Drawings_(Part_9_of_9).pdf

PDF 6 MB Posted

Attached to
FY19 RRAD General Purpose Warehouse Federal contract opportunity
Solicitation number
W9126G19B0007
Issued by
Department of the Army Corps of Engineers Engineering District Fort Worth

About this file

Drawings Part 9 of 9

View the file

Other files for this federal contract opportunity

Other files attached to FY19 RRAD General Purpose Warehouse, newest first.
File Type Posted
C1_SF_1409_Abstract_of_Offerors.pdf PDF
A7_Amendment_5.pdf PDF
A7_Amendment_4.pdf PDF
Amendment_3.pdf PDF
Site_Visit.pdf PDF
A7_Amendment_2.pdf PDF
A10_FF&E_Package_(GPW)_FINAL.pdf PDF
B3_Amendment_1.pdf PDF
FFE_Package_(GPW)_FINAL.pdf PDF
Drawings_(Part_8_of_9).pdf PDF
Drawings_(Part_3_of_9).pdf PDF
Drawings_(Part_7_of_9).pdf PDF
Drawings_(Part_1_of_9).pdf PDF
Drawings_(Part_2_of_9).pdf PDF
Drawings_(Part_4_of_9).pdf PDF
Drawings_(Part_5_of_9).pdf PDF
Drawings_(Part_6_of_9).pdf PDF
B3_W9126G19B0007_(Part_3_of_4).pdf PDF
B3_W9126G19B0007_(Part_4_of_4).pdf PDF
B3_W9126G19B0007_(Part_1_of_4).pdf PDF
B3_W9126G19B0007_(Part_2_of_4).pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R E

D

R

I V

A

M

Y

D

E P

O T

H

O O

K S

T

E X

A S

F Y

D

L

G

N

E R

P

U R

P O

S

W

R

E H

O U

S E

SHEET

SEQUENCE

NUMBER

W G

B

1 2 3 4 5

D r a w n b y

D e s i g n e d b y

S u b m i t t e d b y

F i l

N a m e

D a t e

C o n t r a c t

N o

S o l i c i t a t i o n

N o

U S

A

R M

Y

E

N G

I N

E E

R

D

I S

T R

I C

T

C O

R P

S

O

F

E

N G

I N

E E

R S

F O

T

W

O R

T H

T

E X

A S

R e v i e w d b y

FORT WORTH DISTRICT

US ARMY CORPS

OF ENGINEERS ®

D

C

B

A

P L

C A

L E

P L

D

T

E

R e v

S y m b o l

D e s c r i p t i o n

T r a c k i n g

N o

A c t i o n

D a t e

E N

G I N

E E

R I N

G

C O

N S

T R

U C

T I O

N

D

I V

I S

I O

N

E N

G I N

E E

R I N

G

B

R A

N C

H

D A

R E

N

B

R O

W N

P

E

C H

I E

F

E

L E

C T

R I C

C

T I O

N

F E

B R

U A

Y

ES506

L I F

T

S

T A

T I O

N

E L

E C

T R

I C

D

T

A I L

S

K

L

E

P

E

K

L

E

P

E

A v e r y

P

B r o w n

LIGHTING PLAN SYMBOLS

A, b

A, b

A, b

A, b

A, b

A, b

WALL MOUNTED LED LIGHT FIXTURE. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET

BOX.

LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY

BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

DOWNLIGHT LED FIXTURE. LETTERS SAME AS ABOVE.

BACK MOUNTED EXIT SIGN. CAPITAL LETTER DENOTES TYPE. SHADED AREA

INDICATES FACE SIDES. PROVIDE DIRECTIONAL ARROWS WHERE INDICATED.

MOUNT 7'-6" AFF UNO.

CONTROL SWITCH, WALL MOUNTED 44" AFF.

NO OPTION INDICATES MANUAL CONTROL SWITCH (ON/OFF).

SMALL LETTER DENOTES SWITCH ID OPERATES FIXTURE HAVING SAME LETTER.

"3" OR "4" DENOTES 3-WAY, 4-WAY SWITCH.

"S" DENOTES SENSE LIGHTING CONTROL

"K" DENOTES KEYED SWITCH

"D" DENOTES DIMMER SWITCH

WALL MOUNTED LED LIGHT FIXTURE. LETTERS SAME AS ABOVE.

DESCRIPTIONSYMBOL

GENERAL NOTES:

1. ALL MOTOR STARTERS SHALL BE PROVIDED WITH AN INDICATOR

LAMP. LAMP SHALL BE "ON" WHEN MOTOR IS RUNNING.

2. A GREEN 600V INSULATED GROUND WIRE SHALL BE PROVIDED IN

ALL CONDUITS.

3. EMERGENCY LIGHTING FIXTURES SHALL BE WIRED SO THAT THE

LIGHTS WILL TURN ON AND OFF WITH THE OCCUPANCY SENSORS

OR WALL SWITCH IF APPLICABLE. WHEN THE NORMAL POWER

SUPPLYING THE CIRCUIT HAS FAILED, THE FIXTURE WILL SWITCH

TO EMERGENCY BATTERY POWER. THEY SHALL NOT BE WIRED AS

NIGHT LIGHTS UNO.

4. AT ALL LOCATIONS WHERE ACCESS TO MECHANIC EQUIPMENT,

PIPING, AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE

CONDUIT SHALL BE MOUNTED ABOVE, OR SO THAT THERE WILL BE

SUFFICIENT ACCESS SPACE TO MAINTENANCE AND REPLACEMENT.

5. A DISCONNECT SWITCH CAPABLE OF BEING INDIVIDUALLY LOCKED

IN THE OPEN POSITION SHALL BE LOCATED WITHIN SIGHT OF THE

MOTOR DRIVEN EQUIPMENT AND/OR ASSOCIATED STARTER. THESE

DISCONNECTS SHALL BE IN ADDITION TO ALL OTHER DISCONNECTS

PROVIDED ON OR WITH MOTOR DRIVEN EQUIPMENT. THERE SHALL

NEVER BE A STARTER-DISCONNECT-MOTOR SITUATION.

6. UNO, MINIMUM SIZE FOR SAFETY SWITCH SHALL BE 30A, 3P, 4W,

NEMA 1, 240-V OR 600-V AS APPLIED.

7. PANEL AND CIRCUIT NUMBERS OF EQUIPMENT ARE PLACED NEXT

TO THE EQUIPMENT IN THE DRAWING.

8. UNO, MININUM CIRCUIT CONDUCTORS SHALL BE # 12 AWG IN 1/2" C.

A, b

A, b

LED LIGHT FIXTURE. CAPITAL LETTER DENOTES TYPE. SMALL LETTER DENOTES THE

SWITCH ID CONTROLLING THE FIXTURE IF THE SWITCH IS NOT PLACED IN THE SAME

ROOM OF THE FIXTURE. CIRCLE IS OUTLET BOX.

CEILING MOUNTED EXIT SIGN. CAPITAL LETTER DENOTES TYPE. SHADED AREA

INDICATES FACE SIDES. PROVIDE DIRECTIONAL ARROWS WHERE INDICATED.

A

DESCRIPTIONSYMBOL

AIR TERMINAL, 5/8" DIA x 24 " BLUNT OR ROUNDED ALUMINUM.

TW

b, S K D

POWER PLAN SYMBOLS

R

WP,

GF,

TV

"R" INDICATES RAINTIGHT, NEMA 3R.

