAL
710 SF
MECHANICAL
108 SF
MULTI
PURPOSE
102 SF
OFFICE
170 SF
LASER
123 SF
EXAM
ROOM
124 SF
EXAM
ROOM
124 SF
EXAM
ROOM
124 SF
EXAM
ROOM
124 SF
EXAM
ROOM
122 SF
EXAM
ROOM
125 SF
EXAM
ROOM 126 SF
EXAM
ROOM
213 SF
STAIR 2
847 SF
CORRIDOR
354 SF
STAFF
58 SF
PUBLIC
TOILET
59 SF
PUBLIC
TOILET
179 SF
HALL
210 SF
RECEPTION
75 SF
SHOWER
63 SF
PATIENT
TOILET
174 SF
PHOTO
J
J
J J
J J
801 SF
WAITING
1A01
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
0.9122.1367 5
A
B
C
D
C4
D1
3.1
A.3
A.7
B.3
11' - 0"
11' - 0"
370 SF
CONFERENCE
1078 SF
CORRIDOR
214 SF
LOUNGE
262 SF
CONFERENCE
103 SF
OFFICE
99 SF
MULTI
PURPOSE
316 SF
IT OPEN
OFFICE
101 SF
I.T.
S
F E
L E
C T
R
IC
A L
370 SF
IT STORAGE
293 SF
STAFF
175 SF
GEN
PROCEDURE 172 SF
DERM LAB
174 SF
GEN
PROCEDURE
175 SF
GEN
PROCEDURE
120 SF
PROCEDURE
PREP
240 SF
PROCEDURE
WAITING
631 SF
CORRIDOR
188 SF
MEN'S
TOILET
183 SF
WOMEN'S
TOILET
101 SF
SHAFT81 SF
DIRTY
67 SF
PATIENT
TOILET
8' - 0"
13' - 6"
8' - 0"
8' - 0"
8' - 0" 8' - 0"
0.9122.136 5
A
B
C
D
C4
D1
3.1
80 SF
CLEAN
SUPPLY
STAIR 2
GENERAL NOTES
1.
2.
ALL CEILINGS ARE 9'-0" A.F.F. U.O.N.
AT FIRE RATED ROOMS WITH GWB CEILINGS, (ROOM NUMBER
1AO1A, 2AC2B, AND 2AC2A) CONTRACTOR SHALL TERMINATE
FIRE RATED CONSTRUCTION INCLUDING FIREPROOFING OF
COLUMNS EXCEPT SHAFT WALL AT FIRE RATED CEILING
CONFORMING TO UL DESIGN L524 SYSTEM 1 FOR 1 HR FIRE
RATED CEILING ASSEMLIES. (SEE DETAIL 10/AE509).
SHEET NOTES
1 GWB SOFFIT AND DECORATIVE TRANSLUCENT RESIN PANEL.
SEE DETAIL 7 & 8/AE503. ALIGN CIRCLE CENTER W/ CENTERLINE
INTERSECTION OF BEAMS ABOVE.
EXPOSED METAL ROOF ABOVE.
PREFABRICATED METAL STAIR LANDING.
PROVIDE CEILING MOUNTED PATIENT LIFT SYSTEM ALIGN W/
EXAM TABLE SEAT - FIELD VERIFY EXACT LOCATION W/ VA. SEE
DETAIL 3/AE508.
CEILING MOUNTED PROJECTION SCREEN. SEE DETAIL 4/AE508.
APPLY SPRAYED-ON FIREPROOFING AT EXPOSED COLUMNS,
BEAMS AND FLOOR / ROOF DECK IN THIS ROOM AS SPECIFIED.
PREFABRICATED EXTERIOR ENTRY CANOPY.
OVERHANG TYP.
EIFS SOFFIT
ROOF HATCH ACCESS WELL.
GWB SOFFIT SEE DETAIL 4/AE507.
ACOUSTICAL TILE CEILING TRANSITION SEE DETAIL 3/AE507.
ACOUSTICAL TILE CEILING
LEGEND
ACOUSTICAL TILE CEILING WITH SPECIAL FINISH (SP)
GYPSUM BOARD CEILING/SOFFIT
EXPOSED CEILING
RECESSED LIGHT FIXTURES 2x2
REGISTERS
RECESSED LIGHT FIXTURES 2x4
CEILING SURFACE-MOUNTED
SUSPENDED FROM CENTERED
PATIENT LIFT SYSTEM
CURTAIN TRACK
EXIT SIGN
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:54:06 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE103
ARCHITECTURAL REFLECTED
CEILING PLANS
J.ALFARO
612-501
D.DIMAT
48 151
1/8" = 1'-0"AE103
1 FIRST FLOOR REFLECTED CEILING PLAN
1/8" = 1'-0"AE103
2 SECOND FLOOR REFLECTED CEILING PLAN
PROJECT
NORTH
R
R
129'-6" T.O.C.
