WATERVLI ET WAREHOUSE WATERVLIETWHSE
AMENDMENT 1
SECTI ON 22 00 00
PLUMBI NG, GENERAL PURPOSE
11/15
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AI R- CONDI TI ONI NG, HEATI NG AND REFRI GERATI ON I NSTI TUTE ( AHRI )
AHRI 1010 ( 2002) Sel f - Cont ai ned, Mechani cal l y Ref r i ger at ed Dr i nki ng- Wat er Cool er s
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ANSI Z21. 22/ CSA 4. 4 ( 2015) Rel i ef Val ves f or Hot Wat er Suppl y Systems
AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG
ENGI NEERS ( ASHRAE)
ASHRAE 189. 1 ( 2014; ERTA 1- 2 2015; ERTA 3- 4 2017)
St andar d f or t he Desi gn of Hi gh- Per f or mance Gr een Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs
ASHRAE 90. 1 - I P ( 2016; ERTA 1- 8 2017; I NT 1- 5 2017) Ener gy St andar d f or Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs
AMERI CAN SOCI ETY OF SANI TARY ENGI NEERI NG ( ASSE)
ASSE 1001 ( 2008) Per f or mance Requi r ement s f or At mospher i c Type Vacuum Br eaker s ( ANSI appr oved 2009)
ASSE 1003 ( 2009) Per f or mance Requi r ement s f or Wat er Pr essur e Reduci ng Val ves f or Domest i c Wat er Di st r i but i on Syst ems - ( ANSI appr oved 2010)
ASSE 1010 ( 2004) Per f or mance Requi r ement s f or Wat er Hammer Ar r est er s ( ANSI appr oved 2004)
ASSE 1011 ( 2004; Er r at a 2004) Per f or mance Requi r ement s f or Hose Connect i on Vacuum Br eaker s ( ANSI appr oved 2004)
ASSE 1012 ( 2009) Per f or mance Requi r ement s f or Backf l ow Pr event er wi t h an I nt er medi at e At mospher i c Vent - ( ANSI appr oved 2009)
ASSE 1013 ( 2011) Per f or mance Requi r ement s f or
SECTI ON 22 00 00 Page 1
07/ 17/ 18 3: 27 PM
Reduced Pr essur e Pr i nci pl e Backf l ow Pr event er s and Reduced Pr essur e Fi r e Pr ot ect i on Pr i nci pl e Backf l ow Pr event er s - ( ANSI appr oved 2010)
ASSE 1018 ( 2001) Per f or mance Requi r ement s f or Tr ap Seal Pr i mer Val ves - Pot abl e Wat er Suppl i ed ( ANSI Appr oved 2002
ASSE 1019 ( 2011) Per f or mance Requi r ement s f or Vacuum Br eaker Wal l Hydr ant s, Fr eeze Resi st ant , Aut omat i c Dr ai ni ng Type ( ANSI Appr oved 2004)
ASSE 1020 ( 2004; Er r at a 2004; Er r at a 2004) Per f or mance Requi r ement s f or Pr essur e Vacuum Br eaker Assembl y ( ANSI Appr oved 2004)
AMERI CAN WATER WORKS ASSOCI ATI ON ( AWWA)
AWWA 10084 ( 2005) St andar d Met hods f or t he Exami nat i on of Wat er and Wast ewat er
AWWA B300 ( 2010; Addenda 2011) Hypochl or i t es
AWWA B301 ( 2010) Li qui d Chl or i ne
AWWA C203 ( 2008) Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes - Enamel and Tape - Hot - Appl i ed
AWWA C511 ( 2017) Reduced- Pr essur e Pr i nci pl e Backf l ow Pr event i on Assembl y
AWWA C606 ( 2015) Gr ooved and Shoul der ed Joi nt s
AWWA C651 ( 2014) St andar d f or Di s i nf ect i ng Wat er Mains
AWWA C652 ( 2011) Di s i nf ect i on of Wat er - St or age Facilities
AWWA C700 ( 2015) St andar d f or Col d Wat er Met er s - Di spl acement Type, Br onze Mai n Case
AWWA C701 ( 2015) Col d- Wat er Met er s - Tur bi ne Type f or Cust omer Ser vi ce
AMERI CAN WELDI NG SOCI ETY ( AWS)
AWS A5. 8/ A5. 8M ( 2011; Amendment 2012) Speci f i cat i on f or Fi l l er Met al s f or Br azi ng and Br aze Wel di ng
AWS B2. 2/ B2. 2M ( 2016) Speci f i cat i on f or Br azi ng Pr ocedur e and Per f or mance Qual i f i cat i on
SECTI ON 22 00 00 Page 2
ASME I NTERNATI ONAL ( ASME)
ASME A112. 1. 2 ( 2012) St andar d f or Ai r Gaps i n Pl umbi ng Syst ems ( For Pl umbi ng Fi xt ur es and Wat er - Connect ed Recept or s)
ASME A112. 14. 1 ( 2003; R 2012) Backwat er Val ves
ASME A112. 19. 2/ CSA B45. 1 ( 2013) St andar d f or Vi t r eous Chi na Pl umbi ng Fi xt ur es and Hydr aul i c Requi r ement s f or Wat er Cl oset s and Ur i nal s
ASME A112. 36. 2M ( 1991; R 2012) Cl eanout s
ASME A112. 6. 1M ( 1997; R 2012) Fl oor Af f i xed Suppor t s f or Of f - t he- Fl oor Pl umbi ng Fi xt ur es f or Publ i c Use
ASME A112. 6. 3 ( 2016) St andar d f or Fl oor and Tr ench Dr ai ns
ASME B1. 20. 1 ( 2013) Pi pe Thr eads, Gener al Pur pose ( I nch)
ASME B16. 12 ( 2009; R 2014) Cast I r on Thr eaded Dr ai nage Fittings
ASME B16. 15 ( 2013) Cast Copper Al l oy Thr eaded Fi t t i ngs Cl asses 125 and 250
ASME B16. 18 ( 2012) Cast Copper Al l oy Sol der Joi nt Pr essur e Fi t t i ngs
ASME B16. 21 ( 2011) Nonmet al l i c Fl at Gasket s f or Pi pe Flanges
ASME B16. 22 ( 2013) St andar d f or Wr ought Copper and Copper Al l oy Sol der Joi nt Pr essur e Fi t t i ngs
ASME B16. 23 ( 2011) Cast Copper Al l oy Sol der Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 24 ( 2011) Cast Copper Al l oy Pi pe Fl anges and Fl anged Fi t t i ngs: Cl asses 150, 300, 600, 900, 1500, and 2500
ASME B16. 29 ( 2012) Wr ought Copper and Wr ought Copper Al l oy Sol der Joi nt Dr ai nage Fi t t i ngs - DWV
ASME B16. 3 ( 2011) Mal l eabl e I r on Thr eaded Fi t t i ngs, Cl asses 150 and 300
ASME B16. 34 ( 2017) Val ves - Fl anged, Thr eaded and Wel di ng End
ASME B16. 4 ( 2011) St andar d f or Gr ay I r on Thr eaded Fi t t i ngs; Cl asses 125 and 250
ASME B16. 5 ( 2017) Pi pe Fl anges and Fl anged Fi t t i ngs NPS 1/ 2 Thr ough NPS 24 Met r i c/ I nch St andar d
SECTI ON 22 00 00 Page 3
ASME B16. 50 ( 2013) Wr ought Copper and Copper Al l oy Br aze- Joi nt Pr essur e Fi t t i ngs
ASME B31. 1 ( 2016; Er r at a 2016) Power Pi pi ng
ASME B31. 5 ( 2016) Ref r i ger at i on Pi pi ng and Heat Tr ansf er Component s
ASME B40. 100 ( 2013) Pr essur e Gauges and Gauge Attachments
ASME BPVC SEC I V ( 2010) BPVC Sect i on I V- Rul es f or Const r uct i on of Heat i ng Boi l er s
ASME BPVC SEC I X ( 2010) BPVC Sect i on I X- Wel di ng and Br azi ng Qualifications
ASME CSD- 1 ( 2016) Cont r ol and Saf et y Devi ces f or Aut omat i cal l y Fi r ed Boi l er s