SAFETY OR DISCONNECT SWITCH, UNFUSED UNO.

QUADRUPLEX RECEPTACLE, GROUNDED TYPE MOUNTED 18" AFF, UNO.

DESCRIPTIONSYMBOL

F,C DUPLEX RECEPTACLE. GROUNDED TYPE.

"C" INDICATES CEILING FLUSH-MOUNTED, UNO.

"F" INDICATES FLOOR FLUSH-MOUNTED, WITH HINGED COVER, UNO

J STANDARD J-BOX. WALL FLUSH-MOUNTED 18" AFF UNO.

TR

TELECOMMUNICATIONS SYMBOLS

W WALL MOUNTED OUTLET WITH ONE RJ-45 MODULAR JACK. MOUNTED 48" AFF UNO.

WIRELESS ACCESS POINT WITH (2) RJ-45 MODULAR JACKS FOR DATA. SUSPENDED

29'-0" AFF UNO.

19" TELECOMMUNICATIONS EQUIPMENT RACK.

DESCRIPTIONSYMBOL

WALL MOUNTED OUTLET WITH (2) RJ-45 MODULAR JACK. MOUNTED 18" AFF UNO.

ELECTRICAL GROUND

F QUADRUPLEX RECEPTACLE. GROUNDED TYPE.

FLOOR FLUSH-MOUNTED, WITH HINGED COVER UNO.

SURFACE MOUNTED PANELBOARD .

FLUSH MOUNTED PANELBOARD .

A, b 2' x 2' LED LIGHT FIXTURE. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

A, b

SB

T

ELECTRICAL ABBREVIATIONS

AC ABOVE COUNTER

ACS ACCESS CONTROL SYSTEM

AFF ABOVE FINISHED FLOOR.

AFG ABOVE FINISHED GRADE.

A/V AUDIO VISUAL SYSTEM

COR CONTRACTING OFFICER'S REPRESENTATIVE

DDC DIRECT DIGITAL CONTROL

EMGB ELECTRICAL MAIN GROUNDING BUSBAR

GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED

GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED

GF GROUND FAULT INTERRUPTER

GND GROUND

IDS INTRUSION DETECTION SYSTEM

MNS MASS NOTIFICATION SYSTEM

RECP RECEPTACLE

PoE POWER OVER ETHERNET

SPD SURGE PROTECTIVE DEVICE

TR TELECOMMUNICATIONS ROOM

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

UNO UNLESS NOTED OTHERWISE.

WALL MOUNTED OUTLET WITH (4) RJ-45 MODULAR JACK. MOUNTED 18" AFF UNO.4

WAP

WALL MOUNTED LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER

EMERGENCY BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

2' x 2' LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY

BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

DOWNLIGHT LED FIXTURE WITH CONNECT TO CENTRALIZED INVERTER EMERGENCY

BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

WALL MOUNTED LED LIGHT FIXTURE WITH CONNECT TO CENTRALIZED INVERTER

EMERGENCY BATTERY. LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

SECURITY SYMBOLS

SYMBOLS DESCRIPTION

CR

BALANCED MAGNETIC SWITCH

CARD READER. MOUNTED AT 42" AFF UNO

WEATHERPROOF FIXED CAMERA . MOUNTED AT 10'-0" AFF UNO

ACP ACCESS CONTROL PANEL

ES ELECTRIC STRIKE

INV

ACPS

IDCP

KP

MS

ACCESS CONTROL POWER SUPPLY.

INTRUSION DETECTION CONTROL PANEL.

KEYPAD FOR ACCESS CONTROL SYSTEM

CEILING-MOUNTED MOTION SENSOR.

DUPLEX RECEPTACLE, GROUNDED TYPE

"WP" INDICATES WEATHERPROOF TYPE. MOUNTED 18" AFF, UNO.

"GF" INDICATES GROUND FAULT INTERRUPTER TYPE. MOUNTED 18" AFF, UNO.

"TV" INDICATES DUPLEX RECEPTACLE FOR TV. WALL MOUNTED 8'-0" AFF, UNO

LOCKING RECEPTACLE WITH 208 V, 30 AMP, NEMA L6-30R, PENDANT MOUNT 8'-0" AFF,

UNO

LOCKING RECEPTACLE WITH 125 V, 30 AMP, NEMA L5-30R, MOUNTED IN RACK

SWITCHBOARD .

DRY TYPE TRANSFORMER.

CENTRALIZED INVERTER FOR EMERGENCY LIGHTING SYSTEMS.

KEYED NOTE.

GROUNDING BUS BAR.

MAIN CONDUCTOR, #1/0 ALUMINUM.

DOWN CONDUCTOR.

GROUNDING RING CONDUCTOR, #1/0 AWG COPPER.

GROUND ROD, 3/4" DIA X 10' COPPER-CLAD STEEL. "TW" INDICATES TEST WELL.

LC LIGHTING CONTROL PANEL.

BM

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

IC

T, R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/3 2"

'-0

2/ 7/

4:

:3

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

E-001

IN

TE

RI

O

R

EL

E C

TR

I C

AL

L

EG

EN

D

Av er y, P

E

Br ow n, A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

AA A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A B C D E H

GF

1 2

TW

R E:

/E

G

RE: 1/EG103

RE: 1/EG102 RE: 1/EG104

R

E:

/E G

RE: 1/EG101

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG101

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

A Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA A

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

PLAN

NORTH

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

AA A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A B C D E

GF

2TW

RE: 1/EG103

RE: 1/EG102 RE: 1/EG104

RE: 1/EG101

R E:

/E

G

R E:

/E

G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG102

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

B Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA B

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

GF

H J K L M O P

NG

Q

F

L.2 M.8 O.9

2 TW

R E:

/E

G

RE: 1/EG103

RE: 1/EG104

R E:

/E

G

RE: 1/EG105

RE: 1/EG104 RE: 1/EG106

RE: 1/EG103

RE: 1/EG109

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG103

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

C Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA C

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

H J K L M O P

NG

Q

F

L.2 M.8 O.9

RE: 1/EG103

RE: 1/EG102 RE: 1/EG104

RE: 1/EG101

R E:

/E

G

R E:

/E

G

RE: 1/EG105

RE: 1/EG104 RE: 1/EG106

RE: 1/EG103

R E:

/E

G

R E:

/E

G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG104

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

D Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA D

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

P

Q R S T U V W

X Y Z

O.9

2TW

RE: 1/EG105

RE: 1/EG106

RE: 1/EG107

RE: 1/EG106 RE: 1/EG108

RE: 1/EG105

R E:

/E

G

R

E:

/E G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG105

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

E Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA E

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

P

Q R S T U V W

X Y Z

O.9

RE: 1/EG105

RE: 1/EG106 RE: 1/EG106

RE: 1/EG105

R

E:

/E G

R E:

/E

G

R E:

/E

G

R E:

/E

G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG106

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

F Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA F

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

Y AAZ BB CC DD EE FF GG HH

TW

RE: 1/EG107

RE: 1/EG108

R E:

/E

G

R

E:

/E G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG107

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

G Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA G

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A A A A A A A A A A A A A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

Y AAZ BB CC DD EE FF GG HH

TW

RE: 1/EG107

RE: 1/EG108

R E:

/E

G

R E:

/E

G

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG108

L I G

HT

NI

NG

P

RO

T E

CT

IO

N

PL

A N

A R

EA

H Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA H

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

AA A A A A A A A

A AA A

A

AAAA

A A

GF

G F

L M O P

N

Q

L.2 M.8 O.9

0.1

0.2

TW

RE: 1/EG109

RE: 1/EG103

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

/1 6"

'-0

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG109

LI

G

HT

NI

N G P

R O

TE

C T

IO

N

- A

RE

A

I Av er y, P E

Br ow n, P E

1/16" = 1'-0"1 LIGHTNING PROTECTION - AREA I

08 16 3241216

SCALE: 1/16"=1'-0"

KEYPLAN

A

B

C

D

E

F

G

H

I

GENERAL NOTES:

1. LIGHTNING PROTECTION SHOWN IS TYPICAL, MORE AIR TERMINALS AND DOWN CONDUCTORS

MAY BE ADDED TO MEET THE REQUIREMENTS OF LISTING, BUT THE NUMBER OF AIR TERMINALS

AND DOWN CONDUCTORS SHALL NOT BE REDUCED.