C
AE301
C
AE301
AE403
AE404
B
AE301
AE405
0.9122.1367 5
A
B
C
D
C4
D1
3.1
A.3
A.7
B.3
AE302
AE503
AE505
/2
11' - 9" 3' - 6"
1' - 9"
11' - 3"
R
AE508
AE508
AE509
5 16
SHEET NOTES
PARAPET WITH COMPOSITE ALUM. COPING - TYP. U.O.N.
ROOF DRAIN AND OVERFLOW DRAIN TYP.
CURVED STANDING SEAM METAL ROOF.
SINGLE-PLY EPDM ROOFING OVER R33 ROOF DECK INSULATION
TYP U.O.N.
MECHANICAL EQUIPMENT SCREEN-TYP.
AHU.
SHAFT BELOW.
8' X 6' X 10" PAD.
ELEVATED ROOF PLATFORM AT ELEVATOR HOISTWAY.
METAL GUTTER & RAINWATER LEADER.
OVERHANG - TYP.
HIGH PARAPET.
SINGLE PLY EPDM ROOFING OVER R33 (AVG) TAPERED ROOF
DECK INSULATION.
SAFETY RAILING AND POST. SEE DETAIL 11/AE509
SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF
PARAPET 12" ABOVE TOP OF METAL ROOF).
PROVIDE METAL COUNTER FLASHING CUT-TO-FIT BETWEEN TOP
OF PARAPET COPING AND EDGE OF METAL ROOFING - SEAL ALL
EDGES.
RIDGE
CRICKET
SLOPE DOWN 1/4" : 12"
EXHAUST FAN
CONDENSING UNIT
SOLAR PANELS (SEE ELECTRICAL DWGS)
WALKWAY PADS
ROOF HATCH
LEGEND
R
GENERAL NOTES
1.
2.
3.
4.
5.
6.
SLOPE ROOFING 1/4" PER FOOT MINIMUM.
PROVIDE METAL FLASHING AND/OR SEALANTS AS APPLICABLE FOR
POSITIVE DRAINAGE AT ALL EXTERIOR JOINTS BETWEEN DIFFERENT
MATERIALS.
PROVIDE BASE FLASHING AT ALL VERTICAL-TO -HORIZONTAL
ROOFING SURFACE TRANSITION PER MANUFACTURER
RECOMMENDATIONS.
CONTRACTOR IS RESPONSIBLE FOR INTEGRATING AND
COORDINATING ALL WATERPROOFING ELEMENTS INCLUDING BUT
NOT LIMITED TO JOINT SEALANTS, PARAPET, CURB, WALL COPINGS,
FLASHING AND SIMILAR ROOFING MATERIALS AND ACCESSORIES.
CONTRACTOR SHALL PROVIDE A COMPLETE WATERTIGHT
EXTERIOR BUILDING ENVELOPE SYSTEM FREE OF AIR AND WATER
LEAKS.
THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTING A
WATERTIGHT FACILITY USING THE MEANS AND METHODS
ESTABLISHED BY THE NATIONAL FENESTRATION RATING COUNCIL
(NFRC), THE NATIONAL ROOFING CONTRACTOR'S ASSOCIATION,
WESTERN STATES ROOFING CONTRACTOR'S ASSOCIATION AND
ANY ADDITIONAL STANDARD PRACTICES, CODES AND
REQUIREMENTS AS NECESSARY TO ENSURE A WATERTIGHT
FACILITY FREE OF ANY LEAKS. ANY DETAILS PROVIDED HEREIN ARE
PROVIDED FOR GENERAL GUIDANCE TO CONVEY THE INTENTION OF
THE DESIGN, AND DOES NOT ALLEVIATE THE CONTRACTOR FROM
THE RESPONSIBILITY TO PROVIDE A COMPLETELY WATERTIGHT
FACILITY. THE CONTRACTOR SHALL PERFORM WATER TESTS TO
DEMONSTRATE TO THE SATISFACTION OF THE CONTRACTING
OFFICER THAT THE BUILDING DOES NOT LEAK. ANY DEFECTS OR
LEAKS SHALL BE IMMEDIATELY REPAIRED AT THE CONTRACTOR'S
EXPENSE.
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 9:54:07 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D. DIMAT
AE104
ARCHITECTURAL ROOF PLAN
J. ALFARO
612-501
D. DIMAT
49 151
1/8" = 1'-0"AE104
1 ROOF PLAN PROJECT
F .E
.C
F.E.C.
F .E
.C
F.E.C.
F.E.C.
P3 P1 P3 P1 P3 P1 P3 P1
P3
P2
P2
P2
P1
STAIR 2
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
EXAM
ROOM
847 SF
CORRIDOR
1AC2
STAFF
WAITING
OPEN OFFICEELECTRICAL
MECHANICAL
I.T.
OFFICE
LASER
MULTI
PURPOSE
E L
E V
A T
O R
STAFF
STAFF ELEVATOR
CONTROL
HALL
RECEPTION
H.A.C.
