This federal contract opportunity notice is for the construction of a replacement community living center at a Department of Veterans Affairs medical facility. The solicitation seeks bids to furnish all labor, tools, materials and expertise to complete a minor project to construct a new community living center in accordance with contract documents, specifications and drawings. Some work may be required outside standard administrative hours or in shifts shorter than standard due to specific project items. Bids are requested through the identified solicitation number for the construction services described for Veterans Integrated Service Network 9 of the Veterans Health Administration.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NOTES:
1. REFER TO S000 SERIES FOR TYPICAL DETAILS AND GENERAL NOTES.
2. REFER TO S104 FOR ROOF FRAMING PLAN AND ROOF TRUSS GIRDER LOCATIONS.
3. REFER TO S300 SERIES FOR FRAMING DETAILS.
4. REFER TO S005 FOR WIND LOADING.
KEY NOTES:
1.
TG-H3
SNOW LOAD = 80 PLF
DEAD LOAD = 100 PLF
ROOF LIVE LOAD = 100 PLF
L
S 270
D
310 L = 30 PLF
S = 30 PLF
D = 20 PLF180
SNOW LOAD = 270 PLF
DEAD LOAD = 180 PLF
ROOF LIVE LOAD = 310 PLF
TG-H1
DEAD LOAD = 370 PLF
ROOF LIVE LOAD = 430 PLF
SNOW LOAD = 370 PLF
DEAD LOAD = 100 PLF
LIVE LOAD = 220 PLF
ROOF TRUSS GIRDER A1, A2, A3 AND A4 - LOAD DIAGRAM
DEAD LOAD = 180 PLF
SNOW LOAD = 270 PLF
LIVE LOAD = 320 PLF
TG-B
DEAD LOAD = 180 PLF
ROOF LIVE LOAD = 320 PLF
SNOW LOAD = 270 PLF
DEAD LOAD = 110 PLF
ROOF LIVE LOAD = 200 PLF
SNOW LOAD = 170 PLF
D 310 D = 60 PLF
L = 60 PLF
DEAD LOAD = 310 PLF
ROOF TRUSS GIRDER B - LOAD DIAGRAM ROOF TRUSS GIRDER C - LOAD DIAGRAM
DEAD LOAD = 290 PLF
LIVE LOAD = 40 PLF
ROOF TRUSS GIRDER D - LOAD DIAGRAM ROOF TRUSS GIRDER E - LOAD DIAGRAM
DEAD LOAD = 320 PLF
DEAD LOAD = 200 PLF
LIVE LOAD = 40 PLF
ROOF TRUSS GIRDER F1 AND F2 - LOAD DIAGRAM
DEAD LOAD = 200 PLF
ROOF TRUSS GIRDER G1 - LOAD DIAGRAM ROOF TRUSS GIRDER H1, H2 AND H3 - LOAD DIAGRAM
LVL
DEAD LOAD = 200 PLF
ROOF LIVE LOAD = 360 PLF
SNOW LOAD = 300 PLF
DEAD LOAD = 460 PLF
ROOF LIVE LOAD = 670 PLF
SNOW LOAD = 570 PLF
LIVE LOAD = 40 PLF
DEAD LOAD = 100 PLF
ROOF TRUSS GIRDER I - LOAD DIAGRAM
DEAD LOAD = 180 PLF
LIVE LOAD = 500 PLF
ROOF TRUSS GIRDER J - LOAD DIAGRAM
DEAD LOAD = 40 PLF
ROOF LIVE LOAD = 50 PLF
SNOW LOAD = 40 PLF
DEAD LOAD = 220-310 PLF
ROOF LIVE LOAD = 390 PLF
SNOW LOAD = 330 PLF
ROOF TRUSS GIRDER K - LOAD DIAGRAM ROOF TRUSS GIRDER L - LOAD DIAGRAM ROOF TRUSS GIRDER M1 AND M2 - LOAD DIAGRAM ROOF TRUSS GIRDER N - LOAD DIAGRAM
TG-Q
S = 390 PLF
D = 260 PLF
L = 460 PLF
DEAD LOAD = 210 PLF
ROOF LIVE LOAD = 350 PLF
SNOW LOAD = 300 PLF
ROOF TRUSS GIRDER O1 AND O2 - LOAD DIAGRAM ROOF TRUSS GIRDER P - LOAD DIAGRAM
DL = 460 PLF DEAD LOAD = 300 PLF
ROOF TRUSS GIRDER R - LOAD DIAGRAM
DEAD LOAD = 420-0 PLF
ROOF TRUSS GIRDER S - LOAD DIAGRAM ROOF TRUSS GIRDER T - LOAD DIAGRAM
DEAD LOAD = 70 PLF
LIVE LOAD = 370 PLF DEAD LOAD = 390 PLF
SNOW LOAD = 40 PLF
ROOF LIVE LOAD = 50 PLF
DEAD LOAD = 30 PLF
SNOW LOAD = 20 PLF
ROOF LIVE LOAD = 30 PLF
DEAD LOAD = 20 PLF
SNOW LOAD = 0-405 PLF
DEAD LOAD = 0-270 PLF
ROOF LL = 0-490 PLF DEAD LOAD = 110-220 PLF
SNOW LOAD = 170-330 PLF
ROOF LIVE LOAD = 190-390 PLF
SNOW LOAD = 40 PLF
ROOF LIVE LOAD = 50 PLF
DEAD LOAD = 30 PLF
PASSAGE FOR
ATTIC ACCESS
PASSAGE FOR
ATTIC ACCESS
IN TG-A2
SNOW LOAD = 40 PLF
ROOF LIVE LOAD = 50 PLF
DEAD LOAD = 30 PLF
LVL
PASSAGE FOR
ATTIC ACCESS
TG-C TG-E TG-G3TG-B
TG-C TG-E TG-G3
TG-G2
TG-F1 TG-F2
TG-A2 TG-A4
TG-A3TG-A1
LIVE LOAD = 690 PLF
DEAD LOAD = 70 PLF
LL = 690 PLF
DL = 70 PLF
TG-A3TG-A4
TG-A1
TG-A3
TG-A2
TG-A4
ROOF LIVE LOAD = 0 - 590 PLF
SNOW LOAD = 0 - 510 PLF
DEAD LOAD = 0 - 410 PLF
DEAD LOAD = 0 -590 PLF
COLUMN LOCATION AT TG-H3
LIVE LOAD = 690 PLF
DEAD LOAD = 70 PLF
LVL
TG-F2
ROOF TRUSS GIRDER G2 AND G3 - LOAD DIAGRAM
TG-G1 TG-H2
TG-G2 TG-G3
LVLTG-M2
DEAD LOAD = 170 PLF
LIVE LOAD = 70 PLF
TG-P
DEAD LOAD = 0-490 PLF
TG-M1 TG-M2
DEAD LOAD = 340 PLF
ROOF LIVE LOAD = 320 PLF
SNOW LOAD = 280 PLF
DEAD LOAD = 40 PLF
LIVE LOAD = 50 PLF
DEAD LOAD = 240-0 PLF
ROOF LIVE LOAD = 420-0 PLF
SNOW LOAD = 360-0 PLF
TG-S
DEAD LOAD = 150 PLF
ROOF LIVE LOAD = 250 PLF
SNOW LOAD = 210 PLF
SNOW LOAD = 40 PLF
DEAD LOAD = 30 PLF
ROOF LIVE LOAD = 50 PLF
DEAD LOAD = 250 PLF DEAD LOAD = 50 PLF
ROOF TRUSS GIRDER U1 AND U2 - LOAD DIAGRAM
DEAD LOAD = 50 PLF
SNOW LOAD = 40 PLF
DEAD LOAD = 50 PLF
ROOF LIVE LOAD = 50 PLF
ROOF TRUSS GIRDER V - LOAD DIAGRAM
DL = 70 PLF
DEAD LOAD = 70 PLF
ROOF LIVE LOAD = 110 PLF
SNOW LOAD = 100 PLF
LVL
ROOF TRUSS GIRDER W - LOAD DIAGRAM
DEAD LOAD = 460 PLF
DEAD LOAD = 260 PLF
ROOF LIVE LOAD = 460 PLF
SNOW LOAD = 400 PLF
TG-V
ROOF TRUSS GIRDER Q - LOAD DIAGRAM
DEAD LOAD = 250 PLF
DEAD LOAD = 140-300 PLF
ROOF LIVE LOAD = 250 PLF
SNOW LOAD = 220 PLF
DL = 270 PLF
LL = 220 PLF
LVL
SNOW LOAD = 40 PLF
DEAD LOAD = 30 PLFROOF LIVE LOAD = 50 PLF SL = 230 PLF
DL = 150 PLF
LL = 270 PLF
DL = 70 PLF
LL = 710 PLF
DEAD LOAD = 470 PLF
DEAD LOAD = 260 PLF
ROOF LIVE LOAD = 470 PLF