2. BI-METAL CONNECTOR SHALL BE USED WHERE ALUMINUM-COPPER METALS COME IN CONTACT

WITH EACH OTHER.

3. PROVIDE A BONDING BETWEEN THE BUILDING COLUMMN AND GROUNDING RING FOR EVERY

OTHER COLUMMN AROUND BUILDING PERIMETER. SEE DETAIL 4/EG501.

KEYED NOTES:

1. TYPICAL #1/0 COPPER DOWN CONDUCTOR. DOWN CONDUCTOR SHALL BE CONCEALED IN

WALL. SEE DETAIL 1/EG501 AND 2/EG501.

2. GROUNDING RING SHALL BE INSTALLED 2-FT BELOW GRADE AND AT A DISTANCE NOT LESS

THAN 3-FT NOR MORE THAN 8-FT FROM THE BUILDING STRUCTURE.

1" PVC CONDUIT

NOTE: SEAL ALL PENETRATIONS AND FLASHINGS

THRU-WALL CABLE

CONNECTOR

#1/0 COPPER CABLE

#1/0 COPPER

CABLE

RUN TO GROUND

ALUMINUM CABLE

#1/0 COPPER

CABLE

2'-0" BELOW

FINISHED GRADE

3'-0" Min.

1" PVC CONDUIT

EXOTHERMIC WELD

COPPER CABLE

1" PVC CONDUIT

GROUND ROD

COPPER CABLE RUN

TO

ROOF CIRCUIT

EXOTHERMIC

WELD

EXOTHERMIC

WELD

A SHORT PIECE OF

REBAR WELDED TO

BUILDING REBAR &

BENT

TO EXTEND OUT OF

FINISHED FOUNDATION

FOR BONDING.

ALUMINUM CABLE

CABLE HOLDER

36" O.C. MAXIMUM

SPACING

AIR TERMINAL

#1/0 COPPER

CABLE

2'-0" BELOW

FINISHED GRADE

3'-0" Min.

EXOTHERMIC WELD

COPPER CABLE

1" PVC CONDUIT

EXOTHERMIC

WELD

GROUND

LOOP CABLE

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H N

O T

TO

SC

AL

E

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG501

G

RO

UN

D I

NG

D

ET

AI

L S

Av er y, P

E

Br ow n, P

E

NOT TO SCALE1 THRU-WALL AND CONCEALED DOWNLEAD TO GROUND

NOT TO SCALE2 CONCEALED DOWNLEAD AND GROUND

NOT TO SCALE3 AIR TERMINAL MOUNTING - SIDE MOUNT PARAPET

NOT TO SCALE4 COLUMN BONDING

ROOF CONDUCTOR

FASTENER CLAMP

CONDUCTOR

BOND CLAMP CONDUCTOR

BOND CLAMP

BOND LUG

CONDUCTOR

CONDUCTOR

BOND LUG

BOND PLATE

CONDUCTOR

TO THE GROUNDING ELECTRODE

PVC CONDUIT, EXTENDED AT LEAST 24" BELOW GRADE

CONCRETE

PVC CONDUIT, STUBBED UP 2" AFF,

SIZED PER NEC DUE TO CONDUCTOR SIZE

GROUNDING CONDUCTOR, SIZED PER

REQUIREMENTS ELSEWHERE

CONDUCTOR CONDUCTOR

BOND STRAP

BOND STRAP

NO. C422 OR C424

CLAMP FOR UTILITY

BOND

COPPER CABLE CONNECT TO NEAREST GROUND

OR GROUNDING RING CABLE WITH THERMOWELD

AA

GROUND CLAMP

GRAVEL OR CRUSHED STONE

SECTION A-A

MATERIAL LIST

3 6

TOP VIEW (COVER REMOVED)

COVER FOR BOX, ENGRAVED

"TEST WELL"

TEST WELL

GROUND ROD, 3/4"x10'

COPPER-CLAD STEEL

GROUNDING CONDUCTOR

POLYMER CONCRETE FIBERGLASS

REINFORCED BOX

6" 4"

14"

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG502

G

RO

UN

D I

NG

D

ET

AI

L S

Av er y, P

E

Br ow n, P

E

NOT TO SCALE1 TYPICAL BONDING FASTENING DETAIL

NOT TO SCALE2 TYPICAL BONDING PLATE DETAIL

NOT TO SCALE4 GROUND CONDUCTOR PENETRATING SLAB DETAIL

NOT TO SCALE3 TYPICAL BONDING STRAP DETAIL

NOT TO SCALE5 TYPICAL UNDERGROUND METAL PIPE BOND DETAIL

NOT TO SCALE6 GROUND ROD TEST WELL

TO OSP CONDUITS

TO RACKS

TO TRAY

TMGB/TGB SIZE

4"H x .25" THICK x 24"L.

PROVIDE TWO HOLE BOLTED

CONNECTORS WITH GROUND

RATED BELLEVILLE WASHERS

BETWEEN BUS AND CONNECTOR.

PROVIDE CONDUCTIVE GREASE

BETWEEN BUS AND CONNECTIONS.

PROVIDE FULL WRAP STRAP

CONNECTORS. CLAMPING OF THE

STRAPS SHALL BE WITH FULL

SURFACE CLAMPING TOOL TO

INSURE EVEN COMPRESSION

AROUND THE CABLE.

TO TMGB/TGB

TO PROTECTOR MODULE

TO LIGHTNING PROTECTION GROUND LOOP

TO NEAREST STRUCTURE STEEL COLUMN

SIZE

4"H x .25" THICK x 36"L.

PROVIDE TWO HOLE BOLTED

CONNECTORS WITH GROUND

RATED BELLEVILLE WASHERS

BETWEEN BUS AND CONNECTOR.

PROVIDE CONDUCTIVE GREASE

BETWEEN BUS AND CONNECTIONS.

PROVIDE FULL WRAP STRAP

CONNECTORS. CLAMPING OF THE STRAPS

SHALL BE WITH FULL SURFACE CLAMPING

TOOL TO INSURE EVEN COMPRESSION

AROUND THE CABLE.

TO OTHER INTERIOR METALLIC PIPE

TO THE TRANSFORMER

TO MAIN ELECTRICAL SERVICE GROUND

TO TMGB

SEE SHEET EG601 FOR SIZING OF GROUNDING CONDUCTORS.