PUBLIC
TOILET
PUBLIC
TOILET
PHOTO
SHOWER
PATIENT
TOILET
DRP2
DRP1
DRP2 DRP2
RUBBER FLOORING (SEE
FINISH SCHEDULE AND SPECS)
STAINLESS STEEL GRATING
AT RECESSED MAT W/
FLOORING INSERTS
T Y
P
R
P2
P2
P2
P2
CONFERENCE
PROCEDURE
WAITING
PROCEDURE
PREP
GEN
PROCEDURE
GEN
PROCEDURE
DERM LAB
GEN
PROCEDURE
STAFF
CLEAN
SUPPLY
IT STORAGE
HAC
PATIENT
TOILET
DIRTY SHAFT
WOMEN'S
TOILET
MEN'S
TOILET
LOUNGECONFERENCE
OFFICE
MULTI
PURPOSE
IT OPEN
OFFICE
I.T.
CORRIDOR
CORRIDOR
E L
E C
T R
IC
A
L
P2
P2
P3
P3
P3
P2
P2
P2P3 P2P1
TANK STO.
RUBBER FLOORING (SEE
FINISH SCHEDULE AND SPECS)
R
TYP.
R 5' - 9"
R 9' - 0"
R
R
R 9' - 0"
R
' - 8
R 9' - 0"
P3
P3
P3
P3
P3
P3
P3
CPT
CARPET
MANNINGTON, DESIGN LOCALE TUCSON
MESA 84167, SAGEBRUSH 43163
(3 STEP VERTICAL ASHLAR)
COLOR LEGEND:
RSF-3
SHEET VINYL FLOORING
MANNINGTON, ENTWINED
LINO / BERYL ETW105
RSF-2
SHEET VINYL FLOORING
MANNINGTON, PARADIGM
INTERSECT, CALIBER PAR108
(WITH HEAT WELDED SEAMS AT ROOMS WITH WSF)
RSF-1
SHEET VINYL FLOORING
MANNINGTON, BIOSPEC CHOICES
GRASSLAND 15366
PT-1
PORCELAIN TILE
DAL TILE, CONTINENTAL SLATE
EGYPTIAN BEIGE, CS50
WSF
SHEET VINYL FLOORING
MANNINGTON BIOSPEC
CHOICES GRASSLAND 15366
(HEAT WELDED SEAMS)
EPY
EPOXY
DECORATIVE RESIN PANEL
DESCRIPTION
DRP1
(1) 96" DIAMETER x 1/2" T CEILING DECORATIVE RESIN PANEL. SUSPEND PANEL
FROM FLOOR DECK ABOVE WITH (22) POINT SUPPORT CONNECTORS.
BOTTOM OF PANEL 11'-8"
DRP2
(3) 42" W x 24" H x 1/2" T WALL DECORATIVE RESIN PANEL. MOUNT EACH PANEL
WITH (4) POINT SUPPORT CONNECTORS. BOTTOM OF PANELS @ 4" AFF.
DECORATIVE RESIN PANEL
GENERAL NOTES
1.
2.
3.
4.
ALL DECORATIVE RESIN PANELS (DRP) ARE VARIA ECORESIN BY 3 FORM
OR APPROVED EQUAL.
DRP1 & DRP2 PATTERNS ARE GO-GO CASTAWAY CENTERED + SKYDIVE
B48 + POWDER D03 WITH SANDSTONE FINISH BOTH SIDES
MOUNT WALL PANELS WITH THREADED RODS WELDED OR BOLTED TO
METAL STUDS OR BACKING PLATES (SSD)
MOUNT CEILING PANEL WITH THREADED RODS WELDED OR BOLTED TO
STEEL DECK ABOVE (SSD)
P1
P2
P3
DRP1
DRP2
WALL FINISH LEGEND:
ACCENT PAINT (SEE SPECS.)
ACCENT PAINT (SEE SPECS.)
ACCENT PAINT (SEE SPECS.)
DECORATIVE RESIN PANEL
DECORATIVE RESIN PANEL
L I C
E N S E D A R C H I T E
C T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 11:02:18 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE105
ARCHITECTURAL FINISH PLANS
J.ROBERTS
612-501
D.DIMAT
50 151
PROJECT
NORTH
PROJECT
NORTH
1/8" = 1'-0"AE105
1 FIRST FLOOR FINISH PLAN
1/8" = 1'-0"AE105
2 SECOND FLOOR FINISH PLAN
.E
.C
F.E.C.
F.E.C.
F.E.C.F.E.C.
F.E.C.
F .E
.C
370 SF
CONFERENCE
2A02
214 SF
LOUNGE
2A03
262 SF
CONFERENCE
2A04
103 SF
OFFICE
2A05A
99 SF
MULTI
PURPOSE
2A05B
316 SF
IT OPEN
OFFICE
2A05
101 SF
I.T.
