552-17-101: Renovate Bldg. 410 (East Wing)
Solicitation number
36C25019B0052
Issued by

About this file

36C25019B0052 S02. Project Drawings.pdf

View the file

Other files

File Type Posted
36C25019C0268-000.docx DOCX document
36C25019B0052-0001000.docx DOCX document
36C25019B0052-0001000.docx DOCX document
36C25019B0052-007.pdf PDF
36C25019B0052-003.pdf PDF
36C25019B0052-005.pdf PDF
36C25019B0052-008.pdf PDF
36C25019B0052-006.pdf PDF
36C25019B0052-012.pdf PDF
36C25019B0052-009.pdf PDF
36C25019B0052-011.pdf PDF
36C25019B0052-002.pdf PDF
36C25019B0052-001.docx DOCX document
36C25019B0052-004.pdf PDF
36C25019B0052-010.pdf PDF
36C25019B0052-007.pdf PDF
36C25019B0052-010.pdf PDF
36C25019B0052-003.pdf PDF
36C25019B0052-009.pdf PDF
36C25019B0052-004.pdf PDF
36C25019B0052-012.pdf PDF
36C25019B0052-011.pdf PDF
36C25019B0052-002.pdf PDF
36C25019B0052-006.pdf PDF
36C25019B0052-001.docx DOCX document
36C25019B0052-008.pdf PDF
36C25019B0052-000.docx DOCX document
36C25019B0052-000.docx DOCX document
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 410

Contact:Contact: Contact:

HEAPY ENGINEERING

Matthew Graham, P.E., LEED AP BD+C MEPTF Project Manager

1400 West Dorothy Lane Dayton OH 45409 p: 937.224.0861 e: MSGraham@heapy.com

MEPTF

ENGINEER

DAYTON VA MEDICAL

CENTER

Ravindra Wani Project Engineer

4100 W. Third Street Dayton, OH 45428 p: 937.268.6511 x 2838 e: Ravindra.Wani@va.gov

OWNER

GUIDON DESIGN INC.