GROUNDING LUG

GROUND WIRE

GROUNDING

BUSHING

INCOMING

CONDUIT LOCKNUT

GROUNDING LUG

PANEL

CABINET

CONDUIT

GROUNDING

BUSHING

CONDUIT

LOCKNUTS GREEN OR BARE

GROUNDING WIRE

SPLIT BOLT

CONNECTION

(TYPICAL)

GROUNDING BUS

BONDED TO CABINET

NOTES:

1. ALL WIRES TO BE NEATLY LACED.

2. AT THE POINT OF ATTACHMENT OF THE GROUNDING LUG TO THE CABINET, THE

SURFACES SHALL BE SCRAPED FREE OF PAINT AND THOROUGHLY CLEANED TO

INSURE PROPER BONDING.

3. NEUTRAL CONDUCTOR NOT SHOWN FOR CLARITY.

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG503

G

RO

UN

D I

NG

D

ET

AI

L S

Av er y, P

E

Br ow n, P

E

NOT TO SCALE2 TELECOMMUNICATIONS MAIN GROUNDING BUSBAR - (TMGB/TGB)

NOT TO SCALE3 ELECTRICAL MAIN GROUNDING BUSBAR (EMGB)

NOT TO SCALE4 TYPICAL PANEL GROUNDING DETAIL

1 FOR SIZE SEE POWER RISER DIAGRAM ON SHEET EP601.

2 2

3 #4/0 CU. BOND TO INCOMING CABLE & CONDUIT

4 FOR METALLIC CONDUIT RUNS GREATER THAN

3 FT CONDUCTOR SHALL BE BONDED TO EACH

END OF CONDUIT RUN.

KEYED NOTES:

TYPICAL BRANCH CIRCUIT. FOR SIZES SEE PLANS.

#3 /0

C U

IN

/4 "C

LEGEND

1 KEYED NOTE REFERENCE.

ELECTRICAL EQUIPMENT GROUND

BJ BONDING JUMPER

TMGB

TGB

TELEPHONE MAIN GROUNDING BUSBAR.

TELEPHONE GROUNDING BUSBAR.

DESCRIPTIONSYMBOL

TYPICAL 208/120V PANEL

TYPICAL 480/277V PANEL

MSB

G N N

N G

G

NEAREST STRUCTURAL

STEEL COLUMN

TRANSFORMER GROUND RING

LIGHTNING

ARRESTOR

CONDUIT

GROUNDING

BUSHING

PROTECTOR

BLOCKS

#6 CUTMGB

CABLE

TRAY

#6 C

U

IN

/2

"C

#6 CU

TELECOM

RM 113

#6 C

U

EQUIPMENT

RACKS

SERVICE

ENTRANCE

CONDUCTORS

PROTECTOR

BLOCKS

#6 CUTGB

CABLE

TRAY

#6 CU

REMOTE

TELECOM

(TYP.)

#6 C

U

EQUIPMENT

RACKS

1. FOR METALLIC CONDUIT RUNS GREATER THAN

3 FT CONDUCTOR SHALL BE BONDED TO EACH

END OF CONDUIT RUN.

2. REFER TO NEC 250.50 FOR FURTHER ELECTRODE SYSTEM

REQUIREMENTS.

#3 /0

C U

IN

/4 "C

EMGB IN

RM 112

#3 /0

C U

IN

/4 "C

BUILDING GROUND COUNTERPOISE CONDUCTOR #4/0 BARE COPPER

#3 /0

C U

IN

/4 "C

FIRE ALARM

ANTENNA

#3/0 CU IN 3/4"C

UNDERGROUND

METALLIC

WATER PIPE

#3 /0

C U

EMGB ELECTRICAL MAIN GROUNDING BUSBAR.

EGB ELECTRICAL GROUNDING BUSBAR.

BUILDING REBAR

#3 /0

C U

#3 /0

C U

INTERIOR METALLIC PIPE

#3/0 CU IN 3/4"C

LIGHTNING PROTECTION ROOF CONDUCTOR (TYPICAL)

TY

PI

C

AL

2/

C

U . D

O W

N C

O N

D U

C

TO

R

TYPICAL AIR TERMINAL

TYPICAL GROUND ROD

SPD

BJ

NEUTRAL

480V 208Y/120V

TYPICAL DRY-TYPE

TRANSFORMER

#6 CU#6 CU

BJ

3/0 CU

GENERAL NOTES:

#3 /0

C U

IN

/4 "C

#6 CU

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H N

O T

TO

SC

AL

E

2/ 7/

4:

:0

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EG601

G

RO

U N

DI

NG

R

IS

E R

D

IA

G

RA

M Av er y, P E

Br ow n, NOTES:

1. EACH LIGHT FIXTURE SHALL HAS INTEGRAL OCCUPANCY SENSOR AND AUTOMATICALLY TURNS ON TO FULL BRIGHTNESS UPON DETECTION OF OCCUPANT APPROACHING. LIGHTING CIRCUITS SHALL BE

