36C24618B0616-011.pdf

PDF 751 KB Posted

Attached to
Relocate and Expand Renal Dialysis
Solicitation number
36C24618B0616
Issued by

About this file

36C24618B0616 09 Interiors.pdf

View the file

Other files

File Type Posted
36C24618B0616-0004000.docx DOCX document
36C24618B0616-0003002.pdf PDF
36C24618B0616-0003000.docx DOCX document
36C24618B0616-0003001.pdf PDF
36C24618B0616-0002001.pdf PDF
36C24618B0616-0002000.docx DOCX document
36C24618B0616-0001000.docx DOCX document
36C24618B0616-013.pdf PDF
36C24618B0616-002.pdf PDF
36C24618B0616-012.pdf PDF
36C24618B0616-001.docx DOCX document
36C24618B0616-016.pdf PDF
36C24618B0616-004.pdf PDF
36C24618B0616-003.pdf PDF
36C24618B0616-014.pdf PDF
36C24618B0616-009.pdf PDF
36C24618B0616-008.pdf PDF
36C24618B0616-010.pdf PDF
36C24618B0616-007.pdf PDF
36C24618B0616-005.pdf PDF
36C24618B0616-015.pdf PDF
36C24618B0616-006.pdf PDF
36C24618B0616-000.docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P-03P-02

P-04

PT-04

P-03

P-04 P-04

P-05

P-02

P-05

P-05

P-02

P-02

P-02

P-02

P-05

P-05

P-02

P-02 P-03

WR-01

WR-01

WR-01

WR-01

WR-01

PT-01

P-04

P-04

PROJECT LIMITS

PR

O

JE

C

T

LI

M

IT

S

NOT IN SCOPE

PR

O

JE

C

T

LI

M

IT

S

NOT IN SCOPE

PROJECT LIMITS

NOT IN SCOPE

PROJECT LIMITS

P-03

P-03

WR-01

P-04

/4

8' - 2"

ED COORD &

DIETITIAN

B51

CHIEF NURSE

B52

CHIEF OFFICE

B53

CORRIDOR

CB-10

TRAIN/ PROG RM

B54

VESTIBULE

B40

VESTIBULE

B40

RECEPTION

B41

PATIENT UNISEX

B50

STAFF UNISEX

B49

STAFF LOUNGE

B48

STAFF LOCKERS

B47

PHYSICIAN/PA/

RES/INTERN

B43

ELEC

B46

TELE DATA

B45

PRIVATE ROOM

B63

ISOLATION ROOM

B61

CLEAN LINEN

B55

ISOLATION TLT

B62

PRIVATE TLT

B64

NURSE STATION

B56.2

DIALYSIS

B56

EQUIP STOR

B65

MED PREP

B60

EXAM/ TREAT

B59

TLT

B58

NOURISH

B57

HVAC

B76

ELEC.

B75

ELEC.

B74

CLEAN STORAGE

B73

CLEAN PREP

B72

SOILED REC

B71

UTIL SOILED

B70

CORRIDOR

CB-9

UTIL, STERILE,

CLEAN

B69

CORRIDOR

CB-2C

CORRIDOR

CB-12

BIO-MED REPAIR

B68

DIALYSATE PREP

B67

WATER

TREATMENT

B66

WAITING AREA

B42

DIALYSIS

CIRCULATION

B56.1

P-04

P-04

P-03

P-05

SITE FOR

FUTURE

VERTICAL

CIRCULATION

E2 E1 S1

CORRIDOR

CB-11

CL

DOOR WHERE OCCURS

CERAMIC / PORCELAIN

TILE

SST TRANSITION

STRIP

RESILIANT FLOORING

(TILE, SHEET, OR LINOLEUM)

CRACK ISOLATION OR

WATERPROOFING MEMBRANE

- EXTEND 2" UNDER RESILIANT

SLAB

1/2"

PORCELAIN TO RESILIANT

DOOR WHERE OCCURS

RESILIANT FLOORING

(TILE,PLANK OR SHEET)