Adam Ogrzewalla, AIA A/E Project Manager

1221 N. Pennsylvania Street Suite 200 Indianapolis, IN 46202 p: 317.800.6388 x 103 e: aogrzewalla@guidondesign.com

ARCHITECT

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

DAYTON VAMC

o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

VA DAYTON ENGINEERING 552-17-101

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer

DAYTON VA MEDICAL CENTER

4100 W. THIRD STREET, DAYTON, OH 45428

Mechanical, Electrical, Plumbing, Fire Protection Engineers

HEAPY ENGINEERING

1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861

C U s e rs

\a o g rz e w a lla \D o c u m e n ts

\1 .1

.0

B

L D

G v

A ro g rz e w a lla

.r v t

BID SET

GI000

TAAARO

COVER SHEET

05/20/2019

16.1012.03BUILDING 410 EAST WING

RENOVATION

BUILDING 410 EAST WING RENOVATION

DAYTON VA MEDICAL CENTER

4100 W. THIRD STREET

DAYTON, OH 45428

VICINITY MAP

LOCATION MAP

N

N

SHEET LIST

SHEET NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

GI101 FIRST FLOOR LIFE SAFETY PLAN

GI102 SECOND FLOOR LIFE SAFETY PLANS

GI103 THIRD FLOOR LIFE SAFETY PLAN

GI104 INFECTION CONTROL & PHASING PLAN

GI105 INFECTION CONTROL & PHASING PLAN

GI106 INFECTION CONTROL & PHASING PLAN

GI107 BID ALTERNATES

ARCHITECTURAL

AA001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS

AD101 DEMOLITION FIRST FLOOR PLAN

AD102 DEMOLITION SECOND FLOOR PLAN

AD103 DEMOLITION THIRD FLOOR PLAN

AS101 FIRST FLOOR PLAN

AS102 SECOND FLOOR PLAN

AS111 REFLECTED CEILING PLAN - FIRST FLOOR

AS112 REFLECTED CEILING PLAN - SECOND FLOOR

AS201 BUILDING ELEVATIONS

AS401 ENLARGED PLANS & ELEVATIONS

AS501 ARCHITECTURAL DETAILS

AS601 ARCHITECTURAL DOOR & WINDOW SCHEDULES

AI100 FINISH SCHEDULE

AI101 FINISH WALL TREATMENT PLAN - FIRST FLOOR

AI102 FINISH WALL TREATMENT PLAN - SECOND FLOOR

AI103 FINISH FLOOR PATTERN PLAN - FIRST FLOOR

AI104 FINISH FLOOR PATTERN PLAN - SECOND FLOOR

AI105 FINISH FLOOR PLAN & REFLECTED CEILING PLAN - THIRD FLOOR

AI211 INTERIOR CASEWORK ELEVATIONS AND SECTIONS

FIRE SUPPRESSION

FX001 LEGEND SYMBOLS & INDEX OF DRAWINGS

FX100 PARTIAL BASEMENT & FIRST FLOOR PLANS - FIRE SUPRESSION

FX101 PARTIAL SECOND & THIRD FLOOR PLANS - FIRE SUPRESSION

PLUMBING

P001 LEGEND SYMBOLS & INDEX OF DRAWINGS

PD101 PARTIAL FIRST FLOOR DEMOLITION PLAN

PD102 PARTIAL SECOND FLOOR DEMOLITION PLAN

PP100 PARTIAL BASEMENT NEW WORK PLAN

PP101 PARTIAL FIRST FLOOR NEW WORK PLAN

PP102 PARTIAL SECOND FLOOR NEW WORK PLAN

P601 SCHEDULES

P602 SOIL, WASTE, VENT DIAGRAM

MECHANICAL

M001 LEGEND SYMBOLS & INDEX OF DRAWINGS

MD100 PARTIAL BASEMENT FLOOR PLAN - REMOVALS

MD101 PARTIAL FIRST FLOOR PLAN - REMOVALS

MD102 PARTIAL SECOND FLOOR PLAN - REMOVALS

MD103 PARTIAL THIRD FLOOR PLAN - REMOVALS

MD104 PARTIAL ATTIC FLOOR PLAN - REMOVALS

MH101 PARTIAL FIRST FLOOR PLAN - DUCTWORK

MH102 PARTIAL SECOND FLOOR PLAN - DUCTWORK

MH103 PARTIAL THIRD FLOOR PLAN - DUCTWORK

MH104 PARTIAL ATTIC FLOOR PLAN - DUCTWORK

MP100 PARTIAL BASEMENT FLOOR PLAN - PIPING

MP101 PARTIAL FIRST FLOOR PLAN - PIPING

MP102 PARTIAL SECOND FLOOR PLAN - PIPING

MP103 PARTIAL THIRD FLOOR PLAN - PIPING

MP104 PARTIAL ATTIC FLOOR PLAN - PIPING

M501 DETAILS

M502 DETAILS

M601 SCHEDULES

M602 SCHEDULES

ELECTRICAL

E001 LEGEND SYMBOLS & INDEX OF DRAWINGS

ED101 PARTIAL FIRST FLOOR PLAN - REMOVALS

ED102 SECOND FLOOR PLAN - REMOVALS

ED103 THIRD FLOOR PLAN - REMOVALS

EL101 PARTIAL FIRST & SECOND FLOOR PLANS - LIGHTING

EL102 PARTIAL THIRD FLOOR PLAN - LIGHTING

EP100 BASEMENT PLAN - POWER

EP101 PARTIAL FIRST, SECOND, AND THIRD FLOOR PLANS - POWER

ET100 BASEMENT PLAN - SYSTEMS

ET101 FIRST FLOOR PLAN - SYSTEMS

ET102 SECOND FLOOR PLAN - SYSTEMS

ET103 THIRD FLOOR PLAN - SYSTEMS

E201 SINGLE LINE - DIAGRAM

E202 PANEL SCHEDULES

E301 ENLARGED FLOOR PLANS - SIGNALS CLOSETS

E302 ENLARGED FLOOR PLANS - SIGNALS CLOSETS

E303 ENLARGED FLOOR PLANS - ELECTRICAL

E401 DETAILS - SECURITY

E402 DETAILS - TECHNOLOGY

E403 LIGHTING SCHEDULE

E501 SCHEDULES

BID SET SUBMISSION

D D

C

C

B

10 11

11A

11A

F F

E

G G

H H

D.2D.2

8A

NURSE STATION

CW-101

VISITATION ROOM

EW-158

POLICE HUB

EW-157

OFFICE

EW-156

OFFICE

EW-155

OFFICE

EW-154

OFFICE

EW-153

OFFICE

EW-152

SALLEYPORT

CW-100

LOBBY

CW-102

CORRIDOR

C-1-3

IT

CW-123

CORRIDOR

C-1-1

INTAKE ROOM

CW-140

DEBUG STATION

EW-141

GROUP MEETING

ROOM A

EW-142

MEN'S TOILET

EW-143

WOMEN'S TOILET

EW-144

HAC

EW-145

OFFICE

EW-146A