2A08
73 SF
ELECTRICAL
2AC1E
1078 SF
CORRIDOR
2AC1
240 SF
PROCEDURE
WAITING
2A01
120 SF
PROCEDURE
PREP
2A09
175 SF
GEN
PROCEDURE
2A10
174 SF
GEN
PROCEDURE
2A11
172 SF
DERM LAB
2A12
175 SF
GEN
PROCEDURE
2A13
293 SF
STAFF
2AC2D
80 SF
CLEAN
SUPPLY
2AC2E
370 SF
IT STORAGE
2A06
631 SF
CORRIDOR
2AC2
188 SF
MEN'S
TOILET
2AC1A
183 SF
WOMEN'S
TOILET
2AC1B
101 SF
SHAFT
81 SF
DIRTY
2AC2B
67 SF
PATIENT
TOILET
2AC2C
49 SF
HAC
2AC1D
7279808185
87 82
616471
58 5657
51 52
19 SF
TANK STO.
2AC2A
213 SF
STAIR 2
S2
126 SF
EXAM
ROOM
1A04
125 SF
EXAM
ROOM
1A05
122 SF
EXAM
ROOM
1A06
124 SF
EXAM
ROOM
1A07
124 SF
EXAM
ROOM
1A08
124 SF
EXAM
ROOM
1A09
124 SF
EXAM
ROOM
1A10
123 SF
EXAM
ROOM
1A11
847 SF
CORRIDOR
1AC2
354 SF
STAFF
1AC2B
36 SF
H.A.C.
1AC2A
210 SF
RECEPTION
1A03
179 SF
HALL
1AC1
59 SF
PUBLIC
TOILET
1AC1B
58 SF
PUBLIC
TOILET
1AC1A
34 SF
ELEVATOR
CONTROL
1A01A
801 SF
WAITING
1A01
81 SF
ELEVATOR
E1
63 SF
STAFF
1A02C
56 SF
STAFF
1A02D
1193 SF
OPEN OFFICE
1A02
100 SF
I.T.
1A16
225 SF
ELECTRICAL
1A15
108 SF
MULTI
PURPOSE
1A02B
102 SF
OFFICE
1A02A
170 SF
LASER
1A12
710 SF
MECHANICAL
1A14
174 SF
PHOTO
1A13
75 SF
SHOWER
1A13A
63 SF
PATIENT
TOILET
1AC2C
25 2923
394041
424344
45 46
6 7 8
2 3
4 5
14 10 111617
GENERAL NOTES
1. SEE SIGNAGE SCHEDULE ON SHEET AE602
SYMBOL
SIGN NUMBER
LEGEND
DESCRIPTION
L I C
E N S E D A R C H I T E
C T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
"FULLY SPRINKLERED"
3/13/2018 11:02:19 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE106
ARCHITECTURAL SIGNAGE PLAN
J.ALFARO
612-501
D.DIMAT
51 151
1/8" = 1'-0"AE106
2 SECOND FLOOR SIGNAGE PLAN
1/8" = 1'-0"AE106
1 FIRST FLOOR SIGNAGE PLAN PROJECT
NORTH
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
MECHANICAL EQUIPMENT
SCREENS
EIFS - 2
CURTAIN WALL
GLAZING - TYP
T.O. HIGH
PARAPET
40' - 0"
(95.00')
(111.00')
(127.00')
(131.00')
(135.00')
ABCD C4D1 A.3A.7B.3
EIFS - 1
ALUM
COMP
PANELS
EIFS - 2
FUTURE CORRIDOR
CONNECTION (TYPE OF 3)
FUTURE LOBBY
CONNECTION
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
EIFS - 2
BAND OF
SPLIT FACE
CMU, TYP
MECHANICAL
EQUIPMENT
SCREENS
ALUM COMPOSITE
PANELS
ALUM. FRAMED
WINDOWS - TYP
T.O. HIGH
PARAPET
40' - 0"
(95.00')
(111.00')
(127.00')
(131.00')
(135.00')
CURVED STANDING
SEAM METAL ROOF
A B C DC4 D1A.3 A.7 B.3
AE201
SMOOTH FACE
CMU, TYP
ALUMINUM ENTRY
CANOPY
T.O.W.
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
EIFS - 2
MECHANICAL EQUIPMENT
SCREENS
EIFS - 2
CURVED STANDING
SEAM METAL ROOF
EIFS - 2
ALUM. FRAMED
ENTRANCE
ALUM FRAMED
STORE FRONT
GLAZING - TYP OF 3
ALUM. FRAMED
WINDOWS - TYP
T.O. HIGH
PARAPET
40' - 0"
(95.00')
(107.00')
(111.00')
(127.00')
(131.00')
(135.00')
CMU WALL
0.9 1 2 2.1 3 6 753.1
EIFS - 1
EIFS - 1
PREFAB STEEL STAIRS
AND LANDINGS
ALUM ENTRY
CANOPY
AE508
OH
T.O.W.
