VARIABLE FREQUENCY DRIVE SYSTEMS FOR BRIDGE CRANES
Solicitation number
W9127N-16-R-0099
Issued by

About this file

Amendment 0002 vacates the BRAND NAME ONLY requirement in this solicitation modifies the language in FAR 52.212-2 Evaluation - Commercial Items incorporates FAR provision 52.211-6 to the solicitations' provision/clauses and extends the offer due date to 21 Sep 2016 at 2PM Pacific

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W66QKZ61728120

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

a. The purpose of this amendment is to vacate the BRAND NAME ONLY requirement in this solicitation, modify the language in FAR 52.212-2 "Evaluation - Commercial Items", incorporate FAR provision 52.211-6 to the solicitations' provision/clauses, and extend the offer due date to 21 Sep 2016 at 2PM Pacif ic.

b. There are no other changes made or implied. All Offerors shall provide a signed copy of each amendent w ith their proposal.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 15

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 13-Sep-2016

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W9127N-16-R-0099

X 9B. DATED (SEE ITEM 11)

25-Aug-2016

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

13-Sep-2016

CODE

USACE PORTLAND DISTRICT

333 SW 1ST AVE

PORTLAND OR 97204-3440

W9127N 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W9127N-16-R-0099

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE

The following have been added by full text:

SYNOPSIS OF CHANGE (AMD 0002)

Changes made within the Technical Specifications are identified below. Additionally, the government included FAR Clause 52.212-2, Evalauation of Commercial Items; as well as FAR Clause 52.211-6, Brand Name or Equal.

Part 1.1 Second paragraph Reason: Removed IEEE 519 requirements as they do not apply to VFD only but to a complete system.

Changed from:

" The VFD shall meet IEEE 519 specifications and shall be the same manufacture and of a type regularly supplied for cranes in the last five years. Drive controllers for the four main hoists and four aux hoists shall be variable-frequency AC with closed-loop flux vector control with feedback from a motor-shaft-mounted encoder. Drives for bridge travel and trolley travel shall be variable-frequency AC with open- or closed-loop vector control."

Changed to:

"The VFD shall be the same manufacture and of a type regularly supplied for cranes in the last five years. Drive controllers for the four main hoists and four aux hoists shall be variable-frequency AC with closed-loop flux vector control with feedback from a motor-shaft-mounted encoder. Drives for bridge travel and trolley travel shall be variable-frequency AC with open- or closed-loop vector control."

Part 1.2 REFERENCES Reason: In IEEE paragraph removed IEEE 519 requirements as they do not apply to VFD only but to a complete system.

Deleted:

"IEEE 519 (2014) Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems"

Part 1.3.3 Electrical Requirements Reason: Added "or as otherwise approved"

Changed from:

"Sensor and Control Wiring Surge Protection Ensure I/O functions as specified are protected against surges induced on control and sensor wiring installed indoors. Protect the inputs and outputs in both normal mode and common mode using the following two waveforms:"

Changed to:

" Sensor and Control Wiring Surge Protection

Ensure I/O functions as specified are protected against surges induced on control and sensor wiring installed indoors. Protect the inputs and outputs in both normal mode and common mode using the following two waveforms or as otherwise approved:"

SECTION SF 1449 - CONTINUATION SHEET

SOLICITATION/CONTRACT FORM

The required response date/time has changed from 16-Sep-2016 02:00 PM to 21-Sep-2016 02:00 PM.

The following have been added by full text:

52.211-6 BRAND NAME OR EQUAL (AUG 1999)

(a) If an item in this solicitation is identified as “brand name or equal,” the purchase description reflects the characteristics and level of quality that will satisfy the Government's needs. The salient physical, functional, or performance characteristics that “equal” products must meet are specified in the solicitation.

(b) To be considered for award, offers of “equal” products, including “equal” products of the brand name manufacturer, must--

(1) Meet the salient physical, functional, or performance characteristic specified in this solicitation;

(2) Clearly identify the item by--

(i) Brand name, if any; and

(ii) Make or model number;

(3) Include descriptive literature such as illustrations, drawings, or a clear reference to previously furnished descriptive data or information available to the Contracting Officer; and

(4) Clearly describe any modifications the offeror plans to make in a product to make it conform to the solicitation requirements. Mark any descriptive material to clearly show the modifications.

(c) The Contracting Officer will evaluate “equal” products on the basis of information furnished by the offeror or identified in the offer and reasonably available to the Contracting Officer. The Contracting Officer is not responsible for locating or obtaining any information not identified in the offer.