CORRIDOR

C-1-4

OFFICE

EW-146D

OFFICE

EW-146C

COPY

EW-146B

OFFICE

EW-147

GROUP MEETING

ROOM B

EW-148

GROUP MEETING

ROOM C

EW-149

GROUP MEETING

ROOM D

EW-150

OFFICE

EW-151

EXIT

EXIT

EXIT

EXIT

AA

A.6

A.7

E.2

CLOSET

CW-126

CLOSET

CW-125

CLOSET

CW-124

NIC

NIC

EXIT

FEC FEC

MAX TRAVEL DISTANCE: 114' - 0" MAX TRAVEL DISTANCE: 78' - 9"

CODE ANALYSIS LEGEND

TOTAL OCCUPANCY

FEC

EXIT

OCCUPANCY LOAD FACTOR

EXITS REQUIRED

SQUARE FOOTAGE

OCCUPANCY TYPE

EGRESS EXIT SIGNAGE

FIRE EXTINGUISHER CABINET

DIAGONAL DISTANCE

EXIT SEPARATION DISTANCE

EGRESS PATH

2 HR - FIRE SEPARATION

1 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

B

1500 SF

REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND

REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.

ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)

ASCE-07-10

ACI 318-11

ACI 530-11

AISC 341-10

AISC 360-10

PCI MNL 120-10, DESIGN HANDBOOK

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION

NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016

EDITION

NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE

PROTECTION, 2016 EDITION

NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND

THEIR APPURTENANCE, 2016 EDITION.

NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION

NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION

NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION

NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA

PROCESSING EQUIPMENT, 2017 EDITION

NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION

NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING

SYSTEMS, 2015 EDITION.

NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION

NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION

NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION

NFPA 101, LIFE SAFETY CODE, 2015 EDITION

NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS

NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.

NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017

EDITION

NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION

MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA

5000 AND NFPA 900

ASHRAE 90.1-2016 HVAC SYSTEMS

ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN

BUILDINGS

ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES

ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING

PROCESS

ASHRAE 0 - 2013 COMMISSIONING PROCESS

ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY

ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS

ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ENERGY POLICY ACT OF 2005 (EPACT)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND

TRANSPORTATION MANAGEMENT.

2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND

OUTPATIENT FACILITIES

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)

VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS

ARCHITECTURAL, JUNE 1, 2018

ASBESTOS ABATEMENT, JULY 2011

CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012

ELECTRICAL, DECEMBER 2015

ENERGY SUSTAINABILITY, MAY 2014

EQUIPMENT, JANUARY 2006

ESTIMATING, MARCH 8, 2011

NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010

FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015

HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,

NOVEMBER 2017

INTERIOR DESIGN, MAY 2008

PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015

PLUMBING, NOVEMBER 2014

STRUCTURAL, FEBRUARY 1, 2014

WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012

SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013

ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR

PROJECTS SEPTEMBER 30, 2010

ELEVATOR DESIGN MANUAL, JULY 2017

EPA GUIDELINES CHECKLIST

VA DESIGN MANUALS PG-18-10:

GOVERNING CODES:

CODE ANALYSIS

THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:

1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE

2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)

3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:

STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

BEARING WALLS

EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

NON-BEARING WALLS AND PARTITIONS

EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE

FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)

SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)

4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.