SNOW LOAD = 400 PLF
DL = 110-190 PLF
DEAD LOAD = 190 PLF
ROOF LIVE LOAD = 320 PLF
SNOW LOAD = 280 PLF
DL = 200 PLF DEAD LOAD = 230 PLF
DEAD LOAD = 320 PLF DEAD LOAD = 480 PLF
LIVE LOAD = 530 PLF
DEAD LOAD = 230 PLF
ROOF LIVE LOAD = 410 PLF
SNOW LOAD = 360 PLF
DEAD LOAD = 670 PLFDEAD LOAD = 200 PLF
LIVE LOAD = 40 PLF
SNOW LOAD = 40 PLF
ROOF LIVE LOAD = 50 PLF
DEAD LOAD = 30 PLF
SNOW LOAD = 150 PLF
LIVE LOAD = 170 PLFDEAD LOAD = 100 PLF
DEAD LOAD = 50 PLF
LIVE LOAD = 70 PLF
DEAD LOAD = 50 PLF
LIVE LOAD = 70 PLF
ROOF LIVE LOAD = 250-390 PLF
SNOW LOAD = 210-330 PLF
DEAD LOAD = 140-220 PLF
DEAD LOAD = 250-390 PLF
DL = 270 PLF
LL = 350 PLF
SL = 300 PLF
DL = 260 PLF
LL = 390 PLF
SL = 340 PLF
DEAD LOAD = 190-390 PLF
LIVE LOAD = 500 PLF
DEAD LOAD = 560 PLF
DEAD LOAD = 400 PLF
ROOF LIVE LOAD = 560 PLF
SNOW LOAD = 480 PLF
DEAD LOAD = 320 PLF
ROOF LIVE LOAD = 470 PLF
SNOW LOAD = 400 PLF
DEAD LOAD = 580 PLF
DEAD LOAD = 350 PLF
ROOF LIVE LOAD = 520 PLF
SNOW LOAD = 440 PLF
DL = 290 PLF
THP Limited, Inc.
100 E. Eighth Street, Ste. 300
Cincinnati, Ohio 45202
Phone: 513.241.3222 www.thpltd.com Cincinnati • Cleveland
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
THP JOB #19184.00
Revisions Date
/1
/2
:2
:3
P
M
Construct Replacement CLC - Long Term Rehab
2.12.2021
ROOF TRUSS DIAGRAMS
S401
JPHFJE
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
100% CONSTRUCTION DOCUMENTS 2.12.2021
ABBREVIATIONS
AC - AIR COMPRESSOR
ACC - ACCESS
AD - ACCESS DOOR
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTW N - BETW EEN
CA - COMPRESSED AIR
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CLG - CEILING
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
CW S - COMBINATION W ATER SERVICE
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DN - DOW N
DS - SPRINKLER (DRY)
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES
GPM - GALLONS PER MINUTE
HC - HVAC (D IVISION 23)
HD - HUB DRAIN
HP - HORSEPOW ER OR H IGH POINT
HR - HOSE REEL
HT - HEAT TRACE
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
JS - JANITOR SINK
L - LENGTH
LBS - POUNDS
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL (D IVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MIN - MINIMUM
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER
OFCI - OW NER FURNISHED CONTRACTOR
INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
PC - PLUMBING (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RPM - REVOLUTIONS PER MINUTE
S - SPRINKLER (W ET)
SCH - SCHEDULE
SD - SPRINKLER DRAIN
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
VEL - VELO CITY
VIB - VALVE IN BOX
VOL - VOLUME
W / - W ITH
W /O - W ITHOUT
W IV - W ALL INDICATOR VALVE
W S - W ATER SERVICE
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND
HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION
VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.
LETTER DESIG NATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH
IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
FIRE SUPPRESSION SYMBOLS
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SW ITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE W ALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING DESIGNATIONS
FIRE DEPARTMENT VALVE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE/
SPRINKLER MAIN)
FIRE SERVICE
PRE-ACTION / DELUGE SPRINKLER PIPE
SPRINKLER PIPE (W ET)
SPRINKLER DRAIN PIPE
DS
F
FS
PS
S
SD
COM MM MBINATION FIRE SUPPRESSION &
DOM ESTIC W ATER SERVICE
CW S
VALVES AND FITTINGS
T
P
FOB
FOT
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
GAUGE - PRESSURE
GAUGE - TEMPERATURE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER - W ITH A BLOW DOW N VALVE AND HOSE
CONNECTION
VALVE - DRAIN W ITH HOSE END CONNECTION
VALVE - PRESSURE REGULATING
VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERW ISE.
PLUG - PRESSURE AND TEMPERATURE TEST
TRAP PRIMER
GAUGE - VACUUM W ITH STOP
CLEANOUT - TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
W ALL HYDRANT
VALVE - PLUG
VALVE - SHUTOFF AND BOX
VALVE - SHUTOFF ON RISER
V
VB
TP
CO
VALVE - SOLENOID
S
P/T VALVE - PRESSURE AND TEM PERATURE SAFETY
RELIEF. PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERW ISE.
VALVE - CHECK
VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS)
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN
AND OUT
VALVE - COMBINATION SHUTOFF AND
BALANCING (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
EXPANSION JOINT
W ATER METERM
PIPING SYMBOLS
BOTTOM CONNEC TION (45°)
BRANCH TEE CONNECTION (NOTE :
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
PIPE RISER
BC
TC
FLEX PIPING
A PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM.
B COORDINATE W ORK W ITH VAMC, PHASING PLAN AND OTHER TRADES.
C DESIGN SERVICES SHALL FOLLOW ALL VA STANDARD DESIGN PRACTICES,
DETAILS, SPECIFICATIONS AND SITE SPECIFIC COR REQUIREMENTS AS W ELL AS
W ORK SHOW N ON THESE DOCUMENTS. ALL DEVIATIONS FROM
AFOREMENTIONED REQUIREMENTS SHALL BE APPROVED BY THE COR.
D VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING
REQUIRED TO COMPLETE THIS W ORK.
E ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM OF
STRUCTURE IN EXPOSED STRUCTURAL AREAS), UNLESS OTHERW ISE INDICATED.
F THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE
SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A W ET PIPE SYSTEM
HYDRAULICALLY CALCULATED FOR A:
1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER SPRINKLER
W ITH THE DENSITY OF 0.10 GPM/SQ. FT. OVER THE MOST REMOTE 1500 SQ.
FT. PROVIDE AN ADDITION OF 100 GPM HOSE ALLOW ANCE.
2 ALL MECHANICAL, ELECTRICAL AND SIMILAR SPACE AREAS SHALL BE
ORDINARY HAZARD (GROUP 1) LIM ITED TO A MAXIMUM OF 130 SQ. FT. PER
SPRINKLER W ITH A DENSITY OF 0.15 GPM/SQ. FT. PROVIDE AN ADDITION OF
250 GPM HOSE ALLOW ANCE.
3 ALL STORAGE, TRASH, FILE STORAGE AND SIMILAR SPACE AREAS SHALL BE
ORDINARY HAZARD (GROUP 2) LIM ITED TO A MAXIMUM OF 130 SQ. FT. PER
SPRINKLER W ITH A DENSITY OF 0.20 GPM/ SQ. FT. PROVIDE AN ADDITION OF
250 GPM HOSE ALLOW ANCE.
G PROVIDE SPRINKLER LOCATIONS AND RELATED PIPING.
H THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC STANDARDS, RULES
AND REGULATIONS. REFER TO VA FIRE PROTECTION DESIGN MANUAL.
I CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERS AND PIPING W ITH
ALL OTHER TRADES AND THE ARCHITECT.
J VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIR DEVICES BEFORE
INSTALLATION OF SPRINKLERS.
K PROVIDE SPRINKLER PIPING LAYOUT AND SIZING.
L ALL SPRINKLER LOCATIONS MUST BE COORDINATED W ITH ALL EQUIPMENT
KINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE APPROVED BY
THE ARCHITECT BEFORE W ORK COMMENCES. REFER TO THE ARCHITECTURAL
AND REFLECTIVE CEILING PLANS FOR ADDITIONAL INFORMATION ON ALL CEILING
TYPES, HEIGHTS AND OTHER ARCHITECTURAL FEATURES.
M MAKE NECESSARY FLOW TESTS, LAYOUT SYSTEMS, OBTAIN APPROVALS FROM
THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNING ANY
FABRICATION OR INSTALLATION W ORK.
N SPRINKLER PIPING SHALL BE 1" MINIMUM SIZE.
O SPRINKLERS (UNLESS OTHERW ISE NOTED):
EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASS
CEILING AREAS - RECESSED PENDENT TYPE
ALL HEADS SHALL BE UL LISTED AND FM APPROVED.
P SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS EXCEPT HIGH
TEMPERATURE AREAS.
Q ALL PENDENT TYPE SPRINKLERS LOCATED IN SUSPENDED CEILING TILE AREAS
SHALL BE LOCATED IN THE CENTER OF THE CEILING TILE.
R ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE RATED
ASSEMBLIES SHALL BE FIRE STOPPED. REFER TO SPECIFICATIONS FOR FIRE
STOPPING. REFER TO ARCHITECTURAL DRAW INGS FOR CONSTRUCTION, LAYOUT
AND FIRE RATING OF FLOORS, W ALLS, PARTITIONS AND OTHER BUILD ING
ELEMENTS.
S A FLOW TEST IS REQUIRED. REFER TO SPECIFICATION SECTION 21 13 13 FOR
FLOW TEST INFORMATION.
T ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS.
U REFER TO ARCHITECTURAL DRAW INGS FOR INFORMATION ON SMOKE
COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.
V PHASING: REFER TO ARCHITECTURAL DRAW INGS FOR AN OUTLINE OF PROJECT
PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS MAY BE INCLUDED
THROUGHOUT THIS DRAW ING SET. INCLUDE ALL LABOR AND MATERIAL TO
ACCOMMODATE PHASING.
W BID ITEMS: REFER TO ARCHITECTURAL DRAW ING AND SPECIFICATION SECTION
01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES DESCRIBING BID
ITEM DETAILS MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.
X SPRINKLER SYSTEM PIPING AND FITTINGS SHALL BE IN ACCORDANCE W ITH NFPA
13.
1 PIPING SIZES 2 INCHES AND SMALLER SHALL BE BLACK STEEL SCHEDULE 40
W ITH THREADED END CONNECTIONS.
2 PIPING SIZES 2.5 INCHES AND LARGER SHALL BE BLACK STEEL SCHEDULE 10
W ITH GROOVED CONNECTIONS. GROOVES IN SCHEDULE 10 PIPING SHALL BE
ROLLED GROOVED ONLY.
FIRE SUPPRESSION DESIGN NOTES
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:0
A
M
Construct Replacement CLC - Long Term Rehab
02.12.2021
ABBREVIATIONS, LEGEND & INDEX
OF DRAWINGS
FX001
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
INDEX OF DRAWINGS - FIRE SUPPRESSION
SHEET NUMBER SHEET NAME
FX001 ABBREVIATIONS, LEGEND & INDEX OF DRAWINGS
FX100 GROUND FLOOR PLAN
FX101 FIRST FLOOR PLAN
FX102 ATTIC PLAN
BASIS OF DESIGN FLOW TEST DATA
LOCATION: 2250 LEESTOW N ROAD, LEXINGTON, KY 40511
STATIC PRESSURE: 82 PSI
RESIDUAL PRESSURE: 38 PSI
FLOW : 2354 GPM
DATE: JUNE 24, 2019
NOTE: PERFORM HYDRAULIC CALCULATIONS UTILIZING THE BASIS OF DESIGN FLOW
TEST DATA PROVIDED TO BID THE FIRE SUPPRESSION SPRINKLER SYSTEM. UPON
AW ARD OF THE PROJECT, A HYDRANT FLOW TEST ALONG W ITH CORRESPONDING
HYDRAULIC CALCULATIONS SHALL BE PERFORMED TO VERIFY ADEQUATE PRESSURE
AND FLOW .
Revisions Date
SS
FS
F S
Rehabilitation
Media Center
Pathologist
Elec.
Storage Multi
Purpose Conference
OIT
Corridor 000A
Elevator
Lounge
MD
Superviser
Office
Assistant Nurse
Manager Office
Med Gas
Emergency Elec.
Elev. Mach. Rm .
OH
OH
OH
OH
OH
OH
Workstations
Workstations
Workstations
Director Office
Mech.
HAC
Public Toilet
Toilet - Staff
6"
F S
Nurse Manager
Office
Storage-Site Managem ent
OH
OH
OH
Biomed
FX100
4"
FROM FDC
ZONE AA
EXTEND MAIN (SIZED PER
HYDRAULIC CALCULATIONS) TO
SERVE W ET-PIPE FIRE SUPPRESSION
SPRINKLER SYSTEM IN ZONE AA
Media Center
Lobby
000B Corridor
OH
FIRE SUPPRESSION RISERS
S S
S D S
D S
S S
D S
S S
ZONE AB
EXTEND MAIN (SIZED PER
HYDRAULIC CALCULATIONS) TO
SERVE W ET-PIPE FIRE SUPPRESSION
SPRINKLER SYSTEM IN ZONE AB
S
S
S
4"
4"
4"
4" 4"
4"
4"
4"
4"
4"
Storage
OH
4 2
90 ELL PLUG
45 ELLTEE
1. UNDISTURBED EARTH SURFACE
2. CONCRETE PAD - SEE SCHEDULE
3. PLUG
4. TW O - 1.5" THICK OAK BLOCKS
PIPE
SIZE
90 ELL
45 ELL
TEE &
PLUG
3" 4" 6" 8" 10"
1.5" 2" 3" 4" 8"
1" 1" 1.5" 2" 5"
1" 1.5" 2" 8" 7"
(APPROX. ONE CU.FT. CONCRETE/SQ.FT. BEARING AREA)
EARTH BEARING AREA - SQ. FT.
