36C25019B0052-005.pdf
PDF 26 MB Posted
- Attached to
- 552-17-101: Renovate Bldg. 410 (East Wing)
- Solicitation number
- 36C25019B0052
About this file
36C25019B0052 S02. Project Drawings.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019C0268-000.docx | DOCX document | |
| 36C25019B0052-0001000.docx | DOCX document | |
| 36C25019B0052-0001000.docx | DOCX document | |
| 36C25019B0052-007.pdf | ||
| 36C25019B0052-003.pdf | ||
| 36C25019B0052-005.pdf | ||
| 36C25019B0052-008.pdf | ||
| 36C25019B0052-006.pdf | ||
| 36C25019B0052-012.pdf | ||
| 36C25019B0052-009.pdf | ||
| 36C25019B0052-011.pdf | ||
| 36C25019B0052-002.pdf | ||
| 36C25019B0052-001.docx | DOCX document | |
| 36C25019B0052-004.pdf | ||
| 36C25019B0052-010.pdf | ||
| 36C25019B0052-007.pdf | ||
| 36C25019B0052-010.pdf | ||
| 36C25019B0052-003.pdf | ||
| 36C25019B0052-009.pdf | ||
| 36C25019B0052-004.pdf | ||
| 36C25019B0052-012.pdf | ||
| 36C25019B0052-011.pdf | ||
| 36C25019B0052-002.pdf | ||
| 36C25019B0052-006.pdf | ||
| 36C25019B0052-001.docx | DOCX document | |
| 36C25019B0052-008.pdf | ||
| 36C25019B0052-000.docx | DOCX document | |
| 36C25019B0052-000.docx | DOCX document |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLDG 410
Contact:Contact: Contact:
HEAPY ENGINEERING
Matthew Graham, P.E., LEED AP BD+C MEPTF Project Manager
1400 West Dorothy Lane Dayton OH 45409 p: 937.224.0861 e: MSGraham@heapy.com
MEPTF
ENGINEER
DAYTON VA MEDICAL
CENTER
Ravindra Wani Project Engineer
4100 W. Third Street Dayton, OH 45428 p: 937.268.6511 x 2838 e: Ravindra.Wani@va.gov
OWNER
GUIDON DESIGN INC.
Adam Ogrzewalla, AIA A/E Project Manager
1221 N. Pennsylvania Street Suite 200 Indianapolis, IN 46202 p: 317.800.6388 x 103 e: aogrzewalla@guidondesign.com
ARCHITECT
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
DAYTON VAMC
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
VA DAYTON ENGINEERING 552-17-101
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer
DAYTON VA MEDICAL CENTER
4100 W. THIRD STREET, DAYTON, OH 45428
Mechanical, Electrical, Plumbing, Fire Protection Engineers
HEAPY ENGINEERING
1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861
C U s e rs
\a o g rz e w a lla \D o c u m e n ts
\1 .1
.0
B
L D
G v
A ro g rz e w a lla
.r v t
BID SET
GI000
TAAARO
COVER SHEET
05/20/2019
16.1012.03BUILDING 410 EAST WING
RENOVATION
BUILDING 410 EAST WING RENOVATION
DAYTON VA MEDICAL CENTER
4100 W. THIRD STREET
DAYTON, OH 45428
VICINITY MAP
LOCATION MAP
N
N
SHEET LIST
SHEET NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI101 FIRST FLOOR LIFE SAFETY PLAN
GI102 SECOND FLOOR LIFE SAFETY PLANS
GI103 THIRD FLOOR LIFE SAFETY PLAN
GI104 INFECTION CONTROL & PHASING PLAN
GI105 INFECTION CONTROL & PHASING PLAN
GI106 INFECTION CONTROL & PHASING PLAN
GI107 BID ALTERNATES
ARCHITECTURAL
AA001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS
AD101 DEMOLITION FIRST FLOOR PLAN
AD102 DEMOLITION SECOND FLOOR PLAN
AD103 DEMOLITION THIRD FLOOR PLAN
AS101 FIRST FLOOR PLAN
AS102 SECOND FLOOR PLAN
AS111 REFLECTED CEILING PLAN - FIRST FLOOR
AS112 REFLECTED CEILING PLAN - SECOND FLOOR
AS201 BUILDING ELEVATIONS
AS401 ENLARGED PLANS & ELEVATIONS
AS501 ARCHITECTURAL DETAILS
AS601 ARCHITECTURAL DOOR & WINDOW SCHEDULES
AI100 FINISH SCHEDULE
AI101 FINISH WALL TREATMENT PLAN - FIRST FLOOR
AI102 FINISH WALL TREATMENT PLAN - SECOND FLOOR
AI103 FINISH FLOOR PATTERN PLAN - FIRST FLOOR
AI104 FINISH FLOOR PATTERN PLAN - SECOND FLOOR
AI105 FINISH FLOOR PLAN & REFLECTED CEILING PLAN - THIRD FLOOR
AI211 INTERIOR CASEWORK ELEVATIONS AND SECTIONS
FIRE SUPPRESSION
FX001 LEGEND SYMBOLS & INDEX OF DRAWINGS
FX100 PARTIAL BASEMENT & FIRST FLOOR PLANS - FIRE SUPRESSION
FX101 PARTIAL SECOND & THIRD FLOOR PLANS - FIRE SUPRESSION
PLUMBING
P001 LEGEND SYMBOLS & INDEX OF DRAWINGS