5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)

6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)

7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)

8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)

9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING

CONDITIONS: (LSC 18.1.3.3)

(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY

ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.

(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE

WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.

10. MEANS OF EGRESS

• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.

• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120

MM) IN CLEAR AND UNOBSTRUCTED WIDTH.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL

THERAPY;.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES

• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.

• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)

• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)

• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)

• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)

• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)

• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)

11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)

TABLE 19.3.2.1

• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK

LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR

• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR

• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.

• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR

• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.

13. INTERIOR FINISH

• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.

• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.

• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.

• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS

SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD

METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.

• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA

260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590

14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.

15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.

• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)

• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)

• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)

• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.

• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)

16. FIRE SUPPRESSION:

SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.

THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF

VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:

STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:

ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 250 GPM

ALL OTHER AREAS SHALL BE PROTECTED AS:

LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 100 GPM

ALL SPRINKLERS WITHIN THE SMOKE ZONE SHALL BE QUICK RESPONSE SPRINKLERS.

17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.

CODE CRITERIA

GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD

PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

NOTES:

CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

CODE REVIEW

THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.

FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN

USED.

PROJECT SCOPE

THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN

IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND

PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR

AND AN INPATIENT BEHAVIORAL HEALTH UNIT ON THE SECOND FLOOR.

CODE ANALYSIS - NFPA 101, CHAPTER 19

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

DAYTON VAMC

o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

VA DAYTON ENGINEERING 552-17-101

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer

DAYTON VA MEDICAL CENTER

4100 W. THIRD STREET, DAYTON, OH 45428

Mechanical, Electrical, Plumbing, Fire Protection Engineers

HEAPY ENGINEERING

1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861

C U s e rs

\a o g rz e w a lla \D o c u m e n ts

\1 .1

.0

B

L D

G v

A ro g rz e w a lla

.r v t

BID SET

GI101

TAAARO

FIRST FLOOR LIFE SAFETY PLAN

05/20/2019

16.1012.03BUILDING 410 EAST WING

RENOVATION

SCALE: 3/32" = 1'-0"GI101

3 LIFE SAFETY PLAN - FIRST FLOOR

N

D D

C

C

B

10 11

11A

11A

F F

E

G G

H H

D.2D.2

8A

EXIT

EXIT

EXIT

CORRIDOR

C-1-5

IT

CW-222B

CORRIDOR

C-1-6

SPECIMEN ROOM

CW-261

PATIENT ROOM

EW-262

PATIENT ROOM

EW-263

PATIENT ROOM

EW-264

PATIENT ROOM

EW-265

PATIENT ROOM

EW-266

PATIENT ROOM

EW-267

PATIENT ROOM

EW-268

PATIENT ROOM

EW-269

PATIENT ROOM

EW-270

DOUBLE PATIENT

ROOM

EW-271

PATIENT ROOM

EW-272

PATIENT ROOM

EW-273

PATIENT ROOM

EW-274

PATIENT ROOM

EW-275

PATIENT ROOM

EW-276

PATIENT ROOM

EW-277

PATIENT ROOM

EW-278

PATIENT ROOM

EW-279

PATIENT ROOM

EW-280

CORRIDOR

C-1-7

MAX TRAVEL DISTANCE: 134' - 4"

MAX TRAVEL DISTANCE: 111'-0 1/2"

AA

A.6

A.7

E.2

FEC

FEC

CLOSET

CW-225

CLOSET

CW-224

TOILET

EW-276B

TOILET

EW-277B

TOILET

EW-275B

TOILET

EW-274B

TOILET

EW-273B

TOILET

EW-272B

TOILET

EW-271B

TOILET

EW-270B

TOILET

EW-269B

TOILET

EW-268B

TOILET

EW-267B

TOILET

EW-266B

TOILET

EW-265B

TOILET

EW-264B

TOILET

EW-263B

TOILET

EW-262B

TOILET

EW-280B

TOILET

EW-279B

TOILET

EW-278B

CODE ANALYSIS

THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:

1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE

2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)

3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:

STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

BEARING WALLS

EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

NON-BEARING WALLS AND PARTITIONS

EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE

FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)

SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)

4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.