ASTM I NTERNATI ONAL ( ASTM)
ASTM A105/ A105M ( 2014) St andar d Speci f i cat i on f or Car bon St eel For gi ngs f or Pi pi ng Appl i cat i ons
ASTM A183 ( 2014) St andar d Speci f i cat i on f or Car bon St eel Tr ack Bol t s and Nut s
ASTM A193/ A193M ( 2016) St andar d Speci f i cat i on f or Al l oy- St eel and St ai nl ess St eel Bol t i ng Mat er i al s f or Hi gh- Temper at ur e Ser vi ce and Ot her Speci al Pur pose Appl i cat i ons
ASTM A47/ A47M ( 1999; R 2014) St andar d Speci f i cat i on f or Fer r i t i c Mal l eabl e I r on Cast i ngs
ASTM A515/ A515M ( 2010) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or I nt er medi at e- and Hi gher - Temper at ur e Service
ASTM A516/ A516M ( 2010; R 2015) St andar d Speci f i cat i on f or Pr essur e Vessel Pl at es, Car bon St eel , f or Moder at e- and Lower - Temper at ur e Ser vi ce
ASTM A518/ A518M ( 1999; R 2012) St andar d Speci f i cat i on f or Cor r osi on- Resi st ant Hi gh- Si l i con I r on Castings
ASTM A53/ A53M ( 2012) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess
ASTM A536 ( 1984; R 2014) St andar d Speci f i cat i on f or Duct i l e I r on Cast i ngs
ASTM A74 ( 2016) St andar d Speci f i cat i on f or Cast I r on Soi l Pi pe and Fi t t i ngs
SECTI ON 22 00 00 Page 4
ASTM A888 ( 2013a) St andar d Speci f i cat i on f or Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
ASTM B117 ( 2016) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us
ASTM B152/ B152M ( 2013) St andar d Speci f i cat i on f or Copper Sheet , St r i p, Pl at e, and Rol l ed Bar
ASTM B306 ( 2013) St andar d Speci f i cat i on f or Copper Dr ai nage Tube ( DWV)
ASTM B32 ( 2008; R 2014) St andar d Speci f i cat i on f or Sol der Met al
ASTM B370 ( 2012) St andar d Speci f i cat i on f or Copper Sheet and St r i p f or Bui l di ng Const r uct i on
ASTM B42 ( 2015a) St andar d Speci f i cat i on f or Seaml ess Copper Pi pe, St andar d Si zes
ASTM B43 ( 2014) St andar d Speci f i cat i on f or Seaml ess Red Br ass Pi pe, St andar d Si zes
ASTM B584 ( 2014) St andar d Speci f i cat i on f or Copper Al l oy Sand Cast i ngs f or Gener al Applications
ASTM B75/ B75M ( 2011) St andar d Speci f i cat i on f or Seaml ess Copper Tube
ASTM B813 ( 2016) St andar d Speci f i cat i on f or Li qui d and Past e Fl uxes f or Sol der i ng of Copper and Copper Al l oy Tube
ASTM B88 ( 2016) St andar d Speci f i cat i on f or Seaml ess Copper Wat er Tube
ASTM B88M ( 2016) St andar d Speci f i cat i on f or Seaml ess Copper Wat er Tube ( Met r i c)
ASTM C564 ( 2014) St andar d Speci f i cat i on f or Rubber Gasket s f or Cast I r on Soi l Pi pe and Fittings
ASTM C920 ( 2014a) St andar d Speci f i cat i on f or El ast omer i c Joi nt Seal ant s
ASTM D2000 ( 2012) St andar d Cl assi f i cat i on Syst em f or Rubber Pr oduct s i n Aut omot i ve Appl i cat i ons
ASTM D2235 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement f or Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) Pl ast i c Pi pe and Fi t t i ngs
ASTM D2564 ( 2012) St andar d Speci f i cat i on f or Sol vent
SECTI ON 22 00 00 Page 5
Cement s f or Pol y( Vi nyl Chl or i de) ( PVC) Pl ast i c Pi pi ng Syst ems
ASTM D2822/ D2822M ( 2005; R 2011; E 2011) St andar d Speci f i cat i on f or Asphal t Roof Cement , Asbestos-Containing
ASTM D2855 ( 2015) St andar d Pr act i ce f or Maki ng Sol vent - Cement ed Joi nt s wi t h Pol y( Vi nyl Chl or i de) ( PVC) Pi pe and Fi t t i ngs
ASTM D2996 ( 2015) Fi l ament - Wound " Fi ber gl ass" (Glass-Fiber-Reinforced Ther moset t i ng- Resi n) Pi pe
ASTM D3122 ( 1995; R 2009) Sol vent Cement s f or St yr ene- Rubber ( SR) Pl ast i c Pi pe and Fittings
ASTM D3138 ( 2004; R 2016) St andar d Speci f i cat i on f or Sol vent Cement s f or Tr ansi t i on Joi nt s Bet ween Acr yl oni t r i l e- But adi ene- St yr ene ( ABS) and Pol y( Vi nyl Chl or i de) ( PVC) Non- Pr essur e Pi pi ng Component s
ASTM D3139 ( 1998; R 2011) Joi nt s f or Pl ast i c Pr essur e Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3212 ( 2007; R 2013) St andar d Speci f i cat i on f or Joi nt s f or Dr ai n and Sewer Pl ast i c Pi pes Usi ng Fl exi bl e El ast omer i c Seal s
ASTM D3311 ( 2011; R 2016) Dr ai n, Wast e, and Vent ( DWV) Pl ast i c Fi t t i ngs Pat t er ns
ASTM E1 ( 2014) St andar d Speci f i cat i on f or ASTM Li qui d- i n- Gl ass Ther momet er s
ASTM F2389 ( 2010) St andar d Speci f i cat i on f or Pr essur e- r at ed Pol ypr opyl ene ( PP) Pi pi ng Systems
ASTM F477 ( 2014) St andar d Speci f i cat i on f or El ast omer i c Seal s ( Gasket s) f or Joi ni ng Pl ast i c Pi pe
ASTM F493 ( 2014) Sol vent Cement s f or Chl or i nat ed Pol y ( Vi nyl Chl or i de) ( CPVC) Pl ast i c Pi pe and Fi t t i ngs
CAST I RON SOI L PI PE I NSTI TUTE ( CI SPI )
CI SPI 301 ( 2009) Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and Vent Pi pi ng Appl i cat i ons
CI SPI 310 ( 2011) Coupl i ng f or Use i n Connect i on wi t h Hubl ess Cast I r on Soi l Pi pe and Fi t t i ngs f or Sani t ar y and St or m Dr ai n, Wast e, and
SECTI ON 22 00 00 Page 6
Vent Pi pi ng Appl i cat i ons
COPPER DEVELOPMENT ASSOCI ATI ON ( CDA)
CDA A4015 ( 2010) Copper Tube Handbook
FOUNDATI ON FOR CROSS- CONNECTI ON CONTROL AND HYDRAULI C RESEARCH
(FCCCHR)
FCCCHR Li st ( cont i nuousl y updat ed) Li st of Appr oved Backf l ow Pr event i on Assembl i es
I NTERNATI ONAL ASSOCI ATI ON OF PLUMBI NG AND MECHANI CAL OFFI CI ALS
(IAPMO)
I APMO PS 117 ( 2005b) Pr ess Type Or Pl ai n End Rub Gasket ed W/ Nai l CU & CU Al l oy Fi t t i ngs 4 I nst al l On CU Tubi ng
I NTERNATI ONAL CODE COUNCI L ( I CC)
I CC A117. 1 COMM ( 2009) St andar d And Comment ar y and Usabl e Bui l di ngs and Faci l i t i es
