Drawings_(Part_9_of_9).pdf
PDF 6 MB Posted
- Attached to
- FY19 RRAD General Purpose Warehouse Federal contract opportunity
- Solicitation number
- W9126G19B0007
About this file
Drawings Part 9 of 9
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_SF_1409_Abstract_of_Offerors.pdf | ||
| A7_Amendment_5.pdf | ||
| A7_Amendment_4.pdf | ||
| Amendment_3.pdf | ||
| Site_Visit.pdf | ||
| A7_Amendment_2.pdf | ||
| A10_FF&E_Package_(GPW)_FINAL.pdf | ||
| B3_Amendment_1.pdf | ||
| FFE_Package_(GPW)_FINAL.pdf | ||
| Drawings_(Part_8_of_9).pdf | ||
| Drawings_(Part_3_of_9).pdf | ||
| Drawings_(Part_7_of_9).pdf | ||
| Drawings_(Part_1_of_9).pdf | ||
| Drawings_(Part_2_of_9).pdf | ||
| Drawings_(Part_4_of_9).pdf | ||
| Drawings_(Part_5_of_9).pdf | ||
| Drawings_(Part_6_of_9).pdf | ||
| B3_W9126G19B0007_(Part_3_of_4).pdf | ||
| B3_W9126G19B0007_(Part_4_of_4).pdf | ||
| B3_W9126G19B0007_(Part_1_of_4).pdf | ||
| B3_W9126G19B0007_(Part_2_of_4).pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R E
D
R
I V
A
M
Y
D
E P
O T
H
O O
K S
T
E X
A S
F Y
D
L
G
N
E R
P
U R
P O
S
W
R
E H
O U
S E
SHEET
SEQUENCE
NUMBER
W G
B
1 2 3 4 5
D r a w n b y
D e s i g n e d b y
S u b m i t t e d b y
F i l
N a m e
D a t e
C o n t r a c t
N o
S o l i c i t a t i o n
N o
U S
A
R M
Y
E
N G
I N
E E
R
D
I S
T R
I C
T
C O
R P
S
O
F
E
N G
I N
E E
R S
F O
T
W
O R
T H
T
E X
A S
R e v i e w d b y
FORT WORTH DISTRICT
US ARMY CORPS
OF ENGINEERS ®
D
C
B
A
P L
C A
L E
P L
D
T
E
R e v
S y m b o l
D e s c r i p t i o n
T r a c k i n g
N o
A c t i o n
D a t e
E N
G I N
E E
R I N
G
C O
N S
T R
U C
T I O
N
D
I V
I S
I O
N
E N
G I N
E E
R I N
G
B
R A
N C
H
D A
R E
N
B
R O
W N
P
E
C H
I E
F
E
L E
C T
R I C
C
T I O
N
F E
B R
U A
Y
ES506
L I F
T
S
T A
T I O
N
E L
E C
T R
I C
D
T
A I L
S
K
L
E
P
E
K
L
E
P
E
A v e r y
P
B r o w n
LIGHTING PLAN SYMBOLS
A, b
A, b
A, b
A, b
A, b
A, b
WALL MOUNTED LED LIGHT FIXTURE. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET
BOX.
LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY
BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
DOWNLIGHT LED FIXTURE. LETTERS SAME AS ABOVE.
BACK MOUNTED EXIT SIGN. CAPITAL LETTER DENOTES TYPE. SHADED AREA
INDICATES FACE SIDES. PROVIDE DIRECTIONAL ARROWS WHERE INDICATED.
MOUNT 7'-6" AFF UNO.
CONTROL SWITCH, WALL MOUNTED 44" AFF.
NO OPTION INDICATES MANUAL CONTROL SWITCH (ON/OFF).
SMALL LETTER DENOTES SWITCH ID OPERATES FIXTURE HAVING SAME LETTER.
"3" OR "4" DENOTES 3-WAY, 4-WAY SWITCH.
"S" DENOTES SENSE LIGHTING CONTROL
"K" DENOTES KEYED SWITCH
"D" DENOTES DIMMER SWITCH
WALL MOUNTED LED LIGHT FIXTURE. LETTERS SAME AS ABOVE.
DESCRIPTIONSYMBOL
GENERAL NOTES:
1. ALL MOTOR STARTERS SHALL BE PROVIDED WITH AN INDICATOR
LAMP. LAMP SHALL BE "ON" WHEN MOTOR IS RUNNING.
2. A GREEN 600V INSULATED GROUND WIRE SHALL BE PROVIDED IN
ALL CONDUITS.
3. EMERGENCY LIGHTING FIXTURES SHALL BE WIRED SO THAT THE
LIGHTS WILL TURN ON AND OFF WITH THE OCCUPANCY SENSORS
OR WALL SWITCH IF APPLICABLE. WHEN THE NORMAL POWER
SUPPLYING THE CIRCUIT HAS FAILED, THE FIXTURE WILL SWITCH
TO EMERGENCY BATTERY POWER. THEY SHALL NOT BE WIRED AS
NIGHT LIGHTS UNO.
4. AT ALL LOCATIONS WHERE ACCESS TO MECHANIC EQUIPMENT,
PIPING, AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE
CONDUIT SHALL BE MOUNTED ABOVE, OR SO THAT THERE WILL BE
SUFFICIENT ACCESS SPACE TO MAINTENANCE AND REPLACEMENT.
5. A DISCONNECT SWITCH CAPABLE OF BEING INDIVIDUALLY LOCKED
IN THE OPEN POSITION SHALL BE LOCATED WITHIN SIGHT OF THE
MOTOR DRIVEN EQUIPMENT AND/OR ASSOCIATED STARTER. THESE
DISCONNECTS SHALL BE IN ADDITION TO ALL OTHER DISCONNECTS
PROVIDED ON OR WITH MOTOR DRIVEN EQUIPMENT. THERE SHALL
NEVER BE A STARTER-DISCONNECT-MOTOR SITUATION.
6. UNO, MINIMUM SIZE FOR SAFETY SWITCH SHALL BE 30A, 3P, 4W,
NEMA 1, 240-V OR 600-V AS APPLIED.
7. PANEL AND CIRCUIT NUMBERS OF EQUIPMENT ARE PLACED NEXT
TO THE EQUIPMENT IN THE DRAWING.
8. UNO, MININUM CIRCUIT CONDUCTORS SHALL BE # 12 AWG IN 1/2" C.
A, b
A, b
LED LIGHT FIXTURE. CAPITAL LETTER DENOTES TYPE. SMALL LETTER DENOTES THE
SWITCH ID CONTROLLING THE FIXTURE IF THE SWITCH IS NOT PLACED IN THE SAME
ROOM OF THE FIXTURE. CIRCLE IS OUTLET BOX.
CEILING MOUNTED EXIT SIGN. CAPITAL LETTER DENOTES TYPE. SHADED AREA
INDICATES FACE SIDES. PROVIDE DIRECTIONAL ARROWS WHERE INDICATED.
A
DESCRIPTIONSYMBOL
AIR TERMINAL, 5/8" DIA x 24 " BLUNT OR ROUNDED ALUMINUM.
