36C26118B0618-005.pdf

PDF 10 MB Posted

Attached to
Project #612-501 | Construct New Dermatology Outpatient Service Building
Solicitation number
36C26118B0618
Issued by

About this file

This pre-solicitation notice provides details for an upcoming Invitation for Bid to construct a new Dermatology Outpatient Service Building. The project is located at VA Northern California Healthcare System in Mather, California, with a period of performance of 500 days from notice to proceed. The solicitation will be issued on or about July 20, 2019 via FBO and include specifications and drawings. The construction magnitude is estimated between $5-10 million. The NAICS code is 236220 and it is set aside as a total small business opportunity. The single award will be a firm-fixed price contract for all labor, materials, permits and other requirements to build the outpatient facility.

36C26118B0618 C27 - 02-12-18 - ARCHITECTURAL - MATHER - DERMATOLOGY - 10TH SUBMITTAL_Part2.pdf

View the file

Other files

File Type Posted
36C26118B0618-0004001.docx DOCX document
36C26118B0618-0004000.docx DOCX document
36C26118B0618-0003000.docx DOCX document
36C26118B0618-0003001.pdf PDF
36C26118B0618-0003002.pdf PDF
36C26118B0618-0002000.docx DOCX document
36C26118B0618-0001000.docx DOCX document
36C26118B0618-0001001.pdf PDF
36C26118B0618-008.pdf PDF
36C26118B0618-012.pdf PDF
36C26118B0618-017.pdf PDF
36C26118B0618-007.pdf PDF
36C26118B0618-015.pdf PDF
36C26118B0618-003.pdf PDF
36C26118B0618-013.pdf PDF
36C26118B0618-010.pdf PDF
36C26118B0618-011.pdf PDF
36C26118B0618-014.pdf PDF
36C26118B0618-004.pdf PDF
36C26118B0618-006.pdf PDF
36C26118B0618-016.pdf PDF
36C26118B0618-009.pdf PDF
36C26118B0618-002.docx DOCX document
36C26118B0618-001.docx DOCX document
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F.E.C.F.E.C.

F.E.C.

UP

UP

F .E

.C

S T

A

IR

81 SF

ELEVATOR

E1

CHECK

OUT

FUTURE

CORRIDOR

MECHANICAL YARD

CL

FUTURE

LOBBY

M A

T C

H L

IN

E

M A

T C

H L

IN

E

AAA B

151617181921 20

23 25 27

31 28

A A A A

A A A A

F .O

.F

F .O

.F

F .O

.F

F.O.F.

F.O.F.

L2

AE404

AE403

AE405

A

AE301

A

AE301

95.00'

94.98

94.98'

95.00'

F.O.F.

AE406

AE406

AE406

C

AE301

C

AE301

AE403

AE404

B

AE301

B

AE301

AE302

AE302

AE302

AE402

AE402

AE405

801 SF

WAITING

1A01

210 SF

RECEPTION

1A03

36 SF

H.A.C.

1AC2A

179 SF

HALL

1AC1

58 SF

PUBLIC

TOILET

1AC1A

59 SF

PUBLIC

TOILET

1AC1B

34 SF

ELEVATOR

CONTROL

1A01A

56 SF

STAFF

1A02D

63 SF

STAFF

1A02C

354 SF

STAFF

1193 SF

OPEN OFFICE

1A02

75 SF

SHOWER

1A13A

63 SF

PATIENT

TOILET

1AC2C

174 SF

PHOTO

1A13

102 SF

OFFICE

1A02A

170 SF

LASER

1A12

100 SF

I.T.

1A16

108 SF

MULTI

PURPOSE

1A02B

225 SF

ELECTRICAL

1A15

710 SF

MECHANICAL

1A14

123 SF

EXAM

ROOM

1A11

124 SF

EXAM

ROOM

1A10

124 SF

EXAM

ROOM

1A09

124 SF

EXAM

ROOM

1A08

124 SF

EXAM

ROOM

1A07

122 SF

EXAM

ROOM

1A06

125 SF

EXAM

ROOM

1A05

126 SF

EXAM

ROOM

1A04

213 SF

STAIR 2

S2

847 SF

CORRIDOR

1AC2

L1 4

14 14

0.9122.1367 5

A

B

C C

D D

C4 C4

D1 D1

3.1

1' - 0 7/8"14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"32' - 0"26' - 1"

A.3

A.7

B.3

AE302

C94.98'

14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"1' - 5"

1' - 5"97' - 7"24' - 0"34' - 1"

/8

/8

/8

/8

/2

7"20' - 5"1' - 5"

/8

F.O.F.

F.O.F.

F.O.F.

AE101

94.98'

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

FEC

STC1

A

2 5/8"1' - 2 3/8"

/8

/8

F.O.S.

F.O.F.

F .O

.S

F .O

.F

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:53:45 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D. DIMAT

AE101

ARCHITECTURAL FIRST FLOOR

PLAN

J. ALFARO

612-501

D. DIMAT

42 151

1/8" = 1'-0"AE101

1 FIRST FLOOR PLAN PROJECT

NORTH

1 1/2" = 1'-0"AE101

2 TYPICAL EXTERIOR WALL DIMENSIONING

UP

F .E

.C

S T

A

IR

MECHANICAL YARD

26' - 1" 30' - 7"

1' - 5"

7" 8' - 0" 9"1' - 6" 8' - 0"

C

AE301

F.O.F.

F.O.F.

F.O.F.

F .O

.F

AE404

B

AE301

100 SF

I.T.

1A16

108 SF

MULTI

PURPOSE

1A02B

225 SF

ELECTRICAL

1A15

102 SF

OFFICE

1A02A

170 SF

LASER

1A12

710 SF

MECHANICAL

1A14

123 SF

EXAM

ROOM

1A11

124 SF

EXAM

ROOM

1A10

174 SF

PHOTO

1A13

F.O.F.

STC

STC

S T

C

AE201 5

AE502

4' - 10"

AE603

S T

C

3' - 0"

AE504

AE502

AE502

CL

CL

CL

AE302

AE603

67 5

A

B

C

D

C4

D1

A.3

A.7

B.3

10' - 0"

9 9 9

AE503

AE503

AE503

AE503

AE504

1' - 5"

/4

/4

/4

CL

AE508

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

STC

FEC

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:53:47 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D. DIMAT

AE101-1

ARCHITECTURAL FIRST FLOOR

ENLARGED PLAN - NORTH

J.ALFARO

612-501

D. DIMAT

43 151

1/4" = 1'-0"AE101-1

1 FIRST FLOOR ENLARGED PLAN NORTH

M A

T C

H L

IN

E

S E

E A

E -2

M A

T C

H L

IN

E

S E

E A

E -2

PROJECT

NORTH

UP

100' - 5"

FUTURE

CORRIDOR

FUTURE

CORRIDOR

A

AE301

A

AE301

1' - 6"9' - 0"11' - 5"6' - 0"10' - 6 1/2" 4' - 5"4' - 8"13' - 4"5' - 7"8' - 2 1/2"

1' - 3 1/2"

3 3/4"

1' - 3"12' - 0"2' - 6"12' - 0"9' - 9"1' - 4"8' - 5 1/4"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 9"8' - 0"10' - 7"1' - 5"

5' - 3"4' - 7"4' - 2" 1' - 4"

7' - 2"5' - 6"9' - 3"3' - 5"6' - 7 1/4"

1' - 1 1/4"

8' - 5 1/4"

4' - 3"

C

AE301

C

AE301

5' - 0"

AE403

B

AE301

AE302

AE302

AE402 12

AE402 17

AE405

801 SF

WAITING

1A01

ELEVATOR

E1

63 SF

STAFF

1A02C

56 SF

STAFF

1A02D

1193 SF

OPEN OFFICE

1A02

100 SF

I.T.