I CC I PC ( 2015) I nt er nat i onal Pl umbi ng Code
MANUFACTURERS STANDARDI ZATI ON SOCI ETY OF THE VALVE AND FI TTI NGS
I NDUSTRY ( MSS)
MSS SP- 110 ( 2010) Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
MSS SP- 25 ( 2013) St andar d Mar ki ng Syst em f or Val ves, Fi t t i ngs, Fl anges and Uni ons
MSS SP- 58 ( 1993; Reaf f i r med 2010) Pi pe Hanger s and Suppor t s - Mat er i al s, Desi gn and Manuf act ur e, Sel ect i on, Appl i cat i on, and Installation
MSS SP- 67 ( 2011) But t er f l y Val ves
MSS SP- 70 ( 2011) Gr ay I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 71 ( 2011; Er r at a 2013) Gr ay I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 72 ( 2010a) Bal l Val ves wi t h Fl anged or But t - Wel di ng Ends f or Gener al Ser vi ce
MSS SP- 78 ( 2011) Cast I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 80 ( 2013) Br onze Gat e, Gl obe, Angl e and Check Valves
MSS SP- 85 ( 2011) Gr ay I r on Gl obe & Angl e Val ves
SECTI ON 22 00 00 Page 7
Fl anged and Thr eaded Ends
NACE I NTERNATI ONAL ( NACE)
NACE SP0169 ( 2015) Cont r ol of Ext er nal Cor r osi on on Under gr ound or Submer ged Met al l i c Pi pi ng Systems
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 90A ( 2018) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
NSF I NTERNATI ONAL ( NSF)
NSF 372 ( 2011) Dr i nki ng Wat er Syst em Component s - Lead Cont ent
NSF/ ANSI 14 ( 2016a) Pl ast i cs Pi pi ng Syst em Component s and Rel at ed Mat er i al s
NSF/ ANSI 61 ( 2016) Dr i nki ng Wat er Syst em Component s - Heal t h Ef f ect s
PLASTI C PI PE AND FI TTI NGS ASSOCI ATI ON ( PPFA)
PPFA Fi r e Man ( 2010) Fi r est oppi ng: Pl ast i c Pi pe i n Fi r e Resi st i ve Const r uct i on
PLUMBI NG AND DRAI NAGE I NSTI TUTE ( PDI )
PDI WH 201 ( 2010) Wat er Hammer Ar r est er s St andar d
SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)
SAE J1508 ( 2009) Hose Cl amp Speci f i cat i ons
U. S. DEPARTMENT OF ENERGY ( DOE)
Ener gy St ar ( 1992; R 2006) Ener gy St ar Ener gy Ef f i c i ency Label i ng Syst em ( FEMP)
U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)
EPA SM 9223 ( 2004) Enzyme Subst r at e Col i f or m Test
PL 93- 523 ( 1974; A 1999) Saf e Dr i nki ng Wat er Act
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
PL 109- 58 Ener gy Pol i cy Act of 2005 ( EPAct 05)
UNDERWRI TERS LABORATORI ES ( UL)
UL 499 ( 2014) El ect r i c Heat i ng Appl i ances
1. 2 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
SECTI ON 22 00 00 Page 8 submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG.
Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL
PROCEDURES:
SD- 02 Shop Dr awi ngs
Pl umbi ng Syst em; G
Det ai l dr awi ngs consi st i ng of schedul es, per f or mance char t s, i nst r uct i ons, di agr ams, and ot her i nf or mat i on t o i l l ust r at e t he r equi r ement s and oper at i ons of syst ems t hat ar e not cover ed by t he Pl umbi ng Code. Det ai l dr awi ngs f or t he compl et e pl umbi ng syst em i ncl udi ng pi pi ng l ayout s and l ocat i ons of connect i ons; di mensi ons f or r oughi ng- i n, f oundat i on, and suppor t poi nt s; schemat i c di agr ams and wi r i ng di agr ams or connect i on and i nt er connect i on di agr ams. Det ai l dr awi ngs shal l i ndi cat e c l ear ances r equi r ed f or mai nt enance and oper at i on. Wher e pi pi ng and equi pment ar e t o be suppor t ed ot her t han as i ndi cat ed, det ai l s shal l i ncl ude l oadi ngs and pr oposed suppor t met hods. Mechani cal dr awi ng pl ans, el evat i ons, v i ews, and det ai l s, shal l be dr awn t o scal e.
SD- 03 Pr oduct Dat a
Fixtures
Li st of i nst al l ed f i x t ur es wi t h manuf act ur er , model , and f l ow rate.
Fl ush val ve Wat er Cl oset s; G S
Wal l Hung Lavat or i es; G , S
Dr i nki ng- Wat er Cool er s; G, S
I nst ant aneous Wat er Heat er s; G, S
Backf l ow Pr event i on Assembl i es; G
Cer t i f i cat i on of pr oper oper at i on shal l be as accompl i shed i n accor dance wi t h st at e r egul at i ons by an i ndi v i dual cer t i f i ed by t he st at e t o per f or m such t est s. I f no st at e r equi r ement exi st s, t he Cont r act or shal l have t he manuf act ur er ' s r epr esent at i ve t est t he devi ce, t o ensur e t he uni t i s pr oper l y i nst al l ed and per f or mi ng as i nt ended. The Cont r act or shal l pr ovi de wr i t t en document at i on of t he t est s per f or med and si gned by t he i ndi v i dual per f or mi ng t he t est s
Wal l Hydr ant s ( Fr ost pr oof ) ; G, S
Welding
A copy of qual i f i ed pr ocedur es and a l i s t of names and i dent i f i cat i on symbol s of qual i f i ed wel der s and wel di ng oper at or s.
Pl umbi ng Syst em
Di agr ams, i nst r uct i ons, and ot her sheet s pr oposed f or post i ng.
Manuf act ur er ' s r ecommendat i ons f or t he i nst al l at i on of bel l and
SECTI ON 22 00 00 Page 9 spi got and hubl ess j oi nt s f or cast i r on soi l pi pe.
SD- 06 Test Repor t s
Test s, Fl ushi ng and Di si nf ect i on
Test r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.
Test of Backf l ow Pr event i on Assembl i es; G.
Cer t i f i cat i on of pr oper oper at i on shal l be as accompl i shed i n accor dance wi t h st at e r egul at i ons by an i ndi v i dual cer t i f i ed by t he st at e t o per f or m such t est s. I f no st at e r equi r ement exi st s, t he Cont r act or shal l have t he manuf act ur er ' s r epr esent at i ve t est t he devi ce, t o ensur e t he uni t i s pr oper l y i nst al l ed and per f or mi ng as i nt ended. The Cont r act or shal l pr ovi de wr i t t en document at i on of t he t est s per f or med and si gned by t he i ndi v i dual per f or mi ng t he t est s.