NOTES
1. UNDERGROUND W ATER SERVICE.
2. UNDISTURBED EARTH-SMOOTH BEARING
FOR SUPPORTING STEEL.
3. 5" X 5" X 0.375"L-18" LONG - W ELD TO
CHANNEL/BEAM.
4. CONCRETE INSERTS - (TW O) BOLTS 0.75"
DIA. X 2.5" LONG MINIMUM.
5. STRUCTURAL STEEL SPAN SUPPORT,
TAR COATED. SEE SCHEDULE.
6. FILL CHANNEL W ITH CONCRETE MORTAR
FOR PIPE BEARING.
7. MECHANICAL RUBBER SEALING
ASSEMBLY EQUAL TO THUNDERLINK
CORP. "LINK SEAL"
8. PIPE SLEEVE W ITH W ATER STOP, OR
CORE DRILLED OPENING.
9. EXCAVATION SPAN, REFER TO
SCHEDULE.
6 5
2 5
3 4
3 FT.
BACKFILL
UNDISTURBED
EARTH
SECTION A-A
GRADE
BSMT.
FLR.
STEEL SPAN SUPPORT
EXCAVATIO N SPANPIPE
SIZE 3 FT. 5 FT. 8 FT. 12 FT.
2"
3"
4"
6"
8"
NONE
NONE
NONE
NONE
NONE
3"[-5#
4"[-5.4#
4"[-5.4#
NONE
NONE
4"[5.4#
6"[-10.5#
6"[-10.5#
6"W F-20#
6"W F-20#
4"W F-13#
4"W F-13#
6"W F-20#
6"W F-25#
6"W F-25# A
A
NOTES
Level 0 86'-4"
TO ZONE AA/AB
TO ZONE B
TO ZONE C
TO ATTIC
DRY-PIPE VALVE ASSEMBLY
4" DOUBLE CHECK
DETECTOR ASSEMBLY
SV
(TYP.)
FS (TYP.)
4"4" 4"4"
FROM FDC
4"
FIRE SERVICE
2'
FLOW
SW ITCH
(TYP.)
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:1
A
M
Construct Replacement CLC - Long Term Rehab
02.12.2021
GROUND FLOOR PLAN
FX100
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
N Scale: 1/8" = 1'-0"1
GROUND FLOOR PLAN - BUILDING 205
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET FX001 FOR ABBREVIATIONS, LEGEND, & INDEX OF DRAW INGS.
SCALE: NONE
UNDER GROUND WATER PIPE THRUST BLOCKS
A
SCALE: NONE
WATER SERVICE SUPPORT
B
1. FIRE SERVICE ENTRANCE - REFER TO DETAIL '2' FOR ADDITIONAL INFORMATION.
2. EXTEND SPRINKLER MAIN (SIZED PER HYDRAULIC CALCULATIONS) TO SERVE
W ET-PIPE FIRE SUPPRESSION SPRINKLER SYSTEM THROUGH-OUT ENTIRE NEW
BUILDING EXCEPT FOR THE ATTIC W HICH W ILL BE PROVIDED W ITH A DRY PIPE SYSTEM.
3. ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE ALLOW ED
ABOVE THIS ROOM.
4. PROVIDE SIDEW ALL SPRINKLER IN THE ELEVATOR PIT LOCATED NO MORE THAN 2 FEET
ABOVE THE PIT.
5. PROVIDE SUPERVISED VALVE TO ISOLATE SPRINKLERS SERVING THIS ROOM.
6. LOCATION OF PATIENT LIFT, NO SPRINKLERS SHALL BE LOCATED BETW EEN SIDE
RAILS, BELOW MOVEABLE LIFT RAIL OR MOTOR.
7. PROVIDE ORDINARY OR INTERMEDIATE TEMPERATURE SPRINKLERS IN THE ELEVATOR
MACHINE ROOM.
8. PROVIDE SEPARATE SPRINKLER ZONES TO SERVE EACH SIDE OF SMOKE BARRIER
INDIVIDUALLY ON GROUND FLOOR (TOTAL OF 2 SPRINKLER ZONES).
9. DRY PIPE SPRINKLER SYSTEM AIR COMPRESSOR. AIR COMPRESSOR SHALL COMPLY
W ITH NFPA STANDARDS AND INSTALLED PER MANUFACTURER'S INSTALLATION
REQUIREMENTS.
SCALE: NONE
FIRE SERVICE ENTRANCE
Elevator
Equipm ent
HAC
121Supplies
Med Room
Workroom, Resident
Soiled Holding
Clean Linen
Laundry
Bathing
Den
Bedroom
Bedroom
Bedroom
Bedroom
Bath
108B
Bath
107B
Bath
106B
Bath
105B
Special Care Bedroom
Bath 109B
Special Care Bedroom
Bath
110B
Bedroom
Bath
101B
Bedroom
Bath
102B
Bedroom
Bath
103B
Kitchen 116 Dining
Corridor
100B
IT
Bedroom
Bath
104B
Living
Storage
Public Restroom
Consult
Bedroom
Bath 107B
Bedroom
Bath
108B
Bath
109B Bedroom
Bedroom
Bath 110B
Corridor
100D
IT
Vestibule
Den
Public Toilet
Bath 101B
Bedroom
Bedroom
Bath 102B
Bath
103B
Bedroom
Bedroom
Bath
104B
Supplies
Special Care Bedroom
Special Care Bedroom
Bath 105B
Bath
106B
Soiled Holding
Clean Linen
Laundry
HAC
4 5
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
4 5 4 5 4 5
4 54 54 54 5
4 5
4 5
4 5
4 5
4 5
4 5
4 5
4 5
4 5
4 54 5
4 5
OH
4 5
4 5
4 5
4 5
4 5
4 54 5
4 5
4 5
4 5
4 5
4 5
4 5
4 5
4 4 5
4 5
OH
118B Storage
OH
Dining
Kitchen
Workroom , Resident
100B Corridor
Bathing Suite
Pantry
Living
Electric
Med R oom
Consult
Reception
Garage/Receiving
118C Storage
Screen Porch
OH
OH
OH
Pantry
Screen Porch
4 5
OH
ZONE B
ZONE C
EXTEND MAIN (SIZED PER
HYDRAULIC CALCULATIONS) TO
SERVE W ET-PIPE FIRE SUPPRESSION
SPRINKLER SYSTEM IN ZONE C
EXTEND MAIN (SIZED PER
HYDRAULIC CALCULATIONS) TO
SERVE W ET-PIPE FIRE SUPPRESSION
SPRINKLER SYSTEM IN ZONE B
100C Corridor
FIRE SUPPRESSION R ISER
S S
S
OH
DRY-SPRINKLER SYSTEM
UP TO ATTIC.