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
CMU WALL
ALUM COMPOSITE
PANELS
MECHANICAL
EQUIPMENT
SCREENS
EIFS - 2
T.O. HIGH
PARAPET
40' - 0"
(95.00')
(107.00')
(111.00')
(127.00')
(131.00')
(135.00')
ALUM. LOUVER
TYP. ALUM. FRAME WINDOWS - TYP
0.9122.1367 5 3.1
AE201
CLEAR ANODIZED ALUM COMPOSITE
PANELS AT FINS (TYP. OF 4)
STEEL GATE
CLEAR ANOD PANEL
AT OVERHANG TYP
ALUMINUM EXTERIOR
SUN SHADE
T.O.W.
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
B CA.3 A.7 B.3
ALUM
COMPOSITE
PANELS
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
T.O. HIGH
PARAPET
40' - 0"
D D1
VA SIGN
4' - 1"
COMPOSITE
ALUMINUM
PANELS
ALUMINUM COPING
EIFS
ALUMINUM
COPING
F O
S
T.O. ROOF RIDGE
32' - 0"
T.O. PARAPET
36' - 0"
T.O. HIGH
PARAPET
40' - 0"
CL
ALUMINUM
COMPOSITE
COPING
EIFS
HALO ILLUMINATED ALUM.
DIMENSIONAL LETTERS (SEE
SPECS)
3' - 0" 9"
2"
LINE 120-277 BAC 50/60 HZ
INPUT CURRENT 0.60A
OUTPUT VOLTS 12.0VDC
OUTPUT WATTS 60
OUTPUT CURRENT 5A
LED DRIVER
DISCONNECT SWITCH
BLK (LINE)
WHITE (NEUTRAL)
GRN (GROUNDING WIRE)TX
BONDING SCREW
METAL BACKING PLATE AND
THREADED CONNECTION WITH
WASHER AND NUT - TYP.
LAYOUT SIGN ANCHOR
LOCATIONS AND CORE DRILL
FINISH AND SUBSTRATES
FOR WATERTIGHT FIT - TYP.
F .O
.F
6". 2".
ELECTRICAL WIRE
18 GAUGE PLENUM
RATED WIRING
#18/2C CL3P/CMP
SHLD. OMNIPLEN
ALUMINUM FACE .125"
THREADED INSERT
FOR STUD MOUNT
SIGN TYPE EI-09.7
.1"
SIGN TYPE EN-06.02
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
3/13/2018 9:54:27 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE201
ARCHITECTURAL EXTERIOR
ELEVATIONS
J.ALFARO
612-501
D.DIMAT
52 151
1/8" = 1'-0"AE201
4 SOUTH ELEVATION
1/8" = 1'-0"AE201
2 NORTH ELEVATION
1/8" = 1'-0"AE201
3 EAST ELEVATION
1/8" = 1'-0"AE201
1 WEST ELEVATION
1/8" = 1'-0"AE201
5 NORTH ELEVATION @ MECH YARD
1/2" = 1'-0"AE201
6 T.O. FIN DETAIL
1/2" = 1'-0"AE201
7 VA SIGN DETAIL
SCALE: NTSAE201
8 VA SIGN DETAILS
SECOND FLOOR
16' - 0"
T.O. PARAPET
36' - 0"
(95.00')
T.O. SCREEN
41' - 0"
32'-0"
T.O.C. @ RIDGE
5 3 4
ABCD C4D1
VARIES
T.O.C.
VARIES
T.O.C.
CLEAR ANODIZED
ALUM COMP
PANELS AT FINS
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. SCREEN
41' - 0"
(95.00')
V.I.F. WITH
ELEVATOR MFR.
-5' - 0"
1 2
A B C DC4 D1
VARIES
T.O.C.
ALUMINUM
COMPOSITE PANEL
EIFS - 1
ALUMINUM FRAMED
WINDOW - TYPEIFS - 2
ALUM ENTRY
CANOPY
CLEAR ANODIZED ALUM
COMP PANELS AT FINS
EIFS 2
AE505
T.O.W.
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
16' - 0"
T.O. PARAPET
36' - 0"
T.O. SCREEN
41' - 0"
T.O. PARAPET_2
20' - 0"
(95.00')
0.912367 5 3.1
VARIES
T.O.C.
ALUMINUM
COMPOSITE
PANEL
SMOOTH
FACE CMU
GENERAL NOTES
1. BUILDING SECTIONS ARE DIAGRAMMATIC AND INTENDED TO SHOW
RELATIVE POSITION OF FLOORS, WALLS AND CEILINGS.
SHEET NOTES
1 HVAC UNITS
MECH. EQUIPMENT SCREEN
SHAFT
CEILING (TYP)
PARTITION (TYP)
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
3/13/2018 9:54:32 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE301
ARCHITECTURAL BUILDING
SECTIONS
J.ALFARO
612-501
D.DIMAT
53 151
1/8" = 1'-0"AE301
A BUILDING SECTION A
1/8" = 1'-0"AE301
B BUILDING SECTION B
1/8" = 1'-0"AE301
C BUILDING SECTION C
SHEET NOTES
1 ALUMINUM COMPOSITE COPING
ALUMINUM COMPOSITE PANEL CLADDING SYSTEM
ROOFING MEMBRANE PARAPET FLASHING OVER 5/8" TYPE 'X' GLASS MAT
FACED GWB SHEATHING
SINGLE PLY ROOFING MEMBRANE OVER ROOF DECK INSULATION
COMPOSITE STEEL DECK AND STEEL BEAM - SSD
LINEAR METAL CEILING
ALUMINUM SUN SHADE. SEE DETAIL 3/AE501
GLAZING. SEE SCHEDULE
FLOORING PER FINISH SCHEDULE
5/8" TYPE 'X' GWB. TYP.