(d) Unless the offeror clearly indicates in its offer that the product being offered is an “equal” product, the offeror shall provide the brand name product referenced in the solicitation.

(End of provision)

The following have been modified:

SCOPE

BRIDGE CRANES #1 AND #2

VARIABLE FREQUENCY DRIVES

SCOPE

1. GENERAL: This scope details the general requirements of the variable frequency drives (VFD) and all associated components that are to be provided including delivery information. Based on best engineering, the contractor shall deliver VFDs and all associated components in accordance with these specifications.

2. LOCATION: The VFDs and all associated components shall be delivered to the Bonneville Dam Warehouse, Bonneville Lock and Dam, Cascade Locks, Oregon 97014. The Project can be accessed via the south entrance gate from Interstate 84. Prior to delivery, the contractor shall notify the Bonneville Project POC a minimum of 2 days in advance.

3. CONTRACTOR QUALIFICATION REQUIREMENTS. Reserved.

4. REQUIREMENTS: VFDs and all associated components provided shall be new. Refer to technical specification “Division 26 – Electrical, Section 26 29 23, Bonneville Bridge Crane #1 and #2 - Variable Frequency Drive systems under 600 volts” which provides the salient features required for the design, assembly and programing of the new VFDs to be provided.

5. QUANTITIES. See Bid Schedule

6. SAFETY: All of the Contractors delivery activity shall conform to the requirements of the US ARMY Corps of Engineers Safety and Health Requirements Manual, EM 385-1-1, dated November 20, 2014. This Manual may be viewed/printed from the World Wide Web address at http://www.usace.army.mil/SafetyandOccupationalHealth/SafetyandHealthRequirementsManual.aspx

7. PERFORMANCE PERIOD: All mandatory items including VFDs, all associated components and O&M manuals shall be delivered to the site on or before 8 weeks from award of contract. The optional item onsite support for VFD programing shall be available for the government to exercise up to 12 months from award of contract.

8. DELIVERY: Normal Bonneville Project business hours are between 6:30 am to 5:00 p.m. Monday through Thursday. Non regular delivery hours may be coordinated with the Project in advance. The Contractor shall coordinate with the Project regarding all component delivery.

9. MISCELLANEOUS REQUIRMENTS.

9.1 WARRANTY: The VFDs and all associated components furnished under this contract shall be warranted against defects in materials and workmanship and against loss of use in accordance with manufacturer commercial warranties for the items identified here in.

9.2 SUBMITTALS: The contractor shall provide complete submittal(s) as required in the technical specifications.

The submittals shall be sent to the technical POC. The submittals may be mailed, faxed, or sent by email.

10. MEASUREMENT AND PAYMENT. Direct Purchase of the VFDs and all associated components. The item includes production and delivery including O&M manual and warranty in accordance with the requirements of the specifications. Upon receipt and acceptance of the VFDs, O&M Manuals, and warranty the lump sum price will be paid.

11. POINT OF CONTACTS: The Contractor shall assign an official Point of Contact for Government coordination of activities. Points of Contact for the Government for this contract include:

http://www.usace.army.mil/SafetyandOccupationalHealth/SafetyandHealthRequirementsManual.aspx

Contracting Specialist: Robbie Newland U.S. Army Corps of Engineers P.O. Box 2946 Portland, Or. 97208

(503) 808-4634

(503) 808-4605 (Fax)

Technical POC will be provided after date of award.

SPECIFICATIONS

DIVISION 26 – ELECTRICAL SECTION 26 29 23

BONNEVILLE BRIDGE CRANE #1 AND #2 - VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600

VOLTS

PART 1 GENERAL

1.1 Provide a total of fourteen fully programmed and tested 480VAC Variable Frequency Drives (VFD) with dynamic braking units and/or braking resistors for two bridge cranes at Bonneville Project Powerhouse I.

The VFD for the CMAA class A Bridge Cranes #1 and #2 are assigned as follows:

- Two bridge travel VFD each driving four 25HP motors.

- Four trolley travel VFD each driving one 20HP motor.

- Eight hoist VFD each driving a 60HP motor.

- VFD parameterization and monitoring software. Provide two sets of the manufacturer’s latest software to be licensed to the government.

- The four braking units and resistors for the main hoists shall be CMAA class F rated

The VFD shall be the same manufacture and of a type regularly supplied for cranes in the last five years.