HEAT-WELDED SEAM

BETWEEN RESILIANT

SHEET FLOORING

ADHERED SEAM BETWEEN

RESILIANT SHEET AND

OTHER RESILIANT

RESILIANT FLOORING

(TILE, PLANK OR SHEET)

SLAB

CL

RESILIANT TO RESILIANT

RESILIANT EDGE STRIP -

CENTER UNDER DOOR

WHERE OCCURS

RESILIANT FLOORING SLAB

CL

RESILIANT TO CONCRETE

DOOR WHERE OCCURS

DOOR WHERE OCCURS

RESINOUS FLOORING

- SLOPE TO DRAIN

ACCESSIBLE SST

TRANSITION STRIP

RESILIANT FLOORING

(TILE, PLANK, SHEET, OR

LINOLEUM)

SLAB

CL

RESINOUS TO RESILIANT

1/ 8"

1/ 2"

1 1/8"

FLOOR PATTERN LEGEND

CONC. - SEALED CONCRETE

LVT-02 - LUXURY VINYL TILE -

6"x36" PLANKS

PT-01 -PORCELAIN TILE

WSF-02 - WELDED SEAM SHEET VINYL

LVT-01 - LUXURY VINYL TILE- 6"x36"

PLANKS IN HERRINGBONE PATTERN

RES-01 - RESINOUS FLOORING

WSF-03 - WELDED SEAM SHEET VINYL

LVT-03 - LUXURY VINYL TILE-

18"x18" TILE

WSF-01 - WELDING SEAM SHEET VINYL

WALK OFF MAT

INDICATES PARTITION

INDICATES LOCATION OF HANDRAIL. SEE DETAIL 9D/AE502

INDICATES LOCATION OF CRASH RAIL. SEE DETAIL 9B/AE502

DESIGN/BUILD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Revisions: Date

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FULLY SPRINKLERED

Ve te ra ns

Af fa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

3/

/2

:0 6 :

P

M

SALEM VA MEDICAL CENTER

RELOCATE AND EXPAND RENAL

DIALYSIS

BASEMENT FLOOR PLAN - FLOOR

FINISH

2 AEJALB

2018.02.16

658-315

IN101

CONSTRUCTION DOCUMENTS

1/8" = 1'-0"9F FLOOR FINISH PLAN - BASEMENT

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

KEY PLANPLAN

NORTH

PROJECT AREAPROJECT AREA

BUILDING #2 (EXISTING)

6" = 1'-0"

FLOOR TRANSITION DETAILS

GRAPHIC LEGEND

MATERIAL CODE MANUFACTURER PATTERN/LINE COLOR COMMENT

LVT - LUXURY VINYL TILE

LVT-01

P- PAINT

PLAM- PLASTIC LAMINATE

P-01

WILSONART

PT-02 WALL

SS- SOLID SURFACE

SS-01 CORIAN

WP- WALLPROTECTION

WP-01

LVT-02

CENTIVA WOOD PLANK

SHERWIN WILLIAMS

PT-01 FLOOR CROSSVILLE

PLAM- 01

PTB - PORCELAIN TILE BASE

RES-01

RB - RESILIENT BASE

RB-01

RB-02

JOHNSONITE

JOHNSONITE

TRADITIONAL 4" BASE

PROFILE BASE

WP-02

WP-03

CORNER GUARD

BIOSPEC MD

P-02 SHERWIN WILLIAMS

P-04 SHERWIN WILLIAMS

P-03 SHERWIN WILLIAMS

VENUE WOODS

WELDED SEAM FLOOR

WSF-01 MANNINGTON

CUBICLE CURTAIN

CC-01 IN-PRO CLICKEZE PRIVACY SYSTEMS

CRASH RAIL

HANDRAIL

SS-02 CORIAN

LINEN

PT - PORCELAIN TILE

PT-03 BORDER

WSF-02

WSF-03

CROSSVILLE

CROSSVILLE

MANOIR

MANOIR

S009 QUARTZITE MOSAIC

CROSSVILLE

DECO FLAKE

AV255 BELMONT

AV254 HERMITAGE

12" x 12"

