48 - MH100 - BASEMENT HVAC PLAN.pdf

PDF 769 KB Posted

Attached to
J041--506-20-209 Replace Air Handler Bldg 31 - 1 and 2 Federal contract opportunity
Solicitation number
36C25020B0055
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This pre-solicitation announcement and related federal contract opportunity document provide details for an upcoming Invitation for Bid to replace air handlers at the Ann Arbor VA Medical Center located in Ann Arbor, Michigan. The solicitation number is 36C25020B0055 and will require removal and replacement of existing internal components in Air Handler Units 1 and 2 located in Building 31, including cooling coils, heating coils, heat recovery coils, humidifiers, supply fans, outside air control dampers, and addition of final filters. Additional work includes interior and exterior casing repairs, door seal replacements, and conversion of all components to direct digital control. The contractor must furnish all labor, materials, equipment and supervision to complete the project, estimated at between $500,000 and $1,000,000. The North American Industry Classification System code is 238220 and size standard of $16.5 million applies. The solicitation will be issued on June 30, 2020 on beta.SAM.gov and bids are due on a date specified in that solicitation. The contract type will be firm fixed price with an award date within 120 days of bid receipt and a construction period of 120 days.

View the file

Other files for this federal contract opportunity

Other files attached to J041--506-20-209 Replace Air Handler Bldg 31 - 1 and 2, newest first.
File Type Posted
Sign In Sheet 506-20-209.pdf PDF
36C25020B0055 0004.docx DOCX document
Covid Instructions.docx DOCX document
36 A103.pdf PDF
36C25020B0055 0002.docx DOCX document
01 G001.pdf PDF
03 G002.pdf PDF
47 - M001 - GENERAL MECHANICAL INFORMATION.pdf PDF
48 - MH103 - MECHANICAL HVAC PENTHOUSE PLAN.pdf PDF
36 A320.pdf PDF
36C25020B0055 0003.docx DOCX document
RFI Form 506-20-209.docx DOCX document
Contractor EMR Certification Form 2020.docx DOCX document
36C25020B0055_1.docx DOCX document
506-20-209 AHU - Specifications.pdf PDF
506-20-209 - VA AA AHU Replacement - Bid Drawings.pdf PDF
WD- ML20200100 07-24-2020.pdf PDF
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01A34333231

30A

25 27

19 21

22 23

21A

26A 26B

11 07 05

S-1

S-2

P-1

0406080910

CB-3

CB-2

CB-1

121314

15A

15B

17A

17B

17C

30B

17D

CB-5

CB-4

CB-1A

29A

CB-G

UTILITY

TUNNEL

(EL. 810'-9")

UTILITY

TUNNEL

STAIR

#3

STAIR

#1

STAIR

#2

ELEV.

ELEV.

ELEV.

(EL.

816.13)

STAIR

#4

BLDG. NO.

22LOWER

LEVEL(EL. 816 '-1 1/2")

STAIR

#5

AA A B C D D.6 E F G H J J.5 K L L.1 M

3.4

4.5

1.11

3 3

3 3

2 22 2

300 WATTS HTG

0.25 TONS CLG

225 WATTS HTG

0.15 TONS CLG

225 WATTS HTG

0.15 TONS CLG

225 WATTS HTG

0.15 TONS CLG

225 WATTS HTG

0.15 TONS CLG

300 WATTS HTG

0.25 TONS CLG

350 WATTS HTG

0.25 TONS CLG

350 WATTS HTG

0.25 TONS CLG

300 WATTS HTG

0.2 TONS CLG

300 WATTS HTG

0.2 TONS CLG

300 WATTS HTG

0.2 TONS CLG

300 WATTS HTG

0.25 TONS CLG

350 WATTS HTG

0.2 TONS CLG

400 WATTS HTG

0.2 TONS CLG

225 WATTS HTG

0.15 TONS CLG

1000 WATTS HTG

500 WATTS HTG

500 WATTS HTG

300 WATTS HTG

300 WATTS HTG

0.2 TONS CLG

350 WATTS HTG

0.25 TONS CLG

1000 WATTS HTG

300 WATTS HTG 300 WATTS HTG 300 WATTS HTG 300 WATTS HTG

300 WATTS HTG 300 WATTS HTG 300 WATTS HTG 300 WATTS HTG

1000 WATTS HTG

500 WATTS HTG 1000 WATTS HTG

VALUES SHOWN ARE MINIMUMS FOR HEATING AND COOLING.

HAVE AVAILABLE AN ADDITIONAL 10 KW OF HEATING CAPACITY AND 10 TONS OF COOLING

CAPACITY TO ADDRESS MISCELLANEOUS SPACES IN THE BASEMENT.

PROVIDE DATA LOGGERS TO RECORD TEMP AND HUMIDITY LEVELS IN SPACES IDENTIFIED IF BAS IS UNABLE TO RECORD AND TREND DUE TO CONSTRUCTION ACTIVITIES. TURN TREND DATA OVER

TO THE COR AFTER EACH SHUTDOWN.

MECHANICAL KEYNOTES - BASEMENT?