Drive controllers for the four main hoists and four aux hoists shall be variable-frequency AC with closed-loop flux vector control with feedback from a motor-shaft-mounted encoder. Drives for bridge travel and trolley travel shall be variable-frequency AC with open- or closed-loop vector control.

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and

Less) AC Power Circuits

IEEE C62.41.2 (2002; C 2012) Recommended Practice on Characterization of Surges in Low- Voltage (1000 V and Less) AC Power Circuits

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements

NEMA ICS 2 (2000; R 2005) Industrial Control and System Controllers, Contactors, and

Overload Relays Rated 600 Volts

NEMA ICS 8 (2000: R 2005) Industrial Control and Systems Crane and Hoist Controllers

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014;

Errata 3-4 2014; AMD 4-6 2014) National Electrical Code

UNDERWRITERS LABORATORIES (UL)

UL 508C (2002; Reprint Nov 2010) Power Conversion Equipment

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-STD-461 (2007; Rev F) Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

47 CFR 15 (2014) Radio Frequency Devices

1.3 SYSTEM DESCRIPTION

1.3.1 General Performance Requirements

Electromagnetic Interference Suppression

Certify computing devices, as defined by 47 CFR 15, MIL-STD-461 rules and regulations, comply with the requirements for class A computing devices and labeled as set forth in part 15.

1.3.2 Electromechanical and Electrical Components

Ensure electrical and electromechanical components of the Variable Frequency Drives do not cause electromagnetic interference to adjacent electrical or electromechanical equipment while in operation.

1.3.3 Electrical Requirements

Sensor and Control Wiring Surge Protection Ensure I/O functions as specified are protected against surges induced on control and sensor wiring installed indoors. Protect the inputs and outputs in both normal mode and common mode using the following two waveforms or as otherwise approved:

(1) A 10 microsecond by 1000 microsecond waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.

(2) An 8 microsecond by 20 microsecond waveform with a peak voltage of 1000 volts and a peak current of 500 amperes.

1.4 SUBMITTALS

Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.

SD-02 Shop Drawings

Schematic Diagrams; G Interconnecting Diagrams; G

Installation Instructions; G

Submit drawings for Government approval prior to equipment construction or integration. Record modifications to original drawings made during construction immediately for inclusion into the as-built drawings.

SD-03 Product Data

Variable Frequency Drives; G Dynamic braking units; G Braking resistors; G Motor Compatibility Information and VFD programing; G

SD-08 Manufacturer's Instructions

Installation Instructions; G

SD-10 Operation and Maintenance Data

Variable Frequency Drives; G

Provide service and maintenance information including preventive maintenance, assembly, and disassembly procedures. Submit additional information necessary to provide complete operation, repair, and maintenance information, detailed to the smallest replaceable unit. Provide routine preventative maintenance instructions, and equipment required. Provide instructions on how to modify program settings, and modify the control program. Provide instructions on drive adjustment, trouble-shooting, and configuration. Provide instructions on process tuning and system calibration.

1.4 QUALITY ASSURANCE

1.4.1 Schematic Diagrams

Show circuits and device elements for each replaceable module. Schematic diagrams of printed circuit boards are permitted to group functional assemblies as devices, provided that sufficient information is provided for government maintenance personnel to verify proper operation of the functional assemblies.

1.4.2 Interconnecting Diagrams

Show interconnections between equipment assemblies, and external interfaces, including power and signal conductors. Include for external devices.

1.4.3 Equipment Schedule

Provide a schedule of equipment to be supplied. Provide a cross reference in the schedule between manufacturer data and identifiers indicated in shop drawings. Include the total quantity of each item of equipment supplied in the schedule. For complete assemblies, such as VFD, provide the serial numbers of each assembly, and a sub-schedule of components within the assembly. Provide recommended spare parts listing for each assembly or component.

1.4.4 Installation Instructions

Provide installation instructions issued by the manufacturer of the equipment, including notes and recommendations, prior to shipment to the site. Provide operation instructions prior to delivery.

1.4.6 Motor Compatibility Information and VFD programing

Prior to shipment to the site, for each VFD provide specific crane application data showing VFD compatibility with the corresponding motor listed below and a complete list of each VFD parameters settings required for the VFD to meet all the requirements listed in Part 2.

