36 A103.pdf
PDF 278 KB Posted
- Attached to
- J041--506-20-209 Replace Air Handler Bldg 31 - 1 and 2 Federal contract opportunity
- Solicitation number
- 36C25020B0055
About this file
This pre-solicitation announcement and related federal contract opportunity describe an upcoming invitation for bid to replace air handlers at the Ann Arbor VA Medical Center in Ann Arbor, Michigan. The solicitation will be issued on or around June 20, 2020 on beta.SAM.gov seeking a contractor to remove and replace internal components in air handler units 1 and 2 located in Building 31. Work will include replacing cooling coils, heating coils, humidifiers, supply fans, outside air dampers and adding final filters. Additional repairs to casing rust and interior components are also required. The contract will utilize firm fixed pricing and have an estimated completion date of 120 days from award. The North American Industry Classification size standard of $16.5 million for NAICS code 238220 Plumbing, Heating, and Air Conditioning applies. The project value is estimated between $500,000 to $1 million. The Department of Veterans Affairs Veterans Health Administration is the contracting agency. Interested parties should monitor beta.SAM.gov for solicitation documents and amendments issued on or around June 30, 2020.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sign In Sheet 506-20-209.pdf | ||
| Covid Instructions.docx | DOCX document | |
| 36C25020B0055 0004.docx | DOCX document | |
| 36C25020B0055 0002.docx | DOCX document | |
| 01 G001.pdf | ||
| 47 - M001 - GENERAL MECHANICAL INFORMATION.pdf | ||
| 48 - MH103 - MECHANICAL HVAC PENTHOUSE PLAN.pdf | ||
| 36 A320.pdf | ||
| 03 G002.pdf | ||
| 48 - MH100 - BASEMENT HVAC PLAN.pdf | ||
| 36C25020B0055 0003.docx | DOCX document | |
| RFI Form 506-20-209.docx | DOCX document | |
| Contractor EMR Certification Form 2020.docx | DOCX document | |
| 36C25020B0055_1.docx | DOCX document | |
| 506-20-209 - VA AA AHU Replacement - Bid Drawings.pdf | ||
| WD- ML20200100 07-24-2020.pdf | ||
| 506-20-209 AHU - Specifications.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
AA A B C D D.6 E F G H J J.5 K L L.1
3.4
4.5
1.11
AREA OF WORK
AREA OF WORK
A R
E A
O F W
O R
K
A R
E A
O F W
O R
K
EXISTING AHU EXISTING AHU
NOTE:
CONTRACTOR TO USE THIS AREA AS
REPLACEMENT EQUIPMENT STAGING AREA;
REFER TO MECHANICAL SHEET M001 FOR
ADDITIONAL PHASING INFORMATION
AA A B C
1.11
A320
NOTE:
CONTRACTOR TO REMOVE & SALVAGE EXISTING INSULATED
METAL PANELS & PORTION OF EXISTING METAL STUDS FROM
RUNNER TO RUNNER TO PROVIDE ACCESS TO PENTHOUSE.
PROTECT INSULATED METAL PANELS & METAL STUDS DURING
DEMOLITION FOR RE-INSTALLATION. PATCH & REPAIR ADJACENT
SURFACES AS REQUIRED. REFER TO MECHANICAL & ELECTRICAL
PLANS PRIOR TO STUD REMOVAL FOR DEVICE RELOCATION
COORDINATION.
CONTRACTOR TO ONLY REMOVE REQ. LENGTH FOR PENTHOUSE ENTRY
13' - 2" ± NOTE:
CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND MAINTAINING
A TEMPORARY ENCLOSURE AROUND OPENING WHERE METAL
PANEL IS REMOVED. ONCE METAL PANEL IS RE-INSTALLED,
TEMPORARY ENCLOSURE CAN BE REMOVED.
