RFI__5_DTD_30_Jun_17.pdf

PDF 99 KB Posted

Attached to
New Construction - 175th NWS Facility
Solicitation number
W912K6-17-R-0004
Issued by

About this file

RFI #5 Dated 30 Jun 2017

View the file

Other files

File Type Posted
W912K6-17-R-0004-0001.pdf PDF
RFI__4_DTD_30_Jun_17.docx DOCX document
RFI__3_DTD_30_Jun_17.pdf PDF
C-505.pdf PDF
FtMeade_photo3.jpg JPG image
MAP 2.pdf PDF
FtMeade_photo4.jpg JPG image
Control.txt TXT text file
FtMeade_photo5.jpg JPG image
FtMeade_photo1.jpg JPG image
MAP 1.pdf PDF
RFI___2.docx DOCX document
FtMeade_photo2.jpg JPG image
RFI__1.pdf PDF
Preproposal_slides_FT._MEADE.pptx PPTX presentation
Preproposal_Sign_In_Sheet.pdf PDF
175th_WING_INSTALLATION_ACCESS_APPLICATION.pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI #5 Dated 30 Jun 2017

1) Floor Box Type 2 calls for 4 (four) RJ45 Jacks on Fiber Networks. What is the correct layout?

SIPR connection type should be DUPLEX LC

2) What color is Spare Voice and what Rack/Network do they terminate in?

Spare Voice shall be Green. Rack 9/A

3) Spare Fiber is to be Orange and Violet. How does one know where to put what color?

All fiber spares to be Violet

4) What Rack does Spare Fiber terminate in?

• FB1 – all spares are TS

• FB2 – Provide 1 spare for every 3 TS cables, and provide 1 spare for every 3 SIPR cables.

• FB3 – Provide 1 spare for each 1 TS cable. Provide 1 spare for every SIPR cable.

• FB4 – Provide 3 spares for every 1 TS cable.

• FB5 – Provide 2 spares for every 2 TS cables.

• FB6 – Provide 1 spare for each 1 TS cable. Provide 1 spare for every SIPR cable.

• FB7 – Provide 2 spares for every 2 TS cables, and provide 3 spares for every 1 SIPR cables.

• FB8 – Provide 1 spare for every 2 SIPR cables. Provide 1 spares for 4 TS cables.

All SIPR spare fiber goes to Rack 1/G. All TS spare fiber goes to Rack 6/F.

5) Is there a Basis of Design Manufacturer and/or Part Numbers for the specified Floor Boxes?

See A2 & A3, T-503