Grand Prairie- Inspections_.pdf
PDF 338 KB Posted
- Solicitation number
- 36C25725Q0116
About this file
This is a fire alarm and sprinkler system inspection report conducted by Firetrol Protection Systems for the VA Grand Prairie facility in November 2024. The inspection was performed according to NFPA 72 2010 Edition and NFPA 25 2011 Edition standards.
The report details comprehensive testing of the facility's Notifier NFS2 3030 fire alarm control panel and associated components, including manual pull stations, smoke detectors, heat detectors, duct detectors, and notification devices. The inspection verified 2 manual pull stations, 7 smoke detectors, 6 heat detectors, 2 duct detectors, 6 strobes, 2 speakers, and 14 speaker/strobes - all of which passed testing. The sprinkler system inspection confirmed proper operation of 2 butterfly control valves, waterflow switches, and fire department connections. The main drain test showed static pressure of 70 PSI and residual pressure of 50 PSI. Central station monitoring response time was verified at 16 seconds through SW Dispatch. All systems were tagged BLUE indicating satisfactory condition, with inspection performed by Christopher West (License #FAL-6339).
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Dallas VAMC-Other Inspections_.pdf | ||
| Dallas-Sprinkler Systems_.pdf | ||
| Garland-Inspections_.pdf | ||
| SF30 36C25725Q0116 0003.docx | DOCX document | |
| 36C25725Q0116 0003_1.docx | DOCX document | |
| Bonham-Inspections_.pdf | ||
| SF30 36C25725Q0116 0002.docx | DOCX document | |
| 36C25725Q0116 0002_1.docx | DOCX document | |
| Technical Questions_36C25725Q0116.docx | DOCX document | |
| Updated Price Schedule - 36C25725Q0116.docx | DOCX document | |
| 36C25725Q0116 0001_1.docx | DOCX document | |
| SF30 36C25725Q0116 0001.docx | DOCX document | |
| Att 1_NARA Records Management Language for Contracts.docx | DOCX document | |
| S02 RFQ 36C25725Q0116.docx | DOCX document | |
| 36C25725Q0116_2.docx | DOCX document | |
| Service Contract Act WD 2015-5273_Fannin.pdf | ||
| Service Contract Act WD 2015-5227_Dallas.pdf | ||
| Att 3_Site Plan Grand Prairie_Redacted.pdf | ||
| Att 2_NTX VA Health Care Systems Construction Safety Accident Prevention Plan.doc | DOC document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10320 Markison Rd Dallas, Tx. 75238
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net
Frequency: Annual Month of inspection: Year: 2024
Contact:
Street: E-Mail:
City, State, Zip: Phone:
1. Before Test Notify Proper Authorities A. Owner Representative B. Central Station Monitoring C. Other
2. Control Panel Status Before Test Manufacture: NOTIFIER Model Number: Yes N/A No
A. Have the Monitoring Station and/or Fire Department been notified of test? X B. Is the Power Light On? X C. Does the Panel Indicate Normal Conditions? X D. Does the Supervisory / Trouble Switch Operate? X E. Does the Silence / Acknowledge Switch Operate? X F. Are all Indicating Display's, LED's or Lamps in Operating Order? X G. Is the Printer On-line and Operating Properly? X H. Does the Panel Have Battery Backup? (See J) X I. Is the Charging Circuit Operating Properly? X J. Did Central Station Monitoring receive signals? EP 5 Signal Received in: 16 Seconds X K. Have proper authorities (See #1) been notified system is back in service? X L. Is system reset for normal conditions? X M. Is system restored to operational service? X
3. Suppression Systems Yes No
A. Are Sprinkler Systems Installed on Property? X B. Are Hood Suppression Systems Installed on Property? X C. Are Special Hazard Systems Installed on Property? X D. Are there other types of Fire Protection Equipment Installed on Property? X
Specify:
Test Verification:
Name (Print): Date:
Signature:
Inspector:
Name (Print): Lic #:
Signature: Start Date:
Completion Date:
VA GRAND PRAIRIE
FIRE ALARM DETECTION AND SPRINKLER EQUIPMENT
DEVICE LISTING AND TESTED PER NFPA 72 2010 EDITION and NFPA 25 2011 EDITION
MELANIE KING
SW DISPATCH
November
MELANIE KING
2737 SHERMAN ST
GRAND PRAIRIE TX 75051
melanies.king@va.gov
Comments:
FACP Location: Plant Ops Manager Office Install Date: JANUARY 20 2024
NFS2 3030
Name PHONE
972-437-6773
Melanie King
CHRISTOPHER WEST
11/12/2024
11/12/2024
CHRISTOPHER WEST FAL-6339
11/12/2024
Panel Tagged:
BLUE
Fire Alarm Detection and Sprinkler Equipment http://www.firetrol.net/ mailto:melanies.king@va.gov mailto:melanies.king@va.gov mailto:melanies.king@va.gov mailto:melanies.king@va.gov
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net
Frequency: Annual Month of inspection: November Year: 2024
Pass N/A Fail EP1 Supervisory Signals
A. Pressure Tank 0 0 0 X 0 B. Sprinkler Pressure 0 0 0 X 0 C. Water Level 0 0 0 X 0 D. Water Temperature 0 0 0 X 0 E. Room Temperature 0 0 0 X 0 F. Pump - Phase Reversal 0 0 0 X 0 G. Pump Run 0 0 0 X 0 H. Pump - Power Loss 0 0 0 X 0
EP2 Tamper Switches / Ctrl Valves 2 2 2 0 Water Flow Switches
A. Vane Type 1 1 1 0 B. Pressure 0 0 0 X 0
EP3 Initiating Devices A. Manual Pull Stations 2 2 2 0 B. Smoke Detectors 7 7 7 0 C. Heat Detectors 6 6 6 0 D. Combo Detectors 0 0 0 X 0 E. Flame Detectors 0 0 0 X 0 F. Duct Detectors 2 2 2 0 G. Linear Detection 0 0 0 X 0 H. Control Devices 0 0 0 X 0 I. Smoke Dampers 0 0 0 X 0
EP4 Notification Devices A. Horn Strobe 0 0 0 X 0 B. Strobe 6 6 6 0 C. Chime 0 0 0 X 0 D. Speaker 2 2 2 0 E. Speaker/ Strobe 14 14 14 0 F. Horn 0 0 0 X 0 G. Bell 0 0 0 X 0 H. Water Motor Gong 0 0 0 X 0 I. Doors 0 0 0 X 0
EP19 Ventilation Devices 0 0 0 X 0 EP20 Rolling and Sliding Doors
A. Rolling Doors 0 0 0 X 0 B. Sliding Doors 0 0 0 X 0
Devices not Referenced Under EP's Remote Annunciator 0 0 0 X 0 Batteries 0 0 0 X 0 Firefighter Phones 0 0 0 X 0 Elevators X
A. Primary Recall X B. Alternate Floor Recall X
VA GRAND PRAIRIE
FIRE ALARM DETECTION AND SPRINKLER EQUIPMENT
PER NFPA 72 2010 EDITION and NFPA 25 2011 EDITION
OperationalTotal Number of Devices
Number Tested in Previous Report
Number Tested This Report
Fire Alarm Detection and Sprinkler Equipment Device Count http://www.firetrol.net/
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West License # RME-l-932229
Valve Type/Size Floor Location Valve Secured? Test Results
PASS/FAIL Comments & Notes
1 L1M006 BFLY 1ST AT RISER MECH RM 1020 SUPERVISED PASS
2 L1M050 BFLY 1ST AT RISER MECH RM 1020 SUPERVISED PASS
VA GRAND PRAIRIE
TAMPER SWITCHES/CONTROL VALVE LIST
JOINT COMMISSION EC.02.03.05 STANDARD EP2; NFPA 72 2010 EDITION (table 14.4.5, item 15(L) and (M)) & NFPA 25 2011 EDITION (5.1.1.2)
Address or Zone
EP2
Tamper
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West License # RME-l-932229
Device Type Floor Location Time To Alarm
Notification (Seconds)
Test Results PASS/FAIL Comments & Notes
1 L1M005 VANE TYPE 1ST AT RISER MECH RM 1020 69 SEC PASS
VA GRAND PRAIRIE
WATERFLOW SWITCHES
JOINT COMMISSION EC.02.03.05 STANDARD EP2; NFPA 72 2010 EDITION (table 14.4.5, item 15(L) and (M)) & NFPA 25 2011 EDITION (5.1.1.2)
Address or Zone
EP2
Waterflow
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes
1 L1M001 PULL ALARM 1ST N.E. EXIT VESTIBULE PASS
2 L1M008 PULL ALARM 1ST MECH RM 1020 EXIT PASS
VA GRAND PRAIRIE
MANUAL PULL STATIONS
JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)
Address or Zone
EP3
Manual Pulls
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes
1 L1D001 SMOKE ALARM 1ST MECH RM 1020 ABOVE FACP PASS
2 L1D003 SMOKE ALARM 1ST ELECT RM 1020A PASS
3 L1D004 SMOKE ALARM 1ST N.E. ENTRY VESTIBULE PASS