EXISTING AHU
NOTE:
EXISTING COLD FORMED DOOR FRAMING TO REMAIN
AA A B C
1.11
A320
EXISTING AHU
FLOOR PLAN LEGEND
EXISTING NON-FIRE RATED WALL
NEW NON-FIRE RATED WALL
EXISTING DOOR
NEW DOOR
2-HOUR FIRE RATED BARRIER - UL DES U419
1. PHASING IS TO BE DONE IN SEQUENCE ACCORDING TO
MECHANICAL PHASING DESCRIPTION ON SHEET M001.
2. ALL CONSTRUCTION ENTRANCES ARE REQUIRED TO HAVE STICKY
WALK-OFF MATS ON INSIDE & OUTSIDE OF WORK SPACE.
3. REFER TO SHEETS A103 & A320 FOR ADDITIONAL INFORMATION
ON DEMOLITION INTENT & EXTENT.
4. CONTRACTOR TO COORDINATE ALL AHU SHUT DOWNS WITH VA
COR & BUILDING USERS AT LEAST 6 WEEKS IN ADVANCE, TO
ALLOW USERS TO PREPARE FOR AIR FLOW DISRUPTION.
5. ALL AHU COMPONENT REPLACEMENT TO TAKE PLACE AFTER
HOURS, ON WEEKENDS. AHU SHUT DOWN IS TO TAKE PLACE
BETWEEN 5:00 PM FRIDAY - 3:00 AM MONDAY. CONTRACTOR
TO COORDINATE FINAL SHUTDOWN TIMES WITH VA COR.
6. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO
ENSURE ALL BUILDING AND CONSTRUCTION CODES ARE MET
FOR EACH PHASE PRIOR TO THE PHASE BEING CONSIDERED
CLOSED.
7. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND
MAINTAINING A TEMPORARY ENCLOSURE AROUND OPENING
WHERE METAL PANEL IS REMOVED. ONCE METAL PANEL IS RE-
INSTALLED, TEMPORARY ENCLOSURE CAN BE REMOVED.
8. PARKING WILL BE ALLOWED ON NIGHTS/WEEKENDS IN
DESIGNATED LOCATIONS. PARKING DURING NORMAL BUSINESS
HOURS WILL BE LIMITED TO 2 SPACES. CONTRACTOR TO
COORDINATE PARKING LOCATIONS WITH VA COR.
GENERAL PHASING NOTES
1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com
616 361 2664 OFFICE 616 361 1493 FAX
600 E. Michigan Ave, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
2850 Eisenhower Ave, Suite 310
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
2 3 4 5 6 7 8 9
2 3 4 5 6 7 8 91
A
B
C
D
E
F
A
B
C
D
E
F
CONSULTANTS ARCHITECT/ENGINEERS
DRAWING TITLE:
APPROVED: PROJECT DIRECTOR LOCATION:
PROJECT TITLE:
DATE: CHECKED: DRAWN:
PROJECT NUMBER:
BUILDING NUMBER:
DRAWING NUMBER:
DWG. ___ OF ___
ALLIANCE | 7GAE JV PROJECT NO.: 219008
Office of
Construction and Facilities
Management
VA FORM 08-6231
o n e e ig h th i n c h o n e o e q u a rt e r in c h o th re e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o
6 "
Department of Veterans Affairs17
A103
506-20-209
ANN ARBOR VAMC
JANUARY 10, 2020 JLK EMP
PENTHOUSE FLOOR PLAN REPLACE AHU 1 & 2 -
BLDG. 31
NORTH
SCALE: 1/8" = 1'-0"
PENTHOUSE COMPOSITE PLAN
SCALE: 1/4" = 1'-0"A103
PENTHOUSE DEMOLITION PLAN01
SCALE: 1/4" = 1'-0"A103
PENTHOUSE FLOOR PLAN02
REVISIONS DATE
| Sheets |
| A103 - PENTHOUSE FLOOR PLAN |
| A320 - WALL SECTIONS |
File details come from the government source that posted it. Updated .