Name plate info Bridge Motors Trolley Motors Hoist Motors Manufacturer Marathon Electric Blue Max Marathon Electric Model 6N 286THTP8042AA

L

6N 256THTPA8036AA

L

6N 364THDS7042AN

W

HP 25 20 60

Base Frequency Hz 60 60 60 Nominal RPM 1775 1750 1780 Max RPM 3600 4200 2700 Phases/Voltage/Amps 3/460/32.5 3/460/26 3/460/72 Duty/Service factor CONT/1.0 60 min/1.0 CONT/1.15 Speed Reducer N1/N2 1800/52.67 1800/7.30 1750/39.6* *Additional hoists speed reduction is provided in the drums gear box.

1.5 DELIVERY AND STORAGE

Store equipment delivered and placed in storage with protection from the weather, humidity and temperature variations, dirt and dust, or other contaminants.

1.6 WARRANTY

Warranty the variable speed drives furnished under this contract against defects in materials and workmanship for a minimum period of one year from the date of acceptance of the drives by the Bonneville Project. Provide delivery of parts and/or service to the Government with 24 hours of notice by the Government to the Contractor as part of the warranty.

1.8 MAINTENANCE SUPPORT

During the warranty period, Provide on-site, on-call maintenance services by Contractor's personnel on a per-call basis with 36-hour response. Provide support for the maintenance of all hardware and software of the system supplied. Send various personnel of different expertise on-site depending on the nature of the maintenance service required. Include costs for travel, local transportation, living expenses, and labor rates of the service personnel while responding to the service request. The provisions of this Section are not in lieu of, nor relieve the Contractor of, warranty responsibilities covered in this specification. Should the result of the service request be the uncovering of a system defect covered under the warranty provisions, all costs for the call, including the labor necessary to identify the defect, shall be borne by the Contractor.

PART 2 PRODUCTS

2.1 General

The new VFD and brake units shall fit in the existing enclosures without relocating any other existing components, use existing power supply and interface with the existing sensors and 120VAC controls.

2.1.1 The existing bridge VFD configuration and dimensions in inches are as follows:

a. 145kVA 460/460V Delta/Wye isolation transformer

b. VFD name plate IDM CIMR-G5U4075 output 0-460V 0-400Hz 165A

c. CDBR-4220 brake unit

d. Interface board P/N 101830

e. Single brake system

f. Existing enclosure dimensions 60H x 60W x 18D

g. Existing drive dimensions 18.11W x 32.25H x 13.78D

h. Existing main hoist brake unit dimensions 9.875W x 13H x 8D

i. Existing braking resistor dimensions 24W x 18H x 30.25D

j. Controls inputs: Fwd. 1st speed, Rev. 1st speed, 2nd speed, 3rd speed, 4th speed, 5th speed, and normal/slow speed

k. Rated travel speed 95 feet per minute

2.1.2 The existing trolley VFD configuration and dimensions in inches are as follows:

a. 27kVA 460/460V Delta/Wye isolation transformer

b. VFD name plate IDM CIMR-G5U4011 output 0-460V 0-400Hz 28.6A

c. Resistor only brake system

d. Interface board P/N 101830

e. Single brake system

f. Existing enclosure dimensions 60H x24W x 18D

g. Existing drive dimensions 9.84W x 14.96H x 8.86D

h. Existing braking resistor dimensions 10W x 10H x 28.125D

i. Controls inputs: Fwd. 1st speed, Rev. 1st speed, 2nd speed, 3rd speed, 4th speed, 5th speed, and normal/slow speed

k. Rated travel speed 50 feet per minute

2.1.3 The existing main hoists VFD configuration and dimensions in inches are as follows:

a. 75kVA 460/460V Delta/Wye isolation transformer

b. VFD name plate IDM CIMR-G5U4037 output 0-460V 0-400Hz 80A

c. CDBR-4220 brake unit for Main Hoists

d. DBC-4060 9.6 Ohms 43,466W resistor for Main Hoist

e. PG-X2 encoder interface card with Slim Tach SL56 Encoder 5-15 VDC 1024 PPR

f. 120/240 VAC interface board P/N 101810

g. Interface board P/N 101830

h. Redundant brake system

j. Existing enclosure dimensions 60.06H x 48.06W x 18.06D

k. Existing drive dimensions 12.99W x 30.91H x 11.22D

l. Existing main hoist brake unit dimensions 9.875W x 13.25H x 8D

m. Existing braking resistor dimensions 23W x 24H x 30D

n. Controls inputs: Hoist 1st speed, Lower 1st speed, 2nd speed, 3rd speed, 4th speed, 5th speed, and normal/slow speed