PD101 PARTIAL FIRST FLOOR DEMOLITION PLAN
PD102 PARTIAL SECOND FLOOR DEMOLITION PLAN
PP100 PARTIAL BASEMENT NEW WORK PLAN
PP101 PARTIAL FIRST FLOOR NEW WORK PLAN
PP102 PARTIAL SECOND FLOOR NEW WORK PLAN
P601 SCHEDULES
P602 SOIL, WASTE, VENT DIAGRAM
MECHANICAL
M001 LEGEND SYMBOLS & INDEX OF DRAWINGS
MD100 PARTIAL BASEMENT FLOOR PLAN - REMOVALS
MD101 PARTIAL FIRST FLOOR PLAN - REMOVALS
MD102 PARTIAL SECOND FLOOR PLAN - REMOVALS
MD103 PARTIAL THIRD FLOOR PLAN - REMOVALS
MD104 PARTIAL ATTIC FLOOR PLAN - REMOVALS
MH101 PARTIAL FIRST FLOOR PLAN - DUCTWORK
MH102 PARTIAL SECOND FLOOR PLAN - DUCTWORK
MH103 PARTIAL THIRD FLOOR PLAN - DUCTWORK
MH104 PARTIAL ATTIC FLOOR PLAN - DUCTWORK
MP100 PARTIAL BASEMENT FLOOR PLAN - PIPING
MP101 PARTIAL FIRST FLOOR PLAN - PIPING
MP102 PARTIAL SECOND FLOOR PLAN - PIPING
MP103 PARTIAL THIRD FLOOR PLAN - PIPING
MP104 PARTIAL ATTIC FLOOR PLAN - PIPING
M501 DETAILS
M502 DETAILS
M601 SCHEDULES
M602 SCHEDULES
ELECTRICAL
E001 LEGEND SYMBOLS & INDEX OF DRAWINGS
ED101 PARTIAL FIRST FLOOR PLAN - REMOVALS
ED102 SECOND FLOOR PLAN - REMOVALS
ED103 THIRD FLOOR PLAN - REMOVALS
EL101 PARTIAL FIRST & SECOND FLOOR PLANS - LIGHTING
EL102 PARTIAL THIRD FLOOR PLAN - LIGHTING
EP100 BASEMENT PLAN - POWER
EP101 PARTIAL FIRST, SECOND, AND THIRD FLOOR PLANS - POWER
ET100 BASEMENT PLAN - SYSTEMS
ET101 FIRST FLOOR PLAN - SYSTEMS
ET102 SECOND FLOOR PLAN - SYSTEMS
ET103 THIRD FLOOR PLAN - SYSTEMS
E201 SINGLE LINE - DIAGRAM
E202 PANEL SCHEDULES
E301 ENLARGED FLOOR PLANS - SIGNALS CLOSETS
E302 ENLARGED FLOOR PLANS - SIGNALS CLOSETS
E303 ENLARGED FLOOR PLANS - ELECTRICAL
E401 DETAILS - SECURITY
E402 DETAILS - TECHNOLOGY
E403 LIGHTING SCHEDULE
E501 SCHEDULES
BID SET SUBMISSION
D D
C
C
B
10 11
11A
11A
F F
E
G G
H H
D.2D.2
8A
NURSE STATION
CW-101
VISITATION ROOM
EW-158
POLICE HUB
EW-157
OFFICE
EW-156
OFFICE
EW-155
OFFICE
EW-154
OFFICE
EW-153
OFFICE
EW-152
SALLEYPORT
CW-100
LOBBY
CW-102
CORRIDOR
C-1-3
IT
CW-123
CORRIDOR
C-1-1
INTAKE ROOM
CW-140
DEBUG STATION
EW-141
GROUP MEETING
ROOM A
EW-142
MEN'S TOILET
EW-143
WOMEN'S TOILET
EW-144
HAC
EW-145
OFFICE
EW-146A
CORRIDOR
C-1-4
OFFICE
EW-146D
OFFICE
EW-146C
COPY
EW-146B
OFFICE
EW-147
GROUP MEETING
ROOM B
EW-148
GROUP MEETING
ROOM C
EW-149
GROUP MEETING
ROOM D
EW-150
OFFICE
EW-151
EXIT
EXIT
EXIT
EXIT
AA
A.6
A.7
E.2
CLOSET
CW-126
CLOSET
CW-125
CLOSET
CW-124
NIC
NIC
EXIT
FEC FEC
MAX TRAVEL DISTANCE: 114' - 0" MAX TRAVEL DISTANCE: 78' - 9"
CODE ANALYSIS LEGEND
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND
REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.
ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)
ASCE-07-10
ACI 318-11
ACI 530-11
AISC 341-10
AISC 360-10
PCI MNL 120-10, DESIGN HANDBOOK
NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION
NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION
NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016
EDITION
NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION, 2016 EDITION
NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
THEIR APPURTENANCE, 2016 EDITION.
NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION
NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION
NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION
NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA
PROCESSING EQUIPMENT, 2017 EDITION
NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION
NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION
NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING
SYSTEMS, 2015 EDITION.
NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION
NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION
NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION
NFPA 101, LIFE SAFETY CODE, 2015 EDITION
NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.
NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017
EDITION
NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION
MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA
5000 AND NFPA 900
ASHRAE 90.1-2016 HVAC SYSTEMS
ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN
BUILDINGS
ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES
ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING
PROCESS
ASHRAE 0 - 2013 COMMISSIONING PROCESS
ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY
ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS
ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
ENERGY POLICY ACT OF 2005 (EPACT)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND
TRANSPORTATION MANAGEMENT.
2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND
OUTPATIENT FACILITIES
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD
STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL
INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)
VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS
ARCHITECTURAL, JUNE 1, 2018
ASBESTOS ABATEMENT, JULY 2011
CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012
ELECTRICAL, DECEMBER 2015
ENERGY SUSTAINABILITY, MAY 2014
EQUIPMENT, JANUARY 2006
ESTIMATING, MARCH 8, 2011
NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010
FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015
HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,
NOVEMBER 2017
INTERIOR DESIGN, MAY 2008
PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015
PLUMBING, NOVEMBER 2014
STRUCTURAL, FEBRUARY 1, 2014
WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012
SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013
ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR
PROJECTS SEPTEMBER 30, 2010
ELEVATOR DESIGN MANUAL, JULY 2017
EPA GUIDELINES CHECKLIST
VA DESIGN MANUALS PG-18-10:
GOVERNING CODES:
CODE ANALYSIS
THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:
1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE
2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)
3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:
STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
BEARING WALLS
EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
NON-BEARING WALLS AND PARTITIONS
EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE
FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)
SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)
4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.
5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)
6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)
7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)
8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)
9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING
CONDITIONS: (LSC 18.1.3.3)
(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY
ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.
(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE
WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.
10. MEANS OF EGRESS
• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.
• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120
MM) IN CLEAR AND UNOBSTRUCTED WIDTH.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL
THERAPY;.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES
• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.
• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)
• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)
• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)
• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)
• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)
• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)
11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)
TABLE 19.3.2.1
• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK
LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR
• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR
• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.
• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR
• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.
13. INTERIOR FINISH
• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.
• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.
• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.
• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS
SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD
METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.
• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA
260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590
14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.
15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)
• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)
• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)
• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.
• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)
16. FIRE SUPPRESSION:
SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.
THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF
VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:
STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:
ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 250 GPM
ALL OTHER AREAS SHALL BE PROTECTED AS:
LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 100 GPM
ALL SPRINKLERS WITHIN THE SMOKE ZONE SHALL BE QUICK RESPONSE SPRINKLERS.
17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.
CODE CRITERIA
GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD
PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.
NOTES:
CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
CODE REVIEW
THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.
FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN
USED.
PROJECT SCOPE
THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN
IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND
PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR
AND AN INPATIENT BEHAVIORAL HEALTH UNIT ON THE SECOND FLOOR.
CODE ANALYSIS - NFPA 101, CHAPTER 19
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
DAYTON VAMC
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
VA DAYTON ENGINEERING 552-17-101
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer
DAYTON VA MEDICAL CENTER
4100 W. THIRD STREET, DAYTON, OH 45428
Mechanical, Electrical, Plumbing, Fire Protection Engineers
HEAPY ENGINEERING
1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861
C U s e rs
\a o g rz e w a lla \D o c u m e n ts
\1 .1
.0
B
L D
G v
A ro g rz e w a lla
.r v t
BID SET
GI101
TAAARO
FIRST FLOOR LIFE SAFETY PLAN
05/20/2019
16.1012.03BUILDING 410 EAST WING
RENOVATION
SCALE: 3/32" = 1'-0"GI101
3 LIFE SAFETY PLAN - FIRST FLOOR
N
D D
C
C
B
10 11
11A
11A
F F
E
G G
H H
D.2D.2
8A
EXIT
EXIT
EXIT
CORRIDOR
C-1-5
IT
CW-222B
CORRIDOR
C-1-6
SPECIMEN ROOM
CW-261
PATIENT ROOM
EW-262
PATIENT ROOM
EW-263
PATIENT ROOM
EW-264
PATIENT ROOM
EW-265
PATIENT ROOM
EW-266
PATIENT ROOM
EW-267
PATIENT ROOM
EW-268
PATIENT ROOM
EW-269
PATIENT ROOM
EW-270
DOUBLE PATIENT
ROOM
EW-271
PATIENT ROOM
EW-272
PATIENT ROOM
EW-273
PATIENT ROOM
EW-274
PATIENT ROOM
EW-275
PATIENT ROOM
EW-276
PATIENT ROOM
EW-277
PATIENT ROOM
EW-278
PATIENT ROOM
EW-279
PATIENT ROOM
EW-280
CORRIDOR
C-1-7
MAX TRAVEL DISTANCE: 134' - 4"
MAX TRAVEL DISTANCE: 111'-0 1/2"
AA
A.6
A.7
E.2
FEC
FEC
CLOSET
CW-225
CLOSET
CW-224
TOILET
EW-276B
TOILET
EW-277B
TOILET
EW-275B
TOILET
EW-274B
TOILET
EW-273B
TOILET
EW-272B
TOILET
EW-271B
TOILET
EW-270B
TOILET
EW-269B
TOILET
EW-268B
TOILET
EW-267B
TOILET
EW-266B
TOILET
EW-265B
TOILET
EW-264B
TOILET
EW-263B
TOILET
EW-262B
TOILET
EW-280B
TOILET
EW-279B
TOILET
EW-278B
CODE ANALYSIS
THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:
1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE
2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)
3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:
STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
BEARING WALLS
EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
NON-BEARING WALLS AND PARTITIONS
EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE
FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)
SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)
4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.