1A16

102 SF

OFFICE

1A02A

170 SF

LASER

1A12

174 SF

PHOTO

1A13

75 SF

SHOWER

1A13A

63 SF

PATIENT

TOILET

1AC2C

354 SF

STAFF

1AC2B

34 SF

ELEVATOR

CONTROL

1A01A

58 SF

PUBLIC

TOILET

1AC1A

179 SF

HALL

1AC1

210 SF

RECEPTION

1A03

36 SF

H.A.C.

1AC2A

59 SF

PUBLIC

TOILET

1AC1B

847 SF

CORRIDOR

1AC2

213 SF

STAIR 2

S2

126 SF

EXAM

ROOM

1A04

125 SF

EXAM

ROOM

1A05

122 SF

EXAM

ROOM

1A06

124 SF

EXAM

ROOM

1A07

124 SF

EXAM

ROOM

1A08

124 SF

EXAM

ROOM

1A09

124 SF

EXAM

ROOM

1A10

123 SF

EXAM

ROOM

1A11

AE603

AE504

AE504

AE503

AE502

AE604

AE603 15

8' - 6 1/2"

AE505

AE502

AE603

AE603 11

AE603

AE603

AE603

AE502

OH

AE505

AE502

AE502

7 TYP

AE505

AE504

AE603

0.9

22.13

A

B

C

D

C4

D1

3.1

3.1

EQEQ

7"1' - 0" 8' - 0"2' - 2"8' - 0"6' - 6"4' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 6"8' - 0"2' - 3"8' - 0"

7"

777777

CL

AE302

AE502

AE603

AE503

6 6

F .O

.F

3 3

CL

TYP OF 8

/4

C L R

F.O.F.

F .O

.F

9' - 0"

3' - 0"

10' - 9"10' - 6"10' - 6"10' - 6"10' - 6"10' - 6"10' - 6"9' - 4"

/8

/4

/8

/8

/8

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER

CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

STC

FEC

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:53:50 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D. DIMAT

AE101-2

ARCHITECTURAL FIRST FLOOR

ENLARGED PLAN - SOUTH

J.ALFARO

612-501

D. DIMAT

44 151

1/4" = 1'-0"AE101-2

1 FIRST FLOOR ENLARGED PLAN SOUTH

M A

T C

H L

IN

E

S E

E A

E -1

M A

T C

H L

IN

E

S E

E A

E -1

F .E

.C

UP

F.E.C.

F.E.C.

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

FEC

STC

S T

A

IR

FUTURE

CORRIDOR

M A

T C

H L

IN

E

M A

T C

H L

IN

E

A

AE301

A

AE301

AE403

6564 66 67

45 42

B AABBAA

A

A

AE402

AE405

AE404

AE406

4 AE406

C

AE301

C

AE301

6' - 0"

AE403

AE404

B

AE301

AE302

AE302

AE302

AE405

370 SF

CONFERENCE

2A02

240 SF

PROCEDURE

WAITING

2A01

214 SF

LOUNGE

2A03

262 SF

CONFERENCE

2A04

103 SF

OFFICE

2A05A

99 SF

MULTI

PURPOSE

2A05B316 SF

IT OPEN

OFFICE

2A05

101 SF

I.T.

2A08

1078 SF

CORRIDOR

2AC1

120 SF

PROCEDURE

PREP

2A09

631 SF

CORRIDOR

2AC2

175 SF

GEN

PROCEDURE

2A10

174 SF

GEN

PROCEDURE

2A11

172 SF

DERM LAB

2A12

175 SF

GEN

PROCEDURE

2A13

293 SF

STAFF

2AC2D

370 SF

IT STORAGE

2A06

S

F E

L E

C T

R

IC

A L

A

C E

101 SF

SHAFT

183 SF

WOMEN'S

TOILET

2AC1B

188 SF

MEN'S

TOILET

2AC1A81 SF

DIRTY

2AC2B

67 SF

PATIENT

TOILET

2AC2C

19 SF

TANK STO.

80 SF

CLEAN

SUPPLY

2AC2E

49 SF

HAC

2AC1D

0.9122.1367 5

A A

B

C C

D D

C4

D1

3.1

A.3

A.7

B.3

BBBA

/8

/8

/8

/8

14' - 6"21' - 0"2' - 0"19' - 0"21' - 0"20' - 1"32' - 0"

1' - 5"14' - 6"21' - 0"21' - 0"21' - 0"20' - 1"32' - 0"1' - 5"

AE302

F.O.F.

F .O

.F

F.O.F.

F.O.F.

F.O.F.

F.O.F.

F .O

.F

B

129' - 7"

C

C

FUTURE

CORRIDOR

F.O.F.

F.O.F.

F.O.F.

DN

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:53:59 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D. DIMAT

AE102

ARCHITECTURAL SECOND FLOOR

PLAN

J.ALFARO

612-501

D. DIMAT

45 151

PROJECT

NORTH

1/8" = 1'-0"AE102

1 SECOND FLOOR PLAN

STAIR 1

6' - 0"7' - 10 1/2"

73 SF

ELECTRICAL

2AC1E

370 SF

IT STORAGE

2A06

316 SF

IT OPEN

OFFICE

2A05

101 SF

I.T.

2A08

293 SF

STAFF

2AC2D

AE201 5

80 SF

CLEAN

SUPPLY

2AC2E

AE604

AE502

AE503

AE503

AE604

AE604

AE502

SIM

67 5

A A

B

C C

D D

C4 C4

D1 D1

A.3

A.7

B.3

1' - 5" 32' - 0" 20' - 1"

1' - 5" 32' - 0" 20' - 1"

AE505

AE504

SIM

AE504

SIM

AE505

1' - 5"

1' - 5"

/4

8' - 11"5' - 10 3/4"

2' - 0"

21' - 6"

F .O

.W

DN

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

FEC

STC

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:54:01 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE102-1

ARCHITECTURAL SECOND FLOOR

ENLARGED PLAN - NORTH

J.ALFARO

612-501

D.DIMAT

46 151

1/4" = 1'-0"AE102-1

1 SECOND FLOOR ENLARGED PLAN NORTH

M A

T C

H L

IN

E

S E

E A

E -2

M A

T C

H L

IN

E

S E

E A

E -2

PROJECT

NORTH

STC

.E

.C

F.E.C.

STAIR 1

FUTURE

CORRIDOR

A

AE301

A

AE301

14' - 9 1/2"29' - 1 1/2"14' - 6 3/4"

9' - 7"6' - 2"4' - 0"13' - 0"8' - 0"6' - 6"4' - 0"2' - 6"4' - 0"6' - 6"8' - 0"2' - 3"8' - 0"7"

15' - 0"11' - 6"11' - 6"10' - 9 15/16"1' - 5"

8' - 6"5' - 8"13' - 6 1/4"11' - 10 3/4"7' - 1 1/4"7' - 2 1/2"6' - 0"9' - 0"4' - 0"

C

AE301

C

AE301

AE403

B

AE301

AE302

AE402 4

AE4026

AE405

370 SF

CONFERENCE

2A02

214 SF

LOUNGE

2A03

262 SF

CONFERENCE

2A04

103 SF

OFFICE

2A05A

99 SF

MULTI

PURPOSE

2A05B

316 SF

IT OPEN

OFFICE

2A05

101 SF

I.T.

