Grand Prairie- Inspections_.pdf

PDF 338 KB Posted

Attached to
J063--NTX Fire Alarm/Sprinkler Systems PM Services
Solicitation number
36C25725Q0116
Issued by

About this file

This is a fire alarm and sprinkler system inspection report conducted by Firetrol Protection Systems for the VA Grand Prairie facility in November 2024. The inspection was performed according to NFPA 72 2010 Edition and NFPA 25 2011 Edition standards.

The report details comprehensive testing of the facility's Notifier NFS2 3030 fire alarm control panel and associated components, including manual pull stations, smoke detectors, heat detectors, duct detectors, and notification devices. The inspection verified 2 manual pull stations, 7 smoke detectors, 6 heat detectors, 2 duct detectors, 6 strobes, 2 speakers, and 14 speaker/strobes - all of which passed testing. The sprinkler system inspection confirmed proper operation of 2 butterfly control valves, waterflow switches, and fire department connections. The main drain test showed static pressure of 70 PSI and residual pressure of 50 PSI. Central station monitoring response time was verified at 16 seconds through SW Dispatch. All systems were tagged BLUE indicating satisfactory condition, with inspection performed by Christopher West (License #FAL-6339).

View the file

Other files

File Type Posted
Dallas VAMC-Other Inspections_.pdf PDF
Dallas-Sprinkler Systems_.pdf PDF
Garland-Inspections_.pdf PDF
SF30 36C25725Q0116 0003.docx DOCX document
36C25725Q0116 0003_1.docx DOCX document
Bonham-Inspections_.pdf PDF
SF30 36C25725Q0116 0002.docx DOCX document
36C25725Q0116 0002_1.docx DOCX document
Technical Questions_36C25725Q0116.docx DOCX document
Updated Price Schedule - 36C25725Q0116.docx DOCX document
36C25725Q0116 0001_1.docx DOCX document
SF30 36C25725Q0116 0001.docx DOCX document
Att 1_NARA Records Management Language for Contracts.docx DOCX document
S02 RFQ 36C25725Q0116.docx DOCX document
36C25725Q0116_2.docx DOCX document
Service Contract Act WD 2015-5273_Fannin.pdf PDF
Service Contract Act WD 2015-5227_Dallas.pdf PDF
Att 3_Site Plan Grand Prairie_Redacted.pdf PDF
Att 2_NTX VA Health Care Systems Construction Safety Accident Prevention Plan.doc DOC document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10320 Markison Rd Dallas, Tx. 75238

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net

Frequency: Annual Month of inspection: Year: 2024

Contact:

Street: E-Mail:

City, State, Zip: Phone:

1. Before Test Notify Proper Authorities A. Owner Representative B. Central Station Monitoring C. Other

2. Control Panel Status Before Test Manufacture: NOTIFIER Model Number: Yes N/A No

A. Have the Monitoring Station and/or Fire Department been notified of test? X B. Is the Power Light On? X C. Does the Panel Indicate Normal Conditions? X D. Does the Supervisory / Trouble Switch Operate? X E. Does the Silence / Acknowledge Switch Operate? X F. Are all Indicating Display's, LED's or Lamps in Operating Order? X G. Is the Printer On-line and Operating Properly? X H. Does the Panel Have Battery Backup? (See J) X I. Is the Charging Circuit Operating Properly? X J. Did Central Station Monitoring receive signals? EP 5 Signal Received in: 16 Seconds X K. Have proper authorities (See #1) been notified system is back in service? X L. Is system reset for normal conditions? X M. Is system restored to operational service? X

3. Suppression Systems Yes No

A. Are Sprinkler Systems Installed on Property? X B. Are Hood Suppression Systems Installed on Property? X C. Are Special Hazard Systems Installed on Property? X D. Are there other types of Fire Protection Equipment Installed on Property? X

Specify:

Test Verification:

Name (Print): Date:

Signature:

Inspector:

Name (Print): Lic #:

Signature: Start Date:

Completion Date:

VA GRAND PRAIRIE

FIRE ALARM DETECTION AND SPRINKLER EQUIPMENT

DEVICE LISTING AND TESTED PER NFPA 72 2010 EDITION and NFPA 25 2011 EDITION

MELANIE KING

SW DISPATCH

November

MELANIE KING

2737 SHERMAN ST

GRAND PRAIRIE TX 75051

melanies.king@va.gov

Comments:

FACP Location: Plant Ops Manager Office Install Date: JANUARY 20 2024

NFS2 3030

Name PHONE

972-437-6773

Melanie King

CHRISTOPHER WEST

11/12/2024

11/12/2024

CHRISTOPHER WEST FAL-6339

11/12/2024

Panel Tagged:

BLUE

Fire Alarm Detection and Sprinkler Equipment http://www.firetrol.net/ mailto:melanies.king@va.gov mailto:melanies.king@va.gov mailto:melanies.king@va.gov mailto:melanies.king@va.gov

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net

Frequency: Annual Month of inspection: November Year: 2024

Pass N/A Fail EP1 Supervisory Signals

A. Pressure Tank 0 0 0 X 0 B. Sprinkler Pressure 0 0 0 X 0 C. Water Level 0 0 0 X 0 D. Water Temperature 0 0 0 X 0 E. Room Temperature 0 0 0 X 0 F. Pump - Phase Reversal 0 0 0 X 0 G. Pump Run 0 0 0 X 0 H. Pump - Power Loss 0 0 0 X 0

EP2 Tamper Switches / Ctrl Valves 2 2 2 0 Water Flow Switches

A. Vane Type 1 1 1 0 B. Pressure 0 0 0 X 0

EP3 Initiating Devices A. Manual Pull Stations 2 2 2 0 B. Smoke Detectors 7 7 7 0 C. Heat Detectors 6 6 6 0 D. Combo Detectors 0 0 0 X 0 E. Flame Detectors 0 0 0 X 0 F. Duct Detectors 2 2 2 0 G. Linear Detection 0 0 0 X 0 H. Control Devices 0 0 0 X 0 I. Smoke Dampers 0 0 0 X 0

EP4 Notification Devices A. Horn Strobe 0 0 0 X 0 B. Strobe 6 6 6 0 C. Chime 0 0 0 X 0 D. Speaker 2 2 2 0 E. Speaker/ Strobe 14 14 14 0 F. Horn 0 0 0 X 0 G. Bell 0 0 0 X 0 H. Water Motor Gong 0 0 0 X 0 I. Doors 0 0 0 X 0

EP19 Ventilation Devices 0 0 0 X 0 EP20 Rolling and Sliding Doors

A. Rolling Doors 0 0 0 X 0 B. Sliding Doors 0 0 0 X 0

Devices not Referenced Under EP's Remote Annunciator 0 0 0 X 0 Batteries 0 0 0 X 0 Firefighter Phones 0 0 0 X 0 Elevators X

A. Primary Recall X B. Alternate Floor Recall X

VA GRAND PRAIRIE

FIRE ALARM DETECTION AND SPRINKLER EQUIPMENT

PER NFPA 72 2010 EDITION and NFPA 25 2011 EDITION

OperationalTotal Number of Devices

Number Tested in Previous Report

Number Tested This Report

Fire Alarm Detection and Sprinkler Equipment Device Count http://www.firetrol.net/

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West License # RME-l-932229

Valve Type/Size Floor Location Valve Secured? Test Results

PASS/FAIL Comments & Notes

1 L1M006 BFLY 1ST AT RISER MECH RM 1020 SUPERVISED PASS

2 L1M050 BFLY 1ST AT RISER MECH RM 1020 SUPERVISED PASS

VA GRAND PRAIRIE

TAMPER SWITCHES/CONTROL VALVE LIST

JOINT COMMISSION EC.02.03.05 STANDARD EP2; NFPA 72 2010 EDITION (table 14.4.5, item 15(L) and (M)) & NFPA 25 2011 EDITION (5.1.1.2)

Address or Zone

EP2

Tamper

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West License # RME-l-932229

Device Type Floor Location Time To Alarm

Notification (Seconds)

Test Results PASS/FAIL Comments & Notes

1 L1M005 VANE TYPE 1ST AT RISER MECH RM 1020 69 SEC PASS

VA GRAND PRAIRIE

WATERFLOW SWITCHES

JOINT COMMISSION EC.02.03.05 STANDARD EP2; NFPA 72 2010 EDITION (table 14.4.5, item 15(L) and (M)) & NFPA 25 2011 EDITION (5.1.1.2)