4" 4"
4"
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:4
A
M
Construct Replacement CLC - Long Term Rehab
02.12.2021
FIRST FLOOR PLAN
FX101
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
N Scale: 1/8" = 1'-0"1
FIRST FLOOR PLAN - BUILDINGS 204 & 205
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET FX001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. EXTEND SPRINKLER MAIN (SIZED PER HYDRAULIC CALCULATIONS) TO SERVE
W ET-PIPE FIRE SUPPRESSION SPRINKLER SYSTEM THROUGH-OUT ENTIRE NEW
BUILDING IN SPRINKLER ZONE C .
2. EXTEND SPRINKLER MAIN (SIZED PER HYDRAULIC CALCULATIONS) TO SERVE
W ET-PIPE FIRE SUPPRESSION SPRINKLER SYSTEM THROUGH-OUT ENTIRE NEW
BUILDING IN SPRINKLER ZONE B.
3. ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE ALLOW ED
ABOVE THIS ROOM.
4. GYPSUM BOARD/ PLASTER/ W OOD CEILING.
5. LOCATION OF PATIENT LIFT, NO SPRINKLERS SHALL BE LOCATED BETW EEN SIDE
RAILS, BELOW MOVEABLE LIFT RAIL OR MOTOR.
6. SERVE SCREENED PORCHES/ PORTE COCHERE/ GARAGE W ITH DRY-PENDENT TYPE
OR DRY-SIDEW ALL TYPE SPRINKLERS.
7. KITCHEN COOKTOP HOOD LOCATION.
Revisions Date
Building 204
Building 205
T
EXTEND MAIN (SIZED PER
HYDRAULIC CALCULATIONS) TO
SERVE DRY-PIPE FIRE SUPPRESSION
SPRINKLER SYSTEM IN ATTIC
Mechanical Space
Mechanical Space
UP FROM BELOW .
D S
4"
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:4
A
M
Construct Replacement CLC - Long Term Rehab
02.12.2021
ATTIC PLAN
FX102
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET FX001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. PROVIDE DRY-PIPE SPRINKLER SYSTEM IN UNCONDITIONED ATTIC AREA.
N Scale: 1/8" = 1'-0"1
ATTIC PLAN - BUILDING 204 & 205
Revisions Date
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID W ASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTW N - BETW EEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED W ATER SUPPLY
CHR - CHILLED W ATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT W ATER
CTR - CENTER
CU - COPPER
CW - COLD W ATER
CW S - COMBINATION W ATER SERVICE
OR CONDENSER W ATER SUPPLY
CW R - CONDENSER W ATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR W ATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIONIZED W ATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOW N
DS - DOW N SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DW G - DRAW ING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EEW - EMERGENCY EYE W ASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOW ER
EQS - EQUIPMENT SUPPLIER
EW C - ELECTRICAL W ATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER
MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE W ASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOW ER OR HIGH POINT
HPC - H IGH PRESSURE CONDENSATE RETURN
HPS - H IGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY W ATER
HPW R - HIGH PURITY W ATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR
CONDITIONING
HW - HOT W ATER
HW R - HEATING HOT W ATER RETURN
HW S - HEATING HOT W ATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT W ASTE
JS - JANITOR SINK
K - KITCHEN W ASTE
KEC - KITCHEN EQUIPMENT
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD W ATER
LEC - LABORATORY EQUIPMENT
LHW - LABORATORY HOT W ATER
LHW R - LABORATORY HOT W ATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY
VENT
LW - LABORATORY W ASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MIN IMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - W ATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL N ITROGEN
N/C - NORMALLY CLOSED
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NO - MEDICAL N ITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE W ATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
O2 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW
DRAIN
OFCI - OW NER FURNISHED CONTRACTOR
INSTALLED
OFOI - OW NER FURNISHED OW NER INSTALLED
P - PROPANE GAS
PC - PLUMBING (DIVISION 22) OR PUMPED
CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE W ATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS W ATER SUPPLY
ROR - REVERSE OSMOSIS W ATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (W ET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD W ATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOW ER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR W ASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER
DISCHARGE
TW - TEMPERED W ATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERW ISE
V - VENT OR SANITARY SEW ER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELO CITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W / - W ITH
W /O - W ITHOUT
W - W ASTE
W AGD - W ASTE ANESTHESIA GAS DISPOSAL
W C - W ATER CLOSET
W CO - W ALL CLEANOUT
W H - W ALL HYDRANT OR W ATER HEATER
W IV - W ALL INDICATOR VALVE
W S - W ATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS. ADDITIONALLY, ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND
HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION
VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.
LETTER DESIG NATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH
IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
FIRE SUPPRESSION SYMBOLS
SPRINKLER - CONCEALED PENDENT
FS
PIV
S
FIRE HYDRANT
FLOW SW ITCH
VALVE - GATE OS&Y
SPRINKLER - INSTITUTIONAL PENDENT
SPRINKLER - PENDENT
VALVE - POST INDICATOR
SPRINKLER - RECESSED PENDENT
SPRINKLER - SIDE W ALL
VALVE - SUPERVISED
SPRINKLER - UPRIGHT
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - W ALL
VACUUM CLEANING STATION - FLOOR
PIPING DESIGNATIONS
DOMESTIC COLD W ATER
DOMESTIC HOT W ATER
DOMESTIC HOT W ATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT W ATER PIPE (140 DEGS. F.)
HOT W ATER RETURN PIPE (140 DEGS. F.)
HOT W ATER RETURN PIPE (180 DEGS. F.)
140R
180R
EXPANSION JOINT
VALVE - FIRE DEPARTMENT
W ATER METERM
PIPING SYMBOLS
BOTTOM CONNEC TION (45°)
BRANCH TEE CONNECTION (NOTE :
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
PIPE RISER
HOT W ATER PIPE (180 DEGS. F.)
ARGO N PIPE
COMPRESSED AIR PIPE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
KITCHEN W ASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY W ASTE PIPE
GASOLINE PIPE (NON-LEAD)
NON-POTABLE
(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE W ATER PIPE
SPRINKLER PIPE (W ET)
SANITARY DRAINAGE PIPE
SOFT COLD W ATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARG E PIPE
TEMPERED W ATER PIPE
SANITARY SEW ER VENT
W ATER SERVICE
LV
AR
CA
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IV
IW
LA
LV
LW
NG
NPW
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
W S
INDIR ECT VEN T PIPE
INDIRECT W ASTE PIPE
K
ACID VENT PIPEAV
ACID W ASTE PIPEAW
BC
TC
COM BINATION FIRE SUPPRESSION &
DOM ESTIC W ATER SERVICE
CW S
FLEX PIPING
CAR BON DIOXIDE OUTLET - H OSPITAL TYPE
M EDIC AL AIR OU TLET - HOSPITAL TYPE
M EDIC AL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - H OSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OU TLET - HOSPITAL TYPE
W AGD INLET - HOSPITAL TYPE
M EDICAL INSTRUM ENT AIR PIPE
M EDICAL NITR OGEN PIPE
M EDIC AL COM PRESSED AIR PIPE
MEDICAL SURGICAL VACUUM-EXHAUST PIPE
MEDICAL NITROUS OXIDE PIPE
MEDICAL OXYGEN PIPE
W ASTE ANESTHESIA GAS DISPOSAL PIPE
IA
N2
MA
MV
NO
O2
W AGD
MEDICAL CARBON DIOXIDE PIPECO2
MEDICAL SURGICAL VACUUM PIPE
MEDICAL COMPRESSED AIR-INTAKE PIPEMA-IN
MV-EX
VALVES AND FITTINGS
T
P
FOB
FOT
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
GAUGE - PRESSURE
GAUGE - TEMPERATURE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER - W ITH A BLOW DOW N VALVE AND HOSE
CONNECTION
VALVE - DRAIN W ITH HOSE END CONNECTION
VALVE - PRESSURE REGULATING
VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERW ISE.