2A08

370 SF

IT STORAGE

2A06

293 SF

STAFF

2AC2D

67 SF

PATIENT

TOILET

2AC2C

175 SF

GEN

PROCEDURE

2A13

172 SF

DERM LAB

2A12 174 SF

GEN

PROCEDURE

2A11

175 SF

GEN

PROCEDURE

2A10

120 SF

PROCEDURE

PREP

2A09

240 SF

PROCEDURE

WAITING

2A01188 SF

MEN'S

TOILET

2AC1A

183 SF

WOMEN'S

TOILET

2AC1B

101 SF

SHAFT

81 SF

DIRTY

2AC2B

631 SF

CORRIDOR

2AC2

1078 SF

CORRIDOR

2AC1

19 SF

TANK STO.

2AC2A

ST

AE604

AE604

AE505

AE505

AE505

AE504

AE604

AE604

AE604

AE604

80 SF

CLEAN

SUPPLY

2AC2E

AE504

OH

AE504

AE504

SIM.

AE504

AE502

AE502

49 SF

HAC

2AC1D

0.9

22.1

A

B

C

D

C4

D1

3.1

3.1

AE302

6 67

AE60411

TYP OF 3

FUTURE

CORRIDOR

F.O.F.

F.O.F.

9' - 4"

/4

1' - 3"12' - 0"2' - 6"12' - 0"9' - 9"3' - 3"4' - 0"6' - 6"4' - 0"2' - 6"4' - 0"6' - 6"4' - 0"6' - 6"8' - 0"10' - 10"

3' - 9 3/4" 9' - 2 1/4"

7 7

DN

SYMBOL

2-HOUR FIRE RATED PARTITION

1-HOUR FIRE RATED PARTITION

SOUND RATED PARTITION

FULL HEIGHT PARTITION

CEILING HEIGHT PARTITION

CORNER GUARD/END WALL GUARD

HANDRAIL/WALL GUARD COMBINATION

CHAIR RAIL

FULLY RECESSED FIRE EXTINGUISHER CABINET

FURRING

SOUND TRANSMISSION COEFFICIENT

RATING

LEGEND

CG EG

STC

FEC

GENERAL NOTES

1. NOT ALL SHEET NOTES ARE USED ON EVERY SHEET.

1 EXHAUST FAN (SMD) CENTER ABOVE DOOR.

4'-0" x 3'-0" METAL LOUVER (SMD). MOUNT SILL 12" AFF.

SHELF FURRING AT BRACE. SEE DETAIL 9/AE503

AUTOMATED SUPPLY STORAGE UNIT (CELL).

120"L x 120"W x 3/4" D SLAB RECESS W/ FLUSH ENTRANCE MAT TILES

(C.S. FLOROMETRY 301 OVALS, 902 PEBBLE BEACH OR APPROVED

EQUAL).

PROVIDE ROLLER SHADES.

PROVIDE ROLLER LIGHT ROOF SHADES.

COLLECTION AND STORAGE OF RECYCLABLES. (VV)

SOLID SURFACE WAINSCOT BEHIND LAVATORY - TYP U.O.N. SEE

DETAIL 12/AE604.

MINIMUM ROOM CLEAR DEPTH IS 2'-7" BASED ON ELEVATOR MFR

REQUIREMENTS. BEFORE LAYING OUT WALLS. CONTRACTOR SHALL

CONFIRM REQUIRED CLEAR DIMENSIONS WITH ELEVATOR

MANUFACTURER AND SIZE ROOM ACCORDINGLY AT NO COST TO THE

GOVERNMENT.

RECEPTION COUNTERS AND DIVIDERS PANELS - TYP.

CEILING MOUNTED PATIENT LIFT SYSTEM ABOVE.

(3) 42"W x 24" H UNDER COUNTERS DECORATIVE RESIN PANELS.

45 MINUTE FIRE RATED GLAZING.

WORKSTATION - TYP.

ALUMINUM ROOF ACCESS LADDER. SEE DETAIL 6-7/AE507.

3'-0" x 3'-0" ROOF ACCESS WELL ABOVE.

FRAME 9'-2" HIGH WALL OPENING FOR FUTURE CORRIDOR

CONNECTION (S.S.D. C/SS004).

FRAME 11'-2" HIGH WALL OPENING FOR FUTURE LOBBY CONNECTION

AND PROVIDE INFILL METAL STUDS (S.S.D. A/SS004) (S.S.D.).

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF PARAPET

12" ABOVE TOP OF METAL ROOF).

PRE FABRICATED SHOWER COMPARTMENT. SEE DETAIL 5/AE401

FURNITURE (VV)

SHEET NOTES

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:54:04 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE102-2

ARCHITECTURAL SECOND FLOOR

ENLARGED PLAN - SOUTH

J.ALFARO

612-501

D.DIMAT

47 151

1/4" = 1'-0"AE102-2

1 SECOND FLOOR ENLARGED PLAN SOUTH

M A

T C

H L

IN

E

S E

E A

E -1

M A

T C

H L

IN

E

S E

E A

E -1

9'-0"

ELEVATOR

7'-6"

801 SF

WAITING

56 SF

STAFF

63 SF

STAFF

1193 SF

OPEN OFFICE

100 SF

I.T.

225 SF

ELECTRICAL

710 SF

MECHANICAL

108 SF

MULTI

PURPOSE

102 SF

OFFICE

170 SF

LASER

123 SF

EXAM

ROOM

124 SF

EXAM

ROOM

124 SF

EXAM

ROOM

124 SF

EXAM

ROOM

124 SF

EXAM

ROOM

122 SF

EXAM

ROOM

125 SF

EXAM

ROOM 126 SF

EXAM

ROOM

213 SF

STAIR 2

847 SF

CORRIDOR

354 SF

STAFF

58 SF

PUBLIC

TOILET

59 SF

PUBLIC

TOILET

179 SF

HALL

210 SF

RECEPTION

75 SF

SHOWER

63 SF

PATIENT

TOILET

174 SF

PHOTO

J

J

J J

J J

801 SF

WAITING

1A01

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

8' - 0"

0.9122.1367 5

A

B

C

D

C4

D1

3.1

A.3

A.7

B.3

11' - 0"

11' - 0"

370 SF

CONFERENCE

1078 SF

CORRIDOR

214 SF

LOUNGE

262 SF

CONFERENCE

103 SF

OFFICE

99 SF

MULTI

PURPOSE

316 SF

IT OPEN

OFFICE

101 SF

I.T.

S

F E

L E

C T

R

IC

A L

370 SF

IT STORAGE

293 SF

STAFF

175 SF

GEN

PROCEDURE 172 SF

DERM LAB

174 SF

GEN

PROCEDURE

175 SF

GEN

PROCEDURE

120 SF

PROCEDURE

PREP

240 SF

PROCEDURE

WAITING

631 SF

CORRIDOR

188 SF

MEN'S

TOILET

183 SF

WOMEN'S

TOILET

101 SF

SHAFT81 SF

DIRTY

67 SF

PATIENT

TOILET

8' - 0"

13' - 6"

8' - 0"

8' - 0"

8' - 0" 8' - 0"

0.9122.136 5

A

B

C

D

C4

D1

3.1

80 SF

CLEAN

SUPPLY

STAIR 2

GENERAL NOTES

1.

2.

ALL CEILINGS ARE 9'-0" A.F.F. U.O.N.