AIR BARRIER OVER 5/8" TYPE 'X' GLASS MAT FACED GWB SHEATHING
6" METAL STUDS
BATT INSULATION BETWEEN STUDS WITH VAPOR BARRIER ON INTERIOR
FACE
WEATHER BARRIER OVER 5/8" TYPE 'X' GLASS MAT FACED GWB
SHEATHING
8" METAL STUDS - SSD
EIFS
CEILING PER SCHEDULE
1-HR FIRE RATED SHAFT WALL
STEEL BEAM AND DECK - SSD
STEEL BEAM - SSD
NOT USED
NOT USED
ALUMINUM LOUVER
HORIZONTAL REVEAL, TYP
AE502
AE503
12 13
AE502
AE502
AE502
AE502
D D1
AE502
AE505
AE507
10 OH
OH
AE504
12 13
5 13
AE504
AE504
AE504
A
AE504
AE507
AE505
OH
C
AE505
D D1
AE505
AE507
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
3/13/2018 9:54:34 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE302
ARCHITECTURAL EXTERIOR WALL
SECTIONS
J.ALFARO
612-501
D.DIMAT
54 151
1/2" = 1'-0"AE302
1 SECTION @ ALUM. COMP. PANELS
1/2" = 1'-0"AE302
3 SECTION 3
1/2" = 1'-0"AE302
2 SECTION @ EIFS
1/2" = 1'-0"AE302
5 SECTION @ ALUM COMP PANELS
1/2" = 1'-0"AE302
4 SECTION @ HIGH PARAPET
SHEET NOTES
1 UNDERSIDE OF STRUCTURE
SLOTTED METAL TRACK W/ FASTENER(S) @ 24" O.C. (S.S.D.)
6" METAL STUDS - TOP OF STUDS 1/2" BELOW TOP OF TRACK (S.S.D.)
FIRE CAULK BOTH SIDES
6" THK BATT INSUL. BETWEEN STUDS
5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES - FIRE STOP ALL
PENETRATIONS. DO NOT ATTACH TO TOP TRACK
CEILING PER SCHEDULE
METAL TRACK W/ SHOT PIN @ 32" O.C. (S.S.D.)
FLOORING AND BASE PER SCHEDULE (BOTH SIDES WHERE APPLICABLE)
(2) LAYER 5/8" TYPE 'X'GYPSUM BOARD BOTH SIDES - FIRE STOP ALL
PENETRATIONS. DO NOT ATTACH TO TOP TRACK
5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES, SEAL ALL PENETRATIONS W/
ACOUSTICAL SEALANT. DO NOT ATTACH TO TOP TRACK
ACOUSTICAL JOINT SEALANT BOTH SIDES
5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES. CUT AND PATCH AROUND
PENETRATIONS AS REQUIRED - DO NOT ATTACH TO TOP TRACK
5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES
2-1/2" SOUND ATTENUATION BLANKETS BETWEEN STUDS
PARTITION TYPE PER PLAN
2-1/2" (MIN.) METAL FURRING STUDS
2-1/2" BATT INSULATION BETWEEN STUDS
5/8" TYPE 'X' GYPSUM BOARD
HORIZONTAL STUD FRAMING BETWEEN CHASE PARTITIONS. CLIP TO EA.
STUD AND TRACK
4" METAL STUDS
5/8" CEMENT BOARD BEHIND WAINSCOT
WAINSCOT, BASE AND FLOORING PER SCHEDULE
ACOUSTICAL JOINT SEALANT
1" TYPE 'X' GYPSUM BOARD SHAFT WALL LINER
6" C-H TYPE METAL SHAFT STUD @ 24" O.C.