5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)
6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)
7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)
8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)
9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING
CONDITIONS: (LSC 18.1.3.3)
(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY
ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.
(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE
WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.
10. MEANS OF EGRESS
• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.
• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120
MM) IN CLEAR AND UNOBSTRUCTED WIDTH.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL
THERAPY;.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES
• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.
• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)
• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)
• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)
• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)
• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)
• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)
11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)
TABLE 19.3.2.1
• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK
LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR
• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR
• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.
• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR
• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.
13. INTERIOR FINISH
• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.
• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.
• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.
• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS
SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD
METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.
• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA
260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590
14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.
15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)
• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)
• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)
• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.
• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)
16. FIRE SUPPRESSION:
SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.
THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF
VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:
STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:
ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 250 GPM
ALL OTHER AREAS SHALL BE PROTECTED AS:
LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 100 GPM
17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.
GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD
PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.
NOTES:
CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
CODE REVIEW
THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.
FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN
USED.
PROJECT SCOPE
THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN
IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND
PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR
CODE ANALYSIS LEGEND
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND
REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.
ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)
ASCE-07-10
ACI 318-11
ACI 530-11
AISC 341-10
AISC 360-10
PCI MNL 120-10, DESIGN HANDBOOK
NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION
NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION
NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016
EDITION
NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION, 2016 EDITION
NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
THEIR APPURTENANCE, 2016 EDITION.
NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION
NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION
NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION
NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA
PROCESSING EQUIPMENT, 2017 EDITION
NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION
NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION
NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING
SYSTEMS, 2015 EDITION.
NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION
NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION
NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION
NFPA 101, LIFE SAFETY CODE, 2015 EDITION
NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.
NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017
EDITION
NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION
MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA
5000 AND NFPA 900
ASHRAE 90.1-2016 HVAC SYSTEMS
ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN
BUILDINGS
ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES
ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING
PROCESS
ASHRAE 0 - 2013 COMMISSIONING PROCESS
ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY
ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS
ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
ENERGY POLICY ACT OF 2005 (EPACT)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND
TRANSPORTATION MANAGEMENT.
2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND
OUTPATIENT FACILITIES
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD
STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL
INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)
VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS
ARCHITECTURAL, JUNE 1, 2018
ASBESTOS ABATEMENT, JULY 2011
CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012
ELECTRICAL, DECEMBER 2015
ENERGY SUSTAINABILITY, MAY 2014
EQUIPMENT, JANUARY 2006
ESTIMATING, MARCH 8, 2011
NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010
FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015
HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,
NOVEMBER 2017
INTERIOR DESIGN, MAY 2008
PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015
PLUMBING, NOVEMBER 2014
STRUCTURAL, FEBRUARY 1, 2014
WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012
SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013
ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR
PROJECTS SEPTEMBER 30, 2010
ELEVATOR DESIGN MANUAL, JULY 2017
EPA GUIDELINES CHECKLIST
VA DESIGN MANUALS PG-18-10:
GOVERNING CODES:
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
DAYTON VAMC
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
VA DAYTON ENGINEERING 552-17-101
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer
DAYTON VA MEDICAL CENTER
4100 W. THIRD STREET, DAYTON, OH 45428
Mechanical, Electrical, Plumbing, Fire Protection Engineers
HEAPY ENGINEERING
1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861
C U s e rs
\a o g rz e w a lla \D o c u m e n ts
\1 .1
.0
B
L D
G v
A ro g rz e w a lla
.r v t
BID SET
GI102
TAAARO
SECOND FLOOR LIFE SAFETY PLANS
05/20/2019
16.1012.03BUILDING 410 EAST WING
RENOVATION
SCALE: 3/32" = 1'-0"GI102
1 LIFE SAFETY PLAN - SECOND FLOOR
D D
C C
B
10 11
11A
11A
F F
E
G G
H H
D.2D.2
8A
COMMUNITY ROOM
WW-301
IT
CW-122C
AA
A.6
A.7
E.2
NIC
FOYER
300A
PRINTER ROOM
CW-357
FOYER
301B
CLOSET
301A
NIC
NIC
CLOSET
CW-323
CLOSET
CW-324
EXITTRAVEL DISTANCE : 164' - 6"
M A
X T
R A
V E
L D
IS
T
A N
C E
0"
EXIT
CODE ANALYSIS
THE CONSTRUCTION TYPE IS DETERMINED BASED UPON THE ALLOWABLE AREA AND HEIGHT REQUIREMENTS OF CHAPTER 5 OF THE 2015 IBC. CONSTRUCTION TYPE AND MATERIALS SHALL BE PER CHAPTER 6 OF THE IBC FOR TYPE II-B AND LSC II (000) CONSTRUCTION AS FOLLOWS:
1. OCCUPANCY TYPE: I-1 INSTITUTIONAL, IBC CHAPTER 3/LSC CHAPTER 19 HEALTHCARE
2. CONSTRUCTION TYPE: II-B (IBC CHAPTER 5), II (000) (NFPA 101)
3. FIRE RESISTIVE RATINGS TYPE II-B CONSTRUCTION, CHAPTER 6 IBC/NFPA 101:
STRUCTURAL FRAME: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
BEARING WALLS
EXTERIOR: NONCOMBUSTIBLE, 0 -HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
NON-BEARING WALLS AND PARTITIONS
EXTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
INTERIOR: NONCOMBUSTIBLE, 0-HOUR FIRE-RESISTIVE
FLOOR: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
ROOF: NONCOMBUSTIBLE, 0-HOUR FIRE RESISTIVE
SHAFT ENCLOSURES 2-HOUR FIRE RESISTIVE >4 STORIES (IBC 713.4, LSC 12.3.6)
SHAFT ENCLOSURES 1-HOUR FIRE RESISTIVE <4 STORIES (IBC 713.4, LSC 12.3.6)