AT FIRE RATED ROOMS WITH GWB CEILINGS, (ROOM NUMBER

1AO1A, 2AC2B, AND 2AC2A) CONTRACTOR SHALL TERMINATE

FIRE RATED CONSTRUCTION INCLUDING FIREPROOFING OF

COLUMNS EXCEPT SHAFT WALL AT FIRE RATED CEILING

CONFORMING TO UL DESIGN L524 SYSTEM 1 FOR 1 HR FIRE

RATED CEILING ASSEMLIES. (SEE DETAIL 10/AE509).

SHEET NOTES

1 GWB SOFFIT AND DECORATIVE TRANSLUCENT RESIN PANEL.

SEE DETAIL 7 & 8/AE503. ALIGN CIRCLE CENTER W/ CENTERLINE

INTERSECTION OF BEAMS ABOVE.

EXPOSED METAL ROOF ABOVE.

PREFABRICATED METAL STAIR LANDING.

PROVIDE CEILING MOUNTED PATIENT LIFT SYSTEM ALIGN W/

EXAM TABLE SEAT - FIELD VERIFY EXACT LOCATION W/ VA. SEE

DETAIL 3/AE508.

CEILING MOUNTED PROJECTION SCREEN. SEE DETAIL 4/AE508.

APPLY SPRAYED-ON FIREPROOFING AT EXPOSED COLUMNS,

BEAMS AND FLOOR / ROOF DECK IN THIS ROOM AS SPECIFIED.

PREFABRICATED EXTERIOR ENTRY CANOPY.

OVERHANG TYP.

EIFS SOFFIT

ROOF HATCH ACCESS WELL.

GWB SOFFIT SEE DETAIL 4/AE507.

ACOUSTICAL TILE CEILING TRANSITION SEE DETAIL 3/AE507.

ACOUSTICAL TILE CEILING

LEGEND

ACOUSTICAL TILE CEILING WITH SPECIAL FINISH (SP)

GYPSUM BOARD CEILING/SOFFIT

EXPOSED CEILING

RECESSED LIGHT FIXTURES 2x2

REGISTERS

RECESSED LIGHT FIXTURES 2x4

CEILING SURFACE-MOUNTED

SUSPENDED FROM CENTERED

PATIENT LIFT SYSTEM

CURTAIN TRACK

EXIT SIGN

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:54:06 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE103

ARCHITECTURAL REFLECTED

CEILING PLANS

J.ALFARO

612-501

D.DIMAT

48 151

1/8" = 1'-0"AE103

1 FIRST FLOOR REFLECTED CEILING PLAN

1/8" = 1'-0"AE103

2 SECOND FLOOR REFLECTED CEILING PLAN

PROJECT

NORTH

R

R

129'-6" T.O.C.

C

AE301

C

AE301

AE403

AE404

B

AE301

AE405

0.9122.1367 5

A

B

C

D

C4

D1

3.1

A.3

A.7

B.3

AE302

AE503

AE505

/2

11' - 9" 3' - 6"

1' - 9"

11' - 3"

R

AE508

AE508

AE509

5 16

SHEET NOTES

PARAPET WITH COMPOSITE ALUM. COPING - TYP. U.O.N.

ROOF DRAIN AND OVERFLOW DRAIN TYP.

CURVED STANDING SEAM METAL ROOF.

SINGLE-PLY EPDM ROOFING OVER R33 ROOF DECK INSULATION

TYP U.O.N.

MECHANICAL EQUIPMENT SCREEN-TYP.

AHU.

SHAFT BELOW.

8' X 6' X 10" PAD.

ELEVATED ROOF PLATFORM AT ELEVATOR HOISTWAY.

METAL GUTTER & RAINWATER LEADER.

OVERHANG - TYP.

HIGH PARAPET.

SINGLE PLY EPDM ROOFING OVER R33 (AVG) TAPERED ROOF

DECK INSULATION.

SAFETY RAILING AND POST. SEE DETAIL 11/AE509

SLOPE PARAPET TO MATCH SLOPE OF METAL ROOF (TOP OF

PARAPET 12" ABOVE TOP OF METAL ROOF).

PROVIDE METAL COUNTER FLASHING CUT-TO-FIT BETWEEN TOP

OF PARAPET COPING AND EDGE OF METAL ROOFING - SEAL ALL

EDGES.

RIDGE

CRICKET

SLOPE DOWN 1/4" : 12"

EXHAUST FAN

CONDENSING UNIT

SOLAR PANELS (SEE ELECTRICAL DWGS)

WALKWAY PADS

ROOF HATCH

LEGEND

R

GENERAL NOTES

1.

2.

3.

4.

5.

6.

SLOPE ROOFING 1/4" PER FOOT MINIMUM.

PROVIDE METAL FLASHING AND/OR SEALANTS AS APPLICABLE FOR

POSITIVE DRAINAGE AT ALL EXTERIOR JOINTS BETWEEN DIFFERENT

MATERIALS.

PROVIDE BASE FLASHING AT ALL VERTICAL-TO -HORIZONTAL

ROOFING SURFACE TRANSITION PER MANUFACTURER

RECOMMENDATIONS.

CONTRACTOR IS RESPONSIBLE FOR INTEGRATING AND

COORDINATING ALL WATERPROOFING ELEMENTS INCLUDING BUT

NOT LIMITED TO JOINT SEALANTS, PARAPET, CURB, WALL COPINGS,

FLASHING AND SIMILAR ROOFING MATERIALS AND ACCESSORIES.

CONTRACTOR SHALL PROVIDE A COMPLETE WATERTIGHT

EXTERIOR BUILDING ENVELOPE SYSTEM FREE OF AIR AND WATER

LEAKS.

THE CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTING A

WATERTIGHT FACILITY USING THE MEANS AND METHODS

ESTABLISHED BY THE NATIONAL FENESTRATION RATING COUNCIL

(NFRC), THE NATIONAL ROOFING CONTRACTOR'S ASSOCIATION,

WESTERN STATES ROOFING CONTRACTOR'S ASSOCIATION AND

ANY ADDITIONAL STANDARD PRACTICES, CODES AND

REQUIREMENTS AS NECESSARY TO ENSURE A WATERTIGHT

FACILITY FREE OF ANY LEAKS. ANY DETAILS PROVIDED HEREIN ARE

PROVIDED FOR GENERAL GUIDANCE TO CONVEY THE INTENTION OF

THE DESIGN, AND DOES NOT ALLEVIATE THE CONTRACTOR FROM

THE RESPONSIBILITY TO PROVIDE A COMPLETELY WATERTIGHT

FACILITY. THE CONTRACTOR SHALL PERFORM WATER TESTS TO

DEMONSTRATE TO THE SATISFACTION OF THE CONTRACTING

OFFICER THAT THE BUILDING DOES NOT LEAK. ANY DEFECTS OR

LEAKS SHALL BE IMMEDIATELY REPAIRED AT THE CONTRACTOR'S

EXPENSE.

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 9:54:07 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D. DIMAT

AE104

ARCHITECTURAL ROOF PLAN

J. ALFARO

612-501

D. DIMAT

49 151

1/8" = 1'-0"AE104

1 ROOF PLAN PROJECT

F .E

.C

F.E.C.

F .E

.C

F.E.C.

F.E.C.

P3 P1 P3 P1 P3 P1 P3 P1

P3

P2

P2

P2

P1

STAIR 2

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

EXAM

ROOM

847 SF

CORRIDOR

1AC2

STAFF

WAITING

OPEN OFFICEELECTRICAL

MECHANICAL

I.T.

OFFICE

LASER

MULTI

PURPOSE

E L

E V

A T

O R

STAFF

STAFF ELEVATOR

CONTROL

HALL

RECEPTION

H.A.C.