4 L1D005 SMOKE ALARM 1ST IT RM 1018 PASS
5 L1D006 SMOKE ALARM 1ST DEMARC RM 1029 PASS
6 L1D009 SMOKE ALARM 1ST HAC RM 1022 PASS
7 L1D10 SMOKE ALARM 1ST ELECT RM 1021 PASS
VA GRAND PRAIRIE
SMOKE DETECTORS
JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)
Address or Zone
EP3
Smoke Detectors
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes
1 L1D002 HEAT ALARM 1ST MECH RM ABOVE FACP PASS
2 L1D155 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS
3 L1D156 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS
4 L1D157 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS
5 L1D158 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS
6 L1D159 HEAT ALARM 1ST PHASE 2 TEMPORARY PASS
VA GRAND PRAIRIE
HEAT DETECTORS
JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)
Address or Zone
EP3
Heat Detectors
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Signal Type Floor Location Test Results PASS/FAIL Comments & Notes
1 L1D007 DUCT SUPERVISORY 1ST RTU #1 SUPPLY PASS
2 L1D008 DUCT SUPERVISORY 1ST RTU #1 RETURN PASS
VA GRAND PRAIRIE
DUCT DETECTORS
JOINT COMMISSION EC.02.03.05 STANDARD EP3; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5; 17.14)
Address or Zone
EP3
Duct Detectors
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Floor Location Test Results PASS/FAIL Comments & Notes
1 SPK/STR 1ST O/S RM 1314 PASS
2 SPEAKER 1ST O/S RM 1306 PASS
3 SPEAKER 1ST O/S RM 1020 PASS
4 SPK/STR 1ST MECH RM 1020 PASS
5 STROBE 1ST MECH RM 1020 PASS
6 STROBE 1ST ENTRY VESTIBULE PASS
7 SPK/STR 1ST HALLWAY 1015 PASS
8 SPK/STR 1ST CHECK-IN/ WAITING 1019 PASS
9 SPK/STR 1ST RM 1019 PASS
10 SPK/STR 1ST RM 1019B PASS
11 SPK/STR 1ST O/S RM 1404 PASS
12 STROBE 1ST RESTROOM 1408 PASS
13 STROBE 1ST RESTROOM 1309 PASS
14 SPK/STR 1ST O/S RM 1315 PASS
15 SPK/STR 1ST O/S RM 1028 PASS
16 STROBE 1ST RM 1028 PASS
17 SPK/STR 1ST RM 1027 PASS
18 SPK/STR 1ST RM 1300 O/S RM 1317 PASS
19 STROBE 1ST RM 1300 O/S RM 1313 PASS
20 SPK/STR 1ST RM 1300 O/S RM 1307 PASS
21 SPK/STR 1ST O/S RM 1207 PASS
22 SPK/STR 1ST O/S RM 1203 PASS
VA GRAND PRAIRIE
ALARM NOTIFICATION DEVICES
JOINT COMMISSION EC.02.03.05 STANDARD EP4; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.2.2, item 15(a), (b), and (c))
Address or Zone
EP4
AV's
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: CHRISTOPHER WEST License # FAL-6339
Device Type Time (sec) Floor Location Test Results PASS/FAIL Comments & Notes
1 CELL 16 1ST AT FACP PASS
VA GRAND PRAIRIE
EMERGENCY SERVICES NOTIFICATION
JOINT COMMISSION EC.02.03.05 STANDARD EP5; DEVICE LISTING AND TESTED PER NFPA 72 2010 Edition (table 14.4.5)
Central Station
SW DISPATCH
EP5
Monitoring
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net
General
1. (To be filled out by the Owner or Owner's Representative) a.
b.
c.
d. Has the piping in all dry systems been checked for proper pitch within the past five years?
e. Has the piping in all systems been checked for obstructive materials?
f.
If tested through flow meter, when was pump last testing flow water?
g.
h.
Quick Response (20 Years) Dry (10 years) Greater than 325˚F/163˚C (5yr) Corrosive env't. (5yr.)
i. Are any extra high temperature solder sprinklers regularly exposed to temperatures near 300 F?
j. Have Alarm/Check valves and associated trim been internally inspected in the past 5 years?
k. Have gauges been compared to a calibrated gauge, or replaced in the last 5 years?
l. Standpipe 5 year Requirements:
1. Dry standpipe hydrostatic test
2. Flow test
3. Hose hydrostatic test
4. Pressure control valve test
5. Pressure reducing valve test
m. Have pressure reducing valves been tested at full flow within the past 5 years?
n. Have master pressure reducing valves been tested at full flow within the past year?
