Attachment152025-Lighting_system.pdf
PDF 227 KB Posted
- Attached to
- Remove Structural Columns JSP Building 2025, ASA Federal contract opportunity
- Solicitation number
- W912PF-16-R-0012
About this file
Attachment 15 - 2025 - Lightning system
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment18GeotechnicalReport.pdf | ||
| Amendment0003.pdf | ||
| Attachment122025-Floor_Plan.pdf | ||
| Attachment132025-Foundation_Plan.pdf | ||
| Amendment0002.pdf | ||
| Attachment142025-Frames.pdf | ||
| Attachment172025-Roof_Plan.pdf | ||
| Attachment162025-Pier.pdf | ||
| Attachment9PSCPrel.pdf | ||
| Amendment0001.pdf | ||
| Attachment11CostiSic.pdf | ||
| Attachment10SchedeVal.pdf | ||
| Attachment6RequisitiGenerali.pdf | ||
| Solicitation16R0012.pdf | ||
| Attachment5PastPerformanceQuest.pdf | ||
| Attachment1SOW Att1.pdf | ||
| Attachment4ConstrExperienceQuest.pdf | ||
| Attachment8AntimafiaCert.pdf | ||
| Attachment7RequisitiGeneraliBIS.pdf | ||
| Attachment3DesignExperienceQuest.pdf | ||
| Attachment2TechSpecs.pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 10 11 12 13 14 15 168 9
1 2 3 4 5 6 7 10 11 12 13 14 15 168 9
B
A
C
D
E
F
G
H
L
M
N
P
B
A
C
D
E
F
G
H
L
M
N
P
DIRECTORATE OF PUBLIC WORKS
AA1 00217-4
U.S. ARMY GARRISON VICENZA - DMC, APO AE 09613
SYMBOL DESCRIPTION OF REVISION
E1
DIRECTORATE OF PUBLIC WORKS
REMOVE POLES AND INSTALL EXTERIOR LIGHTS AT PAD 2025
NEW EXTERNAL LIGHTING SYSTEM
NUOVO IMPIANTO DI ILLUMINAZIONE ESTERNA
U.S. Army Garrison Vicenza - DMC, APO AE 09613
DRAWN DATE APPR
DEPARTMENT OF THE ARMY
AMMUNITION STORAGE AREA
REMOVE POLES AND INSTALL EXTERIOR LIGHTS AT PAD 2025
CHECKED BY
ENGINEERED BY
DRAWN BY
SUBMITTED
CHIEF ENGINEERING SERVICES
RECOMMENDED
RECOMMENDED
PROJECT NUMBER DATE SHEET OF
RECOMMENDED
RECOMMENDED
APPROVED
FOR USING ORGANIZATION
DIRECTOR OF PUBLIC WORKSCHIEF ENGINEERING DIVISION
APPROVEDRECOMMENDED
APPROVED
USAG COMMANDER
25 AUGUST 2014AA1 00217-4 1
4 8 12 16 20
20 40 60 8010
METERS
FEET
LUCETTI G.
LUCETTI G.
LUCETTI G.
SCALE
1 : 300
CONSTRUCTION WORK ITEMS
LAVORI DI COSTRUZIONE
NEW FLOODLIGHT WITH NEW BRAKETS SUITABLE FOR THE INSTALLATION ON THE METAL STRUCTURE
NUOVO PROIETTORE CON NUOVE STAFFE ADATTE PER L'INSTALLAZIONE SULLA STRUTTURA METALLICA
UP TO THE PAVEMENT LEVEL
TERMINALS AND LEAVE THEM INSIDE THE POLE MANHOLE. INSTALL A METALLIC COVER ON THE CUT BASE OF POLE E COVER WITH CONCRETE
CUT THE POLE 10 cm UNDER THE PAVEMENT LEVEL; DISCONNECT POLE FEEDING CABLES, PROVIDE WATERPROOFING INSULATION OF CABLES
PAVIMENTAZIONE
TAPPO METALLICO LO SPEZZONE DI PALO RIMASTO E COPRIRE IL TUTTO CON CEMENTO FINO ALLLA QUOTA DELLA
EFFETTURARE UN ISOLAMENTO STAGNO DEI TERMINALI DEI CAVI E LASCIARLI ALL'INTERNO DEL POZZETTO; COPRIRE CON UN
TAGLIARE IL PALO 10cm SOTTO IL LIVELLO DELLA PAVIMENTAZIONE; SCOLLEGARE I CAVI DI ALIMENTAZIONE DEL PALO, LEGEND
LEGENDA
EXISTING ELECTRICAL PANEL
QUADRO ELETTRICO ESISTENTE
NEW GALVANIZED STEEL CONDUIT WALL MOUNTED FROM THE EXISTING CABLE TRAY TO THE NEW LIGHTING FIXTURES
NUOVO TUBO IN ACCIAIO ZINCATO INSTALLATO A PARETE DALLA PASSERELLA ESISTENTE
INSTALLED ON THE METALLIC COLUMN AT 10 METER HEIGHT. POINTING ANGLE 20 DEGREES.