AV255 BELMONT

6" x 12" BASE

BREEZE (DISPOSABLE)

3" STONE STACKEDSTONE VENEER

CENTIVA WOOD PLANK

LVT-03

VENUE WOODS

HERRINGBONE PATTERN

PT-04 BULL NOSE

TOASTED SESAME 15333

MANNINGTON

MANNINGTON

BIOSPEC MD

BIOSPEC MD

SILVER PINE 15374

GREY FLANNEL15370

PLAM- 02

PLAM- 03

PLAM- 04

WILSONART

WILSONART

WILSONART

4911-38 SOFT GOLD MESH

4877-38 GREY MESH

4912-38 GILDED MESH

4794-60 WINDSWEPT BRONZE

CENTIVA TILE EVENT STONE 18" X 18" TILE

STRAIGHT PLANK

SW7015 REPOSE GRAY

SW7016 MINDFUL GRAY

SW6228 REFUGE

SW6214 UNDERSEAS

1" x 1" MOSAIC CUT TO BAND

WIDTH, CONTINUOUS

S009

TB1 PEPPERCORN

TB1 PEPPERCORN

EXPOXY RESINOUS

SIKA OPAL W SF 510 TOPCOAT

IN PRO

STONE VENEER

STN-01

TAUPE (DISPOSABLE)

WR-01 MANNINGTON BIOSPEC MD WELDING ROD

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

SEE SPECIFICATION

842434

EUROPEAN CHERRY

IN PRO

IN PRO

CANVAS

P-05 SHERWIN WILLIAMS SW7045 INTELLECTUAL GRAY

EUROPEAN CHERRY

209 SLATE

209 SLATE

383 VINTAGE WALNUT

STAINLESS STEEL

STNLS STAINLESS STL WORKSURFACE

CASEWORK CABINETS

CASEWORKCAB-01 MIDMARK 801 TIMBER

AT- 01 ACOUSTICAL TILE

CEILINGS

AT- 01 (SP)

GYP BOARD

SEE SPECIFICATIONS

SEE SPECIFICATIONS

SEE SPECIFICATIONS

SEE SPECIFICATIONS

P-06

P-06 SHERWIN WILLIAMS SW7005 PURE WHITE ALL GYP BD CEILINGS UNLESS

INDICATED ON DRAWINGS

SEE SPECIFICATIONS

MATCH EXISTING ON SITE

WALK OFF MAT

WMT-01 PEDIMAT 7/16"

1 - GYP BOARD CEILINGS TO BE PAINTED P-06

2 - ROOMS WITH PT WAINSCOT TO HAVE FULL HEIGHT TILE ON WET WALL

3 - SEE SHEET IN101 FOR WELDED SHEET FLOORING PATTERN

4 - WELDED SHEET FLOORING WELD ROD TO BE CAMOFLAUGE EXCEPT

WHERE NOTED FOR LEAF PATTERN ON SHEET IN101

5 - SEE SHEET GI001 AND FINISH SCHEDULE MISC COLUMN FOR ALL DEDUCTIVE

ALTERNATES

6 - WELDED SHEET FLOORING TO HAVE INTEGRAL BASE WITH TOP CAP

OF MANNINGTON COLOR 918 FLAX - FLOOR PATTERN TO CONTINUE THROUGH

INTEGRAL BASE.

7 - ALL RESINOUS FLOORING TO HAVE 4" INTEGRAL BASE

8 - PORCELAIN TILE BEHIND WATER COOLERS IS TO BE FULL HEIGHT - SEE PLAN

FOR SIDE WALL LIMITS

9 - SEE REFLECTED CEILING PLAN FOR GYP BOARD SOFFIT SIZE AND LOCATION

10 - SEE SHEET AE401 FOR CASEWORK FINISHES

11- SEE SHEET AE401 FOR CONTINUOUS TILE MOSAIC BORDER

12 - GYP BOARD SOFFITS ABOVE NURSES STATION TO BE P-05

DESIGN/BUILD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Revisions: Date

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FULLY SPRINKLERED

Ve te ra ns

Af fa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

3/

/2

:0 6 :