5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)

6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)

7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)

8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)

9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING

CONDITIONS: (LSC 18.1.3.3)

(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY

ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.

(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE

WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.

10. MEANS OF EGRESS

• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.

• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120

MM) IN CLEAR AND UNOBSTRUCTED WIDTH.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL

THERAPY;.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES

• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.

• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)

• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)

• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)

• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)

• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)

• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)

11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)

TABLE 19.3.2.1

• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK

LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR

• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR

• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.

• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR

• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.

13. INTERIOR FINISH

• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.

• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.

• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.

• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS

SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD

METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.

• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA

260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590

14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.

15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.

• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)

• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)

• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)

• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.

• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)

16. FIRE SUPPRESSION:

SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.

THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF

VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:

STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:

ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 250 GPM

ALL OTHER AREAS SHALL BE PROTECTED AS:

LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 100 GPM

17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.

GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD

PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

NOTES:

CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

CODE REVIEW

THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.

FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN

USED.

PROJECT SCOPE

THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN

IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND

PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR

CODE ANALYSIS LEGEND

TOTAL OCCUPANCY

FEC

EXIT

OCCUPANCY LOAD FACTOR

EXITS REQUIRED

SQUARE FOOTAGE

OCCUPANCY TYPE

EGRESS EXIT SIGNAGE

FIRE EXTINGUISHER CABINET

DIAGONAL DISTANCE

EXIT SEPARATION DISTANCE

EGRESS PATH

2 HR - FIRE SEPARATION

1 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

B

1500 SF

REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND

REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.

ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)

ASCE-07-10

ACI 318-11

ACI 530-11

AISC 341-10

AISC 360-10

PCI MNL 120-10, DESIGN HANDBOOK

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION

NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016

EDITION

NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE

PROTECTION, 2016 EDITION

NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND

THEIR APPURTENANCE, 2016 EDITION.

NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION

NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION

NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION

NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA

PROCESSING EQUIPMENT, 2017 EDITION

NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION

NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING

SYSTEMS, 2015 EDITION.

NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION

NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION

NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION

NFPA 101, LIFE SAFETY CODE, 2015 EDITION

NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS

NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.

NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017

EDITION

NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION

MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA

5000 AND NFPA 900

ASHRAE 90.1-2016 HVAC SYSTEMS

ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN

BUILDINGS

ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES

ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING

PROCESS

ASHRAE 0 - 2013 COMMISSIONING PROCESS

ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY

ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS

ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ENERGY POLICY ACT OF 2005 (EPACT)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND

TRANSPORTATION MANAGEMENT.

2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND

OUTPATIENT FACILITIES

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)

VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS

ARCHITECTURAL, JUNE 1, 2018

ASBESTOS ABATEMENT, JULY 2011

CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012

ELECTRICAL, DECEMBER 2015

ENERGY SUSTAINABILITY, MAY 2014

EQUIPMENT, JANUARY 2006

ESTIMATING, MARCH 8, 2011

NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010

FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015

HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,

NOVEMBER 2017

INTERIOR DESIGN, MAY 2008

PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015

PLUMBING, NOVEMBER 2014

STRUCTURAL, FEBRUARY 1, 2014

WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012

SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013

ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR

PROJECTS SEPTEMBER 30, 2010

ELEVATOR DESIGN MANUAL, JULY 2017

EPA GUIDELINES CHECKLIST

VA DESIGN MANUALS PG-18-10:

GOVERNING CODES:

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

DAYTON VAMC

o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

VA DAYTON ENGINEERING 552-17-101

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer

DAYTON VA MEDICAL CENTER

4100 W. THIRD STREET, DAYTON, OH 45428

Mechanical, Electrical, Plumbing, Fire Protection Engineers

HEAPY ENGINEERING

1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861

C U s e rs

\a o g rz e w a lla \D o c u m e n ts

\1 .1

.0

B

L D

G v

A ro g rz e w a lla

.r v t

BID SET

GI102

TAAARO

SECOND FLOOR LIFE SAFETY PLANS

05/20/2019

16.1012.03BUILDING 410 EAST WING

RENOVATION

SCALE: 3/32" = 1'-0"GI102

1 LIFE SAFETY PLAN - SECOND FLOOR

D D

C C

B

10 11

11A

11A

F F

E

G G

H H

D.2D.2

8A

COMMUNITY ROOM

WW-301

IT

CW-122C

AA

A.6

A.7

E.2

NIC

FOYER

300A

PRINTER ROOM

CW-357

FOYER

301B

CLOSET

301A

NIC

NIC

CLOSET

CW-323

CLOSET

CW-324

EXITTRAVEL DISTANCE : 164' - 6"

M A

X T

R A

V E

L D

IS

T

A N

C E

0"

EXIT

CODE ANALYSIS

THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:

1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE

2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)

3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:

STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

BEARING WALLS

EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

NON-BEARING WALLS AND PARTITIONS

EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE

FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE

SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)

SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)

4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.

5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)

6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)

7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)

8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)

9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING

CONDITIONS: (LSC 18.1.3.3)

(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY

ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.

(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE

WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.

10. MEANS OF EGRESS

• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.

• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120

MM) IN CLEAR AND UNOBSTRUCTED WIDTH.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL

THERAPY;.

• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES

• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.

• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)

• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)

• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)

• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)

• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)

• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)

11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)

TABLE 19.3.2.1

• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK

LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR

• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR

• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.

• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR

• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.

13. INTERIOR FINISH

• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.

• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.

• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.

• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS

SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD

METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.

• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA

260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590

14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.

15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.

• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)

• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)

• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)

• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.

• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)

16. FIRE SUPPRESSION:

SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.

THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF

VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:

STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:

ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 250 GPM

ALL OTHER AREAS SHALL BE PROTECTED AS:

LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.

HOSE STREAM ALLOWANCE: 100 GPM

17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.

GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD

PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.

NOTES:

CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

CODE REVIEW

THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.

FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN

USED.

PROJECT SCOPE

THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN

IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND

PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR

CODE ANALYSIS LEGEND

TOTAL OCCUPANCY

FEC

EXIT

OCCUPANCY LOAD FACTOR

EXITS REQUIRED

SQUARE FOOTAGE

OCCUPANCY TYPE

EGRESS EXIT SIGNAGE

FIRE EXTINGUISHER CABINET

DIAGONAL DISTANCE

EXIT SEPARATION DISTANCE

EGRESS PATH

2 HR - FIRE SEPARATION

1 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

B

1500 SF

REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND

REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.

ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)

ASCE-07-10

ACI 318-11

ACI 530-11

AISC 341-10

AISC 360-10

PCI MNL 120-10, DESIGN HANDBOOK

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION

NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016

EDITION

NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE

PROTECTION, 2016 EDITION

NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND

THEIR APPURTENANCE, 2016 EDITION.

NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION

NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION

NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION

NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA

PROCESSING EQUIPMENT, 2017 EDITION

NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION

NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION

NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING

SYSTEMS, 2015 EDITION.

NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION

NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION

NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION

NFPA 101, LIFE SAFETY CODE, 2015 EDITION

NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS

NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.

NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017

EDITION

NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION

MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA

5000 AND NFPA 900

ASHRAE 90.1-2016 HVAC SYSTEMS

ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN

BUILDINGS

ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES

ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING

PROCESS

ASHRAE 0 - 2013 COMMISSIONING PROCESS

ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY

ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS

ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES

2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS

ENERGY POLICY ACT OF 2005 (EPACT)

EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND

TRANSPORTATION MANAGEMENT.

