36C24618B0616-013.pdf

PDF 1 MB Posted

Attached to
Relocate and Expand Renal Dialysis
Solicitation number
36C24618B0616
Issued by

About this file

36C24618B0616 11 Fire Protection.pdf

View the file

Other files

File Type Posted
36C24618B0616-0004000.docx DOCX document
36C24618B0616-0003002.pdf PDF
36C24618B0616-0003000.docx DOCX document
36C24618B0616-0003001.pdf PDF
36C24618B0616-0002001.pdf PDF
36C24618B0616-0002000.docx DOCX document
36C24618B0616-0001000.docx DOCX document
36C24618B0616-002.pdf PDF
36C24618B0616-012.pdf PDF
36C24618B0616-001.docx DOCX document
36C24618B0616-016.pdf PDF
36C24618B0616-004.pdf PDF
36C24618B0616-003.pdf PDF
36C24618B0616-014.pdf PDF
36C24618B0616-011.pdf PDF
36C24618B0616-009.pdf PDF
36C24618B0616-008.pdf PDF
36C24618B0616-010.pdf PDF
36C24618B0616-007.pdf PDF
36C24618B0616-005.pdf PDF
36C24618B0616-015.pdf PDF
36C24618B0616-006.pdf PDF
36C24618B0616-000.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PHYSICIAN/PA/

RES/INTERN

STAFF LOUNGE

UTIL SOILED

UTIL, STERILE,

CLEAN

CORRIDOR

CB-9

TELE DATA

5-A

CASE CART

HOLDING

EXPANSION

JOINT

EXPANSION

JOINT

N

E

W

E

X

I

S

T

I

N

G

N

E

W

E

X

I

S

T

I

N

G

PROJECT LIMITS

P R

O J E

C T

L

I M

I T

S

NOT IN SCOPE

P R

O J E

C T

L

I M

I T

S

CASE CART

HOLDING

NOT IN SCOPE

PROJECT LIMITS

WAITING AREA

ELEC

T E

L E

C O

M

CB-2

CONNECTOR CORRIDOR

(CONNECTS BUILDING #1)

TO

BUILDING

#1

DIALYSIS TLT

MED PREP

EQUIP STOR

ISOLATION ROOM

PRIVATE ROOM

PRIVATE TLT

24-A

ISOLATION TLT

23-A

WATER

TREATMENT

TRAIN/ PROG RM

RECEPTION

BIOMED REPAIR

EQUIP. SOILED

REC

EQUIP. CLEAN

STORAGE

ELEC.

ELEC.

MECH RM

STAFF UNISEX

PATIENT UNISEX

DIALYSATE PREP

27-A

VESTIBULE

EQUIP. CLEAN

PREP

CLEAN LINEN

ED COORD &

DIETITIAN

STAFF LOCKERS

CHIEF NURSE

CHIEF OFFICE

NOURISH

EXAM/ TREAT

STAFF CORRIDOR

CB-2B

CORRIDOR

CB-3

CORRIDOR

CB-4

NOT IN SCOPE

PROJECT LIMITS

NURSE STATION

18-A

DIALYSIS

SITE FOR FUTURE

VERTICAL CIRCULATION

NEW / EXISTING BOUNDARY

PROJECT LIMITS

LINETYPE

WALL LEGEND

DESCRIPTION

NOTE: NOT ALL TYPES SHOWN

ARE USED ON EACH SHEET

2-HR FIRE WALL

FIRE PROTECTION LEGEND

S

S

F

MANUAL FIRE ALARM PULL STATION; 48" MOUNTING

HEIGHT U.N.O

SPEAKER / STROBE; 80" MOUNTING HEIGHT U.N.O.,

C DENOTES CEILING MOUNT

SPEAKER; 80" MOUNTING HEIGHT U.N.O. C

DENOTES CEILING MOUNT

S

FLOOR CONTROL VALVE ASSEMBLY COMPLETE

WITH SUPERVISED CONTROL VALVE, CHECK

VALVE, PRESSURE GAUGE, FLOW SWITCH, TEST

AND DRAIN CONNECTION.

PHOTOELECTRIC SMOKE DETECTOR,

ADDRESSABLE

OH-1

ORDINARY HAZARD -1, 0.15 GPM OVER 1,500 SF

WITH 250 GPM FOR HOSE STREAMS.

OH-2

ORDINARY HAZARD -2, 0.20 GPM OVER 1,500 SF

WITH 250 GPM FOR HOSE STREAMS.

STROBE; 80" MOUNTING HEIGHT U.N.O., C DENOTES

CEILING MOUNT

SPRINKLER SYSTEM NOTES

DUCT MOUNTED SMOKE DETECTOR

S

EXISTING

SIMPLEX

4100U

FACP

FIRE ALARM RISER DIAGRAM

NONE

SCALE:

S

FS

FCV

S

SUPPLY

HAZARDOUS AREA

1 BASE HYDRAULIC CALCULATIONS ON EXISTING WATER

SUPPLY. STATIC 68 PSI, RESIDUAL 50 PSI, FLOW 1,000

GPM.

2 UNLESS NOTED OTHERWISE ALL AREAS ARE LIGHT

HAZARD OCCUPANCY, 0.10 GPM OVER 1,500 SF USING QR

SPRINKLERS, 100 GPM FOR HOSES.

3 ALL SPRINKLERS SHALL BE QUICK RESPONSE.

4 DESIGN AREA MAY BE REDUCED FOR CEILING HEIGHT

AND QR SPRINKLERS PER NFPA 13.

