½” Rigid 3/4” Rigid 1½” Rigid 1” Rigid ½” Rigid

= 4”x4” Box = 6”x6” Box STUB Up 3” Rigid Cat 5/6 and fiber Conduit

STE

MTG

MTG

MTG

MTG

MTG

MTG

Phone Control Listen Comm

Each cat 5/6 drop will have 1 box with 2 cat 5/6 lines and 2 Phone lines Each fiber drop will have 1 box with 2 fiber lines Each cat 5/6 and fiber box will need to have a lock box cover Standard electrical outlets with 2 per room in all meeting rooms and phone rooms Control room will need 4 electrical outlets Communications closet will need a 30amp dedicated outlet and a 20 amp dedicated outlet along with 2 standard electrical outlets Communications closet will need a temperature control system Communications closet will need a ground plate Fiber conduit will need to be Rigid conduit Cat 5/6 conduit can be EMT conduit Cat 5/6 conduit will run below fiber conduit