PUBLIC

TOILET

PUBLIC

TOILET

PHOTO

SHOWER

PATIENT

TOILET

DRP2

DRP1

DRP2 DRP2

RUBBER FLOORING (SEE

FINISH SCHEDULE AND SPECS)

STAINLESS STEEL GRATING

AT RECESSED MAT W/

FLOORING INSERTS

T Y

P

R

P2

P2

P2

P2

CONFERENCE

PROCEDURE

WAITING

PROCEDURE

PREP

GEN

PROCEDURE

GEN

PROCEDURE

DERM LAB

GEN

PROCEDURE

STAFF

CLEAN

SUPPLY

IT STORAGE

HAC

PATIENT

TOILET

DIRTY SHAFT

WOMEN'S

TOILET

MEN'S

TOILET

LOUNGECONFERENCE

OFFICE

MULTI

PURPOSE

IT OPEN

OFFICE

I.T.

CORRIDOR

CORRIDOR

E L

E C

T R

IC

A

L

P2

P2

P3

P3

P3

P2

P2

P2P3 P2P1

TANK STO.

RUBBER FLOORING (SEE

FINISH SCHEDULE AND SPECS)

R

TYP.

R 5' - 9"

R 9' - 0"

R

R

R 9' - 0"

R

' - 8

R 9' - 0"

P3

P3

P3

P3

P3

P3

P3

CPT

CARPET

MANNINGTON, DESIGN LOCALE TUCSON

MESA 84167, SAGEBRUSH 43163

(3 STEP VERTICAL ASHLAR)

COLOR LEGEND:

RSF-3

SHEET VINYL FLOORING

MANNINGTON, ENTWINED

LINO / BERYL ETW105

RSF-2

SHEET VINYL FLOORING

MANNINGTON, PARADIGM

INTERSECT, CALIBER PAR108

(WITH HEAT WELDED SEAMS AT ROOMS WITH WSF)

RSF-1

SHEET VINYL FLOORING

MANNINGTON, BIOSPEC CHOICES

GRASSLAND 15366

PT-1

PORCELAIN TILE

DAL TILE, CONTINENTAL SLATE

EGYPTIAN BEIGE, CS50

WSF

SHEET VINYL FLOORING

MANNINGTON BIOSPEC

CHOICES GRASSLAND 15366

(HEAT WELDED SEAMS)

EPY

EPOXY

DECORATIVE RESIN PANEL

DESCRIPTION

DRP1

(1) 96" DIAMETER x 1/2" T CEILING DECORATIVE RESIN PANEL. SUSPEND PANEL

FROM FLOOR DECK ABOVE WITH (22) POINT SUPPORT CONNECTORS.

BOTTOM OF PANEL 11'-8"

DRP2

(3) 42" W x 24" H x 1/2" T WALL DECORATIVE RESIN PANEL. MOUNT EACH PANEL

WITH (4) POINT SUPPORT CONNECTORS. BOTTOM OF PANELS @ 4" AFF.

DECORATIVE RESIN PANEL

GENERAL NOTES

1.

2.

3.

4.

ALL DECORATIVE RESIN PANELS (DRP) ARE VARIA ECORESIN BY 3 FORM

OR APPROVED EQUAL.

DRP1 & DRP2 PATTERNS ARE GO-GO CASTAWAY CENTERED + SKYDIVE

B48 + POWDER D03 WITH SANDSTONE FINISH BOTH SIDES

MOUNT WALL PANELS WITH THREADED RODS WELDED OR BOLTED TO

METAL STUDS OR BACKING PLATES (SSD)

MOUNT CEILING PANEL WITH THREADED RODS WELDED OR BOLTED TO

STEEL DECK ABOVE (SSD)

P1

P2

P3

DRP1

DRP2

WALL FINISH LEGEND:

ACCENT PAINT (SEE SPECS.)

ACCENT PAINT (SEE SPECS.)

ACCENT PAINT (SEE SPECS.)

DECORATIVE RESIN PANEL

DECORATIVE RESIN PANEL

L I C

E N S E D A R C H I T E

C T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 11:02:18 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE105

ARCHITECTURAL FINISH PLANS

J.ROBERTS

612-501

D.DIMAT

50 151

PROJECT

NORTH

PROJECT

NORTH

1/8" = 1'-0"AE105

1 FIRST FLOOR FINISH PLAN

1/8" = 1'-0"AE105

2 SECOND FLOOR FINISH PLAN

.E

.C

F.E.C.

F.E.C.

F.E.C.F.E.C.

F.E.C.

F .E

.C

370 SF

CONFERENCE

2A02

214 SF

LOUNGE

2A03

262 SF

CONFERENCE

2A04

103 SF

OFFICE

2A05A

99 SF

MULTI

PURPOSE

2A05B

316 SF

IT OPEN

OFFICE

2A05

101 SF

I.T.

2A08

73 SF

ELECTRICAL

2AC1E

1078 SF

CORRIDOR

2AC1

240 SF

PROCEDURE

WAITING

2A01

120 SF

PROCEDURE

PREP

2A09

175 SF

GEN

PROCEDURE

2A10

174 SF

GEN

PROCEDURE

2A11

172 SF

DERM LAB

2A12

175 SF

GEN

PROCEDURE

2A13

293 SF

STAFF

2AC2D

80 SF

CLEAN

SUPPLY

2AC2E

370 SF

IT STORAGE

2A06

631 SF

CORRIDOR

2AC2

188 SF

MEN'S

TOILET

2AC1A

183 SF

WOMEN'S

TOILET

2AC1B

101 SF

SHAFT

81 SF

DIRTY

2AC2B

67 SF

PATIENT

TOILET

2AC2C

49 SF

HAC

2AC1D

7279808185

87 82

616471

58 5657

51 52

19 SF

TANK STO.

2AC2A

213 SF

STAIR 2

S2

126 SF

EXAM

ROOM

1A04

125 SF

EXAM

ROOM

1A05

122 SF

EXAM

ROOM

1A06

124 SF

EXAM

ROOM

1A07

124 SF

EXAM

ROOM

1A08

124 SF

EXAM

ROOM

1A09

124 SF

EXAM

ROOM

1A10

123 SF

EXAM

ROOM

1A11

847 SF

CORRIDOR

1AC2

354 SF

STAFF

1AC2B

36 SF

H.A.C.

1AC2A

210 SF

RECEPTION

1A03

179 SF

HALL

1AC1

59 SF

PUBLIC

TOILET

1AC1B

58 SF

PUBLIC

TOILET

1AC1A

34 SF

ELEVATOR

CONTROL

1A01A

801 SF

WAITING

1A01

81 SF

ELEVATOR

E1

63 SF

STAFF

1A02C

56 SF

STAFF

1A02D

1193 SF

OPEN OFFICE

1A02

100 SF

I.T.

