36C24218B0125-0003001.pdf

PDF 1 MB Posted

Attached to
Renovate 6C for Mental Health
Solicitation number
36C24218B0125
Issued by

About this file

36C24218B0125 0003 S06 - 100=ES201 Bulletin#1 - Corrected Drawing.pdf

View the file

Other files

File Type Posted
36C24219C0071-001.docx DOCX document
36C24218B0125-0005000.docx DOCX document
36C24218B0125-0004000.docx DOCX document
36C24218B0125-0004001.pdf PDF
36C24218B0125-0004002.pdf PDF
36C24218B0125-0003003.pdf PDF
36C24218B0125-0003002.pdf PDF
36C24218B0125-0003000.docx DOCX document
36C24218B0125-0002000.docx DOCX document
36C24218B0125-0001000.docx DOCX document
36C24218B0125-012.zip ZIP file
36C24218B0125-010.docx DOCX document
36C24218B0125-013.docx DOCX document
36C24218B0125-011.pdf PDF
36C24218B0125-000.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. REFER TO DWG. 100-EP501 FOR EMERGENCY CIRCUIT WIRING DETAIL LABELED

ALL EMERGENCY LIGHTING CIRCUITS SHALL BE INSTALLED AT AN ACCESSIBLE

LOCATION.

2. SEE LIGHTING CONTROL DETAIL ON DWG. 100-EP501 FOR WIRING DETAIL AND

SYMBOLS FOR

3. EXIT LIGHTS ARE NOT TO BE DIMMED. WIRE DIRECTLY TO CIRCUIT BREAKER.

4. ALL EMERGENCY LIGHTS SHALL BE DUAL CIRCUIT VIA THE EMERGENCY RELAY.

(CIRCUIT SHOWN AND CIRCUIT FOR LIGHTS IN AREA) SEE DETAIL ON DRAWING

100-EP501.

KEY NOTES:

FOR ALL PATIENT BEDROOMS, TYPICAL SWITCH

LOCATION AND CONTROL FOR 1BR PATIENT (U.O.N.)

TYPICAL SWITCH LOCATION AND CONTROL FOR 2BR

PATIENT (U.O.N.)

LIGHT CONTROL PANEL "LCP" DETAIL

NOT TO SCALE

LIGHTING CONTROL SPECIFICATIONS:

1. LIGHTING CONTROL CABINET SHALL BE AS MANUFACTURED BY LEVITON GREENMAX

OR APPROVED EQUAL .

2. SYSTEM SHALL BE INCLUDING BUT NOT LIMITED TO ENCLOSURE, COMMAND

MODULE, RELAY INSERT PANELS, ASTRONOMICAL TIMECLOCK SCHEDULER AND ALL

OTHER APPURTENANCES REQUIRED FOR A COMPLETE AND FUNCTIONAL SYSTEM

AS DESIGNED.

3. THE CABINET DOOR SHALL OPEN TO EXPOSE LOW VOLTAGE ELEMENTS OF THE

SYSTEM. ACCESSING 120/277V SECTION SHALL REQUIRE REMOVAL OF RETAINING

SCREWS.

4. RELAY MODULES SHALL HAVE A MINIMUM OF 18,000A SHORT CIRCUIT RATING AT

277V.

5. RELAY MODULES SHALL BE RATED AT 30A FOR GENERAL FLUORESCENT BALLASTS

AND 20A FOR INCANDESCENT.

6. RELAY MODULES SHALL HAVE A MANUAL ACTUATION LEVER TO ALLOW USER TO

MANUALLY BYPASS THE SYSTEM TO TURN ON LIGHTS.

7. INTERNAL COMPONENTS SHALL BE FACTORY PRE-WIRED AND TESTED.

8. SYSTEM SHALL BE UL 50BM CA2013 TITLE 24 AND ASHRAE 90.1 COMPLIANT AND

LISTED.

9. RELAY MODULES SHALL BE BACKED BY 10 YEAR WARRANTY; RELAY PANELS SHALL

BE BACKED BY 2 YEAR WARRANTY

10. ENCLOSURE SHALL BE NEMA 1 TYPE, 1P-20 PROTECTION; #16 US GUAGE STEEL FOR

INDOOR ONLY. MOUNTING SHALL BE SURFACE.

11. REFER TO "LCP" RELAY SCHEDULE ON DRAWING.

12. PROVIDE 1 SPARE RELAYS AS SHOWN ON SCHEDULE.

13. MANUFACTURER SHALL PROVIDE MINIMUM 2 WEEKS SETUP, TRAIN AND

COMMISSION SYSTEM.

CIRCUITING LEGEND:

A - L6C (NORMAL 480V)

B - P6C (CRITICAL 208V)

C - E6C (LIFE SAFETY 480V)

D - EL6C (LIFE SAFETY 208V)

E - NL-6C-1 (NORMAL 208V)

F - EQ6C-1 (EQUIPMENT 277/480V)

EXAMPLE: A/1 - PANEL L6C, CIRCUIT 1