1. RADIOACTIVE ISOTOPE CONTAINMENT (NEGATIVE PRESSURE): MAINTAIN ROOM

AT 68°F TO 75°F, 45-60% RH, AND NEGATIVE PRESSURE DURING SHUTDOWNS OF

31-EX.AH-1. PROVIDE TEMPORARY HEATING OR COOLING DURING DURATION OF

SHUTDOWN. EXISTING EXHAUST AIR TERMINAL UNIT SHALL REMAIN OPEN

(MINIMUM POSITION WHERE POSSIBLE).

2. BIOSAFETY LEVEL I CONTAINMENT (POSITIVE PRESSURE): MAINTAIN ROOM AT 68°

F TO 75°F, 45-60% RH, AND POSITIVE PRESSURE DURING SHUTDOWNS OF 31-

EX.AH-1. PROVIDE TEMPORARY HEATING OR COOLING AS REQUIRED DURING

DURATION OF SHUTDOWN. EXISTING EXHAUST AIR TERMINAL UNIT SHALL BE

CLOSED DURING CONSTRUCTION SHUTDOWN.

3. BIOSAFETY LEVEL II CONTAINMENT (NEGATIVE PRESSURE): MAINTAIN ROOM AT

68°F TO 75°F, 45-60% RH, AND NEGATIVE PRESSURE DURING SHUTDOWNS OF 31-

EX.AH-1. PROVIDE TEMPORARY HEATING OR COOLING AS REQUIRED DURING

DURATION OF SHUTDOWN. EXISTING EXHAUST AIR TERMINAL UNIT SHALL REMAIN

OPEN (MINIMUM POSITION WHERE POSSIBLE).

4. EXISTING FUME HOOD 31-HD-8 SHALL BE CLOSED TO MINIMUM POSITION WHILE

MAINTAINING NEGATIVE PRESSURE.

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

600 E. Michigan Ave, Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

2850 Eisenhower Ave, Suite 310

Alexandria, VA 22314

P: 202.617.8485 www.alliance.us.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION:

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

ALLIANCE | 7GAE JV PROJECT NO.: 219008

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o n e o e q u a rt e r in c h o th re e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans Affairs17JANUARY 10, 2020

MH100

506-20-209

ANN ARBOR VAMC

SMB MMK

BASEMENT HVAC PLAN REPLACE AHU 1 & 2 -

BLDG. 31

1/8" = 1'-0"

BASEMENT HVAC PLAN

ROOM LEGEND

1 CLEAN CAGE STORAGE

01A EQUIPMENT STORAGE

2 CAGE WASHING

4 ANIMAL WARD

5 PROCEDURE & TREATMENT ROOM

6 ANIMAL WARD

7 WOMENS LOCKERS

8 ANIMAL WARD

9 ANIMAL WARD

10 ANIMAL WARD

11 MENS LOCKERS

12 CUBICLE ROOM

13 CUBICLE ROOM

14 LARGE ANIMAL WARD / RABBITS

15 PROCEDURE LAB

15A ANIMAL WARD

15B HAZARDOUS WASTE

16 LARGE ANIMAL WARD / DOGS

17 AIR LOCK

17A INFECTIOUS PROCEDURE LAB

17B INFECTIOUS WARD

17C CHANGE & SHOWER ROOM

17D STERILIZER

18 ELECTRICAL

19 H.A.C.

20 LARGE ANIMAL WARD / DOGS

21 NECROPSY

21A COLD STORAGE

22 KITCHEN FEED & BEDDING

23 ANIMAL WARD / DOGS

24 PROCEDURE LAB

25 ELECTRICAL

26 VESTIBULE

26A ANIMAL WARD / PRIMATE

26B ANIMAL WARD / PRIMATE

27 COMMUNICATIONS

28 POST OPERATIVE WARD

29 SURGICAL SUPPLY

29A STERILIZER

30 SURGICAL PREP.

30A WASTE 03 SURVIVAL SURGERY

30B SCRUB & GOWN ROOM

31 TERMINAL SURGERY

32 OFFICE/ VETERINARIAN

33 OFFICE/ SUPERVISOR

34 LOUNGE

35 ANIMAL RECEIVING & EXAM WARD

36 DIAGNOSTIC LAB

37 LINK

37A UTILITY

CB-1 NEUTRAL CORRIDOR

CB-1A ELEVATOR LOBBY

CB-2 CLEAN CORRIDOR

CB-3 DIRTY CORRIDOR

CB-4 NEUTRAL CORRIDOR

CB-5 NEUTRAL CORRIDOR

REVISIONS DATE

kozelm Stamp kozelm Date

Sheets
E601 - ELECTRICAL ONE LINE DIAGRAM
ED103 - ELECTRICAL POWER PENTHOUSE DEMO. PLAN
ED601 - ELECTRICAL ONE LINE DIAGRAM DEMOLITION
EP102 - ELEC. POWER PLAN SECOND FLOOR - FOR REF. ONLY
EP103 - ELECTRICAL POWER PENTHOUSE PLAN
M001 - GENERAL MECHANICAL INFORMATION
M401 - MECHANICAL DETAILS
M501 - MECHANICAL SCHEDULES
M601 - 3D VIEWS - DEMOLITION
M602 - 3D VIEWS - DEMOLITION
MH100 - BASEMENT HVAC PLAN
MH103 - MECHANICAL HVAC PENTHOUSE PLAN
MI101 - MECHANICAL CONTROLS & INSTRUMENTATION
2020-01-06T09:24:48-0500
Maureen M. Kozel, PE
I have reviewed this document