1A16

225 SF

ELECTRICAL

1A15

108 SF

MULTI

PURPOSE

1A02B

102 SF

OFFICE

1A02A

170 SF

LASER

1A12

710 SF

MECHANICAL

1A14

174 SF

PHOTO

1A13

75 SF

SHOWER

1A13A

63 SF

PATIENT

TOILET

1AC2C

25 2923

394041

424344

45 46

6 7 8

2 3

4 5

14 10 111617

GENERAL NOTES

1. SEE SIGNAGE SCHEDULE ON SHEET AE602

SYMBOL

SIGN NUMBER

LEGEND

DESCRIPTION

L I C

E N S E D A R C H I T E

C T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

"FULLY SPRINKLERED"

3/13/2018 11:02:19 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE106

ARCHITECTURAL SIGNAGE PLAN

J.ALFARO

612-501

D.DIMAT

51 151

1/8" = 1'-0"AE106

2 SECOND FLOOR SIGNAGE PLAN

1/8" = 1'-0"AE106

1 FIRST FLOOR SIGNAGE PLAN PROJECT

NORTH

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

MECHANICAL EQUIPMENT

SCREENS

EIFS - 2

CURTAIN WALL

GLAZING - TYP

T.O. HIGH

PARAPET

40' - 0"

(95.00')

(111.00')

(127.00')

(131.00')

(135.00')

ABCD C4D1 A.3A.7B.3

EIFS - 1

ALUM

COMP

PANELS

EIFS - 2

FUTURE CORRIDOR

CONNECTION (TYPE OF 3)

FUTURE LOBBY

CONNECTION

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

EIFS - 2

BAND OF

SPLIT FACE

CMU, TYP

MECHANICAL

EQUIPMENT

SCREENS

ALUM COMPOSITE

PANELS

ALUM. FRAMED

WINDOWS - TYP

T.O. HIGH

PARAPET

40' - 0"

(95.00')

(111.00')

(127.00')

(131.00')

(135.00')

CURVED STANDING

SEAM METAL ROOF

A B C DC4 D1A.3 A.7 B.3

AE201

SMOOTH FACE

CMU, TYP

ALUMINUM ENTRY

CANOPY

T.O.W.

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

EIFS - 2

MECHANICAL EQUIPMENT

SCREENS

EIFS - 2

CURVED STANDING

SEAM METAL ROOF

EIFS - 2

ALUM. FRAMED

ENTRANCE

ALUM FRAMED

STORE FRONT

GLAZING - TYP OF 3

ALUM. FRAMED

WINDOWS - TYP

T.O. HIGH

PARAPET

40' - 0"

(95.00')

(107.00')

(111.00')

(127.00')

(131.00')

(135.00')

CMU WALL

0.9 1 2 2.1 3 6 753.1

EIFS - 1

EIFS - 1

PREFAB STEEL STAIRS

AND LANDINGS

ALUM ENTRY

CANOPY

AE508

OH

T.O.W.

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

CMU WALL

ALUM COMPOSITE

PANELS

MECHANICAL

EQUIPMENT

SCREENS

EIFS - 2

T.O. HIGH

PARAPET

40' - 0"

(95.00')

(107.00')

(111.00')

(127.00')

(131.00')

(135.00')

ALUM. LOUVER

TYP. ALUM. FRAME WINDOWS - TYP

0.9122.1367 5 3.1

AE201

CLEAR ANODIZED ALUM COMPOSITE

PANELS AT FINS (TYP. OF 4)

STEEL GATE

CLEAR ANOD PANEL

AT OVERHANG TYP

ALUMINUM EXTERIOR

SUN SHADE

T.O.W.

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

B CA.3 A.7 B.3

ALUM

COMPOSITE

PANELS

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

T.O. HIGH

PARAPET

40' - 0"

D D1

VA SIGN

4' - 1"

COMPOSITE

ALUMINUM

PANELS

ALUMINUM COPING

EIFS

ALUMINUM

COPING

F O

S

T.O. ROOF RIDGE

32' - 0"

T.O. PARAPET

36' - 0"

T.O. HIGH

PARAPET

40' - 0"

CL

ALUMINUM

COMPOSITE

COPING

EIFS

HALO ILLUMINATED ALUM.

DIMENSIONAL LETTERS (SEE

SPECS)

3' - 0" 9"

2"

LINE 120-277 BAC 50/60 HZ

INPUT CURRENT 0.60A

OUTPUT VOLTS 12.0VDC

OUTPUT WATTS 60

OUTPUT CURRENT 5A

LED DRIVER

DISCONNECT SWITCH

BLK (LINE)

WHITE (NEUTRAL)

GRN (GROUNDING WIRE)TX

BONDING SCREW

METAL BACKING PLATE AND

THREADED CONNECTION WITH

WASHER AND NUT - TYP.

LAYOUT SIGN ANCHOR

LOCATIONS AND CORE DRILL

FINISH AND SUBSTRATES

FOR WATERTIGHT FIT - TYP.

F .O

.F

6". 2".

ELECTRICAL WIRE

18 GAUGE PLENUM

RATED WIRING

#18/2C CL3P/CMP

SHLD. OMNIPLEN

ALUMINUM FACE .125"

THREADED INSERT

FOR STUD MOUNT

SIGN TYPE EI-09.7

.1"

SIGN TYPE EN-06.02

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

3/13/2018 9:54:27 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE201

ARCHITECTURAL EXTERIOR

ELEVATIONS

J.ALFARO

612-501

D.DIMAT

52 151

1/8" = 1'-0"AE201

4 SOUTH ELEVATION

1/8" = 1'-0"AE201

2 NORTH ELEVATION

1/8" = 1'-0"AE201

3 EAST ELEVATION

1/8" = 1'-0"AE201

1 WEST ELEVATION

1/8" = 1'-0"AE201

5 NORTH ELEVATION @ MECH YARD

1/2" = 1'-0"AE201

6 T.O. FIN DETAIL

1/2" = 1'-0"AE201

7 VA SIGN DETAIL

SCALE: NTSAE201

8 VA SIGN DETAILS

SECOND FLOOR

16' - 0"

T.O. PARAPET

36' - 0"

(95.00')

T.O. SCREEN

41' - 0"

32'-0"

T.O.C. @ RIDGE

5 3 4

ABCD C4D1

VARIES

T.O.C.

VARIES

T.O.C.

CLEAR ANODIZED

ALUM COMP

PANELS AT FINS

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. SCREEN

41' - 0"

(95.00')

V.I.F. WITH

ELEVATOR MFR.

-5' - 0"

1 2

A B C DC4 D1

VARIES

T.O.C.

ALUMINUM

COMPOSITE PANEL

EIFS - 1

ALUMINUM FRAMED

WINDOW - TYPEIFS - 2

ALUM ENTRY

CANOPY

CLEAR ANODIZED ALUM

COMP PANELS AT FINS

EIFS 2

AE505

T.O.W.

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

16' - 0"

T.O. PARAPET

36' - 0"

T.O. SCREEN

41' - 0"

T.O. PARAPET_2

20' - 0"

(95.00')

0.912367 5 3.1

VARIES

T.O.C.

ALUMINUM

COMPOSITE

PANEL

SMOOTH

FACE CMU

GENERAL NOTES

1. BUILDING SECTIONS ARE DIAGRAMMATIC AND INTENDED TO SHOW

RELATIVE POSITION OF FLOORS, WALLS AND CEILINGS.

SHEET NOTES

1 HVAC UNITS

MECH. EQUIPMENT SCREEN

SHAFT

CEILING (TYP)

PARTITION (TYP)

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

3/13/2018 9:54:32 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE301

ARCHITECTURAL BUILDING

SECTIONS

J.ALFARO

612-501

D.DIMAT

53 151

1/8" = 1'-0"AE301

A BUILDING SECTION A

1/8" = 1'-0"AE301

B BUILDING SECTION B

1/8" = 1'-0"AE301

C BUILDING SECTION C

SHEET NOTES

1 ALUMINUM COMPOSITE COPING

ALUMINUM COMPOSITE PANEL CLADDING SYSTEM

ROOFING MEMBRANE PARAPET FLASHING OVER 5/8" TYPE 'X' GLASS MAT

FACED GWB SHEATHING

SINGLE PLY ROOFING MEMBRANE OVER ROOF DECK INSULATION

COMPOSITE STEEL DECK AND STEEL BEAM - SSD

LINEAR METAL CEILING

ALUMINUM SUN SHADE. SEE DETAIL 3/AE501

GLAZING. SEE SCHEDULE

FLOORING PER FINISH SCHEDULE

5/8" TYPE 'X' GWB. TYP.