5 REFER TO SPECIFICATIONS FOR FURTHER DETAILS.

6 ALL WORK SHALL BE IAW NFPA 13, NFPA 72, NFPA 101.

7 EXISTING SPRINKLERS AND PIPING SERVING THE

EXISTING PORTION NEW WORK AREA SHALL BE MODIFIED

FOR THE NEW WALL LAYOUT SHOWN. THE SPRINKLER

SYSTEM FOR THE NEW ADDITION AREA SHALL BE A

ZONED AS INDICATED BELOW AND SUPPLIED SUPPLIED

FROM THE EXISTING 4" STANDPIPE IN STAIR 2A.

8 LOCATE ALL SPRINKLERS IN A SYMMETRICAL PATTERN

THAT ALIGN WHEN VIEWED FROM TWO DIRECTIONS.

9 SPRINKLER PIPING SHALL BE SEISMICALLY SUPPORTED.

Ss=0.264.

NOTE:

FIRE ALARM SEQUENCE OF OPERATION

SHALL FOLLOW EXISTING FIRE ALARM

SEQUENCE OF OPERATION

SPRINKLER SYSTEMS

THE EXISTING BUILDING IS FULLY SPRINKLERED. ANY

EXISTING SPRINKLERS AND PIPING SERVING THE EXISTING

PORTION NEW WORK AREA SHALL BE MODIFIED FOR THE

NEW WALL LAYOUT SHOWN. THE EXISTING SYSTEM SHALL

REMAIN IN SERVICE DURING CONSTRUCTION FOR THOSE

AREAS OUTSIDE OF THE WORK SCOPE. THE SPRINKLER

SYSTEM FOR THE NEW ADDITION AREA SHALL BE ZONED AS

INDICATED BELOW AND SHALL BE SUPPLIED SUPPLIED FROM

THE EXISTING 4" STANDPIPE IN STAIR 2A. HAZARD CLASSES

AND DESIGN CRITERIA ARE SHOWN ON THIS DRAWING.

SPRINKLERS SHALL BE ARRANGED IN A SYMMETRICAL

PATTERN SO WHEN VIEWED IN TWO DIRECTIONS ALIGN AS

MUCH A PRACTICAL. CONTROL VALVES AND WATER FLOW

WILL BE SUPERVISED BY THE FIRE ALARM SYSTEM.

FIRE ALARM

EXISTING FIRE ALARM DEVICES WILL BE REMOVED. NEW

DEVICES WILL BE PROVIDED AND LOCATED BASED ON NEW

WALL AND CEILING CONFIGURATIONS. SPEAKER-STROBES

AND ADDITIONAL SPEAKER UNITS WILL BE PROVIDED SO

THAT SPEAKERS ARE SPACED APPROXIMATELY 30 FT ON

CENTERS AS SUGGESTED BY THE VA FIRE PROTECTION

DESIGN GUIDE. MANUAL FIRE ALARM STATIONS WILL BE

PROVIDED AT EXITS AND IN THE NURSES STATION. THE

EXISTING SYSTEM IS MONITORED 24 HRS A DAY. THE

EXISTING FIRE ALARM CIRCUITS AND DEVICES SERVING THE

EXISTING PORTION NEW WORK AREA SHALL BE MODIFIED

FOR THE NEW WALL LAYOUT SHOWN AND REMAIN A PART OF

THE EXISTING ZONE. THE FIRE ALARM CIRCUITS AND

DEVICES FOR THE NEW ADDITION AREA SHALL BE A ZONED

AS INDICATED BELOW. THE SEQUENCE OF OPERATION FOR

THE NEW FIRE ALARM ZONE SHALL FOLLOW THE EXISTING

BUILDING SEQUENCE OF OPERATION.

FIRE PROTECTION

GENERAL NOTES

SHEET NOTES

1 EXISTING SIMPLEX 4100U FIRE ALARM PANEL WITH

CAPACITY FOR EXPANSION.

2 APPROXIMATELY 201 EQ. FT. OF 4 INCH SCH. 40 PIPE

TO TOP OF EXISTING 4 INCH RISER. 4 INCH RISER HAS

6 INCH DDC BACKFLOW PREVENTER.

3 TO NEW SPRINKLER ZONE FOR NEW ADDITION

FCV

S

F

F

F

S

S

S

S

F

S

S

C

C

EXISTING 4" FIRE PROTECTION

RISER STAIR 2A

F C

V

EXISTING 4" FIRE MAIN FROM

EXISTING LIFE SAFETY ROOM

NEW FIRE WATER SUPPLY TO

NEW SPRINKLER ZONES

F A

C P

EXISTING

S

OH-1

OH-2

S

S

F

C

S

S

S

F

S C

S C

S C

S C

F

OH-2

OH-2

OH-2

OH-2

OH-1

OH-1

OH-1

OH-2

DESIGN/BUILD

o n e e i g h t h i n c o e f o t t h r e e i n c h e s o t o n e a d a l f i n c h e s o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Revisions: Date

Corporate Office:

766 Middle St, Fairhope, AL 36532

Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location

Sheet of

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

2017.04.18

658-315

CONSTRUCTION DOCUMENTS

SALEM VA MEDICAL CENTER

RELOCATE AND EXPAND

RENAL DIALYSIS

FIRE PROTECTION PLAN

FP101

FIRE ALARM SEQUENCE OF OPERATIONS MATRIX

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

KEY PLAN

BASEMENT FFE: 1091.3'

PLAN

NORTH

PROJECT AREAPROJECT AREA - OVERALL

BUILDING #2 (EXISTING)

2/16/18