CONNECT THRU LIGHTING CONTROL PANEL WITH MANUAL SWITCH OVERRIDE-OFF. SEE DETAILS

SHEET EL503 THRU EL506

2. EXTERIOR LIGHTING SHALL BE CONTROLLED BY PHOTOCELL AND AN ASTRONOMICAL CLOCK TIMER.

SEE DETAILS SHEET EL503 THRU EL506

BUILDING LIGHTING CONTROL MATRIX

ROOM NAME ROOM NUMBER D

U

AL

L

EV

EL

S W

IT

C

H

IN

G

O C

C U

PA

N

C Y

SE

N

SO

R

W

IT

H D

IM

M

ER

C

O N

TR

O

L

O C

C U

PA

N

C Y

SE

N

SO

R

D U

AL

T

EC

H

O C

C U

PA

N

C Y

SE

N

SO

R

VA

C

AN

C

Y

SE

N

SO

R

M

AN

U

AL

S W

IT

C

H (O

N /O

FF

KE

Y

SW

IT

C H

O

VE

R R

ID

E

O

FF

M

AN

U

AL

S W

IT

C

H O

VE

R

R

ID

E O

FF

EX

TE

R

IO

R B

U

IL

D

IN

G P

H O

TO

C

EL

L(

N O

N -D

IM

M

IN

G

D

AY

LI

G

H

TI

N G

NOTES

BATTERY CHARGER 108 X X

BREAKROOM 116 X X

ELEC. ROOM 112 X

JAN 120 X

STORAGE ROOM 118 X

LOCKER RM 119A X X

LOCKER RM 121A X X

MECHANICAL ROOM 109 X

MEN 121 X X

OFFICE 110 X

OFFICE 111 X

OFFICE 114 X X

TEL. ROOM 113 X

UTILITIES 104 X

UTILITIES 105 X

UTILITIES 121 X

UTILITIES 122 X

VESTIBULE 115 X X

WAREHOUSE 100 X 1

WAREHOUSE 101 X 1

WAREHOUSE 102 X 1

WAREHOUSE 103 X 1

WOMEN 119 X X

EXTERIOR LIGHTING N/A X 2

X

X

X

X

LIGHTING FIXTURE SCHEDULE

FIXTURE LAMP MOUNTING

DETAILTYPE DESCRIPTION FINISH VOLTAGE WATTAGE TYPE

TOTAL

LUMENS

PER FIXTURE TYPE HEIGHT

A2 2x2 RECESSED INDIRECT LED WHITE 277 36 LED 3300 RECESSED N/A 1/EL501

C2 2x2 SURFACE INDIRECT LED WHITE 277 36 LED 3300 SURFACE N/A 2/EL501

C5 SURFACE 4‐FT STRIP LED WITH DEFFUSE LENS WHITE 277 74 LED 4600 SURFACE N/A 4/EL501

D 8" ROUND LED DOWNLIGHT WHITE 277 36 LED 1500 RECESSED N/A 5/EL501

H1 SUSPENDED HIGH BAY INDIRECT LED WHITE 277 281 LED 24850 SUSPENDED 29‐FT AFF, UNO 3/EL502

P5 SUSPENDED 4‐FT STRIP LED WITH DEFFUSE LENS WHITE 277 74 LED 4600 SUSPENDED 9‐FT AFF, UNO

W2 LINEAR 2‐FT LED FIXTURE WITH DIFFUSE LED WHITE 277 17 LED 1850 WALL MOUNTED 7'‐6" AFF, UNO 1/EL502

W4 LINEAR 4‐FT LED FIXTURE WITH DIFFUSE LED WHITE 277 34 LED 3700 WALL MOUNTED 7'‐6" AFF, UNO 2/EL502

X1 LED EXIT LIGHT WHITE 277 4 LED ‐ BACK MOUNTED 8'‐6" AFF 5/EL502

X2 LED EXIT LIGHT WHITE 277 4 LED ‐ PENDANT MOUNTED 15'‐0" AFF 5/EL502

T1

Y1

Y2

WALL PACK

WALL PACK

BRONZE

BRONZE

LED

LED

WALL

WALL

7'‐6" AFF

20'‐0" AFF

4/EL502

4/EL502

6/EL501

3/EL501LED FROSTED GLASS DIFFUSERS YELLOW 120 15 LED WALL‐ 6'‐0" AFF

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H

2"

'-0

2/ 7/

4:

:4

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL001

LI

G

HT

IN

G F

IX

TU

RE

S

CH

E D

UL

E

L I

G

HT

IN

G

C O

NT

R O

L M

AT

RI

X

Av er y, P

E

Br ow n, P

E

GENERAL NOTES:

1. AUTOMATIC CONTROL SHALL BE PROGRAMED TO BE OFF WITHIN 15 MINUTES AFTER

OCCUPANT LEAVES SPACE.

A B C D E

GF

WAREHOUSE

H1

ELA-9

H1

HA-10

H1

HA-10

H1

ELA-9

H1

HA-10

H1

ELA-9

H1

HA-9

H1

HA-9

H1

ELA-9

H1

HA-9

H1

ELA-9

H1

HA-9

H1

HA-9

H1

ELA-9

H1

HA-9

H1

ELA-2

H1

HA-8

H1

HA-8

H1

ELA-5

H1

HA-8

H1

ELA-2

H1

HA-8

H1

HA-8

H1

ELA-5

H1

HA-8

H1

ELA-2

H1

HA-7

H1

HA-7

H1

ELA-5

H1

HA-7

H1

ELA-2

H1

HA-7

H1

HA-7

H1

ELA-5

H1

HA-7

H1

ELA-2

H1

HA-6

H1

HA-6

H1

ELA-5

H1

HA-6

H1

ELA-2

H1

HA-6

H1

HA-6

H1

ELA-5

H1

HA-6

H1

ELA-7

H1

HA-5

H1

HA-5

H1

ELA-8

H1

HA-5

H1

ELA-7

H1

HA-5

H1

HA-5

H1

ELA-8

H1

HA-5

H1

ELA-7

H1

HA-4

H1

HA-4

H1

ELA-8

H1

HA-4

H1

ELA-7

H1

HA-4

H1

HA-4

H1

ELA-8

H1

HA-4

H1

ELA-7

H1

HA-3

H1

HA-3

H1

ELA-8

H1

HA-3

H1

ELA-7

H1

HA-3

H1

HA-3

H1

ELA-8

H1

HA-3

H1

HA-1

H1

HA-1

H1

ELA-4

H1

HA-1

H1

HA-1

H1

HA-1

H1

HA-1

H1

HA-2

H1

ELA-4

H1

HA-2

H1

HA-2

H1

HA-2

H1

HA-2

H1

ELA-4

H1

HA-2

EL101

X1

HA-1

X1

HA-2

X1

HI1-3

X2

HA-1

X2

HA-2

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18

Y1

ELI-16,18 R

E:

/E L1

R

E:

/E L1

T1T1T12 2 2

X1

HA-2

X1

HI1-3

Y2

HI1-30,32

UTILITIES

ELEC. ROOM

TEL. ROOM

P5

ELA-4

P5

ELA-4

C5

ELA-4

C5

HA-2

LC

LCP-A

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL101

LI

G

H T

IN

G P

LA

N

- A

RE

A A

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA A

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOMS 104, 105 AND 107

04 8 16268

SCALE: 1/8"=1'-0"

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

PLAN

NORTH

PLAN NORTH

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

CONDUIT.

2. CONNECT TO 120V CIRCUIT NEARBY. SEE POWER PLAN FOR CIRCUIT INFORMATION.

DN

A B C D E

GF

WAREHOUSE

H1

HB-10

H1

ELA-1

H1

HB-10

H1

HB-10

H1

ELA-9

H1

HB-9

H1

ELA-1

H1

HB-9

H1

HB-9

H1

ELA-9

H1

HB-9

H1

ELA-1

H1

HB-9

H1

HB-9

H1

ELA-9

H1

HB-8

H1

ELA-6

H1

HB-8

H1

HB-8

H1

ELA-2

H1

HB-8

H1

ELA-6

H1

HB-8

H1

HB-8

H1

ELA-2

H1

HB-7

H1

ELA-6

H1

HB-7

H1

HB-7

H1

ELA-2

H1

HB-7

H1

ELA-6

H1

HB-7

H1

HB-7

H1

ELA-2

H1

HB-6

H1

ELA-6

H1

HB-6

H1

HB-6

H1

ELA-2

H1

HB-6

H1

ELA-6

H1

HB-6

H1

HB-6

H1

ELA-2

H1

HB-5

H1

ELA-10

H1

HB-5

H1

HB-5

H1

ELA-7

H1

HB-5

H1

ELA-10

H1

HB-5

H1

HB-5

H1

ELA-7

H1

HB-4

H1

ELA-10

H1

HB-4

H1

HB-4

H1

ELA-7

H1

HB-4

H1

ELA-10

H1

HB-4

H1

HB-4

H1

ELA-7

H1

HB-3

H1

ELA-10

H1

HB-3

H1

HB-3

H1

ELA-7

H1

HB-3

H1

ELA-10

H1

HB-3

H1

HB-3

H1

ELA-7

H1

HD-7

H1

ELI-13

H1

HD-7

H1

HD-7

H1

ELI-9

H1

HB-1

H1

ELA-3

H1

HB-1

H1

HB-1

H1

HB-1

H1

HB-1

H1

ELA-3

H1

HB-1

H1

HB-2

H1

HB-2

H1

HB-2

H1

HB-2

H1

HB-2

H1

ELA-3

H1

HB-2

H1

HD-2

EL102

X1

HD-2

X1

HB-2

X1

HB-1

X2

HB-1 X2

HB-2

T1 T1

Y1

ELI-16,18

Y1

ELI-16,18

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18

RE: 1/EL103

RE: 1/EL104

R E:

/E

L1

R E:

/E

L1

T1

2 2

X1

HB-2

Y2

HI1-30,32

Y2

HI1-30,32

TELECOM

ROOM

ELEC. ROOM

C5

ELA-3

C5

HB-2

P5

ELA-3

LC

LCP-B

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:5

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL102

LI

G

H T

IN

G P

LA

N

- A

RE

A B

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA B

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOMS 127 AND 128

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

H J K L M O P

NG

Q

F

L.2 M.8 O.9

WAREHOUSE

H1

ELA-7

H1

HA-3

H1

HA-3

H1

ELA-8

H1

HA-3

H1

ELI-9

H1

HI1-14

H1

HI1-14

H1

ELI-5

H1

HI1-14

H1

ELI-9

H1

HI1-13

H1

HI1-13

H1

ELI-5

H1

HI1-13

H1

ELI-9

H1

HI1-13

H1

HI1-13

H1

ELI-5

H1

HI1-13

H1

ELI-9

H1

HI1-15

H1

HI1-15

H1

ELI-5

H1

HI1-15

H1

ELI-9

H1

HI1-14

H1

HI1-14

H1

ELI-5

H1

HI1-14

H1

ELI-8

H1

HI1-12

H1

HI1-12

H1

ELI-4

H1

HI1-12

H1

ELI-8

H1

HI1-12

H1

HI1-12

H1

ELI-4

H1

HI1-12

H1

ELI-8

H1

HI1-11

H1

HI1-11

H1

ELI-4

H1

HI1-11

H1

ELI-8

H1

HI1-11

H1

HI1-11

H1

ELI-4

H1

HI1-11

H1

ELI-8

H1

HI1-10

H1

HI1-10

H1

ELI-4

H1

HI1-10

H1

ELI-8

H1

HI1-10

H1

HI1-10

H1

ELI-4

H1

HI1-10

H1

ELI-7

H1

HI1-9

H1

HI1-9

H1

ELI-3

H1

HI1-9

H1

ELI-7

H1

HI1-9

H1

HI1-9

H1

ELI-3

H1

HI1-9

H1

ELI-7

H1

HI1-8

H1

HI1-8

H1

ELI-3

H1

HI1-8

H1

ELI-7

H1

HI1-8

H1

HI1-8

H1

ELI-3

H1

HI1-8

H1

ELI-7

H1

HI1-7

H1

HI1-7

H1

ELI-3

H1

HI1-7

H1

ELI-7

H1

HI1-7

H1

HI1-7

H1

ELI-3

H1

HI1-7

H1

ELI-6

H1

HI1-6

H1

HI1-6

H1

ELI-2

H1

HI1-6

H1

ELI-6

H1

HI1-6

H1

HI1-6

H1

ELI-2

H1

HI1-6

H1

ELI-6

H1

HI1-5

H1

HI1-5

H1

ELI-2

H1

HI1-5

H1

ELI-6

H1

HI1-5

H1

HI1-5

H1

ELI-2

H1

HI1-5

H1

ELI-6

H1

HI1-4

H1

HI1-4

H1

ELI-2

H1

HI1-4

H1

ELI-6

H1

HI1-4

H1

HI1-4

H1

ELI-2

H1

HI1-4

H1

HA-2

H1

HI1-3

H1

HI1-3

H1

HI1-3

H1

HI1-3

H1

ELI-1

H1

HI1-3

H1

ELI-1

H1

HI1-3

H1

HI1-2

H1

HI1-2

H1

HI1-2

H1

HI1-2

H1

ELI-1

H1

HI1-2

H1

HI1-2

H1

HI1-1

H1

HI1-1

H1

HI1-1

H1

ELI-1

H1

HI1-1

H1

HI1-1

H1

ELI-1

H1

HI1-1

EL103

X1

HA-2

X1

HI1-3

X2

HI1-3

X2

HI1-1

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18R

E:

/E L1

RE: 1/EL103

RE: 1/EL104

R E:

/E

L1

RE: 1/EL105

RE: 1/EL104 RE: 1/EL106

RE: 1/EL103

RE: 1/EL109

RE: 1/EL103

T1T1 2 2

X1

HA-2

X1

HI1-3

Y2

HI1-30,32

UTILITIES

P5

ELI-1

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:0

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL103

LI

G

H T

IN

G P

LA

N

- A

RE

A C

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA C

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOM 106

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

H J K L M O P

NG

Q

F

L.2 M.8 O.9

WAREHOUSE

H1

HB-3

H1

ELA-10

H1

HB-3

H1

HB-3

H1

ELA-7

H1

HD-8

H1

ELI-13

H1

HD-8

H1

HD-8

H1

ELI-9

H1

HD-10

H1

ELI-13

H1

HD-10

H1

HD-10

H1

ELI-9

H1

HD-10

H1

ELI-13

H1

HD-10

H1

HD-10

H1

ELI-9

H1

HD-7

H1

ELI-13

H1

HD-7

H1

HD-7

H1

ELI-9

H1

HD-8

H1

ELI-13

H1

HD-8

H1

HD-8

H1

ELI-9

H1

HD-12

H1

ELI-12

H1

HD-12

H1

HD-12

H1

ELI-8

H1

HD-12

H1

ELI-12

H1

HD-12

H1

HD-12

H1

ELI-8

H1

HD-17

H1

ELI-12

H1

HD-17

H1

HD-17

H1

ELI-8

H1

HD-17

H1

ELI-12

H1

HD-17

H1

HD-17

H1

ELI-8

H1

HD-15

H1

ELI-12

H1

HD-15

H1

HD-15

H1

ELI-8

H1

HD-15

H1

ELI-12

H1

HD-15

H1

HD-15

H1

ELI-8

H1

HD-13

H1

ELI-11

H1

HD-13

H1

HD-13

H1

ELI-7

H1

HD-13

H1

ELI-11

H1

HD-13

H1

HD-13

H1

ELI-7

H1

HD-9

H1

ELI-11

H1

HD-9

H1

HD-9

H1

ELI-7

H1

HD-9

H1

ELI-11

H1

HD-9

H1

H1

ELI-7

H1

HD-16

H1

ELI-11

H1

HD-16

H1

HD-16

H1

ELI-7

H1

HD-16

H1

ELI-11

H1

HD-16

H1

HD-16

H1

ELI-7

H1

HD-14

H1

ELI-10

H1

HD-14

H1

HD-14

H1

ELI-6

H1

HD-14

H1

ELI-10

H1

HD-14

H1

HD-14

H1

ELI-6

H1

HD-6

H1

ELI-10

H1

HD-6

H1

HD-6

H1

ELI-6

H1

HD-6

H1

ELI-10

H1

HD-6

H1

HD-6

H1

ELI-6

H1

HD-11

H1

ELI-10

H1

HD-11

H1

HD-11

H1

ELI-6

H1

HD-11

H1

ELI-10

H1

HD-11

H1

HD-11

H1

ELI-6

H1

HB-2

H1

HD-2

H1

HD-2

H1

HD-2

H1

HD-2

H1

ELI-14

H1

HD-2

H1

ELI-14

H1

HD-2

H1

HD-18

H1

HD-18

H1

HD-18

H1

HD-18

H1

ELI-14

H1

HD-18

H1

HD-18

H1

HD-4

H1

HD-4

H1

HD-4

H1

ELI-14

H1

HD-4

H1

HD-4

H1

ELI-14

H1

HD-4

EL104

X1

HD-4X1

HD-2

X1

HB-2

X2

HD-2

X2

HD-4

T1 T1 T1

Y1

ELI-16,18

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18

RE: 1/EL103

R

E:

/E L1

R E:

/E

L1

RE: 1/EL103

R E:

/E

L1

R E:

/E

L1

2 2 2

X1

HB-2

X1

HD-4

Y2

HI1-30,32

ELEC. ROOM

TELECOM

ROOM

C5

ELI-14

C5

HD-4

P5

ELI-14

LC

LCP-D

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:0

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL104

LI

G

H T

IN

G P

LA

N

- A

RE

A D

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA D

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOMS 131 AND 133

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

Q R S T U V W

X Y Z

O.9

WAREHOUSE

H1

ELE-9

H1

HE-15

H1

HE-15

H1

ELE-5

H1

HE-15

H1

ELE-9

H1

HE-14

H1

HE-14

H1

ELE-5

H1

HE-14

H1

ELE-9

H1

HE-14

H1

HE-14

H1

ELE-5

H1

HE-14

H1

ELE-9

H1

HE-13

H1

HE-13

H1

ELE-5

H1

HE-13

H1

ELE-9

H1

HE-13

H1

HE-13

H1

ELE-5

H1

HE-13

H1

ELE-8

H1

HE-12

H1

HE-12

H1

ELE-4

H1

HE-12

H1

ELE-8

H1

HE-12

H1

HE-12

H1

ELE-4

H1

HE-12

H1

ELE-8

H1

HE-11

H1

HE-11

H1

ELE-4

H1

HE-11

H1

ELE-8

H1

HE-11

H1

HE-11

H1

ELE-4

H1

HE-11

H1

ELE-8

H1

HE-10

H1

HE-10

H1

ELE-4

H1

HE-10

H1

ELE-8

H1

HE-10

H1

HE-10

H1

ELE-4

H1

HE-10

H1

ELE-7

H1

HE-9

H1

HE-9

H1

ELE-3

H1

HE-9

H1

ELE-7

H1

HE-9

H1

HE-9

H1

ELE-3

H1

HE-9

H1

ELE-7

H1

HE-8

H1

HE-8

H1

ELE-3

H1

HE-8

H1

ELE-7

H1

HE-8

H1

HE-8

H1

ELE-3

H1

HE-8

H1

ELE-7

H1

HE-7

H1

HE-7

H1

ELE-3

H1

HE-7

H1

ELE-7

H1

HE-7

H1

HE-7

H1

ELE-3

H1

HE-7

H1

ELE-6

H1

HE-6

H1

HE-6

H1

ELE-2

H1

HE-6

H1

ELE-6

H1

HE-6

H1

HE-6

H1

ELE-2

H1

HE-6

H1

ELE-6

H1

HE-5

H1

HE-5

H1

ELE-2

H1

HE-5

H1

ELE-6

H1

HE-5

H1

HE-5

H1

ELE-2

H1

HE-5

H1

ELE-6

H1

HE-4

H1

HE-4

H1

ELE-2

H1

HE-4

H1

ELE-6

H1

HE-4

H1

HE-4

H1

ELE-2

H1

HE-4

H1

HE-3

H1

ELE-1

H1

HE-3

H1

HE-3

H1

HE-3

H1

HE-3

H1

ELE-1

H1

HE-3

H1

HE-2

H1

HE-2

H1

HE-2

H1

HE-2

H1

ELE-1

H1

HE-2

H1

HE-2

H1

HE-1

H1

HE-1

H1

HE-1

H1

ELE-1

H1

HE-1

H1

HE-1

H1

ELE-1

H1

HE-1

EL105

X1

HE-3

X1

HE-1

X2

HE-3 X2

HE-1

T1 T1 T1

Y1

ELI-16,18

Y1

ELI-16,18

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

RE: 1/EL104

RE: 1/EL103 RE: 1/EL107

RE: 1/EL108

R E:

/E

L1

R E:

/E

L1

2 2 2

X1

HE-1

X1

HG-3

X1

HE-1

Y2

HI1-30,32

TEL. ROOM

122A

ELEC. ROOM

UTILITIES

C5

ELE-1

C5

HE-1

P5

ELE-1

P5

ELE-1

LC

LCP-E

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:1

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL105

LI

G

H T

IN

G P

LA

N

- A

RE

A E

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA E

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED 122, 122A AND 123

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

Q R S T U V W

X Y Z

WAREHOUSE

H1

HF-1

H1

ELE-13

H1

HF-1

H1

HF-1

H1

ELE-9

H1

HF-7

H1

ELE-13

H1

HF-7

H1

HF-7

H1

ELE-9

H1

HF-7

H1

ELE-13

H1

HF-7

H1

HF-7

H1

ELE-9

H1

HF-15

H1

ELE-13

H1

HF-15

H1

HF-15

H1

ELE-9

H1

HF-15

H1

ELE-13

H1

HF-15

H1

HF-15

H1

ELE-9

H1

HF-12

H1

ELE-12

H1

HF-12

H1

HF-12

H1

ELE-8

H1

HF-12

H1

ELE-12

H1

HF-12

H1

HF-12

H1

ELE-8

H1

HF-11

H1

ELE-12

H1

HF-11

H1

HF-11

H1

ELE-8

H1

HF-11

H1

ELE-12

H1

HF-11

H1

HF-11

H1

ELE-8

H1

HF-16

H1

ELE-12

H1

HF-16

H1

HF-16

H1

ELE-8

H1

HF-16

H1

ELE-12

H1

HF-16

H1

HF-16

H1

ELE-8

H1

HF-13

H1

ELE-11

H1

HF-13

H1

HF-13

H1

ELE-7

H1

HF-13

H1

ELE-11

H1

HF-13

H1

HF-13

H1

ELE-7

H1

HF-17

H1

ELE-11

H1

HF-17

H1

HF-17

H1

ELE-7

H1

HF-17

H1

ELE-11

H1

HF-17

H1

HF-17

H1

ELE-7

H1

HF-18

H1

ELE-11

H1

HF-18

H1

HF-18

H1

ELE-7

H1

HF-18

H1

ELE-11

H1

HF-18

H1

HF-18

H1

ELE-7

H1

HF-14

H1

ELE-10

H1

HF-14

H1

HF-14

H1

ELE-6

H1

HF-14

H1

ELE-10

H1

HF-14

H1

HF-14

H1

ELE-6

H1

HF-9

H1

ELE-10

H1

HF-9

H1

HF-9

H1

ELE-6

H1

HF-9

H1

ELE-10

H1

HF-9

H1

HF-9

H1

ELE-6

H1

HF-10

H1

ELE-10

H1

HF-10

H1

HF-10

H1

ELE-6

H1

HF-10

H1

ELE-10

H1

HF-10

H1

HF-10

H1

ELE-6

H1

HH-15

H1

ELG-13

H1

HH-15

H1

HH-15

H1

ELG-9

H1

HF-3

H1

ELE-14

H1

HF-3

H1

HF-3

H1

HF-3

H1

HF-3

H1

ELE-14

H1

HF-3

H1

HF-8

H1

HF-8

H1

HF-8

H1

HF-8

H1

ELE-14

H1

HF-8

H1

HF-8

H1

HF-5

H1

HF-5

H1

HF-5

H1

ELE-14

H1

HF-5

H1

HF-5

H1

ELE-14

H1

HF-5

H1

HH-3

EL106

X1

HH-3

X1

HF-5X1

HF-3

X2

HF-3

X2

HF-5

T1 T1 T1

Y1

ELI-16,18

Y1

ELI-16,18

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18

RE: 1/EL105 RE: 1/EL107

RE: 1/EL108

RE: 1/EL105

R E:

/E

L1

R E:

/E

L1

R E:

/E

L1

R E:

/E

L1

2 2

X1

HD-4

X1

HF-5

Y2

HI1-30,32

TELECOM

ROOM

ELEC. ROOM

C5

ELE-14

C5

HF-5

P5

ELE-14

LC

LCP-F

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:2

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL106

LI

G

H T

IN

G P

LA

N

- A

RE

A F

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA F

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOMS 138 AND 139

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE DETERMINED BY

MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL 1/EL503.