4. STRUCTURAL DESIGN SHALL COMPLY WITH CHAPTER 16 OF THE IBC.
5. ALLOWABLE HEIGHT: 55 FT (IBC, TABLE 504.3)
6. ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLAN: 3 (IBC, TABLE 504.4)
7. ALLOWABLE AREA: BASED UPON I-1 OCCUPANCY, II-B CONSTRUCTION TYPE, AND FULLY SPRINKLED: ALLOWABLE AREA: 30,000(IBC, TABLE 506.2)
8. BUILDING SEPARATION: BASED ON A 10'-0" FIRE SEPARATION DISTANCE A 0 -HOUR FIRE RESISTANCE WALL RATING IS REQUIRED. (IBC, TABLE 602)
9. SECTIONS OF HEALTH CARE FACILITIES SHALL BE PERMITTED TO BE CLASSIFIED AS OTHER OCCUPANCIES, PROVIDED THAT THEY MEET BOTH OF THE FOLLOWING
CONDITIONS: (LSC 18.1.3.3)
(1) THEY ARE NOT INTENDED TO PROVIDE SERVICES SIMULTANEOUSLY FOR FOUR OR MORE INPATIENTS FOR PURPOSES OF HOUSING, TREATMENT, OR CUSTOMARY
ACCESS BY INPATIENTS INCAPABLE OF SELF-PRESERVATION.
(2) THEY ARE SEPARATED FROM AREAS OF HEALTH CARE OCCUPANCIES BY CONSTRUCTION HAVING A MINIMUM 2-HOUR FIRE RESISTANCE RATING IN ACCORDANCE
WITH CHAPTER 8.18.1.3.4 CONTIGUOUS NON-HEALTH CARE OCCUPANCIES.
10. MEANS OF EGRESS
• CLEAR WIDTH OF CORRIDORS SHALL BE CLEAR 6 FEET.
• AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE LESS THAN 44 IN. (1120
MM) IN CLEAR AND UNOBSTRUCTED WIDTH.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 42 INCHES FROM SLEEPING ROOMS; DIAGNOSTIC AND TREATMENT AREAS, SUCH AS X-RAY, SURGERY, OR PHYSICAL
THERAPY;.
• CLEAR WIDTH OF DOORS SHALL BE CLEAR 32 INCHES
• NOT LESS THAN 2 EXITS SHALL BE PROVIDED PER FLOOR.
• ADDITION OCCUPANCY LOAD: <500 THEREFORE 2 EXITS REQUIRED (LSC 7.4.1)
• MAXIMUM TRAVEL DISTANCE, FULLY SPRINKLED: 200 FEET (LSC 19.2.6.2.1)
• DEAD END CORRIDORS SHALL NOT EXCEED 20 FEET. (IBC 1020.4)
• MEANS OF EGRESS SHALL BE ILLUMINATED PER 7.8. (LSC 19.2.8)
• EMERGENCY LIGHTING SHALL BE PER 7.9. (LSC 19.2.9)
• EXIT SIGNAGE SHALL BE PROVIDED 7.10. (LSC 19.2.10)
11. HAZARDOUS AREAS. ANY HAZARDOUS AREAS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 8.7, AND THE AREAS SHALL BE PROTECTED AS INDICATED. (LSC 19.3.2)
TABLE 19.3.2.1
• HAZARDOUS AREA PROTECTION HAZARDOUS AREA DESCRIPTION PROTECTION/SEPARATION - BOILER AND FUEL-FIRED HEATER ROOMS 1 HOUR CENTRAL/BULK
LAUNDRIES LARGER THAN 100 FT2 (9.3 M2)1 HOUR
• ROOMS WITH SOILED LINEN IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR
• STORAGE ROOMS LARGER THAN 50 FT2(4.6 M2) BUT NOT EXCEEDING 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL.
• STORAGE ROOMS LARGER THAN 100 FT2 (9.3 M2) AND STORING COMBUSTIBLE MATERIAL 1 HOUR
• ROOMS WITH COLLECTED TRASH IN VOLUME EXCEEDING 64 GAL (242 L)1 HOUR MINIMUM FIRE RESISTANCE RATING.
13. INTERIOR FINISH
• WALLS AND CEILINGS: INTERIOR FINISH FLAME SPREAD SHALL BE LIMITED PER CHAPTER 10.2 OF THE NFPA 101 TO CLASS A MATERIALS.
• · CLASS A: FLAME SPREAD 0-25; SMOKE DEVELOPED 0-450.
• FLOORS: INTERIOR FLOOR FINISH SHALL BE CLASS I.
