Appendix A - Existing PPCS Battery_Inverter Information.pdf
PDF 620 KB Posted
- Attached to
- Fort Peck Station Battery Replacement Federal contract opportunity
- Solicitation number
- W9128F23Q0040
About this file
This federal solicitation requests proposals to replace batteries and inverters at Fort Peck Station in Montana. The selected contractor will be required to supply and install a sixty-cell flooded lead acid battery bank each for the station service and uninterruptible power supply at Plant 1, conduct capacity testing on the station service battery at Plant 2, and optionally procure inverters, chargers, and a new battery rack. The contractor must commence work upon award and complete the project within 210 days of the notice to proceed. An optional site visit is scheduled for June 20, 2023. The estimated cost of construction is between $250,000 and $500,000. The soliciting agency is the Department of the Army Corps of Engineers Omaha District. Proposals are due by the date specified in the solicitation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W91218F23Q0040 A0003pdf.pdf | ||
| Appendix C - Existing PP2 Station Battery Information.pdf | ||
| BATTERY ROOM ACCESS.pdf | ||
| MFP-OPN83E1650_008.pdf | ||
| FP Station Battery Replacement Bidder Inquiries.pdf | ||
| W9128F23Q0040 FP STATION BATTERY - AM0002.pdf | ||
| MFP-OPN83E1601_003.pdf | ||
| IMG_2986.JPG | JPG image | |
| Appendix B - Existing PP1 Station Battery Information.pdf | ||
| MFP-OPN83E1602_017.pdf | ||
| IMG_2987.JPG | JPG image | |
| W9128F23Q0040 Site Visit Sign-In Sheet.pdf | ||
| W91218F23Q0040 AM0001pdf.pdf | ||
| Attachments from FP Powerhouse 1 Battery Replacement SOW.pdf | ||
| W91218F23Q0040 Solicitation.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-1
Appendix A UPS/PPCS Battery Bank and Inverter Charger Information
UPS/PPCS Battery Bank
1. Existing are C&D Technologies product 4XTJ9 for our UPS system. There are 15 jars, 4 cells/jar, and battery voltage is 134.4V.
2. Existing rack dimensions are 170” in length and 19” in width. The containment dimensions are 172” in length and 20.5” in width. Containment width to remain the same to maintain walking space between PPCS battery and PP1 Station Service Battery.
IMG_7325: Batteries and rack on the left side of the image closest to the wall.
IMG_2125: Battery nameplate, XT4J9 (IMG_2127)
PPCS Battery Bank
PP1 Station Service Battery Bank
A-2
Inverter Charger
1. Existing PPCS battery inverter charger is a Powerware 9170 with a max rating of 9kVA.
2. Powerware chassis can hold 6 modules, currently 4 power modules are ASY-0673 split-phase, and 1 charger module ASY-0675 (see images below).
(IMG_0614) Powerware 9170 nameplate
(IMG_2985) 1 charger module ASY-0675 (IMG_2987) 4 power modules, ASY-0673 split-phase
A-3
3. System Data from Powerware 9170:
File details come from the government source that posted it. Updated .