TW
b, S K D
POWER PLAN SYMBOLS
R
WP,
GF,
TV
"R" INDICATES RAINTIGHT, NEMA 3R.
SAFETY OR DISCONNECT SWITCH, UNFUSED UNO.
QUADRUPLEX RECEPTACLE, GROUNDED TYPE MOUNTED 18" AFF, UNO.
DESCRIPTIONSYMBOL
F,C DUPLEX RECEPTACLE. GROUNDED TYPE.
"C" INDICATES CEILING FLUSH-MOUNTED, UNO.
"F" INDICATES FLOOR FLUSH-MOUNTED, WITH HINGED COVER, UNO
J STANDARD J-BOX. WALL FLUSH-MOUNTED 18" AFF UNO.
TR
TELECOMMUNICATIONS SYMBOLS
W WALL MOUNTED OUTLET WITH ONE RJ-45 MODULAR JACK. MOUNTED 48" AFF UNO.
WIRELESS ACCESS POINT WITH (2) RJ-45 MODULAR JACKS FOR DATA. SUSPENDED
29'-0" AFF UNO.
19" TELECOMMUNICATIONS EQUIPMENT RACK.
DESCRIPTIONSYMBOL
WALL MOUNTED OUTLET WITH (2) RJ-45 MODULAR JACK. MOUNTED 18" AFF UNO.
ELECTRICAL GROUND
F QUADRUPLEX RECEPTACLE. GROUNDED TYPE.
FLOOR FLUSH-MOUNTED, WITH HINGED COVER UNO.
SURFACE MOUNTED PANELBOARD .
FLUSH MOUNTED PANELBOARD .
A, b 2' x 2' LED LIGHT FIXTURE. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
A, b
SB
T
ELECTRICAL ABBREVIATIONS
AC ABOVE COUNTER
ACS ACCESS CONTROL SYSTEM
AFF ABOVE FINISHED FLOOR.
AFG ABOVE FINISHED GRADE.
A/V AUDIO VISUAL SYSTEM
COR CONTRACTING OFFICER'S REPRESENTATIVE
DDC DIRECT DIGITAL CONTROL
EMGB ELECTRICAL MAIN GROUNDING BUSBAR
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GF GROUND FAULT INTERRUPTER
GND GROUND
IDS INTRUSION DETECTION SYSTEM
MNS MASS NOTIFICATION SYSTEM
RECP RECEPTACLE
PoE POWER OVER ETHERNET
SPD SURGE PROTECTIVE DEVICE
TR TELECOMMUNICATIONS ROOM
TGB TELECOMMUNICATIONS GROUNDING BUSBAR
TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
UNO UNLESS NOTED OTHERWISE.
WALL MOUNTED OUTLET WITH (4) RJ-45 MODULAR JACK. MOUNTED 18" AFF UNO.4
WAP
WALL MOUNTED LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER
EMERGENCY BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
2' x 2' LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY
BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
DOWNLIGHT LED FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY
BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
WALL MOUNTED LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER
EMERGENCY BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
SECURITY SYMBOLS
SYMBOLS DESCRIPTION
CR
BALANCED MAGNETIC SWITCH
CARD READER. MOUNTED AT 42" AFF UNO
WEATHERPROOF FIXED CAMERA . MOUNTED AT 10'-0" AFF UNO
ACP ACCESS CONTROL PANEL
ES ELECTRIC STRIKE
INV
ACPS
IDCP
KP
MS
ACCESS CONTROL POWER SUPPLY.
INTRUSION DETECTION CONTROL PANEL.
KEYPAD FOR ACCESS CONTROL SYSTEM
CEILING-MOUNTED MOTION SENSOR.
DUPLEX RECEPTACLE, GROUNDED TYPE
"WP" INDICATES WEATHERPROOF TYPE. MOUNTED 18" AFF, UNO.
"GF" INDICATES GROUND FAULT INTERRUPTER TYPE. MOUNTED 18" AFF, UNO.
"TV" INDICATES DUPLEX RECEPTACLE FOR TV. WALL MOUNTED 8'-0" AFF, UNO
LOCKING RECEPTACLE WITH 208 V, 30 AMP, NEMA L6-30R, PENDANT MOUNT 8'-0" AFF,
UNO
LOCKING RECEPTACLE WITH 125 V, 30 AMP, NEMA L5-30R, MOUNTED IN RACK
SWITCHBOARD .
DRY TYPE TRANSFORMER.
CENTRALIZED INVERTER FOR EMERGENCY LIGHTING SYSTEMS.
KEYED NOTE.
GROUNDING BUS BAR.
MAIN CONDUCTOR, #1/0 ALUMINUM.
DOWN CONDUCTOR.
GROUNDING RING CONDUCTOR, #1/0 AWG COPPER.
GROUND ROD, 3/4" DIA X 10' COPPER-CLAD STEEL. "TW" INDICATES TEST WELL.
LC LIGHTING CONTROL PANEL.
BM
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
IC
T, R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/3 2"
'-0
2/ 7/
4:
:3
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
E-001
IN
TE
RI
O
R
EL
E C
TR
I C
AL
L
EG
EN
D
Av er y, P
E
Br ow n, A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
AA A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A B C D E H
GF
1 2
TW
R E:
/E
G
RE: 1/EG103
RE: 1/EG102 RE: 1/EG104
R
E:
/E G
RE: 1/EG101
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG101
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
A Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA A
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
PLAN
NORTH
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
AA A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A B C D E
GF
2TW
RE: 1/EG103
RE: 1/EG102 RE: 1/EG104
RE: 1/EG101
R E:
/E
G
R E:
/E
G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG102
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
B Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA B
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
GF
H J K L M O P
NG
Q
F
L.2 M.8 O.9
2 TW
R E:
/E
G
RE: 1/EG103
RE: 1/EG104
R E:
/E
G
RE: 1/EG105
RE: 1/EG104 RE: 1/EG106
RE: 1/EG103
RE: 1/EG109
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG103
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
C Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA C
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
H J K L M O P
NG
Q
F
L.2 M.8 O.9
RE: 1/EG103
RE: 1/EG102 RE: 1/EG104
RE: 1/EG101
R E:
/E
G
R E:
/E
G
RE: 1/EG105
RE: 1/EG104 RE: 1/EG106
RE: 1/EG103
R E:
/E
G
R E:
/E
G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG104
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
D Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA D
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
P
Q R S T U V W
X Y Z
O.9
2TW
RE: 1/EG105
RE: 1/EG106
RE: 1/EG107
RE: 1/EG106 RE: 1/EG108
RE: 1/EG105
R E:
/E
G
R
E:
/E G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG105
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
E Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA E
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
P
Q R S T U V W
X Y Z
O.9
RE: 1/EG105
RE: 1/EG106 RE: 1/EG106
RE: 1/EG105
R
E:
/E G
R E:
/E
G
R E:
/E
G
R E:
/E
G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG106
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
F Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA F
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Y AAZ BB CC DD EE FF GG HH
TW
RE: 1/EG107
RE: 1/EG108
R E:
/E
G
R
E:
/E G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG107
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
G Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA G
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A A A A A A A A A A A A A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Y AAZ BB CC DD EE FF GG HH
TW
RE: 1/EG107
RE: 1/EG108
R E:
/E
G
R E:
/E
G
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG108
L I G
HT
NI
NG
P
RO
T E
CT
IO
N
PL
A N
A R
EA
H Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA H
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
AA A A A A A A A
A AA A
A
AAAA
A A
GF
G F
L M O P
N
Q
L.2 M.8 O.9
0.1
0.2
TW
RE: 1/EG109
RE: 1/EG103
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
/1 6"
'-0
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG109
LI
G
HT
NI
N G P
R O
TE
C T
IO
N
- A
RE
A
I Av er y, P E
Br ow n, P E
1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA I
08 16 3241216
SCALE: 1/16"=1'-0"
KEYPLAN
A
B
C
D
E
F
G
H
I
GENERAL NOTES:
1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS
MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS
AND DOWN CONDUCTORS SHALL NOT BE REDUCED.