SD- 07 Cer t i f i cat es
Mat er i al s and Equi pment
Wher e equi pment i s speci f i ed t o conf or m t o r equi r ement s of t he ASME Boi l er and Pr essur e Vessel Code, t he desi gn, f abr i cat i on, and i nst al l at i on shal l conf or m t o t he code.
Bolts
Wr i t t en cer t i f i cat i on by t he bol t manuf act ur er t hat t he bol t s f ur ni shed compl y wi t h t he speci f i ed r equi r ement s.
SD- 10 Oper at i on and Mai nt enance Dat a
Pl umbi ng Syst em; G
Submi t i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND
MAI NTENANCE DATA.
SD- 11 Cl oseout Submi t t al s
Wat er - Ef f i c i ent Pr oduct s; S
Ener gy- Ef f i c i ent Wat er Heat er s; S
1. 3 STANDARD PRODUCTS
Specified mat er i al s and equi pment shal l be st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of such pr oduct s.
Speci f i ed equi pment shal l essent i al l y dupl i cat e equi pment t hat has per f or med sat i sf act or i l y at l east t wo year s pr i or t o bi d openi ng.
St andar d pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year use shal l i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been f or sal e on t he commer ci al
SECTI ON 22 00 00 Page 10 mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2 year per i od.
1. 3. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a t wo- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er ' s f act or y or l abor at or y t est s, can be shown.
1. 3. 2 Ser vi ce Suppor t
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons. Submi t a cer t i f i ed l i s t of qual i f i ed per manent ser vi ce or gani zat i ons f or suppor t of t he equi pment whi ch i ncl udes t hei r addr esses and qual i f i cat i ons. These ser vi ce or gani zat i ons shal l be r easonabl y conveni ent t o t he equi pment i nst al l at i on and abl e t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 3. 3 Manuf act ur er ' s Namepl at e
Each i t em of equi pment shal l have a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent wi l l not be acceptable.
1. 3. 4 Modi f i cat i on of Ref er ences
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on" , or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer .
1. 3. 4. 1 Definitions
For t he I nt er nat i onal Code Counci l ( I CC) Codes r ef er enced i n t he cont r act document s, advi sor y pr ovi s i ons shal l be consi der ed mandat or y, t he wor d " shoul d" shal l be i nt er pr et ed as " shal l . " Ref er ence t o t he " code of f i c i al " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For Navy owned pr oper t y, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " Cont r act i ng Of f i cer . " For l eased f aci l i t i es, r ef er ences t o t he " owner " shal l be i nt er pr et ed t o mean t he " l essor . " Ref er ences t o t he " per mi t hol der " shal l be i nt er pr et ed t o mean t he " Cont r act or . "
1. 3. 4. 2 Admi ni st r at i ve I nt er pr et at i ons
For I CC Codes r ef er enced i n t he cont r act document s, t he pr ovi s i ons of Chapt er 1, " Admi ni st r at or , " do not appl y. These admi ni st r at i ve r equi r ement s ar e cover ed by t he appl i cabl e Feder al Acqui s i t i on Regul at i ons ( FAR) i ncl uded i n t hi s cont r act and by t he aut hor i t y gr ant ed t o t he Of f i cer i n Char ge of Const r uct i on t o admi ni st er t he const r uct i on of t hi s pr oj ect . Ref er ences i n t he I CC Codes t o sect i ons of Chapt er 1, shal l be appl i ed appr opr i at el y by t he Cont r act i ng Of f i cer as aut hor i zed by hi s admi ni st r at i ve cogni zance and t he FAR.
1. 4 DELI VERY, STORAGE, AND HANDLI NG
Handl e, st or e, and pr ot ect equi pment and mat er i al s t o pr event damage
SECTI ON 22 00 00 Page 11 bef or e and dur i ng i nst al l at i on i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons, and as appr oved by t he Cont r act i ng Of f i cer . Repl ace damaged or def ect i ve i t ems.
1. 5 PERFORMANCE REQUI REMENTS
1. 5. 1 Welding
Pi pi ng shal l be wel ded i n accor dance wi t h qual i f i ed pr ocedur es usi ng per f or mance- qual i f i ed wel der s and wel di ng oper at or s. Pr ocedur es and wel der s shal l be qual i f i ed i n accor dance wi t h ASME BPVC SEC I X. Wel di ng pr ocedur es qual i f i ed by ot her s, and wel der s and wel di ng oper at or s qual i f i ed by anot her empl oyer , may be accept ed as per mi t t ed by ASME B31. 1.
The Cont r act i ng Of f i cer shal l be not i f i ed 24 hour s i n advance of t est s, and t he t est s shal l be per f or med at t he wor k s i t e i f pr act i cabl e. Wel der s or wel di ng oper at or s shal l appl y t hei r assi gned symbol s near each wel d t hey make as a per manent r ecor d.
1. 6 REGULATORY REQUI REMENTS
Unl ess ot her wi se r equi r ed her ei n, pl umbi ng wor k shal l be i n accor dance with I CC I PC. Ener gy consumi ng pr oduct s and syst ems shal l be i n accor dance wi t h PL 109- 58 and ASHRAE 90. 1 - I P and pr ovi de l ead f r ee products.
1. 7 PROJECT/ SI TE CONDI TI ONS
The Cont r act or shal l become f ami l i ar wi t h det ai l s of t he wor k, ver i f y di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng any wor k.
1. 8 I NSTRUCTI ON TO GOVERNMENT PERSONNEL
When speci f i ed i n ot her sect i ons, f ur ni sh t he ser vi ces of compet ent i nst r uct or s t o gi ve f ul l i nst r uct i on t o t he desi gnat ed Gover nment per sonnel i n t he adj ust ment , oper at i on, and mai nt enance, i ncl udi ng per t i nent saf et y r equi r ement s, of t he speci f i ed equi pment or syst em.
I nst r uct or s shal l be t hor oughl y f ami l i ar wi t h al l par t s of t he i nst al l at i on and shal l be t r ai ned i n oper at i ng t heor y as wel l as pr act i cal oper at i on and mai nt enance wor k.
I nst r uct i on shal l be gi ven dur i ng t he f i r st r egul ar wor k week af t er t he equi pment or syst em has been accept ed and t ur ned over t o t he Gover nment f or r egul ar oper at i on. The number of man- days ( 8 hour s per day) of i nst r uct i on f ur ni shed shal l be as speci f i ed i n t he i ndi v i dual sect i on.
When mor e t han 4 man- days of i nst r uct i on ar e speci f i ed, use appr oxi mat el y hal f of t he t i me f or c l assr oom i nst r uct i on. Use ot her t i me f or i nst r uct i on wi t h t he equi pment or syst em.
When si gni f i cant changes or modi f i cat i ons i n t he equi pment or syst em ar e made under t he t er ms of t he cont r act , pr ovi de addi t i onal i nst r uct i on t o acquai nt t he oper at i ng per sonnel wi t h t he changes or modi f i cat i ons.
1. 9 ACCESSI BI LI TY OF EQUI PMENT
I nst al l al l wor k so t hat par t s r equi r i ng per i odi c i nspect i on, oper at i on, mai nt enance, and r epai r ar e r eadi l y accessi bl e. I nst al l conceal ed val ves, expansi on j oi nt s, cont r ol s, damper s, and equi pment r equi r i ng access, i n l ocat i ons f r eel y accessi bl e t hr ough access door s.