• FABRIC DRAPERIES, CURTAINS (EXCLUDING SHOWER CURTAINS, BUT INCLUDING CUBICLE CURTAINS), AND OTHER LOOSELY HANGING FABRICS AND FILMS
SERVING AS FURNISHINGS OR DECORATIONS IN HEALTH CARE OCCUPANCIES MUST MEET THE FLAME RESISTANCE REQUIREMENTS OF NFPA 701, STANDARD
METHODS OF FIRE TESTS FOR FLAME-RESISTANT TEXTILES AND FILMS.
• UPHOLSTERED FURNITURE AND MATTRESSES. UPHOLSTERED FURNITURE AND MATTRESSES MUST ALSO MEET SPECIFIED REQUIREMENTS, BASED ON NFPA
260, NFPA 261, NFPA 266, 16 CFR 1632, ASTME E1537, AND ASTME E1590
14. EXTINGUISHMENTS REQUIREMENTS, PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED PER NFPA 10.
15. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
• FIRE ALARM SYSTEM SHALL BE PROVIDED LSC, NFPA 70 (NEC) AND NFPA 72. (LSC 9.6.1)
• FIRE ALARM MAY BE BY MANUAL MEANS (LSC 9.6.2)
• OCCUPANT NOTIFICATION SHALL BE THROUGH AUTOMATIC MEANS PER 9.6.3. (LSC 18.3.4.3)
• SMOKE DETECTION SHALL BE PROVIDED PER NFPA 72.
• EMERGENCY RESPONDER NOTIFICATION SHALL BE NOTIFIED BY ALARM AND DETECTION SYSTEM PER 9.6.4. (LSC 18.3.4.3.2)
16. FIRE SUPPRESSION:
SPRINKLER SYSTEM: BUILDING IS REQUIRED TO BE SPRINKLED THROUGHOUT IN ACCORDANCE WITH NFPA 13.
THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH 2013 EDITION OF NFPA 13 AND THE SIXTH EDITION OF THE DEPARTMENT OF
VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL: MINIMUM DESIGN REQUIREMENTS:
STORAGE MECHANICAL AND ELECTRICAL ROOMS SHALL BE PROTECTED AS:
ORDINARY HAZARD OCCUPANCY, GROUP 1: 0.15 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 250 GPM
ALL OTHER AREAS SHALL BE PROTECTED AS:
LIGHT HAZARD OCCUPANCY: 0.10 GPM/FT2 OVER 1,500 FT2.
HOSE STREAM ALLOWANCE: 100 GPM
17. CONSTRUCTION BARRIERS CONSTRUCTED ALONG MEANS OF EGRESS SHALL BE CONSTRUCTED AND MAINTAINED PER NFPA 241.
GENERAL: THIS SUMMARY OF CODE REQUIREMENTS IS BASED PRIMARILY ON NFPA 101 (LSC). DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE IDENTIFIED. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD
PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES.
NOTES:
CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
CODE REVIEW
THE 2015 EDITION OF THE LIFE SAFETY CODE, NFPA 101, HAS BEEN USED TO REVIEW THIS PROJECT FOR COMPLIANCE WITH THE FIRE AND LIFE SAFETY REQUIREMENTS.
FOR FEATURES NOT ADDRESSED BY NFPA 101 AND THE REFERENCED NATIONAL FIRE CODES, THE 2015 EDITION OF THE INTERNATIONAL BUILDING CODE HAS BEEN
USED.
PROJECT SCOPE
THE PROJECT SCOPE INCLUDES THE RENOVATION OF THE FIRST AND SECOND FLOORS OF THE WEST WING OF EXISTING BUILDING 410. TWO ELECTRICAL CLOSETS, AN
IT CLOSET AND COMMUNITY ROOM WILL ALSO BE RENOVATED ON THE THRID FLOOR WEST WING. ON THE FIRST AND SECOND FLOOR, EXISTING PARTITIONS AND
PLUMBING FIXTURES ARE TO BE DEMOLISHED. NEW PARTITIONS AND PLUBMING FIXTURES SHALL BE CONSTRUCTED TO ACCOMODATE OFFICES ON THE FIRST FLOOR
CODE ANALYSIS LEGEND
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
REFER TO VA MANUAL PG-18-3 FOR ADDITIONAL CODES, STANDARDS, GUIDELINES AND
REGULATIONS, BELOW LISTING IS NOT COMPREHENSIVE.
ICC, INTERNATIONAL BUILDING CODES, 2015 EDITION (IBC)
ASCE-07-10
ACI 318-11
ACI 530-11
AISC 341-10
AISC 360-10
PCI MNL 120-10, DESIGN HANDBOOK
NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2013 EDITION
NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2016 EDITION
NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, 2016
EDITION
NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE
PROTECTION, 2016 EDITION
NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
THEIR APPURTENANCE, 2016 EDITION.
NFPA 54 NATOINAL FUEL GAS CODE, 2015 EDITION
NFPA 70, NATIONAL ELECTRIC CODE, 2014 EDITION
NFPA 72, NATIONAL FIRE ALARM CODE, 2016 EDITION
NFPA 75, STANDARD FOR THE PROTECTION OF ELECTRICAL COMPUTER/DATA
PROCESSING EQUIPMENT, 2017 EDITION
NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, 2014 EDITION
NFPA 80, STANDARD FOR FIRE DOORS AND FIRE WINDOWS, 2016 EDITION
NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING
SYSTEMS, 2015 EDITION.
NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS, 2015 EDITION
NFPA 99, STANDARD FOR HEALTHCARE FACILITIES, 2015 EDITION
NFPA,99B, STANDARD FOR HYPOBARIC FACILITIES, 2015 EDITION
NFPA 101, LIFE SAFETY CODE, 2015 EDITION
NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
NFPA 220, STANDARD TYPES OF BUILDING CONSTRUCTION, 2015 EDITION.
NFPA 780, STANDARD FOR INSTALLATION OF LIGHTING PROTECTION SYSTEMS, 2017
EDITION
NFPA 54 TYPE 2 CLOTHES DRYER UL 705 DEDPY, 2015 EDITION
MOST RECENT EDITION OF NFPA NATIONAL FIRE CODES WITH THE EXCEPTION OF NFPA
5000 AND NFPA 900
ASHRAE 90.1-2016 HVAC SYSTEMS
ASHRAE 189.1 -2014 STANDARD FOR THE DESIGN OF HIGH PERFORMANCE GREEN
BUILDINGS
ASHRAE 180 - 2012 VENTILATION FOR HEALTH CARE FACILITIES
ASHRAE 62.1 - 2016 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY
ASHRAE 1.1 - 2007 HVAC & R TECHNICAL REQUIREMENTS FOR COMMISSIONING
PROCESS
ASHRAE 0 - 2013 COMMISSIONING PROCESS
ASHRAE 55- 2013 THERMAL ENVIRONMENTAL CONDITIONS FOR HUMAN OCCUPANCY
ASHRAE 15 – 2013 SAFETY STANDARD FOR REFRIGERATION SYSTEMS
ANSI A117.1-2009 STANDARD ON ACCESSIBLE & USABLE BUILDINGS AND FACILITIES
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
ENERGY POLICY ACT OF 2005 (EPACT)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND
TRANSPORTATION MANAGEMENT.
2014 FGI GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND
OUTPATIENT FACILITIES
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD
STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL
INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
VA MENTAL HEALTH FACILITIES DESIGN GUIDE, DECEMBER 2010 (REV. 08/01/2014)
VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS
ARCHITECTURAL, JUNE 1, 2018
ASBESTOS ABATEMENT, JULY 2011
CMP SCHEDULE AND RISK MANAGEMENT, VOL. 1 & 2, DECEMBER 2012
ELECTRICAL, DECEMBER 2015
ENERGY SUSTAINABILITY, MAY 2014
EQUIPMENT, JANUARY 2006
ESTIMATING, MARCH 8, 2011
NFPA INTERIM GUIDANCE FOR PROJECTS, PG-18-17, SEPTEMBER 30, 2010
FIRE PROTECTION, SEVENTH EDITION REVISED DECEMBER 2015
HVAC FOR NEW, REPLACEMENT, ADD. AND REN. OF EXIST. CA FACILITIES,
NOVEMBER 2017
INTERIOR DESIGN, MAY 2008
PHYSICAL SECURITY DESIGN MANUAL, JANUARY 2015
PLUMBING, NOVEMBER 2014
STRUCTURAL, FEBRUARY 1, 2014
WAY FINDING AND SIGNAGE, INTERIOR, DECEMBER 2012
SEISMIC DESIGN REQUIREMENTS, H-18-8, AUGUST 2013
ENVIRONMENTAL PLANNING GUIDANCE PG-18-17 NEPA INTERIM GUIDELINES FOR
PROJECTS SEPTEMBER 30, 2010
ELEVATOR DESIGN MANUAL, JULY 2017
EPA GUIDELINES CHECKLIST
VA DESIGN MANUALS PG-18-10:
GOVERNING CODES:
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
DAYTON VAMC
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
VA DAYTON ENGINEERING 552-17-101
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer
DAYTON VA MEDICAL CENTER
4100 W. THIRD STREET, DAYTON, OH 45428
Mechanical, Electrical, Plumbing, Fire Protection Engineers
HEAPY ENGINEERING
1400 West Dorothy Lane Dayton OH 45409 Tel: 937-224-0861
C U s e rs
\a o g rz e w a lla \D o c u m e n ts
\1 .1
.0
B
L D
G v
A ro g rz e w a lla
.r v t
BID SET
GI103
TAAARO
THIRD FLOOR LIFE SAFETY PLAN
05/20/2019
16.1012.03BUILDING 410 EAST WING
RENOVATION
SCALE: 3/32" = 1'-0"GI103
1 LIFE SAFETY PLAN - THIRD FLOOR
UP
UP
CONTINUOUS FIRESAFE SEALANT
TOP AND BOTTOM, & BOTH SIDES
3 1/2" SOUND ATTENUATION
BATT.
5/8" TYPE X GYPSUM BOARD, BOTH
SIDES
3 5/8" METAL STUD @ 16" O.C.
WITH RUNNER CHANNELS ALONG
TOP AND BOTTOM
CONSTRUCTION
SIDE
PUBLIC
SIDE
6 MIL. FIRE RETARDANT VISQUEEN
MEMBRANE. CONTINUOUSLY
ADHERE TO THE STRUCTURAL DECK
ABOVE AND TO THE FLOOR BELOW
WITH TAPE.