2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT
WITH EACH OTHER.
3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY
OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.
KEYED NOTES:
1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN
WALL. SEE DETAIL 1/EG501 AND 2/EG501.
2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS
THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.
1" PVC CONDUIT
NOTE: SEAL ALL PENETRATIONS AND FLASHINGS
THRU-WALL CABLE
CONNECTOR
#1/0 COPPER CABLE
#1/0 COPPER
CABLE
RUN TO GROUND
ALUMINUM CABLE
#1/0 COPPER
CABLE
2'-0" BELOW
FINISHED GRADE
3'-0" Min.
1" PVC CONDUIT
EXOTHERMIC WELD
COPPER CABLE
1" PVC CONDUIT
GROUND ROD
COPPER CABLE RUN
TO
ROOF CIRCUIT
EXOTHERMIC
WELD
EXOTHERMIC
WELD
A SHORT PIECE OF
REBAR WELDED TO
BUILDING REBAR &
BENT
TO EXTEND OUT OF
FINISHED FOUNDATION
FOR BONDING.
ALUMINUM CABLE
CABLE HOLDER
36" O.C. MAXIMUM
SPACING
AIR TERMINAL
#1/0 COPPER
CABLE
2'-0" BELOW
FINISHED GRADE
3'-0" Min.
EXOTHERMIC WELD
COPPER CABLE
1" PVC CONDUIT
EXOTHERMIC
WELD
GROUND
LOOP CABLE
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H N
O T
TO
SC
AL
E
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG501
G
RO
UN
D I
NG
D
ET
AI
L S
Av er y, P
E
Br ow n, P
E
NOT TO SCALE1 THRU-WALL AND CONCEALED DOWNLEAD TO GROUND
NOT TO SCALE2 CONCEALED DOWNLEAD AND GROUND
NOT TO SCALE3 AIR TERMINAL MOUNTING - SIDE MOUNT PARAPET
NOT TO SCALE4 COLUMN BONDING
ROOF CONDUCTOR
FASTENER CLAMP
CONDUCTOR
BOND CLAMP CONDUCTOR
BOND CLAMP
BOND LUG
CONDUCTOR
CONDUCTOR
BOND LUG
BOND PLATE
CONDUCTOR
TO THE GROUNDING ELECTRODE
PVC CONDUIT, EXTENDED AT LEAST 24" BELOW GRADE
CONCRETE
PVC CONDUIT, STUBBED UP 2" AFF,
SIZED PER NEC DUE TO CONDUCTOR SIZE
GROUNDING CONDUCTOR, SIZED PER
REQUIREMENTS ELSEWHERE
CONDUCTOR CONDUCTOR
BOND STRAP
BOND STRAP
NO. C422 OR C424
CLAMP FOR UTILITY
BOND
COPPER CABLE CONNECT TO NEAREST GROUND
OR GROUNDING RING CABLE WITH THERMOWELD
AA
GROUND CLAMP
GRAVEL OR CRUSHED STONE
SECTION A-A
MATERIAL LIST
3 6
TOP VIEW (COVER REMOVED)
COVER FOR BOX, ENGRAVED
"TEST WELL"
TEST WELL
GROUND ROD, 3/4"x10'
COPPER-CLAD STEEL
GROUNDING CONDUCTOR
POLYMER CONCRETE FIBERGLASS
REINFORCED BOX
6" 4"
14"
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG502
G
RO
UN
D I
NG
D
ET
AI
L S
Av er y, P
E
Br ow n, P
E
NOT TO SCALE1 TYPICAL BONDING FASTENING DETAIL
NOT TO SCALE2 TYPICAL BONDING PLATE DETAIL
NOT TO SCALE4 GROUND CONDUCTOR PENETRATING SLAB DETAIL
NOT TO SCALE3 TYPICAL BONDING STRAP DETAIL
NOT TO SCALE5 TYPICAL UNDERGROUND METAL PIPE BOND DETAIL
NOT TO SCALE6 GROUND ROD TEST WELL
TO OSP CONDUITS
TO RACKS
TO TRAY
TMGB/TGB SIZE
4"H x .25" THICK x 24"L.
PROVIDE TWO HOLE BOLTED
CONNECTORS WITH GROUND
RATED BELLEVILLE WASHERS
BETWEEN BUS AND CONNECTOR.
PROVIDE CONDUCTIVE GREASE
BETWEEN BUS AND CONNECTIONS.
PROVIDE FULL WRAP STRAP
CONNECTORS. CLAMPING OF THE
STRAPS SHALL BE WITH FULL
SURFACE CLAMPING TOOL TO
INSURE EVEN COMPRESSION
AROUND THE CABLE.
TO TMGB/TGB
TO PROTECTOR MODULE
TO LIGHTNING PROTECTION GROUND LOOP
TO NEAREST STRUCTURE STEEL COLUMN
SIZE
4"H x .25" THICK x 36"L.
PROVIDE TWO HOLE BOLTED
CONNECTORS WITH GROUND
RATED BELLEVILLE WASHERS
BETWEEN BUS AND CONNECTOR.
PROVIDE CONDUCTIVE GREASE
BETWEEN BUS AND CONNECTIONS.
PROVIDE FULL WRAP STRAP
CONNECTORS. CLAMPING OF THE STRAPS
SHALL BE WITH FULL SURFACE CLAMPING
TOOL TO INSURE EVEN COMPRESSION
AROUND THE CABLE.
TO OTHER INTERIOR METALLIC PIPE
TO THE TRANSFORMER
TO MAIN ELECTRICAL SERVICE GROUND
TO TMGB
SEE SHEET EG601 FOR SIZING OF GROUNDING CONDUCTORS.
GROUNDING LUG
GROUND WIRE
GROUNDING
BUSHING
INCOMING
CONDUIT LOCKNUT
GROUNDING LUG
PANEL
CABINET
CONDUIT
GROUNDING
BUSHING
CONDUIT
LOCKNUTS GREEN OR BARE
GROUNDING WIRE
SPLIT BOLT
CONNECTION
(TYPICAL)
GROUNDING BUS
BONDED TO CABINET
NOTES:
1. ALL WIRES TO BE NEATLY LACED.
2. AT THE POINT OF ATTACHMENT OF THE GROUNDING LUG TO THE CABINET, THE
SURFACES SHALL BE SCRAPED FREE OF PAINT AND THOROUGHLY CLEANED TO
INSURE PROPER BONDING.