o. Rated hoisting speed 4 feet per minute, hook travel 85 feet

p. Each main hoist is rated at 150 ton

2.1.4 The existing auxiliary hoists VFD configuration and dimensions in inches are as follows:

a. 75kVA 460/460V Delta/Wye isolation transformer

b. VFD name plate IDM CIMR-G5U4037 output 0-460V 0-400Hz 80A

c. CDBR-4045 brake unit for Aux Hoists

d. DBH-4040 12.00 17,156W resistor for Aux Hoist

e. PG-X2 encoder interface card with Slim Tach SL56 Encoder 5-15 VDC 1024 PPR

f. 120/240 VAC interface board P/N 101810

g. Interface board P/N 101830

h. Redundant brake system

j. Existing enclosure dimensions 60.06H x 48.06W x 18.06D

k. Existing drive dimensions 12.99W x 30.91H x 11.22D

l. Existing aux hoist brake unit dimensions 5.5W x 5.875H x 5.5D

m. Existing braking resistor dimensions 16W x 10H x 28.125D

n. Controls inputs: Hoist 1st speed, Lower 1st speed, 2nd speed, 3rd speed, 4th speed, 5th speed, and normal/slow speed

o. Rated hoisting speed 38.5 feet per minute, hook travel 160 feet

p. Each auxiliary hoist is rated at 30 ton

2.2 VARIABLE FREQUENCY DRIVES (VFD)

2.2.1 General

a. VFD shall be compatible with Allen Bradley Controllogix systems using the Ethernet/IP communications protocol, with documented capability for control and monitoring over Ethernet.

b. VFD shall be of a type regularly supplied for cranes in the last five years. Drive controllers for hoists shall be variable-frequency AC with closed-loop flux vector control with feedback from a motor-shaft-mounted encoder. Drives for travel shall be variable-frequency AC with open- or closed-loop vector control as necessary to meet accuracy requirements. V/Hz shall not be used in the VFD settings. VFD shall be mounted on control panels such that the digital keypad displays are visible without opening the panels; digital keypad displays shall be no lower than three feet and no higher than five feet from the walking surface in front of the displays.

2.2.2 VFD Operating Features

A separate VFD shall be provided for each motion. VFD for each motion shall provide true four-quadrant control and shall be the solid state, pulse width modulated (PWM) type with adequate capacity to drive motors at all specified loads and speeds. VFD shall be rated for continuous duty with an ambient temperature of 40 degrees C and at the motor current necessary to lift rated load at all speeds. VFD shall have an overload capacity rating of 150 percent rated load for 1 minute. Power factor shall be 0.95 or above from full speed to zero speed and at rated torque. Speed regulation shall be less than 1.0 percent from no-load to full-load, over the entire frequency range. Acceleration and deceleration shall be separately adjustable from 0.1 to 20 seconds. Motor overload protection shall be included with the VFD. The control circuit shall include an adjustable-operating current-limiting circuit capable of limiting maximum current to not more than the current necessary to obtain 200 percent motor torque. VFD shall be capable of storing, as a minimum, the most recent ten fault condition codes which shall remain accessible after resetting the drive. VFD shall be provided with communication modules required for proper communication modules required for proper connection with future PLC. In addition, VFD shall: monitor load to verify that enough motor torque has built up before the holding brake is released; monitor load to verify that holding brakes are maintaining load before removing power from the motor; and continuously monitor and alarm if holding brakes slip while the crane is energized. Alarm circuits for the preceding brake monitoring functions shall initiate visible alarm at the operator's control station. Brake monitoring functions shall not be connected to the control system such as to de-activate the main-line contactor when brake fault is detected.

2.3 Hoist and Travel Operating Features

2.3.1 General

Five intermediate points of speed control shall be provided for both hoisting and lowering, and for each direction of travel.

a. Variable speed control from zero to 100 percent shall be provided for both hoisting and lowering. Means shall be provided to limit the maximum torque a hoist motor can develop, and the controls shall be adjusted such that hook loads greater than 200 percent rated hook load cannot be lifted. The load-speed characteristics shall be inherent in the controls at each speed setting.

Speed control in the lowering direction shall be such as to permit the operator to stop the hook from any speed point, without time delay, by returning the master control switch to the "OFF" position. Positive control of the lowering movement of all hoist hooks shall be maintained under all conditions of load.

b. Controls shall be provided with adjustable compensation that allows initial electronic adjustment of the speed between hoists operating at the same selected speed and load to be within

0.1 percent of each other.

c. Variable speed control from zero to 100 percent shall be provided for each direction of travel. Travel motion controls shall provide constant speed on each respective control point for all hook loads. Circuits shall be arranged so that the operator may hold the control on any speed point. Sufficient speed droop or other acceptable means shall be provided in the travel drives to permit satisfactory operation when two drives are mechanically interlocked. Compensating circuits shall be provided so that the steady-state operating deviation and service deviation band of speed regulation shall each not exceed 1 percent of the rated speed for all hook loads.