P

M

SALEM VA MEDICAL CENTER

RELOCATE AND EXPAND RENAL

DIALYSIS

FINISH SCHEDULE

2 ALBJF

2018.02.16

658-315

IN102

CONSTRUCTION DOCUMENTS

ROOM NO. ROOM NAME BASE FLOOR WALLS

ACCENT

WALL CEILING

COUNTER

TOPS VERTICAL MILLWORK WALL PROTECTION CODED NOTES

B40 VESTIBULE RB-02 LVT-01 P-05 ----- AT-01 ----- -----

B41 RECEPTION RB-02 LVT-02 P-02 P-03 GB/ AT-01 SS-01 PLAM- 01 UPPER

PLAM-02 LOWER

WP-01,WP-02,WP-03 10

B42 WAITING AREA RB-02 LVT-01 P-02 P-03 AT-01 ----- WP-01,WP-02,WP-03 5

B43 PHYSICIAN/PA/

RES/INTERN

RB-01 LVT-02 P-02 P-04 AT-01 ----- CAB-01 WP-01 5

B44 TELECOM ----- CONC. ----- ----- ----- ----- ----- 5

B45 TELE DATA ----- CONC. ----- ----- ----- ----- -----

B46 ELEC RB-01 CONC. P-01 ----- ----- ----- ----- 5

B47 STAFF LOCKERS RB-01 LVT-03 P-01 ----- AT-01 ----- -----

B48 STAFF LOUNGE RB-01 LVT-03 P-05 P-03 AT-01 SS-01 WP-01 5,10

B49 STAFF UNISEX PTB-01 PT-01 PT-02 / P-02 /

PT-03

----- GYP BD ----- ----- 1,2

B50 PATIENT UNISEX PTB-01 PT-01 PT-02 / P-02 /

PT-03

----- GYP BD ----- ----- 1,2

B51 ED COORD & DIETITIAN RB-01 LVT-02 P-02 P-04 AT-01 ----- -----

B52 CHIEF NURSE RB-01 LVT-02 P-02 P-04 AT-01 ----- -----

B53 CHIEF OFFICE RB-01 LVT-02 P-02 P-04 AT-01 ----- CAB-01 -----

B54 TRAIN/ PROG RM WSF-03 WSF-03 P-02 P-04 AT-01 SS-01 PLAM- 01 UPPER

PLAM-02 LOWER

----- 4,6

B55 CLEAN LINEN WSF-03 WSF-03 P-02 ----- AT-01 (SP) ----- STNLS ----- 4,6

B56 DIALYSIS WSF-01/WSF-02/

WSF-03

WSF-01/WSF

-02/WSF-03

P-02 P-03/ P-04 GYP BD SS-01 PLAM- 01, 02, 03 WP-01,WP-02,WP-03 4,6

B56.1 DIALYSIS CIRCULATION WSF-02/ WSF-03 WSF-01 P-02 ----- AT-01 ----- WP-01 4,6,12

B56.2 NURSE STATION WSF-02 WSF-02 P-02 P-05 GB/AT-01 SS-01 /

SS-02

PLAM- 01, 02, 03 WP-01 4,6,10

B57 NOURISH WSF-02 WSF-02 P-01 P-04 AT-01 SS-01 PLAM- 01, 02, 03 WP-01 4,6,10

B58 TLT PTB-01 PT-01 PT-02 / P-02 /

PT-03

----- GYP BD ----- ----- 1,2

B59 EXAM/ TREAT WSF-03 WSF-03 P-01 P-03 AT-01 SS-01 PLAM- 01 UPPER

PLAM-02 LOWER

----- 4,6

B60 MED PREP WSF-02 WSF-02 P-02 P-04 AT-01 SS-01 PLAM- 01 UPPER

PLAM-02 LOWER

----- 4,6

B61 ISOLATION ROOM WSF-02 WSF-02 P-02 P-04 GYP BD ----- WP-01 4,6

B62 ISOLATION TLT WSF-02 WSF-02 P-02 ----- GYP BD ----- ----- 4,6

B63 PRIVATE ROOM WSF-03 WSF-03 P-02 P-04 AT-01 ----- WP-01 4,6