PLUG - PRESSURE AND TEMPERATURE TEST
TRAP PRIMER
GAUGE - VACUUM W ITH STOP
CLEANOUT - TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
W ALL HYDRANT
VALVE - PLUG
VALVE - SHUTOFF AND BOX
VALVE - SHUTOFF ON RISER
V
VB
TP
CO
VALVE - SOLENOID
S
P/T VALVE - PRESSURE AND TEM PERATURE SAFETY
RELIEF. PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERW ISE.
VALVE - CHECK
VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS)
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN
AND OUT
VALVE - COMBINATION SHUTOFF AND
BALANCING (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
GENERAL NOTES
A ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN
EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.
B REFER TO SCHEDULES, DETAILS AND D IAGRAMS FOR PIPING, PIPE SIZES AND
PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL TRADES IS
CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.
D REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING
REQUIREMENTS.
E REFER TO ARCHITECTURAL FIRE RATED PARTITION PLAN(S) FOR LOCATIONS
AND FIRE RATINGS OF NEW W ALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE
RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRE STOPPED AS REQUIRED TO
MAINTAIN FIRE RATINGS INDICATED. COORDINATE W ITH ALL TRADES TO ENSURE
FIRE RATED PENETRATION REQUIREMENTS AND DETAILS ARE MET.
F ANNULAR SPACE OF ALL PIPE & OTHER SIMILAR PENETRATIONS OF FIRE RATED
ASSEMBLIES SHALL BE FIRE STOPPED.
G PHASING: REFER TO ARCHITECTURAL DRAW INGS FOR AN OUTLINE OF PROJECT
PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS MAY BE INCLUDED
THROUGHOUT THIS DRAW ING SET.
H BID ITEMS: REFER TO ARCHITECTURAL DRAW ING AND SPECIFICATION SECTION
01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES DESCRIBING BID
ITEM DETAILS MAY BE INCLUDED THROUGHOUT THIS DRAW ING SET.
I OXYGEN AND MEDICAL AIR PIPING SHALL BE MINIMUM 0.5" SIZE. MEDICAL VACUUM
PIPING SHALL BE MINIMUM 0.75" S IZE.
J ALL MEDICAL GAS SYSTEM INSTALLERS SHALL BE CERTIFIED TO THE
REQUIREMENTS OF ASSE 6010. ALL MEDICAL GAS SYSTEM VERIFIERS SHALL BE
CERTIFIED TO THE REQUIREMENTS OF ASSE 6030.
K MEDICAL GAS SYSTEM INSTALLATION AND VERIFICATION SHALL COMPLY W ITH THE
REQUIREMENTS OF NFPA 99, GAS AND VACUUM SYSTEMS.
L DOMESTIC W ATER PIPING SYSTEM SHALL BE DISINFECTED AND TESTED IN ITS
ENTIRETY. DISINFECTION AND TESTING PROCEDURES SHALL FOLLOW LEXINGTON VA
W ATER SAFETY PLAN AND ALL OTHER VA DESIGN MANUAL, VA SPECIFICATIONS, AND
LOCAL REQUIREMENTS.
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:2
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
ABBREVIATIONS, LEGEND & INDEX
OF DRAWINGS
P001
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
INDEX OF DRAWINGS - PLUMBING
SHEET NUMBER SHEET NAME
P001 ABBREVIATIONS, LEGEND & INDEX OF DRAWINGS
PS100 SITE PLAN - PLUMBING UTILITIES
PL099 FOUNDATION PLAN - DRAINAGE
PL100 GROUND FLOOR PLAN - DRAINAGE
PL101 FIRST FLOOR PLAN - DRAINAGE
PL102 ATTIC PLAN
PP100 GROUND FLOOR PLAN - DISTRIBUTION
PP101 FIRST FLOOR PLAN - DISTRIBUTION
P501 DETAILS
P601 SCHEDULES & DIAGRAMS
P901 SOIL, WASTE &VENT DIAGRAM
P902 SOIL, WASTE &VENT DIAGRAM
Down
Down
F D
FD
C O
C O
C O
C O
C O
C O
C O
C
OC
O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
C O
S
C O
C O
O2
8' CHAIN LINK FENCE WITH BARBED WIRE
G A
T E
VI
P
VI
P
W
CDF
W S
T
G E
N
E
E H
TEST-Y & CO
TEST-Y & CO
O
1"
2" 3"
4"
6"
PROPOSED BLDG.
FF: 918.50'
S A
N
F S
F S
W S
6"
6 7
P
1"
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:0
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
SITE PLAN - PLUMBING UTILITIES
PS100
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
N Scale: 1" = 20'-0"1
SITE PLAN - PLUMBING
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBR EVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. EXISTING BULK OXYGEN TANK.
2. NEW ABOVEGROUND PROPANE TANK(S).
BASIS OF DESIGN: FERRELGAS
CONTACT: SABRA OLLER - (502) 523-8506
3. PROVIDE GAS METER AND REGULATOR. OPERATING PRESSURE SHALL BE SET TO 2 PSI.
4. PROVIDE ADAPTOR AND CONNECT TO STUB PROVIDED BY S.U.C.
5. APPROXIMATE LOCATION OF FIRE DEPARTMENT CONNECTION AND POST INDICATOR
VALVE BY S.U.C.
6. PIPING CONTINUED ON SHEET PP100.
7. PIPING CONTINUED ON SHEET PL100.
P609
P103
P103
P502
P524
CO
P418
P418
SAN
S A
N
SAN
1.5" VR
FD2
FD2
FD3
FD3
SE1
FD3
SP1
UP4" PD
UP2" PD
D
INV: 902' - 4 9/32"
INV: 902' - 4 5/16"
2" VR
2" VR
G
P501
J
P501
2" VR
P419
P419
CO
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:5
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
FOUNDATION PLAN - DRAINAGE
PL099
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBR EVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. ELEVATOR SUMP PUMP. REFER TO DETAIL J/ SHEET P501.
2. SEW AGE EJECTOR. REFER TO DETAIL G/ SHEET P501.
N Scale: 1/8" = 1'-0"1
FOUNDATION PLAN - DRAINAGE - BUILDING 205
Rehabilitation
Media Center
Pathologist
Elec.
Storage Multi
Purpose Conference
Mech.
OIT
Corridor
000A
Elevator
Lounge
Workstations
Workstations
MD
Superviser
Office
Assistant Nurse
Manager Office
Workstations
Director Office
Emergency Elec.
Elev. Mach.
Rm.
