This solicitation is for a renovation project at the U.S. Treasury building to establish new office space and infrastructure for the Committee on Foreign Investment in the United States (CFIUS). The scope of work includes renovations to the 5th floor for Phase 2 and Phase 4A and will provide new office space and build-outs for CFIUS employees. Key requirements include interior demolition, new walls, lighting, power, fire protection, HVAC, and telecommunications infrastructure. The solicitation provides architectural and engineering drawings detailing the demolition and new construction work. A site visit is available and offerors must be able to obtain all required permits and approvals. The period of performance is 120 days from NTP. The Treasury Department and Internal Revenue Service are the contracting agencies.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A - 605
SIGNAGE
1/2"= 1'-0"
0 1'
2'
4'
SIGNAGE
OCCUPANCYOFFICE / ROOM
VESTIBULE
INNER VESTIBULE
VESTIBULE
CONFERENCE ROOM
SUITE
5206 TELECOM
5211 OPEN OFFICE
OCCUPANCY
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
5316 OFFICE
OFFICE
OFFICE
OCCUPANT OCCUPANTCUBICLE
5211-A
5211-B
5211-C
5211-D
5211-E
5211-F
5211-G
5211-H
5211-I
5211-J
5211-K
5211-L
5211-M
5211-N
5211-O
5211-P
5211-Q
5211-R
5211-S
5211-AA
5211-BB
5211-CC
5211-DD
5211-EE
5211-FF
5211-GG
5211-HH
5313-A
5313-B
5211-X
5211-Y
5211-Z
OCCUPANTCUBICLE
5211-T
5211-U
5211-V
5211-W
5211-S
OFFICE NUMBER
R E
V I S
I O
N
N
O T
E S
GR
AP
HI
C
SC
AL
E
MARK DATE DESCRIPTION
AGF
SHEET SIZE:
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
2 3 4 5
2 3 4 5
A
B
C
D
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
LSP
CRAIG GARDNER
09/15/2018
5TH FLOOR
0019-13
08 DECEMBER 2019
100%
CERTIFICATIONSKEY PLAN
D O W N
D O W N
N
MIDDLE
SOUTH
COURTYARD
SOUTH
COURT
FEDERAL OFFICE BUILDING 5TH FLOOR
MIDDLE & SOUTH COURTYARD WINGS RENOVATION
INTERIOR SPACE RENOVATION
MERIDIEN GROUP, LLC
208 SOUTH KING ST. SUITE 303
LEESBURG, VA 20175
(703) 777-8285 www.meridiengroupllc.com
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
/26 /20
:01 :04
P M
XX
X.
XX
.03
F-
1.D
W G
F-001
SYMBOLS AND ABBREVIATIONS
1901.03 - F-001.dwg
SYMBOLS FIRE ALARM NOTES
1. THE AUTHORITY HAVING JURISDICTION (AHJ) IS THE TREASURY COR.
2. PROVIDE ALL FIRE ALARM DEVICES AND APPLIANCES THAT ARE COMPATIBLE WITH THE EXISTING
EDWARDS EST FIRE ALARM CONTROL PANEL AND EQUIPMENT AND IN ACCORDANCE WITH NFPA 72
REQUIREMENTS.
3. ALL NEW CIRCUITS OR PATHWAYS MUST BE SIMILAR IN CLASS & STYLE TO THE EXISTING CIRCUITS OR
PATHWAYS. PERFORMANCE FEATURES MUST BE MAINTAINED.
4. NEW NOTIFICATION APPLIANCES WILL BE CONNECTED TO THE NEAREST NOTIFICATION APPLIANCE CIRCUIT CAPABLE OF ACCEPTING THE ADDITIONAL LOAD. IF THE EXISTING CIRCUITS CANNOT
ACCOMMODATE THE ADDITIONAL APPLIANCES, A NEW EXTENDER PANEL/AMPLIFIER WILL BE
PROVIDED.
4.1 CONTRACTOR SHALL METER AND IDENTIFY THE EXISTING NOTIFICATION CIRCUIT TO CONNECT
THE ADDITIONAL NOTIFICATION APPLIANCES. THIS MAY REQUIRE ACTUAL TRACING OF THE
CIRCUITS AND AFTER-HOURS LOAD AND VOLTAGE TESTING. CONTRACTOR SHALL PROVIDE
EXISTING LOAD DATA TO THE AHJ FOR REVIEW AND APPROVAL.
4.2 IN LIEU OF METERING THE EXISTING CIRCUITS, THE CONTRACTOR MAY PERFORM LOAD
CALCULATIONS TO CONFIRM ADEQUATE CIRCUIT CAPACITY TO TIE IN THE ADDITIONAL
NOTIFICATION APPLIANCES. SUBMIT THE CALCULATIONS TO THE AHJ FOR REVIEW AND
APPROVAL.
4.3 ALL LOADING CALCULATIONS NEED TO BE BASED UPON THE AVERAGE LOAD RATING FOR EACH CIRCUIT, AND NOT THE MAXIMUM RATING FOR EACH CIRCUIT. (I.E. A 6.5 AMP TOTAL BPS, WITH FOUR CLASS B CIRCUITS, SHOULD HAVE THEIR SPARE CAPACITY CALCULATED FROM THE 1.625 A AVERAGE, AND NOT A 3 A MAXIMUM RATING. IN THIS EXAMPLE, NO CIRCUIT SHOULD BE DESIGN
LOADED TO MORE THAN 1.3 A.)
5. SHOP DRAWING DESIGN SHALL BE BY A NICET LEVEL III OR IV FIRE ALARM TECHNICIAN OR A
REGISTERED FIRE PROTECTION ENGINEER. INSTALLATION SHALL BE ACCOMPLISHED BY AN
ELECTRICAL CONTRACTOR WITH A MINIMUM OF FIVE YEARS EXPERIENCE IN THE INSTALLATION OF
FIRE ALARM SYSTEMS.
6. CONDUCTORS MUST MATCH EXISTING IN GAUGE, TYPE AND COLOR CODING. ALL CONDUCTORS WHICH ARE TERMINATED, SPLICED, OR OTHERWISE INTERRUPTED IN ANY ENCLOSURE, CABINET, MOUNTING OR JUNCTION BOX SHALL BE CONNECTED TO TERMINAL BLOCKS. USE OF WIRE NUTS IS
PROHIBITED.
7. INSTALL ALL CONDUCTORS IN RIGID METAL CONDUIT OR ELECTRICAL METALLIC TUBING, WITH A MINIMUM DIAMETER OF 3/4". RUN CONDUIT OR TUBING CONCEALED UNLESS SPECIFICALLY SHOWN OTHERWISE ON THE DRAWINGS. ALL WIRING FOR THE FIRE ALARM SYSTEM MUST BE INSTALLED IN SEPARATE CONDUIT. NO OTHER BUILDING WIRING IS PERMITTED IN CONDUIT THAT CONTAINS FIRE ALARM WIRING. ALL CONDUIT MUST BE PROPERLY SUPPORTED FROM THE STRUCTURE, AND MUST BE MARKED OR BANDED (RED) EVERY 10 FEET. ALL JUNCTION OR PULL BOXES MUST BE PAINTED RED
AND MARKED “FA”.
8. SUBMIT CERTIFIED SHOP DRAWINGS BY A FIRE ALARM ENGINEER (HALF SIZE) WHICH SHALL INCLUDE
THE FOLLOWING:
8.1 POINT TO POINT WIRING DIAGRAMS SHOWING THE POINTS OF CONNECTION AND TERMINALS
USED FOR ALL ELECTRICAL FIELD CONNECTIONS IN THE SYSTEM, INCLUDING ALL
INTERCONNECTIONS BETWEEN THE EQUIPMENT OR SYSTEMS WHICH ARE SUPERVISED OR
CONTROLLED BY THE SYSTEM.
8.2 INCLUDE ANNOTATED CATALOG DATA SHOWING MANUFACTURER'S NAME, MODEL, VOLTAGE,
AND CATALOG NUMBERS FOR ALL EQUIPMENT AND COMPONENTS.
8.3 INCLUDE BATTERY CALCULATIONS FOR BOTH THE ALARM AND SUPERVISORY POWER
REQUIREMENTS. AMPERE-¬HOUR REQUIREMENTS FOR EACH SYSTEM COMPONENT SHALL BE
SUBMITTED WITH THE CALCULATIONS.
8.4 CAPACITY: PROVIDE THE BATTERIES WITH SUFFICIENT CAPACITY TO OPERATE ALL SIGNALING LINE CIRCUITS, INITIATING DEVICE CIRCUITS, AND NOTIFICATION APPLIANCE CIRCUITS IN NORMAL
OR SUPERVISORY (NON-ALARM) MODE FOR A PERIOD OF 24 HOURS. FOLLOWING THIS PERIOD
OF OPERATION ON BATTERY POWER, THE BATTERIES SHALL HAVE SUFFICIENT CAPACITY TO
OPERATE ALL COMPONENTS OF THE SYSTEM IN ALARM MODE FOR A PERIOD OF FIFTEEN (15)
MINUTES. BATTERY CAPACITY CALCULATIONS SHALL BE BASED ON EQUIPMENT CURRENT DRAW
AT A MINIMUM OPERATING VOLTAGE OF 24 VDC. PROVIDE BATTERIES SIZED AT 150% OF FIRE
ALARM MANUFACTURER'S CALCULATIONS.
8.5 PROVIDE A COLOR CODE SCHEDULE FOR THE WIRING AND FLOOR PLANS SHOWING THE
LOCATION OF ALL DEVICES AND EQUIPMENT.
8.6 THE SIGNATURE AND SEAL OF A REGISTERED PROFESSIONAL FIRE PROTECTION ENGINEER, REGISTERED PROFESSIONAL ENGINEER WITH A MINIMUM OF TWO YEARS FIRE PROTECTION
DESIGN EXPERIENCE, OR A NICET LEVEL III OR IV TECHNICIAN.
9. THE TREASURY COR, MUST BE CONTACTED TO SCHEDULE AND OUTAGE BEFORE ANY WORK WHICH
COULD AFFECT THE FIRE ALARM SYSTEM, IS PERMITTED.
10. WHEN THE CONTRACTOR WORKS ON THE FIRE ALARM CIRCUITS, THE SYSTEM MUST BE TAKEN OUT-OF-SERVICE BY THE TREASURY PM COR, AND THE SYSTEM MUST BE RETURNED TO "NORMAL"
BEFORE THE ELECTRICIANS/CONTRACTORS LEAVE FOR THE DAY.
11. NO FIRE ALARM CIRCUIT TIE-IN IS PERMITTED WITHOUT TREASURY COR PRESENCE.
12. FIRE ALARM PROGRAMMING CHANGES ARE PERMITTED ONLY WHEN CONFIRMED ACCEPTANCE
TESTING IS SCHEDULED WITH THE AHJ. A FIRE ALARM PROGRAM CHANGE MUST BE ACCEPTANCE
TESTED WITHIN 24 HOURS OF THE CHANGE.
13. FINAL TESTING: NOTIFY THE CONTRACTING OFFICER IN WRITING WHEN THE SYSTEM IS READY FOR FINAL ACCEPTANCE TESTING. SUBMIT THE REQUEST FOR TESTING AT LEAST 5 CALENDAR DAYS PRIOR TO TEST DATE. THE FINAL TESTS SHALL BE WITNESSED BY A REPRESENTATIVE OF THE
TREASURY COR. AT THIS TIME, ANY AND ALL REQUIRED TESTS SHALL BE REPEATED AT THE
DISCRETION OF THE GOVERNMENT.
14. SUBMIT AS-BUILT DRAWINGS TO THE COR UPON COMPLETION OF THE PROJECT. THESE DRAWINGS
SHALL INDICATE CHANGES FROM THE ORIGINAL LAYOUT, MARKED IN RED.
FIRE ALARM WALL MOUNTED COMBINATION STROBE / HORN.
FIRE ALARM WALL MOUNTED COMBINATION STROBE / HORN.
SPRINKLER HEAD.
SIDEWALL SPRINKLER HEAD.
SMOKE DETECTOR;
MNT=MOUNTING LOCATION, TY=TYPE
FIRE ALARM STROBE- CEILING MOUNTED;
CD=CANDELA RATING
SPEAKER
SPRINKLER SYSTEM NOTES
1. THE WORK INCLUDES MODIFYING THE EXISTING WET-PIPE AUTOMATIC SPRINKLER SYSTEM TO
AFFORD COMPLETE FIRE PROTECTION THROUGHOUT THE AREAS INDICATED. THE INSTALLATION
SHALL BE MADE IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13.
2. DESIGN SHALL BE BY A NICET LEVEL III OR IV TECHNICIAN OR A REGISTERED FIRE PROTECTION ENGINEER. INSTALLATION SHALL BE PERFORMED BY A CERTIFIED SPRINKLER CONTRACTOR OR A SPECIALIST WHO IS EXPERIENCED IN THE DESIGN AND INSTALLATION OF AUTOMATIC SPRINKLER SYSTEMS (MINIMUM 3 YEARS). THE SYSTEM SHALL BE DESIGNED PER THE HYDRAULIC CALCULATION
METHOD.
3. LOCATION OF SPRINKLER HEADS: THE SPACING OF SPRINKLER HEADS SHALL NOT EXCEED THAT
PERMITTED BY NFPA 13 FOR THE HAZARD OCCUPANCY.
4. STEEL PIPING WITH WALL THICKNESS LESS THAN SCHEDULE 30 SHALL NOT BE THREADED. PLASTIC PIPING SHALL NOT BE PERMITTED. MINIMUM PIPE SCHEDULE SHALL BE SCHEDULE 10. PLAIN END
FITTINGS ARE NOT PERMITTED. PIPE 2.5” AND SMALLER MUST BE SCHEDULE 40.
5. PIPE AND HANGER SUPPORTS: PROVIDE PIPE SUPPORTS, SWAY BRACES, HANGERS, AND CLAMPS IN
ACCORDANCE WITH NFPA 13.
6. SPRINKLER HEADS SHALL BE IN CONFORMANCE WITH NFPA 13. RELEASE ELEMENTS SHALL BE SUITABLE FOR SPECIFIC APPLICATION AND SHALL MATCH EXISTING. PROVIDE QUICK RESPONSE HEADS IN ALL OCCUPANCIES IN WHICH THEIR USE IS LISTED OR APPROVED. HEADS LOCATED WITHIN THE AIR STREAMS OF UNIT HEATERS OR OTHER HEAT EMITTING EQUIPMENT OR SKYLIGHTS SHALL BE
SELECTED FOR PROPER TEMPERATURE RATING.
7. MANUFACTURER'S DATA SHALL BE PROVIDED AND ANNOTATED TO SHOW THE SPECIFIC MODEL, TYPE
AND SIZE OF EACH ITEM.
8. SHOP DRAWINGS: SUBMIT DETAILED SHOP DRAWINGS CERTIFIED BY A SPRINKLER ENGINEER, IN ACCORDANCE WITH NFPA 13, "WORKING PLANS". DRAWINGS SHALL BE HALF SIZED, TO THE COR FOR REVIEW AND APPROVAL. INFORMATION SHALL INCLUDE BUT IS NOT LIMITED TO THE FOLLOWING:
8.1. LAYOUT INDICATING DETAILS, PLAN VIEW, ELEVATIONS AND SECTIONS OF THE SYSTEM PIPING.
INDICATE THE LOCATION OF SPRINKLER HEADS AND PIPING IN RELATION TO THE CEILING AND
STRUCTURE LAYOUT, SHOWING PIPE LENGTHS AND SIZES.
9. FINAL INSPECTION AND TESTING: ADVISE THE COR WHEN HYDROSTATIC AND ALARM TESTS HAVE BEEN COMPLETED AND ALL NECESSARY CORRECTIONS MADE, SO AS TO PERMIT FINAL INSPECTION AND TESTING. SUBMIT REQUEST FOR TESTING AT LEAST 15 CALENDAR DAYS PRIOR TO TEST DATE.
9.1. THE FINAL TEST SHALL BE WITNESSED BY THE TREASURY COR. THE CONTRACTOR AND AN
AUTHORIZED REPRESENTATIVE FROM EACH SUPPLIER OF EQUIPMENT SHALL BE IN ATTENDANCE
AT THE FINAL TEST.
9.2. FINAL TESTING SHALL INCLUDE, BUT IS NOT LIMITED TO, TESTING OF ALL WATERFLOW AND
TAMPER SWITCHES.
9.3. PROVIDE ALL EQUIPMENT, SERVICES AND LABOR TO PROPERLY PERFORM ALL REQUIRED TESTS.
THE TREASURY COR SHALL SUPERVISE ALL TESTING.
10. SUBMIT AS-BUILT DRAWINGS TO THE COR UPON COMPLETION OF THE PROJECT. THESE DRAWINGS
SHALL INDICATE CHANGES FROM THE ORIGINAL LAYOUT, MARKED IN RED.
11. THE AUTHORITY HAVING JURISDICTION (AHJ) IS THE TREASURY COR.
12. RELOCATED SPRINKLERS: PER NFPA 13, 6.2.1.1: WHEN A SPRINKLER HAS BEEN REMOVED FOR ANY
REASON, IT SHALL NOT BE REINSTALLED.
13. THE TREASURY COR MUST BE CONTACTED 1 WEEK IN ADVANCE TO SCHEDULE AN OUTAGE BEFORE
ANY WORK WHICH COULD AFFECT THE SPRINKLER SYSTEM, IS PERMITTED.
CD
MNT
TY
C
W
NON-SECURE SIDE SECURE SIDE
SLAB ABOVE
SECURE SIDENON-SECURE SIDE
CONDUIT/PIPE
DIELECTRIC FITTING/COUPLING, WITH NO METAL TO METAL
CONTACT FROM ONE SIDE OF BARRIER TO THE OTHER.
CONDUIT/PIPE
IDEAL IND. MODEL "J" PIPE CLAMP OR
EQUAL. GROUND TO GROUND
BUS SHOWN ON SHEET E-102 WITH
#8 CONDUCTOR.
FLOOR
6" MAX
S
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
F-101,102,103,104 F-001 DETAIL
SECURE WALL PENETRATION
NO SCALE
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
AutoCAD SHX Text
KEY PLAN
F
W
W
F
W
1 1
W
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:01 :18
P M
XX
X.
XX
.03
F D1
.D
W G
FD101
EP
KU
10/14/2019
5TH FLOOR - FIRE ALARM DEMOLITION
1901.03 FD101.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
5TH FLOOR NORTH - FIRE ALARM DEMOLITION
8'0 16' 1/8"=1'-0"
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. DEMOLITION DEFINITION: DISCONNECTION AND REMOVAL OF ASSOCIATED
CONDUCTORS SHALL CONSIST OF THE REMOVAL OF THE CONDUCTORS
BACK TO THE NEXT EXISTING DEVICE TO REMAIN, NEW CONDUIT AND
CONDUCTORS SHALL BE PROVIDED TO RECONNECT ANY EXISTING TO
REMAIN DEVICES INTERRUPTED BY THE DEMOLITION UNDER THIS PROJECT.
NOTES
1. PRIOR TO ANY SCHEDULES FIRE ALARM OUTAGE, COORDINATE WITH
THE AHJ AND RECEIVE WRITTEN APPROVAL 3 WEEKS PRIOR TO THE
OUTAGE. ALL LOCAL FIRE ALARM OUTAGES LONGER THAN 4 HOURS
MUST BE PROVIDED WITH A CONTINUOUS MANUAL FIRE WATCH UNTIL
THE EXISTING SYSTEM IS RECONNECTED AND OPERATING AS BEFORE.
PRIOR TO THE WORK, TEMPORARILY DISABLE THE ASSOCIATED
ADDRESSES IN THE EXISTING FIRE ALARM CONTROL PANEL DURING
THE WORK OUTAGE. REPROGRAM THE EXISTING FIRE ALARM CONTROL
PANEL TO ELIMINATE UNUSED ADDRESSES AS REQUIRED. INTERCEPT
THE EXISTING FIRE ALARM BRANCH CIRCUIT WIRING, DISCONNECT AND
REMOVE FIRE ALARM DEVICE INDICATED. PROVIDE A NEW FIRE ALARM
JUNCTION BOX WITH SCREW-DOWN TERMINAL STRIPS AND A PAINTED
RED COVER PLATE LOCATED IN LINE WITH THE EXISTING FIRE ALARM
CONDUIT RUN ABOVE THE SUSPENDED TILE CEILING. EXTEND AND
CONNECT THE FIRE ALARM BRANCH CIRCUIT WIRING TO OPERATE AS
BEFORE. ALL FIRE ALARM BRANCH CIRCUIT WIRING SHALL BE RUN
CONTINUOUS. ALL FIRE ALARM CONNECTIONS SHALL BE SCREW-DOWN
TERMINALS, WIRE NUT CONNECTIONS ARE PROHIBITED. RE-ENABLE THE
EXISTING FIRE ALARM ADDRESSES AT THE EXISTING FIRE ALARM
CONTROL PANEL TO OPERATE AS BEFORE.
N
8'0 16' 1/8"=1'-0"
5TH FLOOR SOUTH - FIRE ALARM DEMOLITION
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:01 :32
P M
XX
X.
XX
.03
F D1
.D
W G
FD102
EP
KU
10/14/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. THE SPRINKLER LAYOUT SHOWN IS EXISTING. ALL SPRINKLER HEADS
AND ASSOCATED PIPING IN THE AREA OF WORK ARE TO BE
DEMOLISHED AS REQUIRED TO PERFORM WORK.
5TH FLOOR - FIRE PROTECTION DEMOLITION
1901.03 FD102.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
5TH FLOOR NORTH - FRE PROTECTION DEMOLITION
8'0 16' 1/8"=1'-0"
N
8'0 16' 1/8"=1'-0"
5TH FLOOR SOUTH - FIRE PROTECTION DEMOLITION
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
C
C
C
C
C
C
FF
F
C
C
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:01 :46
P M
.03
.03
F -1
.D
W G
X
F-101
AM
JG
XX/XX/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. ALL CONDUIT PENETRATIONS THROUGH THE WALL INDICATED SHALL BE
PER DETAIL 1/F-001.
5TH FLOOR - FIRE ALARM
1901.03 F-101.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
5TH FLOOR NORTH - FIRE ALARM
8'0 16' 1/8"=1'-0"
N
8'0 16' 1/8"=1'-0"
5TH FLOOR SOUTH - FIRE ALARM
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
2 3
2 3
2 3
1 2
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:01 :59
P M
XX
X.
XX
.03
F X-
1.D
W G
F-102
AM
JG
10/14/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. PROVIDE PIPING BY HYDRAULIC CALCULATION FOR LIGHT HAZARD, PIPE
SIZES AND LAYOUT INDICATED ARE EXISTING. PROVIDE FIRE
SUPPRESSION SYSTEM AS REQUIRED BY NOTES ON F-001.
2. MODIFY THE EXISTING WET-PIPE AUTOMATIC SPRINKLER SYSTEM TO
AFFORD COMPLETE FIRE PROTECTION TO THE AREA INDICATED. SEE
SPRINKLER SYSTEM NOTES ON F-001.
3. ALL CONDUIT PENETRATIONS THROUGH THE WALL INDICATED SHALL BE
PER DETAIL 1/F-001.
5TH FLOOR - FIRE PROTECTION
1901.03 FX-101.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
5TH FLOOR NORTH - FIRE PROTECTION
8'0 16' 1/8"=1'-0"
N
8'0 16' 1/8"=1'-0"
5TH FLOOR SOUTH - FIRE PROTECTION
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
(E)
LC
ABBREVIATIONS CONT. SYMBOLS CONT. SYMBOLS CONT. SYMBOLS CONT.
ABBREVIATIONS
SYMBOLS
SINGLE LINE PIPE REPRESENTING A
4-PIPE SYSTEM; CWS, CWR, HWS & HWR.
R
PRIMARY CHILLED WATER RETURNPCWR
PCWS PRIMARY CHILLED WATER SUPPLY
REFRIGERANT LIQUIDRL
RS REFRIGERANT SUCTION
SECONDARY CHILLED WATER RETURNSCWR
SCWS SECONDARY CHILLED WATER SUPPLY
SP SPRINKLER PIPING
PIPE TURN UP
PIPE TURN DOWN
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
DIRECTION OF FLOW
PIPE CAP
PIPE CLEANOUT
WALL PIPE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
C.O.
W.C.O.
F.C.O.
FL.D.
GATE VALVE
GLOBE VALVE
SWING CHECK VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
STRAINER
UNION
PRESSURE REDUCING VALVE
SAFETY RELIEF VALVE
O.S.&Y VALVE
MOTORIZED O.S.&Y VALVE
FLOW MEASURING VALVE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
MOTORIZED BUTTERFLY VALVE
BACKFLOW PREVENTER
MANUAL AIR VENT 3/8" BALL VALVEM.A.V.
THERMOMETER AND WELL
PRESSURE GAUGE
2-WAY PLUG VALVE
RECTANGULAR DUCT
SIZE TRANSITION
RIGID ROUND DUCT
SIZE TRANSITION
DUCT TRANSITION FROM
SQUARE TO ROUND
DUCT WITH 1/2"x1/2" WOVEN WIRE
MESH SCREEN WITH HEMMED EDGES.
DUCT ELBOW WITH
TURNING VANES
FLEXIBLE DUCTWORK. 5 FEET MAXIMUM
LENGTH, SIZE AS INDICATED OR SCHEDULED
SQUARE CEILING DIFFUSER WITH FLEXIBLE
DUCT(5' MAXIMUM LENGTH) SAME SIZE AS
DIFFUSER NECK SIZE. DIFFUSER SIZE PER
SCHEDULE UNLESS OTHERWISE NOTED.
PROVIDE CONICAL SPIN-IN TAP WITH
BALANCING DAMPER AT CIRCULAR DUCT.
NUMBER INDICATES BALANCING AIRFLOW CFM.
CEILING REGISTER, SIZE PER SCHEDULE UNLESS
OTHERWISE NOTED. NUMBER INDICATES
BALANCING AIRFLOW CFM.
SUPPLY AIR DIFFUSER, 24x24 FACE AREA, SUITABLE FOR 2'x4' TILE CEILING.
PERFORATED CEILING PANEL, 24x24 FACE AREA, SUITABLE FOR 2'x4' TILE CEILING.
CENTRIFUGAL FAN OR
PUMP BY APPLICATION
DOOR LOUVER
3/4" DOOR UNDERCUT
RETURN AIR SYMBOL
NUMBER INDICATES CFM
SUPPLY AIR SYMBOL
NUMBER INDICATES CFM
THERMOSTAT
U
L
CR
HUMIDITY SENSOR
DOMESTIC COLD WATERCW
CONDENSATE DRAIND
G GAS PIPING
HW DOMESTIC HOT WATER
HWC HOT WATER CIRCULATING
HWR HEATING WATER RETURN
HEATING WATER SUPPLYHWS
PC PUMPED CONDENSATE
PUMPED CONDENSATE RETURNPCR
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATIONM A T C H L I N E A-A
DEMOLITION LINETYPE
CENTERLINE
CENTERLINE SYMBOL
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
EXHAUST OR RETURN DUCT UP
EXHAUST OR RETURN DUCT DOWN
SUPPLY DUCT UP
SUPPLY DUCT DOWN
DUCT WITH ACOUSTICAL SOUND LINING
ROUND DUCT UP
ROUND DUCT DOWN
DUCT WITH MANUAL BALANCING DAMPER.
PROVIDE ACCESS DOOR MINIMUM (DUCT
WIDTH MINUS 2") WIDE BY 16" LONG.M.B.D.
UP DUCT TRANSITION UP
DUCT TRANSITION DOWNDN.
DUCT RISERISE
T
H
M
M
A.D. ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH. ARCHITECTURAL
A.P. ACCESS PANEL
APPROX. APPROXIMATELY
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
C COMMON
C.C. COOLING COIL
C.D. CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
C.G. CEILING GRILLE
CGR CHILLED GLYCOL RETURN
CGS CHILLED GLYCOL SUPPLY
C.O. CLEANOUT
C.R. CEILING REGISTER
CW DOMESTIC COLD WATER
D.B. DRY BULB
db DECIBEL
DDC DIRECT DIGITAL CONTROL
DESIG. DESIGNATION
DIA DIAMETER
DN. DOWN
(E) EXISTING
E.A.T. ENTERING AIR TEMPERATURE
E.D.B. ENTERING DRY BULB
EFF. EFFICIENCY
E.G. EXHAUST GRILLE
ELEV. ELEVATION/ELEVATOR
ENT. ENTERING
E.S.P. EXTERNAL STATIC PRESSURE
E.W.B. ENTERING WET BULB
E.W.T. ENTERING WATER TEMPERATURE
EXIST. EXISTING
°F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
F.D. FIRE DAMPER
FLA FULL LOAD AMPS
FL.D. FLOOR DRAIN
FLR. FLOOR
FPM FEET PER MINUTE
FT. FEET
F.V. FACE VELOCITY
GAL. GALLON
GPM GALLONS PER MINUTE
H.C. HEATING COIL
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
Hz HERTZ
IN. INCHES
JC JANITORS CLOSET
L.A.T. LEAVING AIR TEMPERATURE
LBS. POUNDS
LBS./HR POUNDS PER HOUR
L.D.B. LEAVING DRY BULB
L.W.T. LEAVING WATER TEMPERATURE
MAX. MAXIMUM
M.B.D. MANUAL BALANCING DAMPER
MER MECHANICAL EQUIPMENT ROOM
MIN. MINIMUM
M.O.D. MOTOR OPERATED DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
N.I.C. NOT IN CONTRACT
N.O. NORMALLY OPEN
O.A. OUTSIDE AIR
O.C. ON CENTER
O.S.D. OPEN SITE DRAIN
P.D. PRESSURE DROP
PH PHASE
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
R.A. RETURN AIR
R.G. RETURN GRILLE
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S.A. SUPPLY AIR
SD SMOKE DETECTOR
S.P. STATIC PRESSURE
S.S. STAINLESS STEEL
T.G. TOP GRILLE
T.O.C. TOP OF CONCRETE
T.O.G. TOP OF GRADE
T.O.S. TOP OF STEEL
T.R. TOP REGISTER
TYP. TYPICAL
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VOL. VOLUME
W.B. WET BULB
W.C. WATERCOLUMN
W.G. WATER GAUGE
MECHANICAL PIPE
RISER DESIGNATION
RISER NUMBER
GENERAL SYMBOLS
NORTH ARROW
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
SAMPLE OA SUPPLY AT FCU
FCU RETURN
M.B.D.
BOOT TAP
OA SUPPLY
BALANCED
OA SUPPLY
DUCT SIZE 8x8
FCU
M101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
SECTION IDENTIFICATION
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
M101, M102
FLOOR PLAN AND DETAIL TITLES:
M101
FLOOR PLAN
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :04
P M
XX
X.
XX
.03
M -0
.D
W G
M-001
AM
JG
09/17/2019
SYMBOLS AND ABBREVIATIONS
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
1901.03 M-001.DWG
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
(E )2
0x
(E)14x4
(E)16x10
(E)12x10
12x10
(E)14x4 DN
(E )2
6x
(E)36x14
12x1016x10 10x8
(E)4"CWS
(E)4"CWR
(E)3"HWS
(E)3"HWR
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)12x4 DN (E)12x4 DN (E)12x4 DN
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)12x8 DN(E)12x8 DN(E)8x6 DN(E)12x6 DN(E)12x8 DN
(E)3"HWR
(E)3"HWS
(E)4"CWR(E)4"CWS
(E)1-1/4"D DN
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"D DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"D DN
(E)14x10
1(E)10x8
1 1
1 11
(E)FCU-3L, TYP.
(E)FCU-6L, TYP.
(E)10x10 UP TO EF-27 ON ROOF
(E)14x8
(E)10x6
(E)10x10 OPEN TO CEILING PLENUM
(E)10x10
(E)12x6
(E)14x10
(E)14x8
(E)12"Ø DN
(E)18x10
(E)14x8
(E)6"Ø (E)6"Ø (E )C
HW
R
(E )C
HW
S
(E )H
W R
(E )H
W S
(E)1-1/2"D DN
(E)CHWS&R
(E)CHWS&R
(E)HWS&R
(E)D(E)FCU-3L, TYP.
(E)D1 1
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :17
P M
XX
X.
XX
.03
M D1
.D
W G
MD101
AM
JG
09/17/2019
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. DEMOLISH DUCTWORK, ASSOCIATED SUPPORTS, AND APPURTENANCES
COMPLETE TO POINTS INDICATED.
5TH FLOOR - DEMOLITION
1901.03 MD101.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
FIFTH FLOOR NORTH - DEMOLITION
8'0 16' 1/8"=1'-0"
N
8'0 16' 1/8"=1'-0"
FIFTH FLOOR SOUTH - DEMOLITION
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
(E )2
0x
(E)16x10
(E)14x4
12x4
(E)14x4 DN
(E )2
6x
(E)36x14
(E)4"CWS
(E)4"CWR
(E)3"HWS
(E)3"HWR
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)12x4 DN (E)12x4 DN
(E)12x8 DN
(E)12x8 DN(E)8x6 DN
(E)12x6 DN(E)12x8 DN
(E)3"HWR
(E)3"HWS
(E)4"CWR(E)4"CWS
(E)1-1/4"D DN
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"D DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"HWR DN
(E)1-1/4"HWS DN
(E)1-1/2"CWR DN
(E)1-1/2"CWS DN
(E)1-1/4"D DN
(E)12x10 (E)14x10(E)10x8 12x1014x10
10x8
20x10
10x4
FCU-1
FCU-2
12x8
10x4
16x10 12x10
FCU-3
3/4"HWS&R
3/4"CWS&R
3/4"D
1"CWS&R
3/4"HWS&R
3/4"D
3/4"CWS&R
3/4"HWS&R
3/4"D
T
T
T
24x1024x10
13 3
FCU-4
24"x36" DRIP PAN
2 2 111121
3/4"CWS&R
3/4"D
(E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
2 (E)1-1/2"CWS DN
(E)1-1/2"CWR DN
(E)1-1/4"HWS DN
(E)1-1/4"HWR DN
(E)12x4 DN 11
(E)FCU-3L, TYP.
(E)FCU-6L, TYP.
12x812x8
8x6
8x6
8x6
(E)14x8
(E)10x6
(E)10x10 OPEN TO CEILING PLENUM
(E)10x10
(E)12x6 (E)14x10
(E)14x8
(E)12"Ø DN
(E)18x10
(E)14x8
(E)6"Ø
(E)6"Ø
(E )C
HW
R
(E )C
HW
S
(E )H
W R
(E )H
W S
(E)1-1/2"D DN
(E)CHWS&R
(E)CHWS&R
(E)HWS&R
(E)D(E)FCU-3L, TYP.
(E)D
16050
505050
1 1
CONFERENCE
ROOM
RECEPTION
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HISTORIC CORRIDOR
C5300 B
OFFICE
(E)10x10 UP TO EF-27 ON ROOF
18x103
4 4 4 4 4 4 4 4 4 4 4 4 4 44 4 4
12x8
12x8
12x812x8
12x8
18x10 3
12x10
1 18x103 1
2 2
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :31
P M
XX
X.
XX
.03
M -1
.D
W G
M-101
AM
JG
09/17/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. INSTALL MAN BARS FOR DUCT PENETRATIONS THROUGH SECURE
WALLS IF ONE PENETRATION DIMENSION IS LARGER THAN 5 INCHES OR
DUCT AREA EXCEEDS 96 SQ. INCHES. INSTALL PER DETAIL 2/M-501.
2. INSTALL SECURE WALL PENETRATION PER DETAIL 5/M-501.
3. INSTALL Z-TRANSFER DUCT PER DETAIL 6/M-501.
4. INSTALL SECURE PENETRATIONS FOR ALL EXISTING FCU PIPING
THROUGH FLOORS IN NEW PER DETAIL 5/M-501.
5TH FLOOR PLANS
1901.03 M-101.DWG
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
MIDDLE
SOUTH
COURTYARD
D O
W N
D O
W N
N
MIDDLE
SOUTH
COURTYARD
N
8'0 16' 1/8"=1'-0"
FIFTH FLOOR PLAN - NORTH
8'0 16' 1/8"=1'-0"
N
8'0 16' 1/8"=1'-0"
FIFTH FLOOR PLAN - SOUTH
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
SHEETMETAL DUCT
MBD
STAINLESS STEEL DRAW BAND
FLEXIBLE DUCT
SIZE SAME AS
DIFFUSER
NECK.
DUCT COLLAR
STAINLESS STEEL DRAW BAND
OPPOSED
BLADE
DAMPER
T-BAR CEILING GRID PROVIDE 24x24 SQUARE FACE, ROUND NECK, CEILING DIFFUSER WITH FRAME SUITABLE FOR
CEILING IN WHICH DEVICE IS INSTALLED. NECK
SIZE PER DIFFUSER SCHEDULE. SEE
DRAWINGS FOR CFM.
NO SCALE
DIFFUSER CONNECTION
DETAIL
M-6013
PRIMARY
DRAIN PAN
RETURN
AIR DUCT
EXTENDED DRAIN PAN
FANFAN
COOLING COIL
HEATING COIL 1/4" M.A.V.
SUPPLY AIR DUCT
HW
S
HW
RCW
S
CW
R
C.O.
SEE SCHEDULE
FOR PIPE SIZES
3/4"D
NO SCALE
FAN COIL UNIT PIPING
DETAIL
M-6011
SLAB ABOVE
SECURE SIDENON-SECURE SIDE
CONDUIT/PIPE
DIELECTRIC FITTING/COUPLING, WITH NO METAL TO METAL
CONTACT FROM ONE SIDE OF BARRIER TO THE OTHER.
CONDUIT/PIPE
IDEAL IND. MODEL "J" PIPE CLAMP OR
EQUAL. GROUND TO GROUND
BUS SHOWN ON SHEET E-102 WITH
#8 CONDUCTOR.
FLOOR
6" MAX
NO SCALE
SECURE WALL PENETRATION
DETAIL
M-1015
SECURE SIDENON-SECURE SIDE
3"x10"x1/4" THICK STEEL
ANGLE - FABRICATE TO
FIT DUCT OPENING.
WALL
WELD BARS TO
1/4" THICK STEEL
ANGLE FLANGE
TACK WELD DUCT
TO FLANGE (TYP.)
1/2" Ø STEEL BARS AT
5" O.C.(MAX) BOTH
DIRECTIONS. WELD TO
STEEL ANGLE.
3/8" CARRIAGE THRU BOLTS,
LENGTH TO SUIT WALL
WALL
3/8" NUT, CUT AND PEEN BOLT
ON UNPROTECTED SIDE
3" HIGH, 1/4" THICK PLATE COLLAR,
SHOP-WELD TO CORNERS
1/2" Ø STEEL BARS(WELDABLE) AT 5" ON
CENTER, BOTH DIRECTIONS, SHOP WELD TO
STEEL SLEEVE AND EACH OTHER.
UNPROTECTED SIDE
1/4" THICK STEEL PLATE SLEEVE, 4"
WIDER THAN WALL SIZE TO SUIT DUCT
DRILL SLEEVE WITH 3/16" HOLES, 3" ON
CENTER, ALL AROUND SLEEVE. ATTACH DUCT
WITH #12 SHEET METAL SCREWS AND SEAL
AIR TIGHT.
3" HIGH, 1/4" THICK PLATE
COLLAR, SHOP WELD TO
SLEEVE ALL FOUR SIDES
FLEXIBLE CONNECTION
6" MINIMUM LONG
12x12 ACCESS DOOR ON PROTECTED SIDE
OF WALL. PROVIDE WITH LOCKING HASP.
PROTECTED SIDE
ACOUSTICAL
LINER TYPICAL
3" HIGH, 1/4" THICK PLATE
COLLAR, SHOP WELD TO
SLEEVE ALL FOUR SIDES
NO SCALE
DUCT SECURITY BARS
DETAIL
M-5014
M-501
NO SCALE
MAN BAR BARRIER
DETAIL
M-1012
NOTE: NON-RETURN AIR DUCT PENETRATIONS SIMILAR EXCEPT THERE
IS NO ACOUSTICAL SOUND LINING OR Z-BEND REQUIREMENT. SEE PLANS
FOR DUCT SIZES.
12x12 W/ 1" S.L. UNLESS
OTHERWISE NOTED
AIR FLOW
INSIDE SECURE ROOM
OUTSIDE ROOM
ABOVE LAY-IN
TILE CEILING
BELOW CEILING
AIR FLOW
12x12 W/ 1" S.L. UNLESS
OTHERWISE NOTED
AIR FLOW
AIR FLOW
PROVIDE DUCT ACCESS DOOR (12x12
MIN.) OR BOLTED AND GASKETED
REMOVABLE DUCT SECTION ON
SECURE SIDE OF PARTITION
2 LAYERS OF 5/8" GWB EACH
SIDE. SEE ARCH. DWGS.
MIN. R-13
INSULATION
F.S.D. IN WALL
BOLT
1-1/2"x13 GA. EXPANDED METAL
SHEETMETAL FLANGENUT
RETURN AIR
GRILLE
NO SCALE
SECURE AREA RETURN DUCT PENETRATION
DETAIL
M-1016
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :35
P M
XX
X.
XX
.03
M -5
.D
W G
M-501
AM
JG
09/17/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
DETAILS
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
1901.03 M-501.DWG
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
FAN COIL UNIT SCHEDULE
UNIT NO. TYPE SIZE
AIRFLOW
(CFM)
E.S.P. (IN.
W.G.)
MOTORS ELEC.
DATA
(V/PH/HZ)
COOLING HEATING
MAX
DIMENSIONS NOTES
QTY HP ROWS
TOTAL CAP.
(MBH)
SENS CAP.
(MBH)
FLOW
(GPM)
MAX P.D.
(FT. W.G.)
PIPE SIZE
(IN.) ROWS
TOTAL CAP.
(MBH)
FLOW
(GPM)
MAX P.D.
(FT. W.G.)
(E)FCU-3L VF - 255 0.15 1 1/12 - 3 7.1 5.6 1.5 5.3 - 1 8.2 0.5 0.4 -
(E)FCU-6L VF - 470 0.15 1 1/12 - 3 10.6 9.9 1.6 2.0 - 1 16.1 1.0 2.0 -
FCU-1 HLP 10 1120 0.3 1 0.24 277/1/60 3 24.2 21.0 5.0 5.0 1" 1 30.5 2.5 5.0 75 x 30 x 11
FCU-2 HLP 04 410 0.3 1 0.24 277/1/60 3 9.2 7.8 2.0 5.0 3/4" 1 10.8 1.1 5.0 38 x 30 x 11
FCU-3 HLP 08 780 0.3 1 0.24 277/1/60 3 16.4 14.2 3.4 5.0 3/4" 1 21.5 2.2 5.0 56 x 30 x 11
FCU-4 VS 12 1132 - 1 0.25 277/1/60 4 29.2 19.1 5.0 5.0 3/4" - - - - -
NOTES A. HLP - HORIZONTAL LOW PROFILE
VS - VERTICAL STACKED
VF - VERTICAL FLOOR MOUNTED
B. BASED ON 75°F. D.B. AND 63°F. W.B. ENTERING AIR AND SCHEDULED
CFM AT MEDIUM SPEED.
C. BASED ON CHILLED WATER ENTERING AT 45°F WITH A 10°F
TEMPERATURE DIFFERENCE.
D. BASED ON HEATING WATER ENTERING AT 140°F WITH A 20°F
TEMPERATURE DIFFERENCE. HEATING WATER RUNOUTS ARE 3/4".
E. INSTALL PER DETAIL 1/M-501.
F. PROVIDE CONDENSATE PUMP WITH FLOAT SENSOR CONTROL.
G. DATA PROVIDED FOR EXISTING UNITS IS FOR INFORMATION ONLY.
A
CB D
AIR DEVICE SCHEDULE
SYMBOL DESIG.
AIRFLOW
(CFM)
NECK
SIZE
(INCHES)
OVERALL
SIZE
(INCHES)
MAX. S.P.
DROP
(IN. W.G.)
MAX.
N.C.
HORIZONTAL
THROW @
100 FPM
FACE TYPE NOTES
CD-1
50-120 6 24x24 0.06 20 2 CONE FACE 4-WAY BLOW
125-225 8 24x24 0.06 20 4 CONE FACE 4-WAY BLOW
230-330 10 24x24 0.06 20 5 CONE FACE 4-WAY BLOW
R-1 50-1000 22x22 24x24 0.04 20 - PERFORATED
NOTES
A
A. INSTALL PER DETAIL 3/M-501.
A
A
F
E
E
E
G
G
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :39
P M
XX
X.
XX
.03
M -6
.D
W G
M-601
AM
JG
09/17/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
SCHEDULES
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
1901.03 M-601.DWG
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
G
WALL-MOUNTED CARBON DIOXIDE SENSOR. MOUNT
ADJACENT TO ROOM TEMPERATURE SENSOR.
M
AMS-#
ES-#
WALL-MOUNTED HUMIDITY TRANSMITTER. MOUNT ADJACENT TO ROOM
TEMPERATURE SENSOR.
FLOW METER
(TURBINE-STYLE)
AMS-#
1. PROVIDE THE FOLLOWING AUTOMATIC ALARM AT OWS EVERY MARCH 1ST AND
SEPTEMBER 1ST: "IN CONFORMANCE WITH THE [LOCAL BUILDING
CODES][UFCs][EXECUTIVE ORDERS] AND IN ORDER TO SAVE ENERGY, BUILDING
SENSORS MUST BE CALIBRATED AND CLEANED AT REGULAR INTERVALS. OUTSIDE
AIR, DUCT, AND UNIT-MOUNTED TEMPERATURE, HUMIDITY, AND ENTHALPY
SENSORS SHOULD BE CALIBRATED ANNUALLY. AIR-FLOW MEASURING STATIONS
SHOULD BE CLEANED EVERY SIX MONTHS."
AIR OR WATER DIFFERENTIAL PRESSURE SWITCH, BY APPLICATION.
PROVIDE AIR SWITCH PER DETAIL 4/M-701/M-701. PROVIDE WATER
SWITCH PER DETAIL 6/M-701/M-701.
DIFFERENTIAL PRESSURE GAUGE, CONNECT TO STATIC
PRESSURE TAPS IN ACCORDANCE WITH DETAIL 3/M-701/M-701.
AIR OR WATER DIFFERENTIAL PRESSURE TRANSMITTER, BY APPLICATION.
PROVIDE AIR TRANSMITTER PER DETAIL 4/M-701/M-701. PROVIDE WATER
TRANSMITTER PER DETAIL 6/M-701/M-701.
LOW TEMPERATURE DETECTION FREEZESTAT, MANUAL RESET, WITH
20 FOOT ELEMENT. PROVIDE PER DETAILS 1/M-701/M-701 AND
2/M-701/M-701.
DUCT MOUNTED ELECTRONIC TEMPERATURE SENSOR WITH 20
FOOT AVERAGING ELEMENT. PROVIDE PER DETAILS 1/M-701/M-701
AND 2/M-701/M-701.
DUCT MOUNTED ELECTRONIC TEMPERATURE SENSOR WITH
RIGID STEM ELEMENT. PROVIDE PER DETAIL 2/M-701/M-701.
PIPE MOUNTED INSERTION TYPE ELECTRONIC
TEMPERATURE SENSOR WITH WELL.
WALL-MOUNTED ELECTRONIC TEMPERATURE SENSOR
DUCT MOUNTED CARBON DIOXIDE SENSOR. PROVIDE PER DETAIL
2/M-701/M-701.
DUCT MOUNTED ELECTRONIC RELATIVE HUMIDITY TRANSMITTER
PROVIDE PER DETAIL 2/M-701/M-701.
CURRENT SWITCH
END SWITCH
BINARY INPUT OR OUTPUT POINT
ANALOG INPUT OR OUTPUT POINT
NETWORK CONNECTION
THERMOMETER.
ELECTRIC TO PNEUMATIC SOLENOID VALVE
MOUNTED IN INSTRUMENTATION PANEL,
COIL VOLTAGES AS INDICATED ON WIRING
DIAGRAMS.
DUCT MOUNTED ENTHALPY TRANSMITTER
PROVIDE PER DETAIL 2/M-701/M-701.
EXISTING
INSULATION
GENERAL REQUIREMENTS
SYMBOLS & ABREVIATIONS
AI ANALOG INPUT
ANALOG OUTPUTAO
BI BINARY INPUT
BINARY OUTPUTBO
CLG COOLING
CHANGE OF VALUECOV
Cx COMMISSIONING
HEATINGHTG
I/O INPUT/OUTPUT
NETWORK VARIABLE INPUTNVI
NVO NETWORK VARIABLE OUTPUT
SETPOINTSP
HAND-OFF-AUTO SWITCH
MOTOR
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
RELAY COIL
STARTER HOLDING COIL
THERMAL MOTOR SWITCH
PNEUMATIC TUBING
EXISTING PNEUMATIC TUBING
MOTOR STARTER
NC
NOEP#
C
FAN OR PUMP, BY APPLICATION
EMERGENCY HVAC OFF (SYSTEM VARIABLE)
OUTSIDE AIR TEMPERATURE SENSOR (SYSTEM VARIABLE)
OUTSIDE AIR ENTHALPY TRANSMITTER (SYSTEM VARIABLE)
VARIABLE FREQUENCY DRIVE
AIRFLOW MEASURING STATION - THERMAL DISPERSION TYPE
AIRFLOW MEASURING STATION - PIEZOMETRIC TYPE
R#
SYMBOLS & ABBREVIATIONS
CONTROL AIR MAIN CONNECTION
OPPOSED BLADE DAMPER.D-#
D-# PARALLEL BLADE DAMPER.
A-#
DAMPER OR VALVE ACTUATOR.
2 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
3 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
HYDRONIC PIPING
AIR OR WATER FLOW PATH
FILTER OR COIL (AS LABELED)
MPROVIDE
BRACKET
PER
PROVIDE
0.25" RIGID
COPPER
SUPPORT
TUBE
SCREW TO
DUCT/CASING
WITH SELF
DRILLING/
TAPPING
SCREWS
#12 BARE
COPPER WIRE
ARRANGE IN UNIFORM
MANNER THRU SPACE
JUNCTION BOX AND COVER
CONDUIT TO
FIELD PANEL
FLEXIBLE METAL
CONDUIT TO
OTHER DEVICES,
IF NEEDED
FLEXIBLE CONDUIT BETWEEN
JUNCTION BOX AND DEVICE
TO ALLOW REMOVAL, MINIMUM
LENGTH OF 3 FT.
PROVIDE BRACKET IN
ACCORDANCE WITH
NOTE: DO NOT USE DEVICE AS A JUNCTION BOX. DO NOT
WIRE THRU DEVICE TO OTHER DEVICES
PROVIDE RIGID
FIBERGLASS
INSULATION WITH
VAPOR BARRIER,
THICKNESS TO MATCH
ADJACENT INSULATION
SEAL VAPOR
TIGHT WITH
VAPOR BARRIER
MASTIC
AHU CASING/DUCTWORK
INSULATION
SECURE PITOT TUBE
MOUNTING FLANGE TO DUCT
WITH TWO #10 SHEET METAL
SCREWS AND DUCT SEALANT.
STATIC PITOT
TUBE
0.25" TYPE M
RIGID COPPER
TUBE
AIR FLOW
DIRECTION
FAN, FILTER OR
OTHER DEVICE
DOWNSTREAM
PITOT TUBE INSTALL
IN ACCORDANCE
WITH DETAIL
DIFFERENTIAL PRESSURE SWITCH
OR TRANSMITTER. PROVIDE
BRACKET IN ACCORDANCE WITH
DETAIL
AIR FLOW
TEST TEE WITH PLUG
UPSTREAM PITOT
TUBE INSTALL IN
ACCORDANCE
WITH DETAIL
0.25" TYPE M RIGID
COPPER TUBE
WIRE AND
CONDUIT TO
FIELD PANEL
18 GAUGE GALVANIZED SHEET METAL
BRACKET ATTACHED TO DUCT WITH
FOUR #8 x 0.75" SHEET METAL SCREWS
PROVIDE RIGID FIBERGLASS
INSULATION WITH VAPOR BARRIER,
THICKNESS TO MATCH ADJACENT
INSULATION
SEAL VAPOR TIGHT WITH
VAPOR BARRIER MASTIC
ATTACH DEVICE TO BRACKET
WITH SHEET METAL SCREWS
PROVIDE RIGID FIBERGLASS INSULATION
WITH VAPOR BARRIER, THICKNESS TO
MATCH ADJACENT INSULATION
0.25" HARD COPPER TUBING
PROVIDE
WIRE AND
CONDUIT
TO FIELD
PANEL
FLEXIBLE
CONDUIT
CONNECTION
TO DP SWITCH
TEST TEE
AND PLUG
NC TEST TEE
AND PLUG
CHECK
VALVE(E)
DP SWITCH
NO
HOUSEKEEPING
PAD(E)
PROVIDE 2" STRUT AND
MOUNT DP SWITCH
MINIMUM 2 FT ABOVE
FLOOR.
A O
H
EN-#
VFD-#
DP-#
DP-#
FZ-#
T-#
TS-#
TS-#
CD-#
HT-#
CS-#
EHO
TS-OA
EN-OA
RS-#
HT-#
CD-#
BUTTERFLY VALVE.
NO SCALE
AIR DIFFERENTIAL PRESSURE DEVICE
DETAIL
M-7014
NO SCALE
DEVICE MOUNTING BRACKET
DETAIL
M-7015 NO SCALE
DUCT MOUNTED SENSOR
DETAIL
M-7012
NO SCALE
WATER DIFF. PRESSURE SWITCH
DETAIL
M-7016 NO SCALE
PITOT TUBE INSTALLATION
DETAIL
M-7013
NO SCALE
SENSING ELEMENT INSTALLATION
DETAIL
M-7011
M-701
M-701
M-701
M-701
M-701
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :44
P M
XX
X.
XX
.03
M -7
.D
W G
M-701
AM
JG
10/11/2019
CONTROLS
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
1901.03 M-701.DWG
AutoCAD SHX Text
XXXX
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
GENERAL
ON A RISE IN ROOM TEMPERATURE ABOVE SETPOINT, AS SENSED BY WALL-MOUNTED SENSOR TS-1, HEATING COIL VALVE V-1 SHALL MODULATE CLOSED. ON A FURTHER RISE IN TEMPERATURE COOLING COIL VALVE V-2 SHALL MODULATE OPEN. ON A FURTHER RISE IN TEMPERATURE THE FAN SHALL INCREASE SPEED. ON A FALL IN
TEMPERATURE THE REVERSE SHALL OCCUR.
SETPOINT: TS-1 SHALL HAVE AN OCCUPANT INPUT SLIDER TO ALLOW THE SETPOINT TO BE MODIFIED 2 DEGREES
HIGHER OR LOWER DEPENDING UPON SLIDER POSITION.
OFF/UNOCCUPIED SETPOINT: THE FANS SHALL BE STOPPED AND ALL VALVES AND DAMPERS SHALL RETURN TO
THEIR NORMAL POSITIONS. VALVE V-1 SHALL MAINTAIN 50°F AT TS-1.
FCU-9 ONLY. ON A RISE IN WATER LEVEL IN THE CONDENSATE PAN, THE FLOAT SWITCH SHALL INDICATE AN ALARM AT THE OWS AND THE FCU SHALL BE INDEXED TO OFF. VALVES SHALL RETURN TO THEIR NORMAL
POSITIONS.
FAN
V-1 V-2 N.C.N.C.
H
C
C
C
FLOW DIAGRAM
SEQUENCE OF OPERATION
FAN COIL UNIT
POINTS LIST
POINT
NAME DESCRIPTION NETWORK
CONNECTION I/O TYPE
ALARMS TRENDING
FAIL
WARNING LIMIT Cx
FREQUENCY
OPERATING
FREQUENCYLOW HIGH LOW HIGH
FCU
SUPPLY FAN X
START/STOP COV COV
TS-1 TEMPERATURE AI 45 90 5min 15min
FS-1 FCU-9 FLOAT SWITCH BI COV COV
1 ALL POINTS INCLUDED ON LIST SHALL BE SHOWN ON THE OWS GRAPHICS.
TS-1
FCU-4 ONLY, DRIP PAN FS-1
FI
LE
N
RE
F:
PL
OT
D
AT
E:
/26 /20
:02 :48
P M
XX
X.
XX
.03
M -7
.D
W G
M-702
AM
JG
10/11/2019
GENERAL NOTES
G1. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT UNLESS
SPECIFICALLY MARKED "EXISTING", "EXIST.", OR "(E)".
G2. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
CONTROLS
OF
GR
AP
HI
C
SC
AL
E
SHEET SIZE:
SHEET
DISCIPLINE SHEET TYPE SEQUENCE
DRAWING NO.
DRAWING TITLE
FILE NAME
CHECKED BY
DRAWN BY DATE DRAFTED:
PROJECT NO.
GSA PM
SUB. DATE
SUBMISSION
DESCRIPTION
PROJECT
TITLE
BUILDING NOs.
OTHER
BUILDING NO.
CITY/ST./ZIP
STREET
NAME
DR
AW
IN
G
PR
OJ
EC
T
BU
ILD
IN
G
SUB A/E
PRIME A/E
CONS. CONTR.
A/E CON. NO.
CO
NT
RA
CT
OR
S
FLOOR NO.
CONSTR. CON.
FACILITY CODE
PROJECT
A/E TASK NO.
CONS. WORK
24 x 36
DC-
WASHINGTON, DC
MERIDIEN GROUP / CITADEL DCA
SUMMER CONSULTANTS
CRAIG GARDNER
FEDERAL OFFICE BUILDING:
NEW OFFICE SPACE
5TH FLOOR MIDDLE RENOVATION
5TH FLOOR
0019-13
2 DECEMBER 2019
100%
1901.03 M-702.DWG
AutoCAD SHX Text
REVISION NOTES
AutoCAD SHX Text
MARK
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text
CERTIFICATIONS
J
J
ABBREVIATIONS
OC
CL
B
B
SS
T
E001
E101
DN
UP
Ø
SHEET SYMBOLS
EM2
1,3,5
#10
#10
1,3,5
EM2
#10
EM2
1,3,5
E001 E101
E001 E101
AA
SYMBOLS
EM2
1,3,5
#10
EX
EC
W
S
SYMBOLS SYMBOLS
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
DUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
SINGLE RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
SINGLE RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING TYPE,
NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4" SQUARE x
2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18" ABOVE
FINISHED FLOOR.
QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING
TYPE, NEMA 5-20R CONFIGURATION, RECESS MOUNTED IN 4"
SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18"
ABOVE FINISHED FLOOR.
QUADRUPLEX RECEPTACLE, 20 AMPERE, 125 VOLT GROUNDING
TYPE, NEMA 5-20R CONFIGURATION, SURFACE MOUNTED IN 4"
SQUARE x 2-1/8" DEEP PRESSED STEEL JUNCTION BOX AT 18"
ABOVE FINISHED FLOOR.
SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED
ON FLOOR PLAN, RECESS MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
SPECIAL DEDICATED OUTLET, NEMA CONFIGURATION AS NOTED
ON FLOOR PLAN, SURFACE MOUNTED IN 4" SQUARE x 2-1/8" DEEP
PRESSED STEEL JUNCTION BOX AT 18" ABOVE FINISHED FLOOR.
FAN COIL UNIT WITH SINGLE POINT ELECTRICAL CONNECTION.
JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED
STEEL, RECESS MOUNTED AT 18" ABOVE FINISHED FLOOR, WITH
BLANK COVER PLATE.
JUNCTION BOX, 4" SQUARE x 2-1/8" DEEP GALVANIZED PRESSED
STEEL, MOUNTED ABOVE SUSPENDED TILE CEILING.
CIRCUIT BREAKER TYPE PANELBOARD.
DISTRIBUTION TYPE PANELBOARD.
SWITCH AND FUSE TYPE PANELBOARD.
ELECTRICAL POINT OF CONNECTION.
TRANSFORMER, SEE POWER RISER DIAGRAM FOR
CHARACTERISTICS.
CEILING MOUNTED OCCUPANCY SENSOR, COMBINATION
ULTRASONIC/ PASSIVE INFRARED (PIR) DEVICE WITH ADJUSTABLE
TIME DELAY 5 TO 30 MINUTES.
LIGHT SWITCH, FLUSH TUMBLER, SINGLE POLE, 20 AMPERE,
120/277V, A.C. ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED
FLOOR UNLESS OTHER MOUNTING HEIGHT IS NOTED.
SAME AS LIGHT SWITCH ABOVE, EXCEPT SURFACE MOUNTED.
SAME AS LIGHT SWITCH WITH RED PILOT LIGHT ABOVE, EXCEPT
SURFACE MOUNTED.
3-WAY LIGHT SWITCH, SINGLE POLE, 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
4-WAY LIGHT SWITCH, SINGLE POLE, 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
SAME AS 4-WAY SWITCH ABOVE, EXCEPT SURFACE MOUNTED.
0-10V LOW VOLTAGE DIMMING SWITCH. 20 AMPERE, 120/277V, A.C.
ONLY, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
LOW VOLTAGE LIGHT SWITCH CONNECTED TO DIMMER PANEL.
COMBINATION 2-BUTTON "ON/OFF" LIGHT SWITCH AND
OCCUPANCY SENSOR, IN CAST DEVICE BOX SURFACE MOUNTED
ON WALL AT 48" ABOVE THE FINISHED FLOOR, SINGLE POLE, 20
AMPERE, 120/277V, A.C. ONLY. PROVIDE WITH WHITE PLASTIC
DECORA STYLE COVER PLATE.
FRACTIONAL HORSEPOWER MANUAL MOTOR STARTER WITH
THERMAL OVERLOAD RELAY, SINGLE POLE, 115 VOLT, SURFACE
MOUNTED IN DEVICE BOX ON UNIT UNLESS OTHERWISE NOTED.
MULTIPLE SWITCHES LOCATED IN A SINGLE MULT-GANG DEVICE
BOX, RECESS MOUNTED AT 48" ABOVE FINISHED FLOOR.
LIGHTING…