AIR BARRIER OVER 5/8" TYPE 'X' GLASS MAT FACED GWB SHEATHING

6" METAL STUDS

BATT INSULATION BETWEEN STUDS WITH VAPOR BARRIER ON INTERIOR

FACE

WEATHER BARRIER OVER 5/8" TYPE 'X' GLASS MAT FACED GWB

SHEATHING

8" METAL STUDS - SSD

EIFS

CEILING PER SCHEDULE

1-HR FIRE RATED SHAFT WALL

STEEL BEAM AND DECK - SSD

STEEL BEAM - SSD

NOT USED

NOT USED

ALUMINUM LOUVER

HORIZONTAL REVEAL, TYP

AE502

AE503

12 13

AE502

AE502

AE502

AE502

D D1

AE502

AE505

AE507

10 OH

OH

AE504

12 13

5 13

AE504

AE504

AE504

A

AE504

AE507

AE505

OH

C

AE505

D D1

AE505

AE507

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

3/13/2018 9:54:34 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE302

ARCHITECTURAL EXTERIOR WALL

SECTIONS

J.ALFARO

612-501

D.DIMAT

54 151

1/2" = 1'-0"AE302

1 SECTION @ ALUM. COMP. PANELS

1/2" = 1'-0"AE302

3 SECTION 3

1/2" = 1'-0"AE302

2 SECTION @ EIFS

1/2" = 1'-0"AE302

5 SECTION @ ALUM COMP PANELS

1/2" = 1'-0"AE302

4 SECTION @ HIGH PARAPET

SHEET NOTES

1 UNDERSIDE OF STRUCTURE

SLOTTED METAL TRACK W/ FASTENER(S) @ 24" O.C. (S.S.D.)

6" METAL STUDS - TOP OF STUDS 1/2" BELOW TOP OF TRACK (S.S.D.)

FIRE CAULK BOTH SIDES

6" THK BATT INSUL. BETWEEN STUDS

5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES - FIRE STOP ALL

PENETRATIONS. DO NOT ATTACH TO TOP TRACK

CEILING PER SCHEDULE

METAL TRACK W/ SHOT PIN @ 32" O.C. (S.S.D.)

FLOORING AND BASE PER SCHEDULE (BOTH SIDES WHERE APPLICABLE)

(2) LAYER 5/8" TYPE 'X'GYPSUM BOARD BOTH SIDES - FIRE STOP ALL

PENETRATIONS. DO NOT ATTACH TO TOP TRACK

5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES, SEAL ALL PENETRATIONS W/

ACOUSTICAL SEALANT. DO NOT ATTACH TO TOP TRACK

ACOUSTICAL JOINT SEALANT BOTH SIDES

5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES. CUT AND PATCH AROUND

PENETRATIONS AS REQUIRED - DO NOT ATTACH TO TOP TRACK

5/8" TYPE 'X' GYPSUM BOARD BOTH SIDES

2-1/2" SOUND ATTENUATION BLANKETS BETWEEN STUDS

PARTITION TYPE PER PLAN

2-1/2" (MIN.) METAL FURRING STUDS

2-1/2" BATT INSULATION BETWEEN STUDS

5/8" TYPE 'X' GYPSUM BOARD

HORIZONTAL STUD FRAMING BETWEEN CHASE PARTITIONS. CLIP TO EA.

STUD AND TRACK

4" METAL STUDS

5/8" CEMENT BOARD BEHIND WAINSCOT

WAINSCOT, BASE AND FLOORING PER SCHEDULE

ACOUSTICAL JOINT SEALANT

1" TYPE 'X' GYPSUM BOARD SHAFT WALL LINER

6" C-H TYPE METAL SHAFT STUD @ 24" O.C.

J & C TYPE METAL TRACKS - INSTALL AND FASTEN PER SHAFT WALL

SYSTEM MANUFACTURER INSTRUCTION

CONT. 'Z' METAL CLIP ATTACH TO WALL STUD

M

IN4

M

IN4

M

IN8

20 15

ROOM SHAFT

L I C

E N S E D A R C H I T EC

T

S T

A T

E O F C A L I F O

R N

I A

JO

RGE E . A L FARO

REN._______

C-22051

03/19

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 o n e e ig h t in c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h ts i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h o n e f o o t o n e i n c h o n e f o o t

VA FORM 08-6231

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Drawing Title: Project Title: Project Number:

Building Number:

Drawing Number:Location

Date Checked Drawn

Office of Construction and Facilities Management

Dwg. of02/12/2018

VA MEDICAL CENTER, MATHER, CA 95655

644K F DAVIS ENGINEERING, INC

530 LA GONDA WAY, SUITE E,

DANVILLE, CA 94526

WWW.KFDE.COM

(925) 743-8884

3/13/2018 9:54:35 AMH:\PROJECTS\VA MEDICAL CENTERS\MATHER - DERMATOLOGY - 10TH SUBMITTAL_vball314.rvt

NEW DERMATOLOGY

OUTPATIENT SERVICES

BUILDING

D.DIMAT

AE303

ARCHITECTURAL INTERIOR WALL

SECTIONS

J.ALFARO

612-501

D.DIMAT

55 151

1" = 1'-0"AE303

1 ONE HOUR FIRE RATED PARTITION

1" = 1'-0"AE303

2 TWO HOUR FIRE RATED PARTITION STC 45

1" = 1'-0"AE303

4 FULL HEIGHT PARTITION

1" = 1'-0"AE303

3 SOUND RATED PARTITION STC 40

1" = 1'-0"AE303

5 CEILING HEIGHT PARTITION

1" = 1'-0"AE303

6 WALL FURRING

1" = 1'-0"AE303

7 PLUMBING CHASE

1" = 1'-0"AE303

8 ONE HOUR FIRE RATED SHAFT WALL

(STC 40 WHERE SHOWN)

A1/2" DIA. HANGERS

ANCHORED TO STRUCTURE

ABOVE

LATERALLY BRACE

SUSPENDED CHANNEL

TO WALL OR

STRUCTURE ABOVE

SUSPENDED CEILING

PER FINISH SCHEDULE.

3/8" STUD BOLT

MTL TOILET PARTITION

PILASTER W/CORE

AS SPECIFIED

TOP OF TOILET

PARTITION. SEE

MFGR'S DETAIL

METAL CLIP

GRAB BARS AT ALL

PUBLIC & PATIENT TOILETS

WALL FRAMING

STEEL CHANNEL (SIZE

FOR SPAN AS REQ'D.)

FRONT TRANSFER STANDARD

CEILING MOUNTED

TOILET PARTITIONS

66" 42" 36"

. 9

6" 3' - 0" 1' - 6"

15/16"

M

IN

.1'-6" 15/16" 15/16"

2' - 10"2' - 10"

DETAIL A

ELEVATION

PLAN

PLAN

SECTION

LINE OF CLEAR KNEE SPACE

CLEAR TOE SPACE

ACCESSIBLE FAUCET

M

IN

ACCESSIBLE WALL MOUNTED LAVATORY

30"x48" CLEAR SPACE CENTERED

IN FRONT OF LAVATORY WHICH

ADJOINS OR OVERLAPS AN

ACCESSIBLE ROUTE

COVER OR INSULATE HOT WATER &

DRAIN PIPES UNDER LAVATORY.