S A
N
V
V
V
S A
N
SAN
SAN
S A
N
Nurse Manager
Office
SP1
P103
P103
P524
P418 P418
P609 P502
SE1
Public Toilet
HAC
Toilet - Staff
Biomed
Storage-Site Managem ent
000B Corridor
P103
P418
P418 P103
FD1
FD1
P103
FD1
P418 P103
FD1
P418
P103
FD1
P502
P418
P524
P418
P103
FD1
P808
P103 P418
FD1
FD1
P103
FD1
FD1
P103 P418
P418
P103
FD1
FD1
P418
FD1 FD1
P418
P103
P524
P502
P103
P418
FD1 FD1
P103
P418
P521
P418
P103 P418
FD1
FD1
P103 P418
FD1
FD1
P103 P418
(2)
(2)(2)
(2)
2" VR
1.5" VR
2" VR
(2)
(2)
(2) (2)
P103 P418
P103
2" VR
P418
2" VR
CO
CO
CO
2" VR
2" VR2" VR
FD2
P418
2" VR
2" VR
P528
P521
P526
P419
S A
N
SAN
P103
CO
CO
CO
P526
P419
P808
FD2
P301 P103
SAN
S A
N
S A
N
SAN
SAN SAN
S A
N
SAN
S A
N
P301
P528
2" VR
2" VR
1.5" VR
2" VR
2" VR
2" VR
CO
CO
2" VR
CO
2" VR 2" VR
2" VR
2" VR2" VR
2" VR
FD2
FD2
FD3
FD3
FD2
FD3
1.5" VR
FD2
UP2" PD
FD3
FD3
1.5" VR
UP3" SAN
PD
1FD3
FD3
UP3" V
UP3" SAN
UP3" SAN
FD3
1.5" VR
FD3
MVP1
W S1
INV: 904' - 11"
INV: 916' - 4"
D
D
1 .5" VR
DD
(P301)
(P301)
CO
D
SAN
SAN
SAN
SAN
V SAN
2" VR
CO
CO
SAN
MAC1
2" VR
J
P501
2" VR
UP6" W H-INT
UP8" W H-EXH
(TYP.)
(TYP.)
W H
-I N
T
W H
-E X
H
Med Gas
1.5" VRP419
P419
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:0
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
GROUND FLOOR PLAN - DRAINAGE
PL100
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. PROVIDE STAINLESS STEEL DRAIN PAN BELOW SANITARY PIPING. EXTEND PAN
DISCHARGE TO MOP SINK IN HAC RM 101.
2. FIXTURE SHALL BE VENTED BY A COMBINATION W ASTE AND VENT SYSTEM.
3. PROVIDE SUMP PUMP ALARM AND CONTROL PANEL. COORDINATE LOCATION AND
REQUIREMENTS W ITH DIVISION 26.
4. PROVIDE SEW AGE EJECTOR ALARM AND CONTROL PANEL. COORDINATE LOCATION AND
REQUIREMENTS W ITH DIVISION 26.
N Scale: 1/8" = 1'-0"1
GROUND FLOOR PLAN - DRAINAGE
Revisions Date
C O
CO
C O
Elevator
Equipm ent
HAC
Supplies
Med Room
Workroom, Resident
Soiled Holding
Clean Linen
Laundry
Bathing
Den
Bedroom
Bedroom
Bedroom
Bedroom
Bath 108B
Bath 107B
Bath
106B
Bath 105B
Special Care Bedroom
Bath
109B
Special Care Bedroom
Bath
110B
Bedroom
Bath 101B
Bedroom
Bath
102B
Bedroom
Bath
103B
Kitchen
Dining
Corridor 100B
Bedroom
Bath
104B
Living
Storage
Public Restroom
Consult
Bedroom
Bath
107B
Bedroom
Bath
108B
Bath
109B
Bedroom
Bedroom
Corridor 100D
IT
Vestibule
Den
Public Toilet
Storage
118B
Bedroom
Bedroom
Bedroom
Bedroom
Supplies
Special Care Bedroom
106Special Care Bedroom
Bath
106B
Soiled Holding
Clean Linen
Laundry
HAC
3" VR
V
V
V
V V
V
V
V
VV
V
V
V
V
VV
V V
V
V V
V
V V
V V V
V V
Garage/Receiving
118C Storage
Consult
Screen Porch
Pantry
Living
Kitchen
Med R oom
Workroom , Resident
Bathing Suite
Dining
Electric
Reception
Screen Porch
Pantry
P103
P418
P418 P103
P301
P103 P418
P418
P103
P418
P502
P418 P103
P103
P418
P524
P418
P103
P103 P418
P103 P418
P418 P103
P808
P521
P528
P103 P418
P418
P103
P418
P103
P418
P103
P418
P103
P103 P418
P524
P528
P502
P103
P418
P103
P418
P301 P418
FD2
P419
P521
P103 P418
P103 P418
P418 P103
P103 P418
FD2
P103
P808
P526
103B Bath
102B Bath
101B Bath
P103
UP3" V
UP3" V
2" VR
FD3
1.5" VRV
FD2
FD2
DN2" PD
P419
FD3
FD3
Equipm ent
TEST-Y & CO
TEST-Y & CO
FD3 1.5" VR
FD3
FD3
FD3
1.5" VR
1.5" VR
1.5" VR
2" VR
DN3" SAN
DN3" SAN
2" VR
2" VR 2" VR 2" VR
2" VR
2" VR
2" VR
2" VR
2" VR
2" VR
2" VR
2" VR
2" VR
2" VR2" VR
2" VR
2" VR
2" VR
2" VR
DN3" SAN
P526
FD3
FD3
CO
CO
CO
CO
FD1 FD1 FD1 FD1
FD1
FD1
FD1
FD1
FD1 FD1
FD1
FD1
FD1
FD1
FD1FD1
FD1
FD1
FD1
FD1
1.5" VR
V
2" VR
UP & DN6" W H-INT
UP & DN8" W H-EXH
(TYP.)
(TYP.)
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:2
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
FIRST FLOOR PLAN - DRAINAGE
PL101
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. EXTEND SUMP PUMP PUMPED DRAINAGE PIPING TO EXTERIOR. PROVIDE DOW NTURNED
ELBOW TO SPLASHBLOCK. PROVIDE SLEEVE THROUGH W ALL W ITH W ATERTIGHT SEAL.
N Scale: 1/8" = 1'-0"1
FIRST FLOOR PLAN - DRAINAGE
Revisions Date
3" VTR
3" VTR
FD3
FD3
FD3
3" VTR
1.5" VR
V
3" VTR
P802
P802
Mechanical Space
Mechanical Space
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:2
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
ATTIC PLAN
PL102
DesignerApprover
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
N Scale: 1/8" = 1'-0"1
ATTIC PLAN - DRAINAGE & DISTRIBUTION
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
1. PROVIDE 1" STUB FOR HVAC EQUIPMENT. PIPING TO BE CONTINUED/ COORDINATED BY
DIV 23.
2. 3" MEDICAL AIR INTAKE. TURN DOW N W ITH GOOSENECK FITTING AND PROVIDE BUG
SCREEN. EXTEND PIPING THROUGH ATTIC AND TERMINATE ABOVE ROOF ON BACK
SIDE OF BUILDING. COORDINATE LOCATION W ITH ALL HVAC EXHAUST DUCTS/ FANS
AND SANITARY ROOF VENTS TO BE A MINIMUM DISTANCE OF 25' FROM AIR INTAKE.
3. 3" VACUUM EXHAUST. TURN DOW N W ITH GOOSENECK FITTING AND PROVIDE BUG
SCREEN. EXTEND PIPING THROUGH ATTIC AND TERMINATE ABOVE ROOF ON BACK
SIDE OF BUILDING. COORDINATE LOCATION W ITH ALL HVAC AIR INTAKES. TO BE A
MINIMUM OF 25' FROM EXHAUST VENTING.