J & C TYPE METAL TRACKS - INSTALL AND FASTEN PER SHAFT WALL
SYSTEM MANUFACTURER INSTRUCTION
CONT. 'Z' METAL CLIP ATTACH TO WALL STUD
M
IN4
M
IN4
M
IN8
20 15
ROOM SHAFT
L I C
E N S E D A R C H I T EC
T
S T
A T
E O F C A L I F O
R N
I A
JO
RGE E . A L FARO
REN._______
C-22051
03/19
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t
VA FORM 08-6231
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Drawing Title: Project Title: Project Number:
Building Number:
Drawing Number:Location
Date Checked Drawn
Office of Construction and Facilities Management
Dwg. of02/12/2018
VA MEDICAL CENTER, MATHER, CA 95655
644K F DAVIS ENGINEERING, INC
530 LA GONDA WAY, SUITE E,
DANVILLE, CA 94526
WWW.KFDE.COM
(925) 743-8884
3/13/2018 9:54:35 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt
NEW DERMATOLOGY
OUTPATIENT SERVICES
BUILDING
D.DIMAT
AE303
ARCHITECTURAL INTERIOR WALL
SECTIONS
J.ALFARO
612-501
D.DIMAT
55 151
1" = 1'-0"AE303
1 ONE HOUR FIRE RATED PARTITION
1" = 1'-0"AE303
2 TWO HOUR FIRE RATED PARTITION STC 45
1" = 1'-0"AE303
4 FULL HEIGHT PARTITION
1" = 1'-0"AE303
3 SOUND RATED PARTITION STC 40
1" = 1'-0"AE303
5 CEILING HEIGHT PARTITION
1" = 1'-0"AE303
6 WALL FURRING
1" = 1'-0"AE303
7 PLUMBING CHASE
1" = 1'-0"AE303
8 ONE HOUR FIRE RATED SHAFT WALL
(STC 40 WHERE SHOWN)
A1/2" DIA. HANGERS
ANCHORED TO STRUCTURE
ABOVE
LATERALLY BRACE
SUSPENDED CHANNEL
TO WALL OR
STRUCTURE ABOVE
SUSPENDED CEILING
PER FINISH SCHEDULE.
3/8" STUD BOLT
MTL TOILET PARTITION
PILASTER W/CORE
AS SPECIFIED
TOP OF TOILET
PARTITION. SEE
MFGR'S DETAIL
METAL CLIP
GRAB BARS AT ALL
PUBLIC & PATIENT TOILETS
WALL FRAMING
STEEL CHANNEL (SIZE
FOR SPAN AS REQ'D.)
FRONT TRANSFER STANDARD
CEILING MOUNTED
TOILET PARTITIONS
66" 42" 36"
. 9
6" 3' - 0" 1' - 6"
15/16"
M
IN
.1'-6" 15/16" 15/16"
2' - 10"2' - 10"
DETAIL A
ELEVATION
PLAN
PLAN
SECTION
LINE OF CLEAR KNEE SPACE
CLEAR TOE SPACE
ACCESSIBLE FAUCET
M
IN
ACCESSIBLE WALL MOUNTED LAVATORY
30"x48" CLEAR SPACE CENTERED
IN FRONT OF LAVATORY WHICH
ADJOINS OR OVERLAPS AN
ACCESSIBLE ROUTE
COVER OR INSULATE HOT WATER &
DRAIN PIPES UNDER LAVATORY.
THERE SHALL BE NO SHARP OF
ABRASIVE SURFACES UNDER
LAVATORIES
ACCESSIBLE WALL
MOUNTED LAVATORY
NOTE:
FAUCET CONTROLS SHALL
BE OPERABLE WITH ONE
HAND AND SHALL NOT
REQUIRE TIGHT GRASPING,
PINCHING OR TWISTING OF
THE WRIST.
L A
V A
T O
R Y
C
L E
A R
S P
A C
E
17" MIN.
8" MIN.
M A
X
"2
M
IN
6" MIN.
25" MAX.
19" MAX.
6" MAX.
5'-0"
M
IN
M A
X
1'-0"
K-4329KING
STO
N
C_TO
ILETS
VITREO
US CHINA
K-4329KING STO NC_TO ILETSVITREO US CHINA
16" MIN.
18" MAX.
9" MAX.
7" MIN.
LINE OF FLOOR CLEAR SPACE
36" GRAB BAR, SEE DETAIL ON THIS SHEET
36"
GRAB
BAR
42" GRAB BAR
42" GRAB BAR
ACCESSIBLE WATER CLOSET: CONTROLS SHALL BE
OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
GRASPING, PINCHING OR TWISTING. CONTROLS FOR FLUSH
VALVES SHALL BE MOUNTED ON THE WIDE SIDE OF TOILET
AREAS, NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE
TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5
POUND FORCE (lbf).
AUTOMATIC "SPRING TO LIFTED POSITION" SEATS ARE NOT
ALLOWED.
TOILET SEAT COVER DISPENSER MOUNTED WITH OPERABLE
PARTS WITHIN 40" FROM THE FINISHED FLOOR.
WALLS WITHIN WATER
CLOSET COMPARTMENTS
SHALL BE FINISHED WITH
NON-ABSORBENT MATERIALS
SIMILARLY TO FLOORS.
TOILET ROOM FLOOR TO HAVE A NON-SLIP NONABSORBENT
HARD SURFACE SUCH AS CERAMIC TILE OR OTHER
APPROVED MATERIAL WITH INTEGRAL COVED BASE.
TOILET TISSUE DISPENSER. DISPENSERS THAT CONTROL DELIVERY
OR THAT DO NOT PERMIT CONTINUOUS PAPER FLOW SHALL NOT BE USED.
36" GRAB BAR SECURELY
ATTACHED PARALLEL TO THE FLOOR.