B64 PRIVATE TLT WSF-03 WSF-03 P-02 ----- GYP BD ----- ----- 4,6,11

B65 EQUIP STOR RES-01 RES-01 P-02 ----- AT-01 (SP) ----- STNLS WP-01 7

B66 WATER TREATMENT RES-01 RES-01 P-02 ----- AT-01 (SP) SS-01 STNLS WP-01 7

B67 DIALYSATE PREP RES-01 RES-01 P-02 ----- AT-01 (SP) ----- PLAM- 01 UPPER

PLAM-02 LOWER

WP-01 7

B68 BIO-MED REPAIR RES-01 RES-01 P-01 ----- AT-01 (SP) SS-01 PLAM- 01 UPPER

PLAM-02 LOWER

WP-01 7

B69 UTIL, STERILE, CLEAN WSF-01 WSF-01 P-02 ----- AT-01 (SP) SS-01 STNLS WP-01 4,6

B70 UTIL SOILED WSF-03 WSF-03 P-02 ----- AT-01 (SP) SS-01 STNLS WP-01 4,6

B71 SOILED REC WSF-03 WSF-03 P-02 ----- AT-01 (SP) SS-01 WP-01 4,6

B72 CLEAN PREP WSF-03 WSF-03 P-02 ----- AT-01 (SP) SS-01 ----- 4,6

B73 CLEAN STORAGE WSF-03 WSF-03 P-02 ----- AT-01 (SP) SS-01 WP-01 4,6

B74 ELEC. RB-01 CONC. P-02 ----- ----- ----- -----

B75 ELEC. RB-01 CONC. P-02 ----- ----- ----- -----

B76 HVAC ----- CONC. P-01 ----- ----- ----- -----

CB-2A CORRIDOR RB-01 LVT-02 P-01 AT-01

CB-2B CORRIDOR RB-01 LVT-02 P-02 AT-01

CB-2C CORRIDOR RB-01 LVT-02 P-01 ----- AT-01 ----- WP-01,WP-02,WP-03

CB-9 CORRIDOR RB-01 LVT-02 P-01 ----- AT-01 ----- WP-02, WP-03

CB-10 CORRIDOR RB-01 LVT-02 P-01 ----- AT-01 ----- WP-01,WP-02,WP-03

CB-11 CORRIDOR RB-01 LVT-02 P-01 AT-01

CB-12 CORRIDOR RB-01 LVT-02 P-01 ----- AT-01 ----- WP-01,WP-02,WP-03

FINISH LEGEND FINISH SCHEDULE

A ALL FINISH PRODUCTS ARE INTENDED AS A BASIS OF DESIGN BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED EQUIPMENT OR

EQUIPMENT OF EQAUL CAPACITY, QUALITY, AND PERFORMANCE.

B SEE SHEET IN101 FOR FLOOR PATTERN LAYOUT

C ALL WELDED SHEET VINYL WELD RODS TO COORDINATE WITH THE DARKER WSF AT SEAM AND DARK SOLID AROUND LEAVES WHERE NOTED D WHERE WSF TURNS UP AS BASE - USE THE SAME COLOR CONTINUOUSLY TO EXTEND FLOOR PATTERN AND TOP CAP TO ME MANNINGTON COLOR 918

FLAX

E PT-01 TO BE FULL HEIGHT ON WALL BEHIND WATERCOOLERS IN WAITING AREA 3

F STANDARD CASEWORK: TO SHOW PLAM-01 ON THE UPPER AND PLAM-02 ON THE LOWER ON DESKS G WALL PROTECTION BASIS OF DESIGN IS INPRO, COLORS VINTAGE WALNUT FOR HANDRAIL AND SLATE CRASH RAIL AND BUMPER GUARDS H MANUFACTURED METAL CASEWORK TO BE MIDMARK SERIES "SYNTHESIS" AS A BASIS OF DESIGN-http://www.midmark.com/docs/default-source/marketing-collateral/007-0877-00-synthesis.pdf?sfvrsn=10