4. W ATER HEATER INTAKE - EXHAUST PIPING. EXTEND PIPING THROUGH ATTIC AND
TERMINATE ABOVE ROOF ON BACK SIDE OF BUILDING. REFER TO D IVISION 23
DRAW INGS FOR APPROXIMATE ROUTE. INTAKE PIPING SHALL BE TURNED DOW N
ABOVE ROOF W ITH GOOSENECK FITTING AND PROVIDE BUG SCREEN. REFER TO
DETAIL I/ P501.
Revisions Date
M B
F P
B F
P
PP100
Rehabilitation
Pathologist
Elec.
Storage Multi
Purpose Conference
Mech.
OIT
Corridor
000A
Elevator
Stair
Lounge
Workstations
MD Superviser Office
Assistant Nurse
Manager Office
Med Gas
Workstations
Director Office
Emergency Elec.
Elev. Mach.
Rm.
SLAB ON GRADE
P103
P103
P524
P418
P418
P609
P502
P801
P812
Nurse Manager
Office
Workstations
Public Toilet
HAC
Toilet - Staff
3"
W S
Biomed
000B Corridor
Storage-Site Managem ent
MVP1
0.5" - DHW
0.5" - DCW
P801
Media Center
0.5 GPM
UP0.5" DCW
UP0.5" DHW
0.75"
2"
M V
1"
1"
2"
2.5"
UP1" MV
UP1" DHW RUP2" DHW
UP2.5" DCW
0.75"
2"
2"
0.5"
2" 1"0.75"0.5"1"
1"
O
G S
MAC1
1"
1"
1"
MA
M A
M A
3"
G
2"
SE1
ET1
P524
UP1" MA
P524
4 4 4
P601
MAP
W S1
DW H1 DW H1 DW H1
1"
P
General Storage
MV
2.5" 2" 1"
M V
-E X
H
0.75"
0.75"
P419
P419
Level 0 86'-4"
3"
W S
D C
W
3"
BFP
BFP
3" 3"
3'
W ATER METER
Mech.
N.C.
W ATER METER BY-PASS
SUPPORT BRACKET
ANCHOR TO W ALL.
N.C.
80 MESH
STRAINER
P: 937-224-0861 www.heapy.com
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Departm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
PROJECT NO.
100% CONSTRUCTION DOCUMENTS 02.12.2021
/1
/2
:4
:3
P M
Construct Replacement CLC - Long Term Rehab
02.12.2021
GROUND FLOOR PLAN -
DISTRIBUTION
PP100
RLCKMB
596-333
Lexington, Kentucky
204 & 205
100% CONSTRUCTION
DOCUMENTS
19009.00
2019-05137
GENERAL NOTES
PLAN NOTES
A. REFER TO SHEET P001 FOR ABBREVIATIONS, LEGEND & INDEX OF DRAW INGS.
N Scale: 1/8" = 1'-0"1
GROUND FLOOR PLAN - DISTRIBUTION
1. BOX MOUNTED TRANSFORMER LO CATED ABOVE THE CEILING TO CONTROL SENSOR
OPERATED FAUCET ON FIXTURE(S) BELOW . 120V-1PH POW ER W ILL BE LOCATED IN A
W IR ING BOX ABOVE THE CEILING BY DIVISION 26. A 0.75” CONDUIT (FOR LOW VOLTAGE
W IR ING) STUBBED ABOVE THE CEILING AND EXTENDED DOW N TO AN ELECTRICAL W ALL
BOX LOCATED BELOW EACH LAVATORY W ILL BE PROVIDED BY DIVISION 26. THE
TRANSFORMERS AND LOW VOLTAGE W IRING SHALL BE BY DIVISION 22. COORDINATE ALL
W ORK W ITH DIVISION 26.
2. BOX MOUNTED TRANSFORMER LO CATED ABOVE THE CEILING TO CONTROL SENSOR
OPERATED FLUSH VALVE ON FIXTURE(S) BELOW . 120V-1PH POW ER W ILL BE LOCATED IN
A W IR ING BOX ABOVE THE CEILING BY DIVISION 26. A 0.75” CONDUIT (FOR LOW VOLTAGE
W IR ING) STUBBED ABOVE THE CEILING AND EXTENDED DOW N TO AN ELECTRICAL W ALL
BOX LOCATED ABOVE EACH W ATER CLOSET W ILL BE PROVIDED BY DIVISION 26. THE
TRANSFORMER AND LOW VOLTAGE W IRING SHALL BE BY DIVISION 22. COORDINATE ALL
W ORK W ITH THE DIVISION 26.
3. 3" MEDICAL AIR INTAKE/ VACUUM EXHAUST UP.
4. CONNECT TO EQUIPMENT PER MANUFACTURERS REQUIREMENTS.
5. NO PIPING SHALL BE INSTALLED IN THIS SPACE.
6. PROVIDE GAS REGULATOR FOR EACH W ATER HEATER. OPERATING PRESSURE SHALL
BE SET AT 11" W .C.
SCALE: 1/4" = 1'-0"
WATER SERVICE ENTRANCE
Revisions Date
F D
FD
BFP
BFP
Elevator
Stair
Equipm ent
HAC
Supplies
Med Room
Workroom, Resident
Soiled Holding
Clean Linen
Laundry
Bathing
Den
Bedroom
Bedroom
Bedroom
Bedroom 108Bath
108B
Bath
107B
Bath
106B
Bath
105B
Special Care Bedroom
Bath
109B
Special Care Bedroom
Bath
110B
Bedroom
Bath
101B
Bedroom
Bath
102B
Bedroom
Bath
103B
Kitchen
Dining
Corridor
100B
Bedroom
Bath
104B
Living
Storage
Public Restroom
Consult
Bedroom
Bath
107B
Bedroom
Bath 108B
Bath
109B
Bedroom
Bedroom
Bath
110B
Corridor
100D
IT
Vestibule
Den
Public Toilet
Bath
101B
Bedroom
Bedroom
Bath
102B
Bath
103B
Bedroom
Bedroom
Bath
104B Supplies
Special Care Bedroom
Special Care Bedroom
Bath 105B Bath
106B
Soiled Holding
Clean Linen
Laundry
HAC
P103 P418
P701
P103
P418
P701
P103 P418
P701
P103
P418
P701
P103 P418
P701
P103 P418
P701
P103
P418
P701 P103
P418
P701
P103
P418
P701 P103
P418
P701
P103
P418
P701 P103
P418
P701
P103 P418
P701
P103
P418
P701
P103
P418
P701
P103 P418
P701
P103
P418
P701
P103P418
P701
P103P418
P701
P103
P418
P701
P524 P418
P528
P528
P524
P502
P418
P418
P418
P103
P103
P419
P521
P521
P808
P812
P812
P801
P801
P801
P801
P502
P809
P809
1"
2"
1"
ZVC,AAP
2" 2.5"
2.5" 2" 1"
0.75" 0.5"
0.75" 0.5"
MAP
1.25"
2"
0.5" 0.75"
1"
2"
1"
2"
0.5"
0.75"
0.5" 0.75"
1"2"
1"
0.75" 0.5"
0.5"
0.75"
0.5" 0.75"
0.75" 1"1"
2"2.5" 1.5"
0.5"
0.75"
Pantry
Screen Porch
Reception
Screen Porch
Consult
Garage/Receiving
Living
Kitchen
Pantry
Workroom , Resident
Electric
Med Room
EOSC
M V
O
O2
MV
O2 O2
MV
O2
MV
O…