36C24818Q0491-013.pdf
PDF 924 KB Posted
- Attached to
- Services: Repair Active Vehicle Barriers Federal contract opportunity
- Solicitation number
- 36C24818Q0491
About this file
36C24818Q0491 ATTACHMENT B CLC Loading Dock Receiving Area-.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24818Q0491-00001000.docx | DOCX document | |
| 36C24818Q0491-00001001.docx | DOCX document | |
| 36C24818Q0491-009.pdf | ||
| 36C24818Q0491-011.pdf | ||
| 36C24818Q0491-002.docx | DOCX document | |
| 36C24818Q0491-004.pdf | ||
| 36C24818Q0491-005.pdf | ||
| 36C24818Q0491-010.pdf | ||
| 36C24818Q0491-008.pdf | ||
| 36C24818Q0491-012.pdf | ||
| 36C24818Q0491-006.pdf | ||
| 36C24818Q0491-003.pdf | ||
| 36C24818Q0491-007.pdf | ||
| 36C24818Q0491-001.docx | DOCX document | |
| 36C24818Q0491-000.docx | DOCX document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Monday, January 29, 2018
10:03 PM
CLC Loading Dock Box style Cantilever Gate 45’ with 25’ opening Viking Access Systems Model L-3 S/N 0210-S3B-17341
- Condition Found: Operator is severely damaged and weatherized. It is full of debris and sand.
(See Pictures below). Motor seized and inoperable power was tested and is correct voltage for unit.
- Action: Replace with new HySecurity Slide Driver Like others on campus use nickel plated chain to ensure trouble free operations
- Condition Found: 1 @ 5’ Millers Safety was damaged after the gate contract was awarded. (See
Figure 2 Below)
- Action: Replace Safety Edge and transmitter/Receiver pair gate to bring up to UL325 standard and ensure safe gate operation
- Condition Found: Photo Beam not operational
- Action: Replace with new photo beam to ensure safe operations
Condition Found: Gate its self appears to be in good condition