2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND

OUTPATIENT FACILITIES

VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD

STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)

VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS

ARCHITECTURAL, JUNE 1, 2018

ASBESTOS ABATEMENT, JULY 2011

CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012

ELECTRICAL, DECEMBER 2015

ENERGY SUSTAINABILITY, MAY 2014

EQUIPMENT, JANUARY 2006

ESTIMATING, MARCH 8, 2011

NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010

FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015

HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,

NOVEMBER 2017

INTERIOR DESIGN, MAY 2008

PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015

PLUMBING, NOVEMBER 2014

STRUCTURAL, FEBRUARY 1, 2014

WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012

SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013

ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR

PROJECTS SEPTEMBER 30, 2010

ELEVATOR DESIGN MANUAL, JULY 2017

EPA GUIDELINES CHECKLIST

VA DESIGN MANUALS PG-18-10:

GOVERNING CODES:

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

DAYTON VAMC

o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

B

A

C

D

E

F

1 2 3 4 5 6 7 9

F

E

D

C

B

A

97 8654321

OFFICE OF

FACILITIES

MANAGEMENT

VA Project Number

VA DAYTON ENGINEERING 552-17-101

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204

317.800.6388 | WWW.GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer

DAYTON VA MEDICAL CENTER

4100 W. THIRD STREET, DAYTON, OH 45428

Mechanical, Electrical, Plumbing, Fire Protection Engineers

HEAPY ENGINEERING

1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861

C U s e rs

\a o g rz e w a lla \D o c u m e n ts

\1 .1

.0

B

L D

G v

A ro g rz e w a lla

.r v t

BID SET

GI103

TAAARO

THIRD FLOOR LIFE SAFETY PLAN

05/20/2019

16.1012.03BUILDING 410 EAST WING

RENOVATION

SCALE: 3/32" = 1'-0"GI103

1 LIFE SAFETY PLAN - THIRD FLOOR

UP

UP

CONTINUOUS FIRESAFE SEALANT

TOP AND BOTTOM, & BOTH SIDES

3 1/2" SOUND ATTENUATION

BATT.

5/8" TYPE X GYPSUM BOARD, BOTH

SIDES

3 5/8" METAL STUD @ 16" O.C.

WITH RUNNER CHANNELS ALONG

TOP AND BOTTOM

CONSTRUCTION

SIDE

PUBLIC

SIDE

6 MIL. FIRE RETARDANT VISQUEEN

MEMBRANE. CONTINUOUSLY

ADHERE TO THE STRUCTURAL DECK

ABOVE AND TO THE FLOOR BELOW

WITH TAPE.

UNDERSIDE OF STRUCTURAL DECK

UL LISTING:

U465

COORDINATE WITH EXISTING

CEILING

D

D

C

C

B

10 11

11A

11A

E E

D.2D.2

8A

INTAKE ROOM

CW-140

OFFICE

EW-152

OFFICE

EW-153

OFFICE

EW-154

OFFICE

EW-155

OFFICE

EW-156

POLICE HUB

EW-157

VISITATION ROOM

EW-158

DEBUG STATION

EW-141

GROUP MEETING ROOM A

EW-142 MEN'S TOILET

EW-143

WOMEN'S TOILET

EW-144 HAC

EW-145

CORRIDOR

C-1-4

OFFICE

EW-146A

COPY

EW-146B

OFFICE

EW-146C

OFFICE

EW-146D

OFFICE

EW-147

GROUP MEETING ROOM B

EW-148

GROUP MEETING ROOM C

EW-149

GROUP MEETING ROOM D

EW-150

OFFICE

EW-151

LOBBY

CW-102

NURSE STATION

CW-101

CORRIDOR

C-1-3

IT

CW-123

NIC

NIC

AA

A.6

A.7

E.2

CLOSET

CW-124

CLOSET

CW-125

CLOSET

CW-126

CORRIDOR

C-1-1

PHASE 2

TEMPORARY

PARTITON AND

ACCESS DOOR

PHASE 3

TEMPORARY

PARTITON AND

ACCESS DOOR

PHASE 3

TEMPORARY

PARTITON

PHASE 1

PHASE 1 TEMP

PARTITION AND

ACCESS DOOR

REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED

BY CLASS IN SPECIFICATION 013526 AND ADDITIONAL INFORMATION.

REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE

FOR ADDITIONAL INFORMATION.

PROJECT SHALL BE COMPLETED IN THREE PHASES.

COORDINATE FULL SCOPE OF WORK WITH CONTRACT DOCUMENTS AND

FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE

CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE

PROJECT BOUNDARY.

COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER

WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR

AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY

IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE

APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND

PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA

PROTOCOLS AND PLAN IS APPROVED.

SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR

AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE PHASING

INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR PROVIDED

CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW THE FLOOR

PLATE OF THE PROJECT BOUNDARY.

ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 8:00 AM

AND 5:00 PM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE

CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED IN

A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED AND

BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.

A.

B.

C.

D.

E.

F.

G.

INFECTION CONTROL GENERAL NOTES

EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED AT

ALL TIMES. SEE SPECIFICATION FOR HOURS OF OPERATION.

WORK REQUIRING VIBRATION OR LOUD NOISE SHALL TAKE PLACE BETWEEN

THE HOURS OF 8:00 AM AND 5:00 PM. EVERY EFFORT SHALL BE MADE TO

KEEP NOISE AND VIBRATION TO A MINIMUM.

PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36" STICKY

WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION.

MAT SHALL BE REPLACED OR CLEANED AS NECESSARY

PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH

TEMPORARY DOOR LOCATION.

CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,

MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE

LIQUIDS UP TO 30 GALLONS.

ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED WITH

4 MIL. POLY SHEET.

ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT

BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED

ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED

WITH A LID.

ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY

STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE

MATERIALS SHALL NOT BE STORED IN THE FACILITY.

PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE

PROJECT BOUNDARY.

H.

I.

J.

K.

L.

M.

N.

O.

P.

INFECTION CONTROL PROJECT INFORMATION

CONSTRUCTION ACTIVITY - FIRE RISK: TYPE C

PATIENT RISK GROUP: LOW

CLASS OF PRECAUTION MATRIX: II

INFECTION CONTROL PLAN NOTES #

PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL

CONSTRUCTION PER NFPA 241. REFER TO DETAIL 2/GI104.

PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH CARD

READER ACCESS. DOOR TO BE 3/4 HOUR FIRE RATED AND SELF CLOSING.

PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL

CONSTRUCTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

PHASING GENERAL NOTES

A

B

C

AREAS ADJACENT TO PROJECT AREAS TO BE OCCUPIED BY STAFF AND

VETERANS THROUGHOUT CONSTRUCTION.

PROJECT SHALL BE COMPLETED DURING TYPICAL BUSINESS HOURS, 8:00 AM

TO 5:00 PM. COORDINATE WITH COR.

REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION

FOR EACH PHASE AND AREA OF WORK.

IC/PHASING LEGEND

TEMPORARY WALLS. SEE PLAN AND

PLAN NOTES

TEMPORARY CONSTRUCTION ACCESS

DOORS

PHASE 2: OWNER TO RELOCATE LOBBY DURING

THE DURATION OF PHASE 2 AND 3 CONSTRUCTION.

CONTRACTOR TO DEMOLISH EXISTING LOBBY AND

PROVIDE NEW NURSE STATION AS INDICATED IN

CONSTRUCTION DOCUMENTS

PHASE 3: NURSE STATION TO RELOCATE TO NEW

NURSE STATION. OWNER TO RELOCATE

TECHNICIAN OFFICE. CONTRACTOR TO

DEMOLISH EXISTING NURSE STATION,

TECHNICIAN OFFICE, AND WORKROOM AND

PROVIDE NEW LOBBY AS INDICATED IN

CONSTRUCTION DOCUMENTS.

BEYOND PROJECT BOUNDARY

KEY PLAN

AREA OF WORK

Drawing Title

Approved for Design Concept:

Project Title

Date

Location

Checked By:

Building Number

Project Number

Drawing Number

Drawn By:

Revisions: Date

ARCHITECT/ENGINEERS:

DAYTON VAMC

o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h…