Attachment152025-Lighting_system.pdf

PDF 227 KB Posted

Attached to
Remove Structural Columns JSP Building 2025, ASA Federal contract opportunity
Solicitation number
W912PF-16-R-0012
Issued by
Department of the Army Materiel Command Expeditionary Contracting Command Regional Contracting Office Vicenza-Africa 414th CSB

About this file

Attachment 15 - 2025 - Lightning system

View the file

Other files for this federal contract opportunity

Other files attached to Remove Structural Columns JSP Building 2025, ASA, newest first.
File Type Posted
Attachment18GeotechnicalReport.pdf PDF
Amendment0003.pdf PDF
Attachment122025-Floor_Plan.pdf PDF
Attachment132025-Foundation_Plan.pdf PDF
Amendment0002.pdf PDF
Attachment142025-Frames.pdf PDF
Attachment172025-Roof_Plan.pdf PDF
Attachment162025-Pier.pdf PDF
Attachment9PSCPrel.pdf PDF
Amendment0001.pdf PDF
Attachment11CostiSic.pdf PDF
Attachment10SchedeVal.pdf PDF
Attachment6RequisitiGenerali.pdf PDF
Solicitation16R0012.pdf PDF
Attachment5PastPerformanceQuest.pdf PDF
Attachment1SOW Att1.pdf PDF
Attachment4ConstrExperienceQuest.pdf PDF
Attachment8AntimafiaCert.pdf PDF
Attachment7RequisitiGeneraliBIS.pdf PDF
Attachment3DesignExperienceQuest.pdf PDF
Attachment2TechSpecs.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5 6 7 10 11 12 13 14 15 168 9

1 2 3 4 5 6 7 10 11 12 13 14 15 168 9

B

A

C

D

E

F

G

H

L

M

N

P

B

A

C

D

E

F

G

H

L

M

N

P

DIRECTORATE OF PUBLIC WORKS

AA1 00217-4

U.S. ARMY GARRISON VICENZA - DMC, APO AE 09613

SYMBOL DESCRIPTION OF REVISION

E1

DIRECTORATE OF PUBLIC WORKS

REMOVE POLES AND INSTALL EXTERIOR LIGHTS AT PAD 2025

NEW EXTERNAL LIGHTING SYSTEM

NUOVO IMPIANTO DI ILLUMINAZIONE ESTERNA

U.S. Army Garrison Vicenza - DMC, APO AE 09613

DRAWN DATE APPR

DEPARTMENT OF THE ARMY

AMMUNITION STORAGE AREA

REMOVE POLES AND INSTALL EXTERIOR LIGHTS AT PAD 2025

CHECKED BY

ENGINEERED BY

DRAWN BY

SUBMITTED

CHIEF ENGINEERING SERVICES

RECOMMENDED

RECOMMENDED

PROJECT NUMBER DATE SHEET OF

RECOMMENDED

RECOMMENDED

APPROVED

FOR USING ORGANIZATION

DIRECTOR OF PUBLIC WORKSCHIEF ENGINEERING DIVISION

APPROVEDRECOMMENDED

APPROVED

USAG COMMANDER

25 AUGUST 2014AA1 00217-4 1

4 8 12 16 20

20 40 60 8010

METERS

FEET

LUCETTI G.

LUCETTI G.

LUCETTI G.

SCALE

1 : 300

CONSTRUCTION WORK ITEMS

LAVORI DI COSTRUZIONE

NEW FLOODLIGHT WITH NEW BRAKETS SUITABLE FOR THE INSTALLATION ON THE METAL STRUCTURE

NUOVO PROIETTORE CON NUOVE STAFFE ADATTE PER L'INSTALLAZIONE SULLA STRUTTURA METALLICA

UP TO THE PAVEMENT LEVEL

TERMINALS AND LEAVE THEM INSIDE THE POLE MANHOLE. INSTALL A METALLIC COVER ON THE CUT BASE OF POLE E COVER WITH CONCRETE

CUT THE POLE 10 cm UNDER THE PAVEMENT LEVEL; DISCONNECT POLE FEEDING CABLES, PROVIDE WATERPROOFING INSULATION OF CABLES

PAVIMENTAZIONE

TAPPO METALLICO LO SPEZZONE DI PALO RIMASTO E COPRIRE IL TUTTO CON CEMENTO FINO ALLLA QUOTA DELLA

EFFETTURARE UN ISOLAMENTO STAGNO DEI TERMINALI DEI CAVI E LASCIARLI ALL'INTERNO DEL POZZETTO; COPRIRE CON UN

TAGLIARE IL PALO 10cm SOTTO IL LIVELLO DELLA PAVIMENTAZIONE; SCOLLEGARE I CAVI DI ALIMENTAZIONE DEL PALO, LEGEND

LEGENDA

EXISTING ELECTRICAL PANEL

QUADRO ELETTRICO ESISTENTE

NEW GALVANIZED STEEL CONDUIT WALL MOUNTED FROM THE EXISTING CABLE TRAY TO THE NEW LIGHTING FIXTURES

NUOVO TUBO IN ACCIAIO ZINCATO INSTALLATO A PARETE DALLA PASSERELLA ESISTENTE

INSTALLED ON THE METALLIC COLUMN AT 10 METER HEIGHT. POINTING ANGLE 20 DEGREES.

NUOVO PROIETTORE IODURI METALLICI 400W, CORPO IN ALLUMINIO, IP66, FASCIO ASIMMETRICO

NEW METAL HALIDE FLOODLIGHT 400W, ALUMINUM BODY, IP66, ASYMMETRIC BEAM

INSTALLATO SULLA COLONNA METALLICA A 10 METRI DI ALTEZZA; ANGOLO DI PUNTAMENTO 20 GRADI.

MOUNTED ON THE METAL STRUCTURE.

SHALL BE FG7OR 3G2.5 sqmm, ROUTED IN NEW GALVANIZED STEEL CONDUITS 25mm DIA. AND IN METALLIC JUNCTION BOXES SURFACE

ONE FEEDING THE NORTH SIDE FIXTURES AND ONE FEEDING THE SOUTH SIDE FIXTURES. TERMINAL CABLES CONNECTING THE FIXTURES

N.2 NEW MAIN FEEDING CABLES FG7OR 5G2.5 sqmm, ROUTED INTO THE EXISTING CABLE TRAY AND IN NEW GALVANIZED STEEL CONDUIT DIA. 32, NUOVI TUBI IN ACCIAIO ZINCATO DIA. 25mm E IN CASSETTE DI GIUNZIONE METALLICHE MONTATE SULLA STRUTTURA METALLICA.

APPARECCHIATURE LATO SUD. I CAVI TERMINALI COLLEGANTI LE APPARECCHIATURE SARANNO FG7OR 3G2.5 mmq, CABLATI IN

TUBAZIONE IN ACCIAIO ZINCATO DIA. 32, UNO ALIMENTANTE LE APPARECCHIATURE LATO NORD E UNO ALIMENTANTE LE

N.2 NUOVI CAVI DI ALIMENTAZIONE PRINCIPALI TIPO FG70R 5G2.5 POSATI NELLA PASSERELLA ESISTENTE E IN UNA NUOVA

ALLE NUOVE APPARECCHIATURE ILLUMINANTI

EXISTING METALLIC CABLE TRAY WITH COVER, INSTALLED BETWEEN 9 AND 12 METERS HEIGHT

CANALA METALLICA ESISTENTE CON TAPPO, INSTALLATA FRA 9 E 12 METRI DI ALTEZZA

N

2 2 2

EXISTING GALVANIZED STEEL LIGHTING POLE 12 METER HIGH, WITH MANHOLE

PALO ESISTENTE DI ILLUMINAZIONE IN ACCIAIO ZINCATO, ALTEZZA 12 METRI, CON POZZETTO

.8

.2

.6

.0

6.10 6.10 6.106.10 6.10

61.00

6.10 6.10 6.106.10 6.10

+14.85

+9.25

+1.00

.9

.6

+12.25

HEA400HEA500

HEA600

HE200A

HE200A

HEA400 HEA500

HEA200

HEA200

HEA200

HEA200

HEA200

HEA200

HEA200

HE200A

HE200A

.0

HEA200 HEA200HEA200

PUSH BUTTONS SHALL BE COMPLETE WITH SPY LIGHT INDICATING THE COMMAND OF THE FIXTURES (ON/OFF)

NEW METALLIC BOX IP55 WITH 2 PUSH BUTTONS TO COMMAND THE NEW FIXTURES (NORTH AND SOUTH)

I PULSANTI SARANNO DOTATI DI LUCE SPIA INDICANTE IL COMANDO DELLE APPARECCHIATURE (ON/OFF)

NUOVA CASSETTA METALLICA IP55 CON 2 PULSANTI PER IL COMANDO DELLE NUOVE APPARECCHIATURE (NORD E SUD)

THE PANEL.

THE PANEL, THE NEW LIGHTING FIXTURES. STEP RELAYS SHALL BE COMMANDED BY 2 PUSH BUTTONS INSTALLED IN A METALLIC BOX OUTSIDE

Id=0.03A CLASS A, 4 POLES; THE BREAKERS SHALL FEED, THROUGH 2 NEW STEP RELAYS AND 2 CONTACTORS 4P Ir=25A TO BE INSTALLED IN

N.2 NEW CIRCUIT BREAKERS WITH MAGNETIC-THERMAL AND GROUND FAULT PROTECTION IN THE EXISTING PANEL: Ir=16A, I.C.=10kA, "C" CURVE, UNA CASSETTA METALLICA ESTERNA AL QUADRO.

In=25A, LE NUOVE APPARECCHIATURE ILLUMINANTI. I RELE' PASSO PASSO SARANNO COMANDATI DA 2 PULSANTI INSTALLATI IN

CLASSE A, 4 POLI; GLI INTERRUTTORI ALIMENTERANNO, MEDIANTE 2 NUOVI RELE' PASSO PASSO E 2 NUOVI CONTATTORI 4P

N.2 NUOVI INTERRUTTORI MAGNETOTERMICI DIFFERENZIALI NEL QUADRO ESISTENTE: In=16A, P.I.=10kA,, CURVA "C", Id=0.03A

AS BUILT BERTI 30/12/14

TEL. 0587/489186 FAX 489867

Via VICARESE 73 CALCINAIA (PI)

IMPIANTI TECNOLOGICI

IWORKS

TES www.seti-impianti.it seti@seti-impianti.it

ENTERPRISE EXECUTING

File details come from the government source that posted it. Updated .