GENERAL NOTES

CODED NOTES

PHYSICIAN/PA/

RES/INTERN

B43

UTIL SOILED

B70

UTIL, STERILE,

CLEAN

B69

CORRIDOR

CB-9

TELE DATA

B45

A

B B

A B

B

B

BBBAA

G

B

B

B

F

B

F

C

I

C

A

A

K

H

A

A

J

J

I

B

A

C

A

J

A

I

J

C

K

A

CC

J

J

B K

J B

B F

J

B

SITE FOR

FUTURE

VERTICAL

CIRCULATION

E2 E1 S1

ED COORD &

DIETITIAN

B51

STAFF LOUNGE

B48

ELEC

B46

WAITING AREA

B42

TELECOM

B44

DIALYSIS

B56

TLT

B58

MED PREP

B60

EQUIP STOR

B65

ISOLATION ROOM

B61

PRIVATE ROOM

B63 PRIVATE TLT

B64

ISOLATION TLT

B62

CLEAN LINEN

B55

WATER

TREATMENT

B66

TRAIN/ PROG RM

B54

RECEPTION

B41

BIO-MED REPAIR

B68

DIALYSATE PREP

B67

SOILED REC

B71

CLEAN STORAGE

B73

ELEC.

B74

ELEC.

B75HVAC

B76

STAFF UNISEX

B49

PATIENT UNISEX

B50

VESTIBULE

B40

CLEAN PREP

B72

STAFF LOCKERS

B47

CHIEF NURSE

B52

CHIEF OFFICE

B53

NOURISH

B57

EXAM/ TREAT

B59

CORRIDOR

CB-2C

CORRIDOR

CB-10

CORRIDOR

CB-12

NURSE STATION

B56.2

DIALYSIS

CIRCULATION

B56.1

CORRIDOR

CB-11

CORRIDOR

CB-2A

CORRIDOR

CB-2B

2"

NO HIGHER THAN 60" TO

BOTTOM OF RAISED

TACTILE CHARACTERS

1/ 2"

TO

B

O

TT

O M

O F

SI

G

N

9X9 ROOM ID

(D1A/F/W)

2"

STAIR & RESTROOM ID

+ ROOM NUMBER

(SA/W +D1A/W)

NOTE: ROOM ID SIGNS MUST BE MOUNTED ON A

HORIZONTAL SIGHT LINE AS SHOWN ABOVE.

RESTRICTIVE MESSAGES MOUNTED DIRECTLY ON

DOORS SHOULD ALSO BE 64 1/2" A.F.F.

2"0' - 2"CENTER

7"X24" (C4/FM)

2"

CENTER OVER DOOR 2" ABOVE JAMB.

TYPE: 108/W, C/W, P5/W

(DIRECTIONAL SIGNS)

6'

0" A

.F .F

NOTE: GENERALLY 72" TO TOP (UNLESS

WAINSCOT ON HANDRAIL INTERFERE)

TYPE: V/W (EVAC PLANS)

NOTE: GENERALLY 72" TO TOP (UNLESS

WAINSCOT HANDRAIL INTERFERE)

6'

0" A

.F .F

DIRECTIONAL HEIGHTS 1

NOTE: ADJUST ACCORDINGLY TO WAINSCOT MIN.

4" AWAY

5'

2" A

.F .F

5'

8" A

.F .F

6'

0" A

.F .F

6'

2" A

.F .F

6'

4" A

.F .F

6'

8" A

.F .F

DIRECTIONAL HEIGHTS 2

5'

2" A

.F .F

5'

8" A

.F .F

6'

0" A

.F .F

7' M

IN

IM

U M

TO

B

O

TT

O M

O F

SI

G

N

7' M

IN

IM

U M

TO

B

O

TT

O M

O F

SI

G

N

OVERHEAD SIGNS (C4) &

RIGHT ANGLE (G)