THERE SHALL BE NO SHARP OF

ABRASIVE SURFACES UNDER

LAVATORIES

ACCESSIBLE WALL

MOUNTED LAVATORY

NOTE:

FAUCET CONTROLS SHALL

BE OPERABLE WITH ONE

HAND AND SHALL NOT

REQUIRE TIGHT GRASPING,

PINCHING OR TWISTING OF

THE WRIST.

L A

V A

T O

R Y

C

L E

A R

S P

A C

E

17" MIN.

8" MIN.

M A

X

"2

M

IN

6" MIN.

25" MAX.

19" MAX.

6" MAX.

5'-0"

M

IN

M A

X

1'-0"

K-4329KING

STO

N

C_TO

ILETS

VITREO

US CHINA

K-4329KING STO NC_TO ILETSVITREO US CHINA

16" MIN.

18" MAX.

9" MAX.

7" MIN.

LINE OF FLOOR CLEAR SPACE

36" GRAB BAR, SEE DETAIL ON THIS SHEET

36"

GRAB

BAR

42" GRAB BAR

42" GRAB BAR

ACCESSIBLE WATER CLOSET: CONTROLS SHALL BE

OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT

GRASPING, PINCHING OR TWISTING. CONTROLS FOR FLUSH

VALVES SHALL BE MOUNTED ON THE WIDE SIDE OF TOILET

AREAS, NO MORE THAN 44" ABOVE THE FLOOR. THE FORCE

TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN 5

POUND FORCE (lbf).

AUTOMATIC "SPRING TO LIFTED POSITION" SEATS ARE NOT

ALLOWED.

TOILET SEAT COVER DISPENSER MOUNTED WITH OPERABLE

PARTS WITHIN 40" FROM THE FINISHED FLOOR.

WALLS WITHIN WATER

CLOSET COMPARTMENTS

SHALL BE FINISHED WITH

NON-ABSORBENT MATERIALS

SIMILARLY TO FLOORS.

TOILET ROOM FLOOR TO HAVE A NON-SLIP NONABSORBENT

HARD SURFACE SUCH AS CERAMIC TILE OR OTHER

APPROVED MATERIAL WITH INTEGRAL COVED BASE.

TOILET TISSUE DISPENSER. DISPENSERS THAT CONTROL DELIVERY

OR THAT DO NOT PERMIT CONTINUOUS PAPER FLOW SHALL NOT BE USED.

36" GRAB BAR SECURELY

ATTACHED PARALLEL TO THE FLOOR.

A .F

.F

FRONT ELEVATION

FIXTURE

ACCESSIBLE WATER CLOSET

SIDE ELEVATION

PLAN

M

IN

M A

X

ALTERNATE LOCATION

FOR TOILET SEAT

COVER DISPENSER

FLUSH ACTIVATOR ON

WIDE SIDE OF FIXTURE

(WHERE APPLICABLE)

NOTE: SAME LAYOUT APPLIES TO ACCESSORIES INSTALLED ON WALL/CEILING MOUNTED TOILET PARTITIONS

S O

A P

D

IS

P E

N S

E R

R E

C E

S S

E D

P A

P E

R T

O W

E L D

IS

P

E N

S E

R

W A

S T

E R

E C

E P

T A

C L E

W A

S T

E R

E C

E P

T A

C L E

R E

C E

S S

E D

P A

P E

R T

O W

E L D

IS

P

E N

S E

R

H A

N D

H

A

IR

D R

Y E

R

M

IR

R O

R

T O

IL

E

T S

E A

T C

O V

E R

D

IS

P E

N S

E R

R E

C E

S S

E D

S A

N

IT

A R

Y N

A P

K

IN

T

A M

P O

N V

E N

D O

R

T O

IL

E

T P

A P

E R

D

IS

P E

N S

E R

T O

G R

A B

B A

R

M A

X

S T

A

IN

L E

S S

S T

E E

L S

U R

F A

C E

M O

U N

T E

D H

O R

IZ

O

N T

A L

B A

B Y

C H

A N

G

IN

G S

T A

T

IO

N

THE PURPOSE OF THIS DIAGRAM IS TO ENSURE THAT ANY

TOILET ACCESSORY IS MOUNTED AT AN ACCESSIBLE

HEIGHT. THE TOILET ACCESSORIES AND FIXTURES

SHOWN ARE SCHEMATIC ONLY AND DO NOT MATCH

ACTUAL ITEMS SPECIFIED.

CONTRACTOR SHALL PROVIDE AND/OR INSTALL

ACCESSIBLE TOILET ACCESSORIES AS SPECIFIED OR AS

PROVIDED AND DIRECTED BY THE COR, INCLUDING BUT

NOT LIMITED TO THE ITEMS BELOW (WHERE APPLICABLE)

1. MIRRORS SHALL BE MOUNTED WITH THE BOTTOM

EDGE OF REFLECTIVE SURFACE NO HIGHER THAN

40 INCHES FROM THE FLOOR.

2. TOWEL, SANITARY NAPKINS, DISPENSERS WASTE

RECEPTACLES. WHERE TOWEL, SANITARY

NAPKIN, WASTE RECEPTACLES, AND OTHER

SIMILAR DISPENSING AND DISPOSAL FIXTURES ARE

PROVIDED, AT LEAST ONE OF EACH TYPE SHALL BE

LOCATED WITH ALL OPERABLE PARTS,

INCLUDING COIN SLOTS, WITHIN 40 INCHES FROM

THE FINISHED FLOOR.

3. IN ALL OCCUPANCIES, ACCESSORIES SUCH AS

GRAB BARS, TOWEL BARS, PAPER DISPENSERS

AND SOAP DISHES, PROVIDED ON OR WITHIN

WALLS, SHALL BE INSTALLED AND SEALED TO

PROTECT STRUCTURAL ELEMENTS FROM

MOISTURE.

4. PROVIDE BACKING PLATES, FILLER MATERIALS,

SUPPORTS AND MISCELLANEOUS FASTENERS, AS

REQUIRED FOR EACH ACCESSORY - SEE

SPECIFICATIONS

5. ANY PROTRUDING OBJECTS SHALL STAY 12" CLEAR

ABOVE AND 1-1/2" CLEAR BELOW GRAB BARS

M

IN

5'-0" MIN.

4'-0"

2 1/2"

MAX.

15"

/2

M A

X

M A

X

2'-6"

SEAT WALL

CONTROL

WALL

BACK WALL

F O

L D

A B

L E

S E

A T

GRAB BAR

CLEAR SPACE

NOTE:

VA SHOWER COMPARTMENT SIZE DIFFERS

FROM ABAAS. PROVIDE CUSTOM SIZE FOLDABLE

SEAT WITH ADEQUATE BLOCKING IN WALL TO SUPPORT

MIN. LIVE LOAD OF 500 LBS.

11/2"

DIAMETER OR WIDTH: THE DIAMETER OR WIDTH OF THE GRIPPING SURFACES OF A

GRAB BAR SHALL BE 1 1/4 INCHES TO 1 1/2 INCHES OR THE SHAPE SHALL

PROVIDE AN EQUIVALENT GRIPPING SURFACE. IF GRAB BARS ARE MOUNTED ADJACENT

TO A WALL, THE SPACE BETWEEN THE WALL AND THE GRAB BARS SHALL BE 1 1/2

INCHES.

STRUCTURAL STRENGTH: THE STRUCTURAL STRENGTH OF GRAB BARS, TUB AND

SHOWER SEATS,…