SECTI ON 22 00 00 Page 12
PART 2 PRODUCTS
2. 1 PRODUCT SUSTAI NABI LI TY CRI TERI A
For pr oduct s i n t hi s sect i on, wher e appl i cabl e and t o ext ent al l owed by per f or mance cr i t er i a, pr ovi de and document t he f ol l owi ng:
2. 1. 1 Wat er - Ef f i c i ent Pr oduct s
Pr ovi de document at i on i n conf or mance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG t hat t he f ol l owi ng pr oduct s meet wat er ef f i c i ency r equi r ement s as out l i ned i n t hi s sect i on and when appl i cabl e, t hat t hey ar e EPA Wat er Sense l abel ed pr oduct s:
a. Fi xt ur es
b. Fl ush val ve wat er c l oset s
c. Wal l hung l avat or i es
d. Dr i nki ng- wat er cool er s
e. Wat er heat er s
I nst ant aneous Wat er Heat er
2. 1. 2 Ener gy- Ef f i c i ent Wat er Heat er s
Pr ovi de document at i on i n conf or mance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG t hat t he f ol l owi ng pr oduct s meet ener gy ef f i c i ency r equi r ement s as out l i ned i n t hi s sect i on and when appl i cabl e, t hat t hey ar e Ener gy St ar cer t i f i ed or FEMP- desi gnat ed pr oduct s:
a. El ect r i c Resi st ance I nst ant aneous Wat er Heat er s )
2. 2 Materials
Mat er i al s f or var i ous ser vi ces shal l be i n accor dance wi t h TABLES I and I I . Pi pe schedul es shal l be sel ect ed based on ser vi ce r equi r ement s. Pi pe f i t t i ngs shal l be compat i bl e wi t h t he appl i cabl e pi pe mat er i al s.
Pol ypr opyl ene pi pe and f i t t i ngs shal l conf or m t o di mensi onal r equi r ement s of Schedul e 40, I r on Pi pe si ze and shal l compl y wi t h NSF/ ANSI 14, NSF/ ANSI 61 and ASTM F2389. Pol ypr opyl ene pi pi ng t hat wi l l be exposed t o UV l i ght shal l be pr ovi ded wi t h a Fact or y appl i ed UV r esi st ant coat i ng.
Pi pe t hr eads ( except dr y seal ) shal l conf or m t o ASME B1. 20. 1. Gr ooved pi pe coupl i ngs and f i t t i ngs shal l be f r om t he same manuf act ur er . Mat er i al or equi pment cont ai ni ng a wei ght ed aver age of gr eat er t han 0. 25 per cent l ead shal l not be used i n any pot abl e wat er syst em i nt ended f or human consumpt i on, and shal l be cer t i f i ed i n accor dance wi t h NSF/ ANSI 61, Annex G or NSF 372. I n l i ne devi ces such as wat er met er s, bui l di ng val ves, check val ves, met er st ops, val ves, f i t t i ngs and back f l ow pr event er s shal l compl y wi t h PL 93- 523 and NSF/ ANSI 61, Sect i on 8. End poi nt devi ces such as dr i nki ng wat er f ount ai ns, l avat or y f aucet s, k i t chen and bar f aucet s, r esi dent i al i ce maker s, suppl y st ops and end poi nt cont r ol val ves used t o di spense wat er f or dr i nki ng must meet t he r equi r ement s of NSF/ ANSI 61, Sect i on 9. Hubl ess cast - i r on soi l pi pe shal l not be i nst al l ed under gr ound, under concr et e f l oor s l abs, or i n cr awl spaces bel ow ki t chen f l oor s. Pl ast i c pi pe shal l not be i nst al l ed i n ai r pl enums. Pl ast i c pi pe
SECTI ON 22 00 00 Page 13 shal l not be i nst al l ed i n a pr essur e pi pi ng syst em i n bui l di ngs gr eat er t han t hr ee st or i es i ncl udi ng any basement l evel s.
2. 2. 1 Low Emi t t i ng Mat er i al s ( adhesi ves, cement s, seal ant s, pr i mer s) e
See Sect i on 01 33 29 LEED DOCUMENTATI ON f or VOC l i mi t ( g/ L) of pl umbi ng adhesi ves and seal ant s f i el d- appl i ed i nsi de t he weat her pr oof i ng syst em.
2. 2. 2 Pi pe Joi nt Mat er i al s
Gr ooved pi pe and hubl ess cast - i r on soi l pi pe shal l not be used under gr ound. Sol der cont ai ni ng l ead shal l not be used wi t h copper pi pe.
Cast i r on soi l pi pe and f i t t i ngs shal l be mar ked wi t h t he col l ect i ve t r ademar k of t he Cast I r on Soi l I nst i t ut e. Joi nt s and gasket mat er i al s shal l conf or m t o t he f ol l owi ng:
a. Coupl i ng f or Cast - I r on Pi pe: f or hub and spi got t ype ASTM A74, AWWA C606. For hubl ess t ype: CI SPI 310
b. Coupl i ng f or St eel Pi pe: AWWA C606.
c. Coupl i ngs f or Gr ooved Pi pe: Duct i l e I r on ASTM A536 ( Gr ade 65- 45- 12) .
d. Fl ange Gasket s: Gasket s shal l be made of non- asbest os mat er i al i n accor dance wi t h ASME B16. 21. Gasket s shal l be f l at , 1/ 16 i nch t hi ck, and cont ai n Ar ami d f i ber s bonded wi t h St yr ene But adi ene Rubber ( SBR) or Ni t r o But adi ene Rubber ( NBR) . Gasket s shal l be t he f ul l f ace or sel f cent er i ng f l at r i ng t ype. Gasket s used f or hydr ocar bon ser vi ce shal l be bonded wi t h NBR.
e. Br azi ng Mat er i al : Br azi ng mat er i al shal l conf or m t o AWS A5. 8/ A5. 8M, BCuP-5.
f . Br azi ng Fl ux: Fl ux shal l be i n past e or l i qui d f or m appr opr i at e f or use wi t h br azi ng mat er i al . Fl ux shal l be as f ol l ows: l ead- f r ee; have a 100 per cent f l ushabl e r esi due; cont ai n s l i ght l y aci di c r eagent s;
cont ai n pot assi um bor i des; and cont ai n f l uor i des.
g. Sol der Mat er i al : Sol der met al shal l conf or m t o ASTM B32.
h. Sol der Fl ux: Fl ux shal l be l i qui d f or m, non- cor r osi ve, and conf or m t o ASTM B813, St andar d Test 1.
i . PTFE Tape: PTFE Tape, f or use wi t h Thr eaded Met al or Pl ast i c Pi pe.
j . Rubber Gasket s f or Cast - I r on Soi l - Pi pe and Fi t t i ngs ( hub and spi got t ype and hubl ess t ype) : ASTM C564.
k. Rubber Gasket s f or Gr ooved Pi pe: ASTM D2000, maxi mum t emper at ur e 230 degr ees F.
l . Fl exi bl e El ast omer i c Seal s: ASTM D3139, ASTM D3212 or ASTM F477.
m. Bol t s and Nut s f or Gr ooved Pi pe Coupl i ngs: Heat - t r eat ed car bon st eel , ASTM A183.
n. Sol vent Cement f or Tr ansi t i on Joi nt s bet ween ABS and PVC Nonpr essur e
SECTI ON 22 00 00 Page 14
Pi pi ng Component s: ASTM D3138.
o. Pl ast i c Sol vent Cement f or ABS Pl ast i c Pi pe: ASTM D2235.
p. Pl ast i c Sol vent Cement f or PVC Pl ast i c Pi pe: ASTM D2564 and ASTM D2855.
