36C24218B0125-0003001.pdf
PDF 1 MB Posted
- Attached to
- Renovate 6C for Mental Health
- Solicitation number
- 36C24218B0125
About this file
36C24218B0125 0003 S06 - 100=ES201 Bulletin#1 - Corrected Drawing.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24219C0071-001.docx | DOCX document | |
| 36C24218B0125-0005000.docx | DOCX document | |
| 36C24218B0125-0004000.docx | DOCX document | |
| 36C24218B0125-0004001.pdf | ||
| 36C24218B0125-0004002.pdf | ||
| 36C24218B0125-0003003.pdf | ||
| 36C24218B0125-0003002.pdf | ||
| 36C24218B0125-0003000.docx | DOCX document | |
| 36C24218B0125-0002000.docx | DOCX document | |
| 36C24218B0125-0001000.docx | DOCX document | |
| 36C24218B0125-012.zip | ZIP file | |
| 36C24218B0125-010.docx | DOCX document | |
| 36C24218B0125-013.docx | DOCX document | |
| 36C24218B0125-011.pdf | ||
| 36C24218B0125-000.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
1. REFER TO DWG. 100-EP501 FOR EMERGENCY CIRCUIT WIRING DETAIL LABELED
ALL EMERGENCY LIGHTING CIRCUITS SHALL BE INSTALLED AT AN ACCESSIBLE
LOCATION.
2. SEE LIGHTING CONTROL DETAIL ON DWG. 100-EP501 FOR WIRING DETAIL AND
SYMBOLS FOR
3. EXIT LIGHTS ARE NOT TO BE DIMMED. WIRE DIRECTLY TO CIRCUIT BREAKER.
4. ALL EMERGENCY LIGHTS SHALL BE DUAL CIRCUIT VIA THE EMERGENCY RELAY.
(CIRCUIT SHOWN AND CIRCUIT FOR LIGHTS IN AREA) SEE DETAIL ON DRAWING
100-EP501.
KEY NOTES:
FOR ALL PATIENT BEDROOMS, TYPICAL SWITCH
LOCATION AND CONTROL FOR 1BR PATIENT (U.O.N.)
TYPICAL SWITCH LOCATION AND CONTROL FOR 2BR
PATIENT (U.O.N.)
LIGHT CONTROL PANEL "LCP" DETAIL
NOT TO SCALE
LIGHTING CONTROL SPECIFICATIONS:
1. LIGHTING CONTROL CABINET SHALL BE AS MANUFACTURED BY LEVITON GREENMAX
OR APPROVED EQUAL .
2. SYSTEM SHALL BE INCLUDING BUT NOT LIMITED TO ENCLOSURE, COMMAND
MODULE, RELAY INSERT PANELS, ASTRONOMICAL TIMECLOCK SCHEDULER AND ALL
OTHER APPURTENANCES REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM
AS DESIGNED.
3. THE CABINET DOOR SHALL OPEN TO EXPOSE LOW VOLTAGE ELEMENTS OF THE
SYSTEM. ACCESSING 120/277V SECTION SHALL REQUIRE REMOVAL OF RETAINING
SCREWS.
4. RELAY MODULES SHALL HAVE A MINIMUM OF 18,000A SHORT CIRCUIT RATING AT
277V.
5. RELAY MODULES SHALL BE RATED AT 30A FOR GENERAL FLUORESCENT BALLASTS
AND 20A FOR INCANDESCENT.
6. RELAY MODULES SHALL HAVE A MANUAL ACTUATION LEVER TO ALLOW USER TO
MANUALLY BYPASS THE SYSTEM TO TURN ON LIGHTS.
7. INTERNAL COMPONENTS SHALL BE FACTORY PRE-WIRED AND TESTED.
8. SYSTEM SHALL BE UL 50BM CA2013 TITLE 24 AND ASHRAE 90.1 COMPLIANT AND
LISTED.
9. RELAY MODULES SHALL BE BACKED BY 10 YEAR WARRANTY; RELAY PANELS SHALL
BE BACKED BY 2 YEAR WARRANTY
10. ENCLOSURE SHALL BE NEMA 1 TYPE, 1P-20 PROTECTION; #16 US GUAGE STEEL FOR
INDOOR ONLY. MOUNTING SHALL BE SURFACE.
11. REFER TO "LCP" RELAY SCHEDULE ON DRAWING.
12. PROVIDE 1 SPARE RELAYS AS SHOWN ON SCHEDULE.
13. MANUFACTURER SHALL PROVIDE MINIMUM 2 WEEKS SETUP, TRAIN AND
COMMISSION SYSTEM.
CIRCUITING LEGEND:
A - L6C (NORMAL 480V)
B - P6C (CRITICAL 208V)
C - E6C (LIFE SAFETY 480V)
D - EL6C (LIFE SAFETY 208V)
E - NL-6C-1 (NORMAL 208V)
F - EQ6C-1 (EQUIPMENT 277/480V)
EXAMPLE: A/1 - PANEL L6C, CIRCUIT 1