A .F
.F
FRONT ELEVATION
FIXTURE
ACCESSIBLE WATER CLOSET
SIDE ELEVATION
PLAN
M
IN
M A
X
ALTERNATE LOCATION
FOR TOILET SEAT
COVER DISPENSER
FLUSH ACTIVATOR ON
WIDE SIDE OF FIXTURE
(WHERE APPLICABLE)
NOTE: SAME LAYOUT APPLIES TO ACCESSORIES INSTALLED ON WALL/CEILING MOUNTED TOILET PARTITIONS
S O
A P
D
IS
P E
N S
E R
R E
C E
S S
E D
P A
P E
R T
O W
E L D
IS
P
E N
S E
R
W A
S T
E R
E C
E P
T A
C L E
W A
S T
E R
E C
E P
T A
C L E
R E
C E
S S
E D
P A
P E
R T
O W
E L D
IS
P
E N
S E
R
H A
N D
H
A
IR
D R
Y E
R
M
IR
R O
R
T O
IL
E
T S
E A
T C
O V
E R
D
IS
P E
N S
E R
R E
C E
S S
E D
S A
N
IT
A R
Y N
A P
K
IN
T
A M
P O
N V
E N
D O
R
T O
IL
E
T P
A P
E R
D
IS
P E
N S
E R
T O
G R
A B
B A
R
M A
X
S T
A
IN
L E
S S
S T
E E
L S
U R
F A
C E
M O
U N
T E
D H
O R
IZ
O
N T
A L
B A
B Y
C H
A N
G
IN
G S
T A
T
IO
N
THE PURPOSE OF THIS DIAGRAM IS TO ENSURE THAT ANY
TOILET ACCESSORY IS MOUNTED AT AN ACCESSIBLE
HEIGHT. THE TOILET ACCESSORIES AND FIXTURES
SHOWN ARE SCHEMATIC ONLY AND DO NOT MATCH
ACTUAL ITEMS SPECIFIED.
CONTRACTOR SHALL PROVIDE AND/OR INSTALL
ACCESSIBLE TOILET ACCESSORIES AS SPECIFIED OR AS
PROVIDED AND DIRECTED BY THE COR, INCLUDING BUT
NOT LIMITED TO THE ITEMS BELOW (WHERE APPLICABLE)
1. MIRRORS SHALL BE MOUNTED WITH THE BOTTOM
EDGE OF REFLECTIVE SURFACE NO HIGHER THAN
40 INCHES FROM THE FLOOR.
2. TOWEL, SANITARY NAPKINS, DISPENSERS WASTE
RECEPTACLES. WHERE TOWEL, SANITARY
NAPKIN, WASTE RECEPTACLES, AND OTHER
SIMILAR DISPENSING AND DISPOSAL FIXTURES ARE
PROVIDED, AT LEAST ONE OF EACH TYPE SHALL BE
LOCATED WITH ALL OPERABLE PARTS,
INCLUDING COIN SLOTS, WITHIN 40 INCHES FROM
THE FINISHED FLOOR.
3. IN ALL OCCUPANCIES, ACCESSORIES SUCH AS
GRAB BARS, TOWEL BARS, PAPER DISPENSERS
AND SOAP DISHES, PROVIDED ON OR WITHIN
WALLS, SHALL BE INSTALLED AND SEALED TO
PROTECT STRUCTURAL ELEMENTS FROM
MOISTURE.
4. PROVIDE BACKING PLATES, FILLER MATERIALS,
SUPPORTS AND MISCELLANEOUS FASTENERS, AS
REQUIRED FOR EACH ACCESSORY - SEE
SPECIFICATIONS
5. ANY PROTRUDING OBJECTS SHALL STAY 12" CLEAR
ABOVE AND 1-1/2" CLEAR BELOW GRAB BARS
M
IN
5'-0" MIN.
4'-0"
2 1/2"
MAX.
15"
/2
M A
X
M A
X
2'-6"
SEAT WALL
CONTROL
WALL
BACK WALL
F O
L D
A B
L E
S E
A T
GRAB BAR
CLEAR SPACE
NOTE:
VA SHOWER COMPARTMENT SIZE DIFFERS
FROM ABAAS. PROVIDE CUSTOM SIZE FOLDABLE
SEAT WITH ADEQUATE BLOCKING IN WALL TO SUPPORT
MIN. LIVE LOAD OF 500 LBS.
11/2"
DIAMETER OR WIDTH: THE DIAMETER OR WIDTH OF THE GRIPPING SURFACES OF A
GRAB BAR SHALL BE 1 1/4 INCHES TO 1 1/2 INCHES OR THE SHAPE SHALL
PROVIDE AN EQUIVALENT GRIPPING SURFACE. IF GRAB BARS ARE MOUNTED ADJACENT
TO A WALL, THE SPACE BETWEEN THE WALL AND THE GRAB BARS SHALL BE 1 1/2
INCHES.
STRUCTURAL STRENGTH: THE STRUCTURAL STRENGTH OF GRAB BARS, TUB AND
SHOWER SEATS,…