3. NEUTRAL CONDUCTOR NOT SHOWN FOR CLARITY.
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG503
G
RO
UN
D I
NG
D
ET
AI
L S
Av er y, P
E
Br ow n, P
E
NOT TO SCALE2 TELECOMMUNICATIONS MAIN GROUNDING BUSBAR - (TMGB/TGB)
NOT TO SCALE3 ELECTRICAL MAIN GROUNDING BUSBAR (EMGB)
NOT TO SCALE4 TYPICAL PANEL GROUNDING DETAIL
1 FOR SIZE SEE POWER RISER DIAGRAM ON SHEET EP601.
2 2
3 #4/0 CU. BOND TO INCOMING CABLE & CONDUIT
4 FOR METALLIC CONDUIT RUNS GREATER THAN
3 FT CONDUCTOR SHALL BE BONDED TO EACH
END OF CONDUIT RUN.
KEYED NOTES:
TYPICAL BRANCH CIRCUIT. FOR SIZES SEE PLANS.
#3 /0
C U
IN
/4 "C
LEGEND
1 KEYED NOTE REFERENCE.
ELECTRICAL EQUIPMENT GROUND
BJ BONDING JUMPER
TMGB
TGB
TELEPHONE MAIN GROUNDING BUSBAR.
TELEPHONE GROUNDING BUSBAR.
DESCRIPTIONSYMBOL
TYPICAL 208/120V PANEL
TYPICAL 480/277V PANEL
MSB
G N N
N G
G
NEAREST STRUCTURAL
STEEL COLUMN
TRANSFORMER GROUND RING
LIGHTNING
ARRESTOR
CONDUIT
GROUNDING
BUSHING
PROTECTOR
BLOCKS
#6 CUTMGB
CABLE
TRAY
#6 C
U
IN
/2
"C
#6 CU
TELECOM
RM 113
#6 C
U
EQUIPMENT
RACKS
SERVICE
ENTRANCE
CONDUCTORS
PROTECTOR
BLOCKS
#6 CUTGB
CABLE
TRAY
#6 CU
REMOTE
TELECOM
(TYP.)
#6 C
U
EQUIPMENT
RACKS
1. FOR METALLIC CONDUIT RUNS GREATER THAN
3 FT CONDUCTOR SHALL BE BONDED TO EACH
END OF CONDUIT RUN.
2. REFER TO NEC 250.50 FOR FURTHER ELECTRODE SYSTEM
REQUIREMENTS.
#3 /0
C U
IN
/4 "C
EMGB IN
RM 112
#3 /0
C U
IN
/4 "C
BUILDING GROUND COUNTERPOISE CONDUCTOR #4/0 BARE COPPER
#3 /0
C U
IN
/4 "C
FIRE ALARM
ANTENNA
#3/0 CU IN 3/4"C
UNDERGROUND
METALLIC
WATER PIPE
#3 /0
C U
EMGB ELECTRICAL MAIN GROUNDING BUSBAR.
EGB ELECTRICAL GROUNDING BUSBAR.
BUILDING REBAR
#3 /0
C U
#3 /0
C U
INTERIOR METALLIC PIPE
#3/0 CU IN 3/4"C
LIGHTNING PROTECTION ROOF CONDUCTOR (TYPICAL)
TY
PI
C
AL
2/
C
U . D
O W
N C
O N
D U
C
TO
R
TYPICAL AIR TERMINAL
TYPICAL GROUND ROD
SPD
BJ
NEUTRAL
480V 208Y/120V
TYPICAL DRY-TYPE
TRANSFORMER
#6 CU#6 CU
BJ
3/0 CU
GENERAL NOTES:
#3 /0
C U
IN
/4 "C
#6 CU
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H N
O T
TO
SC
AL
E
2/ 7/
4:
:0
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EG601
G
RO
U N
DI
NG
R
IS
E R
D
IA
G
RA
M Av er y, P E
Br ow n, NOTES:
1. EACH LIGHT FIXTURE SHALL HAS INTEGRAL OCCUPANCY SENSOR AND AUTOMATICALLY TURNS ON TO FULL BRIGHTNESS UPON DETECTION OF OCCUPANT APPROACHING. LIGHTING CIRCUITS SHALL BE
CONNECT THRU LIGHTING CONTROL PANEL WITH MANUAL SWITCH OVERRIDE-OFF. SEE DETAILS
SHEET EL503 THRU EL506
2. EXTERIOR LIGHTING SHALL BE CONTROLLED BY PHOTOCELL AND AN ASTRONOMICAL CLOCK TIMER.
SEE DETAILS SHEET EL503 THRU EL506
BUILDING LIGHTING CONTROL MATRIX
ROOM NAME ROOM NUMBER D
U
AL
L
EV
EL
S W
IT
C
H
IN
G
O C
C U
PA
N
C Y
SE
N
SO
R
W
IT
H D
IM
M
ER
C
O N
TR
O
L
O C
C U
PA
N
C Y
SE
N
SO
R
D U
AL
T
EC
H
O C
C U
PA
N
C Y
SE
N
SO
R
VA
C
AN
C
Y
SE
N
SO
R
M
AN
U
AL
S W
IT
C
H (O
N /O
FF
KE
Y
SW
IT
C H
O
VE
R R
ID
E
O
FF
M
AN
U
AL
S W
IT
C
H O
VE
R
R
ID
E O
FF
EX
TE
R
IO
R B
U
IL
D
IN
G P
H O
TO
C
EL
L(
N O
N -D
IM
M
IN
G
D
AY
LI
G
H
TI
N G
NOTES
BATTERY CHARGER 108 X X
BREAKROOM 116 X X
ELEC. ROOM 112 X
JAN 120 X
STORAGE ROOM 118 X
LOCKER RM 119A X X
LOCKER RM 121A X X
MECHANICAL ROOM 109 X
MEN 121 X X
OFFICE 110 X
OFFICE 111 X
OFFICE 114 X X
TEL. ROOM 113 X
UTILITIES 104 X
UTILITIES 105 X
UTILITIES 121 X
UTILITIES 122 X
VESTIBULE 115 X X
WAREHOUSE 100 X 1
WAREHOUSE 101 X 1
WAREHOUSE 102 X 1
WAREHOUSE 103 X 1
WOMEN 119 X X
EXTERIOR LIGHTING N/A X 2
X
X
X
X
LIGHTING FIXTURE SCHEDULE
FIXTURE LAMP MOUNTING
DETAILTYPE DESCRIPTION FINISH VOLTAGE WATTAGE TYPE
TOTAL
LUMENS
PER FIXTURE TYPE HEIGHT
A2 2x2 RECESSED INDIRECT LED WHITE 277 36 LED 3300 RECESSED N/A 1/EL501
C2 2x2 SURFACE INDIRECT LED WHITE 277 36 LED 3300 SURFACE N/A 2/EL501
C5 SURFACE 4‐FT STRIP LED WITH DEFFUSE LENS WHITE 277 74 LED 4600 SURFACE N/A 4/EL501
D 8" ROUND LED DOWNLIGHT WHITE 277 36 LED 1500 RECESSED N/A 5/EL501
H1 SUSPENDED HIGH BAY INDIRECT LED WHITE 277 281 LED 24850 SUSPENDED 29‐FT AFF, UNO 3/EL502