3. ALL EXIT SIGNS SHALL BE CONNECTED TO UNSWITCHED CIRCUITS.

4. ALL BRANCH WIRING FOR LIGHTING CIRCUITS SHALL BE PROVIDED WITH #10 AWG.

5. MOUNTING HEIGHT FOR FIXTURE TYPE H1 SHALL BE 29' AFF IN RACK AREA AND 26' AFF IN THE

CIRCULATION AREA.

6. CONNECT WAREHOUSE LIGHTING CIRCUITS AND EXTERIOR BUILDING LIGHTING CIRCUITS

THRU LIGHTING CONTROL PANEL. SEE DETAILS FROM DRAWING EL503 THRU EL506

KEYED NOTES:

1. INSTALL FIXTURE BETWEEN TOP OF THE DOOR AND CANOPY. PROVIDE 2 #10 & 1 #12 GND IN 1"

Y AAZ BB CC DD EE FF GG HH

WAREHOUSE

H1

ELG-9

H1

HG-14

H1

HG-14

H1

ELG-5

H1

HG-14

H1

ELG-9

H1

HG-13

H1

HG-13

H1

ELG-5

H1

HG-13

H1

ELG-9

H1

HG-13

H1

HG-13

H1

ELG-5

H1

HG-13

H1

ELG-9

H1

HG-15

H1

HG-15

H1

ELG-5

H1

HG-15

H1

ELG-9

H1

HG-14

H1

HG-14

H1

ELG-5

H1

HG-14

H1

ELG-8

H1

HG-12

H1

HG-12

H1

ELG-4

H1

HG-12

H1

ELG-8

H1

HG-12

H1

HG-12

H1

ELG-4

H1

HG-12

H1

ELG-8

H1

HG-11

H1

HG-11

H1

ELG-4

H1

HG-11

H1

ELG-8

H1

HG-11

H1

HG-11

H1

ELG-4

H1

HG-11

H1

ELG-8

H1

HG-10

H1

HG-10

H1

ELG-4

H1

HG-10

H1

ELG-8

H1

HG-10

H1

HG-10

H1

ELG-4

H1

HG-10

H1

ELG-7

H1

HG-9

H1

HG-9

H1

ELG-3

H1

HG-9

H1

ELG-7

H1

HG-9

H1

HG-9

H1

ELG-3

H1

HG-9

H1

ELG-7

H1

HG-8

H1

HG-8

H1

ELG-3

H1

HG-8

H1

ELG-7

H1

HG-8

H1

HG-8

H1

ELG-3

H1

HG-8

H1

ELG-7

H1

HG-7

H1

HG-7

H1

ELG-3

H1

HG-7

H1

ELG-7

H1

HG-7

H1

HG-7

H1

ELG-3

H1

HG-7

H1

ELG-6

H1

HG-6

H1

HG-6

H1

ELG-2

H1

HG-6

H1

ELG-6

H1

HG-6

H1

HG-6

H1

ELG-2

H1

HG-6

H1

ELG-6

H1

HG-5

H1

HG-5

H1

ELG-2

H1

HG-5

H1

ELG-6

H1

HG-5

H1

HG-5

H1

ELG-2

H1

HG-5

H1

ELG-6

H1

HG-4

H1

HG-4

H1

ELG-2

H1

HG-4

H1

ELG-6

H1

HG-4

H1

HG-4

H1

ELG-2

H1

HG-4

H1

HG-3

H1

HG-3

H1

HG-3

H1

HG-3

H1

ELG-1

H1

HG-3

H1

ELG-1

H1

HG-3

H1

HG-2

H1

HG-2

H1

HG-2

H1

HG-2

H1

ELG-1

H1

HG-2

H1

HG-2

H1

HG-1

H1

HG-1

H1

HG-1

H1

ELG-1

H1

HG-1

H1

HG-1

H1

ELG-1

H1

HG-1

EL107

EL107

X1

HE-1

X1

HG-3

X1

HG-1X2

HG-3

X2

HG-1

T1 T1 T1

Y1

ELI-16,18 Y1

ELI-16,18

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y2

HI1-30,32

Y1

ELI-16,18

R E:

/E

L1

R E:

/E

L1

RE: 1/EL107

RE: 1/EL108

2 2 2 T12

X1

HE-1

X1

HG-3

X1

HE-1

Y2

HI1-30,32

Y2

HI1-30,32

UTILITIES

P5

ELG-1

C5

ELG-1

C5

HG-1

P5

ELG-1

135A

TEL. ROOM

LC

LCP-G

ELEC. ROOM

SHEET

SEQUENCE

NUMBER

1 2 3 4 5

D ra wn b y:

D es ig ne d by

Su bm itt ed b y:

Fi le

N am e:

D at e:

C on tra ct

N o.

So lic ita tio n N o.

U .S

. A R

M Y

EN

G

IN

EE

R D

IS

TR

R

PS

O

F

EN

G

IN

EE

R

S

FO

R T

W O

R

TH

, T

EX

AS

R ev ie we d by

US Army Corps of Engineers ®

D

C

B

A

Pl ot

S ca le

Pl ot

D at e:

R ev

Sy m bo l

D es cr ip tio n

Tr ac ki ng

N o.

Ac tio n D at e

EN

G

IN

EE

R

IN

G

C O

N

ST

R U

C

TI

O N

D

IV

IS

IO

N

EN

G

IN

EE

R

IN

G

B R

AN

C

H As in di ca te d

2/ 7/

4:

:2

PM

R E D

RI

VE

R A R

M Y

DE

PO

T, H

O O

KS

, T

EX

A S

FY

D L A

G

EN

ER

A L

P

UR

PO

SE

W

AR

EH

O

U S E

FE

BR

U

AR

Y

W

G

-1 9-

B-

Fort Worth District

K.

L

E, P

.E

T.

N

G U

YE

N

D

AR

EN

A

. B R

O W

N , P

.E

EL107

LI

G

H T

IN

G P

LA

N

- A

RE

A G

Av er y, P

E

Br ow n, P

E

1/16" = 1'-0"1 LIGHTING PLAN - AREA G

KEYPLAN

A

B

C

D

E

F

G

H

I

08 16 3241216

SCALE: 1/16"=1'-0"

1/8" = 1'-0"2 ENLARGED ROOM 124

1/8" = 1'-0"3 ENLARGED ROOMS 135 AND 135A

04 8 16268

SCALE: 1/8"=1'-0"

04 8 16268

SCALE: 1/8"=1'-0"

PLAN NORTH

GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE LIGHTING CONTROL DEVICES AND CONTROL CIRCUITS AS

REQUIRED TO OBTAIN THE OPERATIONALFEATURES SHOWN IN THE LIGHTING CONTROL

MATRIX ON SHEET EL001.

2. ALL EMERGENCY LIGHTING FIXTURES SHOWN SHALL BE CONNECTED TO CENTRALIZED

INVERTER EMERGENCY BATTERY SYSTEM. EMERGENCY LIGHTING SYSTEM SHALL INCLUDE

EMERGENCY LIGHTING CONTROL UNITS (ELCU), QUANTITY TO BE…