UNDERSIDE OF STRUCTURAL DECK
UL LISTING:
U465
COORDINATE WITH EXISTING
CEILING
D
D
C
C
B
10 11
11A
11A
E E
D.2D.2
8A
INTAKE ROOM
CW-140
OFFICE
EW-152
OFFICE
EW-153
OFFICE
EW-154
OFFICE
EW-155
OFFICE
EW-156
POLICE HUB
EW-157
VISITATION ROOM
EW-158
DEBUG STATION
EW-141
GROUP MEETING ROOM A
EW-142 MEN'S TOILET
EW-143
WOMEN'S TOILET
EW-144 HAC
EW-145
CORRIDOR
C-1-4
OFFICE
EW-146A
COPY
EW-146B
OFFICE
EW-146C
OFFICE
EW-146D
OFFICE
EW-147
GROUP MEETING ROOM B
EW-148
GROUP MEETING ROOM C
EW-149
GROUP MEETING ROOM D
EW-150
OFFICE
EW-151
LOBBY
CW-102
NURSE STATION
CW-101
CORRIDOR
C-1-3
IT
CW-123
NIC
NIC
AA
A.6
A.7
E.2
CLOSET
CW-124
CLOSET
CW-125
CLOSET
CW-126
CORRIDOR
C-1-1
PHASE 2
TEMPORARY
PARTITON AND
ACCESS DOOR
PHASE 3
TEMPORARY
PARTITON AND
ACCESS DOOR
PHASE 3
TEMPORARY
PARTITON
PHASE 1
PHASE 1 TEMP
PARTITION AND
ACCESS DOOR
REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED
BY CLASS IN SPECIFICATION 013526 AND ADDITIONAL INFORMATION.
REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE
FOR ADDITIONAL INFORMATION.
PROJECT SHALL BE COMPLETED IN THREE PHASES.
COORDINATE FULL SCOPE OF WORK WITH CONTRACT DOCUMENTS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE
CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER
WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR
AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY
IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE
APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA
PROTOCOLS AND PLAN IS APPROVED.
SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR
AND NURSING STAFF BEFORE CONSTRUCTION MAY BEGIN. PROVIDE PHASING
INFORMATION FOR ABOVE CEILING WORK IN THE CONTRACTOR PROVIDED
CMP SCHEDULE FOR WORK ALSO REQUIRED ABOVE AND BELOW THE FLOOR
PLATE OF THE PROJECT BOUNDARY.
ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 8:00 AM
AND 5:00 PM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE
CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED IN
A SAFE MANOR UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED AND
BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.
A.
B.
C.
D.
E.
F.
G.
INFECTION CONTROL GENERAL NOTES
EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED AT
ALL TIMES. SEE SPECIFICATION FOR HOURS OF OPERATION.
WORK REQUIRING VIBRATION OR LOUD NOISE SHALL TAKE PLACE BETWEEN
THE HOURS OF 8:00 AM AND 5:00 PM. EVERY EFFORT SHALL BE MADE TO
KEEP NOISE AND VIBRATION TO A MINIMUM.
PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36" STICKY
WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR LOCATION.
MAT SHALL BE REPLACED OR CLEANED AS NECESSARY
PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH
TEMPORARY DOOR LOCATION.
CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,
MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE
LIQUIDS UP TO 30 GALLONS.
ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED WITH
4 MIL. POLY SHEET.
ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT
BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED
ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSED
WITH A LID.
ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY
STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE
MATERIALS SHALL NOT BE STORED IN THE FACILITY.
PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE
PROJECT BOUNDARY.
H.
I.
J.
K.
L.
M.
N.
O.
P.
INFECTION CONTROL PROJECT INFORMATION
CONSTRUCTION ACTIVITY - FIRE RISK: TYPE C
PATIENT RISK GROUP: LOW
CLASS OF PRECAUTION MATRIX: II
INFECTION CONTROL PLAN NOTES #
PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION PER NFPA 241. REFER TO DETAIL 2/GI104.
PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH CARD
READER ACCESS. DOOR TO BE 3/4 HOUR FIRE RATED AND SELF CLOSING.
PROVIDE TEMPORARY INFECTION CONTROL PLASTIC BARRIER WALL
CONSTRUCTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.
PHASING GENERAL NOTES
A
B
C
AREAS ADJACENT TO PROJECT AREAS TO BE OCCUPIED BY STAFF AND
VETERANS THROUGHOUT CONSTRUCTION.
PROJECT SHALL BE COMPLETED DURING TYPICAL BUSINESS HOURS, 8:00 AM
TO 5:00 PM. COORDINATE WITH COR.
REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION
FOR EACH PHASE AND AREA OF WORK.
IC/PHASING LEGEND
TEMPORARY WALLS. SEE PLAN AND
PLAN NOTES
TEMPORARY CONSTRUCTION ACCESS
DOORS
PHASE 2: OWNER TO RELOCATE LOBBY DURING
THE DURATION OF PHASE 2 AND 3 CONSTRUCTION.
CONTRACTOR TO DEMOLISH EXISTING LOBBY AND
PROVIDE NEW NURSE STATION AS INDICATED IN
CONSTRUCTION DOCUMENTS
PHASE 3: NURSE STATION TO RELOCATE TO NEW
NURSE STATION. OWNER TO RELOCATE
TECHNICIAN OFFICE. CONTRACTOR TO
DEMOLISH EXISTING NURSE STATION,
TECHNICIAN OFFICE, AND WORKROOM AND
PROVIDE NEW LOBBY AS INDICATED IN
CONSTRUCTION DOCUMENTS.
BEYOND PROJECT BOUNDARY
KEY PLAN
AREA OF WORK
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
ARCHITECT/ENGINEERS:
DAYTON VAMC
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h…
This is the start of the file's text. The full file is on GovTribe.