P5 SUSPENDED 4‐FT STRIP LED WITH DEFFUSE LENS WHITE 277 74 LED 4600 SUSPENDED 9‐FT AFF, UNO
W2 LINEAR 2‐FT LED FIXTURE WITH DIFFUSE LED WHITE 277 17 LED 1850 WALL MOUNTED 7'‐6" AFF, UNO 1/EL502
W4 LINEAR 4‐FT LED FIXTURE WITH DIFFUSE LED WHITE 277 34 LED 3700 WALL MOUNTED 7'‐6" AFF, UNO 2/EL502
X1 LED EXIT LIGHT WHITE 277 4 LED ‐ BACK MOUNTED 8'‐6" AFF 5/EL502
X2 LED EXIT LIGHT WHITE 277 4 LED ‐ PENDANT MOUNTED 15'‐0" AFF 5/EL502
T1
Y1
Y2
WALL PACK
WALL PACK
BRONZE
BRONZE
LED
LED
WALL
WALL
7'‐6" AFF
20'‐0" AFF
4/EL502
4/EL502
6/EL501
3/EL501LED FROSTED GLASS DIFFUSERS YELLOW 120 15 LED WALL‐ 6'‐0" AFF
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
2"
'-0
2/ 7/
4:
:4
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL001
LI
G
HT
IN
G F
IX
TU
RE
S
CH
E D
UL
E
L I
G
HT
IN
G
C O
NT
R O
L M
AT
RI
X
Av er y, P
E
Br ow n, P
E
GENERAL NOTES:
1. AUTOMATIC CONTROL SHALL BE PROGRAMED TO BE OFF WITHIN 15 MINUTES AFTER
OCCUPANT LEAVES SPACE.
A B C D E
GF
WAREHOUSE
H1
ELA-9
H1
HA-10
H1
HA-10
H1
ELA-9
H1
HA-10
H1
ELA-9
H1
HA-9
H1
HA-9
H1
ELA-9
H1
HA-9
H1
ELA-9
H1
HA-9
H1
HA-9
H1
ELA-9
H1
HA-9
H1
ELA-2
H1
HA-8
H1
HA-8
H1
ELA-5
H1
HA-8
H1
ELA-2
H1
HA-8
H1
HA-8
H1
ELA-5
H1
HA-8
H1
ELA-2
H1
HA-7
H1
HA-7
H1
ELA-5
H1
HA-7
H1
ELA-2
H1
HA-7
H1
HA-7
H1
ELA-5
H1
HA-7
H1
ELA-2
H1
HA-6
H1
HA-6
H1
ELA-5
H1
HA-6
H1
ELA-2
H1
HA-6
H1
HA-6
H1
ELA-5
H1
HA-6
H1
ELA-7
H1
HA-5
H1
HA-5
H1
ELA-8
H1
HA-5
H1
ELA-7
H1
HA-5
H1
HA-5
H1
ELA-8
H1
HA-5
H1
ELA-7
H1
HA-4
H1
HA-4
H1
ELA-8
H1
HA-4
H1
ELA-7
H1
HA-4
H1
HA-4
H1
ELA-8
H1
HA-4
H1
ELA-7
H1
HA-3
H1
HA-3
H1
ELA-8
H1
HA-3
H1
ELA-7
H1
HA-3
H1
HA-3
H1
ELA-8
H1
HA-3
H1
HA-1
H1
HA-1
H1
ELA-4
H1
HA-1
H1
HA-1
H1
HA-1
H1
HA-1
H1
HA-2
H1
ELA-4
H1
HA-2
H1
HA-2
H1
HA-2
H1
HA-2
H1
ELA-4
H1
HA-2
EL101
X1
HA-1
X1
HA-2
X1
HI1-3
X2
HA-1
X2
HA-2
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18
Y1
ELI-16,18 R
E:
/E L1
R
E:
/E L1
T1T1T12 2 2
X1
HA-2
X1
HI1-3
Y2
HI1-30,32
UTILITIES
ELEC. ROOM
TEL. ROOM
P5
ELA-4
P5
ELA-4
C5
ELA-4
C5
HA-2
LC
LCP-A
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL101
LI
G
H T
IN
G P
LA
N
- A
RE
A A
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA A
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOMS 104, 105 AND 107
04 8 16268
SCALE: 1/8"=1'-0"
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
PLAN
NORTH
PLAN NORTH
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
CONDUIT.
2. CONNECT TO 120V CIRCUIT NEARBY. SEE POWER PLAN FOR CIRCUIT INFORMATION.
DN
A B C D E
GF
WAREHOUSE
H1
HB-10
H1
ELA-1
H1
HB-10
H1
HB-10
H1
ELA-9
H1
HB-9
H1
ELA-1
H1
HB-9
H1
HB-9
H1
ELA-9
H1
HB-9
H1
ELA-1
H1
HB-9
H1
HB-9
H1
ELA-9
H1
HB-8
H1
ELA-6
H1
HB-8
H1
HB-8
H1
ELA-2
H1
HB-8
H1
ELA-6
H1
HB-8
H1
HB-8
H1
ELA-2
H1
HB-7
H1
ELA-6
H1
HB-7
H1
HB-7
H1
ELA-2
H1
HB-7
H1
ELA-6
H1
HB-7
H1
HB-7
H1
ELA-2
H1
HB-6
H1
ELA-6
H1
HB-6
H1
HB-6
H1
ELA-2
H1
HB-6
H1
ELA-6
H1
HB-6
H1
HB-6
H1
ELA-2
H1
HB-5
H1
ELA-10
H1
HB-5
H1
HB-5
H1
ELA-7
H1
HB-5
H1
ELA-10
H1
HB-5
H1
HB-5
H1
ELA-7
H1
HB-4
H1
ELA-10
H1
HB-4
H1
HB-4
H1
ELA-7
H1
HB-4
H1
ELA-10
H1
HB-4
H1
HB-4
H1
ELA-7
H1
HB-3
H1
ELA-10
H1
HB-3
H1
HB-3
H1
ELA-7
H1
HB-3
H1
ELA-10
H1
HB-3
H1
HB-3
H1
ELA-7
H1
HD-7
H1
ELI-13
H1
HD-7
H1
HD-7
H1
ELI-9
H1
HB-1
H1
ELA-3
H1
HB-1
H1
HB-1
H1
HB-1
H1
HB-1
H1
ELA-3
H1
HB-1
H1
HB-2
H1
HB-2
H1
HB-2
H1
HB-2
H1
HB-2
H1
ELA-3
H1
HB-2
H1
HD-2
EL102
X1
HD-2
X1
HB-2
X1
HB-1
X2
HB-1 X2
HB-2
T1 T1
Y1
ELI-16,18
Y1
ELI-16,18
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18
RE: 1/EL103
RE: 1/EL104
R E:
/E
L1
R E:
/E
L1
T1
2 2
X1
HB-2
Y2
HI1-30,32
Y2
HI1-30,32
TELECOM
ROOM
ELEC. ROOM
C5
ELA-3
C5
HB-2
P5
ELA-3
LC
LCP-B
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:5
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL102
LI
G
H T
IN
G P
LA
N
- A
RE
A B
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA B
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOMS 127 AND 128
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