NOTE: OVERHEAD SIGNS MUST NOT BLOCK CLEAR

VIEW OF EXIT SIGN OR BE CLOSER THAN 18" TO

SPRINKLER HEAD. (84" MIN. TO BOTTOM OF SIGN)

SIGNAGE TEXT

SIGNAGE

TEXT

62" TO TOP OF SIGN OR MATCH TOP

OF ROOM ID ABOVE

57" TO MIDDLE OF SIGN ON

STRIKE SIDE OF DOOR

(HINGE SIDE IS

SECOND CHOICE)

4'-9" TO CENTER

62" TO TOP OF SIGN OR MATCH TOP

OF ROOM ID ABOVE

62" TO TOP OF SIGN ON STRIKE

SIDE OF DOOR

(HINGE SIDE IS SECOND CHOICE)

A INDICATES LOCATION AND TYPE OF

SIGNAGE. SEE SIGNAGE DETAILS &

SCHEDULE ON IS102

INDICATES PARTITION

INDICATES LOCATION OF HANDRAIL. SEE DETAIL 9D/AE502

INDICATES LOCATION OF CRASH RAIL. SEE DETAIL 9B/AE502

DESIGN/BUILD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Revisions: Date

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FULLY SPRINKLERED

Ve te ra ns

Af fa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

3/

/2

:0 6 :

P

M

SALEM VA MEDICAL CENTER

RELOCATE AND EXPAND RENAL

DIALYSIS

SIGNAGE PLAN

2 AEJALB

2018.02.16

658-315

IS101

CONSTRUCTION DOCUMENTS

1/8" = 1'-0"9F SIGNAGE FLOOR PLAN - BASEMENT

SIGNAGE INSTALLATION STANDARDS

SCALE: 1/8" = 1'-0"

0 4' 8' 16'KEY PLANPLAN

NORTH

PROJECT AREAPROJECT AREA

BUILDING #2 (EXISTING)

GRAPHIC LEGEND

DESIGN/BUILD

on e ei gh th in ch o ne fo ot th re e in ch es o ne fo ot 6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

E

F

A

B

C

D

E

F

Drawing Title Project Title

CheckedBuilding Number Drawn

Revisions: Date

Corporate Office:

766 Middle St, Fairhope, AL 36532 Phone: 251.990.5778

Fax: 251.990.3716

Date

Project No.

Drawing No.

Location Sheet of

FULLY SPRINKLERED

Ve te ra ns

Af fa irsApproved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

3/

/2

:0 6 :

P

M

SALEM VA MEDICAL CENTER

RELOCATE AND EXPAND RENAL

DIALYSIS

SIGNAGE SCHEDULE

2 AEJALB

2018.02.16

658-315

IS102

CONSTRUCTION DOCUMENTS

SIGNAGE ROOM NAME

Room Number

Code

SIGNAGE

TYPE TEXT

B40 VESTIBULE 1 K,J,G SEE LEGEND

B41 RECEPTION 2 A ROOM NUMBER

B42 WAITING AREA 3 J,K DIRECTIONAL

B43 PHYSICIAN/PA/ RES/INTERN 4 C MEDICAL OFFICES

B44 TELECOM 5 A ROOM NUMBER

B45 TELE DATA 5-A A ROOM NUMBER

B46 ELEC 6 A ROOM NUMBER

B47 STAFF LOCKERS 8 B STAFF LOCKERS

B48 STAFF LOUNGE 9 B STAFF LOUNGE

B49 STAFF UNISEX 10 F GRAPHIC - RESTROOM

B50 PATIENT UNISEX 11 F GRAPHIC - RESTROOM

B51 ED COORD & DIETITIAN 13 C EDUCATION COORDINATOR DIETITIAN

B52 CHIEF NURSE 14 C CHIEF NURSE

B53 CHIEF OFFICE 15 C CHIEF OFFICE

B54 TRAIN/ PROG RM 16 C TRAINING

B55 CLEAN LINEN 17 B CLEAN LINEN

B56 DIALYSIS 18 C DIALYSIS

B56.1 DIALYSIS CIRCULATION --- ---

B56.2 NURSE STATION 18-A A,A ROOM NUMBER

B57 NOURISH 19 B NOURISMENT

B58 TLT 20 F GRAPHIC - RESTROOM

B59 EXAM/ TREAT 21 B EXAM ROOM

B60 MED PREP 22 B MED PREP

B61 ISOLATION ROOM 23 B ISOLATION ROOM

B62 ISOLATION TLT 23-A A ROOM NUMBER

B63 PRIVATE ROOM 24 B PRIVATE ROOM

B64 PRIVATE TLT 24-A A ROOM NUMBER

B65 EQUIP STOR 25 B EQUIPMENT STORAGE

B66 WATER TREATMENT 26 B WATER TREATMENT

B67 DIALYSATE PREP 27-A B DIALYSATE PREP

B68 BIO-MED REPAIR 27 B BIOMED REPAIR

B69 UTIL, STERILE, CLEAN 28 B UTILITY CLEAN STORAGE

B70 UTIL SOILED 30 B UTILITY SOILED

B71 SOILED REC 31 B EQUIPMENT SOILED RECEIVING

B72 CLEAN PREP 32 B EQUIPMENT CLEAN PREP

B73 CLEAN STORAGE 33 B EQUIPMENT CLEAN STORAGE

B74 ELEC. 34 A ROOM NUMBER

B75 ELEC. 35 A ROOM NUMBER

B76 HVAC 36 A,K ROOM NUMBER, PRINTED NOTICE

CB-2A CORRIDOR CB-2A J, G

CB-2B CORRIDOR CB-2B ---

CB-2C CORRIDOR CB-2C I PRINTED NOTICE

CB-9 CORRIDOR CB-9 J,I CORRIDOR NUMBER, PRINTED NOTICE

CB-10 CORRIDOR CB-3 J,J CORRIDOR NUMBER

CB-11 CORRIDOR CB-11 J CORRIDOR NUMBER

CB-12 CORRIDOR CB-4 J,J,K CORRIDOR NUMBER, PRINTED NOTICE

SIGNAGE SCHEDULE

IN-03.01 B DC E F

G

H I J

Braille Grade 2 Domed

Copy Helvetica Medium raised tactile text

Baseline spacing

3/8" Min. clear space 1/8" Min.

Letter Spacing

3/8" Min. clear space

1 1/4" height 3/8" Min. clear space, Approx 1/4"

3/8" Min clear spacing 1/2"

3/8" Min. clear space

9" 229 mm 3/4" 19mm

3" 76 mm

6" 152 mm

3" 76 mm

3/4" 19mm

1/2" 12.7 mm 1 1/4" 31.8 mm

3/8" 9.5mm 1/4"

9" 229 mm

3/4" 19mm

9" 229 mm 3/4" 19mm

1/2" 12.7 mm 1 1/4" 31.8 mm

3/8" 9.5mm 1/4"

3" 76 mm

3/4" 19mm

9" 229 mm

3/4" 19mm

3/4" 19 mm 3/4" 19 mm 1/4"

9" 229 mm 3/4" 19mm

1/2" 12.7 mm 1 1/4" 31.8 mm

3" 76 mm 3/8" 9.5mm

3/4" 9 mm

9 1/4" 229 mm 6" Icon area

152.4 mm

3/4" 9 mm 1" 25 mm

15" 476 mm

30" 762 mm

1'0" 305 mm

1" 25.4 mm

1" 25.4 mm

15/18" 41.3 mm

1'-8" 508 mm

10" 260.4 mm

DIGITAL PRINT

"YOU ARE HERE"

MAP

9" 229 mm

1 1/8" 28.5 mm

6 1/2" 165 mm

6 1/2" 165 mm

1'8" 508 mm

1'6" 457 mm

A

IN-04.04 IN-04.03 IN-09.01 IN-09.02 IN-09.03

IN-11.01 IN-08.02 IN-14.00

IN-14.18 K

IN-02.01

IN-02.02

IN-02.03

.1'6" 456 mm

20" 508 mm