36C24818Q0491-009.pdf

PDF 3 MB Posted

Attached to
Services: Repair Active Vehicle Barriers Federal contract opportunity
Solicitation number
36C24818Q0491
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

36C24818Q0491 ATTACHMENT B Warehouse Service barrier Survey v3-.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Services: Repair Active Vehicle Barriers, newest first.
File Type Posted
36C24818Q0491-00001001.docx DOCX document
36C24818Q0491-00001000.docx DOCX document
36C24818Q0491-008.pdf PDF
36C24818Q0491-012.pdf PDF
36C24818Q0491-006.pdf PDF
36C24818Q0491-003.pdf PDF
36C24818Q0491-007.pdf PDF
36C24818Q0491-011.pdf PDF
36C24818Q0491-002.docx DOCX document
36C24818Q0491-004.pdf PDF
36C24818Q0491-005.pdf PDF
36C24818Q0491-013.pdf PDF
36C24818Q0491-010.pdf PDF
36C24818Q0491-001.docx DOCX document
36C24818Q0491-000.docx DOCX document
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Warehouse Service barrier Survey v3.docx

Warehouse Service Entrance - Outbound Side Lane

General Notes:

-Limit Sensors wiring is damaged not properly terminated for below grade application. The cable should be shortened, terminations should be soldiered, adhesive heat shrunk, and cable sleeved Lead in cables are damaged and need replaced with shielded cable

Warehouse Service Entrance - Middle Lane

General Notes:

-Limit Sensors wiring is damaged and not properly terminated for below grade application. The cable should be shortened, terminations should be soldiered, adhesive heat shrunk, and cable sleeved

-Hose needs replaced and rerouted. We moved it back slightly to avoid rubbing.

Ware Service Entrance - Left/Middle – Power Unit

General Notes:

-Hydraulic oil is extremely dirty. The oil, suction strainer needs to be replaced. The hydraulic hoses need to be blown out and flushed. The hydraulic drum needs to be wiped and cleaned thoroughly

-Eliminate the un-necessary secondary layer of PLC control

-Noticeable rusting and paint chipping is on the outdoor enclosure. The chipping spots at a minimum needs to be touched up. Full painting is suggested.

-Lid is cracked, replace with OEM reservoir lid

Warehouse Service Entrance - Inbound Side Lane

General Notes:

-Hydraulic oil is extremely dirty. The oil, suction strainer needs to be replaced. The hydraulic hoses replaced and shortened up. The hydraulic drum needs to be wiped and cleaned thoroughly

- Eliminate the un-necessary secondary layer of PLC control

-Front Rubber pad starting to come off. Needs to be replaced

-Concrete pad under the barrier needs to be repaired.

-Limit Sensors wiring is not properly terminated for below grade application. The cable should be shortened, terminations should be soldiered, adhesive heat shrunk, and cable sleeved

-limit wire damaged replace with shielded cable

-Noticeable rusting and paint chipping is on the outdoor enclosure. Full painting is suggested.