H J K L M O P
NG
Q
F
L.2 M.8 O.9
WAREHOUSE
H1
ELA-7
H1
HA-3
H1
HA-3
H1
ELA-8
H1
HA-3
H1
ELI-9
H1
HI1-14
H1
HI1-14
H1
ELI-5
H1
HI1-14
H1
ELI-9
H1
HI1-13
H1
HI1-13
H1
ELI-5
H1
HI1-13
H1
ELI-9
H1
HI1-13
H1
HI1-13
H1
ELI-5
H1
HI1-13
H1
ELI-9
H1
HI1-15
H1
HI1-15
H1
ELI-5
H1
HI1-15
H1
ELI-9
H1
HI1-14
H1
HI1-14
H1
ELI-5
H1
HI1-14
H1
ELI-8
H1
HI1-12
H1
HI1-12
H1
ELI-4
H1
HI1-12
H1
ELI-8
H1
HI1-12
H1
HI1-12
H1
ELI-4
H1
HI1-12
H1
ELI-8
H1
HI1-11
H1
HI1-11
H1
ELI-4
H1
HI1-11
H1
ELI-8
H1
HI1-11
H1
HI1-11
H1
ELI-4
H1
HI1-11
H1
ELI-8
H1
HI1-10
H1
HI1-10
H1
ELI-4
H1
HI1-10
H1
ELI-8
H1
HI1-10
H1
HI1-10
H1
ELI-4
H1
HI1-10
H1
ELI-7
H1
HI1-9
H1
HI1-9
H1
ELI-3
H1
HI1-9
H1
ELI-7
H1
HI1-9
H1
HI1-9
H1
ELI-3
H1
HI1-9
H1
ELI-7
H1
HI1-8
H1
HI1-8
H1
ELI-3
H1
HI1-8
H1
ELI-7
H1
HI1-8
H1
HI1-8
H1
ELI-3
H1
HI1-8
H1
ELI-7
H1
HI1-7
H1
HI1-7
H1
ELI-3
H1
HI1-7
H1
ELI-7
H1
HI1-7
H1
HI1-7
H1
ELI-3
H1
HI1-7
H1
ELI-6
H1
HI1-6
H1
HI1-6
H1
ELI-2
H1
HI1-6
H1
ELI-6
H1
HI1-6
H1
HI1-6
H1
ELI-2
H1
HI1-6
H1
ELI-6
H1
HI1-5
H1
HI1-5
H1
ELI-2
H1
HI1-5
H1
ELI-6
H1
HI1-5
H1
HI1-5
H1
ELI-2
H1
HI1-5
H1
ELI-6
H1
HI1-4
H1
HI1-4
H1
ELI-2
H1
HI1-4
H1
ELI-6
H1
HI1-4
H1
HI1-4
H1
ELI-2
H1
HI1-4
H1
HA-2
H1
HI1-3
H1
HI1-3
H1
HI1-3
H1
HI1-3
H1
ELI-1
H1
HI1-3
H1
ELI-1
H1
HI1-3
H1
HI1-2
H1
HI1-2
H1
HI1-2
H1
HI1-2
H1
ELI-1
H1
HI1-2
H1
HI1-2
H1
HI1-1
H1
HI1-1
H1
HI1-1
H1
ELI-1
H1
HI1-1
H1
HI1-1
H1
ELI-1
H1
HI1-1
EL103
X1
HA-2
X1
HI1-3
X2
HI1-3
X2
HI1-1
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18R
E:
/E L1
RE: 1/EL103
RE: 1/EL104
R E:
/E
L1
RE: 1/EL105
RE: 1/EL104 RE: 1/EL106
RE: 1/EL103
RE: 1/EL109
RE: 1/EL103
T1T1 2 2
X1
HA-2
X1
HI1-3
Y2
HI1-30,32
UTILITIES
P5
ELI-1
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:0
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL103
LI
G
H T
IN
G P
LA
N
- A
RE
A C
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA C
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOM 106
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
H J K L M O P
NG
Q
F
L.2 M.8 O.9
WAREHOUSE
H1
HB-3
H1
ELA-10
H1
HB-3
H1
HB-3
H1
ELA-7
H1
HD-8
H1
ELI-13
H1
HD-8
H1
HD-8
H1
ELI-9
H1
HD-10
H1
ELI-13
H1
HD-10
H1
HD-10
H1
ELI-9
H1
HD-10
H1
ELI-13
H1
HD-10
H1
HD-10
H1
ELI-9
H1
HD-7
H1
ELI-13
H1
HD-7
H1
HD-7
H1
ELI-9
H1
HD-8
H1
ELI-13
H1
HD-8
H1
HD-8
H1
ELI-9
H1
HD-12
H1
ELI-12
H1
HD-12
H1
HD-12
H1
ELI-8
H1
HD-12
H1
ELI-12
H1
HD-12
H1
HD-12
H1
ELI-8
H1
HD-17
H1
ELI-12
H1
HD-17
H1
HD-17
H1
ELI-8
H1
HD-17
H1
ELI-12
H1
HD-17
H1
HD-17
H1
ELI-8
H1
HD-15
H1
ELI-12
H1
HD-15
H1
HD-15
H1
ELI-8
H1
HD-15
H1
ELI-12
H1
HD-15
H1
HD-15
H1
ELI-8
H1
HD-13
H1
ELI-11
H1
HD-13
H1
HD-13
H1
ELI-7
H1
HD-13
H1
ELI-11
H1
HD-13
H1
HD-13
H1
ELI-7
H1
HD-9
H1
ELI-11
H1
HD-9
H1
HD-9
H1
ELI-7
H1
HD-9
H1
ELI-11
H1
HD-9
H1
H1
ELI-7
H1
HD-16
H1
ELI-11
H1
HD-16
H1
HD-16
H1
ELI-7
H1
HD-16
H1
ELI-11
H1
HD-16
H1
HD-16
H1
ELI-7
H1
HD-14
H1
ELI-10
H1
HD-14
H1
HD-14
H1
ELI-6
H1
HD-14
H1
ELI-10
H1
HD-14
H1
HD-14
H1
ELI-6
H1
HD-6
H1
ELI-10
H1
HD-6
H1
HD-6
H1
ELI-6
H1
HD-6
H1
ELI-10
H1
HD-6
H1
HD-6
H1
ELI-6
H1
HD-11
H1
ELI-10
H1
HD-11
H1
HD-11
H1
ELI-6
H1
HD-11
H1
ELI-10
H1
HD-11
H1
HD-11
H1
ELI-6
H1
HB-2
H1
HD-2
H1
HD-2
H1
HD-2
H1
HD-2
H1
ELI-14
H1
HD-2
H1
ELI-14
H1
HD-2
H1
HD-18
H1
HD-18
H1
HD-18
H1
HD-18
H1
ELI-14
H1
HD-18
H1
HD-18
H1
HD-4
H1
HD-4
H1
HD-4
H1
ELI-14
H1
HD-4
H1
HD-4
H1
ELI-14
H1
HD-4
EL104
X1
HD-4X1
HD-2
X1
HB-2
X2
HD-2
X2
HD-4
T1 T1 T1
Y1
ELI-16,18
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18
RE: 1/EL103
R
E:
/E L1
R E:
/E
L1
RE: 1/EL103
R E:
/E
L1
R E:
/E
L1
2 2 2
X1
HB-2
X1
HD-4
Y2
HI1-30,32
ELEC. ROOM
TELECOM
ROOM
C5
ELI-14
C5
HD-4
P5
ELI-14
LC
LCP-D
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:0
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL104
LI
G
H T
IN
G P
LA
N
- A
RE
A D
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA D
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOMS 131 AND 133
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
