Attachment_K_-__Q&A_Set_2.pdf

PDF 15 KB Posted

Attached to
Dehumidification Upgrades at NCTC Federal contract opportunity
Solicitation number
140F0918B0002
Issued by
Department of the Interior Fish and Wildlife Service Region 9 Headquarters

About this file

Attachment K - Q&A Set 2

View the file

Other files for this federal contract opportunity

Other files attached to Dehumidification Upgrades at NCTC, newest first.
File Type Posted
Sol_140F0918B0002_Amd_0003.pdf PDF
Attachment_J_-_140F0918B0002_Q&A_Set_1.pdf PDF
Sol_140F0918B0002_Amd_0002.pdf PDF
Attachment_H_-_Site_Visit_Attendance_Sheet.pdf PDF
Attachment_I_-_Site_Visit_Agenda.pdf PDF
Sol_140F0918B0002_Amd_0001.pdf PDF
Attachment_B_-_Specifications.pdf PDF
Sol_140F0918B0002.pdf PDF
Attachment_F_-_DI-137_-_DOI_Release_of_Claims.pdf PDF
Attachment_D_-_SF25_Performance_Bond.pdf PDF
Attachment_A_-_Drawings.pdf PDF
Attachment_G_-_Important_Notice_to_Bidders.pdf PDF
Attachment_C_-_Wage_Determination.pdf PDF
Attachment_E_-_SF-25A_Payment_Bond.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation 140F0918B0002

Dehumidification Upgrades at NCTC Question and Answer Set 2

Question 1: Is there a piping plan for the coil connections forthcoming (see drawing MD-401-

E-T, general note #3). Also please read the clarification below from the supplier of the NovalAire Dehumidification units and advise.

Some of the specification language comes from the larger size NovelAire DES/DX-CR units, but are not available on the smaller 600 DES/DX CR

EXCEPTIONS / CLARIFICATIONS

• VFD is not available for 600 DES/DX CR

• Cabinet Insulation is 1 inch thick

• Removable Panel over Electrical Section

• No DDC Controller

The 600 DES/DX CR only needs a closed contact for a 24VAC control circuit to run so the unit will interface with almost any standard humidistat. The schedule notes indicate DH unit shall energize any time respective AHU is running. In addition to interlocking the DH with the AHU, there should be a separate “dehumidify” input based on space Relative Humidity or some other metric that calls on our unit to dehumidify. It is designed for low-temp operation but there is a limit. Fans will run on a separate contact to maintain balance for OA flow.

Answer 1: No, the note in parentheses was left in error. See M-401-E-T for new work required and additional information.

1. VFD is not required. But motor starter for unit is. Coordinate with electrical to verify unit installed is a turnkey installation.

2. Cabinet insulation thickness from factory may by 1”. Material shall remain as specified.

3. Electrical cabinet needs to be enclosed so no wires are exposed or pose a danger to maintenance staff. Factory assembled unit is required and any miscellaneous items filed installed shall meet all NFPA, IBC, and NEC codes. Panel does not have to be removable.

4. DDC controller is not required to operate the unit per Note 4 on equipment schedule. Intent is to only monitor the unit to verify it is running.

5. The DDC input output summary table on M-601 shows a sensor for outside air RH and T. To protect the desiccant unit, have the unit shut off when outside air temperature drops below 40 degrees. The intent of the unit is to dry the building out even when RH outside is low, so do not recommend controlling the unit off the RH levels inside or outside the building.