2. (To be answered by the inspector)
a. Have the sprinkler systems been extended to all visible areas of the building?
b. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector?
c. Do sprinklers heads generally appear to be in good external condition?
d. Do sprinklers heads generally appear to be free of corrosion, paint, or loading and visible obstruction?
e. Are extra sprinklers heads available on the premises in a head box at the riser?
f. Does the exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainer appear to be satisfactory?
List Changes in the Occupancy Hazard or Fire Protection Equipment, as Advised by the Owner in Section 1A:
Control Valves a.
b. Are all control valves sealed or supervised in the open position?
c. Have all control valves been fully exercised?
d. Any control valves leaking or the presence of other abnormal conditions or any physical damage?
Water Supplies
a. Water Supply Source? City Pressure Fire Pump: Tank X City Pond
X
X X
X
X
Have fire pumps been tested to full capacity through use of hose streams or flow meters in the past 12 months?
Are gravity, surface, or pressure tanks protected from freezing? X Date: X
X
No
Have there been any changes in the occupancy, machinery, or operations since the last inspection? X
X XDate:
Date:
Have there been any changes or repairs to the fire protection systems since the last inspection? X If a fire has occurred since the last inspection, have all damaged sprinkler system components been replaced? X
Date:
Date:
X
Yes N/A
Are any of the sprinklers 50 years old or older? (Testing and/or replacement is recommended for such sprinklers)
Date:
Date:
Date:
X
X
X X X X
X
Are all sprinkler system main control valves and all other valves in the appropriate open or closed position?
X
X X
Date:
Date:
Date:
Date:
X X X
X X
Contact:
Phone:
SPRINKLER SYSTEM INSPECTION REPORT
PER NFPA 25 2011 EDITION
2737 SHERMAN ST
GRAND PRAIRIE TX 75051
Property Name:
Street:
City, State & Zip: Inspector: CHRISTOPHER WEST
VA GRAND PRAIRIE MELANIE KING
Type of inspection: Annual Month of inspection: November Year:
GRAND PRAIRIE Gravity Tank
Sprinkler System Inspection Report
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net
SPRINKLER SYSTEM INSPECTION REPORT
PER NFPA 25 2011 EDITION
2024Type of inspection: Annual Month of inspection: November Year:
Tanks, Pumps, Fire Dept. Connections a.
b.
c. Has the storage tank been internally inspected in the last 3 yrs. (unlined) or 5 yrs. (lined)?
d.
e.
Wet systems
a. No. of Systems
b. Are cold weather valves in the appropriate open or closed position?
If closed, has piping been drained?
c. Has the owner or owner's representative been advised that cold weather valves are not recommended by NFPA?
d. Have all the antifreeze systems been tested?
e. Date antifreeze systems were tested
f. The antifreeze tests indicate protection to: 1. 2. 3. 4. 5.
g. Did alarm valves, water flow alarm indicators and retards test satisfactorily?
Dry systems a.
1.) Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
2.) Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
4.) Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
5.) Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
6.) Air pressure before trip: Air pressure at trip:
Water psi before trip: Water psi at trip:
b.
c.
d.
e.
f.
g.
h. Is the dry valve house heated?
Special Systems
a. No. of Systems b.
c.
d.
Auxiliary Equipment: No. Type:
Location:
Test Results:
Alarms
a. Did the water motors and gong operate during testing?
b. Did the electric alarms operate during testing?
c. Did the supervisory alarms operate during testing?
Date:
Yes N/A No Do fire pumps, gravity, surface or pressure tanks appear to be in good external condition? X Are gravity, surface and pressure tanks at the proper pressure and/or water levels?
Date trip tested:
sec. Time to trip: sec.
psi
Time to ITD:
psi psi
Time to ITD: Time to trip:
psi
Date trip tested:
psi
Do dry valves appear to be protected from freezing?
psi psi psi psi
X
Date trip tested:
3.)
Time to ITD: Time to trip:
psi sec.
X
X psi psi psi
Is the air pressure and priming water levels normal? X Did the air compressor operate satisfactorily? X
Time to ITD: sec. Time to trip:
X
X psi
X
X
X psi
X X
Are fire dept. connections in satisfactory condition, couplings free, caps or plugs in place and check valves tight?
Yes N/A No 1 Make & Model FIRELOCK S751
XAre fire dept. connections visible and accessible?
X
Temperature Date:
System
X Did all quick opening devices operate satisfactorily? X psi
Time to ITD: sec. Time to trip: sec.
psi psi
Date trip tested:
psi
No. of Systems Make & Model psi psi psi sec.
Time to trip:
Date trip tested:
sec.
psi psi
Did all the dry valves operate satisfactorily during this inspection?
sec.
Date trip tested:
Time to ITD: sec.
sec.
sec.
Were all low points drained during this inspection?
Did all devices operate satisfactorily? X Did the supervisory features operate during testing? X
X Were valves tested as required? X
Make & Model Type
No X
Device type: Type of Test:
Yes N/A
X X
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net
SPRINKLER SYSTEM INSPECTION REPORT
PER NFPA 25 2011 EDITION
2024Type of inspection: Annual Month of inspection: November Year:
Inspection and Suggested Improvements were Discussed with the Undersigned Owner or Owner's Representative:
Test Verification Name Print Signature
Title Date
Test Date Inspector
Signature:
Christopher West
CHRISTOPHER WEST; Lic.# RME-I-1932229 System Tagged: BLUE
MELANIE KING
11/12/24 to 11/12/2411/12/24
*Sprinkler system was just installed this year.Inspector Notes:
Adjustments or Corrections Made:
10320 Markison Rd.
Dallas, TX 75238 Phone: 214-343-9200 Fax: 214-343-9265 www.firetrol.net
Annual November Year 2024
Contact: MELANIE KING Phone: 0
Inspector: CHRISTOPHER WEST
Test Pipe Size
Static Pressure
Before
Flow Pressure
Return Time to Static Pressure
Flow Alarm Time Comments
6" 70 50 60 69 SEC
SPRINKLER SYSTEM FLOW READINGS
PER NFPA 25 2011 EDITION
Test Pipe Location
MECH RM 1020
2737 SHERMAN ST
GRAND PRAIRIE TX 75051
Propert Name:
Street:
City, State & Zip:
VA GRAND PRAIRIE
Type of inspection Month of inspection
Flow Readings
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency: Annual Inspection Date: 11/12/2024 Completion Date: 11/12/2024 Inspector: Christopher West
RME-l-932229
Size Static Pressure Residual Pressure Return Time (Sec.)
to Static PSI
Results of Test
PASS / FAIL
1 6" 70 50 PASS
MECH RM 1020 AT RISER
License #
VA GRAND PRAIRIE
MAIN DRAIN TEST
JOINT COMMISSION EC.02.03.05 STANDARD EP9; DEVICE LISTING AND TESTED PER NFPA 25 2011 Edition (13.2.5; 13.3.3.4; table 13.1.1.2 & 13.8.1)
Main Drain Location
EP9
Main Drain Test
Phone (214) 343- 9200 Fax (214) 343-9265 www.firetrol.net Frequency:
Inspection Date:
Completion Date:
Inspector:
License #
LOCATION TYPE VISIBLE &
ACCESSIBLE
COUPLINGS
or SWIVELS
ARE NOT
DAMAGED
AND ROTATE
SMOOTHLY
PLUGS or
CAPS ARE IN
PLACE AND
UNDAMAGED
GASKETS
ARE IN PLACE
AND IN GOOD
CONDITION
IDENTIFICATION
SIGNS ARE IN
PLACE
THE CHECK
VALVE IS NOT
LEAKING
THE
AUTOMATIC
DRAIN VALVE
IS IN PLACE
AND
OPERATING
PROPERLY
IS THE FDC
CLAPPER IN
PLACE &
OPERATING
PROPERLY
RESULTS OF
TESTING
PASS / FAIL
1 OUTSIDE OF BLDG AT RISER
RM SIAMESE YES YES YES YES YES YES N/A YES PASS
VA GRAND PRAIRIE
FIRE DEPARTMENT CONNECTIONS
JOINT COMMISSION EC.02.03.05 STANDARD EP10; NFPA 25 2011 (13.7; 13.1.1.2)
Annual 11/12/2024 11/12/2024 Christopher West RME-l-932229
EP10
Fire Department Connections http://www.firetrol.net/
| FA1 |
| FA2 |
| Tamp |
| Flow |
| Pull |
| Smoke |
| Heat |
| Duct |
| AVs |
| Monitoring |
| Sprinkler |
| Sprinkler Flow |
| Main Drain |
| FDC |