Q R S T U V W
X Y Z
O.9
WAREHOUSE
H1
ELE-9
H1
HE-15
H1
HE-15
H1
ELE-5
H1
HE-15
H1
ELE-9
H1
HE-14
H1
HE-14
H1
ELE-5
H1
HE-14
H1
ELE-9
H1
HE-14
H1
HE-14
H1
ELE-5
H1
HE-14
H1
ELE-9
H1
HE-13
H1
HE-13
H1
ELE-5
H1
HE-13
H1
ELE-9
H1
HE-13
H1
HE-13
H1
ELE-5
H1
HE-13
H1
ELE-8
H1
HE-12
H1
HE-12
H1
ELE-4
H1
HE-12
H1
ELE-8
H1
HE-12
H1
HE-12
H1
ELE-4
H1
HE-12
H1
ELE-8
H1
HE-11
H1
HE-11
H1
ELE-4
H1
HE-11
H1
ELE-8
H1
HE-11
H1
HE-11
H1
ELE-4
H1
HE-11
H1
ELE-8
H1
HE-10
H1
HE-10
H1
ELE-4
H1
HE-10
H1
ELE-8
H1
HE-10
H1
HE-10
H1
ELE-4
H1
HE-10
H1
ELE-7
H1
HE-9
H1
HE-9
H1
ELE-3
H1
HE-9
H1
ELE-7
H1
HE-9
H1
HE-9
H1
ELE-3
H1
HE-9
H1
ELE-7
H1
HE-8
H1
HE-8
H1
ELE-3
H1
HE-8
H1
ELE-7
H1
HE-8
H1
HE-8
H1
ELE-3
H1
HE-8
H1
ELE-7
H1
HE-7
H1
HE-7
H1
ELE-3
H1
HE-7
H1
ELE-7
H1
HE-7
H1
HE-7
H1
ELE-3
H1
HE-7
H1
ELE-6
H1
HE-6
H1
HE-6
H1
ELE-2
H1
HE-6
H1
ELE-6
H1
HE-6
H1
HE-6
H1
ELE-2
H1
HE-6
H1
ELE-6
H1
HE-5
H1
HE-5
H1
ELE-2
H1
HE-5
H1
ELE-6
H1
HE-5
H1
HE-5
H1
ELE-2
H1
HE-5
H1
ELE-6
H1
HE-4
H1
HE-4
H1
ELE-2
H1
HE-4
H1
ELE-6
H1
HE-4
H1
HE-4
H1
ELE-2
H1
HE-4
H1
HE-3
H1
ELE-1
H1
HE-3
H1
HE-3
H1
HE-3
H1
HE-3
H1
ELE-1
H1
HE-3
H1
HE-2
H1
HE-2
H1
HE-2
H1
HE-2
H1
ELE-1
H1
HE-2
H1
HE-2
H1
HE-1
H1
HE-1
H1
HE-1
H1
ELE-1
H1
HE-1
H1
HE-1
H1
ELE-1
H1
HE-1
EL105
X1
HE-3
X1
HE-1
X2
HE-3 X2
HE-1
T1 T1 T1
Y1
ELI-16,18
Y1
ELI-16,18
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
RE: 1/EL104
RE: 1/EL103 RE: 1/EL107
RE: 1/EL108
R E:
/E
L1
R E:
/E
L1
2 2 2
X1
HE-1
X1
HG-3
X1
HE-1
Y2
HI1-30,32
TEL. ROOM
122A
ELEC. ROOM
UTILITIES
C5
ELE-1
C5
HE-1
P5
ELE-1
P5
ELE-1
LC
LCP-E
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:1
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL105
LI
G
H T
IN
G P
LA
N
- A
RE
A E
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA E
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED 122, 122A AND 123
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
Q R S T U V W
X Y Z
WAREHOUSE
H1
HF-1
H1
ELE-13
H1
HF-1
H1
HF-1
H1
ELE-9
H1
HF-7
H1
ELE-13
H1
HF-7
H1
HF-7
H1
ELE-9
H1
HF-7
H1
ELE-13
H1
HF-7
H1
HF-7
H1
ELE-9
H1
HF-15
H1
ELE-13
H1
HF-15
H1
HF-15
H1
ELE-9
H1
HF-15
H1
ELE-13
H1
HF-15
H1
HF-15
H1
ELE-9
H1
HF-12
H1
ELE-12
H1
HF-12
H1
HF-12
H1
ELE-8
H1
HF-12
H1
ELE-12
H1
HF-12
H1
HF-12
H1
ELE-8
H1
HF-11
H1
ELE-12
H1
HF-11
H1
HF-11
H1
ELE-8
H1
HF-11
H1
ELE-12
H1
HF-11
H1
HF-11
H1
ELE-8
H1
HF-16
H1
ELE-12
H1
HF-16
H1
HF-16
H1
ELE-8
H1
HF-16
H1
ELE-12
H1
HF-16
H1
HF-16
H1
ELE-8
H1
HF-13
H1
ELE-11
H1
HF-13
H1
HF-13
H1
ELE-7
H1
HF-13
H1
ELE-11
H1
HF-13
H1
HF-13
H1
ELE-7
H1
HF-17
H1
ELE-11
H1
HF-17
H1
HF-17
H1
ELE-7
H1
HF-17
H1
ELE-11
H1
HF-17
H1
HF-17
H1
ELE-7
H1
HF-18
H1
ELE-11
H1
HF-18
H1
HF-18
H1
ELE-7
H1
HF-18
H1
ELE-11
H1
HF-18
H1
HF-18
H1
ELE-7
H1
HF-14
H1
ELE-10
H1
HF-14
H1
HF-14
H1
ELE-6
H1
HF-14
H1
ELE-10
H1
HF-14
H1
HF-14
H1
ELE-6
H1
HF-9
H1
ELE-10
H1
HF-9
H1
HF-9
H1
ELE-6
H1
HF-9
H1
ELE-10
H1
HF-9
H1
HF-9
H1
ELE-6
H1
HF-10
H1
ELE-10
H1
HF-10
H1
HF-10
H1
ELE-6
H1
HF-10
H1
ELE-10
H1
HF-10
H1
HF-10
H1
ELE-6
H1
HH-15
H1
ELG-13
H1
HH-15
H1
HH-15
H1
ELG-9
H1
HF-3
H1
ELE-14
H1
HF-3
H1
HF-3
H1
HF-3
H1
HF-3
H1
ELE-14
H1
HF-3
H1
HF-8
H1
HF-8
H1
HF-8
H1
HF-8
H1
ELE-14
H1
HF-8
H1
HF-8
H1
HF-5
H1
HF-5
H1
HF-5
H1
ELE-14
H1
HF-5
H1
HF-5
H1
ELE-14
H1
HF-5
H1
HH-3
EL106
X1
HH-3
X1
HF-5X1
HF-3
X2
HF-3
X2
HF-5
T1 T1 T1
Y1
ELI-16,18
Y1
ELI-16,18
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18
RE: 1/EL105 RE: 1/EL107
RE: 1/EL108
RE: 1/EL105
R E:
/E
L1
R E:
/E
L1
R E:
/E
L1
R E:
/E
L1
2 2
X1
HD-4
X1
HF-5
Y2
HI1-30,32
TELECOM
ROOM
ELEC. ROOM
C5
ELE-14
C5
HF-5
P5
ELE-14
LC
LCP-F
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:2
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL106
LI
G
H T
IN
G P
LA
N
- A
RE
A F
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA F
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOMS 138 AND 139
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY
MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.