q. Pl ast i c Sol vent Cement f or CPVC Pl ast i c Pi pe: ASTM F493.
r . Fl anged f i t t i ngs i ncl udi ng, but not l i mi t ed t o, f l anges, bol t s, nut s and bol t pat t er ns shal l be i n accor dance wi t h ASME B16. 5 c l ass 150 and shal l have t he manuf act ur er ' s t r ademar k af f i xed i n accor dance wi t h MSS SP- 25. Fl ange mat er i al shal l conf or m t o ASTM A105/ A105M. Bl i nd f l ange mat er i al shal l conf or m t o ASTM A516/ A516M col d ser vi ce and ASTM A515/ A515M f or hot ser vi ce. Bolts shal l be hi gh st r engt h or i nt er medi at e st r engt h wi t h mat er i al conf or mi ng t o ASTM A193/ A193M.
s. Pl ast i c Sol vent Cement f or St yr ene Rubber Pl ast i c Pi pe: ASTM D3122.
t . Pr ess f i t t i ngs f or Copper Pi pe and Tube: Copper pr ess f i t t i ngs shal l conf or m t o t he mat er i al and si z i ng r equi r ement s of ASME B16. 18 or ASME B16. 22 and per f or mance cr i t er i a of I APMO PS 117. Seal i ng el ement s f or copper pr ess f i t t i ngs shal l be EPDM, FKM or HNBR.
Seal i ng el ement s shal l be f act or y i nst al l ed or an al t er nat i ve suppl i ed f i t t i ng manuf act ur er . Seal i ng el ement shal l be sel ect ed based on manuf act ur er ' s appr oved appl i cat i on gui del i nes.
u. Copper t ubi ng shal l conf or m t o ASTM B88, Type K, L or M.
v. Heat - f usi on j oi nt s f or pol ypr opyl ene pi pi ng: ASTM F2389.
2. 2. 3 Mi scel l aneous Mat er i al s
Mi scel l aneous mat er i al s shal l conf or m t o t he f ol l owi ng:
a. Wat er Hammer Ar r est er : PDI WH 201. Wat er hammer ar r est er shal l be di aphr agm or pi st on t ype.
b. Copper , Sheet and St r i p f or Bui l di ng Const r uct i on: ASTM B370.
c. Asphal t Roof Cement : ASTM D2822/ D2822M.
d. Hose Cl amps: SAE J1508.
e. Suppor t s f or Of f - The- Fl oor Pl umbi ng Fi xt ur es: ASME A112. 6. 1M.
f . Met al l i c Cl eanout s: ASME A112. 36. 2M.
g. Pl umbi ng Fi xt ur e Set t i ng Compound: A pr ef or med f l exi bl e r i ng seal mol ded f r om hydr ocar bon wax mat er i al . The seal mat er i al shal l be nonvol at i l e nonasphal t i c and cont ai n ger mi ci de and pr ovi de wat er t i ght , gast i ght , odor pr oof and ver mi npr oof pr oper t i es.
h. Coal - Tar Pr ot ect i ve Coat i ngs and Li ni ngs f or St eel Wat er Pi pel i nes:
AWWA C203.
i . Hypochl or i t es: AWWA B300.
j . Li qui d Chl or i ne: AWWA B301.
SECTI ON 22 00 00 Page 15
k. Gauges - Pr essur e and Vacuum I ndi cat i ng Di al Type - El ast i c El ement :
ASME B40. 100.
l . Ther momet er s: ASTM E1. Mer cur y shal l not be used i n t her momet er s.
2. 2. 4 Pi pe I nsul at i on Mat er i al
I nsul at i on shal l be as speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON
FOR MECHANI CAL SYSTEMS.
2. 3 PI PE HANGERS, I NSERTS, AND SUPPORTS
Pi pe hanger s, i nser t s, and suppor t s shal l conf or m t o MSS SP- 58.
2. 4 VALVES
Val ves shal l be pr ovi ded on suppl i es t o equi pment and f i xt ur es. Valves 2- 1/ 2 i nches and smal l er shal l be br onze wi t h t hr eaded bodi es f or pi pe and sol der - t ype connect i ons f or t ubi ng. Val ves 3 i nches and l ar ger shal l have f l anged i r on bodi es and br onze t r i m. Pr essur e r at i ngs shal l be based upon t he appl i cat i on. Gr ooved end val ves may be pr ovi ded i f t he manuf act ur er cer t i f i es t hat t he val ves meet t he per f or mance r equi r ement s of appl i cabl e MSS st andar d. Val ves shal l conf or m t o t he f ol l owi ng st andar ds:
Description Standard
But t er f l y Val ves MSS SP- 67
Cast - I r on Gat e Val ves, Fl anged and Thr eaded Ends
MSS SP- 70
Cast - I r on Swi ng Check Val ves, Fl anged and Thr eaded Ends
MSS SP- 71
Bal l Val ves wi t h Fl anged But t - Wel di ng Ends f or Gener al Ser vi ce
MSS SP- 72
Bal l Val ves Thr eaded, Socket - Wel di ng, Sol der Joi nt , Gr ooved and Fl ar ed Ends
MSS SP- 110
Cast - I r on Pl ug Val ves, Fl anged and Thr eaded Ends
MSS SP- 78
Br onze Gat e, Gl obe, Angl e, and Check Val ves MSS SP- 80
St eel Val ves, Socket Wel di ng and Thr eaded Ends
ASME B16. 34
Cast - I r on Gl obe and Angl e Val ves, Fl anged and Thr eaded Ends
MSS SP- 85
SECTI ON 22 00 00 Page 16
Backwat er Val ves ASME A112. 14. 1
Vacuum Rel i ef Val ves ANSI Z21. 22/ CSA 4. 4
Wat er Pr essur e Reduci ng Val ves ASSE 1003
Wat er Heat er Dr ai n Val ves ASME BPVC SEC I V, Par t HLW- 810:
Requi r ement s f or Pot abl e- Wat er Heat er s Bot t om Dr ai n Val ve
Tr ap Seal Pr i mer Val ves ASSE 1018
Temper at ur e and Pr essur e Rel i ef Val ves f or Hot Wat er Suppl y Syst ems
ANSI Z21. 22/ CSA 4. 4
Temper at ur e and Pr essur e Rel i ef Val ves f or Aut omat i cal l y Fi r ed Hot Wat er Boi l er s
ASME CSD- 1
Saf et y Code No. , Par t CW, Ar t i c l e 5
2. 4. 1 Wal l Hydr ant s ( Fr ost pr oof )
ASSE 1019 wi t h vacuum- br eaker backf l ow pr event er shal l have a ni ckel - br ass or ni ckel - br onze wal l pl at e or f l ange wi t h nozzl e and det achabl e key handl e. A br ass or br onze oper at i ng r od shal l be pr ovi ded wi t hi n a gal vani zed i r on casi ng of suf f i c i ent l engt h t o ext end t hr ough t he wal l so t hat t he val ve i s i nsi de t he bui l di ng, and t he por t i on of t he hydr ant bet ween t he out l et and val ve i s sel f - dr ai ni ng. A br ass or br onze val ve wi t h coupl i ng and uni on el bow havi ng met al - t o- met al seat shal l be pr ovi ded. Val ve r od and seat washer shal l be r emovabl e t hr ough t he f ace of t he hydr ant . The hydr ant shal l have 3/ 4 i nch exposed hose t hr ead on spout and 3/ 4 i nch mal e pi pe t hr ead on i nl et .
2. 5 FIXTURES
Fi xt ur es shal l be wat er conser vat i on t ype, i n accor dance wi t h ASHRAE 189. 1 Sect i on 6. 3. 2. 1 ( Pl umbi ng f i xt ur es and Fi t t i ngs) . Wat er c l oset r epl acement s i n maj or r enovat i ons may have a f l ush val ve of up t o 1. 6 GPF t o accommodat e exi st i ng pl umbi ng capaci t y. Fi xt ur es f or use by t he physi cal l y handi capped shal l be i n accor dance wi t h I CC A117. 1 COMM.
Vi t r eous Chi na, nonabsor bent , har d- bur ned, and vi t r i f i ed t hr oughout t he body shal l be pr ovi ded. Por cel ai n enamel ed war e shal l have speci al l y sel ect ed, c l ear whi t eaci d- r esi st i ng enamel coat i ng evenl y appl i ed on sur f aces. No f i xt ur e wi l l be accept ed t hat shows cr acks, cr azes, bl i st er s, t hi n spot s, or ot her f l aws. Fi xt ur es shal l be equi pped wi t h appur t enances such as t r aps, f aucet s, st op val ves, and dr ai n f i t t i ngs.
Each f i xt ur e and pi ece of equi pment r equi r i ng connect i ons t o t he dr ai nage syst em, except gr ease i nt er cept or s, shal l be equi pped wi t h a t r ap. Br ass expansi on or t oggl e bol t s capped wi t h acor n nut s shal l be pr ovi ded f or suppor t s, and pol i shed chr omi um- pl at ed pi pe, val ves, and f i t t i ngs shal l be
SECTI ON 22 00 00 Page 17 pr ovi ded wher e exposed t o v i ew. Fi xt ur es wi t h t he suppl y di schar ge bel ow t he r i m shal l be equi pped wi t h backf l ow pr event er s. I nt er nal par t s of f l ush val ves and f l ushomet er val ves, shower mi xi ng val ves, shower head f ace pl at es, pop- up st opper s of l avat or y wast e dr ai ns, and pop- up st opper s and over f l ow t ees and shoes of bat ht ub wast e dr ai ns shal l be copper al l oy wi t h al l v i s i bl e sur f aces chr ome pl at ed
2. 5. 1 Lavatories
Vi t r eous chi na l avat or i es shal l be pr ovi ded wi t h t wo i nt egr al mol ded l ugs on t he back- under si de of t he f i x t ur e and dr i l l ed f or bol t i ng t o t he wal l i n a manner s i mi l ar t o t he hanger pl at e. Lavat or y f aucet s and l avat or y f aucet accessor i es must meet t he EPA Wat er Sense pr oduct def i ni t i on speci f i ed i n http://www.epa.gov/watersense/partners/product_program_specs.html and must be EPA Wat er Sense l abel ed pr oduct s.
2. 5. 2 Aut omat i c Cont r ol s
Fl ushi ng and f aucet syst ems shal l consi st of sol enoi d- act i vat ed val ves wi t h l i ght beam sensor s. Fl ush val ve f or wat er c l oset shal l i ncl ude an over r i de pushbut t on. Fl ushi ng devi ces shal l be pr ovi ded as descr i bed i n par agr aph FI XTURES AND FI XTURE TRI MMI NGS.
2. 5. 3 Fl ush Val ve Wat er Cl oset s
ASME A112. 19. 2/ CSA B45. 1, whi t evi t r eous chi na, s i phon j et , el ongat ed bowl , f l oor - mount ed, f l oor out l et Top of t oi l et seat hei ght above f l oor shal l be 14 t o 15 i nches, except 17 t o 19 i nches f or wheel chai r wat er c l oset s.
Pr ovi de wax bowl r i ng i ncl udi ng pl ast i c s l eeve. Pr ovi de whi t e sol i d pl ast i c el ongat ed cl osed- f r ont seat wi t h cover .
Wat er f l ushi ng vol ume of t he wat er c l oset and f l ush val ve combi nat i on shal l not exceed 1. 28 gal l ons per f l ush. Wat er c l oset s must meet t he EPA Wat er Sense pr oduct def i ni t i on speci f i ed i n http://www.epa.gov/watersense/partners/product_program_specs.html and must be EPA Wat er Sense l abel ed pr oduct s.
Pr ovi de l ar ge di amet er f l ush val ve i ncl udi ng angl e cont r ol - st op val ve, vacuum br eaker , t ai l pi eces, s l i p nut s, and wal l pl at es; exposed t o v i ew component s shal l be chr omi um- pl at ed or pol i shed st ai nl ess st eel . Fl ush val ves shal l be nonhol d- open t ype. Mount f l ush val ves not l ess t han 11 inches above t he f i xt ur e. Mount ed hei ght of f l ush val ve shal l not i nt er f er e wi t h t he hand r ai l i n ADA st al l s.
2. 5. 4 Wal l Hung Lavat or i es
ASME A112. 19. 2/ CSA B45. 1, whi t evi t r eous chi na, , st r ai ght back t ype, mi ni mum di mensi ons of 19 i nches, wi de by 17 i nches f r ont t o r ear , wi t h suppl y openi ngs f or use wi t h t op mount ed cent er set f aucet s, and openi ngs f or conceal ed ar m car r i er i nst al l at i on. Pr ovi de aer at or wi t h f aucet .
Wat er f l ow r at e shal l not exceed 0. 5 gpm when measur ed at a f l owi ng wat er pr essur e of 60 psi . Lavat or y f aucet s and l avat or y f aucet accessor i es must meet t he EPA Wat er Sense pr oduct def i ni t i on speci f i ed i n http://www.epa.gov/watersense/partners/product_program_specs.html and must be EPA Wat er Sense l abel ed pr oduct s. Pr ovi de ASME A112. 6. 1M conceal ed chai r car r i er s wi t h ver t i cal st eel pi pe suppor t s and conceal ed ar ms f or t he l avat or y. Mount l avat or y wi t h t he f r ont r i m 34 i nches above f l oor and with 29 i nches mi ni mum cl ear ance f r om bot t om of t he f r ont r i m t o f l oor .
SECTI ON 22 00 00 Page 18
Pr ovi de t op mount ed washer l ess cent er set l avat or y f aucet s.
2. 5. 5 Dr i nki ng- Wat er Cool er s
AHRI 1010 wi t h mor e t han a s i ngl e t hi ckness of met al bet ween t he pot abl e wat er and t he r ef r i ger ant i n t he heat exchanger , wal l - hung, bubbl er st y l e, ai r - cool ed condensi ng uni t , 4. 75 gph mi ni mum capaci t y, st ai nl ess st eel spl ash r ecept or and basi n, and st ai nl ess st eel cabi net . Bubbl er s shal l be cont r ol l ed by push l ever s or push bar s, f r ont mount ed or s i de mount ed near t he f r ont edge of t he cabi net . Bubbl er spout s shal l be mount ed at maxi mum of 36 i nches above f l oor and at f r ont of uni t basi n. Spout s shal l di r ect wat er f l ow at l east 4 i nches above uni t basi n and t r aj ect or y par al l el or near l y par al l el t o t he f r ont of uni t . Pr ovi de ASME A112. 6. 1M conceal ed st eel pi pe chai r car r i er s.
2. 6 BACKFLOW PREVENTERS
Backf l ow pr event i on devi ces must be appr oved by t he St at e or l ocal r egul at or y agenci es. I f t her e i s no St at e or l ocal r egul at or y agency r equi r ement s, t he backf l ow pr event i on devi ces must be l i s t ed by t he Foundat i on f or Cr oss- Connect i on Cont r ol & Hydr aul i c Resear ch, or any ot her appr oved t est i ng l abor at or y havi ng equi val ent capabi l i t i es f or bot h l abor at or y and f i el d eval uat i on of backf l ow pr event i on devi ces and assemblies.
Reduced pr essur e pr i nci pl e assembl i es, doubl e check val ve assembl i es, at mospher i c ( nonpr essur e) t ype vacuum br eaker s, and pr essur e t ype vacuum br eaker s shal l be meet t he above r equi r ement s.
Reduced pr essur e pr i nci pl e t ype conf or mi ng t o t he appl i cabl e r equi r ement s AWWA C511. Pr ovi de backf l ow pr event er compel et e wi t h 150 pounds, br onze, br ass mount ed gat e val ve and st r ai ner s, 304 st ai nl ess st eel or br onze, i nt er nal par t s. THe par t i cul aer make, model / desi gn, and si ze of backl f ow pr event er s t o be i nst al l ed must be i ncl uded i n t he l at est edi c i ot n of t he Li st of Appr oved Backf l ow Pr event i on Assembl i es i ssued by t he FCCCHR Li st and be accompani ed by a cer t i f i cat e of Ful l Appr oval f r om FCCCHR Li st .
Sel ec mat er i al s f or pi pi ng, st r ai ner s, and val ves used i n assembl y i nst al l at i on t hat ar e gal vani cal l y compat i bl e. Mat er i al s j oi ned, connect ed, or ot her wi se i n cont act ar e t o have no gr eat er t han 0. 25 V di f f er ence on t he Anodi c I ndex, unl ess separ at ed by a di el ect i r c t ype uni on or f i t t i ng.
Backf l ow pr event er s wi t h i nt er medi at e at mospher i c vent shal l conf or m t o ASSE 1012. Reduced pr essur e pr i nci pl e backf l ow pr event er s shal l conf or m to ASSE 1013. Hose connect i on vacuum br eaker s shal l conf or m t o ASSE 1011.
Pi pe appl i ed at mospher i c t ype vacuum br eaker s shal l conf or m t o ASSE 1001.
Pr essur e vacuum br eaker assembl y shal l conf or m t o ASSE 1020. Ai r gaps i n pl umbi ng syst ems shal l conf or m t o ASME A112. 1. 2.
2. 7 DRAINS
2. 7. 1 Fl oor Dr ai ns
Fl oor and shower dr ai ns shal l consi st of a gal vani zed body, i nt egr al seepage pan, and adj ust abl e per f or at ed or s l ot t ed chr omi um- pl at ed br onze, ni ckel - br onze, or ni ckel - br ass st r ai ner , consi st i ng of gr at e and t hr eaded col l ar . Fl oor dr ai ns shal l be cast i r on except wher e met al l i c wat er pr oof i ng membr ane i s i nst al l ed. Dr ai ns shal l be of doubl e dr ai nage pat t er n f or embeddi ng i n t he f l oor const r uct i on. The seepage pan shal l
SECTI ON 22 00 00 Page 19 have weep hol es or channel s f or dr ai nage t o t he dr ai npi pe. The st r ai ner shal l be adj ust abl e t o f l oor t hi ckness. A c l ampi ng devi ce f or at t achi ng f l ashi ng or wat er pr oof i ng membr ane t o t he seepage pan wi t hout damagi ng t he f l ashi ng or wat er pr oof i ng membr ane shal l be pr ovi ded when r equi r ed.
Dr ai ns shal l be pr ovi ded wi t h t hr eaded connect i on. Bet ween t he dr ai n out l et and wast e pi pe, a neopr ene r ubber gasket conf or mi ng t o ASTM C564 may be i nst al l ed, pr ovi ded t hat t he dr ai n i s speci f i cal l y desi gned f or t he r ubber gasket compr essi on t ype j oi nt . Fl oor and shower dr ai ns shal l conf or m t o ASME A112. 6. 3. Pr ovi de dr ai n wi t h t r ap pr i mer connect i on, t r ap pr i mer , and connect i on pi pi ng. Pr i mer shal l meet ASSE 1018.
2. 7. 1. 1 Dr ai ns and Backwat er Val ves
Dr ai ns and backwat er val ves i nst al l ed i n connect i on wi t h wat er pr oof ed f l oor s or shower pans shal l be equi pped wi t h bol t ed- t ype devi ce t o secur el y c l amp f l ashi ng.
2. 8 TRAPS
Unl ess ot her wi se speci f i ed, t r aps shal l be copper - al l oy adj ust abl e t ube t ype wi t h s l i p j oi nt i nl et and swi vel . Tr aps shal l be wi t hout a c l eanout . Pr ovi de t r aps wi t h r emovabl e access panel s f or easy c l ean- out at s i nks and l avat or i es. Tubes shal l be copper al l oy wi t h wal l s not l ess than 0. 032 i nch t hi ck wi t hi n commer ci al t ol er ances, except on t he out si de of bends wher e t he t hi ckness may be r educed sl i ght l y i n manuf act ur e by usual commer ci al met hods. I nl et s shal l have r ubber washer and copper al l oy nut s f or s l i p j oi nt s above t he di schar ge l evel . Swi vel j oi nt s shal l be bel ow t he di schar ge l evel and shal l be of met al - t o- met al or met al - t o- pl ast i c t ype as r equi r ed f or t he appl i cat i on. Nut s shal l have f l at s f or wr ench gr i p. Out l et s shal l have i nt er nal pi pe t hr ead, except t hat when r equi r ed f or t he appl i cat i on, t he out l et s shal l have socket s f or sol der - j oi nt connect i ons. The dept h of t he wat er seal shal l be not l ess than 2 i nches. The i nt er i or di amet er shal l be not mor e t han 1/ 8 i nch over or under t he nomi nal s i ze, and i nt er i or sur f aces shal l be r easonabl y smoot h t hr oughout . A copper al l oy " P" t r ap assembl y consi st i ng of an adj ust abl e " P" t r ap and t hr eaded t r ap wal l ni ppl e wi t h cast br ass wal l f l ange shal l be pr ovi ded f or l avat or i es. The assembl y shal l be a st andar d manuf act ur ed uni t and may have a r ubber - gasket ed swi vel j oi nt .
2. 9 I nst ant aneous WATER HEATERS
Wat er heat er t ypes and capaci t i es shal l be as i ndi cat ed. Each pr i mar y wat er heat er shal l have cont r ol s wi t h an adj ust abl e r ange t hat i ncl udes 90 t o 160 degr ees F. The t her mal ef f i c i enci es and st andby heat l osses shal l conf or m t o TABLE I I I f or each t ype of wat er heat er speci f i ed. Pl ast i c mat er i al s pol yet her i mi de ( PEI ) and pol yet her sul f one ( PES) ar e f or bi dden t o be used f or vent pi pi ng of combust i on gases. .
2. 9. 1 El ect r i c I nst ant aneous Wat er Heat er s ( Tankl ess)
UL 499 and UL l i s t ed f l ow swi t ch act i vat ed, t ankl ess el ect r i c i nst ant aneous wat er heat er f or wal l mount i ng bel ow si nk or l avat or y. El ect r i c i nst ant aneous ( t ankl ess) t ype heat er s must meet t he Ener gy St ar pr oduct def i ni t i on speci f i ed i n https://www.energystar.gov/products/spec and must be Ener gy St ar cer t i f i ed.
2. 10 DOMESTI C WATER SERVI CE METER
The r equi r ement s f or met er i ng and submet er i ng ar e speci f i ed i n Sect i on
SECTI ON 22 00 00 Page 20
33 11 00 WATER UTI LI TY…