Address or Zone

EP2

Waterflow

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes

1 L1M001 PULL ALARM 1ST N.E. EXIT VESTIBULE PASS

2 L1M008 PULL ALARM 1ST MECH RM 1020 EXIT PASS

VA GRAND PRAIRIE

MANUAL PULL STATIONS

JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)

Address or Zone

EP3

Manual Pulls

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes

1 L1D001 SMOKE ALARM 1ST MECH RM 1020 ABOVE FACP PASS

2 L1D003 SMOKE ALARM 1ST ELECT RM 1020A PASS

3 L1D004 SMOKE ALARM 1ST N.E. ENTRY VESTIBULE PASS

4 L1D005 SMOKE ALARM 1ST IT RM 1018 PASS

5 L1D006 SMOKE ALARM 1ST DEMARC RM 1029 PASS

6 L1D009 SMOKE ALARM 1ST HAC RM 1022 PASS

7 L1D10 SMOKE ALARM 1ST ELECT RM 1021 PASS

VA GRAND PRAIRIE

SMOKE DETECTORS

JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)

Address or Zone

EP3

Smoke Detectors

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes

1 L1D002 HEAT ALARM 1ST MECH RM ABOVE FACP PASS

2 L1D155 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS

3 L1D156 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS

4 L1D157 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS

5 L1D158 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS

6 L1D159 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS

VA GRAND PRAIRIE

HEAT DETECTORS

JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)

Address or Zone

EP3

Heat Detectors

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes

1 L1D007 DUCT SUPERVISORY 1ST RTU #1 SUPPLY PASS

2 L1D008 DUCT SUPERVISORY 1ST RTU #1 RETURN PASS

VA GRAND PRAIRIE

DUCT DETECTORS

JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)

Address or Zone

EP3

Duct Detectors

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Floor Location Test Results PASS/FAIL Comments & Notes

1 SPK/STR 1ST O/S RM 1314 PASS

2 SPEAKER 1ST O/S RM 1306 PASS

3 SPEAKER 1ST O/S RM 1020 PASS

4 SPK/STR 1ST MECH RM 1020 PASS

5 STROBE 1ST MECH RM 1020 PASS

6 STROBE 1ST ENTRY VESTIBULE PASS

7 SPK/STR 1ST HALLWAY 1015 PASS

8 SPK/STR 1ST CHECK-IN/ WAITING 1019 PASS

9 SPK/STR 1ST RM 1019 PASS

10 SPK/STR 1ST RM 1019B PASS

11 SPK/STR 1ST O/S RM 1404 PASS

12 STROBE 1ST RESTROOM 1408 PASS

13 STROBE 1ST RESTROOM 1309 PASS

14 SPK/STR 1ST O/S RM 1315 PASS

15 SPK/STR 1ST O/S RM 1028 PASS

16 STROBE 1ST RM 1028 PASS

17 SPK/STR 1ST RM 1027 PASS

18 SPK/STR 1ST RM 1300 O/S RM 1317 PASS

19 STROBE 1ST RM 1300 O/S RM 1313 PASS

20 SPK/STR 1ST RM 1300 O/S RM 1307 PASS

21 SPK/STR 1ST O/S RM 1207 PASS

22 SPK/STR 1ST O/S RM 1203 PASS

VA GRAND PRAIRIE

ALARM NOTIFICATION DEVICES

JOINT COMMISSION EC.02.03.05 STANDARD EP4; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.2.2, item 15(a), (b), and (c))

Address or Zone

EP4

AV's

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339

Device Type Time (sec) Floor Location Test Results PASS/FAIL Comments & Notes

1 CELL 16 1ST AT FACP PASS

VA GRAND PRAIRIE

EMERGENCY SERVICES NOTIFICATION

JOINT COMMISSION EC.02.03.05 STANDARD EP5; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5)

Central Station

SW DISPATCH

EP5

Monitoring

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net

General

1. (To be filled out by the Owner or Owner's Representative) a.

b.

c.

d. Has the piping in all dry systems been checked for proper pitch within the past five years?

e. Has the piping in all systems been checked for obstructive materials?

f.

If tested through flow meter, when was pump last testing flow water?

g.

h.

Quick Response (20 Years) Dry (10 years) Greater than 325˚F/163˚C (5yr) Corrosive env't. (5yr.)

i. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300 F?

j. Have Alarm/Check valves and associated trim been internally inspected in the past 5 years?

k. Have gauges been compared to a calibrated gauge, or replaced in the last 5 years?

l. Standpipe 5 year Requirements:

1. Dry standpipe hydrostatic test

2. Flow test

3. Hose hydrostatic test

4. Pressure control valve test

5. Pressure reducing valve test

m. Have pressure reducing valves been tested at full flow within the past 5 years?

n. Have master pressure reducing valves been tested at full flow within the past year?

2. (To be answered by the inspector)

a. Have the sprinkler systems been extended to all visible areas of the building?

b. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector?

c. Do sprinklers heads generally appear to be in good external condition?

d. Do sprinklers heads generally appear to be free of corrosion, paint, or loading and visible obstruction?

e. Are extra sprinklers heads available on the premises in a head box at the riser?

f. Does the exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainer appear to be satisfactory?

List Changes in the Occupancy Hazard or Fire Protection Equipment, as Advised by the Owner in Section 1A:

Control Valves a.

b. Are all control valves sealed or supervised in the open position?

c. Have all control valves been fully exercised?

d. Any control valves leaking or the presence of other abnormal conditions or any physical damage?

Water Supplies

a. Water Supply Source? City Pressure Fire Pump: Tank X City Pond

X

X X

X

X

Have fire pumps been tested to full capacity through use of hose streams or flow meters in the past 12 months?

Are gravity, surface, or pressure tanks protected from freezing? X Date: X

X

No

Have there been any changes in the occupancy, machinery, or operations since the last inspection? X

X XDate:

Date:

Have there been any changes or repairs to the fire protection systems since the last inspection? X If a fire has occurred since the last inspection, have all damaged sprinkler system components been replaced? X

Date:

Date:

X

Yes N/A

Are any of the sprinklers 50 years old or older? (Testing and/or replacement is recommended for such sprinklers)

Date:

Date:

Date:

X

X

X X X X

X

Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?

X

X X

Date:

Date:

Date:

Date:

X X X

X X

Contact:

Phone:

SPRINKLER SYSTEM INSPECTION REPORT

PER NFPA 25 2011 EDITION

2737 SHERMAN ST

GRAND PRAIRIE TX 75051

Property Name:

Street:

City, State & Zip: Inspector: CHRISTOPHER WEST

VA GRAND PRAIRIE MELANIE KING

Type of inspection: Annual Month of inspection: November Year:

GRAND PRAIRIE Gravity Tank

Sprinkler System Inspection Report

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net

SPRINKLER SYSTEM INSPECTION REPORT

PER NFPA 25 2011 EDITION

2024Type of inspection: Annual Month of inspection: November Year:

Tanks, Pumps, Fire Dept. Connections a.

b.

c. Has the storage tank been internally inspected in the last 3 yrs. (unlined) or 5 yrs. (lined)?

d.

e.

Wet systems

a. No. of Systems

b. Are cold weather valves in the appropriate open or closed position?

If closed, has piping been drained?

c. Has the owner or owner's representative been advised that cold weather valves are not recommended by NFPA?

d. Have all the antifreeze systems been tested?

e. Date antifreeze systems were tested

f. The antifreeze tests indicate protection to: 1. 2. 3. 4. 5.

g. Did alarm valves, water flow alarm indicators and retards test satisfactorily?

Dry systems a.

1.) Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

2.) Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

4.) Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

5.) Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

6.) Air pressure before trip: Air pressure at trip:

Water psi before trip: Water psi at trip:

b.

c.

d.

e.

f.

g.

h. Is the dry valve house heated?

Special Systems

a. No. of Systems b.

c.

d.

Auxiliary Equipment: No. Type:

Location:

Test Results:

Alarms

a. Did the water motors and gong operate during testing?

b. Did the electric alarms operate during testing?

c. Did the supervisory alarms operate during testing?

Date:

Yes N/A No Do fire pumps, gravity, surface or pressure tanks appear to be in good external condition? X Are gravity, surface and pressure tanks at the proper pressure and/or water levels?

Date trip tested:

sec. Time to trip: sec.

psi

Time to ITD:

psi psi

Time to ITD: Time to trip:

psi

Date trip tested:

psi

Do dry valves appear to be protected from freezing?

psi psi psi psi

X

Date trip tested:

3.)

Time to ITD: Time to trip:

psi sec.

X

X psi psi psi

Is the air pressure and priming water levels normal? X Did the air compressor operate satisfactorily? X

Time to ITD: sec. Time to trip:

X

X psi

X

X

X psi

X X

Are fire dept. connections in satisfactory condition, couplings free, caps or plugs in place and check valves tight?

Yes N/A No 1 Make & Model FIRELOCK S751

XAre fire dept. connections visible and accessible?

X

Temperature Date:

System

X Did all quick opening devices operate satisfactorily? X psi

Time to ITD: sec. Time to trip: sec.

psi psi

Date trip tested:

psi

No. of Systems Make & Model psi psi psi sec.

Time to trip:

Date trip tested:

sec.

psi psi

Did all the dry valves operate satisfactorily during this inspection?

sec.

Date trip tested:

Time to ITD: sec.

sec.

sec.

Were all low points drained during this inspection?

Did all devices operate satisfactorily? X Did the supervisory features operate during testing? X

X Were valves tested as required? X

Make & Model Type

No X

Device type: Type of Test:

Yes N/A

X X

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net

SPRINKLER SYSTEM INSPECTION REPORT

PER NFPA 25 2011 EDITION

2024Type of inspection: Annual Month of inspection: November Year:

Inspection and Suggested Improvements were Discussed with the Undersigned Owner or Owner's Representative:

Test Verification Name Print Signature

Title Date

Test Date Inspector

Signature:

Christopher West

CHRISTOPHER WEST; Lic.# RME-I-1932229 System Tagged: BLUE

MELANIE KING

11/12/24 to 11/12/2411/12/24

*Sprinkler system was just installed this year.Inspector Notes:

Adjustments or Corrections Made:

10320 Markison Rd.

Dallas, TX 75238 Phone: 214-343-9200 Fax: 214-343-9265 www.firetrol.net

Annual November Year 2024

Contact: MELANIE KING Phone: 0

Inspector: CHRISTOPHER WEST

Test Pipe Size

Static Pressure

Before

Flow Pressure

Return Time to Static Pressure

Flow Alarm Time Comments

6" 70 50 60 69 SEC

SPRINKLER SYSTEM FLOW READINGS

PER NFPA 25 2011 EDITION

Test Pipe Location

MECH RM 1020

2737 SHERMAN ST

GRAND PRAIRIE TX 75051

Propert Name:

Street:

City, State & Zip:

VA GRAND PRAIRIE

Type of inspection Month of inspection

Flow Readings

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West

RME-l-932229

Size Static Pressure Residual Pressure Return Time (Sec.)

to Static PSI

Results of Test

PASS / FAIL

1 6" 70 50 PASS

MECH RM 1020 AT RISER

License #

VA GRAND PRAIRIE

MAIN DRAIN TEST

JOINT COMMISSION EC.02.03.05 STANDARD EP9; DEVICE LISTING AND TESTED PER NFPA 25 2011 Edition (13.2.5; 13.3.3.4; table 13.1.1.2 & 13.8.1)

Main Drain Location

EP9

Main Drain Test

Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency:

Inspection Date:

Completion Date:

Inspector:

License #

LOCATION TYPE VISIBLE &

ACCESSIBLE

COUPLINGS

or SWIVELS

ARE NOT

DAMAGED

AND ROTATE

SMOOTHLY

PLUGS or

CAPS ARE IN

PLACE AND

UNDAMAGED

GASKETS

ARE IN PLACE

AND IN GOOD

CONDITION

IDENTIFICATION

SIGNS ARE IN

PLACE

THE CHECK

VALVE IS NOT

LEAKING

THE

AUTOMATIC

DRAIN VALVE

IS IN PLACE

AND

OPERATING

PROPERLY

IS THE FDC

CLAPPER IN

PLACE &

OPERATING

PROPERLY

RESULTS OF

TESTING

PASS / FAIL

1 OUTSIDE OF BLDG AT RISER

RM SIAMESE YES YES YES YES YES YES N/A YES PASS

VA GRAND PRAIRIE

FIRE DEPARTMENT CONNECTIONS

JOINT COMMISSION EC.02.03.05 STANDARD EP10; NFPA 25 2011 (13.7; 13.1.1.2)

Annual 11/12/2024 11/12/2024 Christopher West RME-l-932229

EP10

Fire Department Connections http://www.firetrol.net/

FA1
FA2
Tamp
Flow
Pull
Smoke
Heat
Duct
AVs
Monitoring
Sprinkler
Sprinkler Flow
Main Drain
FDC