NUOVO PROIETTORE IODURI METALLICI 400W, CORPO IN ALLUMINIO, IP66, FASCIO ASIMMETRICO
NEW METAL HALIDE FLOODLIGHT 400W, ALUMINUM BODY, IP66, ASYMMETRIC BEAM
INSTALLATO SULLA COLONNA METALLICA A 10 METRI DI ALTEZZA; ANGOLO DI PUNTAMENTO 20 GRADI.
MOUNTED ON THE METAL STRUCTURE.
SHALL BE FG7OR 3G2.5 sqmm, ROUTED IN NEW GALVANIZED STEEL CONDUITS 25mm DIA. AND IN METALLIC JUNCTION BOXES SURFACE
ONE FEEDING THE NORTH SIDE FIXTURES AND ONE FEEDING THE SOUTH SIDE FIXTURES. TERMINAL CABLES CONNECTING THE FIXTURES
N.2 NEW MAIN FEEDING CABLES FG7OR 5G2.5 sqmm, ROUTED INTO THE EXISTING CABLE TRAY AND IN NEW GALVANIZED STEEL CONDUIT DIA. 32, NUOVI TUBI IN ACCIAIO ZINCATO DIA. 25mm E IN CASSETTE DI GIUNZIONE METALLICHE MONTATE SULLA STRUTTURA METALLICA.
APPARECCHIATURE LATO SUD. I CAVI TERMINALI COLLEGANTI LE APPARECCHIATURE SARANNO FG7OR 3G2.5 mmq, CABLATI IN
TUBAZIONE IN ACCIAIO ZINCATO DIA. 32, UNO ALIMENTANTE LE APPARECCHIATURE LATO NORD E UNO ALIMENTANTE LE
N.2 NUOVI CAVI DI ALIMENTAZIONE PRINCIPALI TIPO FG70R 5G2.5 POSATI NELLA PASSERELLA ESISTENTE E IN UNA NUOVA
ALLE NUOVE APPARECCHIATURE ILLUMINANTI
EXISTING METALLIC CABLE TRAY WITH COVER, INSTALLED BETWEEN 9 AND 12 METERS HEIGHT
CANALA METALLICA ESISTENTE CON TAPPO, INSTALLATA FRA 9 E 12 METRI DI ALTEZZA
N
2 2 2
EXISTING GALVANIZED STEEL LIGHTING POLE 12 METER HIGH, WITH MANHOLE
PALO ESISTENTE DI ILLUMINAZIONE IN ACCIAIO ZINCATO, ALTEZZA 12 METRI, CON POZZETTO
.8
.2
.6
.0
6.10 6.10 6.106.10 6.10
61.00
6.10 6.10 6.106.10 6.10
+14.85
+9.25
+1.00
.9
.6
+12.25
HEA400HEA500
HEA600
HE200A
HE200A
HEA400 HEA500
HEA200
HEA200
HEA200
HEA200
HEA200
HEA200
HEA200
HE200A
HE200A
.0
HEA200 HEA200HEA200
PUSH BUTTONS SHALL BE COMPLETE WITH SPY LIGHT INDICATING THE COMMAND OF THE FIXTURES (ON/OFF)
NEW METALLIC BOX IP55 WITH 2 PUSH BUTTONS TO COMMAND THE NEW FIXTURES (NORTH AND SOUTH)
I PULSANTI SARANNO DOTATI DI LUCE SPIA INDICANTE IL COMANDO DELLE APPARECCHIATURE (ON/OFF)
NUOVA CASSETTA METALLICA IP55 CON 2 PULSANTI PER IL COMANDO DELLE NUOVE APPARECCHIATURE (NORD E SUD)
THE PANEL.
THE PANEL, THE NEW LIGHTING FIXTURES. STEP RELAYS SHALL BE COMMANDED BY 2 PUSH BUTTONS INSTALLED IN A METALLIC BOX OUTSIDE
Id=0.03A CLASS A, 4 POLES; THE BREAKERS SHALL FEED, THROUGH 2 NEW STEP RELAYS AND 2 CONTACTORS 4P Ir=25A TO BE INSTALLED IN
N.2 NEW CIRCUIT BREAKERS WITH MAGNETIC-THERMAL AND GROUND FAULT PROTECTION IN THE EXISTING PANEL: Ir=16A, I.C.=10kA, "C" CURVE, UNA CASSETTA METALLICA ESTERNA AL QUADRO.
In=25A, LE NUOVE APPARECCHIATURE ILLUMINANTI. I RELE' PASSO PASSO SARANNO COMANDATI DA 2 PULSANTI INSTALLATI IN
CLASSE A, 4 POLI; GLI INTERRUTTORI ALIMENTERANNO, MEDIANTE 2 NUOVI RELE' PASSO PASSO E 2 NUOVI CONTATTORI 4P
N.2 NUOVI INTERRUTTORI MAGNETOTERMICI DIFFERENZIALI NEL QUADRO ESISTENTE: In=16A, P.I.=10kA,, CURVA "C", Id=0.03A
AS BUILT BERTI 30/12/14
TEL. 0587/489186 FAX 489867
Via VICARESE 73 CALCINAIA (PI)
IMPIANTI TECNOLOGICI
IWORKS
TES www.seti-impianti.it seti@seti-impianti.it