3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.
4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.
5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE
CIRCULATION AREA.
6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS
THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506
KEYED NOTES:
1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"
Y AAZ BB CC DD EE FF GG HH
WAREHOUSE
H1
ELG-9
H1
HG-14
H1
HG-14
H1
ELG-5
H1
HG-14
H1
ELG-9
H1
HG-13
H1
HG-13
H1
ELG-5
H1
HG-13
H1
ELG-9
H1
HG-13
H1
HG-13
H1
ELG-5
H1
HG-13
H1
ELG-9
H1
HG-15
H1
HG-15
H1
ELG-5
H1
HG-15
H1
ELG-9
H1
HG-14
H1
HG-14
H1
ELG-5
H1
HG-14
H1
ELG-8
H1
HG-12
H1
HG-12
H1
ELG-4
H1
HG-12
H1
ELG-8
H1
HG-12
H1
HG-12
H1
ELG-4
H1
HG-12
H1
ELG-8
H1
HG-11
H1
HG-11
H1
ELG-4
H1
HG-11
H1
ELG-8
H1
HG-11
H1
HG-11
H1
ELG-4
H1
HG-11
H1
ELG-8
H1
HG-10
H1
HG-10
H1
ELG-4
H1
HG-10
H1
ELG-8
H1
HG-10
H1
HG-10
H1
ELG-4
H1
HG-10
H1
ELG-7
H1
HG-9
H1
HG-9
H1
ELG-3
H1
HG-9
H1
ELG-7
H1
HG-9
H1
HG-9
H1
ELG-3
H1
HG-9
H1
ELG-7
H1
HG-8
H1
HG-8
H1
ELG-3
H1
HG-8
H1
ELG-7
H1
HG-8
H1
HG-8
H1
ELG-3
H1
HG-8
H1
ELG-7
H1
HG-7
H1
HG-7
H1
ELG-3
H1
HG-7
H1
ELG-7
H1
HG-7
H1
HG-7
H1
ELG-3
H1
HG-7
H1
ELG-6
H1
HG-6
H1
HG-6
H1
ELG-2
H1
HG-6
H1
ELG-6
H1
HG-6
H1
HG-6
H1
ELG-2
H1
HG-6
H1
ELG-6
H1
HG-5
H1
HG-5
H1
ELG-2
H1
HG-5
H1
ELG-6
H1
HG-5
H1
HG-5
H1
ELG-2
H1
HG-5
H1
ELG-6
H1
HG-4
H1
HG-4
H1
ELG-2
H1
HG-4
H1
ELG-6
H1
HG-4
H1
HG-4
H1
ELG-2
H1
HG-4
H1
HG-3
H1
HG-3
H1
HG-3
H1
HG-3
H1
ELG-1
H1
HG-3
H1
ELG-1
H1
HG-3
H1
HG-2
H1
HG-2
H1
HG-2
H1
HG-2
H1
ELG-1
H1
HG-2
H1
HG-2
H1
HG-1
H1
HG-1
H1
HG-1
H1
ELG-1
H1
HG-1
H1
HG-1
H1
ELG-1
H1
HG-1
EL107
EL107
X1
HE-1
X1
HG-3
X1
HG-1X2
HG-3
X2
HG-1
T1 T1 T1
Y1
ELI-16,18 Y1
ELI-16,18
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y2
HI1-30,32
Y1
ELI-16,18
R E:
/E
L1
R E:
/E
L1
RE: 1/EL107
RE: 1/EL108
2 2 2 T12
X1
HE-1
X1
HG-3
X1
HE-1
Y2
HI1-30,32
Y2
HI1-30,32
UTILITIES
P5
ELG-1
C5
ELG-1
C5
HG-1
P5
ELG-1
135A
TEL. ROOM
LC
LCP-G
ELEC. ROOM
SHEET
SEQUENCE
NUMBER
1 2 3 4 5
D ra wn b y:
D es ig ne d by
Su bm itt ed b y:
Fi le
N am e:
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R D
IS
TR
R
PS
O
F
EN
G
IN
EE
R
S
FO
R T
W O
R
TH
, T
EX
AS
R ev ie we d by
US Army Corps of Engineers ®
D
C
B
A
Pl ot
S ca le
Pl ot
D at e:
R ev
Sy m bo l
D es cr ip tio n
Tr ac ki ng
N o.
Ac tio n D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H As in di ca te d
2/ 7/
4:
:2
PM
R E D
RI
VE
R A R
M Y
DE
PO
T, H
O O
KS
, T
EX
A S
FY
D L A
G
EN
ER
A L
P
UR
PO
SE
W
AR
EH
O
U S E
FE
BR
U
AR
Y
W
G
-1 9-
B-
Fort Worth District
K.
L
E, P
.E
T.
N
G U
YE
N
D
AR
EN
A
. B R
O W
N , P
.E
EL107
LI
G
H T
IN
G P
LA
N
- A
RE
A G
Av er y, P
E
Br ow n, P
E
1/16" = 1'-0"1 LIGHTING PLAN - AREA G
KEYPLAN
A
B
C
D
E
F
G
H
I
08 16 3241216
SCALE: 1/16"=1'-0"
1/8" = 1'-0"2 ENLARGED ROOM 124
1/8" = 1'-0"3 ENLARGED ROOMS 135 AND 135A
04 8 16268
SCALE: 1/8"=1'-0"
04 8 16268
SCALE: 1/8"=1'-0"
PLAN NORTH
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS
REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL
MATRIX ON SHEET EL001.
2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED
INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE
EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE…