St. Johns River Power Park (SJRPP) Unit 3 Combined Cycle - Unit Auxiliary Transformers
Solicitation number
1412175446
Issued by
Duval County, Florida

About this file

This is Addendum 4 to an RFP issued by the Procurement Department of JEA (Jacksonville Electric Authority) in Florida for the procurement of Unit Auxiliary Transformers (UATs) for the St. Johns River Power Park (SJRPP) Unit 3 Combined Cycle project. The solicitation seeks two Combustion Turbine Generator (CTG) UATs and two Steam Turbine Generator (STG) UATs. The original response due date was June 23, 2026, which was extended to July 14, 2026, with responses due by 12:00 PM EST. An optional pre-response meeting was scheduled for May 26, 2026, at 3:00 PM. The effective date for submittals is defined as the EPC LNTP (Engineering, Procurement, and Construction Lump-Sum Turnkey) date of February 2027, unless mutually agreed otherwise in writing by both parties.

Addendum 4 addresses technical clarifications regarding the transformers' impedance specifications and updates the list of approved manufacturers. In response to a bidder inquiry, JEA confirmed that the 18% impedance shown on the Power Transformer Data Sheet (lines 18 and 19, page 7 of the Technical Specification) is correct and suitable as designed. Under normal operating conditions, the two UATs will operate in parallel with a combined operating impedance of 9%. JEA's engineering analysis, conducted through ETAP modeling and reviewed by BV, confirmed that the impedance was selected to balance short-circuit currents with voltage drop conditions and remains suitable even in worst-case scenarios with one UAT out of service. Additionally, JEA revised Attachment C, the "All Approved Transformer Manufacturers" document, which is referenced in a separate accompanying document.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Procurement Department Bid Section

June 10, 2026

ADDENDUM NUMBER: FOUR (4)

TITLE: 1412175446 (RFP) JEA St. Johns River Power Park (SJRPP) Unit 3 Combined Cycle – Unit Auxiliary Transformers

PROPOSAL DUE DATE: July 14, 2026

TIME OF RECEIPT: 12:00 PM EST

THIS ADDENDUM IS FOR THE PURPOSE OF MAKING THE FOLLOWING CHANGES OR CLARIFICATIONS:

1. Question: Can you verify the Impedance of 18% shown on lines 18 and 19 of the Power Transformer

Data Sheet is correct? You will find this on page 7 Technical Specification attached.

Answer: Confirmed – 18% impedance is correct and suitable as designed. Under normal conditions, (2)

UATs will be operating in parallel with an operating impedance of 9%. Impedance was selected through

ETAP modeling to balance short-circuit currents with voltage drop conditions. BV analyzed multiple operating scenarios, including a worst-case scenario with (1) UAT out-of-service, and confirms the system impedance to be suitable as designed.

2. Revision: JEA has revised the Attachment C “All Approved Transformer Manufacturers” document.

Please see “1412175446 Addendum 4 - Attachment C - All Approved Transformer

Manufacturers_2026” document.