2.3.2 Hoisting and Lowering Performances

The following hoisting and lowering performances are required, and shall be suitable for administering all loads, from no load on the hook to rated load.

a. The starting speed control setting for hoisting and lowering shall provide one-hundredth of one (0.01) percent speed regulation, 1000 to one (1000:1) control range, and position control at zero speed. The starting speed control setting shall start at the beginning of the master switch range (microswitch run command to the VFD).

b. Hoists. The highest (fastest) normal speed control setting for hoisting and lowering shall provide a hoisting speed of 100 percent rated speed at rated load.

c. Main Hoists. The highest (fastest) speed control setting for hoisting and lowering shall provide a hoisting speed of 100 percent rated speed at rated load. This setting shall be field-programmable for a range of 100 to 200 percent rated speed, operable above 100 percent rated speed only when there is light load on the hook/block and when the ultralift is selected via future ultralift selector switch. The initial setting for ultralift shall be 200 percent rated speed.

d. All intermediate speed control settings for hoisting and lowering shall operate linearly between the starting speed control setting and the highest (fastest) speed control setting.

2.3.3 Travel Performances

Bridge and trolley travel control shall provide travel speeds as follows:

a. The starting speed control setting for travel shall have a minimum operating travel speed of no more than one (1) percent of the 100 percent rated travel speed. The starting speed control setting shall start at the beginning of the master switch range (microswitch run command to the

VFD).

b. The highest (fastest) speed control setting for travel shall be 100 percent rated travel speed (for normal operating speed).

c. All intermediate speed control settings for travel shall operate linearly between the starting speed control setting and the highest (fastest) speed control setting.

2.3.4 Tandem Main Hoisting and Lowering Performances

There shall be no more than one-quarter (1/4) of an inch difference per twenty (20) feet of hoisting or lowering measured in one direction, or as otherwise approved, between all hoist in tandem. All "Hoisting and Lowering Performances" shall be achieved in tandem

2.3.5 Positioning Accuracy

The control system shall be so designed that it will be possible to limit the motion of any hoist or travel motion to not more than 0.0625-inch starting from complete standstill with any load up to and including rated load. The Government will verify this during acceptance testing by monitoring drum and/or brake wheel movement in relation to block and wheel travel.

2.4 Dynamic Braking for VFD

Hoist and travel controls shall provide dynamic braking. Mechanical or electrical load brakes shall not be used. Resistors for dynamic braking circuits shall: be of the non-breakable, corrosion-resisting type; have a low temperature coefficient; have a thermal capacity of not less than Class 160 series in accordance with Part 11 of NEMA ICS 8; and be rated for continuous duty.

2.5 Source Quality Control - VFD Factory Test Plan

To ensure proper performance upon delivery, subject each VFD to 100 percent factory tests. Provide test plans and test reports.

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Hardware installation will be performed by the government.

3.1.2 The Contractor shall work with the equipment manufacturers to make available “onsite support” services of competent installation technicians for configuration, startup, and testing. Technicians shall have the responsibility of checking the VFD settings and making any field adjustments necessary to obtain a working system within the applicable requirements.

52.212-2 EVALUATION--COMMERCIAL ITEMS (OCT 2014)

The Government will award a contract resulting from this solicitation to the responsible offeror whose offer is the lowest price and whom conforms to the solicitation’s salient characteristics of the brand name or equal identified in the specifications. The following shall serve as the basis in evaluating or equal brands:

If an offeror submits a brand other than what is specified as an ‘or equal’ the contractor shall provide literature, cut-outs or other data illustrating that it meets the ‘salient characteristics’ of the brand name identified. The Government will evaluate the ‘or equal’ to determine if the product offered meets the salient characteristics of the brand name identified in the solicitation. If it is found that it does not, the offer will not be considered for award.

The Government does not intend to enter into discussions with the offeror for the purpose of examining other products the offeror may choose to offer inplace of what was submitted with their offer. Award will be made to the lowest priced offer meeting the salient characteristics of the brand(s) or equals specified.

(End of provision)

(End of Summary of Changes)

BRIDGE CRANES #1 AND #2
VARIABLE FREQUENCY DRIVES
Technical POC will be provided after date of award.